Burner Controls - System Control Engineering, Penrose

Burner Controls with Integral Ignition
Brahma CE11 U MICROFLAT
• Restart attempt
• Plug in electrical connections
• Single gas valve
• Volatile lock-out
• Pre-purge 1.5 seconds
• Flame failure safety time 10
seconds
• Ionization flame electrode control
• 240 or 110 volt AC
Typical Photo
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
#B1150
Brahma CM11 U MICROFLAT
• Restart attempt
• Plug in electrical connections
• Single gas valve
• Non Volatile lock-out
• Pre-purge 1.5 seconds
• Flame failure safety time
10 seconds
• Ionization flame electrode control
• 240 or 110 volt AC
#B1152
Brahma CE12 U MICROFLAT
• Restart attempt
• Plug in electrical connections
• Pilot / Main Gas (2 valves)
• Volatile lock-out
• Pre-purge 1.5 seconds
• Flame failure safety time 10
seconds
• Ionization flame electrode control
• 240 or 110 volt AC
#B1154X
Brahma CM12 U MICROFLAT
• Restart attempt
• Plug in electrical connections
• Pilot / Main Gas (2 valve)
• Non Volatile lock-out
• Pre-purge 1.5 seconds
• Flame failure safety time
10 seconds
• Ionization flame electrode control
• 240 or 110 volt AC
#B1154
Brahma CE31 U MICROFLAT
• Restart attempt
• Plug in electrical connections
• Single gas valve
• Volatile lock-out
• Pre-purge 1.5 seconds
• Flame failure safety time
10 seconds
• Ionization flame electrode control
• 240 or 110 volt AC
• Air pressure Proving / Fan
#B1156
Non Volatile Lock out versions require an external re set button to reset.
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
6.1
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Brahma CM31 U MICROFLAT
• Restart attempt
• Plug in electrical connections
• Single gas valve
• Non Volatile lock-out
• Pre-purge 1.5 seconds
• Flame failure safety time
10 seconds
• Remote flame failure reset
push button
• Ionization flame electrode control
• 240 or 110 volt AC
#B1156
Brahma CM32 EUROFLAT
• Restart attempt
• Plug in electrical connections
• Pilot and Main gas valves
• Non Volatile lock-out
• Pre-purge - 5 or 30 seconds
• Flame failure safety time 5 seconds
• Remote flame failure reset
• Ionization flame electrode control
• 240 or 110 volt AC
• Fan control with air pressure proving
#B1164
Note: Plugs and pins as standard on all Brahma Microflat controllers.
Wiring kits available for all Brahma Microflat controllers
White-Rodgers 50A72 HSI Control
• Plug in connectors
• Re-start attempt
• Single gas valve
• Flame sensor
• Hot surface ignitor
• LED Indicator
• 240 volt AC
• Suitable for Rheems hot water
cylinders
#W0212
6.2
RAM 3EM 10-07 CONTROL
• Plug in electrical connectors
• Single valves
• Re- Start attempt
• Volatile lock-out
• Flame failure safety time - 5 sec
• Single sensor Ionization / Ignition
• LED operation indication diagnostics
• 24 volt AC
• Fan control with Air Pressure
Proving
• Wiring kit available (#RAM0110K)
#RAM0112
RAM 5EM 7-01 CONTROL
• Plug in electrical connectors
• Pilot / Main valves
• Re- Start attempt
• Volatile lock-out
• Flame failure safety time - 5 sec
• Separate sensors for
Ionization / Ignition
• LED operation indication diagnostics
• 24 volt AC
• Wiring kit available (#RAM0160K)
#RAM0160
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
Programmed Oil & Gas Burner Controls
Fenwall Burner Control C/W
Wiring Loom
•
12 VDC
•
Integral Ignition transformer
•
Inter purge time 25 seconds
•
Trial for ignition time ( TFI ) 10 seconds
# FW-35-53056-035
300e/04 /98
A Honeywell Company
ety Control
TF 801 / 801.2
TF 802 / 802.2
er burners up to
rmittent operations.
r IRD 1010
VD 970
r safety control boxes are
il power burner up to 30 kg/
ed according to DIN 4787).
TF 802.2 are approved and
n
ca. 20
sec.
ty
Control
ca. 20 sec.
ction according to EN230
n
er2-4
burners
sec. up to
nmittent operations.
2-4 sec.
ction according to EN230
IRD 1010
VD 970
ES
ected by a flame resistant,
incorporates the thermoensated timer, flame check
safety control boxes are
power burner up to 30 kg/
d according
to DIN
4787).
vided
by a push
button
with
F 802.2
are approved
and
mp.
A central
fixing screw
g base. The wiring base and
-in arrangement, making it
ct connection between the
try points provides utmost
compatible with the TF 701,
ca.
