- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Power supply units
- Mircom
- PFC-5008
- Instruction manual
advertisement
PFC-5000 Series
Installation, Operation, and
Instruction Manual
4 or 8 Zone
Fire Alarm
Control Panel
(All specifi cations subject to revision.)
PFC-5004E
POTTER ELECTRIC SIGNAL COMPANY, LLC
St. Louis, MO
(866) 956-1211 • (314) 595-6900 • FAX (314) 595-6999 www.pottersignal.com
Manual #5403546-E
10/09
List of Figures and Tables
Figures
Figure 1: PFC-5002 and PFC-5004 Enclosure Installation and Dimensions ....................................5
Figure 2: PFC-5004E Enclosure Installation and Dimensions ..........................................................6
Figure 3: PFC-5002 and PFC-5004 Module Mounting Locations ....................................................7
Figure 4: PFC-5004E Module Mounting Locations ..........................................................................8
Figure 5: Main Fire Alarm Module ....................................................................................................9
Figure 6: ZA-42 Zone Adder Module ................................................................................................10
Figure 7: ARM-4 or ARM-8 Relay Adder Modle (Zone Operated) ..................................................10
Figure 8: UDACT-9100 Dialer Module .............................................................................................11
Figure 9: PR-5100 Polarity Reversal and City Tie Module ...............................................................11
Figure 10: General Field Wiring Considerations ...............................................................................12
Figure 11-A: Main Fire Alarm Module Terminal Connections .........................................................13
Figure 11-B: Main Fire Alarm Module Terminal Connections (cont’d) ............................................14
Figure 12: ZA-42 Zone Adder Module Terminal Connections ..........................................................15
Figure 13: Relay Module (ARM-4 or ARM-8) Terminal Connections .............................................16
Figure 14: UDACT-9100 Wiring Diagram ........................................................................................17
Figure 15: PR-510 Polarity Reversal and City Tie Module Terminal Connections ...........................18
Figure 16: Power Supply Connections ..............................................................................................19
Figure 17: Indicators and Control Location .......................................................................................22
Figure 18: Evacuation Codes .............................................................................................................27
Tables
Table 1: Wiring Table for Initiating Circuits ......................................................................................20
Table 2: Wiring Table for NAC Circuits ............................................................................................20
Table 3: Confi guration DIP Switch Functions on Main Fire Alarm Board........................................29
Table 4: Confi guration DIP Switch Functions on ZA-42 Module .....................................................31
Table of Contents
Introduction ..................................................................................................................................................1
About this Manual ..............................................................................................................................1
About the PFC-5000 ..........................................................................................................................1
Technical Support ..............................................................................................................................1
Document Conventions ................................................................................................................................2
Circuits and Zones .............................................................................................................................2
Wiring Styles ......................................................................................................................................2
Circuit Adder Modules .......................................................................................................................4
Auxiliary Models ...............................................................................................................................4
PFC-5000 Accessories .......................................................................................................................4
Mechanical Installation and Dimensions ...................................................................................................5
Modules Mounting Locations .....................................................................................................................7
Module Settings ............................................................................................................................................9
Main Fire Alarm Module ...................................................................................................................9
Zone Adder Module (Model ZA-42) .................................................................................................10
Relay Modules (Models ARM-4 or ARM-8) .....................................................................................10
UDACT / DACT (Model UDACT-9100) ..........................................................................................11
Polarity Reversal and City Tie Module (Model: PR-5100) ...............................................................11
Field Wiring ..................................................................................................................................................12
General Field Wiring Considerations .................................................................................................12
Main Fire Alarm Module Terminal Connections ...............................................................................13
Figure 12: Zone Adder Module (ZA-42) Terminal Connections .......................................................15
Figure 13: Relay Module (ARM-4 or ARM-8) Terminal Connections .............................................16
UDACT / DACT (UDACT-9100) Terminal Connections .................................................................17
Polarity Reversal and City Tie Module (Model:PR-5100) Terminal Connections ............................18
Power Supply Connections ................................................................................................................19
Wiring Tables .....................................................................................................................................20
System Checkout ..........................................................................................................................................21
Before Turning The Power On... ........................................................................................................21
Power-up Procedure ..........................................................................................................................21
Troubleshooting .................................................................................................................................21
Indicators, Controls, & Operation .............................................................................................................22
Indicators ............................................................................................................................................22
Controls .............................................................................................................................................24
Operation ............................................................................................................................................25
Circuit Types .....................................................................................................................................25
Initiating (Detection) Circuit Types ...................................................................................................26
NAC (Signal) Circuits Types .............................................................................................................27
System Confi guration ..................................................................................................................................28
Main Fire Alarm Board ......................................................................................................................28
ZA-42 Module ...................................................................................................................................30
Walk Test Operation ....................................................................................................................................32
Appendix A: Compatible Devices ...............................................................................................................33
(ULC) Canadian: Two-wire Smoke Detector Control Panel Compatibility ......................................33
(UL) United States: Two-Wire Smoke Detector Control Panel Compatibility ..................................34
(UL) United States: 4-Wire Smoke Detector Control Panel Compatibility .......................................35
(UL) United States: Signalling Device Control Panel Compatibility ................................................35
Appendix B: Remote Annunciators ............................................................................................................36
Appendix C: Module Specifi cations And Features ...................................................................................37
Appendix D: Power Supply & Battery Calculations ................................................................................39
WARRANTY INFORMATION ..................................................................................................................40
Introduction
About this Manual
This installation and operation manual provides information on installing and operating the PFC-5000 Microprocessor-Based
Fire Alarm Control Panel.
