advertisement
ZETA 2002
38 - 266 kW
Installation, operating, and maintenance manual
Manual 101010B02
Issue 11.02
Replaces 04.02
Water chillers Air/water self-contained
0062
Axial fans and scroll compressors
ISO 9001 - Cert. n. 0201
CONTENTS Page
ZETA 2002 - water chiller ......................................................................................................... 1
UNIT FRAME ............................................................................................................ 1
COMPRESSORS ........................................................................................................ 1
CONDENSER ............................................................................................................ 1
CONDENSER FANS ................................................................................................... 1
EVAPORATOR .......................................................................................................... 1
REFRIGERANT CIRCUIT ............................................................................................. 1
ELECTRICAL PANEL .................................................................................................. 1
CONTROLS AND SAFETY DEVICES ............................................................................ 2
TESTING .................................................................................................................. 2
ZETA UNIT VERSIONS .............................................................................................................. 2
ZETA 2002 /HP: reverse cycle heat pump ................................................................... 2
ZETA 2002 LE: condensing unit. ................................................................................ 2
ZETA 2002 LE /HP: heat pump condensing unit .......................................................... 2
HYDRAULIC MODULE OPTIONS ............................................................................................... 3
ZETA 2002 /ST 2PS : ZETA 2002 /ST 2PS : unit with storage tank and pumps .............................. 3
ACCESSORY VERSIONS ........................................................................................................... 3
ZETA 2002 /DS: unit with desuperheaters ................................................................... 3
ZETA 2002 /LN: low noise unit .................................................................................. 3
ZETA 2002 /SLN: extra low noise unit ........................................................................ 3
REFRIGERANT CIRCUIT ACCESSORIES: ..................................................................................... 4
- Step type condensing pressure contro ...................................................................... 4
- Condensing pressure control by means of fan speed regulator .................................. 4
- Dual set-point ........................................................................................................ 4
- Pressure gauges ..................................................................................................... 4
- Liquid receivers ..................................................................................................... 4
- Compressor suction and discharge valves ................................................................. 4
- Liquid line solenoid valve ........................................................................................ 4
HYDRAULIC CIRCUIT ACCESSORIES ......................................................................................... 4
- Leaving water temperature control .......................................................................... 4
- Anti-freeze heater .................................................................................................. 4
- Water side relief valve (version ST only). .................................................................. 4
ELECTRICAL ACCESSORIES ...................................................................................................... 4
- Serial interface ....................................................................................................... 4
- Power factor correction cos φ ≥ 0.9 .......................................................................... 4
- Single voltage-free contacts for machine status signals .............................................. 4
- Set-point variable ................................................................................................... 4
- Remote user terminal panel .................................................................................... 4
VARIOUS ACCESSORIES ........................................................................................................... 5
- Rubber antivibration mountings ............................................................................... 5
- Spring-type antivibration mounts .............................................................................. 5
- Timber packing crate .............................................................................................. 5
- Pallet/skid for shipment in a container ...................................................................... 5
- Mesh coil guard with metallic filter .......................................................................... 5
- Anticorrosion treatment of coils for use in aggressive environments ............................ 5
- Non-standard RAL paint colours ............................................................................... 5
Blue Box
3.3
4.
4.1
1.
2.
2.1
2.2
2.3
SERIES ............................................................................................................................... 6
TECHNICAL DATA - R22 ........................................................................................... 7
TECHNICAL DATA - ELECTRICAL SPECIFICATIONS AND COMPONENTS R22 .......... 11
TECHNICAL DATA - ZETA 2002 /ST 2PS - R22 ........................................................... 13
TECHNICAL DATA - R407C ..................................................................................... 14
TECHNICAL DATA - ELECTRICAL SPECIFICATIONS AND COMPONENTS R407C ..... 18
TECHNICAL DATA - ZETA 2002 /ST 2PS - R407C ...................................................... 20
SOUND POWER AND PRESSURE LEVELS ................................................................... 21
FIELD OF APPLICATION............................................................................................ 23
3.
3.1
3.2
INTRODUCTION ...................................................................................................... 23
INSPECTION, TRANSPORT, SITE HANDLING .............................................................. 23
INSPECTION ........................................................................................................... 23
LIFTING AND SITE HANDLING .................................................................................. 23
UNPACKING ........................................................................................................... 24
SAFETY PRECAUTIONS ............................................................................................ 25
DEFINITION OF DANGER ZONE ................................................................................. 25
SAFETY PRESCRIPTIONS .......................................................................................... 25
MECHANICAL HAZARDS .................................................................................... 26
THERMAL HAZARDS ........................................................................................... 27
NOISE-RELATED HAZARDS .................................................................................. 28
ELECTRICAL HAZARDS ....................................................................................... 28
R407C REFRIGERANT SAFETY SHEETS .................................................................. 29
R22 REFRIGERANT SAFETY SHEETS ....................................................................... 31
POSITIONING .......................................................................................................... 33
INSTALLATION ........................................................................................................ 34
INSTALLATION CLEARANCES .................................................................................. 34
4.4
4.5
4.6
4.7
4.8
4.9
4.9.1
4.9.2
4.9.3
4.10
4.11
4.12
4.13
4.14
4.2
4.2.1
4.2.2
4.3
ANTI-VIBRATION ISOLATORS (option) ....................................................................... 35
Rubber Anti-Vibration Isolators ............................................................................. 35
Spring Anti-Vibration Isolators .............................................................................. 35
WATER PIPING CONNECTIONS ................................................................................ 36
RECOMMENDED HYDRAULIC CIRCUIT DIAGRAM FOR ZETA 2002 UNITS .............. 37
RECOMMENDED HYDR. CIRCUIT DIAGR. FOR MODELS ZETA 2002 / ST 2PS ......... 38
HYDRAULIC CIRCUIT DIAGRAM VERSION ST /2PS ................................................ 39
EVAPORATOR WATER PIPE CONNECTIONS .............................................................. 40
WATER FLOW SWITCH INSTALLATION INSTRUCTIONS (models 3.2 to 13.2) .............. 41
DESUPERHEATER HYDRAULIC CONNECTION (optional) ............................................ 43
ZETA 2002/DC HEAT RECOVERY EXCHANGER HYDRAULIC CONNECTIONS .............. 43
DIAGRAM WITH 3-WAY VALVE ........................................................................... 43
DIAGRAM WITH CONDENSING PRESSURE CONTROL VALVE ................................. 44
PRESSURE RELIEF VALVES ........................................................................................ 44
CONNECTIONS FOR VERSION /LE (MOTOCONDENSING UNIT) .................................. 45
Procedures to follow when sizing refrigerant lines .................................................. 45
Evaporating section at lower level than condensing section .................................... 45
Evaporating section positioned higher than the condensing unit section ................... 46
TABLE 1 - EXTERNAL PIPE DIAMENTERS FOR /LE VERSIONS ................................. 46
WATER FLOW RATE TO EVAPORATOR ...................................................................... 47
CHILLER WATER TEMPERATURE (SUMMER CYCLE) .................................................. 47
HOT WATER TEMPERATURE (WINTER CYCLE) .......................................................... 47
AMBIENT TEMPERATURE ........................................................................................ 47
FAN SPEED CONTROL (OPTIONAL) ........................................................................... 47
Blue Box
4.15
4.16
4.16.1
4.16.2
4.16.3
4.16.4
4.16.5
4.17
4.17.1
4.17.2
5.
5.1
6.1.7
6.1.8
6.1.9
6.1.10
6.1.11
6.2
6.3
6.3.1
6.3.2
6.4
6
6.1
6.1.1
6.1.2
6.1.3
6.1.4
6.1.5
6.1.6
7.
8.2.4
8.2.5
8.2.7
8.2.8
8.2.9
8.2.10
8.2.11
8.2.12
8
8.1
8.1.1
8.1.2
8.2
8.2.1
8.2.2
8.2.3
OPERATION WITH LOW TEMPERATURE CHILLED WATER AT EVAPORATOR ............... 48
TABLE 2 - FREEZING POINT FOR WATER-ANTIFREEZE MIXTURES ........................... 48
OPERATING LIMITS - R22 refrigerant .................................................................... 49
OPERATING LIMITS - R407C refrigerant ................................................................ 51
EVAPORATOR PRESSURE DROP ........................................................................... 53
PUMPS AVAILABLE PRESSURE - MODEL ZETA 2002 /ST 2PS ................................ 54
ELECTRICAL CONNECTIONS .................................................................................... 55
General ........................................................................................................... 55
Power supply to crankcase heaters ....................................................................... 56
Potential free contacts ......................................................................................... 56
Flow switch electrical connections ........................................................................ 56
Circulating pump electrical connections ................................................................ 56
MICROPROCESSOR CONTROLLERS ........................................................................... 56
Microprocessor controller for /LE and HP/LE versions .............................................. 57
RS485 serial interface (optional) ........................................................................... 57
ELECTRICAL PANEL LAY OUT .................................................................................. 58
START-UP ........................................................................................................... 60
PRELIMINARY CHECKS ............................................................................................ 60
UNITS WITH µCHILLER MICROPROCESSOR (models from 3.2 to 13.2) ......................... 61
INTRODUCTION ...................................................................................................... 61
Display ........................................................................................................... 61
Machine status information .................................................................................. 61
Keypad ........................................................................................................... 61
Controls and display screens ................................................................................ 62
Muting the BUZZER ............................................................................................. 62
ALARMS reset .................................................................................................... 62
Activation/deactivation of COOLING operation (Summer mode) ............................. 63
Activation/deactivation of HEATING mode (winter mode) ...................................... 63
Switching off the machine (stand by) .................................................................... 63
Inlet water temperature control ............................................................................ 64
Defrosting (heat pump mode only) ....................................................................... 64
STARTING THE UNIT ............................................................................................... 66
STOPPING THE UNIT ............................................................................................... 66
Temporary stop ................................................................................................... 66
Seasonal stop ..................................................................................................... 67
EMERGENCY STOP ................................................................................................. 67
TROUBLESHOOTING ................................................................................................ 67
UNIT WITH pCO 2 MICROPROCESSOR (models from 14.4 to 26.4) ............................... 75
INTRODUCTION ...................................................................................................... 75
Display ........................................................................................................... 75
Keypad ........................................................................................................... 75
OPERATING DESCRIPTION ....................................................................................... 77
Introduction ........................................................................................................ 77
Unit in stand-by mode ......................................................................................... 77
Enabling the unit ................................................................................................. 77
Pumps management (ST units only) ...................................................................... 77
Compressor start up ............................................................................................ 77
Heat pump mode operation ................................................................................. 78
Evaporator low temperature chilled water protection ............................................. 78
No-frost heater installed on the evaporator (optional) ............................................. 78
Compressor operation ......................................................................................... 78
Compressors management .................................................................................. 79
High and low pressure alarms .............................................................................. 79
Blue Box
12.
12.1
12.2
12.3
12.3.1
12.3.2
12.3.3
12.4
13.
9.
10.
10.1
10.1.1
11.
11.1
8.2.13
8.2.14
8.2.15
8.2.16
8.2.17
8.2.18
8.3
8.4
8.4.1
8.4.2
8.5
Low ambient temp. kit (option - condensing control with fan speed regulator) ......... 79
Changeover from chiller to heat pump and vice versa ............................................ 79
Defrosting (heat pump mode operation only) ........................................................ 80
Total heat recovery (option) ................................................................................. 80
Dual set-point (option) ......................................................................................... 81
Operation leaving water temperature control (option) ............................................ 81
STARTING THE UNIT ............................................................................................... 82
STOPPING THE UNIT ............................................................................................... 82
Temporary stop ................................................................................................... 82
Seasonal stop ..................................................................................................... 82
EMERGENCY STOP ................................................................................................. 83
TROUBLESHOOTING ................................................................................................ 83
CHECKS DURING OPERATION .................................................................................. 91
INTRODUCTION ...................................................................................................... 91
Checking the refrigerant charge ........................................................................... 91
CALIBRATION OF CONTROL EQUIPMENT .................................................................. 92
INTRODUCTION ...................................................................................................... 92
TABLE 3 - CALIBRATION OF CONTROL EQUIPMENT .............................................. 92
TABLE 4 - CALIBRATION OF SAFETY DEVICES ....................................................... 90
MAINTENANCE AND PERIODIC CHECKS ................................................................. 93
WARNINGS ........................................................................................................... 93
INTRODUCTION ...................................................................................................... 93
REPAIRING THE REFRIGERANT CIRCUIT .................................................................... 94
Leak test ........................................................................................................... 94
High vacuum and dehydration of the refrigerant circuit .......................................... 94
Refrigerant charge ............................................................................................... 95
ENVIRONMENTAL CONSIDERATIONS ....................................................................... 95
DECOMMISSIONING THE UNIT ................................................................................ 96
REFRIGERANT CIRCUIT ........................................................................................ 97
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CIRCUIT CONNECTIONS ....... 109
Blue Box
ZETA 2002 - water chiller
Air-cooled liquid chillers with hermetic scroll compressors and plate type evaporator, suitable for outdoor installations.
The unit has a refrigerant circuit for each pair of compressors.
UNIT FRAME
Self supporting frame with removable panels, internally coated with expanded polyurethane sound-absorbing material; constructed from galvanized sheet steel with RAL 5014 powder paint baked at 180°C to provide a durable weatherproof finish. Threaded fasteners in stainless steel.
COMPRESSORS
Hermetic scroll type with orbital motion, connected in tandem and equipped with oil level sight glass, Klixon internal thermal protection and oil equalisation line.
The compressors are housed in a sound insulated compartment and separated from the air flow; access is provided by removable panels which allow maintenance work to be performed in safety even when the unit is in operation.
CONDENSER
Composed of a high efficiency coil manufactured from copper tubes and aluminium fins.
The finned coil is protected by a metal grille which is installed as standard.
CONDENSER FANS
Axial fans directly coupled to 6 pole motors with internal Klixon overload protection.
Motor protection category is IP 54. The fan is equipped with a safety grille to UNI EN 294.
EVAPORATOR
Brazed plate type in 316 AISI stainless steel. Thermal insulation of evaporator is provided by closed cell expanded material. Each evaporator is equipped with a low water temperature probe for freeze protection and each unit is equipped as standard with a mechanical flow switch.
REFRIGERANT CIRCUIT
Comprising: liquid valve, charge connection, liquid sight-glass, filter/dryer, thermostatic expansion valve with external pressure equalisation, high and low pressure switches for 2-compressor models.
For 4-compressor models high and low pressure values and relative condensation and evaporation temperatures are measured by pressure transducers that relay the signals to the controller so that they can be read directly on the display. The high pressure side of the circuit is equipped with high pressure switches and relief valves.
ELECTRICAL PANEL
The electrical panel includes:
- main switch
- thermal magnetic circuit-breakers for fans and (if present) pumps; compressor fuses for the power circuit
- compressor contactors
- fan contactors
- pump contactors (ST version)
The microprocessor controls the following functions on all units:
- water temperature regulation
- freeze protection
- compressor time intervals
- compressor start sequence and automatic lead/lag selection
- alarm reset
- common alarm contact for remote signalling
- operating and alarm indicator LEDs
Blue Box - 1
LCD display of the following information:
- water inlet and outlet temperature
- programmed temperature set-point and differential
- alarms description
- compressor hours run meter for 4 compressor units:
- number of starts of the unit and the compressors
- high and low pressure values and relative condensation and evaporation temperature values.
Electrical power supply [V/f/Hz]: 400/3~/50 ±5%
CONTROLS AND SAFETY DEVICES
- chilled water temperature probe (at evaporator inlet)
- freeze protection probe at the outlet of each evaporator
- safety high pressure switch with manual reset
- low pressure switch (with manual reset controlled by the control)
- high pressure relief valve
- compressor over-temperature protection
- fan over-temperature protection
- mechanical flow switch, supplied as standard on all units, as kit for units 3.2 to 13.2 and factory installed for units 14.4 to 26.4.
TESTING
The units are subjected to a dry run in the factory and supplied complete with oil and refrigerant.
ZETA UNIT VERSIONS
ZETA 2002 /HP: reverse cycle heat pump
The heat pump version operates as a air cooled chiller in summer and a air to water heat pump in winter by reversing the refrigerant flow to suit the required operating mode.
- Refrigerant circuit:
4-way reversing valve, liquid receiver, second thermostatic valve.
- Electrical panel:
Microprocessor enabled for summer/winter changeover and automatic defrosting.
ZETA 2002 LE: condensing unit.
The basic ZETA 2002 model is not equipped with an evaporator or thermostatic valve.
Also the four compressor models are not supplied with a microprocessor controller. Liquid receivers can be supplied as an accessory. The solenoid valve on the liquid line is supplied as standard.
ZETA 2002 LE /HP: heat pump condensing unit.
The basic ZETA 2002/HP model is not equipped with an evaporator, a thermostatic valve and four compressor models are not supplied with a microprocessor controller. Liquid receivers can be supplied as an accessory. The solenoid valve on the liquid line is supplied as standard.
Blue Box - 2
HYDRAULIC MODULE OPTIONS
ZETA 2002 /ST 2PS : unit with storage tank and pumps.
In addition to the components of version ZETA 2002, this unit includes: insulated storage tank; run and standby circulating pumps, with automatic changeover for four compressor models and manual changeover for two compressor models;
Also provided are an expansion tank, check valves and gate valves.
Version ST is available in the following additional four configurations:
- ST 1PS : with 1 pump and tank;
- ST 2P : with 2 pumps and no tank;
- ST S : with tank and no pumps;
- ST 1P : with 1 pump and no tank.
ACCESSORY VERSIONS
ZETA 2002 /DC: unit with heat recovery condenser.
Not available for HP versions.
This accessory is available for the following models: 3.2-13.2 “1p-2p” 18.4-26.4”s”.
In addition to the components of version ZETA 2002, this unit includes a 100% heat recovery condenser for the production of hot water, a recovery water temperature control thermostat, and a recovery circuit safety pressure switch.
ZETA 2002 /DS: unit with desuperheaters
The brazed plate type desuperheater is arranged in series with the condensing coil. It is available for the following models: from 3.2 to 13.2 with “1p-2p” and from 14.4 to 26.4 “1p-2p-1ps-2ps-s”.
It is also available in the HP configuration. In this case the installation must be fitted with a shut-off valve on the water recovery circuit, to be closed during heat pump mode operation as described in the manual.
ZETA 2002 /LN: low noise unit
In addition to the components of version ZETA 2002, this unit includes: galvanised sheet steel compressor compartment with full sound insulation using expanded polyurethane sound absorption material and expanded polyurethane with an intermediate layer of high acoustic impedance material applied to the sides of the compartment.
ZETA 2002 /SLN: extra low noise unit
In addition to the components of version LN, this unit is designed to operate with a slower fan speed to further reduce noise levels.
Blue Box - 3
REFRIGERANT CIRCUIT ACCESSORIES:
- Step type condensing pressure control
(ambient air minimum temperature 0 °C).
The control is managed in On/Off mode by the microprocessor by means of the pressure transducers.
Available for models 18.4 to 26.4 only.
- Condensing pressure control by fan speed regulator
(ambient air minimum temperature -20 °C).
Fan speed is regulated in accordance with the condensation pressure read by the pressure transducers.
Available for all models.
- Dual set-point.
With double thermostatic valves + solenoid valves. In units with two compressors the set-point must be modified manually on the controller. For four compressor units two set-points can be programmed and switched between them from the keypad or using a digital input. The type of selection must be specified at the time of the order. In all cases the thermostatic valves switch automatically on the basis of the water temperature.
- Pressure gauges.
Available for all models. Note however that on 4-compressor units the suction and discharge pressure values are read by transducers that relay the results to the controller display.
- Liquid receivers
(standard on versions /HP and /HP/LE)
- Compressor suction and discharge valves
- Liquid line solenoid valve
.
HYDRAULIC CIRCUIT ACCESSORIES
- Leaving water temperature control.
Available only on 4-compressor models (not HP versions).
- Anti-freeze heater
- Water side relief valve (version ST only).
The value is set at 6 bar, corresponding to the maximum permissible working pressure.
ELECTRICAL ACCESSORIES
- Serial interface:
- 2-compressor units are equipped with RS485 type serial interface with Carel protocol.
- 4-compressor units are equipped with RS485 type serial interface with Modbus protocol; the following optional protocols are available on request: Carel; Echelon in version RS485 or in version FTT10
- Power factor correction cos φ ≥ 0.9 at nominal operating conditions
- Single voltage-free contacts for machine status signals
- Set-point variable in a range of 3 °C with remote signal (0-1V, 0-10V, 0-4mA, 0-20mA).
Available only for models from 16.4 to 26.4
- Remote user terminal panel (in addition to the standard terminal)
Blue Box - 4
VARIOUS ACCESSORIES
- Rubber anti-vibration mountings.
Available for all models in the series
- Spring type anti-vibration mounts.
Available for models 18.4 to 26.4
- Timber crate packing
- Pallet/skid for container shipment
- Mesh coil guard with metallic filter.
Standard equipment on models from 14.4 to 26.4.
- Anti-corrosion treatment of coils for use in aggressive environments
- Non-standard RAL paint colours
Blue Box - 5
SERIES
The ZETA 2002 series of water cooled chillers and heat pumps, are available in various sizes with capacities from
38 to 266 kW.
Model designations consist of two numbers:
Shows the model
ZETA 2002 14.4
number of compressors
The model, serial number, characteristics, power supply, etc. are shown by means of decals on the unit.
Modello/Model
Modell/Modèle
Via Enrico Mattei, 20
35028 Piove di Sacco (PD)
ITALY
Tel. +039.049.9716300
0062
Matricola/Serial number
(BBOX) Matrikel/Matricule
Tensione-Fasi-Frequenza
Voltage-Phasses-Frequency
Spannung-Phasses-Frequenz
Tension-Phasses-Fréquence
Tensione circuiti ausiliari
Auxiliary circuit voltage
Steuerspannung
Tension circuits auxiliares
Corrente massima assorbita
Max absorbed current
Maximalstromverbrauch
Courant maxi absorbée
A
Tipo refrigerante
Refrigerant type
Kältemittel Typ
Type de refrigerant
Corrente massima di spunto
Max starting current
Max. Anlaufstrom
Courant maxi démarrage
IP quadro elettrico
IP electrical board
IP E-Schrank
IP tableau electrique
A
Numero circuiti refrigerante
Refrigerant circuit number
Anzahl des Kältemittelkreislaufes
Numero circuits refrigerant
Press. massima circuito refriger.
