Mitsubishi Electric LT-3050 User`s manual

Side
Side
Side
B ENGLISH
[WIRING PRECAUTIONS]
Electromagnetic Compatibility
Standards (EMC)
DANGER
●SAFETY PRECAUTIONS●
(Read these precautions before using)
Please read this manual carefully and pay special attention to safely in order
to handle this product properly. Also pay careful attention to safely and handle
the module properly.
These precautions apply only to Mitsubishi equipment. Refer to the user’s
manual of the CPU module to use for a description of the PLC system safety
precautions.
These ●SAFETY PRECAUTIONS● classify the safety precautions into two
categories: "DANGER" and "CAUTION".
DANGER
Procedures which may lead to a dangerous condition
and cause death or serious injury if not carried out
properly.
CAUTION
Procedures which may lead to a dangerous condition
and cause superficial to medium injury, or physical
damage only, if not carried out properly.
CAUTION
Depending on circumstances, procedures indicated by
may also be linked to serious results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
[STARTING AND MAINTENANCE PRECAUTIONS]
CAUTION
• Do not have control cables and communication cables bundled with or
placed near by the main circuit and/or power cables. Wire those cables
at least 100mm(3.94 inch) away from the main circuit and/or power
cables. It may cause malfunction due to noise interference.
• Use the module and the flat cable dedicated to CC-Link/LT without
applying any force on them.
Otherwise, such cables may be broken or fail.
[INSTALLATION PRECAUTIONS]
CAUTION
• Use the module in an environment that meets the general specifications
contained in this manual. Using this module in an environment outside
the range of the general specifications could result in electric shock, fire,
erroneous operation, and damage to or deterioration of the product.
• Do not directly touch the module's conductive parts.Doing so could
cause malfunction or trouble in the module.
• Tighten the module securely using DIN rail or installation screws within
the specified torque range.
If the screws are too lose, the module may drop from its installation
position, short circuit, or malfunction. If the screws are too tight, the
screws may be damaged, which may cause the module to drop from its
installation position or short circuit.
• Install the module on a flat surface.
If the mounting surface has concave and/or convex, an excessive force
may be applied on the module, and nonconformity may be caused.
CAUTION
• During transportation avoid any impact as the module is a precision
instrument. Doing so could cause trouble in the module.
• If is necessary to check the operation of module after transportation, in case
of any impact damage.
R
Input impedance
5.6 kΩ
1.7 mA or less
R: Bleeder resistor
...
...
• If chattering is present in the external input equipment, set 1.5ms.
• If the ON or OFF time of the input signal is less than 1.5 ms, set it to 0.5 ms.
(The ON and OFF time of the input signal are required to be 0.5 ms or more.)
When setting 1.5 ms:
Set both the ON and OFF time of the input signal to 1.5 ms or more.
When setting 0.5 ms:
Set both the ON and OFF time of the input signal to 0.5 ms or more.
Connected to DC 24A terminal
φ 3.2 (0.13")
6.2 mm (0.24" )
or less
Terminal screw
Crimp-style
terminal
When wiring two cables to one terminal
Terminal screw
Crimp-style
terminal
Bleeder resistor *1
X *
Detection
circuit
Terminal
4
6
8
COMB
X2
X3
Status indicator
LED
ON
Description
ON while the power is supplied.
• RAV1.25-3
• V1.25-3 (manufactured by JST Mfg. Co., Ltd.)
• 1.25-3 and TG1.25-3 (manufactured by NICHIFU Co., Ltd.)
Connected to DC 24A terminal
Bleeder resistor *1
X *
Detection
circuit
COMB
COMB
5.
5.2 Input specifications
DC input (External power supply of the input part)
Number of inputs
4 points
Isolation method
Isolation with photocoupler
Rated input voltage
24V DC
Rated input current
Approx. 4 mA
Operating voltage range
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Max. simultaneous ON
input points
100% (at 24V DC)
ON voltage/ON current
19 V or more/3 mA or more
OFF voltage/OFF current
11 V or less/1.7 mA or less
5.6 kΩ
OFF→ON
0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
ON→OFF
0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
4 points/1 common (2 points)
(terminal block two-wire type)
X *
Detection
circuit
Vibration resistance (*1)
COMB
Replace * in the figure with the used input No.
Notes:
*1 Bleeder resistor
When connecting a two-wire type sensor or input equipment containing a
parallel resistor, select a sensor or equipment whose leakage current is
1.7mA or less.
If the leakage current is more than 1.7mA, connect a bleeder resistor
obtained in the following calculation formula.
0 to 55°C (32 to 131°F)
-25 to 75°C (-13 to 167°F)
5 to 95%RH: Dew condensation shall not be
considered.
5 to 95%RH: Dew condensation shall not be
considered.
Number of
When intermittent vibration is present
times of
sweep
Frequency Acceleration Half amplitude
10 to 57Hz
0.075mm
−
10 times in
−
9.8m/s2
When continuous vibration is present
Frequency Acceleration Half amplitude
10 to 57Hz
0.035mm
−
57 to 150Hz
57 to 150Hz
Impact resistance (*1)
Operating atmosphere
Operating altitude
Installation place
Over-voltage category
Degree of contamination
Item
Voltage
4.9m/s2
Specification
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Current
consumption
40mA (when all points are ON)
Initial current
70mA
Max. allowable
momentary power PS1:1ms
failure period
Specification
each of X, Y
and Z
directions
(for 80 min)
−
147 m/s2, 3 times in each of X, Y and Z directions
Corrosive gas shall not be present.
2,000m(6561'8") or less (*2)
Inside control panel (*3)
ΙΙ or less (*4)
2 or less (*5)
Number of stations
occupied
4-, 8- or 16-point mode: 1 station
Noise durability
500Vp-p
Noise width: 1µs Cycle: 25 to 60 Hz
(by noise simulator)
Withstand voltage
500V AC for 1 min
Isolation resistance
10 MΩ or more between primary area (external
DC terminal) and secondary area (internal circuit)
by 500V DC megger
Protection class
IP2X
I/O part connection method Connection with terminal block
DIN rail installation, mounted by screws of type
Module installation method M4 × 0.7mm(0.03") × 16mm(0.63") or larger
Can be installed in six directions
Mass (weight)
M4 × 0.7mm(0.03") × 16mm(0.63") or more
(Tightening torque range: 0.78 to 1.08 N⋅m)
Wiring
The input terminals of the CL1X4-D1B2 can be wired as positive common
or negative common depending on the used sensor.
Outside Dimensions
50(1.97")
2 - φ4.5(0.18") mounting
hole (M4 mounting screw)
Center of DIN rail 10(0.40")
41.5(1.64") ± 0.4(0.02")
40(1.58")
Specification
Input method
Module
power
supply
5.1 General specifications
• When using a three-wire type sensor
(when using the power supply for sensor other than 24V DC)
Applicable screw
4.1 External wiring
5.3 Performance specifications
Specifications
Item
Ambient working
temperature
Ambient storage
temperature
Ambient operating
humidity
Ambient storage
humidity
Screw-tighten the module by attaching M4 screws to the upper and lower
mounting holes (two holes in all) provided in the module.
Install the module so that the clearance of 1 to 2mm (0.04" to 0.08") is
assured for each module.
4.
*2 The module cannot be used in an environment pressurized above the
atmospheric pressure which can be generated around the altitude of 0 m. If the
module is used in such an environment, it may fail.
*3 The module can be used in any environment even outside the control panel as
far as the requirements of the ambient operating temperature, the ambient
operating humidity, etc. are satisfied.
*4 This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution
network and the machinery within premises. Category ΙΙ applies to equipment
for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*5 This index indicates the degree of conductive generating substances in the
environment in which the module is used. The degree of contamination 2
indicates that contamination is caused by generation of only non-conductive
substances.
In this degree, however, temporary conduction may be caused by accidental
condensation.
Tighten the terminal screws (M3 screws) on the terminal block with a tightening
torque of 0.42 to 0.58 N⋅m. Do not tighten terminal screws exceeding the
specified torque. Failure to do so may cause short circuit, equipment failures, or
malfunctions.
Negative common (PNP)
• When using a two-wire type sensor y When using a three-wire type sensor
3.2 Direct installation
6.
