MODEL ENERZONE SOLUTION 2.5ZC

Installation Instructions

This installation manual will help you obtain a safe, efficient, dependable installation for your fireplace and chimney system. Please read and understand these installation instructions before beginning your installation.

CAUTION: Do not attempt to modify or alter the construction of the fireplace or its components. Any modification or alteration of construction may void the warranty, listings and approvals of this system. In that case, Stove Builder International (SBI) will not be responsible for damages. Install the fireplace only as described in these instructions.

PLEASE RETAIN THIS MANUAL

FOR FUTURE REFERENCE

Listed to standards ULC-S610 and UL-127

Manufactured by:

Stove Builder International Inc.

STOVE BUILDER INTERNATIONAL INC.

1700 Leon-Harmel Street, Quebec City, Quebec, Canada, G1N 4R9 Tel.: (418) 527-3060

45181 Printed in Canada

TABLE OF CONTENTS

Page

1. SAFETY RULES FOR OPERATING YOUR FIREPLACE ....................................... 1

2. CERTIFICATION LABEL ......................................................................................... 3

3. THE FIREPLACE ..................................................................................................... 4

3.1 INTRODUCTION .................................................................................................................. 4

3.2 OPERATING THE ENERZONE SOLUTION 2.5ZC ....................................................... 5

3.2.2 The use of manufactured logs .......................................................................................... 5

3.2.4 Building a Fire .................................................................................................................. 6

3.2.5 Maintaining the Fire ......................................................................................................... 6

Causes and Troubleshooting .......................................................................... 9

3.3 MAINTAINING YOUR ENERZONE SOLUTION 2.5ZC ............................................. 11

3.3.1 Creosote – Formation and need for removal .................................................................. 11

3.3.3 Top Baffle Removal Prior to Cleaning the Chimney ..................................................... 11

3.3.4 Dealing with a Chimney Fire ........................................................................................ 12

3.3.5 Plated Finish Maintenance ............................................................................................. 12

3.3.6 Disposal of Ashes ........................................................................................................... 13

3.3.8 Glass Care – Replacement ............................................................................................. 13

3.3.9 Glass Care – Cleaning .................................................................................................... 13

3.4 FIREPLACE INSTALLATION ......................................................................................... 15

3.4.1 Locating the ENERZONE SOLUTION 2.5ZC ............................................................. 15

3.4.2 Heart Extension Requirements ....................................................................................... 16

3.4.3 Framing, Facing, Mantel, and Combustible Shelf ......................................................... 16

3.5 HOT AIR DUCTING INSTALLATION ........................................................................... 21

3.5.1 Gravity ..................................................................................................................... 21

3.5.2 Central Forced Air Kit (Not tested under EPA certification) ........................................ 23

3.6 FRESH AIR KIT (Optional) ............................................................................................... 25

3.6.1 Outside .................................................................................................. 25

3.7 DOOR OVERLAY INSTALLATION ............................................................................... 26

4. THE CHIMNEY ....................................................................................................... 27

4.1 CHIMNEY INSTALLATION NOTES .............................................................................. 27

4.2 CHIMNEY INSTALLATION INSTRUCTIONS ............................................................. 28

4.3 OFFSET CHIMNEY INSTALLATION ............................................................................ 31

4.4 ANGLED WALL RADIATION SHIELD ......................................................................... 35

4.5 CHIMNEY SUPPORT INSTALLATION ......................................................................... 36

4.6 CHIMNEY CHASE AND MULTIPLE TERMINATIONS ............................................ 36

4.7 INSTALLATION INSTRUCTIONS FOR MASONRY APPLICATION ...................... 38

5. OPTIONS ............................................................................................................... 39

6. APPENDIX ............................................................................................................. 40

7. ENERZONE LIMITED LIFETIME WARRANTY ..................................................... 42 ii

1. SAFETY RULES FOR OPERATING YOUR

FIREPLACE

• Use only an Enerzone glass door, specifically designed for the model Enerzone Solution

2.5ZC.

• When cleaning the fireplace, the ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be placed on a non-combustible floor or on the ground outside the house, pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be retained in the closed container until all cinders have thoroughly cooled.

CAUTION: NEVER USE GASOLINE, KEROSENE, CHARCOAL LIGHTER

FLUID OR SIMILAR LIQUIDS TO START OR REKINDLE A FIRE IN

THIS FIREPLACE. KEEP ALL SUCH LIQUIDS WELL AWAY FROM

THE FIREPLACE AT ALL TIMES.

CAUTION: KEEP COMBUSTIBLE MATERIALS AT LEAST 48 INCHES AWAY

FROM THE FRONT OF THE FIREPLACE OPENING.

CAUTION: NEVER LEAVE CHILDREN UNATTENDED WHEN THERE IS A

FIRE BURNING IN THE FIREPLACE.

CAUTION: NEVER USE GRATE OR ELEVATE FIRE. BUILD WOOD FIRE

DIRECTLY ON HEARTH.

CAUTION: DO NOT USE A FIREPLACE INSERT AND OTHER PRODUCTS NOT

SPECIFIED FOR USE WITH THIS FIREPLACE.

WARNING: THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED

OR VENTED GAS LOG SET. TO REDUCE RISK OF FIRE OR

INJURY, DO NOT INSTALL AN UNVENTED GAS LOG SET INTO

THIS FIREPLACE.

WARNING: DO NOT USE MATERIALS OTHER THAN THOSE LISTED IN THE

REPLACEMENT PARTS SECTION DURING INSTALLATION AS

THEY MAY BE SAFETY HAZARDS, AND A FIRE COULD RESULT.

1

PLEASE NOTE THAT THE PICTURES SHOWN IN THIS

MANUAL ARE GENERIC AND MAY NOT MATCH

EXACTLY THE LOOK OF YOUR FIREPLACE.

REGISTER YOU WARRANTY ONLINE

To receive full warranty coverage, you will need to show evidence of the date you purchased your unit. Keep your sales invoice. We also recommend that you register your warranty online at www.enerzone-intl.com

Registering your warranty online will help us track rapidly the information we need

on your unit.

2

2. CERTIFICATION LABEL

3

3.1 INTRODUCTION

The ENERZONE SOLUTION 2.5ZC fireplace is an energy efficient, heat circulating, close combustion fireplace. You will receive a lifetime of comfort and enjoyment from your fireplace provided it is installed, maintained and operated properly.

• Please read these instructions and retain this manual for future reference.

• Before beginning the fireplace installation, consult the local authorities to obtain your building permit and check your local building codes. Install the fireplace only as described in these instructions and using only components from the manufacturers listed in table 2.

• The ENERZONE SOLUTION 2.5ZC is not intended for use with a gas log. Failure to follow these instructions will void the certification and the warranty of the fireplace and may result in an unsafe installation.