Max. Refrigerant circuit pressure
Max. Druck Kältekreislauf
Pression maxi circuit refrigerant kPa bar
Press. massima circuito idraulico
Max. Hydraultic circuit pressure
Max. Druck im Hydraul. Kreislauf
Pression maxi circuit hydraulique
Data di produzione
Manufacturing date
Erstellungsdatum
Date de fabrication kPa bar
Carica refrigerante per circuito(kg)/Refrigerant charge per circuit (kg)
/ Kältemittelfüllung Kreislauf (kg)/ Charge de refigerant chaque circuit (kg)
C1 C2 C3 C4
Via Enrico Mattei, 20
35028 Piove di Sacco (PD)
ITALY
Tel. +039.049.9716300
MODELLO - MODELE - MODEL - TYP
MATRICOLA - MATRICULE - SERIAL NO. - SERIENUMMER
0062
REFRIGERANTE - REFRIGERANT - KÄLTEMITTEL - REFRIGERANT
MODELLO
MATRICOLA
Via Enrico Mattei, 20
35028 Piove di Sacco (PD)
ITALY
Tel. +039.049.9716300
REFRIGERANTE
MODELLO - MODELE - MODEL - TYP
ESECUZIONE SECONDO
NORMATIVE
SCHEMA FRIGORIFERO
DISEGNO MECCANICO
0062
MODELLO MODELE
MODEL -TYP
MATRICOLA - MATRICULE
SERIAL NO. - SERIENUMMER
Buono di Produzione Buono di Produzione
Blue Box - 6
TECHNICAL DATA
R22 refrigerant
MODEL ZETA 2002
Cooling (*)
Nominal capacity
Evaporator water flow
Evaporator pressure drop
Heating (**)
Nominal capacity
Condenser water flow
Condenser pressure drop
Compressors
Quantity
Refrigerant circuits
Absorbed power cooling (*)
Absorbed power heating (**)
Capacity steps
Condenser cooling fans
Total air flow
Fan motor power
Nominal revolution speed
Electric motor supply
Refrigerant charge
Chiller version
Heat pump version
Oil
Oil charge
Oil producer
Oil type
Evaporator
Heat exchanger water volume
Max operating pressure water side
Dimension and weight
Length
Width
Heigth
Shipping weight l type l bar mm mm mm kg kW l/s l/h kPa kW l/s l/h kPa type n n kW kW
% type m
3
/s m 3 /h n x kW
RPM
V/Ph/Hz kg kg
3.2
38,4
1,835
6.607
59,1
38,4
1,833
6.600
59
2
1
12
12,8
0/50/100
4,472
16.100
2 x 0,6
1 x 14,5
1 x 15
2 x 3,3
4,6
2.233
1.043
1.740
594
4.2
5.2
47,1
2,251
8.105
59,2
52,9
2,528
9.102
46,9
46,9
2,239
8.061
58,6
53,2
2,540
9.146
47,3 scroll
2
1
14,3
15,4
0/50/100
2
1
16,5
16,9
0/50/100 axial
4,472
16.100
2 x 0,6
860
230/~/50
4,472
16.100
2 x 0,6
1 x 14,5
1 x 15
1 x 14,5
1 x 15
1 x 19,5
1 x 22
2 x 3,3
Maneurop
2 x 3,8
160 P plate
5,7 7,4
30
2.233
1.043
1.740
604
2.233
1.043
1.740
625
1 x 4 + 1 x 3,8
8,4
2.233
1.043
1.740
672
6.2
61,6
2,943
10.596
51,5
60,8
2,907
10.466
50,3
2
1
18,7
19,5
0/50/100
4,528
16.300
2 x 0,6
(*) ambient air temperature 35°C; evaporator entering/leaving water temperature 12-7 °C;.
(**) ambient air temperature 8°C DB, 70%RH; condenser entering/leaving water temperature 40-45 °C.
Blue Box - 7
TECHNICAL DATA
R22 refrigerant
MODEL ZETA 2002
Cooling (*)
Nominal capacity
Evaporator water flow
Evaporator pressure drop
Heating (**)
Nominal capacity
Condenser water flow
Condenser pressure drop
Compressors
Quantity
Refrigerant circuits
Absorbed power cooling (*)
Absorbed power heating (**)
Capacity steps
Condenser cooling fans
Total air flow
Fan motor power
Nominal revolution speed
Electric motor supply
Refrigerant charge
Chiller version
Heat pump version
Oil
Oil charge
Oil producer
Oil type
Evaporator
Heat exchanger water volume
Max operating pressure water side
Dimension and weight
Length
Width
Heigth
Shipping weight type l bar mm mm mm kg kW l/s l/h kPa kW kW
% type m 3 /s m 3 /h n x kW
RPM
V/Ph/Hz kW l/s l/h kPa type n n kg kg
7.2
68,9
3,292
11.852
43,8
68,5
3,274
11.787
43,3
2
1
21,7
22,1
0/50/100
4,528
16.300
2 x 0,6
1 x 19,5
1 x 22 l
8.2
9.2
78,9
3,771
13.577
45,2
93,4
4,460
16.057
47,9
79,7
3,807
13.704
46
92,6
4,425
15.931
47,2 scroll
2
1
25
25,5
0/50/100
2
1
29,7
29,8
0/50/100 axial
4,389
15.800
2 x 0,6
860
230/~/50
6,833
24.600
3 x 0,6
1 x 22
1 x 27
1 x 27,5
1 x 32
1 x 27,5
1 x 32
2 x 4
4,2
160 P
2 x 6,6 1 x 8 + 1 x 6,6
Maneurop
320 SZ plate
4,8 6,3
30
2 x 8
7,3
2.233
1.043
1.740
690
2.233
1.043
1.740
737
3.234
1.144
1.740
981
3.234
1.144
1.740
1.058
10.2
105,4
5,034
18.121
45,6
105,6
5,044
18.158
45,8
2
1
35,7
34,1
0/50/100
6,833
24.600
3 x 0,6
(*) ambient air temperature 35°C; evaporator entering/leaving water temperature 12-7 °C;.
(**) ambient air temperature 8°C DB, 70%RH; condenser entering/leaving water temperature 40-45 °C.
Blue Box - 8
TECHNICAL DATA
R22 refrigerant
MODEL ZETA 2002
Cooling (*)
Nominal capacity
Evaporator water flow
Evaporator pressure drop
Heating (**)
Nominal capacity
Condenser water flow
Condenser pressure drop
Compressors
Quantity
Refrigerant circuits
Absorbed power cooling (*)
Absorbed power heating (**)
Capacity steps
Condenser cooling fans
Total air flow
Fan motor power
Nominal revolution speed
Electric motor supply
Refrigerant charge
Chiller version
Heat pump version
Oil
Oil charge
Oil producer
Oil type
Evaporator
Heat exchanger water volume
Max operating pressure water side
Dimension and weight
Length
Width
Heigth
Shipping weight type l bar mm mm mm kg kW l/s l/h kPa kW l/s l/h kPa type n n kW kW
% type m 3 /s m 3 /h n x kW
RPM
V/Ph/Hz kg kg
12.2
13.2
14.4
16.4
120,4
5,754
20.715
50,9
130,3
6,225
22.409
44
139,4
6,659
23.974
51,6
159,6
7,626
27.453
55,1
118,4
5,656
20.362
49,2
2
1
38,1
37,7
0/50/100
6,600
23.760
3 x 0,6
230/~/50
131,2
6,268
22.566
44,6
2
1
43,6
41,3
0/50/100
6,583
23.700
3 x 0,6
137,1
6,548
23.573
50
159,4
7,614
27.409
55 scroll
4 4
44,1 51
0/25/50/75/100 0/25/50/75/100 axial
2
42,6
2
49
11,267
40.560
2 x 2,0
11,267
40.560
2 x 2,0
860
400/3~/50
1 x 32
1 x 36
1 x 32
1 x 36
2 x 19,5
2 x 22
2 x 21
2 x 23 l 2 x 8
8,4
320 SZ
2 x 8
Maneurop
4 x 4 plate
9,4 5,2
30
160 P
4 x 6,6
4,8
3.234
1.144
1.740
1.124
3.234
1.144
1.740
1.158
3.234
1.119
2.380
1.400
3.234
1.119
2.380
1.464
(*) ambient air temperature 35°C; evaporator entering/leaving water temperature 12-7 °C;.
(**) ambient air temperature 8°C DB, 70%RH; condenser entering/leaving water temperature 40-45 °C.
Blue Box - 9
TECHNICAL DATA
R22 refrigerant
MODEL ZETA 2002
Cooling (*)
Nominal capacity
Evaporator water flow
Evaporator pressure drop
Heating (**)
Nominal capacity
Condenser water flow
Condenser pressure drop
Compressors
Quantity
Refrigerant circuits
Absorbed power cooling (*)
Absorbed power heating (**)
Capacity steps
Condenser cooling fans
Total air flow
Fan motor power
Nominal revolution speed
Electric motor supply
Refrigerant charge
Chiller version
Heat pump version
Oil
Oil charge
Oil producer
Oil type
Evaporator
Heat exchanger water volume
Max operating pressure water side
Dimension and weight
Length
Width
Heigth
Shipping weight
18.4
20.4
24.4
26.4
kW l/s l/h kPa
188,8
9,019
32.469
61,6
215,5
10,298
37.073
64
240,9
11,508
41.430
71,4
266,2
12,718
45.786
70,9
% type m 3 /s m 3 /h n x kW
RPM
V/Ph/Hz kW l/s l/h kPa type n n kW kW
185,2
8,851
31.863
59,4
211,1
10,088
36.316
61,6
236,8
11,312
40.724
69,1
262,4
12,536
45.131
68,9 scroll
4
2
58,2
59,6
4
2
68,7
68,2
4
2
76,3
75,4
4
2
83,9
82,7
0/25/50/75/100 0/25/50/75/100 0/25/50/75/100 0/25/50/75/100 axial
16,417 19,389 16,375
58.950
3 x 2,0
59.100
3 x 2,0
880
400/3~/50
69.800
4 x 2,0
18,500
66.600
4 x 2,0 kg kg
2 x 27
2 x 30
2 x 27
2 x 30
2 x 26
2 x 30
2 x 31,5
2 x 35
4 x 8 l 2 x 8 + 2 x 6,6 type l bar mm mm mm kg
6,3
4.234
1.119
2.380
1.930
4 x 8
Maneurop
320 SZ plate
7,3
30
4 x 8
8,4
4.234
1.119
2.380
2.089
4.234
1.119
2.380
2.208
9,4
4.234
1.119
2.380
2.349
(*) ambient air temperature 35°C; evaporator entering/leaving water temperature 12-7 °C;.
(**) ambient air temperature 8°C DB, 70%RH; condenser entering/leaving water temperature 40-45 °C.
Blue Box - 10
TECHNICAL DATA - ELECTRICAL CHARACTERISTICS AND COMPONENTS
R22 refrigerant
MODEL ZETA 2002
Maximum absorbed power (1)
Maximum starting current
Full load current (2)
Fan motor nominal power
Fan motor nominal absorbed current
Pump motor nominal power
Pump motor nominal absorbed power
Power supply
Control power supply
Control circuit supply
Condenser fans supply
Pump supply, ST groups
MODEL ZETA 2002
Maximum absorbed power (1)
Maximum starting current
Full load current (2)
Fan motor nominal power
Fan motor nominal absorbed current
Pump motor nominal power
Pump motor nominal absorbed power
Power supply
Control power supply
Control circuit supply
Condenser fans supply
Pump supply, ST groups kW kW
A
A
A
A n x kW n x A kW
A
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
3.2
17,6
(18,1)
120,4
(122,1)
39,4
(41,1)
2 x 0,6
2 x 2,7
(1 x 0,5)
(1 x 1,7)
4.2
5.2
19,6
(20,1)
155,4
(157,1)
24
(24,5)
150,4
(152,1)
45,4
(47,1)
2 x 0,6
2 x 2,7
55,4
(57,1)
2 x 0,6
2 x 2,7
(1 x 0,5)
(1 x 1,7)
(1 x 0,5)
(1 x 1,7)
400V 3N ~ 50Hz ±5% V
230V/ ~/50Hz
24V/~/50Hz
230V/ ~/50Hz
400V/3~/50
6.2
27
(28,1)
205,4
(208,3)
65,4
(68,3)
2 x 0,6
2 x 2,7
(1 x 1,1)
(1 x 2,9) kW kW
A
A
A
A n x kW n x A kW
A
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
7.2
30
(31,1)
215,4
(218,3)
75,4
(78,3)
2 x 0,6
2 x 2,7
(1 x 1,1)
(1 x 2,9)
8.2
9.2
35,2
(36,3)
215,4
(218,3)
41,7
(43,2)
258,1
(262,4)
75,4
(78,3)
2 x 0,6
2 x 2,7
93,1
(97,4)
3 x 0,6
3 x 2,7
(1 x 1,1)
(1 x 2,9)
(1 x 1,5)
(1 x 4,3)
400V 3N ~ 50Hz ±5% V
230V/ ~/50Hz
24V/~/50Hz
230V/ ~/50Hz
400V/3~/50
10.2
47,6
(49,1)
273,1
(277,4)
108,1
(112,4)
3 x 0,6
3 x 2,7
(1 x 1,5)
(1 x 4,3)
(1) mains power supply to allow unit operation.
(2) maximum current before safety cut-outs stop the unit. This value is never exceeded and must be used to size the electrical supply cables and relevant safety devices (refer to electrical wiring diagram supplied with the unit).
All values in brackets are refer to /ST version (units with storage tank) or units with pump.
Blue Box - 11
TECHNICAL DATA - ELECTRICAL CHARACTERISTICS AND COMPONENTS
R22 refrigerant
MODEL ZETA 2002
Maximum absorbed power (1)
Maximum starting current
Full load current (2)
Fan motor nominal power
Fan motor nominal absorbed current
Pump motor nominal power
Pump motor nominal absorbed power
Power supply
Control power supply
Control circuit supply
Condenser fans supply
Pump supply, ST groups
MODEL ZETA 2002
Maximum absorbed power (1)
Maximum starting current
Full load current (2)
Fan motor nominal power
Fan motor nominal absorbed current
Pump motor nominal power
Pump motor nominal absorbed power
Power supply
Control power supply
Control circuit supply
Condenser fans supply
Pump supply, ST groups kW kW
A
A
A
A n x kW n x A kW
A
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
12.2
13.2
14.4
16.4
52,4
(54,6)
328,1
(333,4)
127,1
57,2
(59,4)
347,1
(352,4)
146,1
61,6
(63,8)
288
(293,3)
148
72
(74,2)
288
(293,3)
148
(132,4)
3 x 0,6
3 x 2,7
(1 x 2,2)
(1 x 5,3)
(151,4)
3 x 0,6
3 x 2,7
(1 x 2,2)
(153,3)
2 x 2,0
2 x 4,0
(1 x 2,2)
(1 x 5,3) (1 x 5,3)
400V 3N ~ 50Hz ±5% V
230V/ ~/50Hz
24V/~/50Hz
230V/ ~/50Hz
400V/3~/50
400V/3~/50
(153,3)
2 x 2,0
2 x 4,0
(1 x 2,2)
(1 x 5,3) kW kW
A
A
A
A n x kW n x A kW
A
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
18.4
85,8
(89,8)
347
(356,5)
182
(191,5)
3 x 2,0
3 x 4,0
(1 x 4,0)
(1 x 9,5)
20.4
24.4
26.4
97,6
(101,6)
377
(386,5)
212
(221,5)
3 x 2,0
3 x 4,0
109,2
(113,2
455
(464,5)
254
(263,5)
4 x 2,0
4 x 4,0
118,8
(124,3)
493
(505)
292
(304)
4 x 2,0
4 x 4,0
(1 x 4,0)
(1 x 9,5)
(1 x 4,0) (1 x 5,5)
(1 x 9,5) (1 x 12,0)
400V 3N ~ 50Hz ±5% V
230/~/50
24V ~ 50Hz
400V/3~/50
400V/3~/50
(1) mains power supply to allow unit operation.
(2) maximum current before safety cut-outs stop the unit. This value is never exceeded and must be used to size the electrical supply cables and relevant safety devices (refer to electrical wiring diagram supplied with the unit).
All values in brackets are refer to /ST version (units with storage tank) or units with pump.
Blue Box - 12
TECHNICAL DATA - ZETA 2002 /ST 2PS
R22 refrigerant
MODEL ZETA 2002
Pump section
Evaporator water flow
Pump nominal power
External available pressure
Storage tank water volume
Dimension and weight
Length
Width
Heigth
Shipping weight
MODEL ZETA 2002
Pump section
Evaporator water flow
Pump nominal power
External available pressure
Storage tank water volume
Dimension and weight
Length
Width
Heigth
Shipping weight
MODEL ZETA 2002
Pump section
Evaporator water flow
Pump nominal power
External available pressure
Storage tank water volume
Dimension and weight
Length
Width
Heigth
Shipping weight
MODEL ZETA 2002
Pump section
Evaporator water flow
Pump nominal power
External available pressure
Storage tank water volume
Dimension and weight
Length
Width
Heigth
Shipping weight l/s l/h kW kPa l mm mm mm kg l/s l/h kW kPa l mm mm mm kg l/s l/h kW kPa l mm mm mm kg l/s l/h kW kPa l mm mm mm kg
5,03
18.121
1,5
107
450
3.234
1.144
1.740
1.219
16.4
6.2
2,94
10.596
1,1
139
200
2.233
1.043
1.740
807
10.2
7,63
27.453
2,2
98
340
3.234
1.119
2.380
1.678
26.4
12,72
45.786
5,5
159
700
5.234
1.119
2.380
2.749
4,46
16.057
1,5
122
450
3.234
1.144
1.740
1.142
14.4
5.2
2,53
9.102
0,5
93
200
2.233
1.043
1.740
755
9.2
6,66
23.974
2,2
134
340
3.234
1.119
2.380
1.642
24.4
11,51
41.430
4
100
700
5.234
1.119
2.380
2.622
3,77
13.577
1,1
113
200
2.233
1.043
1.740
868
13.2
4.2
2,25
8.105
0,5
95
200
2.233
1.043
1.740
734
8.2
6,23
22.409
2,2
108
450
3.234
1.144
1.740
1.309
20.4
10,30
37.073
4
123
700
5.234
1.119
2.380
2.449
3,29
11.852
1,1
134
200
2.233
1.043
1.740
825
12.2
3.2
1,84
6.607
0,5
114
200
2.233
1.043
1.740
724
7.2
5,75
20.715
2,2
114
450
3.234
1.144
1.740
1.275
18.4
9,02
32.469
4
139
700
5.234
1.119
2.380
2.290
Blue Box - 13
TECHNICAL DATA
R407C refrigerant
MODEL ZETA 2002
Cooling (*)
Nominal capacity
Evaporator water flow
Evaporator pressure drop
Heating (**)
Nominal capacity
Condenser water flow
Condenser pressure drop
Compressors
Quantity
Refrigerant circuits
Absorbed power cooling (*)
Absorbed power heating (**)
Capacity steps
Condenser cooling fans
Total air flow
Fan motor power
Nominal revolution speed
Electric motor supply
Refrigerant charge
Chiller version
Heat pump version
Oil
Oil charge
Oil producer
Oil type
Evaporator
Heat exchanger water volume
Max operating pressure water side
Dimension and weight
Length
Width
Heigth
Shipping weight l type l bar mm mm mm kg kW l/s l/h kPa kW l/s l/h kPa type n n kW kW
% type m
3
/s m 3 /h n x kW
RPM
V/Ph/Hz kg kg
3.2
37,1
1,77
6.377
57,2
36,4
1,74
6.267
55,3
2
1
12,3
12,7
0-50-100
4,47
16.100
2 x 0,6
1 x 14,5
1 x 15
2 x 3,3
4,6
2.233
1.043
1.740
594
4.2
1 x 15
5.2
44,7
2,13
7.682
55,4
51,4
2,45
8.833
45,9
44,8
2,14
7.698
55,6
51,9
2,48
8.923
46,8 scroll
2
1
14,8
15,9
0-50-100
2
1
17,5
18,4
0-50-100 axial
4,47
16.100
2 x 0,6
860
230/~/50
4,47
16.100
2 x 0,6
1 x 14,5 1 x 14,5
1 x 15
1 x 19,5
1 x 22
2 x 3,3
Maneurop
2 x 3,8
160 SZ plate
5,7 7,4
30
2.233
1.043
1.740
604
2.233
1.043
1.740
625
1 x 4 + 1 x 3,8
8,4
2.233
1.043
1.740
672
6.2
60,3
2,88
10.379
51,4
60
2,87
10.318
50,8
2
1
19,7
20,9
0-50-100
4,53
16.300
2 x 0,6
(*) ambient air temperature 35°C; evaporator entering/leaving water temperature 12-7 °C;.
(**) ambient air temperature 8°C DB, 70%RH; condenser entering/leaving water temperature 40-45 °C.
Blue Box - 14
TECHNICAL DATA
R407C refrigerant
MODEL ZETA 2002
Cooling (*)
Nominal capacity
Evaporator water flow
Evaporator pressure drop
Heating (**)
Nominal capacity
Condenser water flow
Condenser pressure drop
Compressors
Quantity
Refrigerant circuits
Absorbed power cooling (*)
Absorbed power heating (**)
Capacity steps
Condenser cooling fans
Total air flow
Fan motor power
Nominal revolution speed
Electric motor supply
Refrigerant charge
Chiller version
Heat pump version
Oil
Oil charge
Oil producer
Oil type
Evaporator
Heat exchanger water volume
Max operating pressure water side
Dimension and weight
Length
Width
Heigth
Shipping weight l type l bar mm mm mm kg kW l/s l/h kPa kW l/s l/h kPa type n n kW kW
% type m
3
/s m 3 /h n x kW
RPM
V/Ph/Hz kg kg
7.2
67,5
3,23
11.608
43,7
68,1
3,25
11.712
44,4
2
1
22,7
23,4
0-50-100
4,53
16.300
2 x 0,6
1 x 19,5
1 x 22
2 x 4
4,2
2.233
1.043
1.740
690
8.2
9.2
77,6
3,71
13.347
45,4
91,6
4,37
15.748
47,9
78,7
3,76
13.530
46,5
92,7
4,43
15.937
49 scroll
2
1
26,6
27,5
0-50-100
2
1
31,3
32,1
0-50-100 axial
4,39
15.800
2 x 0,6
860
230/~/50
6,83
24.600
3 x 0,6
1 x 22
1 x 27
1 x 27,5
1 x 32
2 x 6,6 1 x 8 + 1 x 6,6
Maneurop
160 SZ plate
4,8 6,3
30
2.233
1.043
1.740
737
3.234
1.144
1.740
981
1 x 27,5
1 x 32
2 x 8
7,3
3.234
1.144
1.740
1.058
10.2
102,4
4,89
17.611
44,8
106,6
5,10
18.343
48,4
2
1
37,6
36,7
0-50-100
6,83
24.600
3 x 0,6
(*) ambient air temperature 35°C; evaporator entering/leaving water temperature 12-7 °C;.
(**) ambient air temperature 8°C DB, 70%RH; condenser entering/leaving water temperature 40-45 °C.