Response
time
3)
Applicable DIN rail TH35-7.5Fe and TH35-7.5AI
ON:When a communication error or DIP switch
setting error occurred
Flickering at a constant interval:
When the setting of the DIP switch was changed
while the power was supplied (even while the
LED is flickering, the operation continues. The
L ERR.
new setting becomes valid when the power is
turned OFF once, then ON again.)
Flickering at a intermittent interval:
When a terminal resistor is not attached or when
the module or a connection cable is affected by
noise
Common wiring method
4.4 Module terminal screw
COMB
4)
L RUN ON while normal operation is executed.
Use a crimp-style terminal in a status in which no force is applied on the cable.
Detection
circuit
Sensor (PNP)
Terminal block for
I/O interface
Hook for installation to DIN rail
DIP switch
Terminal arrangement (Terminal number and Signal name)
DIP switch assignment
1
3
5
7
0.5ms
40 20 10 8 4 2 1 1.5ms
X0
X1
DC24A
COMB
Input resistance
Terminal
Applicable wire size 0.3 to 1.25 mm2
X *
Removal
1)
2)
Orange color
COMB
Applicable crimpstyle terminal
Installation
X1
Item
4.3 Crimp-style terminal
When wiring one cable to one terminal
DIN rail mounting screw pitch
When installing the module to the DIN rail, tighten the mounting screws at
the pitch of 200mm(7.87") or less.
*1 The criterion is shown in IEC61131-2.
The power capacity W of the bleeder resistor R is as follows:
W = (Input voltage)2/R
Positive common (NPN)
• When using a two-wire type sensor y When using a three-wire type sensor
Align the upper DIN rail installation groove in the module with the DIN rail
1), and press the module in that status 2).
When removing the module, pull the hook downward for installation to DIN
rail 3), then remove the module 4).
402010 8 4 2 1 0.5ms
STATION NO. 1.5ms
Notes:
Leakage
Unit
current
6.2 mm (0.24" )
or less
3.1 Installation to DIN rail
X3
PW
Standards with which this product complies
Type : Programmable Controller (Open Type Equipment) Remote I/O module
Models : Products manufactured:
from November 1st, 2002 to April 30th, 2006 are compliant with
EN61000-6-4 and EN61131-2:1994+A11:1996+A12:2000
after May 1st, 2006 are compliant with EN61131-2:2007
Electromagnetic Compatibility
Remark
Standards (EMC)
Compliance with all relevant aspects of
EN61000-6-4:2001
the standard.
Electromagnetic compatibility
-Generic standards - Emission standard (Radiated Emissions and Mains
Terminal Voltage Emissions)
for Industrial environment
24V DC
Installation
The CL1X4-D1B2 can be installed to DIN rail or directly installed using
mounting screws.
Each installation procedure is described below.
X2
• Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
4.2 Connection to sensor
Detection
circuit
LINK/PW
Name
R(kΩ) < 1.7(mA) / Leakage current(mA) - 1.7(mA) x 5.6(kΩ)
• When using a three-wire type sensor
(when using the power supply for sensor other than 24V DC)
L RUN L ERR.
IN
DC24B
φ 3.2 (0.13")
X *
24G
DB
DA
+24V
2
• Manufactured at:
Mitsubishi Electric Corporation Himeji Works
840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan
R
COMB
4
3
2
1
PW
3.
X0
Note
• Manufactured by:
Mitsubishi Electric Corporation
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan
R
Example: When setting the station No. to "32", set the
DIP switch as follows.
10's digit
1's digit
Station
No.
40
20
10
8
4
2
1
32
OFF ON ON OFF OFF ON OFF
Sets the response speed.
0.5ms
ON: 0.5 ms (fast response type)
1.5ms
OFF: 1.5 ms (standard type)
CL1X4-D1B2
●Notification of CE marking●
This notification does not guarantee that an entire mechanical module produced
in accordance with the contents of the notification comply with the following
standards. Compliance to EMC standards of the entire mechanical module
should be checked by the user / manufacturer.
Attention
• This product is designed for use in industrial applications.
For I/O wiring, use crimp-style terminals of the following dimensions.
Connected to DC 24A terminal
0 1 2 3
Input operation indicator LEDs
Input is ON: Lit
Input is OFF: Extinguished
2-φ4.5
mounting hole
0 1 2 3
(M4 mounting
screw)
ON
Status
indicator
LEDs
Connector terminal
assignment
CAUTION
Detection
circuit
1 DC24A
2 DC24B
Sensor (NPN)
Name and Setting of Each Part and Terminal Arrangement
• When disposing of this product, treat it as industrial waste.
Sensor
External power
supply of the input
Interface terminal block for I/O (Negative common)
part (24V DC)
X *
2.
Connector for
CC-Link/LT interface
Circuit image
Negative common
Detection
circuit
Outline of Product
This product is a terminal block type input module connected to CC-Link/LT.
This product has four input points (24V DC).
CAUTION
Connector for CL1X4-D1B2
CC-Link/LT
Isolation
interface
1 +24V
2 DA
DC DC
3 DB
4 24G
External power
supply of the input
Interface terminal block for I/O (Positive common)
part (24V DC)
Connected to DC 24A terminal
1.
[DISPOSAL PRECAUTIONS]
Positive common
DC24A
DC24B
X0
COMB
X1
X2
COMB
X3
Zone C = Factory mains which is isolated from public mains by dedicated
transformers.
Zone B = Dedicated power distribution which is protected by secondary
surge pro tection. (300V or le ss in the ra ted vo ltage is
assumed.)
Zone A = Local power distribution which is isolated from dedicated power
distribution by AC/DC converters, isolation transformers, etc.
(120V or less in the rated voltage is assumed.)
DANGER
• Do not touch the terminals when the power is ON. It may cause an electric
shock or malfunction.
• Perform cleaning the module or retightening of terminal screws after turning
OFF the all external power supply for sure. Failure to do so may cause failure
or malfunction of the modules
• Do not disassemble or modify the module. Doing so may cause failure,
malfunction, injury, or fire.
• The module case is made of resin; do not drop it or subject it to strong shock.
A module damage may result.
• Make sure to switch all phases of the external power supply OFF before
installing or removing the module to/from the panel. Failure to do so may
cause failure or malfunction of the modules.
DIP switch
*1 Zone defined in EN61131-2
Separation defined in EN61131-2 for EMC LVD regulation decided
depending on condition in industrial setting.
[TRANSPORTATION AND MAINTENANCE PRECAUTIONS]
• Configure an interlock circuit in a sequence program so that the system
operates on the safety side using the communication status information
in the event the data link falls into a communication problem.
Otherwise, erroneous output and malfunction may result in accidents.
• Remote input and output can not be switched ON or OFF when a
problem occurs in the remote I/O modules. Therefore build an external
monitoring circuit that will monitor any input signals that could cause a
serious accident.
1
2
3
4
5
6
7
8
• Use this product in Zone A*1 as defined in EN61131-2.
6.5(0.26")
CL1X4-D1B2
JY997D04101F
December 2010
Terminal block
for I/O interface
22(0.87")
MODEL
MANUAL Number
Date
• Terminal screws which are not to be used must be tightened always.
Otherwise there will be a danger of short circuit against the bare solderless
terminals.
• Perform correct wiring for the module according to the product’s rated voltage
and terminal arrangement. Connecting to a power supply different from rating
or miss-wiring may cause fire, product failure or malfunction.
• Fix terminal screws securely within the regulated torque. Loose terminal
screws may cause fire and/or malfunction.
If the terminal screws are too tight, it may cause short circuit, equipment
failures, or erroneous operation due to damage of the screws.
• Make sure foreign objects do not get inside the module, such as dirt and wire
chips. It may cause fire, product failure or malfunction.
• Attach a warning label (hazard symbol 417-IEC-5036) concerning the electric
shock to the location.
Connector for CC-Link/LT communication line/module
power supply (24G/DB/DA/+24V)
Terminal block for connecting input signals and I/O power
supply
Set the 10's digit of the station No. using "STATION NO.
10", "STATION NO. 20" and "STATION NO. 40". Set the 1's
digit of the station No. using "STATION NO. 1", "STATION
NO. 2", "STATION NO. 4" and "STATION NO. 8".
Factory default = All bits are OFF.