• This heating unit must serve as a supplementary heat source. An alternative heat source should be available in the home if needed. The manufacturer cannot be responsible for additional heating costs associated with the use of an alternative heat source. It is highly recommended that the user buys this product from a retailer who can provide installation and maintenance advices.

3.1.1 Parts Required

• Fireplace model ENERZONE SOLUTION 2.5ZC

• Insulated chimney made by the manufacturers listed in table 2, with the corresponding specifications :

− Chimney lengths

− Elbows (where necessary)

− Associated components as per these installation instructions.

3.1.2 Additional Equipment (optional)

• Forced air kit

• Gravity venting system

• Outside air kit

• Spark screen

4

3.2 OPERATING THE ENERZONE SOLUTION 2.5ZC

3.2.1 Fuel

The ENERZONE SOLUTION 2.5ZC is designed to work best when fuelled with seasoned cordwood. Use solid wood or processed solid fuel firelogs only. Hardwoods are preferred to softwoods since the energy content of wood is relative to its density. Hardwoods will result in a longer burning fire and less frequent refuelling. A moisture content of 15% to 20%

(seasoned) is recommended. Wood that has been cut and split and let to dry under a cover for a period of one year will usually meet that criteria. Excessively wet wood will be difficult to burn and will result in lower efficiency, increased creosoting and deposits on the glass and in the chimney. Excessively dry wood will burn well but will also have higher emissions and shorter burning time.

Do not burn scrap or garbage, treated wood or wood such as driftwood from the ocean which has been exposed to salt or other chemicals. Salt or chemicals can corrode the firebox and chimney. Do not burn large amounts of paper, cardboard, Christmas tree branches or building construction materials. Intense firing with these materials may overheat the fireplace, causing damage to the unit, a fire or even possibly igniting a chimney fire if the chimney is creosoted.

C AUTION : D O NOT OVER FIRE THIS HEATER O VER FIRING CAN RESULT IN A SAFETY HAZARD AND

CAN PERMANENTLY DAMAGE THE FIREPLACE AND CHIMNEY .

3.2.2 The use of manufactured logs

There are numerous types of manufactured logs sold on the market. You must be very careful with this type of product. Many brands of manufactured logs contain chemical additives. DO NOT BURN ANY MANUFACTURED LOGS CONTAINING CHEMICAL

ADDITIVES. IF YOU DO, YOU MAY OVERHEAT YOUR FIREPLACE, THEREFORE

CAUSING A FIRE HAZARD AND VOIDING YOUR WARRANTY. Logs containing chemical additives burn a lot hotter and were designed for decorative fireplaces. Decorative fireplaces generally have larger, cooler, and less air-tight fireboxes. Your ENERZONE

SOLUTION 2.5ZC, on the other hand, has a smaller, completely sealed firebox which attains much higher temperatures. It is therefore not designed to support excessive heat caused by the addition of chemicals in manufactured logs. Manufactured logs made of 100% wood residues do not pose a threat to your fireplace. However, they must be used carefully.

Manufactured logs typically release a much larger heat output over a short period of time.

Therefore, you cannot place a large quantity of such logs into your fireplace. Start with one log, and gradually increase the load. Never put more than 4 logs. The logs should be of an average size and not exceed 8 inches in diameter.

WARNING: Do not poke or stir the logs while they are burning. Use only firelogs that have been evaluated for the application in fireplace and refer to firelog warnings and caution markings on packaging prior to use.

5

3.2.3 First Fires

The fresh paint on your fireplace needs to be cured to preserve its quality. Once the fuel load is properly ignited, only burn small fires in your fireplace for the first four hours of operation.

Never open the air control more than necessary to achieve a medium burn rate. Make sure that there is enough air circulation while curing the stove. Open one or more windows. The odours can be smelled during the 3 or 4 first fires.

3.2.4 Building a Fire

To start a fire, place several crumpled up balls of newspaper in the firebox behind the andiron.

Place small dry pieces of kindling on top of the paper, criss-crossing the kindling so that there are air spaces in between. Keep the fuel far back enough so that air can get underneath. Open the air controls fully and light the newspaper. Once the newspaper and the kindling is well ignited, close the door. Once the kindling fire is well established, cordwood can be added.

(See Primary Air Combustion Control section for proper operation of the air controls.). Make sure that cordwood is always behind the andiron.

The unit will burn best with 2-3 pieces of cordwood spaced 1 to 2 inches apart and allowing air to get under the fuel. Criss-crossing or arranging the fuel so that air can get underneath, will help the fire to get started easily. The unit should be operated with the air control fully open long enough to get the cordwood well ignited

3.2.5 Maintaining the Fire

Once the wood has been consumed (or partially consumed) and you have obtained a good bed of embers, you should reload the unit. In order to do so, open the air control to its maximum for approximately 15 seconds prior to opening the fireplace door. Then, proceed by opening the door very slowly. Open it by 2" to 4" (52 to 104 mm) for 10 seconds before opening it completely. This procedure will increase the draft and thus eliminate the smoke which is stagnant in a state of slow combustion in the fireplace. Then, bring the red embers to the front of the stove and reload the unit.

Your ENERZONE SOLUTION 2.5ZC fireplace will work best if a thick bed of hot embers is maintained in the bottom of the firebox, and a minimum of two large pieces of seasoned fuel are added. Combustion efficiency is largely related to establishing a hot ember bed, and hot firebox temperatures. The quicker the fireplace and chimney (flue) get up to normal operating temperatures, the better. A small intense fire is preferred to a large smouldering fire, both to improve combustion efficiency and to reduce the amount of creosote build-up. The best performance will be obtained by adding relatively small amounts of fuel to a well established ember bed, and then operating with the air inlet control open long enough to achieve a hot fire. Use a poker to make an air channel in the embers below the wood. This will allow air to flow under the wood for a more efficient burn. Once you have reached the desired temperature, the primary air can be set to a medium setting. You know you have reached the desired temperature when, closing the primary air control, you can see a flame at the top of

6

the firebox. The benefit of this technique will be cleaner glass, less creosoting, greater efficiency and the most pleasing fire for your enjoyment.

In order to achieve an optimum efficiency from your unit, we suggest that you operate it with the air control completely closed. Make sure that you have a good fire going and an adequate ember bed before you completely close the air control. Closing the air control too soon will lower combustion efficiency and may cause the fire to die out. The addition of a blower (if not already included) is highly recommended to maximize your unit’s efficiency.

7

3.2.6 Primary Air

There is no flue damper in the ENERZONE SOLUTION 2.5ZC. As in common with air tight stoves, the combustion air control sets the flow of air entering the firebox. This allows for a more precise control of the fire. The combustion air control is located below the door on the right side. The main source of air (primary air) entering the firebox can be diminished by moving the air combustion control from right to left. The primary air is fully opened when the air control is completely moved to the right. The combustion air control should be in the closed position (primary air) when the fireplace is not in use. This will minimize air leakage up the chimney. The combustion air control should be opened before opening the door to minimize the possibility of back draft coming into the room.