About the PFC-5000
Potter’s PFC-5000 Fire Alarm Control Panels provide 2, 4, or 8 supervised Class B (ULI Style B) Initiating Circuits, or 1,2 or 4 supervised Class A (ULI Style D) Initiating Circuits, and 2 or 4 supervised Class A or B (ULI Style Z or Y) NAC Circuits. All
Circuits are supervised for opens and ground faults, and NAC Circuits for shorts. Optional Modules include a ZA-42 Zone
Adder (required for full capacity in the PFC-5004E only), a UDACT-9100 Digital Alarm Communicator Transmitter (DACT) or a PR-5100 Polarity Reversal & City Tie Module, and ARM-4 or ARM-8 Relay Modules. The two enclosures are fl ush or surface mountable, and can be used for retrofi ts and on new installations.
Overall Features:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
The small enclosure versions, PFC-5002, & PFC-5004, have 2 and 4 Class B (Style B) initiating circuits respectively which may be confi gured as 1 or 2 Class A (Style D) Circuits respectively. These also have 2 Power Limited Class A/B (Style Z/Y)
NAC circuits with individual trouble indicators.
The large enclosure version, PFC-5004E, has 4 Class B (Style B) initiating circuits which may be confi gured as 2 Class A
(Style D) circuits respectively. It also has 2 power limited Class A/B (Style Z/Y) NAC circuits with individual trouble indicators. With a ZA-42 Zone Adder Module, an extra 4 Class B (2 Class A) initiating circuits, and 2 Class A/B NAC circuits are added.
Each initiating circuit is confi gurable as a normal or verifi ed alarm. In addition, on a Class B PFC-5004 or PFC-5004E,
Initiating Circuit 3 may be a Waterfl ow Zone (as may Initiating Circuit 7 if a ZA-42 is installed), and initiating circuit 4 may be a latched or non-latched supervisory zone (as may initiating circuit 8 if a ZA-42 is installed). On a Class A PFC-5004E with a ZA-42, initiating circuit 3 may be a waterfl ow zone and initiating circuit 4 may be a latched or non-latched supervisory zone.
NAC circuits can be confi gured as audible or visual and as silenceable or non-silenceable. Audibles may be Steady,
Temporal Code, California Code, or March Time.
Initiating circuits may be individually disconnected by a slide-switch.
Confi gurable signal silence inhibit (disabled or 1 minute), auto signal silence (disabled or 20 minutes), and one-man walk test.
Subsequent alarm, supervisory, and trouble operation.
Four-wire resettable smoke power supply (100 mA max.).
Auxiliary relay contacts for common alarm and common supervisory (disconnectable), and a common trouble relay. If no
Supervisory zones are confi gured then the common supervisory relay can be used as an extra common alarm relay.
Interface for an RTI Remote Trouble Indicator.
RS-485 Interface for 1 to 3 Remote Multiplex Annunciators (RA8F.)
The PFC-5002, PFC-5004 may use two of optional UDACT-9100 (DACT), PR-5100 (City Tie), ARM-4 or ARM-8 Relay Modules.
The PFC-5004E may use optional UDACT-9100 (DACT), PR-5100 (City Tie), and one of ARM-4 or ARM-8 Relay Modules.
The PFC-5008 is the same as PFC-5004E except the ZA-42 zone adder module is factory installed and may have UDACT-
9100 (DACT) factory installed.