Make sure to set the station No. in the range from 1 to 64.
If any station No. outside the range from 1 to 64 is set, it is
regarded as an error and the L ERR. LED lights.
Interface
6(0.24")
User’s Manual
CAUTION
41(1.62") ± 0.4(0.02")
Please read this manual thoroughly before starting to use the product and
handle the product properly.
• Perform installation and wiring after disconnecting the power supply at all
phases externally. If the power is not disconnected at all phases an electric
shock or product damage may result.
Description
ON while the input is ON.
0 1 2 3
Extinguished while the input is
OFF.
Input operation indicator
Input operation
indicator LED
49(1.93")
CL1X4-D1B2
CC-Link/LT Remote I/O Module
Name
Remark
Compliance with all relevant aspects of
EN61131-2:1994/A11:1996/A12:2000
the standard.
Programmable controllers
(RF Immunity, Fast transients, ESD and
-Equipment requirements and tests
Damped oscillatory wave)
Compliance with all relevant aspects of
the standard.
(Radiated Emissions, Conducted
EN61131-2: 2007
Emissions, Radiated electromagnetic
Programmable controllers
field, Fast transient burst, Electrostatic
-Equipment requirements and tests
discharge, High-energy surge, Voltage
drops and interruptions, Conducted RF
and Power frequency magnetic field)
For more details please contact the local Mitsubishi Electric sales site.
• Notes for compliance to EMC regulation.
It is necessary to install the CL1 series module in a shielded metal control
panel.
4.5(0.18")
A JAPANESE
0.06 kg (0.13 lbs)
40(1.58")
B
Unit: mm(inches)
This manual confers no industrial property rights or any rights of any other kind, nor
does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held
responsible for any problems involving industrial property rights which may occur as
a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the
cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi
products; damage, secondary damage, accident compensation caused by special
factors unpredictable by Mitsubishi; damages to products other than Mitsubishi
products; and to other duties.
For safe use
• This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in a
device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power,
aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
• This product has been manufactured under strict quality control. However when
installing the product where major accidents or losses could occur if the product
fails, install appropriate backup or failsafe functions in the system.
Country/Region Sales office/Tel
U.S.A.
Mitsubishi Electric Automation, Inc.
500 Corporate Woods Parkway, Vernon
Hills, IL 60061 U.S.A.
Tel : +1-847-478-2100
Brazil
MELCO-TEC Representacao
Comercial e Assessoria Tecnica Ltda.
Av. Paulista 1439, conj.74, Bela Vista CEP:
01311-200 Sao Paulo-SP-Brazil
Tel : +55-11-3146-2200
Germany
Mitsubishi Electric Europe B.V. German
Branch
Gothaer Strasse 8, D-40880 Ratingen,
Germany
Tel : +49-2102-486-0
Mitsubishi Electric Europe B.V. UK
U.K.
Branch
Travellers Lane, Hatfield, Hertfordshire.,
AL10 8XB, U.K.
Tel : +44-1707-276100
Mitsubishi Electric Europe B.V. Italian
Italy
Branch
VIALE COLLEONI 7-20041 Agrate Brianza
(Milano), Italy
Tel : +39-39-60531
Mitsubishi Electric Europe B.V. Spanish
Spain
Branch
Ctra. de Rubi 76-80-AC. 420, E-08190 Sant
Cugat del Valles (Barcelona), Spain
Tel : +34-93-565-3131
Mitsubishi Electric Europe B.V. French
France
Branch
25, Boulevard des Bouvets, F-92741
Nanterre Cedex, France
Tel: +33-1-55685568
Mitsubishi Electric Europe B.V. Moscow
Russia
Representative Office
52, bld. 5, Kosímodamianskaya nab,
RU-115054, Moscow, Russia
Tel: +7-495-721-2070
Country/Region Sales office/Tel
Hong Kong
Mitsubishi Electric Automation
(Hong Kong) Ltd.
10th Floor, Manulife Tower, 169 Electric
Road, North Point, HongKong
Tel : +852-2887-8870
China
Mitsubishi Electric Automation
(China) Ltd.
17F, ChuangXing Financial Center,
No. 288 West Nanjing Road, Shanghai
China 200003
Tel : +86-21-2322-3030
Taiwan
Setsuyo Enterprise Co., Ltd.
6F No.105 Wu Kung 3rd RD, Wu-Ku
Hsiang, Taipei Hsien, 248, Taiwan
Tel : +886-2-2299-2499
Korea
Mitsubishi Electric Automation Korea Co.,
Ltd.
3F, 1480-6, Gayang-Dong, Gangseo-Gu,
Seoul, 157-200, Korea
Tel : +82-2-3660-9552
Singapore
Mitsubishi Electric Asia Pte, Ltd.
307 Alexandra Road #05-01/02,
Mitsubishi Electric Building,
Singapore 159943
Tel : +65-6470-2460
Thailand
Mitsubishi Electric Automation (Thailand)
Co., Ltd.
Bang-Chan Industrial Estate No.111,
Soi Serithai 54, T.Kannayao, A.Kannayao,
Bangkok 10230
Tel : +66-2-517-1326
India
Messung Systems Pvt. Ltd.
Sapphire House EL-3 J-Block MIDC
Bhosari Pune 411026, India
Tel : +91-20-27102000
Australia
Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road PO BOX 11,
Rydalmere, N.S.W 2116, Australia
Tel : +61-2-9684-7777
South Africa Circuit Breaker Industries Ltd.
Private Bag 2016, ZA-1600 Isando,
South Africa
Tel : +27-11-9282000
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy,
Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Side
Side
Side
B ENGLISH
[WIRING PRECAUTIONS]
Electromagnetic Compatibility
Standards (EMC)
DANGER
●SAFETY PRECAUTIONS●
(Read these precautions before using)
Please read this manual carefully and pay special attention to safely in order
to handle this product properly. Also pay careful attention to safely and handle
the module properly.
These precautions apply only to Mitsubishi equipment. Refer to the user’s
manual of the CPU module to use for a description of the PLC system safety
precautions.
These ●SAFETY PRECAUTIONS● classify the safety precautions into two
categories: "DANGER" and "CAUTION".
DANGER
Procedures which may lead to a dangerous condition
and cause death or serious injury if not carried out
properly.
CAUTION
Procedures which may lead to a dangerous condition
and cause superficial to medium injury, or physical
damage only, if not carried out properly.
CAUTION
Depending on circumstances, procedures indicated by
may also be linked to serious results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
[STARTING AND MAINTENANCE PRECAUTIONS]
CAUTION
• Do not have control cables and communication cables bundled with or
placed near by the main circuit and/or power cables. Wire those cables
at least 100mm(3.94 inch) away from the main circuit and/or power
cables. It may cause malfunction due to noise interference.
• Use the module and the flat cable dedicated to CC-Link/LT without
applying any force on them.
Otherwise, such cables may be broken or fail.
[INSTALLATION PRECAUTIONS]
CAUTION
• Use the module in an environment that meets the general specifications
contained in this manual. Using this module in an environment outside
the range of the general specifications could result in electric shock, fire,
erroneous operation, and damage to or deterioration of the product.
• Do not directly touch the module's conductive parts.Doing so could
cause malfunction or trouble in the module.
• Tighten the module securely using DIN rail or installation screws within
the specified torque range.
If the screws are too lose, the module may drop from its installation
position, short circuit, or malfunction. If the screws are too tight, the
screws may be damaged, which may cause the module to drop from its
installation position or short circuit.
• Install the module on a flat surface.
If the mounting surface has concave and/or convex, an excessive force
may be applied on the module, and nonconformity may be caused.
CAUTION
• During transportation avoid any impact as the module is a precision
instrument. Doing so could cause trouble in the module.
• If is necessary to check the operation of module after transportation, in case
of any impact damage.
R
Input impedance
5.6 kΩ
1.7 mA or less
R: Bleeder resistor
...
...
• If chattering is present in the external input equipment, set 1.5ms.
• If the ON or OFF time of the input signal is less than 1.5 ms, set it to 0.5 ms.
(The ON and OFF time of the input signal are required to be 0.5 ms or more.)
When setting 1.5 ms:
Set both the ON and OFF time of the input signal to 1.5 ms or more.
