Datel | 20A | User manual | Murata ACA-20PC Series

Add to my manuals
6 Pages

advertisement

Datel | 20A | User manual | Murata ACA-20PC Series | Manualzz

www.murata-ps.com

ACA-20PC Series

Digital, LED-Display AC Ammeters with

Built-in Current Transformers

Now

Available with

Wire Lead CTs

FEATURES

  of 0 to 2/20/50/100 Amps

 

On-board current transformers

Scaling/interface circuitry

Precision A/D converters

Bright red LED displays

 

 

 

 

  built-in load connections

 

 

SIMPLIFIED SCHEMATIC DIAGRAM

C

®

US E156931

DATEL's new ACA-20PC Series are the fi rst digital ac ammeters to incorporate on-board current transformers (CT’s), and they are amazingly easy to use. Simply pass the current-carrying load wire through the ACA-20PC’s on-board CT, apply power to the meter's two supply terminals, and you’re instantly measuring ac currents over one of four ranges (0-2A with 1mA resolution, 0-20A with 10mA resolution, or 0-50A and 0-100A with 100mA resolution). Absolutely no external components, such as expensive low-value shunts or 5A "donut" CT’s, are required.

Meters are ac powered (120/220Vac @ 50/60Hz) or dc powered (+5-40V) and impose minimal loads (50mA max. and 120mA max., respectively) on their supplies. All models employ auto-zeroing circuits, precision bandgap references, and super stable thin-fi lm resistors for unsurpassed accuracy (±0.15%FS) and stability.

The functionally complete ACA-20PC ammeters provide all the scaling/interface circuitry to mate the CT’s output to a precision (3½ digit) A/D converter. The A/D's output goes directly to drivers for the meters’ large (0.37"/9.4mm digit height), easy-to-read, LED displays. AC-powered units have on-board AC/DC converters, and wide-range dc-powered units have on-board linear regulators. AC-powered models can be powered by the same ac supply whose current they are monitoring. The 2A and 20A, 85-264Vac, 50/60Hz ("AC1") models feature additional on-board terminal blocks to supply power to the external load. All models provide 2000Vdc isolation between the measured ac current and their power supply, and all are UL/CSA recognized.

Each meter is housed in a subminiature, 1.38" x 0.88", epoxy-encapsulated package. Total behind-the-panel installation depth is approximately 2 inches.

 

For full details go to www.murata-ps.com/rohs

BUILT-IN

CURRENT

TRANSFORMER

RMS-to-DC

CONVERTER

(L1)

MEASURED AC

LOAD CURRENT

CAL.

+

3½ DIGIT

A/D CONVERTER

+V –V

POWER

CONVERTER

LED DISPLAY

A B

Figure 1. ACA-20PC Series simplifi ed schematic

TB1

CURRENT LIMITED

AC OR DC SUPPLY www.murata-ps.com/support

MPM_ACA_20PC.B13

Page 1 of 6

Performance/Functional Specifi cations

Typical at T

A

= +25°C, unless otherwise noted.

Full-Scale Current

(45-450Hz)

ACA-20PC-1-XXX-XX

ACA-20PC-2-XXX-XX

ACA-20PC-3-XXX-XX

ACA-20PC-4-XXX-XX

DMS-30798-C

Overcurrent Rating

Performance

Sampling Rate

Accuracy

Measurement Type

Min.

Typ.

Max.

1.999

19.99

50.0

100.0

30.0

Amps

Amps

Amps

1.5 x rated full-scale current

2.5 reading per second

±0.15%FS ±6 Counts

Units

Amps

Amps

Temperature Drift (0 = +60°C)

Zero Reading (Vin = 0 Volts)

Sine wave input, full-wave averaging, rms calibrated

– ±0.2

±0.4

Cnts/°C

“–001” “000” “001” Counts

Dielectric Withstanding Voltage

UL/IEC61010-1

Power Supply Voltage

ACA-20PC-X-AC1-RL (47-99Hz)

ACA-20PC-X-DC1-RL

Power Supply Current

ACA-20PC-X-AC1-RL (47-99Hz)

ACA-20PC-X-DC1-RL

2000

85

+4.75

Measurement category II

120

264

+40

Vdc

Vac

Vdc

30

+8

50 mA

+12 mAdc

Power Supply Terminal Block

ACA-20PC-1-AC1-RL and ACA-20PC-2-AC1-RL

(2A and 20A ac-powered models with 4-position terminal blocks):

Wire Size and Type 12-20AWG (solid), 14-20AWG (stranded)

Insulation Strip Length 0.25 inches

Screw Tightening Torque

Maximum Rated Current

4.4 lb·in (0.5N·m) ±20%

20A with 12AWG solid wire; 15A with

14AWG solid or stranded wire

Maximum Rated Voltage 630V (VDE 0110-V. Group 2)