Blue Box - 15
TECHNICAL DATA
R407C refrigerant
MODEL ZETA 2002
Cooling (*)
Nominal capacity
Evaporator water flow
Evaporator pressure drop
Heating (**)
Nominal capacity
Condenser water flow
Condenser pressure drop
Compressors
Quantity
Refrigerant circuits
Absorbed power cooling (*)
Absorbed power heating (**)
Capacity steps
Condenser cooling fans
Total air flow
Fan motor power
Nominal revolution speed
Electric motor supply
Refrigerant charge
Chiller version
Heat pump version
Oil
Oil charge
Oil producer
Oil type
Evaporator
Heat exchanger water volume
Max operating pressure water side
Dimension and weight
Length
Width
Heigth
Shipping weight kW l/s l/h kPa kW l/s l/h kPa type n n kW kW
% type m 3 /s m 3 /h n x kW
RPM
V/Ph/Hz kg kg
12.2
13.2
14.4
16.4
117,9
5,63
20.283
50,7
126,6
6,05
21.780
43,2
137
6,55
23.567
51,8
157,6
7,53
27.103
55,8
119,5
5,71
20.561
52
2
1
40
40,5
0-50-100
6,60
23.760
3 x 0,6
132,4
6,33
22.779
47
136,2
6,51
23.425
51,2
157,3
7,52
27.061
55,6 scroll
2
1
45,9
44,4
4
2
44,4
46,8
4
2
52
55
0-50-100 0-25-50-75-100 0-25-50-75-100 axial
6,58
23.700
3 x 0,6
11,27
40.560
2 x 2,0
11,27
40.560
2 x 2,0
860
230/~/50 400/3~/50
1 x 32
1 x 36
1 x 32
1 x 36
2 x 19,5
2 x 22
2 x 21
2 x 23 l type l bar mm mm mm kg
2 x 8
8,4
3.234
1.144
1.740
1.124
2 x 8
Maneurop
160 SZ plate
9,4
30
4 x 4
5,2
3.234
1.144
1.740
1.158
3.234
1.119
2.380
1.400
4 x 6,6
4,8
3.234
1.119
2.380
1.464
(*) ambient air temperature 35°C; evaporator entering/leaving water temperature 12-7 °C;.
(**) ambient air temperature 8°C DB, 70%RH; condenser entering/leaving water temperature 40-45 °C.
Blue Box - 16
TECHNICAL DATA
R407C refrigerant
MODEL ZETA 2002
Cooling (*)
Nominal capacity
Evaporator water flow
Evaporator pressure drop
Heating (**)
Nominal capacity
Condenser water flow
Condenser pressure drop
Compressors
Quantity
Refrigerant circuits
Absorbed power cooling (*)
Absorbed power heating (**)
Capacity steps
Condenser cooling fans
Total air flow
Fan motor power
Nominal revolution speed
Electric motor supply
Refrigerant charge
Chiller version
Heat pump version
Oil
Oil charge
Oil producer
Oil type
Evaporator
Heat exchanger water volume
Max operating pressure water side
Dimension and weight
Length
Width
Heigth
Shipping weight
18.4
20.4
24.4
26.4
kW l/s l/h kPa
185,8
8,88
31.965
62
211
10,08
36.296
63,8
235,8
11,27
40.565
71,1
260,7
12,45
44.834
70,6
% type m 3 /s m 3 /h n x kW
RPM
V/Ph/Hz kW l/s l/h kPa type n n kW kW
185,3
8,85
31.873
61,6
213,3
10,19
36.686
65,1
239,1
11,42
41.122
73
264,9
12,66
45.558
72,8 scroll
4
2
61,2
64,2
4
2
72
73,3
4
2
80
81,1
4
2
88,1
88,8
0-25-50-75-100 0-25-50-75-100 0-25-50-75-100 0-25-50-75-100 axial
16,42 19,39 16,38
58.950
3 x 2,0
59.100
3 x 2,0
880
400/3~/50
69.800
4 x 2,0
18,50
66.600
4 x 2,0 kg kg
2 x 27
2 x 30
2 x 27
2 x 30
2 x 26
2 x 30
2 x 31,5
2 x 35
4 x 8 l 2 x 8 + 2 x 6,6 type l bar mm mm mm kg
6,3
4.234
1.119
2.380
1.930
4 x 8
Maneurop
160 SZ plate
7,3
30
4 x 8
8,4
4.234
1.119
2.380
2.089
4.234
1.119
2.380
2.208
9,4
4.234
1.119
2.380
2.349
(*) ambient air temperature 35°C; evaporator entering/leaving water temperature 12-7 °C;.
(**) ambient air temperature 8°C DB, 70%RH; condenser entering/leaving water temperature 40-45 °C.
Blue Box - 17
TECHNICAL DATA - ELECTRICAL CHARACTERISTICS AND COMPONENTS
R407C refrigerant
MODEL ZETA 2002
Maximum absorbed power (1)
Maximum starting current
Full load current (2)
Fan motor nominal power
Fan motor nominal absorbed current
Pump motor nominal power
Pump motor nominal absorbed power
Power supply
Control power supply
Control circuit supply
Condenser fans supply
Pumps supply, ST groups
Maximum absorbed power
(1)
Maximum starting current
Full load current (2)
Fan motor nominal power
Fan motor nominal absorbed current
Pump motor nominal power
Pump motor nominal absorbed power
Power supply
Control power supply
Control circuit supply
Condenser fans supply
Pumps supply, ST groups kW kW
A
A
A
A n x kW n x A kW
A
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
3.2
17,6
(18,1)
120,4
(122,1)
39,4
(41,1)
2 x 0,6
2 x 2,7
(1 x 0,5)
(1 x 1,7)
4.2
5.2
20,6
(21,1)
155,4
(157,1)
25,6
(26,1)
150,4
(152,1)
45,4
(47,1)
2 x 0,6
2 x 2,7
55,4
(57,1)
2 x 0,6
2 x 2,7
(1 x 0,5)
(1 x 1,7)
(1 x 0,5)
(1 x 1,7)
400V 3N ~ 50Hz ±5% V
230/~/50
24V ~ 50Hz
230V/ ~/50Hz
400V/3~/50
6.2
28,5
(29,6)
205,4
(208,3)
65,4
(68,3)
2 x 0,6
2 x 2,7
(1 x 1,1)
(1 x 2,9) kW kW
A
A
A
A n x kW n x A kW
A
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
53,4
(55,6)
328,1
(333,4)
127,1
(132,4)
3 x 0,6
3 x 2,7
(1 x 2,2)
(1 x 5,3)
58,4
(60,6)
347,1
(352,4)
64,4
(66,6)
288
(293,3)
146,1
(151,4)
3 x 0,6
3 x 2,7
148
(153,3)
2 x 2,0
2 x 4,0
(1 x 2,2)
(1 x 5,3)
(1 x 2,2)
(1 x 5,3)
400V 3N ~ 50Hz ±5% V
230/~/50
24V ~ 50Hz
230V/ ~/50Hz
400V/3~/50
76,4
(78,6)
288
(293,3)
148
(153,3)
2 x 2,0
2 x 4,0
(1 x 2,2)
(1 x 5,3)
(1) mains power supply to allow unit operation.
(2) maximum current before safety cut-outs stop the unit. This value is never exceeded and must be used to size the electrical supply cables and relevant safety devices (refer to electrical wiring diagram supplied with the unit).
All values in brackets are refer to /ST version (units with storage tank) or units with pump.
Blue Box - 18
TECHNICAL DATA - ELECTRICAL CHARACTERISTICS AND COMPONENTS
R407C refrigerant
Maximum absorbed power (1)
Maximum starting current
Full load current (2)
Fan motor nominal power
Fan motor nominal absorbed current
Pump motor nominal power
Pump motor nominal absorbed power
Power supply
Control power supply
Control circuit supply
Condenser fans supply
Pumps supply, ST groups kW kW
A
A
A
A n x kW n x A kW
A
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
53,4
(55,6)
328,1
(333,4)
127,1
(132,4)
3 x 0,6
3 x 2,7
(1 x 2,2)
(1 x 5,3)
58,4
(60,6)
347,1
(352,4)
64,4
(66,6)
288
(293,3)
146,1
(151,4)
3 x 0,6
3 x 2,7
148
(153,3)
2 x 2,0
2 x 4,0
(1 x 2,2)
(1 x 5,3)
(1 x 2,2)
(1 x 5,3)
400V 3N ~ 50Hz ±5% V
230/~/50
24V ~ 50Hz
230V/ ~/50Hz
400V/3~/50
76,4
(78,6)
288
(293,3)
148
(153,3)
2 x 2,0
2 x 4,0
(1 x 2,2)
(1 x 5,3)
Maximum absorbed power
(1)
Maximum starting current
Full load current (2)
Fan motor nominal power
Fan motor nominal absorbed current
Pump motor nominal power
Pump motor nominal absorbed power
Power supply
Control power supply
Control circuit supply
Condenser fans supply
Pumps supply, ST groups kW kW
A
A
A
A n x kW n x A kW
A
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
V/Ph/Hz
88,8
(92,8)
347
(356,5)
182
(191,5)
3 x 2,0
3 x 4,0
(1 x 4,0)
(1 x 9,5)
99,2
(103,2)
377
(386,5)
111,2
(115,2)
455
(464,5)
212
(221,5)
3 x 2,0
3 x 4,0
254
(263,5)
4 x 2,0
4 x 4,0
292
(304)
4 x 2,0
4 x 4,0
(1 x 4,0)
(1 x 9,5)
(1 x 4,0) (1 x 5,5)
(1 x 9,5) (1 x 12,0)
400V 3N ~ 50Hz ±5% V
230/~/50
24V ~ 50Hz
400V/3~/50
400V/3~/50
121,2
(126,7)
493
(505)
(1) mains power supply to allow unit operation.
(2) maximum current before safety cut-outs stop the unit. This value is never exceeded and must be used to size the electrical supply cables and relevant safety devices (refer to electrical wiring diagram supplied with the unit).
All values in brackets are refer to /ST version (units with storage tank) or units with pump.
Blue Box - 19
TECHNICAL DATA - ZETA 2002 /ST 2PS
R407C refrigerant
MODEL ZETA 2002
Pump section
Evaporator water flow
Pump nominal power
External available pressure
Storage tank water volume
Dimension and weight
Length
Width
Heigth
Shipping weight
MODEL ZETA 2002
Pump section
Evaporator water flow
Pump nominal power
External available pressure
Storage tank water volume
Dimension and weight
Length
Width
Heigth
Shipping weight
MODEL ZETA 2002
Pump section
Evaporator water flow
Pump nominal power
External available pressure
Storage tank water volume
Dimension and weight
Length
Width
Heigth
Shipping weight
MODEL ZETA 2002
Pump section
Evaporator water flow
Pump nominal power
External available pressure
Storage tank water volume
Dimension and weight
Length
Width
Heigth
Shipping weight l/s l/h kW kPa l mm mm mm kg l/s l/h kW kPa l mm mm mm kg l/s l/h kW kPa l mm mm mm kg l/s l/h kW kPa l mm mm mm kg
6.2
2,88
10.379
1,1
139
200
2.233
1.043
1.740
807
10.2
4,89
17.611
1,5
109
450
3.234
1.144
1.740
1.219
16.4
7,53
27.103
2,2
96
340
3.234
1.119
2.380
1.678
26.4
12,45
44.834
5,5
159
700
5.234
1.119
2.380
2.749
5.2
2,45
8.833
0,5
96
200
2.233
1.043
1.740
755
9.2
4,37
15.748
1,5
122
450
3.234
1.144
1.740
1.142
14.4
6,55
23.567
2,2
134
340
3.234
1.119
2.380
1.642
24.4
11,27
40.565
4
101
700
5.234
1.119
2.380
2.622
4.2
2,13
7.682
0,5
103
200
2.233
1.043
1.740
734
8.2
3,71
13.347
1,1
112
200
2.233
1.043
1.740
868
13.2
6,05
21.780
2,2
110
450
3.234
1.144
1.740
1.309
20.4
10,08
36.296
4
124
700
5.234
1.119
2.380
2.449
3.2
1,77
6.377
0,5
117
200
2.233
1.043
1.740
724
7.2
3,23
11.608
1,1
134
200
2.233
1.043
1.740
825
12.2
5,63
20.283
2,2
115
450
3.234
1.144
1.740
1.275
18.4
8,88
31.965
4
138
700
5.234
1.119
2.380
2.290
Blue Box - 20
SOUND POWER AND PRESSURE LEVELS
STANDARD UNITS
Z E T A
2002
63 dB
125 dB
250 dB
Octave band [Hz]
500 dB
1000 dB
2000 dB
4000 dB
8000 dB
Total dB(A)
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
3.2
96,1 78,8 87,3 70,0 81,2 63,8 79,7 62,4 78,6 61,3 73,2 55,9 69,8 52,4 60,7 43,4 83,0 65,7
4.2
96,5 79,1 87,7 70,3 81,5 64,2 80,0 62,7 78,9 61,6 73,6 56,2 70,1 52,8 61,0 43,7 83,3 66,0
5.2
96,6 79,2 87,8 70,4 81,6 64,3 80,1 62,8 79,0 61,7 73,7 56,3 70,2 52,9 61,1 43,8 83,4 66,1
6.2
97,3 79,9 88,5 71,1 82,3 65,0 80,8 63,5 79,7 62,4 74,4 57,0 70,9 53,6 61,8 44,5 84,1 66,8
7.2
97,5 80,1 88,7 71,3 82,5 65,2 81,0 63,7 79,9 62,6 74,6 57,2 71,1 53,8 62,0 44,7 84,3 67,0
8.2
98,1 80,8 89,3 72,0 83,2 65,8 81,7 64,4 80,6 63,2 75,2 57,9 71,8 54,4 62,7 45,3 85,0 67,7
9.2
99,7 81,8 90,9 73,0 84,8 66,8 83,3 65,4 82,2 64,2 76,9 58,9 73,4 55,4 64,3 46,3 86,6 68,7
10.2
100,0 82,0 91,2 73,2 85,0 67,0 83,5 65,6 82,4 64,5 77,1 59,1 73,6 55,6 64,5 46,6 86,8 68,9
12.2
100,1 82,2 91,3 73,4 85,1 67,3 83,7 65,8 82,6 64,7 77,2 59,3 73,7 55,9 64,7 46,8 87,0 69,1
13.2
100,3 82,3 91,5 73,5 85,3 67,3 83,8 65,9 82,7 64,8 77,4 59,4 73,9 55,9 64,8 46,9 87,1 69,2
14.4
101,1 82,5 92,3 73,7 86,1 67,5 84,6 66,0 83,5 64,9 78,2 59,6 74,7 56,1 85,6 47,0 87,9 69,3
16.4
103,6 85,0 94,8 76,2 88,6 70,1 87,2 68,6 86,1 67,5 80,7 62,1 77,2 58,7 68,2 49,6 90,5 71,9
18.4
104,5 85,4 95,7 76,6 89,6 70,5 88,1 69,0 87,0 67,9 81,6 62,5 78,2 59,1 69,1 50,0 91,4 72,3
20.4
105,2 86,1 96,4 77,3 90,3 71,2 88,8 69,7 87,7 68,6 82,3 63,2 78,9 59,8 69,8 50,7 92,1 73,0
24.4
106,1 87,0 97,3 78,2 91,2 72,1 89,7 70,6 88,6 69,5 83,2 64,1 79,8 60,7 70,7 51,6 93,0 73,9
26.4
106,2 87,1 97,4 78,3 91,3 72,2 89,8 70,7 88,7 69,6 83,3 64,2 79,9 60,8 70,8 51,7 93,1 74,0
LOW NOISE UNITS
Octave band [Hz]
Z E T A
2002
63 dB
125 dB
250 dB
500 dB
1000 dB
2000 dB
4000 dB
8000 dB
Total dB(A)
/LN Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
3.2
93,4 76,0 84,6 67,2 78,4 61,1 76,9 59,6 75,8 58,5 70,5 53,1 67,0 49,7 57,9 40,6 80,2 62,9
4.2
93,5 76,2 84,7 67,4 78,5 61,3 77,0 59,8 75,9 58,7 70,6 53,3 67,1 49,9 58,0 40,8 80,3 63,1
5.2
93,7 76,4 84,9 67,6 78,7 61,5 77,2 60,0 76,1 58,9 70,8 53,5 67,3 50,1 58,2 41,0 80,5 63,3
6.2
94,3 77,0 85,5 68,2 79,3 62,1 77,8 60,6 76,7 59,5 71,4 54,1 67,9 50,7 58,8 41,6 81,1 63,9
7.2
94,4 77,1 85,6 68,3 79,4 62,2 77,9 60,7 76,8 59,6 71,5 54,2 68,0 50,8 58,9 41,7 81,2 64,0
8.2
96,3 79,0 87,5 70,2 81,3 64,1 79,8 62,6 78,7 61,5 73,4 56,1 69,9 52,7 60,8 43,6 83,1 65,9
9.2
97,3 79,0 88,5 70,6 82,3 64,5 80,9 63,0 79,8 61,9 74,4 56,5 70,9 53,1 61,9 44,0 84,2 66,3
10.2
97,8 79,5 89,0 71,1 82,8 65,0 81,4 63,5 80,3 62,4 74,9 57,0 71,4 53,6 62,4 44,5 84,7 66,8
12.2
97,3 79,0 88,5 70,6 82,3 64,5 80,9 63,0 79,8 61,9 74,4 56,5 70,9 53,1 61,9 44,0 84,2 66,3
13.2
97,6 79,3 88,8 70,9 82,6 64,8 81,2 63,3 80,1 62,2 74,7 56,8 71,2 53,4 62,2 44,3 84,5 66,6
14.4
99,1 80,5 90,3 71,7 84,1 65,5 82,6 64,0 81,5 62,9 76,2 57,6 72,7 54,1 63,6 45,0 85,9 67,3
16.4
101,8 82,6 93,0 74,4 86,8 68,3 85,4 66,8 84,3 65,7 78,9 60,3 75,4 56,9 66,4 47,8 88,7 70,1
18.4
102,6 82,7 93,8 74,7 87,7 68,6 86,2 67,1 85,1 66,0 79,7 60,6 76,3 57,2 67,2 48,1 89,5 70,4
20.4
103,0 83,1 94,2 75,1 88,1 69,0 86,6 67,5 85,5 66,4 80,1 61,0 76,7 57,6 67,6 48,5 89,9 70,8
24.4
103,9 84,0 95,1 76,0 89,0 69,9 87,5 68,4 86,4 67,3 81,0 61,9 77,6 58,5 68,5 49,4 90,8 71,7
26.4
104,0 84,1 95,2 76,1 89,1 70,0 87,6 68,5 86,5 67,4 81,1 62,0 77,7 58,6 68,6 49,5 90,9 71,8
Lw: sound power values in free field conditions are calculated in accordance with ISO 3746.
Lp : sound pressure values measured at 1 m from the unit in free field conditions in compliance with ISO 3746
Blue Box - 21
SOUND POWER AND PRESSURE LEVELS
EXTRA LOW NOISE UNITS
Octave band [Hz]
Z E T A
2002
63 dB
125 dB
250 dB
500 dB
1000 dB
2000 dB
4000 dB
8000 dB
Total dB(A)
/SLN Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
3.2
90,2 73,0 81,4 64,2 75,3 58,1 73,8 56,6 72,7 55,5 67,3 50,1 63,9 46,7 54,8 37,6 77,1 59,9
4.2
90,6 73,5 81,8 64,7 75,7 58,6 74,2 57,1 73,1 56,0 67,7 50,6 64,3 47,2 55,2 38,1 77,5 60,4
5.2
91,1 73,9 82,3 65,1 76,2 59,0 74,7 57,5 73,6 56,4 68,2 51,0 64,8 47,6 55,7 38,5 78,0 60,8
6.2
91,8 74,6 83,0 65,8 76,9 59,7 75,4 58,2 74,3 57,1 68,9 51,7 65,5 48,3 56,4 39,2 78,7 61,5
7.2
92,1 74,9 83,3 66,1 77,2 60,0 75,7 58,5 74,6 57,4 69,2 52,0 65,8 48,6 56,7 39,5 79,0 61,8
8.2
94,8 76,8 86,0 68,0 79,9 61,9 78,4 60,4 77,3 59,3 71,9 53,9 68,5 50,5 59,4 41,4 81,7 63,7
9.2
95,0 77,1 86,2 68,3 80,1 62,2 78,6 60,7 77,5 59,6 72,1 54,2 68,7 50,8 59,6 41,7 81,9 64,0
10.2
95,7 77,8 86,9 69,0 80,8 62,9 79,3 61,4 78,2 60,3 72,8 54,9 69,4 51,5 60,3 42,4 82,6 64,7
12.2
95,3 77,4 86,5 68,6 80,4 62,5 78,9 61,0 77,8 59,9 72,4 54,5 69,0 51,1 59,9 42,0 82,2 64,3
13.2
95,6 77,7 86,8 68,9 80,7 62,8 79,2 61,3 78,1 60,2 72,7 54,8 69,3 51,4 60,2 42,3 82,5 64,6
14.4
97,1 78,1 88,3 69,3 82,1 63,1 80,6 61,6 79,5 60,5 74,2 55,2 70,7 51,7 61,6 42,6 83,5 64,9
16.4
99,6 81,0 90,8 72,2 84,7 66,1 83,2 64,6 82,1 63,5 76,7 58,1 73,3 54,7 64,2 45,6 86,5 67,9
18.4
100,1 80,9 91,3 72,1 85,2 66,0 83,7 64,5 82,6 63,4 77,2 58,0 73,8 54,6 64,7 45,5 87,0 67,8
20.4
100,7 81,5 91,9 72,7 85,8 66,6 84,3 65,1 83,2 64,0 77,8 58,6 74,4 55,2 65,3 46,1 87,6 68,4
24.4
101,6 82,5 92,8 73,7 86,7 67,6 85,2 66,1 84,1 65,0 78,7 59,6 75,3 56,2 66,2 47,1 88,5 69,4
26.4
102,3 82,7 93,5 73,9 87,4 67,8 85,9 66,3 84,8 65,2 79,4 59,8 76,0 56,4 66,9 47,3 89,2 69,6
Lw: sound power values in free field conditions are calculated in accordance with ISO 3746.
Lp : sound pressure values measured at 1 m from the unit in free field conditions in compliance with ISO 3746
Blue Box - 22
1. FIELD OF APPLICATION
The equipment is designed for cooling (chiller only versions) or cooling/heating (heat pump version) water, which is usually utilised for air conditioning or refrigeration applications.
The units must be used exclusively within the operating limits specified in Section 4.
1.1 INTRODUCTION
- When installing or servicing the unit, it is necessary to strictly follow the rules described in this manual, to conform to all the items detailed on the unit labels and take any necessary precaution.
- Pressure in refrigerant circuits and danger from electrical shock can be hazardous when installing or servicing the unit.
- The warranty will be invalid if the rules described in this manual are not observed and if any modifications are made to the unit without prior authorisation of the manufacturer.
Any work on the unit must be carried out by trained people only.
Attention: before repairing or servicing the unit, ensure that the electrical supply is disconnected.
2. INSPECTION, TRANSPORT, SITE HANDLING
2.1 INSPECTION
After receiving the unit, immediately check its integrity. The unit will have left the factory in perfect condition.
Therefore on receiving the unit any damage must be verbally described to the carrier and recorded on the
Delivery Note before it is signed by both parties. Blue Box or their Agent must be informed as soon as possible of the extent of the damage.
The Customer should prepare a written statement and photographic evidence regarding any severe damage.
2.2 LIFTING AND SITE HANDLING
Avoid sudden movements and jolts when unloading and positioning the unit. Internal handling procedures must be conducted with care. Do not exert leverage on the components of the machine. The unit must be lifted by inserting steel tubes through the lifting attachments shown by the relative signs (yellow arrow).