When setting 0.5 ms:
Set both the ON and OFF time of the input signal to 0.5 ms or more.
Connected to DC 24A terminal
φ 3.2 (0.13")
6.2 mm (0.24" )
or less
Terminal screw
Crimp-style
terminal
When wiring two cables to one terminal
Terminal screw
Crimp-style
terminal
Bleeder resistor *1
X *
Detection
circuit
Terminal
4
6
8
COMB
X2
X3
Status indicator
LED
ON
Description
ON while the power is supplied.
• RAV1.25-3
• V1.25-3 (manufactured by JST Mfg. Co., Ltd.)
• 1.25-3 and TG1.25-3 (manufactured by NICHIFU Co., Ltd.)
Connected to DC 24A terminal
Bleeder resistor *1
X *
Detection
circuit
COMB
COMB
5.
5.2 Input specifications
DC input (External power supply of the input part)
Number of inputs
4 points
Isolation method
Isolation with photocoupler
Rated input voltage
24V DC
Rated input current
Approx. 4 mA
Operating voltage range
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Max. simultaneous ON
input points
100% (at 24V DC)
ON voltage/ON current
19 V or more/3 mA or more
OFF voltage/OFF current
11 V or less/1.7 mA or less
5.6 kΩ
OFF→ON
0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
ON→OFF
0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
4 points/1 common (2 points)
(terminal block two-wire type)
X *
Detection
circuit
Vibration resistance (*1)
COMB
Replace * in the figure with the used input No.
Notes:
*1 Bleeder resistor
When connecting a two-wire type sensor or input equipment containing a
parallel resistor, select a sensor or equipment whose leakage current is
1.7mA or less.
If the leakage current is more than 1.7mA, connect a bleeder resistor
obtained in the following calculation formula.
0 to 55°C (32 to 131°F)
-25 to 75°C (-13 to 167°F)
5 to 95%RH: Dew condensation shall not be
considered.
5 to 95%RH: Dew condensation shall not be
considered.
Number of
When intermittent vibration is present
times of
sweep
Frequency Acceleration Half amplitude
10 to 57Hz
0.075mm
−
10 times in
−
9.8m/s2
When continuous vibration is present
Frequency Acceleration Half amplitude
10 to 57Hz
0.035mm
−
57 to 150Hz
57 to 150Hz
Impact resistance (*1)
Operating atmosphere
Operating altitude
Installation place
Over-voltage category
Degree of contamination
Item
Voltage
4.9m/s2
Specification
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Current
consumption
40mA (when all points are ON)
Initial current
70mA
Max. allowable
momentary power PS1:1ms
failure period
Specification
each of X, Y
and Z
directions
(for 80 min)
−
147 m/s2, 3 times in each of X, Y and Z directions
Corrosive gas shall not be present.
2,000m(6561'8") or less (*2)
Inside control panel (*3)
ΙΙ or less (*4)
2 or less (*5)
Number of stations
occupied
4-, 8- or 16-point mode: 1 station
Noise durability
500Vp-p
Noise width: 1µs Cycle: 25 to 60 Hz
(by noise simulator)
Withstand voltage
500V AC for 1 min
Isolation resistance
10 MΩ or more between primary area (external
DC terminal) and secondary area (internal circuit)
by 500V DC megger
Protection class
IP2X
I/O part connection method Connection with terminal block
DIN rail installation, mounted by screws of type
Module installation method M4 × 0.7mm(0.03") × 16mm(0.63") or larger
Can be installed in six directions
Mass (weight)
M4 × 0.7mm(0.03") × 16mm(0.63") or more
(Tightening torque range: 0.78 to 1.08 N⋅m)
Wiring
The input terminals of the CL1X4-D1B2 can be wired as positive common
or negative common depending on the used sensor.
Outside Dimensions
50(1.97")
2 - φ4.5(0.18") mounting
hole (M4 mounting screw)
Center of DIN rail 10(0.40")
41.5(1.64") ± 0.4(0.02")
40(1.58")
Specification
Input method
Module
power
supply
5.1 General specifications
• When using a three-wire type sensor
(when using the power supply for sensor other than 24V DC)
Applicable screw
4.1 External wiring
5.3 Performance specifications
Specifications
Item
Ambient working
temperature
Ambient storage
temperature
Ambient operating
humidity
Ambient storage
humidity
Screw-tighten the module by attaching M4 screws to the upper and lower
mounting holes (two holes in all) provided in the module.
Install the module so that the clearance of 1 to 2mm (0.04" to 0.08") is
assured for each module.
4.
*2 The module cannot be used in an environment pressurized above the
atmospheric pressure which can be generated around the altitude of 0 m. If the
module is used in such an environment, it may fail.
*3 The module can be used in any environment even outside the control panel as
far as the requirements of the ambient operating temperature, the ambient
operating humidity, etc. are satisfied.
*4 This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution
network and the machinery within premises. Category ΙΙ applies to equipment
for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*5 This index indicates the degree of conductive generating substances in the
environment in which the module is used. The degree of contamination 2
indicates that contamination is caused by generation of only non-conductive
substances.
In this degree, however, temporary conduction may be caused by accidental
condensation.
Tighten the terminal screws (M3 screws) on the terminal block with a tightening
torque of 0.42 to 0.58 N⋅m. Do not tighten terminal screws exceeding the
specified torque. Failure to do so may cause short circuit, equipment failures, or
malfunctions.
Negative common (PNP)
• When using a two-wire type sensor y When using a three-wire type sensor
3.2 Direct installation
6.
Response
time
3)
Applicable DIN rail TH35-7.5Fe and TH35-7.5AI
ON:When a communication error or DIP switch
setting error occurred
Flickering at a constant interval:
When the setting of the DIP switch was changed
while the power was supplied (even while the
LED is flickering, the operation continues. The
L ERR.
new setting becomes valid when the power is
turned OFF once, then ON again.)
Flickering at a intermittent interval:
When a terminal resistor is not attached or when
the module or a connection cable is affected by
noise
Common wiring method
4.4 Module terminal screw
COMB
4)
L RUN ON while normal operation is executed.
Use a crimp-style terminal in a status in which no force is applied on the cable.
Detection
circuit
Sensor (PNP)
Terminal block for
I/O interface
Hook for installation to DIN rail
DIP switch
Terminal arrangement (Terminal number and Signal name)
DIP switch assignment
1
3
5
7
0.5ms
40 20 10 8 4 2 1 1.5ms
X0
X1
DC24A
COMB
Input resistance
Terminal
Applicable wire size 0.3 to 1.25 mm2
X *
Removal
1)
2)
Orange color
COMB
Applicable crimpstyle terminal
Installation
X1
Item
4.3 Crimp-style terminal
When wiring one cable to one terminal
DIN rail mounting screw pitch
When installing the module to the DIN rail, tighten the mounting screws at
the pitch of 200mm(7.87") or less.
*1 The criterion is shown in IEC61131-2.
The power capacity W of the bleeder resistor R is as follows:
W = (Input voltage)2/R
Positive common (NPN)
• When using a two-wire type sensor y When using a three-wire type sensor
Align the upper DIN rail installation groove in the module with the DIN rail
1), and press the module in that status 2).
When removing the module, pull the hook downward for installation to DIN
rail 3), then remove the module 4).
402010 8 4 2 1 0.5ms
STATION NO. 1.5ms
Notes:
Leakage
Unit
current
6.2 mm (0.24" )
or less
3.1 Installation to DIN rail
X3
PW
Standards with which this product complies
Type : Programmable Controller (Open Type Equipment) Remote I/O module
Models : Products manufactured:
from November 1st, 2002 to April 30th, 2006 are compliant with
EN61000-6-4 and EN61131-2:1994+A11:1996+A12:2000
after May 1st, 2006 are compliant with EN61131-2:2007
Electromagnetic Compatibility
Remark
Standards (EMC)
Compliance with all relevant aspects of
EN61000-6-4:2001
the standard.
Electromagnetic compatibility
-Generic standards - Emission standard (Radiated Emissions and Mains
Terminal Voltage Emissions)
for Industrial environment
24V DC
Installation
The CL1X4-D1B2 can be installed to DIN rail or directly installed using
mounting screws.
Each installation procedure is described below.