SLOW

MEDIUM

ACCELERATED

Figure 1

3.2.7 Combustion Settings

Accelerated Combustion

The maximum heat output for the ENERZONE SOLUTION 2.5ZC is achieved by burning with the door closed and the combustion air opened. By this method, the ENERZONE

SOLUTION 2.5ZC can produce up to 75,000 BTU of heat per hour. However, it will be necessary to reload with wood every one or two hours. This is the least efficient method of burning the ENERZONE SOLUTION 2.5ZC. Use caution when firing with the combustion air control wide open. Only burn cordwood in this manner. Small dry pieces of softwood and construction scraps will burn very intensely using this method and may damage the firebox.

8

Medium Combustion

This is the recommended mode of operating the ENERZONE SOLUTION 2.5ZC and should be the one normally used since it will deposit the least amount of creosote on the glass and in the chimney. The combustion air control must be ¾ closed. The precise setting will depend on many factors, including chimney length and the moisture content of the wood.

For instance, a long chimney will necessitate closing the combustion air control. To obtain the proper combustion, close the combustion air control completely, then open it about ¼" to ½".

Three medium size pieces of wood should be burning on a bed of hot coals. The heat output will be approximately 35,000 BTU per hour and the loading time will be about every 3-4 hours. Softwoods may be burned using this method but the time will be substantially reduced.

Slow Combustion

When the air combustion control is completely closed, the fireplace is in a slow combustion phase. If the heart is hot enough, slow combustion will not stop the fire, but there will be a noticeable change in the flame pattern. The flames will be slow and may appear dirty if the wood is too wet (moisture content of 20% and more). Do not allow the wood to burn without flame, since this will produce excessive creosote in the unit.

Creosote may accumulate on the glass door. This method of burning should be used only after operating the ENERZONE SOLUTION 2.5ZC with the air control opened to produce a hot fire for about an hour or at medium pace for at least 2 hours. Slow combustion can be used at night in order to reduce the heat output and to prolong the burn. The refuelling interval time will be between 6-8 hours.

To reduce the likelihood of smoking when opening the door, set the combustion air controls to the right (accelerated) before opening the door. Your fireplace has been designed and tested to provide smoke free operation. Occasionally, there may be a small amount of smoking upon lighting the fire, until the chimney heats up but this should not continue. If the fireplace continues to smoke it is probably for one of the following reasons:

A. Negative pressure in the house

As the fire burns, air goes up the chimney. This air must be replaced through leakage into the house or through the fresh air kit. When operating the ENERZONE SOLUTION

2.5ZC, open a nearby window temporarily to check if there is adequate air supply replacement. If opening a window solves the problem, the house is under negative pressure.

B. Fans operating (e.g. : range hood)

These fans draw air out of the house and may actually cause a negative pressure in the house. Turn off all fans and open a nearby window to determine if this is the cause of the problem.

9

C. Wet wood

Wet or tarred wood will smoulder and smoke instead of burning properly.

D. Dirty or blocked chimney

Check to make sure the chimney is clear and clean.

E. Chimney not long enough

The minimum system height is 15 feet (4.6m). The chimney must extend at least 3 feet

(915 mm) above its point of contact with the roof and at least 2 feet (0.6 m) higher than any roof or wall within 10 feet (3 m) of it. When installed with offsets, the minimum system height is 15 feet (4.6 m) to 17 feet (5.2 m) as per Table 1. Additional height will increase draught and will decrease the tendency to smoke. If only the minimum chimney height is installed, operating conditions must be optimal (interior chimney, minimum height of 18” before any offset, etc.).

F. Poor chimney draft

With no fire, there should be sufficient draught to exhaust cigarette smoke introduced under the baffle. Chimneys installed against an outside wall without protection may generate back draught problems which will cause start-up problems. To prevent this, open a nearby window, roll up a piece of paper and light it. Then, hold it in the upper part of the firebox to warm up the chimney. Wait until the draught is sufficient, then start the fire.

IMPORTANT NOTES

A. Do not block the hot air vents to the fireplace as this will cause the fireplace to overheat.

B. Never start a fire using gasoline, kerosene, charcoal lighter fluid or any other combustible liquid.

C. Do not burn coal. The sulphur in coal will corrode the firebox.

D. Do not burn driftwood which has been in the ocean or salt water. The salt will corrode the firebox and chimney.

E. Do not abuse the unit by burning paper, or cardboard or construction material such as pressed wood, plywood or lumber.

F. Do not allow the wood to smoulder or burn without flame, since this will produce excessive creosote in the unit.

10

3.3 MAINTAINING YOUR ENERZONE SOLUTION 2.5ZC

3.3.1 Creosote – Formation and need for removal

When wood is burned slowly without a flame, it produces tar and other organic vapours which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited this creosote makes an extremely hot fire.

The chimney shall be inspected at least twice a year during the heating season to determine when a creosote build-up has occurred.

When creosote has accumulated it shall be removed to reduce the risk of a chimney fire.

3.2.2 Chimney Maintenance

Regular chimney inspection and maintenance combined with proper operation will prevent chimney fires. Keep your chimney clean. Do not allow more than 1/16

″ creosote build up in your chimney. The amount of creosote will depend on variables such as frequency of use and type of fire. We recommend that you:

A. Initially inspect the chimney system weekly. From this, you will learn how often it will be necessary to clean your chimney.

B. Have your chimney cleaned by a qualified chimney sweep. If you wish to clean it yourself, we recommend using a stiff plastic or non-metallic brush. If a metal brush is used, its size should be slightly smaller than the flue to avoid damaging the chimney.

Do not use a brush that will scratch the stainless steel interior of the chimney.

C. Do not expect chemical cleaners to keep your chimney clean. The rain cap can be removed for inspection and/or cleaning of the chimney.

3.3.3 Top Baffle Removal Prior to Cleaning the Chimney

Before starting to clean your chimney, we recommend that you remove the top baffle to avoid creosote dust collection at the top of the baffle. Follow these steps to set the top baffle out of the way:

1. Remove the front air tube by pulling out the cutter pin on the side of the tube. They are located at the top, underneath the baffle.

2. Lift the baffle assembly and slide it out of the fireplace. You now have access to the chimney.

11

FONT AIR

TUBE

Figure 2

3.3.4 Dealing with a Chimney Fire

Regular chimney maintenance and inspection can prevent chimney fires. If you have a chimney fire, follow these steps:

1. Close the fireplace door and the combustion air controls;

2. Alert your family of the possible danger;

3. If you require assistance, alert your fire department;

4. If possible, use a dry chemical fire extinguisher, baking soda or sand to control the fire.

Do not use water as it may cause a dangerous steam explosion;

5. Check outside to ensure that sparks and hot embers coming out of the chimney are not igniting the roof;

6. Do not use the fireplace again until your chimney and fireplace have been inspected by a qualified chimney sweep or a Fire Department Inspector;

3.3.5 Plated Finish Maintenance

Use a glass cleaner and a soft cloth to polish the plated finish on the door frame. Do not use abrasives such as steel wool, steel pads or an abrasive polish for they may scratch the finish.