The unit must be lifted by harnessing it as shown in figure 1: use ropes or straps of sufficient length and spacer bars to avoid damage to the unit’s side panels and cover. Alternatively, the unit (with a maximum length less than
3.5 m) can be lifted by a forklift truck, inserting the forks under the pallet.
Blue Box - 23
2.5 m min.
mind. 2.5 m
1 2
3.5 m max
(1) Space bar (not supplied)
(2) Side panel protection (not supplied)
(3) Lifting holes
(4) Pallet
3
4
Figure 1
Caution: ensure that the method of lifting does not allow the unit to slip from chains and slings and does not allow the unit to turn over or slide from lifting devices.
2.3 UNPACKING
When unpacking the unit pay attention not to damage the unit.
Packaging consists of different materials: wood, paper, nylon etc.
Separate the materials and deliver to the proper gathering centre in order to reduce their environmental impact.
Blue Box - 24
3. SAFETY PRECAUTIONS
3.1 DEFINITION OF DANGER ZONE
Only authorised operators must be allowed in the vicinity of the unit.
- The external danger zone concerns a space of approximately 2 m in width around the perimeter of the machine.
Access to this area must be prevented by suitable guarding in the event that the unit is located in an unprotected area that is easily accessible to unauthorised persons.
- The internal danger zone is defined as the interior of the machine. Access to the interior of the machine must not be permitted to unqualified personnel and never before the machines' electrical supply has been disconnected.
3.2 SAFETY PRESCRIPTIONS
The unit is designed and built in accordance with the PED 97/23CE rules, to ensure the maximum level of safety.
To avoid possible situations of risk adhere to the following rules at all times:
- All work on the unit must be performed by qualified personnel. Before working on the unit, ensure that the designated personnel are conversant with the documentation supplied. Always ensure there is a copy of the documentation in the immediate vicinity of the unit.
- Use the appropriate personal safety equipment (gloves, helmet, safety goggles, safety footwear, etc.) for all maintenance and control operations on the unit.
- Use only tools and equipment that are in good working order.
- The fans have protective grilles to prevent accidental contact. Use the maximum caution to avoid inserting or dropping objects through the grilles.
- The exchanger coils have sharp edges. Do not touch the coils without using suitable protection.
- The compressor compartment contains various high temperature components. Adopt the maximum caution when working in the vicinity of the compressors and avoid touching any parts of the unit without appropriate protection.
- Do not work within the theoretical discharge trajectory of the relief valves.
Blue Box - 25
MECHANICAL HAZARDS
Operating mode
Normal operating regime
Maintenance
Handling during transport and installation.
Normal operating regime
Maintenance
Operating regime
Maintenance
Normal operating regime
Maintenance
Normal operating regime
Analysed risk or hazard
Stability
Stability
Pipeline bursts.
Surfaces, sharp corners and edges.
Surfaces, sharp corners and edges.
Cutting or severing.
Cutting or severing.
Cutting or severing.
Solution adopted
Because of their intrinsic characteristics, the units are not associated with problems of possible falling or tipping while in operation.
Carefully read the items described in this manual concerning the methods of positioning the unit.
The unit's base frame has specific lifting holes; the positions of which are marked with yellow decals. Following this procedure will eliminate the risk of the unit tipping.
Carefully read the items descriptions in this manual concerning the methods of handling the unit.
Pipes are rigidly anchored to reduce the degree of vibration.
The machine is designed and built in such a way as to minimise the presence of sharp corners and edges as far as possible.
In the interior parts of the unit it is not possible to totally eliminate risks from the presence of surfaces, sharp corners and edges. The operating, installation, and maintenance manual specifies that maintenance operations should be carried out exclusively by qualified personnel, and provides indications of the protective equipment to be used.
The moving parts of the unit are located in clearly defined areas. Specifically, the fans are enclosed in an inaccessible compartment and are equipped with an upper protection grille to UNI EN 294. All the protections supplied to limit and enclose the fan compartments cannot be removed without the use of special tools.
The moving parts of the unit are located in clearly defined areas. Specifically, the fans are enclosed in an inaccessible compartment and are equipped with an upper protective grille to UNI EN 294. If present, the fan speed regulator accessory, located in the condensing section compartment, does not require adjustment or calibration during maintenance operations.
All units are supplied as standard with specific protection grilles designed to protect against accidental contact with the finned coils, which can cause minor cuts to the hands.
Blue Box - 26
MECHANICAL HAZARDS
Operating mode
Maintenance
Normal operating regime
Maintenance
Normal operating regime
Maintenance
Analysed risk or hazard
Cutting or severing.
Entanglement, dragging, impact.
Entanglement, dragging, impact.
Projection of high pressure jets of fluid - Explosion hazard
Solution adopted
The operating, installation, and maintenance manual describes the use of suitable protections to avoid contact with the finned coils, which can cause slight wounds to the hands.
The moving parts of the unit are located in clearly defined areas. Specifically, the fans are enclosed in an inaccessible compartment and they are equipped with an upper protective grille to UNI EN 294. All the protections supplied to limit and enclose the fan compartments cannot be removed without the use of special tools.
The moving parts of the unit are located in clearly defined areas. Specifically, the fans are enclosed in an inaccessible compartment and they are equipped with an upper protective grille to UNI EN 294.
If present, the fan speed regulator accessory, located in the condensing section compartment, does not require adjustment or calibration during maintenance operations.
All units are equipped with relief valves to eliminate the risk of pressure bursts.
The outlet from relief valves must be piped appropriately to eliminate risks associated with the expulsion of gas at high pressure from the machine. The warnings regarding these expulsion points are fixed to the outside of the unit and given in the operating and maintenance manual.
THERMAL HAZARDS
Operating mode
Normal operating regime
Maintenance
Analysed risk or hazard
Burns caused by high temperatures.
Burns caused by high temperatures.
Solution adopted
Most of the pipelines that could cause burns, when touched, are lagged with heat insulating material. All the parts that are potentially dangerous are confined in compartments that cannot be accessed without the use of tools
Most of the pipelines that could cause burns, when touched, are lagged with heat insulating material. The operating, installation, and maintenance manual describes the use of suitable protections to avoid contact with high temperature pipelines that could result in burns.
Blue Box - 27
NOISE-RELATED HAZARDS
Operating mode
Normal operating regime
Maintenance
Analysed risk or hazard
Hearing damage.
Solution adopted
All units are designed and built with the aim of reducing noise emissions to the minimum.
ELECTRICAL HAZARDS
Operating mode
Normal operating regime
Maintenance
Normal operating regime
Maintenance
Normal operating regime
Maintenance
Normal operating regime
Maintenance
Analysed risk or hazard
Contact with electrically live parts (direct contact).
Elements carrying electrical current in the case of faults.
Inappropriate insulation.
Radiated heat due to shortcircuits or overloads.
Solution adopted
All units are designed and built in compliance with harmonised standard EN
60204-1.
Blue Box - 28
R407C REFRIGERANT SAFETY SHEETS
1. IDENTIFICATION OF
THE SUBSTANCE
1.1 Identification of the preparation:
Synonyms:
Formula:
EE-No:
407C
HFC-32lHFC-125IHFG134a
Mixture difluoromethane (HFC-32) : 200-839-4
1-1-1-2-tetrafluoroethane UHFC-134a) : 212-377-0 pentafluoroethane (HFC-125) : 206-557-8
2. COMPOSITION /
INFORMATION ON
INGREDIENTS
Chemical Name difluoromethane
1-2-2-2-tetrafluoroethane pentafluoroethane
CAS-No - Wt % - Symbol(s): & phrases "R"
75/10/5 - 23 - F+;R12
811/97/2 - 52
354/33/ 6 - 25
3. HAZARDS
IDENTIFICATION:
4. FIRST-AID
MEASURES:
3.1 Most important hazards:
Liquefied gas: may cause frostbite. Contact with eyes may cause irritation.
4.1 Eyes
Skin
Inhalation
Ingestion
General advice
Rinse immediately with plenty of water for at least 15 minutes.
Keep eye wide open while rinsing. If symptoms persist, call a physician.
Liquefied gas may cause frostbite. Wash frostbitten areas with plenty of water. Do not remove clothing. Wash off with warm water. if skin irritation persists, call a physician.
Move to fresh air in case of accidental inhalation of vapours.
Oxygen or artificial respiration if needed. Do not apply artificial respiration if patient is breathing; Consult a physician after significant exposure. Do not give adrenaline or similar drugs.
Do not induce vomiting without medical advice. Call a physician immediately. Do not give drugs from adrenaline-ephedrine group.
Consult a physician alter significant exposure.
5. FIRE-FIGHTING
MEASURES:
5.1 Suitable extinguishing media:
5.2 Extinguishing media which must not be used for safety reasons:
5.3 Specific hazards:
The product itself does not burn. Extinguish with carbon dioxide, dry chemical, foam or water spray. Use extinguishing measures that are appropriate to the environment.
None
5.4 Special protective equipment for firefighters:
5.5 Specific methods:
Possibility of generating hazardous reactions during a fire due to the presence of F and/or Cl groups. Fire or intense heat may cause violent rupture of packages.
In case of fire, west a self contained breathing apparatus.
Protective suit.
Standard procedure for chemical fires. In the event of fire, cool tanks with water spray.
6. ACCIDENTAL
RELEASE MEASURES:
6.1 Personal precautions: Use personal protective equipment. Evacuate personnel to safe areas. Do not breath vapours or spray mist. Ensure adequate ventilation.
6.2 Methods for cleaning up:
Shut off leaks it without risk. Solid evaporates. Ensure adequate ventilation.
Blue Box - 29
7. HANDLING AND
STORAGE:
7.1 Handling:
7.2 Storage:
Keep away from heat, sources of ignition. Do not puncture or drop container, Provide sufficient air exchange and / or exhaust in work rooms.
Keep containers tightly closed in a cool, well-ventilated place.
Store in a cool and shaded area. Do not expose to temperatures above 50 °C. Keep tightly closed.
8. EXPOSURE
CONTROLS /
PERSONAL
PROTECTION:
8.1
8.2
8.3
Engineering measures to reduce exposure:
Personal protection equipment:
Ensure adequate ventilation, especially in confined areas.
Respiratory protection: In case of insufficient ventilation wear suitable respiratory equipment, preferably a compressed airline breathing apparatus.
Hand protection: Impervious butyl rubber gloves.
Eye protection: Wear as appropriate: safety glasses, gaggles, Wear face-shield and protective suit for abnormal processing problems.
Skin and body protection:
Exposure limit(s):
Chemical resistant apron, long sleeved clothing, safety shoes.
1-1-1-2-tetrafluoroethane 1000 ppm (TWA); difluoromethane: 1000 ppm (TWA); pentafluoroethane: 1000 ppm (TWA)(AIHA);
9. STABILITY AND
REACTIVITY:
9.1 Stability:
9.2 Conditions to avoid:
9.3 Materials to avoid:
9.4 Hazardous decomposition products:
10. TOXICOLOGICAL
INFORMATION:
10.1 Acute toxicity:
10.2 Irritation :
Skin:
Eyes:
10.4 Chronic toxicity:
11. DISPOSAL
CONSIDERATIONS:
11.1 Waste from residues / unused products:
Contaminated packaging:
Stable at normal conditions. No decomposition if stored and applied as directed. Decomposition starting from 250°C.
Do not expose to temperatures above 50 °C. Fire or Intense heat may cause violent rupture of packages. alkaline metals (Na, K), alkaline earth metals (Ca, Mg), finely divided aluminium, zinc. halogenated compounds, hydrogen halides (HF, HCI), carbonyl halides (COCl
2
), carbon monoxide, carbon dioxide (C0
2
).
LC50/inh./4 h/rat : > 500000 ppm slightly irritant, may cause frostbite. slightly irritant. chronic inhalation, no-observed-effect level (NOEL):> 10000pprn rat.
Offer surplus and non-recyclable solutions to an established disposal company. In accordance with local and national regulations. S59 - Refer to manufacturer/supplier for information on recovery/recycling.
Do not reuse empty containers. Empty pressure vessels should be returned to supplier.
12. TRANSPORT
INFORMATIQN:
No. O.N.U.
ADR/RID
3340
UN 3340 Refrigerant gas R407C, 2, 2° A, ADR/RID
Label: 2
Blue Box - 30
R22 REFRIGERANT SAFETY SHEETS
1. IDENTIFICATION OF
THE SUBSTANCE
1.1 Identification of the preparation:
Synonyms:
Formula:
CAS-No
EEC-No
HCFC-22 chlorodifluoromethane
CHClF
2
75-45-6
200-871-9
2. COMPOSITION /
INGREDIENTS
3. HAZARDS
4. FIRST-AID
MEASURES:
Chemical Name
Chlorodifluoromethane
3.1 Major hazards:
CAS-No - Wt % - Symbol(s): & phrases "R"
75/45/6 - 100 - R59
Causes damage to ozone layer.
4.1 Eyes
Skin
Inhalation
Ingestion
General advice
Rinse immediately with plenty of water for at least 15 minutes.
Keep eye wide open while rinsing. If symptoms persist, call a physician.
Liquefied gas may cause frostbite. Wash frostbitten areas with plenty of water. Do not remove clothing. Wash off with warm water. if skin irritation persists, call a physician.
Move to fresh air in case of accidental inhalation of vapours.
Oxygen or artificial respiration if needed. Do not apply artificial respiration if patient is breathing; Consult a physician after significant exposure. Do not give adrenaline or similar drugs.
Do not induce vomiting without medical advice. Call a physician immediately. Do not give drugs from adrenaline-ephedrine group.
Consult a physician alter significant exposure.
5. FIRE-FIGHTING
MEASURES:
5.1 Suitable extinguishing media:
5.2 Extinguishing media which must not be used for safety reasons:
5.3 Specific hazards:
The product itself does not burn. Extinguish with carbon dioxide, dry chemical, foam or water spray. Use extinguishing measures that are appropriate to the environment.
None
5.4 Special protective equipment for firefighters:
5.5 Specific methods:
Possibility of generating hazardous reactions during a fire due to the presence of F and/or Cl groups. Fire or intense heat may cause violent rupture of packages.
In case of fire, west a self contained breathing apparatus.
Protective suit.
Standard procedure for chemical fires. In the event of fire, cool tanks with water spray.
6. ACCIDENTAL
RELEASE MEASURES:
6.1 Personal precautions: Use personal protective equipment. Evacuate personnel to safe areas. Do not breath vapours or spray mist. Ensure adequate ventilation.
6.2 Methods for cleaning up:
Shut off leaks it without risk. Solid evaporates. Ensure adequate ventilation.
Blue Box - 31
7. HANDLING AND
STORAGE:
7.1 Handling:
7.2 Storage:
Keep away from heat, sources of ignition. Do not puncture or drop container. Provide sufficient air exchange and / or exhaust in work rooms.
Keep containers tightly closed in a cool, well-ventilated place.
Store in a cool and shaded area. Do not expose to temperatures above 50 °C. Keep tightly closed.
8. EXPOSURE
CONTROLS /
PERSONAL
PROTECTION:
8.1
8.2
Engineering measures to reduce exposure:
Personal protection equipment:
Respiratory protection: In case of insufficient ventilation wear suitable respiratory equipment, preferably a compressed airline breathing apparatus.
Hand protection:
Eye protection:
Impervious butyl rubber gloves.
Wear as appropriate: safety glasses, gaggles, Wear face-shield and protective suit for abnormal processing problems.
Skin and body protection:
8.3 Exposure limit(s):
Ensure adequate ventilation, especially in confined areas.
Chemical resistant apron, long sleeved clothing, safety shoes.
Chlorodifluoromethane: 3600 mg/m3, 1000 ppm (TLV)
9. STABILITY AND
REACTIVITY:
9.1
9.2
Stability:
Conditions to avoid:
9.3 Materials to avoid:
9.4 Hazardous decomposition products:
10. TOXICOLOGICAL
INFORMATION:
10.1 Acute toxicity:
10.2 Irritation:
10.3 Sensitisation:
10.4 Chronic toxicity:
11. DISPOSAL
CONSIDERATIONS:
11.1 Waste from residues / unused products:
Contaminated packaging:
Stable
Keep well clear of naked flame and sparks. Do not smoke. If burned, the product can give off toxic fumes . use self-contained breathing apparatus. alkaline earth metals, alkaline metals, aluminium precipitate, zinc. halogenated compounds (e. g. acids), carbonyl halides.
LC50/inh./4 h/rat : > 300,000 ppm
Hearth sensitisation: 50,000 ppm
Sub-chronic exposure, effects not observed below level (NOEL):
10,000 ppm
Offer surplus and non-recyclable solutions to an established disposal company. In accordance with local and national regulations. S59 - Refer to manufacturer/supplier for information on recovery/recycling.
Do not reuse empty containers. Empty pressure vessels should be returned to supplier.
12. TRANSPORT
INFORMATIQN:
No. O.N.U.
ADR/RID
1018
UN 1018 Chlorodifluoromethane, 2, 2° A, ADR/RID
Label: 2
Blue Box - 32
3.3 POSITIONING
Read the following points carefully when choosing the most suitable site for the unit and its connections:
- dimensions and connection point of hydraulic pipelines;
- location of the electrical power connection point;
- accessibility for maintenance and repair work;
- loading capacity and compactness of the supporting surface;
- ventilation of air-cooled condenser;
- orientation and exposure to sunlight; as far as possible the condenser coil should not be
exposed to direct sunlight;
- direction of prevailing winds: do not position the unit in such a way that prevailing winds can give rise to air recirculation at the condenser coil;
- type of support surface: to limit the risk of overheating, do not install the unit on a dark coloured surface
(e.g.bitumen roofing membranes and compounds);
- possible sound reverberation.
All models in the ZETA 2002 series are designed for exterior installation (patios, gardens, etc.): of undesirable air recirculation, these units must not be covered by a shelter roof or located under trees (even if the unit is only partially covered).
It is advisable to make a supporting plinth of dimensions commensurate with the footprint of the unit. This precaution is indispensable if the unit is to be located on unstable ground (various types of terrain, gardens, etc.).
to avoid the risks of undesirable air recirculation, these units must not be covered by a shelter roof or located under trees (even if the unit is only partially covered).
It is advisable to make a supporting plinth of dimensions commensurate with the footprint of the unit. This precaution is indispensable if the unit is to be located on unstable ground.
The unit transmits a low level of vibration to the supporting structure: we recommend interposing a layer of rigid rubber sheeting between the base of the unit and the supporting surface.
If a higher level of vibration damping is required, use anti-vibration mounts (contact Bluebox for details).
The units should not be installed next to offices, bedrooms, or other areas where low noise levels are a necessity.
To avoid excess sound reverberation do not install the units in narrow or confined spaces.
15 mm gauge hard rubber sheet
Foundation plinth made of 500 kg/mm 2 reinforced concrete
Plinth slab
15-20 cm
Sealant
Cork underlayment
Soil
Figure 2
Blue Box - 33
4. INSTALLATION
4.1 INSTALLATION CLEARANCES
It is important that an adequate air volume is available at the intake and exhaust sides of the condenser coil. It is essential to avoid air recirculation between the intake and exhaust sides to prevent a reduction of the rated performance levels and unit operating problems.
The minimum clearances required for satisfactory operation of the unit is as follows (refer to figures 3 and 4):
- condensing coil side: 1.5 metres
- electrical panel side: 1 metre
- compressors compartment side: 1 metre
- hydraulic connection sides: 1 metre.
- top: no impediments that obstruct the air discharge.
- units installed side by side: 4 metres.
1 m
1 m
Figure 3
SIDE BY SIDE UNITS
4 m min.
Figure 4
Blue Box - 34
4.2 ANTI-VIBRATION ISOLATORS (option)
It is recommended that the unit is installed on rubber or spring anti-vibration mountings, supplied as an option, to reduce vibrations transmitted to the building structure. It is advisable to use rubber isolators for units installed in the basement, or ground floors in contact with the earth, and spring isolators for units installed on intermediate floors.
The anti-vibration isolators must be installed before the unit is positioned.
Ensure that during lifting the unit is firmly secured with straps.
4.2.1 Rubber Anti-Vibration Isolators
Rubber isolators are made of an upper metallic bell with a fixing screw to the base-frame of the unit. The isolator is fixed at the foundation via 2 holes on the flange. On the flange there is a number (45, 60, 70 ShA) which identifies the hardness of the rubber isolator. The dimensional drawing, enclosed in the machine, shows the unit footprint with the position and weight of each isolator.
Rubber/metal anti-vibration i s o l a t o r
Designed to reduce the vibration.
Figure 5
4.2.2 Spring Anti-Vibration Isolators
Anti-Vibration Isolators with cylindrical springs are recommended to reduce any mechanical and sound vibration.
Each isolator has a code which identifies the maximum permitted load.
When installing spring Anti-Vibration Isolators, it is compulsory to carefully follow all recommendations and assembly instructions. The dimensional drawing, enclosed in the machine, shows the footprint with the position and weight of each isolator.
Standard spring antivibration isolators
The isolator is fixed to the unit's baseframe with a nut and two bolts and washers.
Spring anti-vibration isolators for heavy l o a d s
The load of the unit is supported by the full surface of the isolators. The load is not exerted on the bolt.
Figure 6
Blue Box - 35
4.3 WATER PIPING CONNECTIONS
Unit water pipework must be installed in accordance with national and local regulation and codes.
Follow the recommendations below when designing the water piping circuit (refer to the diagrams included in this manual).
- Piping should be connected to the unit with flexible joints, to avoid vibration transmission and allow for thermal expansion (the same procedure should be adopted for the circulating pumps).
- The following devices should be located on the piping system:
- isolating/regulating valves, temperature gauges or thermometer pockets, pressure gauges or binder points required for servicing operations.
- Serviceable mesh strainer, with a filtration level no larger than 1mm, located on the unit inlet to prevent debris from entering the heat exchangers.
- vent valves, to be installed in the upper parts of the circuit, for air bleeding.
- expansion device with accessories for circuit pressurisation, water thermal expansion compensation and system filling.
- unload valve and if necessary drainage tank for circuit emptying during maintenance and seasonal stop.
Blue Box - 36
Blue Box - 37
Blue Box - 38
HYDRAULIC CIRCUIT DIAGRAM VERSION ST /2PS
Blue Box - 39
4.4 EVAPORATOR WATER PIPE CONNECTIONS
The water inlet and outlet must be connected in the positions indicated as labelled on the unit.
EVAPORATOR WATER
If incorrectly connected the antifreeze thermostat will not operate and the evaporator may freeze.
The hydraulic connections are threaded. The type and size are indicated on the dimensional drawings at the end of this manual.
A constant water flow to the evaporator must be guaranteed at all operating conditions to prevent liquid refrigerant from entering the compressor and causing irreparable damage.
Compressors start and stop often due to changes in cooling demand. In hydraulic circuits with low water volume, where the thermal inertia action is low, it is advisable to verify that the water volume equals or exceeds the following ratio:
24 · Q
COMPTOT
M>= ---------------------
N where:
M
Q
COMPTOT
N
= system water content [kg]
= unit cooling capacity [kW]
= number of capacity steps
If the water volume does not reach the value given by the formula, it is advisable to provide the circuit with a storage vessel to increase the volume (tank + circuit) to match the result of the formula.