X2
• Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
4.2 Connection to sensor
Detection
circuit
LINK/PW
Name
R(kΩ) < 1.7(mA) / Leakage current(mA) - 1.7(mA) x 5.6(kΩ)
• When using a three-wire type sensor
(when using the power supply for sensor other than 24V DC)
L RUN L ERR.
IN
DC24B
φ 3.2 (0.13")
X *
24G
DB
DA
+24V
2
• Manufactured at:
Mitsubishi Electric Corporation Himeji Works
840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan
R
COMB
4
3
2
1
PW
3.
X0
Note
• Manufactured by:
Mitsubishi Electric Corporation
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan
R
Example: When setting the station No. to "32", set the
DIP switch as follows.
10's digit
1's digit
Station
No.
40
20
10
8
4
2
1
32
OFF ON ON OFF OFF ON OFF
Sets the response speed.
0.5ms
ON: 0.5 ms (fast response type)
1.5ms
OFF: 1.5 ms (standard type)
CL1X4-D1B2
●Notification of CE marking●
This notification does not guarantee that an entire mechanical module produced
in accordance with the contents of the notification comply with the following
standards. Compliance to EMC standards of the entire mechanical module
should be checked by the user / manufacturer.
Attention
• This product is designed for use in industrial applications.
For I/O wiring, use crimp-style terminals of the following dimensions.
Connected to DC 24A terminal
0 1 2 3
Input operation indicator LEDs
Input is ON: Lit
Input is OFF: Extinguished
2-φ4.5
mounting hole
0 1 2 3
(M4 mounting
screw)
ON
Status
indicator
LEDs
Connector terminal
assignment
CAUTION
Detection
circuit
1 DC24A
2 DC24B
Sensor (NPN)
Name and Setting of Each Part and Terminal Arrangement
• When disposing of this product, treat it as industrial waste.
Sensor
External power
supply of the input
Interface terminal block for I/O (Negative common)
part (24V DC)
X *
2.
Connector for
CC-Link/LT interface
Circuit image
Negative common
Detection
circuit
Outline of Product
This product is a terminal block type input module connected to CC-Link/LT.
This product has four input points (24V DC).
CAUTION
Connector for CL1X4-D1B2
CC-Link/LT
Isolation
interface
1 +24V
2 DA
DC DC
3 DB
4 24G
External power
supply of the input
Interface terminal block for I/O (Positive common)
part (24V DC)
Connected to DC 24A terminal
1.
[DISPOSAL PRECAUTIONS]
Positive common
DC24A
DC24B
X0
COMB
X1
X2
COMB
X3
Zone C = Factory mains which is isolated from public mains by dedicated
transformers.
Zone B = Dedicated power distribution which is protected by secondary
surge pro tection. (300V or le ss in the ra ted vo ltage is
assumed.)
Zone A = Local power distribution which is isolated from dedicated power
distribution by AC/DC converters, isolation transformers, etc.
(120V or less in the rated voltage is assumed.)
DANGER
• Do not touch the terminals when the power is ON. It may cause an electric
shock or malfunction.
• Perform cleaning the module or retightening of terminal screws after turning
OFF the all external power supply for sure. Failure to do so may cause failure
or malfunction of the modules
• Do not disassemble or modify the module. Doing so may cause failure,
malfunction, injury, or fire.
• The module case is made of resin; do not drop it or subject it to strong shock.
A module damage may result.
• Make sure to switch all phases of the external power supply OFF before
installing or removing the module to/from the panel. Failure to do so may
cause failure or malfunction of the modules.
DIP switch
*1 Zone defined in EN61131-2
Separation defined in EN61131-2 for EMC LVD regulation decided
depending on condition in industrial setting.
[TRANSPORTATION AND MAINTENANCE PRECAUTIONS]
• Configure an interlock circuit in a sequence program so that the system
operates on the safety side using the communication status information
in the event the data link falls into a communication problem.
Otherwise, erroneous output and malfunction may result in accidents.
• Remote input and output can not be switched ON or OFF when a
problem occurs in the remote I/O modules. Therefore build an external
monitoring circuit that will monitor any input signals that could cause a
serious accident.
1
2
3
4
5
6
7
8
• Use this product in Zone A*1 as defined in EN61131-2.
6.5(0.26")
CL1X4-D1B2
JY997D04101F
December 2010
Terminal block
for I/O interface
22(0.87")
MODEL
MANUAL Number
Date
• Terminal screws which are not to be used must be tightened always.
Otherwise there will be a danger of short circuit against the bare solderless
terminals.
• Perform correct wiring for the module according to the product’s rated voltage
and terminal arrangement. Connecting to a power supply different from rating
or miss-wiring may cause fire, product failure or malfunction.
• Fix terminal screws securely within the regulated torque. Loose terminal
screws may cause fire and/or malfunction.
If the terminal screws are too tight, it may cause short circuit, equipment
failures, or erroneous operation due to damage of the screws.
• Make sure foreign objects do not get inside the module, such as dirt and wire
chips. It may cause fire, product failure or malfunction.
• Attach a warning label (hazard symbol 417-IEC-5036) concerning the electric
shock to the location.
Connector for CC-Link/LT communication line/module
power supply (24G/DB/DA/+24V)
Terminal block for connecting input signals and I/O power
supply
Set the 10's digit of the station No. using "STATION NO.
10", "STATION NO. 20" and "STATION NO. 40". Set the 1's
digit of the station No. using "STATION NO. 1", "STATION
NO. 2", "STATION NO. 4" and "STATION NO. 8".
Factory default = All bits are OFF.
Make sure to set the station No. in the range from 1 to 64.
If any station No. outside the range from 1 to 64 is set, it is
regarded as an error and the L ERR. LED lights.
Interface
6(0.24")
User’s Manual
CAUTION
41(1.62") ± 0.4(0.02")
Please read this manual thoroughly before starting to use the product and
handle the product properly.
• Perform installation and wiring after disconnecting the power supply at all
phases externally. If the power is not disconnected at all phases an electric
shock or product damage may result.
Description
ON while the input is ON.
0 1 2 3
Extinguished while the input is
OFF.
Input operation indicator
Input operation
indicator LED
49(1.93")
CL1X4-D1B2
CC-Link/LT Remote I/O Module
Name
Remark
Compliance with all relevant aspects of
EN61131-2:1994/A11:1996/A12:2000
the standard.
Programmable controllers
(RF Immunity, Fast transients, ESD and
-Equipment requirements and tests
Damped oscillatory wave)
Compliance with all relevant aspects of
the standard.
(Radiated Emissions, Conducted
EN61131-2: 2007
Emissions, Radiated electromagnetic
Programmable controllers
field, Fast transient burst, Electrostatic
-Equipment requirements and tests
discharge, High-energy surge, Voltage
drops and interruptions, Conducted RF
and Power frequency magnetic field)
For more details please contact the local Mitsubishi Electric sales site.
• Notes for compliance to EMC regulation.
It is necessary to install the CL1 series module in a shielded metal control
panel.
4.5(0.18")
A JAPANESE
0.06 kg (0.13 lbs)
40(1.58")
B
Unit: mm(inches)
This manual confers no industrial property rights or any rights of any other kind, nor
does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held
responsible for any problems involving industrial property rights which may occur as
a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the
cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi
products; damage, secondary damage, accident compensation caused by special
factors unpredictable by Mitsubishi; damages to products other than Mitsubishi
products; and to other duties.
For safe use
• This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in a
device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power,
aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
• This product has been manufactured under strict quality control. However when
installing the product where major accidents or losses could occur if the product
fails, install appropriate backup or failsafe functions in the system.
Country/Region Sales office/Tel
U.S.A.
Mitsubishi Electric Automation, Inc.
500 Corporate Woods Parkway, Vernon
Hills, IL 60061 U.S.A.
Tel : +1-847-478-2100
Brazil
MELCO-TEC Representacao
Comercial e Assessoria Tecnica Ltda.
Av. Paulista 1439, conj.74, Bela Vista CEP:
01311-200 Sao Paulo-SP-Brazil
Tel : +55-11-3146-2200
Germany
Mitsubishi Electric Europe B.V. German
Branch
Gothaer Strasse 8, D-40880 Ratingen,
Germany
Tel : +49-2102-486-0
Mitsubishi Electric Europe B.V. UK
U.K.