20 sec.
he flame
detector IRD 910
y its compatible type IRD
ca. 20 sec.
tion
according
on
button
(item to
no.EN230
70601)
ight differences.
2-4 sec.
S
300e/04 /98
TF 801 / 801.2
A Honeywell Company
TECHNICAL DATA TF 802 / 802.2
n
2-4 sec.
tion according to EN230
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Operating voltage
Fuse rating
Power consumption
Max. load per output
- terminal 3
- terminal 4
- terminal 5
- terminal 6
- terminal 7
total load
Pre-purge time
Pre-ignition time
Post-ignition time TF 801/TF801.2
TF 802/TF802.2
Delay time to oil valve 2
Lockout safety time
Reset time from lockout
Flame detector:
FZ 771 S red
FZ 771 S white
220/240 V (-15..+10%)
50 Hz (40-60Hz)
10 A fast, 6 A slow
ca. 5 VA
1.5 A, cos ϕ 0.2
4 A, cos ϕ 0.4
0.5 A, cos ϕ 0.4
0.5 A, cos ϕ 0.4
0.1 A, cos ϕ 0.4
5A, cos ϕ 0.4
ca. 12 sec.
ca. 12 sec.
ca. 20 sec.
ca. 2-4 sec
40 sec. (TF 802)
10 sec.
ca. 90 sec
side-on viewing
side-on and end-on
viewing
Light sensitivity FZ 711S
> 10 Lux
IRD 1010
side-on or end-on
viewing
UVD 970
end-on viewing
TECHNICAL
DATA base
Weight incl. wiring
0.25 kg
Mounting position
any
Operating
220/240
Protectionvoltage
class
IP44 V (-15..+10%)
Recommended ambient operating 50 Hz (40-60Hz)
Fuse
rating for control and
10 A fast, 6 A slow
temperature
Power
ca.
5 VA
flame consumption
detector
0°C...+60°C
Max.
load per
approved
andoutput
certified according
- to
terminal
3 standards
1.5 A, cos ϕ 0.2
European
- terminal 4
A, 230
cos ϕ 0.4
TF 801.2/TF802.2 4EN
- terminal 5
0.5
cos ϕ 0.4
TF 801/TF802
DINA,4787
- terminal 6
0.5 A, cos ϕ 0.4
- terminal 7
0.1 A, cos ϕ 0.4
total load
5A, cos ϕ 0.4
ca. 12 sec.
1 Pre-purge time
Pre-ignition time
ca. 12 sec.
Satronic TF801- OIL BURNER
CONTROLLER
• Oil burner control
• Plug in base (SA7531001)
• Single stage operation
• FZ 771 / IRD 1010 / UVD 970 Flame
detector
• Pre - purge 12 seconds
• Post ignition time 2 - 5 seconds
• Manual reset from lockout
• 240 volt AC
#SA02001
Satronic TF802- OIL BURNER
CONTROLLER
• Oil burner control
• Plug in base (SA7531001)
• 2 stage operation
• FZ 771 / IRD 1010 / UVD 970 Flame
detector
• Pre - purge 12 seconds
• Post ignition time 2 - 5 seconds
• Manual reset from lockout
• 240 volt AC
#SA02404
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
6.3
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
TF 830.3 / 832.3
Programmed Oil & Gas Burner Controls
A Honeywell Company
y Control
Satronic TF830.3 - OIL BURNER
CONTROLLER
• Oil burner control
• Plug in base (SA7531001)
• Single stage operation
• MZ 770S / UVD 970 Flame detector
• Pre - purge 12 seconds
• Post ignition time 2 - 5 seconds
• Manual reset from lockout
• 240 volt AC
#SA02231
urners up to 30kg/
operations.
D 1010.1
970
r safety control boxes
oil power burner up to
certified according to
20 sec.
n according to EN230
TECHNICAL DATA
Operating voltage
sec.
n according to EN230
Fuse rating
Power consumption
Max. load per output
- terminal 3
- terminal 4
- terminal 5
- terminal 6
- terminal 7
total load
Pre-purge time
Pre-ignition time
Post-ignition time
TF 830.3
TF 832.3
Delay time to oil valve 2
Lockout safety time
Reset time from lockout
Flame detector:
MZ 770 S
Light sensitivity MZ 770 S
IRD 1010.1
UVD 970
Sensor operating current
Weight incl. wiring base
Mounting position
Protection class
Recommended ambient operating
temperature for control and
flame detector
approved and certified according
to European standards
d by a flame resistant,
orporates the thermoated timer, flame check
d by a push button with
A central fixing screw
se. The wiring base and
arrangement, making it
onnection between the
points provides utmost
patible with the TF 730,
utton (item no. 70601)
ifferences to the TF 730
1
220/240 V (-15..+10%)
50 Hz (40-60Hz)
10 A fast, 6 A slow
ca. 5 VA
1.5 A, cos ϕ 0.2
4.0 A, cos ϕ 0.4
0.5 A, cos ϕ 0.4
0.5 A, cos ϕ 0.4
0.1 A, cos ϕ 0.4
5.0 A, cos ϕ 0.4
ca. 12 sec.