The chilled water piping and storage vessel must be insulated to prevent condensation on the pipe surfaces and to avoid circuit performance losses.
For models from 3.2 to 13.2 it is mandatory to install a flow switch
(supplied with the unit) on the evaporator water outlet connection identified by the following decal:
USER WATER
For models from 14.4 to 26.4 the flow switch is already installed as part of the standard equipment.
Blue Box - 40
All units are equipped with plate heat exchangers. It is compulsory to install a metallic filter, on the water inlet piping, with a mesh not larger than 1 mm. If a filter is not installed the warranty will be terminated immediately.
We strongly recommend installing a pressure relief valve on the hydraulic circuit. In the event of serious system breakdown or emergency (e.g.
fire), the relief valve will make it possible to depressurise the system thus forestalling possible pipe bursts. Always connect the relief valve outlet to a pipe of diameter no smaller than the valve opening, and route it to a location in which persons are protected from the jet of expelled water.
Caution: When making hydraulic connections never use naked flames close to or inside the unit.
4.5 WATER FLOW SWITCH INSTALLATION INSTRUCTIONS (models 3.2 to 13.2)
- Clean the pipeline system into which the flow switch is to be fitted and take away any magnetic particle, such as welding residues. To prevent turbulent flow there must be straight pipework, equal to 5 times the diameter of the pipe, either side of the flow switch.
" Connect the "T" shaped metallic manifold (on which the flow switch is mounted) into the evaporator male threaded water outlet labelled with:
USER WATER
To avoid leakage, seal the connection by using teflon. The flow switch should be installed on the heat exchanger that is closer to the electrical board.
User exchanger
(evaporator)
Make the electrical connections on the unit’s terminal board
Figure 7
Blue Box - 41
- The flow switch must be tightened on the “T” shaped metallic manifold by the plastic knurled union nut. Check that the arrow located on the upper side is pointing in the direction of flow.Be sure to fit the O-ring seal, through the brass manifold and the plastic ring nut. The O-ring seal is supplied in a plastic cover to protect the flow switch shaft.
- Connect the flow switch to the other end of the “T” manifold.
- Route the flow switch electrical cable through the hole in the unit structure and run it to the electrical panel by ascending the upright in the machine interior. Connect the flow switch to terminals 1-14 as indicated on the electrical drawing.
- The flow switch can be removed by screwing out the plastic knurled union nut. In order to reassemble it, ensure that the o-ring seal is positioned in the proper location. (See figure10).
Arrow
Flow switch
Seal
Electric cable
Ring nut
“T” Connector
Figure 8
4.6 DESUPERHEATER HYDRAULIC CONNECTION (optional)
For all units equipped with desuperheaters the connections, for the relative hydraulic circuit, are steel tubes with male threads.
The water inlet and outlet must be connected in the positions indicated as labelled on the unit.
Heat recovery water inlet:
IN
WATER DESUPERHEATER
Heat recovery water outlet:
OUT
WATER DESUPERHEATER
On HP version units the hydraulic connection to the desuperheater must be isolated during heat pump operation
Blue Box - 42
4.7 ZETA 2002/DC HEAT RECOVERY EXCHANGER HYDRAULIC CONNECTIONS
For all units equipped with a recovery condenser, the relative hydraulic circuit connections are male threaded steel pipes (the diameter depends on the unit's size)
The units are equipped with a probe that monitors the temperature of the water returning from the system. The microprocessor controller enables recovery when necessary, disconnecting the fans, and restarting regular operation once the water has reached the desired temperature.
If faults occur on the recovery condenser the microprocessor controller restarts the fans.
The calibration values of the thermostat and pressure switches are given in the relevant controller instruction manual.
For units equipped with a recovery condenser:
The water inlet and outlet must be connected in the positions indicated as labelled on the unit.
IN
3-way valve
Recovery water outlet
Recovery water inlet
It is mandatory to install a three-way modulating, valve with water temperature probe, on the inlet to the unit to ensure that, at steady state conditions, the inlet water temperature is not less than 20 °C.
DIAGRAM WITH 3-WAY VALVE
Figure 9
Blue Box - 43
Alternatively: a condensing pressure control valve for each refrigerant circuit that ensures an average condensing temperature of at least 33
°C.
DIAGRAM WITH CONDENSING PRESSURE CONTROL VALVE
Condensing pressure control valve
To the refrigerant circuit
Recovery water outlet
Recovery water inlet
×
Ø
Figure 10
This method ensures that the recovery unit is supplied with a flow that increases as the water temperature rises, thus allowing the system to operating with optimum functional parameters at all times.
4.8 PRESSURE RELIEF VALVES
Pressure relief valves are fitted on the high pressure side and low pressure side of the refrigerant circuit. The valves must be vented, to outdoors, through a vent pipe.
The vent pipe must be sized no smaller than the relief valve and it must not be supported from the valve.
Caution: The relief valve must be directed into a safe zone where no injuries can be caused to people.
Blue Box - 44
4.9 CONNECTIONS FOR VERSION /LE (MOTOCONDENSING UNIT)
/LE (condensing unit) versions must be connected to a remote evaporator by means of refrigerant lines.
For separate section type /LE versions, the route followed by refrigerant lines depends on the location of the sections and the characteristics of the surrounding building structure.
Pipe runs should be as short as possible to limit the pressure drop and the refrigerant charge volume. The maximum permissible pipeline length is 30 metres.
If this limits cannot be adhered to contact Blue Box for further information.
4.9.1 Procedures to follow when sizing refrigerant lines
Depending on the relative position of the sections, there are certain procedures to follow when installing the refrigerant line.
4.9.2 Evaporating section at lower level than condensing section: a) The vertical riser must be equipped with siphons at least every 6 metres to facilitate the return of oil to the compressor; b) Make a collection pit on the suction line downstream of the thermostatic valve bulb; c) Horizontal sections of the suction line should follow a grade of at least 1% to facilitate oil return to the compressor (see above).
The diameter of pipes can be obtained from table 1, according to the selected model and length of connecting pipes.
1 %
Figure 11
6 m
6 m
1 %
Evaporator
Blue Box - 45
4.9.3 Evaporating section positioned higher than the condensing unit section: a) Form a siphon on the suction line,at the same height as the evaporator, to avoid drainage of liquid towards the compressor when the unit is stopped.
b) Make a collection pit on the suction line, downstream from the thermostatic valve bulb, for the collection of liquid refrigerant that can accumulate during unit shutdown. When the compressor restarts the refrigerant will evaporate rapidly: it is advisable to create the accumulation pit well away from the bulb to avoid the risk of affecting the operation of the thermostatic valve.
c) Horizontal sections of the suction line should follow a grade of at least 1% to facilitate oil return to the compressor.
Evaporator
1 %
Figure 12
TABLE 1 - EXTERNAL PIPE DIAMENTERS FOR /LE VERSIONS
Distance [m]
MODEL
ZETA 2002
3.2
4.2
5.2
6.2
7.2
8.2
9.2
10.2
12.2
13.2
14.4
16.4
18.4
20.4
24.4
26.4
Suction
[mm]
35
35
35
54
54
54
42
42
42
42
54
42
54
54
54
54
10
28
35
35
28
22
28
28
28
28
28
28
35
35
Liquid
[mm]
18
22
22
Suction
[mm]
35
42
42
54
54
67
42
42
42
42
54
42
54
54
54
67
20
28
35
35
28
22
28
28
28
28
28
28
35
35
Liquid
[mm]
18
22
22
Suction
[mm]
35
42
42
54
54
67
54
42
54
54
54
54
54
54
67
67
30
Liquid
[mm]
18
22
22
28
35
35
28
22
28
28
28
28
28
28
35
35
Blue Box - 46
4.10 WATER FLOW RATE TO EVAPORATOR
The nominal water flow rate is based on a 5 °C temperature difference between inlet and outlet in relation to the supplied cooling capacity.
The maximum permissible flow rate is that which results in a temperature difference of 3 °C: higher flow rates will lead to excessive pressure drops and could damage the evaporator.
The minimum permissible flow rate is that which results in a temperature difference of 8 °C or a pressure drop of no less than 10 kPa: lower flow rates will lead to excessively low evaporation temperatures with consequent tripping of safety devices and shutdown of the unit.
4.11 CHILLER WATER TEMPERATURE (summer cycle)
For the minimum water temperature at the evaporator outlet refer to section 4.14.
The maximum water temperature at the evaporator inlet is 20 °C. In the case of higher temperatures specific solutions are necessary (dual circuits, three-way valves, by-pass, storage tanks): consult the Bluebox Engineering
Department to discuss the most suitable solution for your application.
4.12 HOT WATER TEMPERATURE (winter cycle)
The minimum water temperature at the condenser inlet, once the system is operating in steady state conditions, must be no lower than 23 °C: lower values could result in operating anomalies of the compressor with the consequent risk of compressor breakdown.
The maximum water temperature at the condenser outlet must be no higher than 48 °C. In the event of higher temperatures the safety devices will trip causing the unit to shut down.
Warning: speed control calibration settings must not be altered. If it proves necessary to alter speed calibration settings, this task must be entrusted to a skilled engineer, who should refer to the attached instruction sheet.
4.13 Ambient air temperature
- The units are designed and built to operate with ambient air temperatures within the limits shown on the operating limits diagrams. Contact Bluebox if the unit is required to operate at different ambient temperatures.
- It should be noted that the performance of heat pump units decreases significantly at lower ambient temperatures.
- The units can be optionally equipped with an electric element for heating the evaporator. The heater cuts in, when the machine is switched off, if the water temperature in the evaporator falls below the freeze protection calibration temperature.
4.14 FAN SPEED CONTROL (optional)
If the unit is required to operate at ambient air temperatures less than 18 °C a fan speed controller must be included. With fan speed control the unit can function correctly, at low ambient temperatures, by reducing the air flow supplied to the condenser so that it operates within acceptable parameters.
This control is calibrated and tested in the factory.
Blue Box - 47
4.15 OPERATION WITH LOW TEMPERATURE CHILLED WATER AT EVAPORATOR
Units from the normal production range are not designed to operate with lower chilled water temperatures, at the evaporator outlet, than those indicated in the operating limit diagrams. To operate outside this limit the unit may require structural modifications. If this should become necessary Bluebox.
With temperatures lower than those shown in the operating limit diagrams, the hydraulic circuit should be filled with a suitable water and antifreeze solution. In such cases the service thermostat and the freeze protection thermostat must be reset:
These calibrations are normally set in the factory.
The ethylene glycol percentage must be selected in relation to the required chilled water temperature.
See Table 2.
TABLE 2 - FREEZING POINT FOR WATER-ANTIFREEZE MIXTURES
LIQUID OUTLET TEMPERATURE
OR MINIMUM AMBIENT TEMPERATURE (°C)
FREEZING POINT (°C)
ANTIFREEZE
ETHYLENE GLYCOL
PROPYLENE GLYCOL
METHANOL
CALCIUM CHLORIDE
TEMPER -20
TEMPER -40
TEMPER -60
TIFOXITE
FREEZIUM
PEKASOL 50
+0° -5° -10° -15° -20° -25° -30° -35° -40°
6
15
8
9
-5°
10
50
-10° -15° -20° -25° -30° -35° -40° -45°
% BY WEIGHT
22
25
14
14
30
33
20
18
T -20°C
36
39
26
21
41
44
30
24
46
48
34
26
50
51
38
27
---
53
54
41
28
56
57
45
30
---
40
20 25
59
50
30
T -40°C
T -60°C
60
34
68 75
63
37
81
69
40
86
73
43
90
---
45
---
In the case of ST versions with a glycol content greater than 30% pumps with special seals must be specified at the time of the order.
Blue Box - 48
OPERATING LIMITS
ZETA 2002 - R22 refrigerant
20
15
10
Con dispositivi opzionali per basse temperature dell’aria esterna.
With low ambient temperature kit.
(1)
5
0
-25 -20 -15 -10 -5 0 5 10 15
Refrigeratore
Chiller
Raffreddamento
Cooling
(1)
20 25 30 35 40 45 50
Ambient air temperature [°C]
55
50
45
40
35
30
25
20
15
10
5
0
-25 -20 -15 -10 -5
(1)
0
Riscaldamento
Heating
Con dispositivi opzionali per basse temperature dell’aria esterna.
With low ambient temperature kit.
5 10
Ambient air temperature [°C]
Pompa di calore
Heat pump
Raffreddamento
Cooling
(1)
20 25 30 35 40 45 50
The water temperature rise for all versions must be between 3 °C (min) and 8 °C (max)
(1) Working limits of units with 2 compressors
Blue Box - 49
OPERATING LIMITS
ZETA 2002/LE - R22 refrigerant
20
10
0
-10
Con dispositivi opzionali per basse temperature dell’aria esterna.
With low ambient temperature kit.
-20
-25 -20 -15 -10 -5 0 5 10 15 20 25
Refrigeratore
Chiller
Raffreddamento
Cooling
30 35 40 45 50
Ambient air temperature [°C]
70
60
50
40
30
20
10
0
-10
-20
-30
Riscaldamento
Heating
Con dispositivi opzionali per basse temperature dell’aria esterna.
With low ambient temperature kit.
Pompa di calore
Heat pump
Raffreddamento
Cooling
-25 -20 -15 -10 -5
Ambient air temperature [°C]
0 5 10 15 20 25 30 35 40 45 50
The water temperature rise for all versions must be between 3 °C (min) and 8 °C (max)
Blue Box - 50
OPERATING LIMITS
ZETA 2002 - R407C refrigerant
20
15
10
5
Con dispositivi opzionali per basse temperature dell’aria esterna.
With low ambient temperature kit.
(1)
0
-25 -20 -15 -10 -5 0 5 10 15 20 25
Refrigeratore
Chiller
Raffreddamento
Cooling
(1)
30 35 40 45 50
Ambient air temperature [°C]
55
50
45
40
35
30
25
20
15
10
5
0
-25 -20 -15 -10 -5
Ambient air temperature [°C]
0
Riscaldamento
Heating
Con dispositivi opzionali per basse temperature dell’aria esterna.
With low ambient temperature kit.
(1)
5 10 15
Pompa di calore
Heat pump
Raffreddamento
Cooling
(1)
20 25 30 35 40 45 50
The water temperature rise for all versions must be between 3 °C (min) and 8 °C (max)
(1) Working limits of units with 2 compressors
Blue Box - 51
OPERATING LIMITS
ZETA 2002/LE - R407C refrigerant
20
10
0
Con dispositivi opzionali per basse temperature dell’aria esterna.
With low ambient temperature kit.
-10
-20
-25 -20 -15 -10 -5 0 5 10 15 20 25
Refrigeratore
Chiller
Raffreddamento
Cooling
30 35 40 45 50
Ambient air temperature [°C]
40
30
20
10
70
60
50
0
-10
-20
-30
Riscaldamento
Heating
Con dispositivi opzionali per basse temperature dell’aria esterna.
With low ambient temperature kit.
Pompa di calore
Heat pump
Raffreddamento
Cooling
-25 -20 -15 -10 -5
Ambient air temperature [°C]
0 5 10 15 20 25 30 35 40 45 50
The water temperature rise for all versions must be between 3 °C (min) and 8 °C (max)
Blue Box - 52
EVAPORATOR PRESSURE DROP
100
90
80
70
60
50
40
3.2
4.2
5.2
6.2
7.2
8.2
9.2
10.2
12.2
13.2
30
20
100
90
80
70
60
50
40
30
20
10
1 2 3 4 5
Portata acqua [ l/s]
6
Water flow
7 8 9 10
16.4
18.4
20.4
24.4
14.4
26.4
10
2
4 6 7 8 9 10 11 12
Portata acqua [l/s]
Water flow
14 16 18 20
The water temperature rise for all versions must be between 3 °C (min) and 8 °C (max)
Blue Box - 53
PUMPS AVAILABLE PRESSURE - MODEL ZETA 2002 /ST 2PS
AVAILABLE PRESSURE
300
250
200
7.2
26.4
150
100
50
3.2
6.2
5.2
4.2
0
1 3
14.4
8.2
13.2
9.2
10.2
12.2
16.4
5
24.4
18.4-20.4
7 9
Portata acqua [l/s]
Water flow
11 13 15 17
Blue Box - 54
4.16 ELECTRICAL CONNECTIONS
4.16.1 General
Electrical connections must be made in accordance with the information given on the electrical drawing attached to the unit and in compliance with the applicable local regulations.
An Earth (ground) connection is compulsory. The installer must connect the earth cable with a dedicated terminal on the earth bar in the electrical board (refer to the illustration on the following page) labelled PE.
It must be verified that the electrical supply corresponds to the unit electrical nominal data (tension, phases, frequency) indicated on the label on the front panel of the unit.
Line voltage fluctuations must not be more than ±5% of the nominal value, while the voltage unbalance between one phase and another must not exceed 2%. If these tolerances are not possible contact Blue Box to provide the necessary devices.
Check that the line is connected with the correct phase sequence.
The cable inlet point is created by drilling a hole in the side or base of the electrical enclosure, depending on the model.
The control circuit is derived from the power supply through a transformer located inside the electrical panel.
The control circuit is protected by fuses.
Electrical cable anchorage: anchor the electrical power cables with fixing systems able to withstand pulling and torsional stress.
Before any operation on the electrical section, be sure that the electric supply is disconnected.
Power cable and line protection must be sized according to the specification indicated on the wiring diagram and the documents supplied with the unit.
The crankcase heaters must be connected at least 12 hours before starting the unit; the heaters are automatically connected when the main disconnect switch is set to the ON position.
The electrical supply must be within the limits shown. If this is not the case the warranty will be terminated immediately.
Blue Box - 55
4.16.2 Power supply to crankcase heaters
1) Close the main disconnect switch by turning it from position “0” to position “1”
2) Check that the word “OFF” is shown on the display
3) Ensure that the unit is in “OFF” status and that the external enabling contact is open
4) After a few moments, if the phase sequence is incorrect the alarm “INCORRECT PHASE SEQUENCE” will be displayed (4-compressor models from 14.4 to 26.4 only, with pCO2 controller). In this case invert the connections of two of the power line phase wires.
5) Leave the unit in this condition for at least 12 hours to allow the crankcase heaters to perform their function
4.16.3 Potential free contacts
The following potential free contacts are available:
- 1 potential free contact for general alarm (terminals 100 - 101 - 102)
- 1 potential free contact for each compressor (option)
- 1 contact for each pair of fans (option)
- 1 contact for each pump (option - ST models)
4.16.4 Flow switch electrical connections
Flow switch electrical connections (see paragraph 4.4 ) must be connected to terminal 1-14 for chiller units.
4.16.5 Circulating pump electrical connections
The external interlocks of unit must close for the unit to operate. The normally open external water circulating pump contactor terminals must be wired in series with terminals 1 and 2, on the unit control panel, to ensure that the chiller can only start after the pump is in operation.
In ST units external enabling contacts 1-2 must be jumpered (unless they are required for system functions).
Turn on the pump before the unit starts and stop it after the unit has stopped (recommended time delay: 60 sec.).
4.17 MICROPROCESSOR CONTROLLERS
Chillers in the ZETA 2002 series with 2 scroll compressors, models from 3.2 to 13.2, are equipped with the mCHILLER type microprocessor controller.
Chillers in the ZETA 2002 series with 4 scroll compressors, models from 14.4 to 26.4, are equipped with the pCO2 microprocessor controller.
Blue Box - 56
4.17.1 Microprocessor controller for /LE and HP/LE versions
- Versions ZETA 2002 /LE and ZETA 2002 HP/LE with two compressors are equipped with an mchiller controller.
- Versions ZETA 2002 /LE and ZETA 2002 HP/LE with four compressors do not have an integral controller and therefore an external controller, or thermostats, must be connected to the auxiliary terminals 1-21, 1-31, 1-41 and 1-51.
Consult the electrical diagram attached to the unit.
4.17.2 RS485 serial interface (optional)
All units can be equipped with a serial interface board for supervision or remote diagnostics functions by means of a computer.
The serial interface board plugs into a dedicated slot on the connection board.
Connection to the supervision or remote diagnostics serial line is executed in compliance with standard RS485 and is achieved by means of the serial interface boards.
Models from 3.2 to 13.2 with two scroll compressors and µchiller controller
When the serial interface board is inserted the Carel communications protocol is available.
A conversion gateway is required for the Modbus-jbus and BacNet protocols.
Models from 14.4 to 26.4 with 4 scroll compressors and pCO 2 controller
When the serial interface board is inserted the following communications protocols are available: Carel, Modbusjbus, BacNet. If a connection is to be made with networks that utilise the Lon-Talk protocol, a dedicated board must be installed.
In this case, a conversion gateway is not required.
Blue Box - 57
ELECTRICAL PANEL LAY OUT
Unit with 2 compressors - µchiller controller
ZETA 2002 - Models 3.2 - 8.2
REMOTE CONTROL CARD -
OPTIONAL
MICRO CHILLER CARD -
1 COMPRESSOR
POSITION OF CONNECTION
TO EARTH TERMINAL
MICRO CHILLER CARD -
2 COMPRESSOR
ZETA 2002 - Models 9.2 - 13.2
REMOTE CONTROL CARD -
OPTIONAL
MICRO CHILLER CARD -
1 COMPRESSOR
POSITION OF CONNECTION
TO EARTH TERMINAL
MICRO CHILLER CARD -
2 COMPRESSOR
KEY TO ELECTRICAL COMPONENT PART NUMBERS
A10 ON/OFF CONTROL CIRCUIT BOARD
A5 SPEED REGULATOR
A8 SPEED REGULATOR
FU1 COMPRESSOR 1 FUSES
FU2 COMPRESSOR 2 FUSES
FU21 FAN UNIT FUSES
FU21 FAN UNIT FUSES
FU40 HEATER FUSES
FU50 AUXILIARY TRANSFORMER FUSES
FU51 CONTROL CIRCUITS FUSE
FU52 CONTROLLER FUSE
FU56 PHASE SEQUENCE RELAY FUSES
KA1 POWER “ON” RELAY
KA2 FAN UNIT ALARMS RELAY
KA3 HP RELAY
KA5 PHASE SEQUENCE RELAY
KM1 COMPRESSOR 1 CONTACTOR
KM13 PUMP 1 CONTACTOR
KM14 PUMP 2 CONTACTOR
KM2 COMPRESSOR 2 CONTACTOR
KM21 FAN UNITS CONTACTOR
KM40 EVAPORATOR HEATER CONTACTOR
QM13 PUMP 1 MOTOR OVERLOAD CUT-OUT
QM14 PUMP 2 MOTOR OVERLOAD CUT-OUT
QS1 MAIN POWER DISCONNECT SWITCH
TC1 CONTROL CIRCUITS TRANSFORMER
Blue Box - 58
ELECTRICAL PANEL LAY OUT
Unit with 4 compressors - pCO 2 controller
ZETA 2002 - Models 14.4 - 26.4
RGF EXPANSION
MODULE FOR LE UNIT
KEY TO ELECTRICAL COMPONENT PART NUMBERS
A2
A3
A5
A7
CONTROL BOARD
2-COMPRESSOR EXPANSION BOARD
SPEED REGULATOR
RGF EXPANSION MODULE, UNIT /LE
FU1
FU2
COMPRESSOR 1 FUSES
COMPRESSOR 2 FUSES
FU20 RGF FUSES
FU21 FAN UNIT FUSES
FU22 FUSES - FAN UNITS 2
FU23 FUSES - FAN UNITS 3
FU3
FU4
FUSES - COMPRESSOR 3
FUSES - COMPRESSOR 4
FU40 FUSES- HEATERS
FU50 FUSES - AUXILIARY TRANSFORMER
FU51 CONTROL CIRCUITS FUSE
FU52 CONTROLLER FUSE
FU56 PHASE SEQUENCE RELAY FUSES
KA1
KA2
KA5
KM1
POWER “ON” RELAY
FAN UNIT ALARMS RELAY
PHASE SEQUENCE RELAY
COMPRESSOR 1 CONTACTOR
KM13 PUMP 1 CONTACTOR
KM14 PUMP 2 CONTACTOR
KM2 COMPRESSOR 2 CONTACTOR
KM21 FAN UNITS CONTACTOR
KM22 FAN UNIT 2 CONTACTOR
KM23 FAN UNIT 3 CONTACTOR
KM3
KM4
COMPRESSOR 3 CONTACTOR
COMPRESSOR 4 CONTACTOR
KM40 EVAPORATOR HEATER CONTACTOR
QM13 PUMP 1 MOTOR OVERLOAD CUT-OUT
QM14 PUMP 2 MOTOR OVERLOAD CUT-OUT
QS1 MAIN POWER DISCONNECT SWITCH
TC1 CONTROL CIRCUITS TRANSFORMER
Blue Box - 59
5. START-UP
5.1 PRELIMINARY CHECKS
- Check that the electrical connections have been made correctly, and that all terminals are well tightened.