Branch
Travellers Lane, Hatfield, Hertfordshire.,
AL10 8XB, U.K.
Tel : +44-1707-276100
Mitsubishi Electric Europe B.V. Italian
Italy
Branch
VIALE COLLEONI 7-20041 Agrate Brianza
(Milano), Italy
Tel : +39-39-60531
Mitsubishi Electric Europe B.V. Spanish
Spain
Branch
Ctra. de Rubi 76-80-AC. 420, E-08190 Sant
Cugat del Valles (Barcelona), Spain
Tel : +34-93-565-3131
Mitsubishi Electric Europe B.V. French
France
Branch
25, Boulevard des Bouvets, F-92741
Nanterre Cedex, France
Tel: +33-1-55685568
Mitsubishi Electric Europe B.V. Moscow
Russia
Representative Office
52, bld. 5, Kosímodamianskaya nab,
RU-115054, Moscow, Russia
Tel: +7-495-721-2070
Country/Region Sales office/Tel
Hong Kong
Mitsubishi Electric Automation
(Hong Kong) Ltd.
10th Floor, Manulife Tower, 169 Electric
Road, North Point, HongKong
Tel : +852-2887-8870
China
Mitsubishi Electric Automation
(China) Ltd.
17F, ChuangXing Financial Center,
No. 288 West Nanjing Road, Shanghai
China 200003
Tel : +86-21-2322-3030
Taiwan
Setsuyo Enterprise Co., Ltd.
6F No.105 Wu Kung 3rd RD, Wu-Ku
Hsiang, Taipei Hsien, 248, Taiwan
Tel : +886-2-2299-2499
Korea
Mitsubishi Electric Automation Korea Co.,
Ltd.
3F, 1480-6, Gayang-Dong, Gangseo-Gu,
Seoul, 157-200, Korea
Tel : +82-2-3660-9552
Singapore
Mitsubishi Electric Asia Pte, Ltd.
307 Alexandra Road #05-01/02,
Mitsubishi Electric Building,
Singapore 159943
Tel : +65-6470-2460
Thailand
Mitsubishi Electric Automation (Thailand)
Co., Ltd.
Bang-Chan Industrial Estate No.111,
Soi Serithai 54, T.Kannayao, A.Kannayao,
Bangkok 10230
Tel : +66-2-517-1326
India
Messung Systems Pvt. Ltd.
Sapphire House EL-3 J-Block MIDC
Bhosari Pune 411026, India
Tel : +91-20-27102000
Australia
Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road PO BOX 11,
Rydalmere, N.S.W 2116, Australia
Tel : +61-2-9684-7777
South Africa Circuit Breaker Industries Ltd.
Private Bag 2016, ZA-1600 Isando,
South Africa
Tel : +27-11-9282000
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy,
Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Side
Side
Side
B ENGLISH
[WIRING PRECAUTIONS]
Electromagnetic Compatibility
Standards (EMC)
DANGER
●SAFETY PRECAUTIONS●
(Read these precautions before using)
Please read this manual carefully and pay special attention to safely in order
to handle this product properly. Also pay careful attention to safely and handle
the module properly.
These precautions apply only to Mitsubishi equipment. Refer to the user’s
manual of the CPU module to use for a description of the PLC system safety
precautions.
These ●SAFETY PRECAUTIONS● classify the safety precautions into two
categories: "DANGER" and "CAUTION".
DANGER
Procedures which may lead to a dangerous condition
and cause death or serious injury if not carried out
properly.
CAUTION
Procedures which may lead to a dangerous condition
and cause superficial to medium injury, or physical
damage only, if not carried out properly.
CAUTION
Depending on circumstances, procedures indicated by
may also be linked to serious results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
[STARTING AND MAINTENANCE PRECAUTIONS]
CAUTION
• Do not have control cables and communication cables bundled with or
placed near by the main circuit and/or power cables. Wire those cables
at least 100mm(3.94 inch) away from the main circuit and/or power
cables. It may cause malfunction due to noise interference.
• Use the module and the flat cable dedicated to CC-Link/LT without
applying any force on them.
Otherwise, such cables may be broken or fail.
[INSTALLATION PRECAUTIONS]
CAUTION
• Use the module in an environment that meets the general specifications
contained in this manual. Using this module in an environment outside
the range of the general specifications could result in electric shock, fire,
erroneous operation, and damage to or deterioration of the product.
• Do not directly touch the module's conductive parts.Doing so could
cause malfunction or trouble in the module.
• Tighten the module securely using DIN rail or installation screws within
the specified torque range.
If the screws are too lose, the module may drop from its installation
position, short circuit, or malfunction. If the screws are too tight, the
screws may be damaged, which may cause the module to drop from its
installation position or short circuit.
• Install the module on a flat surface.
If the mounting surface has concave and/or convex, an excessive force
may be applied on the module, and nonconformity may be caused.
CAUTION
• During transportation avoid any impact as the module is a precision
instrument. Doing so could cause trouble in the module.
• If is necessary to check the operation of module after transportation, in case
of any impact damage.
R
Input impedance
5.6 kΩ
1.7 mA or less
R: Bleeder resistor
...
...
• If chattering is present in the external input equipment, set 1.5ms.
• If the ON or OFF time of the input signal is less than 1.5 ms, set it to 0.5 ms.
(The ON and OFF time of the input signal are required to be 0.5 ms or more.)
When setting 1.5 ms:
Set both the ON and OFF time of the input signal to 1.5 ms or more.
When setting 0.5 ms:
Set both the ON and OFF time of the input signal to 0.5 ms or more.
Connected to DC 24A terminal
φ 3.2 (0.13")
6.2 mm (0.24" )
or less
Terminal screw
Crimp-style
terminal
When wiring two cables to one terminal
Terminal screw
Crimp-style
terminal
Bleeder resistor *1
X *
Detection
circuit
Terminal
4
6
8
COMB
X2
X3
Status indicator
LED
ON
Description
ON while the power is supplied.
• RAV1.25-3
• V1.25-3 (manufactured by JST Mfg. Co., Ltd.)
• 1.25-3 and TG1.25-3 (manufactured by NICHIFU Co., Ltd.)
Connected to DC 24A terminal
Bleeder resistor *1
X *
Detection
circuit
COMB
COMB
5.
5.2 Input specifications
DC input (External power supply of the input part)
Number of inputs
4 points
Isolation method
Isolation with photocoupler
Rated input voltage
24V DC
Rated input current
Approx. 4 mA
Operating voltage range
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Max. simultaneous ON
input points
100% (at 24V DC)
ON voltage/ON current
19 V or more/3 mA or more
OFF voltage/OFF current
11 V or less/1.7 mA or less
5.6 kΩ
OFF→ON
0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
ON→OFF
0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
4 points/1 common (2 points)
(terminal block two-wire type)
X *
Detection
circuit
Vibration resistance (*1)
COMB
Replace * in the figure with the used input No.
Notes:
*1 Bleeder resistor
When connecting a two-wire type sensor or input equipment containing a
parallel resistor, select a sensor or equipment whose leakage current is
1.7mA or less.
If the leakage current is more than 1.7mA, connect a bleeder resistor
obtained in the following calculation formula.
0 to 55°C (32 to 131°F)
-25 to 75°C (-13 to 167°F)
5 to 95%RH: Dew condensation shall not be
considered.
5 to 95%RH: Dew condensation shall not be
considered.
Number of
When intermittent vibration is present
times of
sweep
Frequency Acceleration Half amplitude
10 to 57Hz
0.075mm
−
10 times in
−
9.8m/s2
When continuous vibration is present
Frequency Acceleration Half amplitude
10 to 57Hz
0.035mm
−
57 to 150Hz
57 to 150Hz
Impact resistance (*1)
Operating atmosphere
Operating altitude
Installation place
Over-voltage category
Degree of contamination
Item
Voltage
4.9m/s2
Specification
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Current
consumption
40mA (when all points are ON)
Initial current
70mA
Max. allowable
momentary power PS1:1ms
failure period
Specification
each of X, Y
and Z
directions
(for 80 min)
−
147 m/s2, 3 times in each of X, Y and Z directions
Corrosive gas shall not be present.