12

3.3.6 Disposal of Ashes

Do not attempt to clean the fireplace when the unit is hot. Ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be placed on a noncombustible floor or on the ground, well away from combustible materials pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container until all cinders have thoroughly cooled.

3.3.7 Refractory Replacement

The intense heat of the fire will normally cause hairline cracks in the refractory. These cracks can be minimized by proper curing as described in “First Fires”. They will not normally diminish the effectiveness of the refractory. If large cracks develop, then the refractory should be replaced. To replace the refractory bricks, follow these steps:

1. Remove the andiron.

2. Remove the left side bricks

3. Remove the right side bricks

4. Remove the back bricks

5. Remove the c-cast block

6. Remove the two floor bricks

To install the new bricks, follow the above steps in reverse.

Figure 3

3.3.8 Glass Care – Replacement

The glass used for the Enerzone Solution 2.5ZC is a high temperature ceramic glass (1400º

F). Do not abuse the glass door by striking or slamming shut. Do not use the stove if the glass is broken. If the glass breaks, it must be replaced with an identical ceramic glass. Tempered glass or ordinary glass will now withstand the high temperatures of the ENERZONE

SOLUTION 2.5ZC. Replacement glass should be purchased from a Enerzone dealer (see

“Replacement Parts”, in Section 7 – APPENDIX). Do not operate the unit with a cracked or broken glass.

3.3.9 Glass Care – Cleaning

The ENERZONE SOLUTION 2.5ZC is designed to keep the glass clean under normal operating conditions. If the ENERZONE SOLUTION 2.5ZC is operated continuously with the combustion air controls closed, the glass will tend to get dirty unless the fuel, firebox and

13

glass are maintained at hot. To clean the glass, there are a number of specially designed cleaners. Your authorized Enerzone dealer can recommend a suitable cleaner which is available in your area. Regular household glass cleaners will not clean creosote. Do not use abrasives such as steel pads, steel wool or oven cleaner as they will scratch the glass. Only wash when the stove is cold.

3.3.10 Gasket Replacement

Remove the doors from the unit and lay them on a clean, unabrasive surface. To replace the gasket around the door frame, first remove the old gasket and adhesive. Make sure that the surface is totally clean before applying new adhesive (a high temperature silicone caulking rated for at least 500ºF, 260ºC, is suitable) or adhesion problems may result. Apply the adhesive inside the door groove (gasket channel) and install the new gasket with a gentle pressure. Let dry for at least 24 hours. To replace the glass gasket, simply remove the glass retainers holding the glass to the door frame. Remove the glass and peel off the gasket surrounding it. Replace it by a new, self-adhesive glass gasket. The proper replacement gaskets are available from your Enerzone dealer in the following dimensions:

Gasket Length Dimensions

Around each glass 51 ½" (131 cm) U SHAPE

On each door frame

Along the door joint

41 ¼" (105 cm)

14" (36 cm)

Flat ¼" x ½"

Flat ¼" x ½"

14

3.4.1 Locating the ENERZONE SOLUTION 2.5ZC

A. The best location to install your fireplace is determined by considering the location of windows, doors, and the traffic flow in the room where the fireplace is located, allowing space in front of the unit for the heart extension and the mantel, and taking into consideration the location of the hot air ducts (optional), outside air kit and chimney. If possible, you should choose a location where the chimney will pass through the house without cutting floor or roof rafters.

B. Usually, no additional floor support is needed for the fireplace. The adequacy of the floor can be checked by first estimating the weight of the fireplace system. Weights are given in the appendix. Next, measure the area occupied by the fireplace which is normally 36.75"

× 26". Note the floor construction and consult your local building code to determine if additional support is needed.

C. The ENERZONE SOLUTION 2.5ZC may be installed directly on the floor or on a raised base (for proper guidelines, refer to “Heart Extension Requirements”) and a minimum of 7 feet (2.15 m) measured from the base of the appliance to the ceiling is required. The hearth extension is to be installed only as illustrated in the drawing below.

Spacers must be installed

15

3.4.2 Heart Extension Requirements

The ENERZONE SOLUTION 2.5ZC may be installed directly on a combustible floor; however, the combustible floor in front of the fireplace must be covered with a noncombustible material (tile, marble, stone, etc.). The hearth extension floor area shall extend at least 16" in front and at least 8" on each side of the fireplace opening. (see figure 4). T he floor protector in front of the fireplace must have a R value of 1.53 or greater.

Convert specification to R-value: k-factor is given with a required thickness (T) in inches: R=1/k x T

C-factor is given: R=1/C

AREA WHERE

WOOD MANTEL

CAN BE INSTALLED

COMBUSTIBLE

SHELF

6.000"

17" MIN.

50" MIN.

3"

45°

41 3/4"

16"

NON COMBUSTIBLE

MATERIAL

Figure 4

3.4.3 Framing, Facing, Mantel, and Combustible Shelf

The construction of the framing, facing, and mantel must be in accordance with the standards and the following illustrations (figures 4 to 11):

A. Frame the fireplace using 2" × 3" or heavier lumber.

B. WARNING: Combustible framing material cannot be used in the space directly above the fireplace, except for the studs above the facing that support the facing material and mantel. This area must remain empty for a height of 7′ (2,15 m) measured from the base of the appliance.

C. Frame the fireplace with vertical studs at the sides of the fireplace running from floor to ceiling (see figure 6). Position the studs back from the front edge of the fireplace, a space the thickness of the facing material so that the facing can be installed flush with the

16

fireplace facing (within limitations of figure 11). Frame headers between the vertical studs only as follows:

− Place 2" × 3" or 2" × 4" headers, only along the upper part of the front, side and back faces. Do not put wood or any combustible material within the area above the fireplace except on the front facing.

− Place headers only as required to support the facing and mantel.

D. WARNING: DO NOT PACK REQUIRED AIR SPACES WITH INSULATION

OR OTHER MATERIALS.

THE FIREPLACE MUST NOT BE IN CONTACT WITH ANY INSULATION OR

LOOSE FILLING MATERIAL. COVER THE INSULATION WITH GYPROC

PANELS AROUND THE FIREPLACE.

36

3

4

"

36"

19 13/16" 10

1

4

"

2"

53 23/32"

37 31/32"

22

7

8

"

8

3

32

"

12

13

32

"

24

1

32

"

26"

20"

1

1

2

"

75 31/32"

Figure 5 Figure 7

7' MIN.