- Check that the voltage on the RST terminals is 400 V ± 5% (or the unit’s rated value, in the event of units supplied to run on non-standard power supplies). If the mains voltage is subject to frequent fluctuations, consult our Engineering Department to discuss the necessary protection systems.
- Check that the display shows the gas pressure in the refrigerant circuit (4-compressor models only).
- Inspect the unit for refrigerant leaks using a leak detector if necessary.
- Check that the crankcase heaters are correctly supplied with power.
Significant leakage of R407C refrigerant in the gaseous state will alter the percentages of the remaining mixture with consequent fall-off of performance.
The heaters must be connected at least 12 hours before starting the unit; the heaters are automatically connected when the main disconnect switch is set to the ON position.
- Verify that heaters are working correctly: after the warm up period the crankcase must be warm to the touch and must have at least a temperature 10 - 15 °C higher than ambient temperature.
- Check that all hydraulic connections are correctly installed and all indications on unit labels are observed.
- Check that the hydraulic system has been vent to eliminate any air remaining; charge it gradually and open the vent devices on the upper part, provided at the care of the installer together with an expansion tank of a proper size.
Warning: before starting up the unit check that all the closing panels are in position and secured with the relative screws.
Blue Box - 60
Models 3.2 - 13.2, µ chiller control
6 UNIT WITH mCHILLER MICROPROCESSOR (models from 3.2 to 13.2)
6.1 INTRODUCTION
“µchiller” is an electronic microprocessor system designed to control all the unit’s functions.
The terminal is equipped with five LEDs indicating the operating status of the machine (summer/winter), the compressor status (On/Off) and indication of the compressors/pump hour counter after the first 100 hours of operation. An internal beeper (which can be inhibited by means of a microswitch or a parameter) sounds to warn of machine operating anomalies.
6.1.1 Display
The display comprises three digits with automatic display of the decimal point. During normal operation the display shows the value of the evaporator inlet water temperature.
“µchiller” can be connected to a computer, by means of an optional electronic board, making available remote supervision and telediagnostic services for complete management, supervision and diagnostics of the systems from a remote location.
Figure 13
6.1.2 Machine status information
Machine status information is shown by five LEDs on the remote control display (figure 14).
Figure 14
6.1.3 Keypad
The keypad allows machine operating parameters to be programmed. The wall-mounted version features an extended number of keys to facilitate use. The function of each key is illustrated on the following pages.
Figure 15
Blue Box - Page 61
Models 3.2 - 13.2, µ chiller control
6.1.4 Control and display screens
Method of accessing the set-point and main machine control parameters.
Parameter scroll keys
Figure 16
Pressing the keys marked with an up or down arrow allows you to scroll through the parameters. The SEL key is pressed again to display the value of the selected parameter, with the facility to edit the value if required using the Up or Down keys. The PRG key is pressed to store changed values and to stop the procedure, while pressing the SEL key returns you to the parameter selection menu. If no keys are pressed, in an interval of 10 seconds, during parameter editing the display starts flashing. If no keys have been pressed within 60 seconds, after activating the programming procedure, the controller will return to the temperature display without saving any changes that have been made. This procedure is useful if it proves unnecessary to alter any parameters.
6.1.5 Muting the BUZZER
Press the MUTE key to silence the buzzer if it is currently sounding.
Figure 17
6.1.6 ALARMS reset
Pressing the Up or Down keys for more than 5 seconds cancels any alarms currently in the memory (manual reset), clear the associated message from the display and deactivate the alarm relay. In wall mounted models this function is obtained by pressing the CLEAR key for 5 seconds.
Figure 18
Blue Box - Page 62
Models 3.2 - 13.2, µ chiller control
6.1.7 Activation/deactivation of COOLING operation (summer mode)
Pressing the key for more than 5 seconds activates or deactivates the summer operating mode (refer also to parameter P6). It is not possible to switch directly from Winter mode to Summer mode without first deactivating
Winter mode. If the machine was previously running in Winter mode pressing this key will have no effect.
Figure 19
6.1.8 Activation/deactivation of HEATING mode (winter mode)
Pressing the key for more than 5 seconds activates or deactivates the winter operating mode. It is not possible to switch directly from Summer mode to Winter mode. If the machine was previously running in Summer mode pressing this key will have no effect - Summer mode must be deactivated before the change can be made.
Figure 20
6.1.9 Switching off the machine (stand by)
To switch off the machine deactivate both Summer and Winter modes.
Switch off the unit when working in cooling mode
(Summer).
Figure 21
Switch off the unit when working in heating mode
(Winter).
Figure 22
Blue Box - Page 63
Models 3.2 - 13.2, µ chiller control
6.1.10 Inlet water temperature control:
To edit the operating values (within the operating limits) hold down the SEL button for 5 seconds. When it flashes use the Up or Down arrow keys to enter the required inlet water temperature on the display. Confirm the value you have just entered by pressing the SEL button again (figure 23).
Parameter scroll keys
Figure 23
6.1.11 Defrosting (heat pump mode only)
During winter heat pump mode operation the finned coil of the air cooled condenser functions as an evaporator, cooling and dehumidifying ambient air.
During heat pump operation, the evaporation pressure is monitored to prevent it from falling below a preset value. The evaporation control is active only during heating mode operation.
Depending on the ambient air temperature and humidity conditions, condensate or frost will tend to form, consequently obstructing the free passage of air and causing thermal insulation. The frost that builds up on the coil obstructs the passage of air and reduces the available heat exchange surface area (and thus the thermal efficiency) and can damage the heat exchanger.
Defrosting is the procedure that eliminates the ice that has formed on the evaporator coil during heat pump mode operation of an air/water unit.
Defrosting is performed simultaneously for the entire unit.
All heat pump versions are equipped with a control that activates an automatic coil defrost cycle when necessary.
After starting however, the first defrost cycle will be started after a preset minimum operating time to allow the formation of sufficient thermal inertia to allow the cycle to be completed successfully.
Defrost cycle activation is based on the detection of a low suction pressure value due to insufficient heat exchange between the evaporator and the air due to the formation of a layer of ice, which exerts a thermal insulation effect. For a defrost cycle to be able to start a suction pressure of at least one of the currently operating compressors must remain below the pressure set for the defrost cycle trip signal for a preset time interval.
Before starting to defrost the coils, all the compressors are started, after which the unit reverses its operation from heat pump to chiller mode.
When the cycle is reversed the fans stop and the compressors force hot gas into the coil.
A pressure switch on the high pressure circuit maintains the discharge gas pressure below the defrost end value.
To maintain the pressure lower than the defrost end pressure the pressure switch activates the fans.
To reduce the air flow and obtain more efficient heating of the outer part of the coil, the pressure switch signal causes the fans to rotate in reverse.
When the defrost end temperature is reached, as measured by a thermostat with a probe located in the lower part of the coil, the pressure switch allows the discharge pressure to reach the defrost end pressure.
When the defrost end pressure has been reached, the controller reverses the unit from chiller mode to heat pump mode, thereby terminating the defrost procedure.
Even though in certain conditions the surface temperature of the coil and the condensation pressure fail to reach the defrost values within the preset time limit, the defrost cycle is forcibly terminated as though the defrost end signal were present. The controller restarts the fans, and when the pressure lowers again to the preset value, it reverses the unit’s operating mode again.
If the defrost cycle is forcibly interrupted, with the timeout signal, a message is displayed on the controller, although no controller functions are activated.
The defrost timeout alarm is automatically cleared from the active alarms menus when a defrost cycle terminates
Blue Box - Page 64
Models 3.2 - 13.2, µ chiller control normally because the defrost end pressure has been reached. In any event, the alarms historical file will contain a record of all defrost cycles that were terminated forcibly due to a timeout intervention.
Consecutive defrost cycles must be at least 30 minutes apart. If the forced defrost signal persists, inform the
Service organisation.
If the unit fails to start: do not change internal electrical connections on penalty of immediate invalidation of the warranty.
Warning: The operating mode changeover should only be seasonal.
Frequent changeover from summer to winter operating mode and viceversa could cause damage to the compressors.
During idle periods do not disconnect the unit from the power supply (the compressor crankcase heaters must remain switched on). Disconnect the unit from the power supply only in the event of prolonged disuse (e.g.
seasonal shutdowns). For temporary shutdown of the unit refer to the guide lines given in the specific headings of this manual.
Electronic components of the microprocessor may be damaged at temperatures below - 20 °C.
Blue Box - Page 65
Models 3.2 - 13.2, µ chiller control
6.2 STARTING THE UNIT
The ZETA 2002 unit is equipped, as standard, with direct keypad control.
Optionally the unit can be equipped to operate via a remote permissive (e.g. a clock, etc.). The remote interlock must be connected across terminals 1-2. Enabling the unit to start or stop is only possible via the keypad.
6.2.1 COOLING:
- Press the button as shown in figure 24.
Figure 24
6.2.2 HEATING (operation in heat pump mode):
- Press the button as shown in figure 25.
Figure 25
6.3 STOPPING THE UNIT
6.3.1 Temporary stop
The unit is stopped by pressing the cooling key or, in the case of a heat pump unit operating in winter mode, by pressing the heating key.
Shutdown of unit operating in summer cooling mode
Figure 26
Shutdown of unit operating in winter heating mode
Figure 27
Warning: do not use the machine main power switch to stop the unit.
The crankcase heaters will be disconnected, resulting in serious risk to the compressors when the unit is started again.
Blue Box - Page 66
Models 3.2 - 13.2, µ chiller control
6.3.2 Seasonal stop:
- Disconnect the power supply
- Drain the system circuit (unless it contains a water/glycol solution)
- When the unit is to be restarted repeat the initial start-up procedure
Warning: do not use the machine main power switch to stop the unit: this switch must be used to disconnect the electrical supply when no current is flowing on the circuit, i.e. only when the unit is in OFF status.
Note also that if power is disconnected from the unit the crankcase heaters will be switched off with the resulting risk of compressor damage at the time of restarting.
6.4 EMERGENCY STOP
Emergency stops are obtained by turning the red colour main disconnect switch on the electrical panel to position
0.
7. TROUBLESHOOTING
The following pages contain a list of the most common causes that can result in the shutdown or anomalous operation of the chiller. Faults are arranged in accordance with easily identifiable symptoms.
In relation to possible corrective action pay maximum attention to the operations you intend to perform as overconfidence coupled with insufficient attention due to lack of expertise can lead to serious accidents.
We therefore recommend that Blue Box or other skilled HVAC engineers are contacted to identify and correct the problem.
Blue Box - Page 67
Models 3.2 - 13.2, µ chiller control
SYMPTOM
A)
No compressor running. Fans stopped (display off)
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
PROBABLE CAUSE POSSIBLE CORRECTIVE ACTION
No mains power Check presence of mains power
Main power switch Off
(position "O")
Turn mains power selector to position "I"
No power to control circuits Check condition of fuses FU50,
FU51, FU52.
Check operation of the transformer
Incorrect phase sequence
(relay KA5 with only green
LED illuminated)
Invert two of the phase wires of the power feed line; when the unit is powered up again both the green LED and the yellow
LED should light
Relay KA5 with green and yellow LEDs off
Check fuses FU56;
If fuses are OK replace phase sequence relay
B)
No compressor running. Fans stopped (display on no alarm messages)
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
Unit in stand-by mode
No consent from service thermostat
Start unit (see relative section of the manual)
System at set-point temperature, no heating/cooling demand; check settings and operation.
No external consent Check operation of circulating pumps, flow switches, bleed air from the system; check that contacts 1 and 2 are closed, check other external consents.
Compressor motor burnt out or compressor seized
Replace compressor
Anti-recycle timer running Wait for 5 minutes until the timer generates a consent
Blue Box - Page 68
Models 3.2 - 13.2, µ chiller control
SYMPTOM
C)
No compressor running. Fans stopped
(display On with alarm "FL")
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
PROBABLE CAUSE
No water flow at evaporator
Faulty flow switch
D)
No compressor running. Fans stopped
(display On with alarm
“F1” or “F2”)
E)
No compressor running. Fans stopped
(display On with alarm
"A1")
⊗
⊗
⊗
⊗
⊗
⊗
Fan thermal protection intervention
No consent of defrost thermostat due to insufficient water flow rate
No consent of defrost thermostat due to insufficient glycol concentration
POSSIBLE CORRECTIVE ACTION
Check hydraulic system
Check contact of flow switch and replace if necessary
Check insulation between windings and between windings and earth; replace fan if necessary.
Check hydraulic circuit and wait until the water temperature exceeds the value necessary for the unit to restart
The programmed set-point is too low for the percentage of glycol in the circuit. Increase the glycol percentage and reduce the defrost set-point.
F)
No compressor running. Fans stopped
(display On with alarm "E1")
⊗
⊗
⊗
⊗
Connections to evaporator inlet temperature sensor interrupted
Evaporator inlet temperature sensor faulty
Restore correct connection of temperature sensor
Replace temperature sensor
Blue Box - Page 69
Models 3.2 - 13.2, µ chiller control
SYMPTOM
G)
No compressor running. Fans running
(display On with alarm "E3" or "E5")
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
⊗ ⊗
PROBABLE CAUSE
Resistance RK3 or RK4 faulty or disconnected
Connections to pressure sensor interrupted (HP version only or if condensation pressure control with fan speed regulator is fitted)
Faulty pressure sensor (only on HP version or if condensation pressure control with fan speed regulator is fitted)
H)
Unit runs with insufficient capacity
(Display On without alarms)
⊗
⊗
⊗
⊗
Insufficient refrigerant charge
Presence of moisture in refrigerant circuit
⊗
⊗
⊗
⊗
⊗
One compressor fails to start, power circuit open and compressor contactor energised
A compressor fails to start, fuses are OK and compressor contactor is deenergised
4-way reversing valve seized or coil faulty
POSSIBLE CORRECTIVE ACTION
Check resistance and replace if necessary
Restore correct connections to pressure sensor ("E3" refers to compressor 1, "E5" refers to compressor 2)
Replace pressure sensor ("E3" refers to compressor 1, "E5" refers to compressor 2)
Check refrigerant circuits with leak detector, repair leak and recharge circuit
Replace refrigerant filter and, if necessary, dehydrate and recharge circuit
Find and eliminate the cause of the protection intervention; change the fuses.
If the fuses blow immediately, replace the compressor.
Check voltage across compressor contactor coil and continuity of coil; if necessary, replace coil
Check power supply and coils of valves and replace valves if necessary
Blue Box - Page 70
Models 3.2 - 13.2, µ chiller control
SYMPTOM
I)
Compressor 1 and/or 2 not working (display
On with alarm
“H1” and/or “H2”)
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
PROBABLE CAUSE POSSIBLE CORRECTIVE ACTION
Circuit overcharged Check refrigerant charge and remove if necessary;
High pressure switch faulty Check and replace if necessary
Coil filters clogged; air flow too low
Presence of incondensable gas in the refrigerant circuit
Clean filters with compressed air
Empty circuit, apply vacuum, and recharge
Fans faulty
Faulty circulating pump
Defrost-end pressure switch not working
Fan motor electrical connections incorrect
Fan contactors not energised
Check and replace fans
Check and replace
Check and replace
Check that connections are as indicated on electrical drawing
Check voltage across coil of contactor KM21 and electrical continuity of coil circuit
Blue Box - Page 71
Models 3.2 - 13.2, µ chiller control
SYMPTOM
L)
Compressor 1 and/or 2 not working (display
On with alarm “L1” and/or “L2”)
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
PROBABLE CAUSE POSSIBLE CORRECTIVE ACTION
Refrigerant circuit completely empty
Check refrigerant circuit with leak detector after pressurising to approximately 4 bar. Repair leak, apply vacuum, charge circuit.
Low pressure switch faulty Check and replace if necessary
Coil filter clogged; air flow too low
Clean filter with compressed air
Refrigerant filter clogged Check and replace if necessary
Fans faulty Check and replace if necessary
Faulty water circulating pump
Defrost pressure switch has incorrect setting
Liquid refrigerant valve not completely open (if present)
Check and replace if necessary
Check and correct setting
Check and open fully
Thermostatic expansion valve not operating correctly
Fan motor electrical connections incorrect
Check, clean, or replace if necessary
Check that connections are as indicated on electrical schematic
Fan contactors not energised
Check voltage across coil of contactor KM21 and electrical continuity of coil circuit
Blue Box - Page 72
Models 3.2 - 13.2, µ chiller control
SYMPTOM
M)
Compressor 1 and/or 2 not working (display
On with alarm
“C1” and/or “C2”)
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
⊗
N)
Ice on liquid refrigerant pipe
⊗
⊗
O)
Compressor 1 and/or 2 running. Ice on coil
(display On with warning message “r1”)
P)
Compressors run constantly
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
PROBABLE CAUSE
Insufficient refrigerant charge
4-way valve locked
Lack of oil
Liquid refrigerant filter clogged
Valve on liquid refrigerant line (if present) not completely open
Replace filter
Open valve fully
Insufficient refrigerant charge
Operating thermostat incorrectly set or faulty
Lack of refrigerant gas charge
Excess thermal load
POSSIBLE CORRECTIVE ACTION
Find leak with leak detector, repair, and recharge circuit
Replace valve
Check quantity of oil in circuit and replenish as necessary.
Check that the circuit has all the necessary measures to ensure oil return to the compressor
Find leak with leak detector, repair, and recharge circuit
Check setting; replace thermostat if necessary
Check and recharge if necessary
Reduce thermal load
Blue Box - Page 73
Models 3.2 - 13.2, µ chiller control
SYMPTOM
Q)
Anomalous noise from system
OPERATION
COOLING HEATING
⊗ ⊗
PROBABLE CAUSE
Compressor noisy
⊗ ⊗ Thermostatic valve noisy
⊗
⊗
⊗
⊗
⊗
⊗
Vibrating pipes
Casing panels vibrate
Worn fan bearings
POSSIBLE CORRECTIVE ACTION
Contact service organisation for check and replacement if necessary
Contact service organisation for check and replenish refrigerant charge
Contact service organisation to secure piping
Check that panels are properly fastened; contact service organisation if necessary
Check; replace fan if necessary
If the display presents alarms other than those described previously, contact the Service organisation.
Blue Box - Page 74
Models 14.4 - 26.4, pCO 2 control
8 UNIT WITH pCO
2
MICROPROCESSOR (models from 14.4 to 26.4)
8.1 INTRODUCTION
The pCO 2 electronic microprocessor controller with the DBBB0*P20Z program is designed to manage chiller and heat pump units, with control of 4 compressors.
The program configuration manages the total control of the air-cooled unit with plate exchangers including compressor start/stop times, safety devices and other auxiliary functions such as condensation control in cooling mode, free-cooling, heat recovery and other functions described later in this manual.
The necessary hardware is optimised to obtain the maximum advantage from the available inputs and outputs; the connection between various circuit boards and the user interface terminal is achieved via the pLANE using the dedicated RS485 serial connector for network connections.
Each unit can also be connected to remote supervision and/or telediagnostics systems by means of an RS485 serial line.
Detailed information on the operation of the above systems is provided in the specific controller manual supplied with the unit.
8.1.1 Display
The back-lit LCD display comprises 4 lines and 20 columns.
Figure 28
8.1.2 Keypad
In addition to the LCD display, the user interface is equipped with the following function keys:
“Menu” key: press this key from any menu to return to the opening menu.
Maintenance key: press this key to access the maintenance menus.
Print key: this key is currently not used.
"I/O" key: pressing this key opens the menus containing the status of the digital inputs and outputs together with the values read on the analogue inputs and the value of the analogue outputs
Blue Box - Page 75
Models 14.4 - 26.4, pCO 2 control
“Clock” key: press this key to open the clock menus.
“Set” key: this key opens the menus in which the various operating set-points can be edited.
“Prog” key: this key opens the service menus.
"? info" key: pressing this key opens a menu in which the address of the component connected to the terminal can be changed.
"Summer" key (blue) and "winter" key (red): in the case of chiller + heat-pump units, press these keys to select the required operating mode.
“ON/OFF” key: press this key to switch from Stand- by to ON or vice versa.
“Alarm” key: this key serves to mute the alarm buzzer, display any active alarms, and reset them in certain cases.
Arrow key: the arrow keys allow you to navigate through the menus; when an editable field is selected, the arrow keys serve to change the current value.
“Enter” key: pressing this key allows you to access fields containing editable parameters and also to confirm any changes you make to such parameters.
Electronic components could be damaged by air temperature below -20
°C.
Blue Box - Page 76
Models 14.4 - 26.4, pCO 2 control
8.2 OPERATING DESCRIPTION
8.2.1 Introduction
The microprocessor control regulates the water temperature of the evaporator maintaining it at the set-point value acting on the compressors management.
As well as the compressors the controller manages the operation of other components of the chiller such as the pumps (ST version) and fans, with relative operating times and alarms, and "ancillary" functions such as condensation control, etc., as described below.
Almost all the parameters referred to below (set-points, differentials, calibration, delays...) can be programmed by means of the various menus. Refer to the specific manual for the pCO 2 controller.
8.2.2 Unit in stand-by mode
The unit is in stand-by mode when it is correctly supplied with power but not actually enabled to operate.
In this condition the display shows the values of the various machine parameters, but the operation of the compressor is not inhibited.
Power-on is obtained by pressing the “ON-OFF” button of the microprocessor control or via an external interlock.
8.2.3 Enabling the unit
Start-up of the unit from stand-by mode can be achieved after closing the external enabling contact, by pressing the “ON/OFF” button, or by means of a signal on the serial line.