2,000m(6561'8") or less (*2)
Inside control panel (*3)
ΙΙ or less (*4)
2 or less (*5)
Number of stations
occupied
4-, 8- or 16-point mode: 1 station
Noise durability
500Vp-p
Noise width: 1µs Cycle: 25 to 60 Hz
(by noise simulator)
Withstand voltage
500V AC for 1 min
Isolation resistance
10 MΩ or more between primary area (external
DC terminal) and secondary area (internal circuit)
by 500V DC megger
Protection class
IP2X
I/O part connection method Connection with terminal block
DIN rail installation, mounted by screws of type
Module installation method M4 × 0.7mm(0.03") × 16mm(0.63") or larger
Can be installed in six directions
Mass (weight)
M4 × 0.7mm(0.03") × 16mm(0.63") or more
(Tightening torque range: 0.78 to 1.08 N⋅m)
Wiring
The input terminals of the CL1X4-D1B2 can be wired as positive common
or negative common depending on the used sensor.
Outside Dimensions
50(1.97")
2 - φ4.5(0.18") mounting
hole (M4 mounting screw)
Center of DIN rail 10(0.40")
41.5(1.64") ± 0.4(0.02")
40(1.58")
Specification
Input method
Module
power
supply
5.1 General specifications
• When using a three-wire type sensor
(when using the power supply for sensor other than 24V DC)
Applicable screw
4.1 External wiring
5.3 Performance specifications
Specifications
Item
Ambient working
temperature
Ambient storage
temperature
Ambient operating
humidity
Ambient storage
humidity
Screw-tighten the module by attaching M4 screws to the upper and lower
mounting holes (two holes in all) provided in the module.
Install the module so that the clearance of 1 to 2mm (0.04" to 0.08") is
assured for each module.
4.
*2 The module cannot be used in an environment pressurized above the
atmospheric pressure which can be generated around the altitude of 0 m. If the
module is used in such an environment, it may fail.
*3 The module can be used in any environment even outside the control panel as
far as the requirements of the ambient operating temperature, the ambient
operating humidity, etc. are satisfied.
*4 This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution
network and the machinery within premises. Category ΙΙ applies to equipment
for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*5 This index indicates the degree of conductive generating substances in the
environment in which the module is used. The degree of contamination 2
indicates that contamination is caused by generation of only non-conductive
substances.
In this degree, however, temporary conduction may be caused by accidental
condensation.
Tighten the terminal screws (M3 screws) on the terminal block with a tightening
torque of 0.42 to 0.58 N⋅m. Do not tighten terminal screws exceeding the
specified torque. Failure to do so may cause short circuit, equipment failures, or
malfunctions.
Negative common (PNP)
• When using a two-wire type sensor y When using a three-wire type sensor
3.2 Direct installation
6.
Response
time
3)
Applicable DIN rail TH35-7.5Fe and TH35-7.5AI
ON:When a communication error or DIP switch
setting error occurred
Flickering at a constant interval:
When the setting of the DIP switch was changed
while the power was supplied (even while the
LED is flickering, the operation continues. The
L ERR.
new setting becomes valid when the power is
turned OFF once, then ON again.)
Flickering at a intermittent interval:
When a terminal resistor is not attached or when
the module or a connection cable is affected by
noise
Common wiring method
4.4 Module terminal screw
COMB
4)
L RUN ON while normal operation is executed.
Use a crimp-style terminal in a status in which no force is applied on the cable.
Detection
circuit
Sensor (PNP)
Terminal block for
I/O interface
Hook for installation to DIN rail
DIP switch
Terminal arrangement (Terminal number and Signal name)
DIP switch assignment
1
3
5
7
0.5ms
40 20 10 8 4 2 1 1.5ms
X0
X1
DC24A
COMB
Input resistance
Terminal
Applicable wire size 0.3 to 1.25 mm2
X *
Removal
1)
2)
Orange color
COMB
Applicable crimpstyle terminal
Installation
X1
Item
4.3 Crimp-style terminal
When wiring one cable to one terminal
DIN rail mounting screw pitch
When installing the module to the DIN rail, tighten the mounting screws at
the pitch of 200mm(7.87") or less.
*1 The criterion is shown in IEC61131-2.
The power capacity W of the bleeder resistor R is as follows:
W = (Input voltage)2/R
Positive common (NPN)
• When using a two-wire type sensor y When using a three-wire type sensor
Align the upper DIN rail installation groove in the module with the DIN rail
1), and press the module in that status 2).
When removing the module, pull the hook downward for installation to DIN
rail 3), then remove the module 4).
402010 8 4 2 1 0.5ms
STATION NO. 1.5ms
Notes:
Leakage
Unit
current
6.2 mm (0.24" )
or less
3.1 Installation to DIN rail
X3
PW
Standards with which this product complies
Type : Programmable Controller (Open Type Equipment) Remote I/O module
Models : Products manufactured:
from November 1st, 2002 to April 30th, 2006 are compliant with
EN61000-6-4 and EN61131-2:1994+A11:1996+A12:2000
after May 1st, 2006 are compliant with EN61131-2:2007
Electromagnetic Compatibility
Remark
Standards (EMC)
Compliance with all relevant aspects of
EN61000-6-4:2001
the standard.
Electromagnetic compatibility
-Generic standards - Emission standard (Radiated Emissions and Mains
Terminal Voltage Emissions)
for Industrial environment
24V DC
Installation
The CL1X4-D1B2 can be installed to DIN rail or directly installed using
mounting screws.
Each installation procedure is described below.
X2
• Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
4.2 Connection to sensor
Detection
circuit
LINK/PW
Name
R(kΩ) < 1.7(mA) / Leakage current(mA) - 1.7(mA) x 5.6(kΩ)
• When using a three-wire type sensor
(when using the power supply for sensor other than 24V DC)
L RUN L ERR.
IN
DC24B
φ 3.2 (0.13")
X *
24G
DB
DA
+24V
2
• Manufactured at:
Mitsubishi Electric Corporation Himeji Works
840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan
R
COMB
4
3
2
1
PW
3.
X0
Note
• Manufactured by:
Mitsubishi Electric Corporation
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan
R
Example: When setting the station No. to "32", set the
DIP switch as follows.
10's digit
1's digit
Station
No.
40
20
10
8
4
2
1
32
OFF ON ON OFF OFF ON OFF
Sets the response speed.
0.5ms
ON: 0.5 ms (fast response type)
1.5ms
OFF: 1.5 ms (standard type)
CL1X4-D1B2
●Notification of CE marking●
This notification does not guarantee that an entire mechanical module produced
in accordance with the contents of the notification comply with the following
standards. Compliance to EMC standards of the entire mechanical module
should be checked by the user / manufacturer.
Attention
• This product is designed for use in industrial applications.
For I/O wiring, use crimp-style terminals of the following dimensions.
Connected to DC 24A terminal
0 1 2 3
Input operation indicator LEDs
Input is ON: Lit
Input is OFF: Extinguished
2-φ4.5
mounting hole
0 1 2 3
(M4 mounting
screw)
ON
Status
indicator
LEDs
Connector terminal
assignment
CAUTION
Detection
circuit
1 DC24A
2 DC24B
Sensor (NPN)
Name and Setting of Each Part and Terminal Arrangement
• When disposing of this product, treat it as industrial waste.
Sensor
External power
supply of the input
Interface terminal block for I/O (Negative common)
part (24V DC)
X *
2.
Connector for
CC-Link/LT interface
Circuit image
Negative common
Detection
circuit
Outline of Product
This product is a terminal block type input module connected to CC-Link/LT.
This product has four input points (24V DC).
CAUTION
Connector for CL1X4-D1B2
CC-Link/LT
Isolation
interface
1 +24V
2 DA
DC DC
3 DB
4 24G
External power
supply of the input
Interface terminal block for I/O (Positive common)
part (24V DC)
Connected to DC 24A terminal
1.
[DISPOSAL PRECAUTIONS]
Positive common
DC24A
DC24B
X0
COMB
X1
X2
COMB
X3
Zone C = Factory mains which is isolated from public mains by dedicated
transformers.
Zone B = Dedicated power distribution which is protected by secondary
surge pro tection. (300V or le ss in the ra ted vo ltage is
assumed.)
Zone A = Local power distribution which is isolated from dedicated power
distribution by AC/DC converters, isolation transformers, etc.