250V (VDE 0110-V Group 3)

ACA-20PC-X-XXX-XX

(All other ac or dc-powered models with 2-position terminal blocks):

Wire Size and Type 16-24AWG (solid or stranded)

Insulation Strip Length

Screw Tightening Torque

Display

Display Type and Size

Overrange Indication

0.25 inches

2.2 lb·in (0.25 N·m) ±20%

3½ digit, 0.37"/9.4mm high LED

“1_ _ _”

Decimal Point

Physical/Environmental

Operating Temperature

Storage Temperature

Humidity (non-condensing)

0

–40

0

Fixed, model dependent

+60

+75

95

°C

°C

%

ACA-20PC Series

Digital, LED-Display AC Ammeters with

Built-in Current Transformers

Physical/Environmental

Case Material

Dimensions

Weight:

ACA-20PC-1-XXX-XX

ACA-20PC-2-XXX-XX

ACA-20PC-3-XXX-XX

ACA-20PC-4-XXX-XX

DMS-30798-C

Polycarbonate

1.38”W x 0.88”H. Depth is model dependent (see mechanical specifi cation)

1.1 ounces (31 grams)

1.1 ounces (31 grams)

1.3 ounces (37 grams)

1.5 ounces (43 grams)

1.0 ounces (28 grams)

➀ The ACA-20PC-1-AC1-RL and ACA-20PC-2-AC1-RL have 4-position on-board terminal blocks. All other models have 2-position terminal blocks.

➁ Specifi ed full-scale currents are those passing through the built-in CT's primary(load) circuit, over the frequency of 45-450Hz. The Overcurrent Rating is a continuous rating that applies to the measured ac load current. It does not apply to any circuitry external to the meter. Accuracy is guaranteed to the rated current.

➁ For the ACA-20PC-2-AC1-RL, if the load is connected to the meter's on-board

4-position terminal block, the 20A full scale range requires 12AWG solid copper wire on all connections. If 14AWG solid copper wire is used, the current should be limited to 15A. See Figure 3.

➃ All specifi ed maximum power supply currents are steady-state values.

AC-powered models can draw higher surges at initial turn-on.

➄ Maximum reverse polarity protection on "DC1" models is –40Vdc.

Ordering Information

ACA - 20PC - 1 - AC1 - RL - L - C

(45-450Hz)

Input Range:

1 = 1.999A

2 = 19.99A

3 = 50.0A

4 = 100.0A

RoHS

Leaded CT (100A model)

LED Color:

RL = Red Standard

BL = Blue Standard

Power Supply: PGL = Green Standard

AC1 = 85-264Vac@50/60Hz

DC1 = +5-40Vdc

DMS-30798-C: 30Amp model with a wire lead CT and “-AC1” power supply specifi cations. See Mechanical section for dimensions.

Accessories: DMS-20-CP Panel cutout punch

A DMS-BZL4-C bezel assembly with sealing gasket is supplied with each ammeter.

www.murata-ps.com/support

MPM_ACA_20PC.B13

Page 2 of 6

TECHNICAL NOTES

IMPORTANT! To ensure safe and reliable operation, ACA-20PC ammeters must be installed and serviced by qualifi ed technical personnel. Contact DATEL if there is any doubt regarding ammeter installation and/or operation.

1. Measurement Type: ACA-20PC ac ammeters employ a full-wave- rectifi ed, average responding, rms-calibrated circuit to measure the stepped-down output of their on-board, L1 current transformer (CT) .

Stated accuracy specifi cations are measured using a sine-wave current at or close to the specifi ed full scale input level, at nominal line frequency.

2. Calibration: Periodic recalibration of ACA-20PC ammeters is not required under normal, indoor operating environments. If user calibration is necessary, it should be performed by qualifi ed technical personnel. Calibration is performed with potentially lethal voltages applied to the ACA-20PC and its associated wiring, with the specifi ed full-scale current fl owing through the ammeter’s built-in current transformer.

A plastic, fully insulated adjusting tool must be used to access the recessed calibration potentiometer located on the back of the meter

(see Mechanical Specifi cations). Contact DATEL if additional information is required regarding calibration, setup, or any other technical issue pertaining to the ACA-20PC.

3. Wire Gauges and Fusing: Wires specifi ed in the Functional Specifi cations section must be used for making connections to ACA-20PC

Series ammeters. All power-supply and load wiring must be rated for the supply voltages and currents they will conduct and must comply with any code or application-mandated requirements pertaining to the user’s specifi c installation.