Activation of the controller outputs that manage the various sections of the chiller is executed in strict compliance with the operating times. If the “ON” button is pressed before the external interlocks are closed, the display indicates which of the external interlocks is not yet enabled.
Operation of the pump has priority to the compressors, which can start only after the evaporator and condenser pumps are running.
8.2.4 Pump management (ST units only)
If system pump control is included switching on the unit will automatically enable the pump.
If there are two pumps (run and stand-by) they will be activated alternately when the programmed operating time limit for each pump has elapsed.
When the pumps are switched over both pumps will run in tandem, for a few seconds, to ensure a constant flow of water in the system circuit.
When the unit is switched from active status to stand-by, if performed by opening an external permissive, the currently active pump of the ST unit will be stopped with a delay interval, after the disconnection of the last compressor in operation, making it possible to exploit the thermal inertia of the system.
8.2.5 Compressor start-up
The controller allows the compressors to be started if the flow switch input is closed within the compressor startup delay time interval. If the flow switch input opens, after the compressor has started, the trip is retarded if it occurs within the time programmed for the compressor stop.
If the unit trips due to the opening of the flow switch input, the relative alarm is displayed.
Starting and stopping of the compressors and capacity step control is managed by the controller in accordance with the building cooling demands.
8.2.6 Chiller mode operation
In chiller operation, the controller lowers the water temperature value, maintaining it as close as possible to the programmed set-point.
Blue Box - Page 77
Models 14.4 - 26.4, pCO 2 control
In the standard version, in which the control acts on the evaporator entering water, the management of compressor operation and capacity steps is linked to the difference between the entering water temperature and the programmed set-point.
8.2.7 Heat pump mode operation
In heat pump operation, the controller increases the water temperature value, maintaining it as close as possible to the programmed set-point.
Management of compressor operation is performed in the same way as already illustrated for chiller mode operation.
8.2.8
Evaporator low temperature chilled water protection
If the evaporator leaving water temperature is lower than the limit value programmed in the low temperature chilled water protection set-point, the controller will stop all the compressors and activate the low temperature water alarm.
This alarm must be reset manually and the compressor restarted only when the evaporator leaving water temperature is equal to or higher than the alarm trip value, increased by the low temperature water differential.
The low temperature water alarm can only appear when the unit is switched on (in stand-by conditions the freeze alarm is not operational).
8.2.9 Evaporator anti-freeze protection electric heater (optional)
In conditions that lead to tripping the freeze alarm, the controller energises the heater.
The heater remains powered for the entire time that the conditions for the freeze alarm continue.
Unlike the low water temperature alarm, which is enabled only when the unit is powered on, the anti-freeze heater can be energised when the machine is on stand-by.
8.2.10 Compressor operation
When the unit is running correctly and no general alarms are present, the microprocessor controller starts the compressors in accordance with the water temperature reading.
Compressor starts are staggered in accordance with preset delay intervals, thus avoiding excess input current surges.
Before starting a compressor, the microprocessor checks the value of the delivery pressure by means of the relevant transducer, the status of the high pressure switch and the compressor motor windings temperature by checking the thermal protection.
When the compressor has been started, tripping of any of the safety devices will cause the compressor to stop immediately and an alarm will be displayed.
While the compressor is running, discharge pressure and suction pressure are monitored constantly by means of the relevant sensors.
On unit start-up the first compressor is started with a delay, set on the microprocessor controller, after the start of the hydraulic system circulating pump.
Once started, each compressor must run for a minimum operating period, unless a critical alarm should trip in the meantime.
The critical alarms which can stop the compressor during the minimum operating time are the high pressure alarm and the compressor thermal cut-out alarm. Once stopped each compressor can be restarted only after a minimum idle time or after a minimum time interval between two consecutive starts has elapsed.
The consecutive starting of two compressors or the consecutive starting of one compressor, is executed with minimum delay intervals equal to the capacity step activation time.
Stopping compressors is also performed with a minimum programmed delay interval.
Blue Box - Page 78
Models 14.4 - 26.4, pCO 2 control
8.2.11 Compressor management
Start-up of the compressors is automatic when the reference water temperature changes with respect to the programmed set-point.
Normally the reference water temperature is the value detected at the inlet to the chiller unit.
Balancing of duty hours over all the compressors in the unit is performed by selecting the rotation of starts.
With the rotation function of starts active, the first compressor to start is the first one that previously stopped. The first compressor to start will be the one with the least operating hours.
8.2.12 High and low pressure alarms
Discharge pressure (high pressure) and suction pressure (low pressure) are managed by the microprocessor controller through the relevant sensors.
When a compressor is running, the controller checks that:
- Discharge pressure is always lower than the safety value set for cooling or heating mode operation. If the values are exceeded, the controller immediately stops the compressor and displays a high pressure alarm. The high pressure alarm can be reset manually on the controller only when the pressure detected by the discharge pressure sensor is lower than the value that caused the alarm to trip, less the differential value.
- The suction pressure is always higher than the safety value set for operation in cooling or heating mode. If the value read by the suction pressure sensor is lower than the limits set for the relative operating conditions, the controller will stop the compressor and generate a low pressure alarm. The low pressure alarm is not instantaneous, but operates after a preset delay interval, both in the starting phase and during the normal running of the machine. The low pressure alarm can be reset automatically or manually, depending on the relative parameter setting. In all cases the low pressure alarm can only be reset when the pressure detected by the suction sensor is higher than the value that caused the alarm to trip, plus the differential value. It is possible to program the number of permissible consecutive compressor starts before the unit shuts down in safety status.
8.2.13 Low ambient temperature kit (option - condensing control with fan speed regulator)
As the ambient air temperature decreases the necessary condensing pressure for correct operation of the chiller cycle is maintained, within the machine operating range, by adjusting the cooling air flow through the condenser.
Condensing pressure control is only active when the machine is operating in chiller mode.
When the unit is operating in heat pump mode this function is inhibited and the fans are forced to their maximum speed.
The controller checks the condensing pressure and adjusts fan speed on the basis of the circuit with the highest pressure reading. The speed regulator adjusts fan speed with a phase control system that minimises problems related to electromagnetic compatibility.
Speed control is available over a 40-100% range. At the time of start-up the fans always run at 40% nominal speed.
8.2.14 Changeover from chiller to heat pump and vice versa
The changeover from chiller to heat pump and back can be performed at any time, either by means of an external signal on a digital input, from the keypad, or via the serial line. The operating mode changeover must be only seasonal and only with the unit off.
After a mode changeover, the controller re-starts the unit in the new mode with a factory set minimum delay time.
The unit operates with temperature control on the inlet to which has been inactive for the longest time. the unit
(or return from the system).
8.2.15 Defrosting (heat pump units only)
Blue Box - Page 79
Models 14.4 - 26.4, pCO 2 control
During winter heat pump mode operation the finned coil of the air cooled condenser functions as an evaporator, cooling and dehumidifying ambient air.
During heat pump operation, the evaporation pressure is monitored to prevent it from falling below a preset value. The evaporation control is active only during heating mode operation.
Depending on the ambient air temperature and humidity conditions, condensate or frost will tend to form, consequently obstructing the free passage of air and causing thermal insulation. The frost that builds up on the coil obstructs the passage of air and reduces the available heat exchange surface area (and thus the thermal efficiency) and can damage the heat exchanger.
Defrosting is the procedure that eliminates the ice that has formed on the evaporator coil during heat pump mode operation of an air/water unit.
Defrosting is performed simultaneously for the entire unit.
All heat pump versions are equipped with a control that activates an automatic coil defrost cycle when necessary.
After starting however, the first defrost cycle will be started after a preset minimum operating time to allow the formation of sufficient thermal inertia to allow the cycle to be completed successfully.
Defrost cycle activation is based on the detection of a low suction pressure value due to insufficient heat exchange between the evaporator and the air due to the formation of a layer of ice, which exerts a thermal insulation effect. For a defrost cycle to be able to start a suction pressure of at least one of the currently operating compressors must remain below the pressure set for the defrost cycle trip signal for a preset time interval.
Before starting to defrost the coils, all the compressors are started, after which the unit reverses its operation from heat pump to chiller mode.
When the cycle is reversed the fans stop and the compressors force hot gas into the coil.
A pressure switch on the high pressure circuit maintains the discharge gas pressure below the defrost end value.
To maintain the pressure lower than the defrost end pressure the pressure switch activates the fans.
To reduce the air flow and obtain more efficient heating of the outer part of the coil, the pressure switch signal causes the fans to rotate in reverse.
When the defrost end temperature is reached, as measured by a thermostat with a probe located in the lower part of the coil, the pressure switch allows the discharge pressure to reach the defrost end pressure.
When the defrost end pressure has been reached, the controller reverses the unit from chiller mode to heat pump mode, thereby terminating the defrost procedure.
Even though in certain conditions the surface temperature of the coil and the condensation pressure fail to reach the defrost values within the preset time limit, the defrost cycle is forcibly terminated as though the defrost end signal were present. The controller restarts the fans, and when the pressure lowers again to the preset value, it reverses the unit’s operating mode again.
If the defrost cycle is forcibly interrupted, with the timeout signal, a message is displayed on the controller, although no controller functions are activated.
The defrost timeout alarm is automatically cleared from the active alarms menus when a defrost cycle terminates normally because the defrost end pressure has been reached. In any event, the alarms historical file will contain a record of all defrost cycles that were terminated forcibly due to a timeout intervention.
Consecutive defrost cycles must be at least 30 minutes apart. If the forced defrost signal persists, inform the
Service organisation.
8.2.16 Total heat recovery (option)
Heat recovery is the function where all the energy that would normally be rejected to the air cooled condenser is recovered at a refrigerant to water condenser installed in series with the air-cooled condenser.
The heat recovery process is managed by the microprocessor controller.
During energy recovery the fans are stopped and the condensing coil is by-passed via solenoid valves connected downstream of the thermostat valve. The machine is equipped with a liquid receiver.
Heat recovery can only occur when the water temperature at the recovery exchanger inlet is lower than the recovery set-point. Heat recovery is terminated when the temperature increases by the recovery differential value.
It is mandatory to use a condensing pressure control valve (one for each hydraulic circuit) or three-way valve, fitted by the installer, to avoid condensation values that are incompatible with operation of the machine.
8.2.17 Dual set-point (option)
Blue Box - Page 80
Models 14.4 - 26.4, pCO 2 control
Operation with a dual set-point is possible only in chiller mode.
With double thermostatic valves and solenoid valves that are automatically switched according to the required expansion temperature. Two set-point values can be programmed on the microprocessor controller via the keypad or a digital input. Switching of the thermostatic valves is always automatic, in accordance with the water temperature.
The valves are sized on the basis of the temperature values specified at the time of the order. The machine operating limits shown in the catalogue are not affected. If the hydraulic circuit contains glycol in sufficient quantities to eliminate the risk of freezing, the lower limit is extended to a minimum of -5 °C leaving water temperature.
8.2.18 Operation leaving water temperature control (option)
With leaving chilled water temperature control the reference sensor must be installed on the evaporator outlet or, if there is more than one evaporator, on the common outlet pipeline downstream from the relative manifold.
The unit’s capacity steps are activated / deactivated with delay intervals in relation to a dead zone. When the leaving water temperature is higher than the programmed set-point compressors start is enabled.
Blue Box - Page 81
Models 14.4 - 26.4, pCO 2 control
8.3 STARTING THE UNIT
For the start-up procedure refer also to the microprocessor controller manual.
- Close the external enabling contacts
- Press the "ON" button on the microprocessor controller
- If all the controls are enabled the display will show the message "UNIT ON"
After having performed the above procedures the unit will start automatically after a delay of approximately 5 minutes, assuming that the enabling signals of the microprocessor, the flow switches, and the water pumps continue to be present.
If the unit fails to start: do not change internal electrical connections on penalty of immediate invalidation of the warranty.
Important: on heat pump versions the operating cycle must be reversed at the start and end of the season. Frequent switching from summer to winter mode, and vice versa, should be avoided at all costs because it can lead to malfunctions and subsequent breakdown of the compressors.
During idle periods do not disconnect the unit from the power supply (the compressor crankcase heaters must remain switched on in these intervals).
Disconnect the unit from the power supply only in the event of prolonged disuse (e.g. seasonal shutdowns). For temporary shutdown of the unit refer to the guide lines given in paragraph 8.4.
8.4 STOPPING THE UNIT
8.4.1 Temporary stop:
- To stop the unit press the "OFF" button on the front panel.
8.4.2 Seasonal stop:
- Disconnect the power supply
- Drain the system circuit (unless it contains a water/glycol solution)
- When the unit is to be restarted repeat the initial start-up procedure
Figure 29
Warning: do not use the machine main power switch to stop the unit: this switch must be used to disconnect the electrical supply when no current is flowing on the circuit, i.e. only when the unit is in OFF status.
Note also that if power is disconnected from the unit, the crankcase heaters will be switched off with the resulting risk of compressor damage at the time of restarting.
Blue Box - Page 82
Models 14.4 - 26.4, pCO 2 control
8.5 EMERGENCY STOP
Emergency stops are obtained by turning the red colour main disconnect switch on the electrical panel to position 0.
9. TROUBLESHOOTING
The following pages contain a list of the most common causes that can result in the shutdown or anomalous operation of the chiller. Faults are arranged in accordance with easily identifiable symptoms.
In relation to possible corrective action, adopt the maximum attention in the operations you intend to perform as overconfidence coupled with insufficient attention due to lack of expertise can lead to serious accidents.
We therefore recommend that Blue Box or other skilled HVAC engineers are contacted to identify and correct the problem.
Blue Box - Page 83
Models 14.4 - 26.4, pCO 2 control
SYMPTOM
A)
No compressor running. Fans stopped (display Off)
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
PROBABLE CAUSE
No mains power
POSSIBLE CORRECTIVE ACTION
Check presence of mains power
Main power switch Off
(position "O")
Turn main power selector to position "I"
No power to control circuits Check fuses FU50, FU51, FU52.
Check operation of transformer
Incorrect phase sequence
(relay KA5 with only green
LED lit)
Invert two of the phase wires of the power supply line; when the unit is powered up again both the green and yellow LEDs should light
Relay KA5 with green and yellow LEDs off
Check fuses FU56;
If fuses are OK replace phase sequence relay
B)
No compressor running. Display On:
”OFF from external consent”
C)
No compressor running. Display On:
”OFF from supervision system”
D)
No compressor running. Display On:
”OFF”
⊗
⊗
⊗
⊗
⊗
⊗
No external consent
No consent from supervision system
No consent from “on/off” key of user interface
Check presence of external consent; if not present, bridge terminals 1 and 2
Activate operation from supervision system
Press “on/off” key
Blue Box - Page 84
Models 14.4 - 26.4, pCO 2 control
SYMPTOM
E)
No compressor running. Display On: unit ON with alarm
“High Pressure
Compressor 1, 2, 3, 4”
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
⊗
PROBABLE CAUSE POSSIBLE CORRECTIVE ACTION
220V fuses burnt-out
(FU51)
Change fuses. If fuses burn-out again, contact assistance
Fans contactor not energised
Check voltage across the contactor coil and coil continuity
Fan fuses burnt-out (FU21) Check cause of burn-out and change fuses.
Fan motor faulty Check and replace if necessary
F)
No compressor running. Display On: unit ON with alarm
“Fans protection”
G)
No compressor running. Display On: unit ON with alarm
“Thermal protections
Compressor 1, 2, 3, 4”
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
Fan thermal protection intervention
Fan motor faulty
Faulty fan alarm relay
Drop in power feeding voltage
Check insulation between windings and from windings to ground
Check and replace if necessary
Check and replace relay
Check voltage stability and fit appropriate protection if necessary
Setting of thermal protections
Contact assistance
Circuits partially discharged Call service to replenish charge
Blue Box - Page 85
Models 14.4 - 26.4, pCO 2 control
SYMPTOM
H)
No compressor running. Display On: unit ON with alarm
“Low Pressure compressor 1, 2, 3, 4”
OPERATION
COOLING HEATING
⊗
⊗
⊗
PROBABLE CAUSE
Insufficient percentage of glycol in hydraulic circuit
⊗ Both circuits have insufficient refrigerant charge
⊗ Fans contactor not energised
⊗ Fan motor faulty
Insufficient water flow to evaporator
⊗ Incorrect setting of defrost set-point
I)
No compressor running. Display On: unit ON with alarm
“Exceeded Threshold
Low Temperature of leaving User Water”
J)
No compressor running. Display On: unit ON with alarm
“Exceeded Threshold
Low Temperature User
Water Reference”
⊗
⊗
⊗
⊗
⊗
Insufficient water flow to evaporator
Faulty controller
Excessive thermal load
POSSIBLE CORRECTIVE ACTION
Restore correct glycol percentage
Check voltage across the contactor coil and coil continuity
Check and replace if necessary
Check hydraulic circuit
Check and correct setting if necessary
Increase water flow to evaporator and check temperature rise
Find possible leaks in circuit, repair, and recharge
Contact service organisation
Defrost sensor short circuit Contact service organisation
Reduce thermal load
Blue Box - Page 86
Models 14.4 - 26.4, pCO 2 control
K)
SYMPTOM
No compressor running. Display On: unit ON with alarm
“Exceeded Threshold
High Temperature of entering User Water
L)
No compressor running. Display On: unit ON with alarm
“No power to
Control circuits”
M)
No compressor running.
Display On: unit
OFF with alarm
“Flow Switch Alarm”
N)
No compressor running. Display On: unit OFF with alarm
”Incorrect Phase
Sequence” and phase sequence relay with green LED On and orange LED Off
O)
No compressor running. Display On: unit OFF with alarm
”Incorrect Phase
Sequence” and phase sequence relay with green and orange LEDs
On
OPERATION
COOLING HEATING
⊗
⊗
PROBABLE CAUSE POSSIBLE CORRECTIVE ACTION
Excessive thermal load
Refrigerant circuits partially discharged
Wait until entering water temperature is below the alarm set point. Start hydraulic circuit of evaporator and unit. If not sufficient contact assistance.
Call assistance
⊗
⊗
⊗
⊗
Power supply voltage not stable
Fuses FU51 burnt-out
Check power supply voltage; if not correct contact the electricity company
Check cause of fuse burn-out and replace fuses.
⊗
⊗
⊗
⊗
No water flow to evaporator
Flow switch faulty
Check hydraulic circuit
Check flow switch contact and replace if necessary
⊗
⊗
⊗
⊗
Incorrect phase sequence
Faulty relay
Invert two of the phase wires of the power supply line
Check to ensure that relay closes contact
Blue Box - Page 87
Models 3.2 - 13.2, µ chiller control
SYMPTOM
P)
No compressor running. Display On: unit OFF with alarm
”Incorrect Phase
Sequence” and phase sequence relay with green and orange LEDs Off
Q)
No compressor running. Display On: unit ON without alarm
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
R)
One or more compressors switched off. Display On with alarm “High Pressure
Compressor”
⊗
⊗
⊗
⊗
Fuses FU56 burnt-out
One of the three phases is not present
PROBABLE CAUSE
No consent from digital input to compressors
⊗ Unit at temperature
⊗ Compressor fuses burntout
⊗ Controller faulty
Excess refrigerant charge
Check fuse FU56 and replace if necessary
Check connection of each phase
Check consent to compressors and close relative contacts
Normal operation
Check continuity of fuses; if burnt-out call service
Call service
POSSIBLE CORRECTIVE ACTION
Check refrigerant charge and call service organisation
⊗
⊗
⊗ Refrigerant circuit contains non-condensable gas
⊗ High pressure switch incorrectly set or faulty
Condenser coil or coil filters
(if present) clogged
Empty circuit, apply vacuum, and recharge
Check pressure switch setting
Clean coil and filters (if present) with compressed air
Blue Box - Page 88
Models 14.4 - 26.4, pCO 2 control
SYMPTOM
S)
One or more compressors switched off. Display On with alarm “Low Pressure
Compressors”
OPERATION
COOLING HEATING
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
PROBABLE CAUSE POSSIBLE CORRECTIVE ACTION
Insufficient refrigerant charge due to leak in circuit
Call service organisation
Thermostatic valve faulty Call service organisation
Solenoid valve of liquid refrigerant line faulty (if present)
Call service organisation
Dehydrating filter clogged Call service organisation
Evaporator coil or coil filters
(if present) clogged
Clean coil and filters (if present) with compressed air
T)
One or more compressors switched off. Display On with alarm “Compressor
Thermal Protections”
U)
One or more compressors Off.
Display On without alarms
V)
All compressors running. Display On with alarm
“Compressor
Maintenance”
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
Problems at the compressor Call service organisation
Unit capacity step active
Fuses burnt-out
Faulty controller
No external consent to compressor
Compressors specified by alarm require maintenance
Normal operation
Call service organisation
Call service organisation
Check compressor external consent
Call service for scheduled maintenance
Blue Box - Page 89
Models 14.4 - 26.4, pCO 2 control
SYMPTOM
W)
All compressors running. Display On with alarm “Unit
Maintenance”
X)
All compressors running without stopping. Display
On without alarm ⊗
⊗
⊗
OPERATION
COOLING HEATING
⊗ ⊗
PROBABLE CAUSE POSSIBLE CORRECTIVE ACTION
Unit maintenance required Call service for scheduled maintenance
⊗ ⊗
⊗
⊗
⊗
Y)
Anomalous noise from system
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
⊗
Excessive thermal load
Refrigerant circuits partially discharged
Liquid refrigerant filter clogged
Controller not working
4-way reversing valve not energised
Call service organisation
Call service organisation
Clean or replace
Call service organisation
Check power supply and solenoid valve coils and replace if necessary
Compressor noisy
Thermostatic valve noisy
Vibrating pipes
Casing panels vibrate
Worn fan bearings
Contact service organisation for check and replacement if necessary
Contact service to check and add refrigerant
Contact service organisation to secure pipes
Check that panels are properly fastened; contact service organisation if necessary
Check; replace fan if necessary
If the display presents alarms other than those described above, contact the service organisation.
Blue Box - Page 90
10 CHECKS DURING OPERATION
10.1 INTRODUCTION
- Check that the water temperature at the evaporator inlet is close to the set-point value of the service thermostat.
- For units equipped with pump units, if the pump runs noisily, close the relative delivery cock until the pump starts running smoothly again. This situation can occur when system pressure drops deviate significantly from the pump available pressure.
10.1.1 Checking the refrigerant charge
- After a few hours of unit operation check that the sight glass moisture indicator has a green coloured core. if the core is yellow, moisture is present in the circuit. In such a situation the circuit must be dehydrated by a qualified technician.
- Check the sight glass for air bubbles. A constant passage of bubbles through the sight glass could indicate that the refrigerant must be replenished. Occasional bubbles are considered normal.
- Check that refrigerant liquid superheating is between 5 and 7 °C; to do this:
1) measure the temperature using a contact thermometer placed on the compressor suction pipeline;
2) read the temperature, equivalent to the pressure read on the pressure gauge connected to the compressor suction side (saturation temperature corresponding to suction pressure); for units charged with R407C refrigerant, refer to the D.P. (Dew Point) pressure gauge scale.
The difference between the temperatures measured in this manner is equivalent to the superheating value.