(120V or less in the rated voltage is assumed.)
DANGER
• Do not touch the terminals when the power is ON. It may cause an electric
shock or malfunction.
• Perform cleaning the module or retightening of terminal screws after turning
OFF the all external power supply for sure. Failure to do so may cause failure
or malfunction of the modules
• Do not disassemble or modify the module. Doing so may cause failure,
malfunction, injury, or fire.
• The module case is made of resin; do not drop it or subject it to strong shock.
A module damage may result.
• Make sure to switch all phases of the external power supply OFF before
installing or removing the module to/from the panel. Failure to do so may
cause failure or malfunction of the modules.
DIP switch
*1 Zone defined in EN61131-2
Separation defined in EN61131-2 for EMC LVD regulation decided
depending on condition in industrial setting.
[TRANSPORTATION AND MAINTENANCE PRECAUTIONS]
• Configure an interlock circuit in a sequence program so that the system
operates on the safety side using the communication status information
in the event the data link falls into a communication problem.
Otherwise, erroneous output and malfunction may result in accidents.
• Remote input and output can not be switched ON or OFF when a
problem occurs in the remote I/O modules. Therefore build an external
monitoring circuit that will monitor any input signals that could cause a
serious accident.
1
2
3
4
5
6
7
8
• Use this product in Zone A*1 as defined in EN61131-2.
6.5(0.26")
CL1X4-D1B2
JY997D04101F
December 2010
Terminal block
for I/O interface
22(0.87")
MODEL
MANUAL Number
Date
• Terminal screws which are not to be used must be tightened always.
Otherwise there will be a danger of short circuit against the bare solderless
terminals.
• Perform correct wiring for the module according to the product’s rated voltage
and terminal arrangement. Connecting to a power supply different from rating
or miss-wiring may cause fire, product failure or malfunction.
• Fix terminal screws securely within the regulated torque. Loose terminal
screws may cause fire and/or malfunction.
If the terminal screws are too tight, it may cause short circuit, equipment
failures, or erroneous operation due to damage of the screws.
• Make sure foreign objects do not get inside the module, such as dirt and wire
chips. It may cause fire, product failure or malfunction.
• Attach a warning label (hazard symbol 417-IEC-5036) concerning the electric
shock to the location.
Connector for CC-Link/LT communication line/module
power supply (24G/DB/DA/+24V)
Terminal block for connecting input signals and I/O power
supply
Set the 10's digit of the station No. using "STATION NO.
10", "STATION NO. 20" and "STATION NO. 40". Set the 1's
digit of the station No. using "STATION NO. 1", "STATION
NO. 2", "STATION NO. 4" and "STATION NO. 8".
Factory default = All bits are OFF.
Make sure to set the station No. in the range from 1 to 64.
If any station No. outside the range from 1 to 64 is set, it is
regarded as an error and the L ERR. LED lights.
Interface
6(0.24")
User’s Manual
CAUTION
41(1.62") ± 0.4(0.02")
Please read this manual thoroughly before starting to use the product and
handle the product properly.
• Perform installation and wiring after disconnecting the power supply at all
phases externally. If the power is not disconnected at all phases an electric
shock or product damage may result.
Description
ON while the input is ON.
0 1 2 3
Extinguished while the input is
OFF.
Input operation indicator
Input operation
indicator LED
49(1.93")
CL1X4-D1B2
CC-Link/LT Remote I/O Module
Name
Remark
Compliance with all relevant aspects of
EN61131-2:1994/A11:1996/A12:2000
the standard.
Programmable controllers
(RF Immunity, Fast transients, ESD and
-Equipment requirements and tests
Damped oscillatory wave)
Compliance with all relevant aspects of
the standard.
(Radiated Emissions, Conducted
EN61131-2: 2007
Emissions, Radiated electromagnetic
Programmable controllers
field, Fast transient burst, Electrostatic
-Equipment requirements and tests
discharge, High-energy surge, Voltage
drops and interruptions, Conducted RF
and Power frequency magnetic field)
For more details please contact the local Mitsubishi Electric sales site.
• Notes for compliance to EMC regulation.
It is necessary to install the CL1 series module in a shielded metal control
panel.
4.5(0.18")
A JAPANESE
0.06 kg (0.13 lbs)
40(1.58")
B
Unit: mm(inches)
This manual confers no industrial property rights or any rights of any other kind, nor
does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held
responsible for any problems involving industrial property rights which may occur as
a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the
cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi
products; damage, secondary damage, accident compensation caused by special
factors unpredictable by Mitsubishi; damages to products other than Mitsubishi
products; and to other duties.
For safe use
• This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in a
device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power,
aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
• This product has been manufactured under strict quality control. However when
installing the product where major accidents or losses could occur if the product
fails, install appropriate backup or failsafe functions in the system.
Country/Region Sales office/Tel
U.S.A.
Mitsubishi Electric Automation, Inc.
500 Corporate Woods Parkway, Vernon
Hills, IL 60061 U.S.A.
Tel : +1-847-478-2100
Brazil
MELCO-TEC Representacao
Comercial e Assessoria Tecnica Ltda.
Av. Paulista 1439, conj.74, Bela Vista CEP:
01311-200 Sao Paulo-SP-Brazil
Tel : +55-11-3146-2200
Germany
Mitsubishi Electric Europe B.V. German
Branch
Gothaer Strasse 8, D-40880 Ratingen,
Germany
Tel : +49-2102-486-0
Mitsubishi Electric Europe B.V. UK
U.K.
Branch
Travellers Lane, Hatfield, Hertfordshire.,
AL10 8XB, U.K.
Tel : +44-1707-276100
Mitsubishi Electric Europe B.V. Italian
Italy
Branch
VIALE COLLEONI 7-20041 Agrate Brianza
(Milano), Italy
Tel : +39-39-60531
Mitsubishi Electric Europe B.V. Spanish
Spain
Branch
Ctra. de Rubi 76-80-AC. 420, E-08190 Sant
Cugat del Valles (Barcelona), Spain
Tel : +34-93-565-3131
Mitsubishi Electric Europe B.V. French
France
Branch
25, Boulevard des Bouvets, F-92741
Nanterre Cedex, France
Tel: +33-1-55685568
Mitsubishi Electric Europe B.V. Moscow
Russia
Representative Office
52, bld. 5, Kosímodamianskaya nab,
RU-115054, Moscow, Russia
Tel: +7-495-721-2070
Country/Region Sales office/Tel
Hong Kong
Mitsubishi Electric Automation
(Hong Kong) Ltd.
10th Floor, Manulife Tower, 169 Electric
Road, North Point, HongKong
Tel : +852-2887-8870
China
Mitsubishi Electric Automation
(China) Ltd.
17F, ChuangXing Financial Center,
No. 288 West Nanjing Road, Shanghai
China 200003
Tel : +86-21-2322-3030
Taiwan
Setsuyo Enterprise Co., Ltd.
6F No.105 Wu Kung 3rd RD, Wu-Ku
Hsiang, Taipei Hsien, 248, Taiwan
Tel : +886-2-2299-2499
Korea
Mitsubishi Electric Automation Korea Co.,
Ltd.
3F, 1480-6, Gayang-Dong, Gangseo-Gu,
Seoul, 157-200, Korea
Tel : +82-2-3660-9552
Singapore
Mitsubishi Electric Asia Pte, Ltd.
307 Alexandra Road #05-01/02,
Mitsubishi Electric Building,
Singapore 159943
Tel : +65-6470-2460
Thailand
Mitsubishi Electric Automation (Thailand)
Co., Ltd.
Bang-Chan Industrial Estate No.111,
Soi Serithai 54, T.Kannayao, A.Kannayao,
Bangkok 10230
Tel : +66-2-517-1326
India
Messung Systems Pvt. Ltd.
Sapphire House EL-3 J-Block MIDC
Bhosari Pune 411026, India
Tel : +91-20-27102000
Australia
Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road PO BOX 11,
Rydalmere, N.S.W 2116, Australia
Tel : +61-2-9684-7777
South Africa Circuit Breaker Industries Ltd.
Private Bag 2016, ZA-1600 Isando,
South Africa
Tel : +27-11-9282000
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy,
Trade and Industry for service transaction permission.
Specifications subject to change without notice.