ACA-20PC Series ammeters are not internally fused. Special attention must be paid to ACA-20PC-1-AC1 (0-2A range) and ACA-20PC-2-AC1

(0-20A range) ac-powered models when their built-in auxiliary terminal block connections on TB1 are used to supply power to an external load. The input supply wires connected to both the ammeter and the load must be fused according to the current rating of the wire gauge being used, in accordance with applicable regulatory codes, but not to exceed TB1’s maximum 20A rating. If TB1 is not used to supply power to external loads, a 0.25A/250V time delay/time lag fuse must be used.

ACA-20PC-3-AC1 (0-50A range, ac-powered) and ACA-20PC- 4-AC1

(0-100A, ac-powered) models’ TB1 is to be used only for powering the ammeters’ internal circuitry; it must not be used to supply power to external loads. The supply wires feeding these models must be fused with a 0.25A time delay/time lag fuse, in accordance with applicable regulatory codes.

Wire insulation must be stripped to within ±10% of the stated dimensions, and wires should be inserted into TB1 such that their insulation is not pinched by the screw terminal.

4. AC Supply Polarity and Grounding: The two ac supply inputs,

TB1-A and TB1-B, on ac-powered ammeters are not in themselves polarity sensitive, that is, they have no internal "AC LO" or "AC HI"

ACA-20PC Series

Digital, LED-Display AC Ammeters with

Built-in Current Transformers designations. Also, ac-powered ACA-20PC ammeters do not include or require a connection to earth/chassis ground. However, in many applications, external ac loads which are connected directly to the

ACA-20PC’s built-in auxiliary terminal blocks must be wired with proper polarity and connected to earth/chassis ground.

5. Connector Torque Ratings: It is important to tighten TB1's screw terminals to their rated torque specifi cations of 4.4 pound-inches

(0.5Nm) for four-terminal ammeters (ACA-20PC-1-AC1-RL and ACA-

20PC-2-AC1-RL), and 3.6 pound-inches (0.4Nm) for two-terminal ammeters. Proper tightening will minimize connector losses and ensure safe, reliable operation.

6. 100 Amp Model (ACA-20PC-4-XXX): This model’s built-in current transformer requires a larger panel cutout width dimension. See

Mechanical Specifi cations for more information.

7. DC-Powered Models: DC-powered models draw minimal supply currents and in most applications can be fused according to the supply wire’s maximum amperage rating. However, be sure to check and comply with all applicable codes and regulations to ensure proper installation and operation.

8. Isolation: The on-board CT (L1) provides a minimum 2000Vdc isolation between the current-carrying conductor passing through its primary circuit and the ammeter supply voltage connected to TB1. Of course, this isolation rating only applies to applications in which the load wiring (i.e., the wire passing through the CT’s center hole) does not connect directly or indirectly to TB1-A or TB1-B.

PANEL INSTALLATION

All connections to ACA-20PC Series ammeters must be made after the ammeter is securely attached to the panel and with all load and supply voltages de-energized (off).

Care should be exercised when passing the load-carrying conductor through the meter’s built-in CT— particularly when larger-gauge conductors are used. The position of the installed wire should be such that minimal forces are applied to the built-in CT, TB1, or to the ammeter itself. In high-vibration environments, adequate strain reliefs be used for all load and supply wiring.

To ensure a secure panel-mount installation, DATEL recommends using the DMS-BZL4 bezel assembly (with sealing gasket) supplied with each ammeter. Also, please note that the ACA-20PC-4-XXX

100A oversize CT requires a larger panel-cutout width of 1.350"

(34.3mm). See Mechanical Specifi cations for detailed cutout and ammeter dimensions.

Following the four-step sequence shown in Figure 2 below — being careful not to apply excessive force or twisting motions— insert the ammeter into the panel opening. When using the DMS-BZL4 bezel assembly, install its sealing gasket so it is positioned between the ammeter’s front fl ange and panel front surface (see Mechanical

Specifi cations). Be sure to use and securely tighten all four screws supplied with the bezel assembly.

www.murata-ps.com/support

MPM_ACA_20PC.B13

Page 3 of 6

Step 3.

ACA-20PC Series

Digital, LED-Display AC Ammeters with

Built-in Current Transformers

Step 4.

Step 1.

Panel

Step 2.

Figure 2. Panel Installation

TYPICAL WIRING DIAGRAM

First pass and carefully dress one external load wire through the on-board CT (L1). Then connect the ac supply and load wires to TB1 as shown. If required, verify that correct line-power polarities are applied to the external load (see Technical Note 4). Ensure all wires are stripped and terminals torqued correctly. For proper operation, pass only one load wire through the on-board CT’s center hole.