- Check that refrigerant subcooling is between 5 and 7 °C; to do this:
1) measure the temperature using a contact thermometer placed on the compressor discharge pipeline;
2) read the temperature, equivalent to the pressure read on the pressure gauge connected to the liquid connection at the condenser outlet (saturation temperature corresponding to condenser delivery pressure); for units charged with R407C refrigerant, refer to the B.P. (Bubble Point) pressure gauge scale.
The difference between the temperature values measured in this manner is equivalent to the subcooling value.
Blue Box - 91
11. CALIBRATION OF CONTROL EQUIPMENT
11.1 INTRODUCTION
All the control equipment is factory calibrated before the machine is shipped. Control equipment and safety devices should nonetheless be checked after a reasonable period of operation. Calibration values are given in
Tables 3 and 4.
All service operations on the control equipment must be carried out by
QUALIFIED PERSONNEL ONLY; incorrect calibration values can cause serious damage to the unit and personal injury.
TABLE 3 - CALIBRATION OF CONTROL EQUIPMENT
CAPACITY STEPS
CONTROL ELEMENT
Service calibration (summer)
Service calibration (winter)
°C
°C
SET POINT
10
42
2
DIFFERENTIAL
2
2
SET POINT
9
43
4
DIFFERENTIAL
3
3
TABLE 4 - CALIBRATION OF SAFETY DEVICES
CONTROL ELEMENT
No-frost setting
Maximum pressure switch setting
Minimum pressure switch setting
Evaporator heater setting
Defrost start setting
Defrost end setting
Defrost end thermostat setting
Defrost pressure switch setting
°C bar bar
°C bar bar
°C bar
ACTIVATION
SET-POINT
3
27
2.5 / 0.7 *
3
2
18
5
16
DIFFERENTIAL
--
--
1
6
6
7
--
2
RESET manual manual manual (from controller) automatic automatic automatic automatic automatic
* Chiller / heat pump
Blue Box - 92
12. MAINTENANCE AND PERIODIC CHECKS
12. 1 WARNINGS
All operations described in this chapter MUST BE PERFORMED
EXCLUSIVELY BY QUALIFIED PERSONNEL.
Make sure that the unit has been disconnected from the power supply before carrying out any work or accessing internal parts.
The compressor head and discharge pipeline can reach high temperatures.
Always exert caution when working in the vicinity of the compressor.
Adopt the maximum caution when working in the vicinity of the finned coils because of the sharp edges of the aluminium fins.
After performing maintenance work always refit the outer panels and secure them with the screws.
12.2 INTRODUCTION
Carry out the following periodic checks to ensure the unit is operating correctly:
CHECK
Check that safety and control devices work correctly as previously described
Check that all the terminals within the electric panel and compressor are tight The sliding terminals of the contactors should be periodically cleaned: if any damage is found, replace the contactors
Check the sight glass to verify the refrigerant charge.
Check that there is no oil leakage from the compressor
Check that there is no water leakage in the hydraulic system
If the unit is to be stopped for a long period the hydraulic circuit, including all pipes and heat exchangers, should be drained. This is compulsory if the ambient temperature is expected to fall below the freezing point of the liquid employed.
Check process water levels
Check that the flow switch is operating correctly.
Check that the crankcase heater is operating correctly and there is a power supply.
Clean metallic filters on water piping
Clean the finned coil or the filter coils, if present, by means of compressed air, which should be directed in the opposite direction to the normal direction of air flow. If the coil is completely clogged clean with a jet of water.
Execute a defrost test (heat pump units only)
Check the condition, anchorage, and balancing of fans
Check the colour of the sight glass core (green = no moisture, yellow = moisture present): if it is yellow change the refrigerant filter
Check that the noise level has not increased.
PERIOD monthly monthly monthly monthly monthly seasonal operation monthly monthly monthly monthly monthly monthly every 4 months every 4 months every 4 months
Blue Box - 93
12.3 REPAIRING THE REFRIGERANT CIRCUIT
If repairs have been made to the refrigerant circuit, perform the following steps:
- leak test;
- vacuum and dehydration of refrigerant circuit;
- refrigerant charge.
If the circuit is to be emptied, use the appropriate equipment to collect the refrigerant.
12.3.1 Leak test
Charge the refrigerant circuit to a pressure of 15 bar with dry nitrogen gas by means of a cylinder fitted with a pressure reducer. Check the circuit for leaks with a leak detector. The formation of bubbles or foam indicates the presence of leaks.
If leaks are found during the test, empty the refrigerant circuit and then repair the point of leakage by welding with appropriate alloys.
Do not use oxygen instead of nitrogen: explosion hazard.
12.3.2 High vacuum and dehydration of the refrigerant circuit
To generate a high vacuum in the refrigerant circuit use a high vacuum pump able to reach 0.1 mbar of absolute pressure with a flow rate of 10 m3/h. With this type of pump, a single vacuum cycle is normally sufficient to reach an absolute pressure of 0.1 mbar.
If this type of pump is not available, or in the event that the circuit has been left open for a long period of time, you are strongly advised to use the triple evacuation method. This procedure is also prescribed in the event of moisture in the refrigerant circuit.
Connect the vacuum pump to the charge connector.
Proceed as follows:
- Evacuate the circuit to a pressure of at least 35 mbar absolute. Charge the circuit with nitrogen to a relative pressure of approx. 1 bar.
- Repeat the operation described above.
- Repeat the operation described above for the third time in order to reach the highest degree of vacuum possible.
This procedure should guarantee the elimination of up to 99% of contaminants.
Blue Box - 94
12.3.3 Refrigerant charge
- Connect the refrigerant gas cylinder to the male 1/4 SAE charge connector on the liquid line and allow a small amount of gas to escape in order to purge the connection hose of air.
- The circuit must be charged exclusively with liquid; therefore, if the cylinder is not equipped with a dip pipe it must be turned upside-down.
Units operating with R407C must be charged exclusively with liquid refrigerant by way of the charge connection on the liquid line.
A unit that was originally factory charged with R22 cannot be charged with R407C (and vice versa) without major modifications. Consult Bluebox if necessary.
12.4 ENVIRONMENTAL CONSIDERATIONS
Laws governing the use of substances detrimental to the ozone layer prohibit the dispersal of refrigerant gases in the environment, obliging users to recover refrigerants at the end of their useful life and consign them to the dealer or to specific collection centres.
Refrigerants R22 and R407C are mentioned among substances subject to special monitoring regimes established by law, and as such they are subject to the prescriptions indicated above.
Use special care during maintenance work in order to limit the risk of refrigerant leakage as far as possible.
Blue Box - 95
13. DECOMMISSIONING THE UNIT
When the unit has reached the end of its useful life and must therefore be removed and replaced, adhere to the following rules:
- the refrigerant must be recovered by a qualified technician and sent to an authorised collection centre;
- also the compressor lubrication oil must be recovered and sent to a collection centre;
- the structure and components, if unusable, must be stripped down and separated according to the material type; this is particularly important for copper and aluminium, which are fairly abundant on the machine.
This procedure is designed to assist the work of collection, disposal, and recovery specialists and to reduce the associated environmental impact.
Blue Box - 96
REFRIGERANT CIRCUIT
ZETA 2002 - MODELS 3.2 - 13.2
Blue Box - 97
REFRIGERANT CIRCUIT
ZETA 2002 - MODELS 14.4 - 26.4
Blue Box - 98
REFRIGERANT CIRCUIT
ZETA 2002/HP - MODELS 3.2 - 8.2
Blue Box - 99
REFRIGERANT CIRCUIT
ZETA 2002/HP - MODELS 9.2 - 13.2
Blue Box - 100
REFRIGERANT CIRCUIT
ZETA 2002/HP - MODELS 14.4 - 16.4
Blue Box - 101
REFRIGERANT CIRCUIT
ZETA 2002/HP - MODELS 18.4 - 26.4
Blue Box - 102
REFRIGERANT CIRCUIT
ZETA 2002/LE - MODELS 3.2 - 13.2
Blue Box - 103
REFRIGERANT CIRCUIT
ZETA 2002/LE - MODELS 14.4 - 26.4
Blue Box - 104
REFRIGERANT CIRCUIT
ZETA 2002/LE/HP - MODELS 3.2 - 13.2
Blue Box - 105
REFRIGERANT CIRCUIT
ZETA 2002/LE/HP - MODELS 14.4 - 26.4
Blue Box - 106
REFRIGERANT CIRCUIT
ZETA 2002/DC - MODELS 3.2 - 13.2
Blue Box - 107
REFRIGERANT CIRCUIT
ZETA 2002/DC - MODELS 14.4 - 26.4
Blue Box - 108
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002 - ZETA 2002/HP - MODELS 3.2 - 8.2
Blue Box - 109
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002 - ZETA 2002/HP - FOOTPRINT - MODELS 3.2 - 8.2
MODELLO
MODEL
ZETA 2002 3.2
ZETA 2002 4.2
ZETA 2002 5.2
ZETA 2002 6.2
ZETA 2002 7.2
ZETA 2002 8.2
ZETA 2002/ST 1P-2P 3.2
ZETA 2002/ST 1P-2P 4.2
ZETA 2002/ST 1P-2P 5.2
ZETA 2002/ST 1P-2P 6.2
ZETA 2002/ST 1P-2P 7.2
ZETA 2002/ST 1P-2P 8.2
ZETA 2002/DC/DS 3.2
ZETA 2002/DC/DS 4.2
ZETA 2002/DC/DS 5.2
ZETA 2002/DC/DS 6.2
ZETA 2002/DC/DS 7.2
ZETA 2002/DC/DS 8.2
ZETA 2002/DC/DS/ST 1P-2P 3.2
ZETA 2002/DC/DS/ST 1P-2P 4.2
ZETA 2002/DC/DS/ST 1P-2P 5.2
ZETA 2002/DC/DS/ST 1P-2P 6.2
ZETA 2002/DC/DS/ST 1P-2P 7.2
ZETA 2002/DC/DS/ST 1P-2P 8.2
ZETA 2002/HP 3.2
ZETA 2002/HP 4.2
ZETA 2002/HP 5.2
ZETA 2002/HP 6.2
ZETA 2002/HP 7.2
ZETA 2002/HP 8.2
ZETA 2002/HP/ST 1P-2P 3.2
ZETA 2002/HP/ST 1P-2P 4.2
ZETA 2002/HP/ST 1P-2P 5.2
ZETA 2002/HP/ST 1P-2P 6.2
ZETA 2002/HP/ST 1P-2P 7.2
ZETA 2002/HP/ST 1P-2P 8.2
ZETA 2002/HP/DS 3.2
ZETA 2002/HP/DS 4.2
ZETA 2002/HP/DS 5.2
ZETA 2002/HP/DS 6.2
ZETA 2002/HP/DS 7.2
ZETA 2002/HP/DS 8.2
ZETA 2002/HP/DS/ST 1P-2P 3.2
ZETA 2002/HP/DS/ST 1P-2P 4.2
ZETA 2002/HP/DS/ST 1P-2P 5.2
ZETA 2002/HP/DS/ST 1P-2P 6.2
ZETA 2002/HP/DS/ST 1P-2P 7.2
ZETA 2002/HP/DS/ST 1P-2P 8.2
ZETA 2002/ST 1PS-2PS-S 3.2
ZETA 2002/ST 1PS-2PS-S 4.2
ZETA 2002/ST 1PS-2PS-S 5.2
ZETA 2002/ST 1PS-2PS-S 6.2
ZETA 2002/ST 1PS-2PS-S 7.2
ZETA 2002/ST 1PS-2PS-S 8.2
ZETA 2002/HP/ST 1PS-2PS-S 3.2
ZETA 2002/HP/ST 1PS-2PS-S 4.2
ZETA 2002/HP/ST 1PS-2PS-S 5.2
ZETA 2002/HP/ST 1PS-2PS-S 6.2
ZETA 2002/HP/ST 1PS-2PS-S 7.2
ZETA 2002/HP/ST 1PS-2PS-S 8.2
PESO IN FUNZIONE(Kg)
OPERATING WEIGHT(Kg)
601
610
631
679
795
846
650
663
683
731
741
790
696
706
726
776
806
829
830
644
653
677
724
752
802
699
713
733
785
804
854
949
959
981
1031
1051
751
775
830
704
715
749
753
799
655
671
699
699
748
649
660
680
734
1096
979
990
1010
1061
1080
1128
PESO(Kg)
WEIGHT(Kg)
594
604
625
672
788
835
643
654
675
723
734
781
689
699
719
770
789
812
810
638
648
669
716
741
790
693
704
724
776
794
843
724
734
755
807
825
735
758
810
693
703
732
744
791
644
658
683
690
737
644
654
674
726
868
754
764
785
836
854
902
G1(Kg) G2(Kg) G3(Kg) G4(Kg)
270
230
236
247
256
268
283
271
284
232
238
251
258
271
284
233
238
251
258
264
279
295
232
238
251
258
271
284
232
238
250
257
270
283
220
225
236
244
257
265
280
295
225
231
247
251
261
226
234
248
217
222
235
241
255
268
215
219
231
238
175
159
160
164
169
170
174
84
89
58
59
62
67
67
72
73
74
77
83
95
97
86
58
58
62
67
85
89
160
161
68
73
73
74
77
84
165
170
171
78
80
86
84
85
92
86
91
69
71
76
67
72
73
75
78
85
57
58
61
67
134
125
125
124
133
132
137
68
74
50
51
51
58
56
61
61
61
61
69
74
73
67
49
49
50
57
70
76
121
121
58
63
62
63
63
71
121
130
129
61
61
67
67
67
68
67
73
55
56
57
54
59
58
59
59
68
47
47
47
54
208
181
184
187
201
208
223
220
236
202
205
206
223
224
240
195
198
199
214
204
210
229
198
201
202
218
229
246
197
201
203
218
224
241
167
170
173
187
194
208
213
229
177
180
182
196
210
181
183
185
176
178
180
196
202
218
172
173
175
190
Blue Box - 110
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/LE - ZETA 2002 /LE/HP - MODELS 3.2 - 8.2
Blue Box - 111
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/LE - ZETA 2002 /LE/HP - FOOTPRINT - MODELS 3.2 - 8.2
MODELLO
MODEL
ZETA 2002/LE 3.2
ZETA 2002/LE 4.2
ZETA 2002/LE 5.2
ZETA 2002/LE 6.2
ZETA 2002/LE 7.2
ZETA 2002/LE 8.2
ZETA 2002/LE/HP 3.2
ZETA 2002/LE/HP 4.2
ZETA 2002/LE/HP 5.2
ZETA 2002/LE/HP 6.2
ZETA 2002/LE/HP 7.2
ZETA 2002/LE/HP 8.2
PESO IN FUNZIONE(Kg)
OPERATING WEIGHT(Kg)
582
592
601
649
665
705
626
634
646
692
708
750
G1(Kg) G2(Kg) G3(Kg) G4(Kg)
200
206
208
214
223
232
216
221
224
231
240
249
57
58
61
66
67
71
58
58
61
66
67
72
49
49
50
58
58
63
51
51
53
60
60
65
170
172
171
187
192
205
192
195
194
209
214
227
Blue Box - 112
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002 - ZETA 2002/HP - MODELS 9.2 - 13.2
Blue Box - 113
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002 - ZETA 2002/HP - FOOTPRINT - MODELS 9.2 - 13.2
ZETA 2002 9.2
MODELLO
MODEL
ZETA 2002 10.2
ZETA 2002 12.2
ZETA 2002 13.2
ZETA 2002/ST 1P-2P 9.2
ZETA 2002/ST 1P-2P 10.2
ZETA 2002/ST 1P-2P 12.2
ZETA 2002/ST 1P-2P 13.2
ZETA 2002/DC-DS 9.2
ZETA 2002/DC-DS 10.2
ZETA 2002/DC-DS 12.2
ZETA 2002/DC-DS 13.2
ZETA 2002/DC-DS/ST 1P-2P 9.2
ZETA 2002/DC-DS/ST 1P-2P 10.2
ZETA 2002/DC-DS/ST 1P-2P 12.2
ZETA 2002/DC-DS/ST 1P-2P 13.2
ZETA 2002/HP 9.2
ZETA 2002/HP 10.2
ZETA 2002/HP 12.2
ZETA 2002/HP 13.2
ZETA 2002/HP/ST 1P-2P 9.2
ZETA 2002/HP/ST 1P-2P 10.2
ZETA 2002/HP/ST 1P-2P 12.2
ZETA 2002/HP/ST 1P-2P 13.2
ZETA 2002/HP/DS 9.2
ZETA 2002/HP/DS 10.2
ZETA 2002/HP/DS 12.2
ZETA 2002/HP/DS 13.2
ZETA 2002/HP/DS/ST 1P-2P 9.2
ZETA 2002/HP/DS/ST 1P-2P 10.2
ZETA 2002/HP/DS/ST 1P-2P 12.2
ZETA 2002/HP/DS/ST 1P-2P 13.2
PESO(Kg)
WEIGHT(Kg)
981
1058
1124
1158
1035
1112
1233
1305
1346
1027
1104
1170
1204
1081
1177
1212
1072
1159
1232
1272
1146
1158
1223
1258
1052
1160
1195
1234
1106
1183
1248
1288
PESO IN FUNZIONE(Kg)
OPERATING WEIGHT(Kg)
993
1068
1136
1169
1045
1122
1258
1333
1378
1037
1114
1180
1217
1091
1190
1223
1095
1184
1261
1301
1168
1168
1234
1271
1068
1177
1211
1253
1122
1199
1265
1306
G2(Kg)
140
144
148
116
132
132
139
170
178
185
106
118
122
126
127
138
151
155
162
106
118
123
127
128
141
145
149
130
147
154
161
153
G1(Kg)
259
272
284
240
262
275
288
284
300
314
231
253
266
278
237
246
268
281
294
223
245
258
269
228
251
264
275
248
274
290
303
259
G4(Kg)
201
216
220
190
208
213
217
200
214
218
191
199
214
218
193
192
200
215
218
178
185
201
204
180
187
203
206
186
193
208
211
192
G3(Kg)
108
114
115
92
105
103
104
120
127
129
87
92
98
99
104
108
112
118
120
96
101
105
111
112
97
103
111
112
113
85
90
95
MODELLO
MODEL
ZETA 2002/ST 1PS-2PS-S 9.2
ZETA 2002/ST 1PS-2PS-S 10.2
ZETA 2002/ST 1PS-2PS-S 12.2
ZETA 2002/ST 1PS-2PS-S 13.2
ZETA 2002/HP/ST 1PS-2PS-S 9.2
ZETA 2002/HP/ST 1PS-2PS-S 10.2
ZETA 2002/HP/ST 1PS-2PS-S 12.2
ZETA 2002/HP/ST 1PS-2PS-S 13.2
PESO(Kg)
WEIGHT(Kg)
1142
1219
1275
1309
1178
1255
1321
1355
PESO IN FUNZIONE(Kg)
OPERATING WEIGHT(Kg)
1594
1670
1728
1762
1630
1706
1776
1808
Blue Box - 114
G1(Kg)
234
257
271
281
230
249
261
271
G2(Kg)
208
221
223
226
214
223
224
227
G3(Kg)
176
173
178
177
170
171
175
175
G4(Kg)
197
202
216
220
183
192
204
208
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/LE - ZETA 2002/LE/HP - MODELS 9.2 - 13.2
Blue Box - 115
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/LE - ZETA 2002/LE/HP - FOOTPRINT - MODELS 9.2 - 13.2
Blue Box - 116
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002 - ZETA 2002/HP - MODELS 14.4 - 16.4
Blue Box - 117
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002 - ZETA 2002/HP - FOOTPRINT - MODELS 14.4 - 16.4
Blue Box - 118
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/LE - ZETA 2002 /LE/HP - MODELS 14.4 - 16.4
Blue Box - 119
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/LE - ZETA 2002 /LE/HP - FOOTPRINT - MODELS 18.4 - 26.4
Blue Box - 120
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002 - ZETA 2002/HP - MODELS 18.4 - 26.4
Blue Box - 121
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002 - ZETA 2002/HP - FOOTPRINT - MODELS 18.4 - 26.4
Blue Box - 122
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/LE - ZETA 2002/LE/HP - MODELS 18.4 - 26.4
Blue Box - 123
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/LE - ZETA 2002/LE/HP - FOOTPRINT - MODELS 18.4 - 26.4
Blue Box - 124
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/ST - ZETA 2002/HP/ST - MODELS 18.4 - 26.4
Blue Box - 125
OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS
ZETA 2002/ST - ZETA 2002/HP/ST - FOOTPRINT - MODELS 18.4 - 26.4
Blue Box - 126
BLUE BOX srl
is an associate company of
BLUE BOX GROUP
BLUE BOX srl
Via E. Mattei, 20
35028 Piove di Sacco PD Italy
Tel. +39.049.9716300
Fax +39.049.9704105
BLUE BOX GROUP
on the internet www.blueboxgroup.it
Manual 101010A02 - Issued 11.02 - Replaces 04.02
All data in this manual is subject to change without prior notice
advertisement
Related manuals
advertisement
Table of contents
- 7 ZETA 2002 - water chiller
- 7 UNIT FRAME
- 7 COMPRESSORS
- 7 CONDENSER
- 7 CONDENSER FANS
- 7 EVAPORATOR
- 7 REFRIGERANT CIRCUIT
- 7 ELECTRICAL PANEL
- 8 CONTROLS AND SAFETY DEVICES
- 8 TESTING
- 8 ZETA UNIT VERSIONS
- 8 ZETA 2002 /HP: reverse cycle heat pump
- 8 ZETA 2002 LE: condensing unit
- 8 ZETA 2002 LE /HP: heat pump condensing unit
- 9 HYDRAULIC MODULE OPTIONS
- 9 ZETA 2002 /ST 2PS : ZETA 2002 /ST 2PS : unit with storage tank and pumps
- 9 ACCESSORY VERSIONS
- 9 ZETA 2002 /DS: unit with desuperheaters
- 9 ZETA 2002 /LN: low noise unit
- 9 ZETA 2002 /SLN: extra low noise unit
- 10 REFRIGERANT CIRCUIT ACCESSORIES
- 10 - Step type condensing pressure contro
- 10 - Condensing pressure control by means of fan speed regulator
- 10 - Dual set-point
- 10 - Pressure gauges
- 10 - Liquid receivers
- 10 - Compressor suction and discharge valves
- 10 - Liquid line solenoid valve
- 10 HYDRAULIC CIRCUIT ACCESSORIES
- 10 - Leaving water temperature control
- 10 - Anti-freeze heater
- 10 - Water side relief valve (version ST only)
- 10 ELECTRICAL ACCESSORIES
- 10 - Serial interface
- 10 - Single voltage-free contacts for machine status signals
- 10 - Set-point variable
- 10 - Remote user terminal panel
- 11 VARIOUS ACCESSORIES
- 11 - Rubber antivibration mountings
- 11 - Spring-type antivibration mounts
- 11 - Timber packing crate
- 11 - Pallet/skid for shipment in a container
- 11 - Mesh coil guard with metallic filter
- 11 - Anticorrosion treatment of coils for use in aggressive environments
- 11 - Non-standard RAL paint colours