43 3/16"

24 1/32"

36"

36

3

4

"

Figure 6 Figure 8

INSULATED CHASE CONSTRUCTION

38"

43

1

4

"

17

ROOF SUPPORT

STORM COLLAR

FLASHING

FLOOR /

CEILING WALL

ATTIC

RADIATION

SHIELD

Spacers must be installed

7 MIN.

FIRESTOP

FOYER

MUST HAVE THE SAME FIRESTOPPING RESISTANCE

AS ADJACENT WALL.

MUST HAVE THE SAME INSULATION AS ADJACENT

CEILING.

FOLLOW LOCAL RULES REGARDING FRAMING

CONSTRUCTION.

NOTE:

FLOOR AND WALL BELOW THE ATTIC

MUST BE INSULATED USING THE SAME

INSULATION.

Spacers must be installed

GYPROC

2" X 4"

1/2" PLYWOOD

Figure 9

Facing

1. Combustible material may be installed flush with the fireplace decorative frame.

Combustible material may not project in front of and onto the fireplace decorative frame (figure 11).

2. Non-combustible materials such as brick, stone or ceramic tile may project in front of and onto the fireplace decorative frame.

18

Combustible shelf

Any combustible shelf must be installed at least 50" (127 cm) above the base of the fireplace if the depth of the shelf is 6" or less. If the depth of the shelf is more that 6" but less that 12", the shelf must be installed at least 52" (132 cm) from the base of the fireplace (see figure 10).

12

6"

50"

52

COMBUSTIBLE

FACING

Figure 10

1/2" GYPROC

2" X 4"

Figure 11

19

3.4.4 Blower connection

The fan will come on as soon as the fireplace reaches its minimum start temperature. Have the wiring installed by a qualified electrician. Connect the wires from the power outlet to the terminal block, making sure that the white wire matches the white wire on the terminal.

Connect the black wire with the black wire of the terminal block. The ground(green or skinned wire) must be attached to the fireplace metal frame.

BLACK

BLACK

BLACK WHITE

GREEN/GROUND

BLACK

THERMODISC

BLOWER

SWITCH

BLACK

RHEOSTAT

BLACK

WHITE

TERMINAL

BLACK

WHITE

GREEN/

GROUND

GREEN/

GROUND

BLOWER

BLOWER

20

3.5 HOT AIR DUCTING INSTALLATION

Different hot air ducting systems can be installed with the ENERZONE SOLUTION 2.5ZC:

− Gravity kit

− Forced air kit

3.5.1 Gravity Kit

The kit includes:

− 2 x hot air outlets (grilles and frames);

− 2 x 90 o

elbows with brackets;

− 1 deflector.

The gravity kit allows you to block the upper fireplace louver. To do so, follow the steps below: a) Remove the upper louver from the fireplace; b) Install the deflector as shown on figure 12; c) Put the upper louver back into place.

FRAME

DEFLECTOR

GRILLE

UPPER

LOUVER

Figure 12 Figure 13

The safety rules for hot air ducting gravity kit installations are the following:

Minimum height* 68" (1.7 m)

Maximum length 10' (3m) (see figure 14)

*The minimum height of the hot air ducting must be measured from the floor to the top of the hot air grilles.

The hot air grilles can be installed in the same room as the fireplace, or one or both of the grilles can be installed in adjacent or upper rooms. Installing the ducts at different elevations will tend to exhaust more heat out of the higher grilles (figure 15).

21

FIRESTO P

10' MAX.

13" X 13"

FIRESTO P

10' MAX.

Figure 14

RAIN CAP

COLLAR

FLASHING

ROOF SUPPORT

ATTIC RADIATION

SHIELD

FIRESTOP

FACING

Figure 15

The duct system must be installed respecting the following:

1. Remove the plates closing up the 8" dia. holes on top of the fireplace. Then, cut the insulation in order to obtain two 8" dia. openings. Insert the ducting into each opening and fix it in place using the 6 steel brackets supplied (3 for each duct).

2. Maintain at least a 2" (50 mm) clearance between the ducts and the firestop; the required hole size for the hot air grilles (outlet) is 8¼" × 8¼" (210 mm × 210 mm).

22

3. The maximum number of elbows in a run of duct is two.

4. Maintain at least 10" (254 mm) clearance from the outlet grille framing to a combustible ceiling, side wall or mantel.

5. When passing through a combustible wall or floor, a firestop must be installed at the wall or floor penetration. The hole size must be in accordance with the duct manufacturer’s instructions.

6. Do not connect the hot air ducts to a central heating system. Malfunction of the heating system’s fan will cause the fireplace to overheat.

8. Do not use insulated flexible ducts as they may overheat.

9. Do not use tees or any other components than the ones specifically listed here.

10. All ducts must extend upwards or horizontally. Never route the ducting downwards.

11. The hot air outlet grilles must be installed with the louvers pointing downwards in order to prevent overheating adjacent ceilings.

12. Always install the two outlet grilles when using the hot air outlet kit and blocking the upper louver of the fireplace.

3.5.2 Central Forced Air Kit (Not tested under EPA certification)

The knock-outs provided on the back and on the sides of the ENERZONE SOLUTION 2.5ZC allow the connection of insulated flexible pipe which enables you to heat adjacent rooms up to

50 feet from the fireplace (see figure 18).

The ducting system must be installed as described below:

A) Remove the knock outs at the back and/or the side of the fireplace and cut the insulation around the hole. Fix the adapter into place with screws. You can use more than one outlet on the fireplace (figure 16);

B) Attach the 5

″ flexible pipe, using the collars provided. Important: Make sure that the plastic wrapping around the flexible pipe is not in contact with the fireplace;

C) Attach the flexible pipe to the fan’s air inlet using the collars provided (figure 17);

D) Attach a flexible pipe to the fan’s air outlet and route the flexible pipe to the chosen location. The ducting system can be installed either in an upper room or in a lower room;

E) At that point, the flexible pipe can be attached to any air distribution grille.

F) Make the electrical connections to the PC Board as explained with the forced air kit owner’s manual.

23

Since the forced air kit requires electricity, make sure that the connections to the fan have been made according to the local codes and comply with their requirements (see instruction provided with the kit).

INSULATION 5"Ø FLEX

INSULATED

FLEX PIPE

ADAPTER ALUMINUM

TAPE

COLLAR

FAN

Figure 17

ROOM

Figure 16

FAN

FAN

BASEMENT

Figure 18

24

During operation, the fireplace requires fresh air for combustion and draws air out of the house. It may starve other fuel burning appliances such as gas or oil furnaces. As well, exhaust fans may compete for air, causing negative pressure in the house, resulting in smoke entering the house from the fireplace. This situation is aggravated in modern airtight houses.

To overcome this problem, we strongly recommend that you install fresh air kit. Check with

local authorities having jurisdiction in your area, it may be mandatory.

3.6.1 Outside Air Installation

The fresh air kit may be installed according to the following requirements:

A) Insulated duct length should be sufficient to avoid condensation.

B) The outside wall termination must not be installed more than 10 ft. (3 m) above the base of the fireplace.