Slide Switch controls and LED Common indicators.
Easy confi guration via DIP switches.
Extensive transient protection.
Technical Support
For all technical support inquiries, please contact Potter ’s Technical Support Department between 8 A.M. and 5 P.M. (CDT) Monday through
Friday, excluding holidays.
1
Document Conventions
Circuits and Zones
The term circuits refers to an actual electrical interface, initiating (detection), NAC (signal), or relay.
The term zone is a logical concept for a fi re alarm protected area, and will consist of at least one circuit.
Often the terms zone and circuit are used interchangeably, but in this manual the term circuit is used.
Wiring Styles
Initiating circuits are confi gured by default as Class B (Style B). They may be globally (all or none) confi gured as Class A
(Style D) as described in System Confi guration on page 28. This operation uses odd and even pairs of two-wire Class B (Style B) circuits to make one four-wire Class A (Style D) circuit, thus cutting in half the number of available initiating circuits.
Indicating circuits may be individually wired as Class A (Style Z) or Class B (Style Y) without affecting the number of circuits available (see Field Wiring on page 12). Indicating Circuits may also be referred to as Notifi cation Appliance Circuits (NAC).
2
Model
PFC-5002
PFC-5004
PFC-5004E
PFC-5008
Description
Small enclosure fi re alarm control panel with 2 Class B
(Style B) or 1 Class A (Style D) Initiating Circuits, and 2
Power Limited Class A/B (Style Z/Y) NAC Circuits
(1.70 amperes each, 2.0 amperes total) with individual trouble indicators. Common Alarm & Trouble Relays.
Interface for Remote Trouble Indicator. Resettable Four
Wire Smoke Detector Power Supply. May have two of
UDACT-9100 or PR-5100, ARM-4, or ARM-8 installed. Can be used with BT-40 (4 AHr), BT-80 (8
AHr), BT-120 (12 AHr), BT-180 (18 AHr) or BA-240
(24 AHr)batteries (2 required). Note that the BT-180 and the BA-240 Batteries require a Listed Battery Cabinet.
Small enclosure fi re alarm control panel with 2 Class B
(Style B) or 1 Class A (Style D) Initiating Circuits, and 2
Power Limited Class A/B (Style Z/Y) NAC Circuits
(1.70 amperes each, 2.0 amperes total) with individual trouble indicators. Common Alarm & Trouble Relays.
Interface for Remote Trouble Indicator. Resettable Four
Wire Smoke Detector Power Supply. May have two of
UDACT-9100 or PR-5100, ARM-4, or ARM-8 installed.Can be used with BT-40 (4 AHr), BT-80 (8
AHr), BT-120 (120 AHr), BT-180 (18 AHr) or BA-240
(24 AHr)batteries (2 required). Note that the BT-180 and the BA-240 Batteries require a Listed Battery Cabinet.
Large enclosure Fire Alarm Control Panel with 4 Class
B (Style B) or 2 Class A (Style D) Initiating Circuits, and 2 Power Limited Class A/B (Style Z/Y) NAC
Circuits (1.70 amperes each, 5 amperes total) with individual trouble indicators. Common Alarm &
Trouble Relays. Interface for Remote Trouble Indicator and/or 1 to 3 of RA8F Remote Multiplex Annunciators.
Resettable Four Wire Smoke Detector Power Supply.
May have ZA-42 installed. May have UDACT-9100 or
PR-5100, and one of ARM-4 or ARM-8 installed.Can be used with BT-40 (4 AHr), BT-80 (8 AHr), BT-120
(12 AHr), BT-180 (18 AHr) or BA-240 (24 AHr) batteries (2 required). Note that the BT-180 and the
BA-240 Batteries require a Listed Battery Cabinet.
Same as PFC-5004e except ZA-42 zone adder module is factory installed and may have UDACT-9100 factory installed.
3
Circuit Adder Modules
Auxiliary Models
Model Description
ZA-42 Zone Adder Module for the PFC-5004E. Brings the total capacity to 8 Class B (Style B) or four Class A (Style D) Initiating Circuits, and 4 Power Limited Class A/B (Style Z/Y) NAC Circuits (up to
1.7 amperes each, 5 amperes total).
ARM-8 Relay Adder Module for the PFC-5002, PFC-5004, PFC-5008 or
PFC-5004E. Adds eight confi gurable Form-C Relays rated 1A, 28
VDC.