FUSED

85-264Vac

POWER

ACA-20PC-1-AC1-RL

FUSED

85-264Vac

POWER

ACA-20PC-X-ACX

FUSED

AC POWER

SUPPLY

TO AC LOAD

AC SUPPLY

Figure 4. All Other AC-Powered Models

ACA-20PC-2-AC1-RL

85-264Vac TO LOAD TO LOAD

Figure 3. 2A and 20A, 85-264V AC-Powered Models

With Auxilliary Load Connections

ACA-20PC-X-DCX

+

FUSED

DC POWER

SUPPLY

+ –

TO AC LOAD

AC SUPPLY

Figure 5. All DC-Powered Models www.murata-ps.com/support

MPM_ACA_20PC.B13

Page 4 of 6

MECHANICAL SPECIFICATIONS

ACA-20PC-1 & 2-AC1-RL

2A and 20A, 85-264V ac-powered models

Hole Diameter:

0.27 (6.9) min.

0.040

(1.02)

1.30

(33.0)

1.38

(35.1)

FRONT VIEW

0.040

(1.02)

1.00

(25.4)

2.01

(51.1)

0.040

(1.02)

0.80

(20.3)

0.88

(22.4)

1.32

(33.5)

BACK VIEW

CAL.

ACA-20PC Series

Digital, LED-Display AC Ammeters with

Built-in Current Transformers

ACA-20PC-1 & 2

2A and 20A, all other models

Hole Diameter:

0.27 (6.9) min.

0.040

(1.02)

1.30

(33.0)

1.38

(35.1)

FRONT VIEW

0.040

(1.02)

1.00

(25.4)

2.01

(51.1)

0.040

(1.02)

0.80

(20.3)

0.88

(22.4)

1.32

(33.5)

BACK VIEW

CAL.

ACA-20PC-3 Series

50A models

Hole Diameter:

0.35 (8.9) min.

0.040

(1.02)

1.30

(33.0)

1.38

(35.1)

FRONT VIEW

0.040

(1.02)

1.00

(25.4)

2.12

(53.8)

0.040

(1.02)

0.80

(20.3)

0.88

(22.4)

1.54

(39.1)

BACK VIEW

CAL.

ACA-20PC-4 Series

100A models with pc-board mounted CTs

1.33

(33.8)

*

* THIS MODEL REQUIRES A PANEL

CUTOUT WIDTH OF 1.350" (34.3MM)

Hole Diameter:

0.55 (14.0) min.

0.040

(1.02)

1.30

(33.0)

1.38

(35.1)

FRONT VIEW

2.53

(64.3)

0.040

(1.02)

1.00

(25.4)

0.040

(1.02)

0.80

(20.3)

0.88

(22.4)

1.32

(33.5)

BACK VIEW

CAL.

Mechanical Dimensions: Inches (mm) Tolerances: 2 PL DEC ±0.02 (±0.51), 3 PL DEC ±0.010 (±0.254) www.murata-ps.com/support

MPM_ACA_20PC.B13

Page 5 of 6

MECHANICAL SPECIFICATIONS, CONTINUED

ACA-20PC-4-XXX-L (100A model)

DMS-30798-C (30A model)

OD: 100A Model: 1.18 (30.0)

DMS-30798-C (30A): 0.87 (22.0)

ID: 100A Model: 0.58 (14.7)

DMS-30798-C (30A): 0.35 (8.9)

Lead Length:

2.0 (50.5) min.

0.040

(1.02)

®

1.30

(33.0)

1.38

(35.1)

®

0.040

(1.02)

1.00

(25.4)

0.040

(1.02)

FRONT VIEW

0.80

(20.3)

0.88

(22.4)

1.14

(29.0)

BACK VIEW

CAL.

ACA-20PC Series

Digital, LED-Display AC Ammeters with

Built-in Current Transformers

BEZEL INSTALLATION AND RECOMMENDED DRILL AND

PANEL CUTOUT

#2-56 INSERT

0.156 (3.96) DEEP

0.187

(4.75)

FRONT VIEW

1.280

(32.51)

1.07

(27.18)

1.826 (46.38)

INTERNAL CORNER RADII:

0.032 (0.81) MAX.

PANEL CUTOUT

0.116 (2.95)

0.838

(21.29)

0.093 (2.362) DIA

(4 REQUIRED)

1.336 (33.93)*

1.626 (41.30)

0.145 (3.68)

*

1.350 (34.3) for ACA-20PC-4-XXX 100A model with pc-board mounted CTs .

1. Description of safety marks:

Caution, risk of electrical shock

Caution, risk of danger

Equipment is protected throughout by double or reinforced insulation

2. Cleaning Instructions: Gently clean with dry cloth only.

3. Caution: if the equipment is used in a manner not specifi ed by Murata Power Solutions, the protection provided by the equipment may be impaired.

Murata Power Solutions, Inc.

11 Cabot Boulevard, Mansfi eld, MA 02048-1151 U.S.A.

ISO 9001 and 14001 REGISTERED

Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifi cations are subject to change without notice. © 2014 Murata Power Solutions, Inc.

www.murata-ps.com/support

MPM_ACA_20PC.B13

Page 6 of 6