C) The fresh air must come from outside the house. The air intake must not draw air from the attic, from the basement, or from a garage.

D) The outside wall termination should be installed where it is not likely to be blocked by snow or exposed to extreme wind and away from automobile exhaust fumes, gas meter and other vents.

E) The outside termination may be installed above or below floor level.

F) If more fresh air is needed (airtight house or conduit exceeding 10 ft or 3 m), two intakes may be installed, providing twice the quantity of incoming fresh air; you may also increase both conduits to 4 inches, with the use of a 3 to 4 inch adaptor, again increasing substantially the quantity of incoming fresh air.

The fresh air kit contains the following components:

1- A 3" flex adapter; 4- Plate for room air intake;

2- 2 pipe clamps;

3- An outside air register;

5- 6 screws;

6- 3” to 4” adaptor.

To complete the fresh air kit installation, you will need a 3" insulated flexible pipe. Use the length required for your installation while respecting the maximum length of 10 ft (3 m).

Make a 3 1/4" (83 mm) hole in the outside wall of the house at the chosen location. From outside, place the outside air register in the hole (open side down) and fasten the register to the wall, with screws as shown (see figure 6). Place the insulated pipe over the register tube and over the fireplace’s outside air connector (see figure 6 & 7). At each end, carefully pull back the insulation and plastic cover, exposing the flexible pipe. Attach the flexible pipe using pipe clamps. For a better seal, you may also use aluminum tape. Wrap the tape around the joint between the flexible pipe and the air inlets. Carefully push the insulation and plastic cover back over the pipe. Fix the plastic in place using aluminum tape.

25

FRESH AIR INTAKE

ALUMINUM

TAPE

PLASTIC

COVER

FLEXIBLE PIPE

OUTSIDE

INTAKE

SCREW

OPENING

FACING

DOWN

INSULATION

ALUMINUM

TAPE

Figure 19

WALL

3.7 DOOR OVERLAY INSTALLATION

OUTSIDE AIR

CONNECTION TO THE

FIREPLACE

FIREPLACE

FIRE PLACE

CONNECTION

ALUMINUM TAPE

3" FLEXIBLE PIPE

PLASTIC COVER

ALUMINUM TAPE

INSULATION

Figure 20

OVERLAY

DOOR FRAME

Figure 21

In order to install the door overlay, simply place the overlay over the door frame. From behind the door frame, locate the 4 attachment holes and use the 4 screws provided with the overlay to secure it to the door frame.

26

4.1 CHIMNEY INSTALLATION NOTES

1. If possible, install an interior chimney as it will provide better performance. In areas with continuous temperatures below

−18° C (0° F), the use of an exterior chimney increases the likelihood of operating problems such as low draught, high rate of creosoting, and poor start-up characteristics. Exterior chimneys are also prone to down-drafting and flow reversal. Installations, which are located on lower floors in the house, such as in a basement, in combination with outside chimney, are especially prone to flow reversal.

2. The ENERZONE SOLUTION 2.5ZC is listed only with chimney systems described in table 2.

3. A chimney venting a fireplace shall not vent any other appliance.

4. The minimum chimney system height is 15 ft. (4.6 m).

5. All chimney installations must include at least one support. Reducing the amount of chimney weight on the fireplace will help avoid the noise created when the fireplace expands. This can be achieved by having the chimney supported by the supports. The maximum chimney length that should be supported by the fireplace is 9 ft. (2.75 m) for 2"

Solid Pack Chimney, 12 ft. (3.7 m) for 1" Solid Pack Chimney, and 26 ft. (8 m) for AC

Triple Wall Chimney.

6. The chimney must extend at least 3 ft. (1 m) above its point of contact with the roof and at least 2 ft. (0.6 m) higher than any wall, roof or building within 10 ft. (3 m) of it (Figure

21).

7. If the chimney extends higher than 5 ft.

(1.5 m) above its point of contact with the roof, it must be secured using a roof brace.

8. A rain cap must be installed on top of the chimney. Failure to install a rain cap may cause corrosion problems.

9. Cut and frame square holes in all floors, ceilings, and roof that the chimney will go through to provide a 2" (50 mm) clearance between the chimney and any combustible materials. Do not fill this 2

″ space with insulation or any other combustible material.

10'

2' MIN.

3' MIN.

extend through accessible spaces must be enclosed to avoid contact with combustible materials or damage the chimney.

Figure 22

27

4.2 CHIMNEY INSTALLATION INSTRUCTIONS

1. Cut and frame the holes in the ceiling, floor and roof where the chimney will pass (see figure 23). Use a plumb bob to line up the center of the holes. Make sure that the size of the floor and ceiling holes are in accordance with the chimney manufacturer’s instructions.

Figure 23

2. From below, install a firestop supplied by the chimney manufacturer in each ceiling/floor separation through which the chimney will pass. At the attic level, install an attic radiation shield from above (see figure 24).

3. Follow the chimney’s manufacturers’ instructions and place the first chimney length on he fireplace. For all chimneys, you must use an anchor plate supplied by the chimney manufacturer before installing the first chimney length (see figure 24). Continue installing chimney lengths making sure to lock each length in place.

4. Every time the chimney passes through a ceiling or a wall, install the appropriate firestop.

When you reach the desired height, install the roof support. (Refer to instructions included with the support.).

5. Then, put the roof flashing in place and seal the joint between the roof and the flashing with roofing pitch (see figures 24). For sloping roofs, place the flashing under the upper shingles and on top of the lower shingles. Nail the flashing to the roof, using roofing nails.

6. Place the storm collar over the flashing, and tighten it with the bolt supplied. Finally, seal the joint between the storm collar and the chimney, using silicone caulking.

7. Install the chimney cap.

8. When a ventilated roof flashing is installed, precautions are to be taken not to caulk or seal the ventilating openings.

28

EXAMPLE OF TYPICAL CHIMNEY INSTALLATION

RAIN CAP

COLLAR

FLASHING

ATTIC

RADIATION

SHIELD

FIRESTOP

ANCHOR

PLATE

OUTSIDE

AIR KIT

Figure 24

29

When you build a combustible chase enclosure for chimney sections above the roof, refer to the chimney manufacturer for clearances to combustible materials.

Figure 25 – Example of a combustible chase enclosure installation above the roof

30

The minimum system height when using elbows is:

Fireplace model ENERZONE SOLUTION 2.5ZC

Chimney model

Vertical installation

Two (2) elbows

Four (4) elbows

All models

15 ft. (4.6 m)

15 ft. (4.6 m)

17 ft. (5.2 m)

After reaching the location requiring the elbow, proceed as follows:

1. Install the first elbow; turn it in the required direction. Secure it to the chimney according to the chimney manufacturer’s instructions. In many cases, it is recommended to secure connections with three (3) ½" (12 mm) metal screws.