ARM-4 Relay Adder Module for the PFC-5002, PFC-5004, PFC-5008 or
PFC-5004E. Adds four confi gurable Form-C Relays rated 1A, 28
VDC.
Model Description
PR-5100 Polarity Reversal and City Tie Module
UDACT-9100 Digital Communicator
PFC-5000 Accessories
Model
RA8F
BC-2
MP-300R
MP-300
BC-160
Description
Eight-Zone Remote Annunciator (ULC and ULI approved)
External Battery Cabinet (ULC and ULI approved)
EOL Resistor Plate, red (ULC approved)
EOL Resistor Plate, stainless steel fi nish
External Battery Cabinet (ULC and ULI approved)
4
Mechanical Installation and Dimensions
Figure 1: PFC-5002 and PFC-5004 Enclosure Installation and Dimensions
-
8
-
5 "
16
DOOR DOOR
MATERIAL: 18GA (0.048") THICK
COLD ROLLED STEEL
FINISH: PAINTED
BACKBOX
SURFACE
(SIDE VIEW)
WALL WALL
FLUSH
(SIDE VIEW)
BACKBOX
#6 x 5/16" SCREW
DOOR
14 -
1"
8
1 -
5
8
"
15 -
1"
8
BACKBOX
13
3
10 - "
2
1" 1
5
-
3
DIA.
HOLE
8 "
12
3
3
7
-
1
1 -
1
8
"
& -
7"
8
KNOCKOUT
Note: Use Security Screw provided to meet UL 864
Rev 9 requirement.
5
Figure 2: PFC-5004E/PFC-5008 Enclosure Installation and Dimensions
-
4
DOOR DOOR
-
5 "
16
MATERIAL: BACKBOX 18GA (0.048") THICK
DOOR 16GA (0.059") THICK
COLD ROLLED STEEL
FINISH: PAINTED
#6 x 5/16" SCREW
DOOR
BACKBOX
BACKBOX
SURFACE
(SIDE VIEW)
WALL WALL
FLUSH
(SIDE VIEW)
16
5 "
1 -
3 "
4
2 "
14 -
1
2
"
11 "
1"
BACKBOX
1 -
3
4
"
1 -
1
2
"
Four Mounting
Holes
2 "
12 -
1"
2
14 -
7
8
"
-
1
-
7
8
KNOCKOUT
4 -
3 "
8
15 -
7
8
"
5
"
Note: Use the Security
Screw provided to meet
UL/ULC Rev 9 requirement.
6
Modules Mounting Locations
The PFC-5000 Series come pre-assembled with all components and boards, except for adder modules. Module installation locations are shown below.
Be sure to connect a solid Earth Ground (from building system ground or cold water pipe) to the Chassis Earth Ground Mounting
Lug, and to connect the Earth Ground Wire Lugs from the Main Chassis to the ground screw on the backbox.
Figure 3: PFC-5002 and PFC-5004 Module Mounting Locations
UDACT-9100)
PR-5100)
Note:
1. Relay module may be Model ARM-4 or ARM-8.
2. Only two of PR-5100, UDACT-9100 or ARM-4/ARM-8 may be installed.
7
Fig. 4: PFC-5004E/PFC-5008 Module Mounting Locations
ZONE ADDER
MODULE
(ZA-42)
P8
P7
P6
P1
MAIN FIRE
ALARM
MODULE
DISPLAY
PLATE
(MODEL UDACT-9100)
POLARITY REVERSAL AND
CITY TIE MODULE
(MODEL PR-5100)
Note
1. Relay module may be Model ARM-4 or ARM-8.
8
Module Settings
Main Fire Alarm Module
Class A / B Selection
On the PFC-5002, PFC-5004, PFC-5008 and PFC-5004E, to select Class B (Style B) move JW1 & JW2 to position “B.” To select Class A (Style D) move JW1 & JW2 to position “A”.
Note: The Class A/B selection affects all initiating circuits, and must be used with the correct Confi guration DIP switch 9 #6. See
Table 3 on page 29.
Zone Adder Module: On an PFC-5004E only, remove the jumper on JW4 if a ZA-42 Zone Adder Module is installed. The zone adder module is plugged into P6 & P7.
Relay Module: Remove the jumper on JW3 if an ARM-4 or ARM-8 Relay Module is installed. The relay module is plugged into
P1.
Digital Communicator: Remove the jumper on JW6 if a UDACT-9100 Digital Communicator is installed. The digital communicator is plugged into P8.