ca. 12 sec.
ca. 20 sec.
ca. 2-5 sec
40 sec. (TF 832.3)
10 sec.
ca. 90 sec
side-on and end-on viewing
> 6 Lux
side-on or end-on viewing
end-on viewing
min. 30 µA
0.25 kg
any
IP44
0°C...+60°C
EN 230
Satronic TF832.3 - OIL BURNER
CONTROLLER
• Oil burner control
• Plug in base (SA7531001)
• 2 stage operation
• MZ770S / UVD 970 Flame detector
• Pre - purge 12 seconds
• Post ignition time 2 - 5 seconds
• Manual reset from lockout
• 240 volt AC
#SA02431
OBSOLETE USE #SA0312005
DKO 972 MOD.5 OIL BURNER
CONTROLLER
•
Plug in Base ( SA7531001)
•
2 Stage Operation
•
MZ 770/UVD 970 flame detectors
•
Pre- Purge 15 seconds
•
Safety Time 5 seconds
•
Post Ignition time (afterV1) 7 seconds
•
Delay time to V2 20 seconds.
•
Pre Purge 15 seconds
#SA0312005
6.4
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
Satronic TF834.3 - OIL BURNER
CONTROLLER
• Oil burner control
• Plug in base (SA7531001)
• 2 stage operation
• MZ 770S / UVD 970
Flame detector
• Pre - purge 12 seconds
• Post ignition time 2 - 5 seconds
• Manual reset from lockout
• 240 volt AC
#SA02234
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Satronic DKG 972 MOD 5
• Atmospheric Gas burner control
• Plug in base (SA7531001)
• Pilot / Main gas valve
• Remote reset / Flame failure
indicator
• 2 Stage operation
• Flame failure safety time - 5
seconds
• UV Cell or ionization control
• 240 volt AC
#SA0332005
Satronic DMG 970.MOD03
• Forced draught gas burner control
• Plug in base (SA7531001)
• Pilot / Main gas valve
• Remote reset / Flame
failure indicator
• 2 Stage operation
• Pre-purge - 40 seconds
• Flame failure safety time 3 seconds
• UV Cell or ionization control
• 240 volt AC
#SA0350003
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
6.5
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Satronic MMI 810.1 MOD 43
• Forced draught gas burner control
• Plug in base (SA7531001)
• Pilot / Main gas valve
• Remote reset / Flame failure indicator
• 2 Stage operation
• Pre-purge - 40 seconds
• Flame failure safety time - 3 seconds
• UV Cell or ionization control
• 240 volt AC
#SA0622520
A Honeywell Company
MMI 962.1
Satronic MMG 810.1 MOD 45
• Forced draught gas burner control
• Plug in base (SA7531001)
• Pilot / Main gas valve
• Remote reset / Flame failure indicator
• 2 Stage operation
• Pre-purge - 40 seconds
• Flame failure safety time - 5 seconds
• UV Cell or ionization control
• 240 volt AC
#SA0642620
atic
Satronic MMI 962.1 MOD 43
• Forced draught gas burner control
• Plug in base (SA7531001)
• Pilot / Main gas valve
• Air damper motor terminals
• Remote reset / Flame failure
indicator
• Pre-purge - 40 seconds
• Flame failure safety time - 5
seconds
• UV Cell or ionization control
• 240 volt AC
#SA06256
ts
MMI 962.1 controls
d burners of any
ied according to
ge operation with
with one fuel valve
differentiate the
o the programme
ational standards.