2. Install the necessary chimney lengths to achieve the required offset. Lock the chimney lengths together according to the chimney manufacturer’s instructions. In many cases, it is recommended to use three (3) ½" (12 mm) screws. If the offset length is made of two

(2) chimney lengths or more, many chimney manufacturers may require that you use an offset or roof support halfway up the offset. If penetrating a wall, install a wall radiation shield supplied by the chimney manufacturer (see figures 26 & 27).

3. Use another elbow to turn the chimney vertically. Secure the elbow.

4. Use a plumb bob to line up the centre of the hole. Cut a hole for the chimney in the ceiling/floor. Frame this hole as described previously.

5. From below, install a firestop supplied by the chimney manufacturer (see figure 24).

6. A support must be used on the first 15' section (4.6 m).

7. Continue with the regular installation.

31

STRAPS

SUPPORT

STRAPS

CHIMNEY

ANCHOR PLATE

RAIN CAP

Figure 26

COLLAR

ROOF FLASHING

OFFSET SUPPORT

INSULATED WALL

RADIATION SHIELD

FRAMING

2" X 3"

18"

15'

Figure 27

32

TABLE 2 - LISTED CHIMNEYS FOR YOUR ENERZONE SOLUTION 2.5ZC

CHIMNEY

MANUFACTURER

BRAND TYPE

INNER

DIAMETER

Selkirk

Selkirk

Selkirk

Selkirk

Selkirk

Ultra-Temp (UT)

Super Pro (SPR)

Super Vent (JSC)

Hart & Cooley (TLC)

Sure-Temp (ST)

1" Solid Pack

1" Solid Pack

1" Solid Pack

1" Solid Pack

1" Solid Pack

6"

6"

6"

6”

6”

Selkirk

Selkirk

Selkirk

CF Sentinel (CF) 2" Solid Pack

Super Pro 2100 (ALT) 2" Solid Pack

Super Vent 2100 (JM) 2" Solid Pack

6"

6"

6"

Security Chimney

Security Chimney

ASHT+

S-2100

1" Solid Pack

2" Solid Pack

6"

6"

Simpson Dura-Vent Dura Tech 1" Solid Pack 6"

Simpson Dura-Vent Wall

American Metal Model HSS AC Triple Wall 6"

American Metal

ICC

Model HS

Excel 2100

AC Triple Wall

1" Solid Pack

6"

6"

Oliver Macloed Nova-Temp HT 6103 + 1" Solid Pack 6"

Oliver Macloed Nova-Temp HT 6000 + 2" Solid Pack

Note: See next page for mandatory components

6"

33

TABLE 3 – LIST OF MANDATORY COMPONENTS

CHIMNEY

MANUFACTURER

MANDATORY COMPONENTS TYPE/BRAND

Selkirk

Security Chimney

Simpson Dura-Vent

ICC

• Ventilated roof flashing.

• Must have rafter protectors at the roof level if the chimney is enclosed at the attic level (see section 5).

• Rafter protector at the roof level if chimney is enclosed at the attic level (see section 5).

• Requires insulated attic radiation shield unless chimney is enclosed at the attic level.

• Ventilated roof flashing.

• Rafter protector at the roof level is chimney is enclosed at the attic level (see section 5).

• Ventilated roof flashing.

Ultra-Temp (UT),

Super Pro (SPR), Super vent (JSC), Hart &

Cooley (TLC), Sure-

Temp (ST)

ASHT +

Dura Tech

Excel 2100

American Metal

NOTE: The floor protector in front of the fireplace must have a R value of 1.53 or greater.

34

4.4 ANGLED WALL RADIATION SHIELD

When passing through a combustible wall with the chimney at a 30

° or 45° angle (30° or 45° in

Canada and 30

° only in the USA), an angled firestop or wall radiation shield provided by the chimney manufacturer must be installed. Only one is required. Follow the chimney manufacturer’s installation instructions.

In cold climate locations, it is recommended that you use the insulated wall radiation shield since it will maintain the home’s thermal barrier.

GYPROC

INSULATED WALL

RADIATION SHIELD

INSULATED WALL

Figure 28

35

4.5 CHIMNEY SUPPORT INSTALLATION

Universal Roof Support

This support has three possible uses:

1. It must be used on a roof to support the chimney.

2. It may be used on a floor, ceiling or roof above an offset to support the chimney above the offset.

3. It may be used on a floor, ceiling or roof as a supplementary support.

For roof support installation, refer to the instructions provided with the support by the chimney manufacturer. Many manufacturers will provide the maximum height of chimney that can be supported by the support. Make sure you respect those parameters.

Universal Offset Support

This support is used to support the chimney above an offset. When the chimney offset is used to pass through a wall, this support may be used on the wall to support the chimney. For offset support installation, refer to the instructions provided with the support by the chimney manufacturer. Many manufacturers will provide the maximum height of chimney that can be supported by the support. Make sure you respect those parameters.

4.6 CHIMNEY CHASE AND MULTIPLE TERMINATIONS

For the purpose of this manual, a chimney chase is considered a part of the chimney system rather than part of a building. The termination must be placed a minimum of 18" (460 mm) above the chase.

For installations where more than one chimney is located in the same chase or within the same area, we suggest that their terminations be separated by at least 16" (410 mm) horizontally, and

18" (460 mm) vertically. This separation is to prevent smoke migrating from one chimney to another (see figure 29).

36

18"

457.2mm

18"

457.2mm

16"

406.4mm

16"

406.4mm

18"

457.21mm

Figure 29

37

4.7 INSTALLATION INSTRUCTIONS FOR MASONRY APPLICATION

WARNING: Before starting the installation, the masonry chimney must be inspected by a qualified sweep.

The following requirements must be respected:

1. The chimney must be absolutely clear of any soot residue or creosote. Check for cracks, loose or missing bricks that could inhibit correct installation of the liner.

2. The clearance to combustible must be a minimum of 1" between the outside of the masonry and any wood framing or loose insulation.

3. The chimney must be built in accordance with the current building code.

4. No other appliance can be connected to the same chimney.

Installation:

The chimney must be relined with a stainless steel liner of the same diameter as the outlet of the fireplace. For connection at 30 o or 45 ° angle, a special connector must be used to connect the liner to the insulated chimney.

Verify availability and installation instructions for this connector with the chimney manufacturer.

Follow these steps:

1. Position the fireplace in its location.

Temporarily install the elbow on the top of the fireplace and, using a level, mark with an oval the location where the flue liner will enter the masonry chimney.

2. In the middle of the oval, drill a hole in the masonry chimney at 45

° or 30°.

3. Increase the size of the hole until a 45

° or 30

° liner elbow can be easily slipped through.

4. Slide the liner down from the top of the masonry chimney until you reach the hole level.

5. Slip through the hole a 45

° or 30° liner elbow and connect it to the liner.

6. Add a small liner section to the liner elbow which will allow the liner to extend at least 12" (measured at the top of the liner) from the masonry chimney.