City Tie: Remove the jumper on JW6 if a PR-5100 City Tie is installed. The City Tie is plugged into P8.
Battery: Connected to P2(+) & P3(-) via the factory installed cables.
Transformer: Factory wired to P4 & P5, do not disconnect.
SW9,11,13: Confi guration DIP switches.
Figure 5: Main Fire Alarm Module
C
O
M
-
N
O
N
C
C
O
M
N
O
N
C
C
O
M
TBL RLY
C
N
O
N
C
O
M
NA C2 (IND2) N 1 (IND1) INI4 INI3 INI2 INI1
- + - + - + - + T
R
B
T
R
L
C
O
M
+
RS-485
S - +
4 WIRE
- +
A B A B
MANU CTURER USE
9
Zone Adder Module (Model ZA-42)
Figure 6: ZA-42 Zone Adder Module
Class A / B Selection: JW2 & JW3 are connected from 1 to 2 for initiating circuit Class B (Style B) operation, and from 2 to 3 for Class A (Style D) operation.
Note:
The Class A/B selection affects all initiating circuits, and must be used with the correct Confi guration DIP switch 9 #6.
P1 & P2: Connections to P7 & P6 respectively on the main fi re alarm board.
SW5,6: Confi g DIP switches.
P2 P1
1 2 3
JW2
1 2 3
JW3
SW5
SW6
Relay Modules (Models ARM-4 or ARM-8)
Figure 7: ARM-4 or ARM-8 Relay Adder Module (Zone Operated)
P1: Connect to P1 on the main fi re alarm board.
By the factory setting, the four or eight relays are controlled by initiating circuits 1 to 8 respectively. This is confi gured by selecting:
•
•
•
JW1: Initiating Circuit #1 controls Relay #1.
JW2 : Initiating Circuit #2 controls Relay #2.
JW8: Initiating Circuit #8 controls Relay #8.
Alternately, each relay may be set as a Common Alarm or Common Supervisory Relay by removing the jumper from JW1 to
JW1A, etc. These jumpers have two positions to select Alarm or
Supervisory each.
•
•
•
JW1A: Alarm or supervisory control for Relay #1.
JW2A: Alarm or supervisory control for Relay #2.
JW8A: Alarm or supervisory control for Relay #8.
K1
RLY1
A LM
K2
RLY2
JW1.2
A LM
K3
RLY3
JW2.3
A LM
K4
RLY4
JW 3.4
A LM
K5
RLY5
JW4.5
A LM
K6
RLY6
JW5.6
A LM
K7
RLY7
JW6.7
A LM
K8
RLY8
JW7.8
A LM
Finally, there are jumpers JW1.2,
JW2.3, up to JW7.8 that allow a relay to have the same control as an adjacent relay. For example, starting with the factory default setting, moving the jumper from JW2 to JW1.2 will make both relays 1 & 2 operate with Initiating
Circuit #1.Contact Potter Technical
Support for assistance if required.
SUPV SUPV
JW 1
SUPV
JW 2
SUPV
JW 3
P1
SUPV
JW 4
SUPV
JW 5
SUPV
JW 6
SUPV
JW 7 JW 8
10
UDACT / DACT (Model UDACT-9100)
P1: Cable to P8 on the main fi re alarm board.
Jumper JW6 on the main fi re alarm module must be removed if a UDACT-9100 is installed. Note that this module cannot be installed if a polarity reversal and city tie module is used.
Figure 8: UDACT-9100 DACT Module
Note: The UDACT is Tip & Ring sensitive. If any of the two LEDs are illuminated amber, reverse the wiring, then wait 30
seconds for the LED to clear.
Please see the UDACT-9100 Manual (LT-888POT) for more information.
Polarity Reversal and City Tie Module (Model: PR-5100)
P1: Cable to P8 on the main fi re alarm module.
Jumper JW6 on the main fi re alarm panel must be removed if a polarity reversal and city tie module is installed.
Figure 9: PR-5100 Polarity Reversal and City Tie Module
Mounting hole for
#6-32 screws
P1 P2
Mounting hole for
#6-32 screws
11
Field Wiring
General Field Wiring Considerations
Because most of the Field Wiring on the PFC-5000’s is to the Main Boards on the swinging dead front, it is very important to properly dress the wires so as not to place stress on either their connection to the boards, or runs to conduit. The Figure below shows the required wiring techniques.