23 can be used
23 or MMI 812.1
6.6
TECHNICAL DATA
Operating voltage
Tel frequency
: 09-636-1401
Differing
Rating fuse
Power consumption
Max. load per output:
•
220 / 240 V (-15... +10%)
50 Hz
Fax:Results
09-636-1525
• sales@systemcontrol.co.nz
in a proportional
deviation of the time
max. 10 A rapid, 6 A slow
10 VA
• www.systemcontrol.co.nz
Satronic MMG 870.1 MOD 65
• Forced draught gas burner control
• Plug in base (SA7531001)
• Pilot / main gas valve
• Remote reset / Flame failure
indicator
• Pre-purge 65 seconds
• Flame failure safety time - 5
seconds
• UV cell or ionization control
• 240 volt AC
#SA0642120
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Satronic TMG 740-3 MOD 43-35
• Forced draught modulating gas
burner control
• Plug in base (SA70205)
• Pilot / Main gas valve
• Air damper motor terminals
• Remote reset / Flame failure
indicator
• Pre-purge - 32 seconds (60 seconds
Mod 63-55)
• Flame failure safety time - 5
seconds
• UVZ 780 Cell / ionization control
• 240 volt AC
#SA08218
(#SA08213, TMG 740-3 Mod 63-55)
Satronic TMO 720-4 Mod 35
• Oil burner control
• Plug in base (SA70201)
• Remote reset / Flame failure
indicator
• Pre-purge - 32 seconds
• Post ignition time - 7.5 seconds
• FZ 771 / IRD 1010 infra red flame
detector
• 240 volt AC
#SA08001
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
6.7
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Programmed Oil & Gas Burner Controls
SIEMENS
Siemens LFL1.635 CONTROL
Forced draught modulating
gas burner control
• Plug in base (Z3013)
• Pilot / Main gas valves
• Remote reset / Flame failure
indicator
• Pre-purge 60 seconds, (30 seconds
LFL1.335)
• QRA UV cell / ionization control
• Flame failure safety time - 5
seconds
• Air pressure proving / Fan control
• Fault indication
• 240 or 110 volt AC
#SBLFL1.635 (#SBLFL1.335)
Siemens LGB 21 350 A27 CONTROL
• Forced draught / atmospheric gas /
oil burner control
• Plug in base (C16800)
• Pilot / Main gas valves
• Single or two stage operation
• Remote reset / Flame failure
indicator
• Pre-purge 30 seconds
• QRA UV cell / ionization control
• Air pressure proving / Fan control
• Fault indication
• 240 volt AC
#SBLGB21.350A27
If used in atmospheric application then
AGK 25 (Z3064) PTC resistor must be
fitted across terminal 3 and neutral
6.8
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
Siemens LOA 24.171B27
• Atmospheric Gas burner control
• Plug in base (Z3061)
• Remote reset / Flame failure
indicator
• 2 Stage operation
• Post ignition time 10 seconds
• QRB flame detector
• 240 volt AC
#SBLOA24.171B27
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
TEST EQUIPMENT
Siemens LFL Test Box
LFL Test box for commisioning
•
Run/Stop switch
•
Bypass/measure switch for flame current testing
•
2 x terminal plugs for meter connection.
#Z3010TESTB
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
6.9
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Kromschroder IFW 15 CONTROL
• Plug in base
• UV Cell - Series UVS* or Flame
Rod sensing
• Amber light - Flame on
• Electrical open contact
• Electrical closed contact
• 240 or 110 volt AC
• Use in conjunction with
KR28086, IFS 110-IM control
#KR28162
Kromschroder IFS 110-IM CONTROL
• Forced draught gas burner control
• Plug in base
• Pilot / Main Gas Valves
• Remote reset / Flame Failure
Indicator
• Pre-Purge 5 seconds
• Flame Failure Safety Time 5 seconds
• Single electrode / UV Cell
• 110/240 volt AC
#KR28086
Semi Automatic Burner Controls
Brahma RE3 CONTROL
• Plug in base
• UV Cell or Flame Rod sensing
• Green light - Power on
• Red light - Flame on
• Two electrical change-over contacts
• 240 volt AC
#B1115
6.10
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
Satronic FFW 930.1 CONTROL
• Plug in base
• UV Cell or Flame Rod sensing
• Flame on indication
• Two electrical change-over contacts
• 240 volt AC
#SA0690320
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Siemens LFE 10 CONTROL
• Plug in base
• UV Cell - Series QRA*
or Flame Rod sensing
• Electrical open contact
• Electrical closed contact
• 240 volt AC
#Z3050
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz
6.11
Section 6
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Flame Detectors
Siemens QRA4U
• Flame detector (Oil & Gas)
#Z3018
Siemens QRA2
UV Detector (for gas)
#Z3030
Siemens RAR9
Photo cell (for oil)
#Z3064
Siemens QRB 1
Photo cell (for oil)
#Z3032
Satronic MZ 770 S
Photo cell (for oil) Requires SA59101,
mounting flange & SA7225001, two
wire cable
#SA50001
Satronic UVZ 780
• UV Cell (for gas)
#SA18812 Blue Lo Sensitivity
#SA18813 Red Hi Sensitivity
#SA1881w White Medium Sensitivity
Brahma UV1
UV Detector (for gas)
#B1190
6.12
Tel : 09-636-1401 • Fax: 09-636-1525 • sales@systemcontrol.co.nz • www.systemcontrol.co.nz