7. Seal the opening around the liner with high temperature refractory cement.

7'

See typical installation illustrated below.

FIRESTOP

STAINLESS

STEEL LINER

1"

HIGH TEMP

CEMENT

SPECIAL

CONNECTOR

3 X SCREWS

INSULATED

LENGTH

INSULATED

ELBOW

8. Then, follow the chimney manufacturer’s instructions to connect the extended liner section to the special chimney connector.

38

5. OPTIONS

No.:

Includes: one deflector, two 90 o elbows, and two outlet grilles and frames, . #AC01309

Central forced air kit:

Includes: one blower, one 5" flex adapter, 3 pipe clamps,

And one control box with heat sensor and PC Board.

Outside air kit

#AC01310

Includes: one 3" flex adapter, 2 pipe clamps, and one outside wall register.

Rigid spark screen

Includes: one rigid spark screen.

Rafter protector kit

#AC03500

#AC01308

Includes: four rafter protectors as shown below #AC03510

*May be required if the chimney manufacturer does not supply rafter protectors.

Each rafter is made of 22GA galvanized steel (10.44”W x 5.376”H).

39

6. APPENDIX

SPECIFICATIONS

Weight: 385 lbs

Height: 38"

Width: 36.75"

Depth: 26"

Maximum recommended heating area : 500 to 2,100 square feet (with forced air kit)

Heating capacity* – BTU/hr., EPA test wood : 30,500

Heating capacity* – BTU/hr., seasoned cordwood : 75,000

Optimum efficiency : 77%

*Why is the BTU indicated on the EPA label smaller than the one advertised?

You will notice a difference between the BTU output as indicated on the unit’s white EPA label affixed to the glass and the BTU as advertised on our web site and/or product literature. The maximum BTU output we advertise for this unit is what will be obtained with a full load of seasoned cordwood inserted inside the firebox. The EPA output, on the other hand, is what has been obtained during emissions testing. The EPA test procedure requires that a special type of wood be used and positioned inside the firebox in a manner that does not represent the way the firebox volume would normally be utilized using seasoned cordwood. The EPA test load is typically much smaller.

Hence, the BTU as per the EPA label is reduced. The BTU output that should be considered by a normal user is the one we advertise for seasoned cordwood.

CLEARANCE TO COMBUSTIBLES

The following clearances meet the minimum requirements for a safe installation

Side wall: 17" (43 cm) measured from the outside door frame.

Side mantle:

In front of fireplace :

0" (must have a depth no greater than 3”).

36"

Ceiling:

Fireplace enclosure:

7 ft. (2.15 m) measured from the base of the fireplace.

Bottom: 0"

Chimney:

Combustible shelf :

Top: Do not fill the space above the fireplace with any material

(except the wood framing).

2" (50 mm)

50" (127 cm) measured from the base of the fireplace for a shelf with a depth of 6" or less.

52" (132 cm) measured from the base of the fireplace for a shelf with a depth of more than 6" (15 cm), but less than 12" (30 cm).

40

REPLACEMENT PARTS

Description

Front air tube (1)

Air tube (2) – second from front

Part No. Description

PL53030 Bricks (side and rear)

PL53031 Left floor brick

Air tube (3) – third from front PL53032 brick

Back air tube (4)

Vermiculite baffle

PL53033

21134

Flue insulation collar

Blowers

Top insulation (2 ½” thick)

Door gasket

Glass gasket

21150 Door glass

AC06100 Door handle

AC06400 Air control handle

Part No.

29020

22122

22123

21152

44073

SE53240

30560

30561

41

7. ENERZONE LIMITED LIFETIME WARRANTY

The warranty of the manufacturer extends only to the original consumer purchaser and is not transferable. This warranty covers brand new products only, which have not been altered, modified nor repaired since shipment from factory. Products covered under this warranty must have been manufactured after the revision date indicated below.

Proof of purchase (dated bill of sale), model name and serial number must be supplied when making any warranty claim to your ENERZONE dealer.

This warranty applies to normal residential use only. Damages caused by misuse, abuse, improper installation, lack of maintenance, over firing, negligence, accident during transportation, power failures, downdrafts, or venting problems are not covered by this warranty.

This warranty does not cover any scratch, corrosion, warping, or discoloration caused by over firing, abrasives or chemical cleaners. Any defect or damage caused by the use of unauthorized parts or others than original parts void this warranty. An authorized qualified technician must perform the installation in accordance with the instructions supplied with this product and all local and national building codes. Any service call related to an improper installation is not covered by this warranty.

The manufacturer may require that defective products be returned or that digital pictures be provided to support the claim. Returned products are to be shipped prepaid to the manufacturer for investigation. If a product is found to be defective, the manufacturer will repair or replace such defect. Transportation fees to ship the product back to the purchaser will be paid by the manufacturer. Repair work covered by the warranty, executed at the purchaser’s domicile by an authorized qualified technician requires the prior approval of the manufacturer. Labour cost and repair work to the account of the manufacturer are based on predetermined rate schedule and must not exceed the wholesale price of the replacement part. All parts and labour costs covered by this warranty are limited according to the table below.

The manufacturer at its discretion may decide to repair or replace any part or unit after inspection and investigation of the defect. The manufacturer may, at its discretion, fully discharge all obligations with respect to this warranty by refunding the wholesale price of any warranted but defective parts. The manufacturer shall in no event be responsible for any special, indirect, consequential damages of any nature, which are in excess of the original purchase price of the product. A one-time replacement limit applies to all parts benefiting from a lifetime coverage. This warranty applies to products purchased after March 1 st

, 2009.

WARRANTY APPLICATION

DESCRIPTION

Combustion chamber (welds only), castings, convector air-mate, ceramic glass (thermal breakage only*), and secondary air tubes*.

PARTS LABOUR

Plating* (defective manufacture) – subject to limitations above.

Stainless steel firebox components, surrounds and heat shields, ash drawer, steel legs, pedestal, trims (aluminum extrusions), C-Cast baffle*, and vermiculite baffle*.

Carbon steel firebox components, glass retainers, and handle assembly.

Blowers, heat sensors, switches, rheostat, wiring, and other controls.

Lifetime

5 years

3 years

2 years n/a

3 years

2 years

1 year

Paint (peeling), gaskets, insulation, firebrick, and ceramic fibre blankets. 1 year n/a

*Pictures required

Shall your unit or a components be defective, contact immediately your ENERZONE dealer. Prior to your call make sure you have the following information necessary to your warranty claim treatment:

Your name, address and telephone number;

Bill of sale and dealer’s name;

Serial number and model name as indicated on the nameplate fixed to the back of your unit;

Nature of the defect and any relevant information.

Before shipping your unit or defective component to our plant, you must obtain from your ENERZONE dealer an Authorization Number. Any merchandise shipped to our plant without authorization will be refused automatically and returned to sender.

42

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!