Figure 10: General Field Wiring Considerations
USE AT LEAST 3 WIRE TIES
AS SUPPLIED THROUGH
HOLES ON DEADFRONT
WIRE TIE IN 2 PLACES TO
BACK OF ENCLOSURE
DRESS WIRES NEAR TOP
OF ENCLOSURE CLEAR OF
ADDER MODULES
12
Do not run panel line voltage in the same conduit as initiating circuits. Undesired transient voltage could cause faults on initiating circuits.
Main Fire Alarm Module Terminal Connections
Wire devices to terminals as shown in Figure 11 below. See Wiring Tables on page 20 for wiring instructions, Appendix A on page 33 for compatible devices, and Appendix C on page 37 for specifi cations.
Do not exceed power supply ratings:
PFC-5002, PFC-5004, total current for NAC circuits is
2A max.
PFC-5004E/PFC-5008, total current for NAC circuits is 5A max.
Figure 11A: Main Fire Alarm Module Terminal Connections
SUPV.
REL AY
ALARM
REL AY
TROUBLE
REL AY
COM-
NO
NC
COM
NO
NC
COM
NC
NO
COM
REMOTE ANNUNCIATORS
AUXILIARY COMMON
SUPERVISORY
CON TACTS
RESISTIVE LOAD
AUXILIARY COMMON
ALARM CON TACTS
RESISTIVE LOAD
COMMON TROUBLE
CON TACTS
RESISTIVE LOAD
MUST BE
CONNECTED
A
LISTED POWER
LIMITED SOURCE
OF SUPPLY
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
NAC2- (Z)
NAC2+ (Z)
SUPERVISED NAC #2
ONLY ONE CLASS OF WIRING M AY BE USED IN ANY INSTALLATION.
CLASS B /
STYLE Y
WIRING
NAC1- (Z)
NAC1+ (Z)
SUPERVISED NAC #1
(POWER LIMITED), REGUL ATED 24FWR
STYLE Z
WIRING
When wiring devices, please keep in mind the following:
• All terminals are shown from the back of the main fi re alarm board assembly (pointing towards the rear of the enclosure).
•
•
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Initiating circuits are fully supervised and rated for 26 VDC, 3 ma standby, 2.2 Vp-p ripple, 50 mA max. alarm. They may be confi gured as required. Maximum loop resistance is 100 ohms, 50 ohms per side.
•
•
•
NAC circuits are fully supervised and rated for 24 FWR 1.7 amp max. each. They must be wired as shown in the wiring tables on page 20.
On the PFC-5004 & PFC-5004E/PFC-5008, the auxiliary common supervisory relay contacts will act as a second set of common alarm contacts if there are no initiating circuits set as supervisory.
Initiating circuits must be all either Style B or D. If Style D is selected, cut the number of circuits in half.
13
Figure 11B: Main Fire Alarm Module Terminal Connections (cont’d)
STYLE D
INI2
STYLE D
INI1
RTI
RS-485
4-WIRE
SUPPLY
TRB
TRL
COM+
S
-
+
+
-
INI4-
INI4+
INI3-
INI3+
INI2-
INI2+
INI1-
INI1+
SUPERVISED INITIATING CIRCUIT #4
SUPERVISED INITIATING CIRCUIT #3
ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION.
SUPERVISED INITIATING CIRCUIT #1
(POWER LIMITED)
CLASS B /
STYLE B
WIRING
CLASS B /
STYLE B
WIRING
CLASS A /
STYLE D
WIRING
UNFILTERED SPECIAL APPLIC ATION
COM-
(SEE FIG.11)
24VDC POWER +
(POWER LIMITED) -
BLK
BLU
RED & WHT
RT I
RTI REMOTE TROUBLE INDIC AT OR (NOT SUPERVISED)
(N OT USED WITH RAM-208'S)
SEE APPLICABLE OPERATION & INS ALL ATION
RS-485 INTERFACE
(POWER LIMITED)
RESETTABLE 4-WIRE
SMOKE DETEC TOR POWER
1.5VP-P RIPPLE.
LEGEND: for compatible devices.
SMOKE DETEC TOR
SUPERVISORY OR
W ATERFLOW
SWITCH (NO)
HEAT DETEC TOR
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
PULL STATION
When wiring devices, please keep in mind the following:
• All terminals are shown from the back of the main fi re alarm board assembly (pointing towards the rear of the enclosure).
•
•
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Initiating circuits are fully supervised and rated for 26 VDC, 3 ma standby, 1.5 Vp-p ripple, 50 mA max. alarm. They may be confi gured as required. Maximum loop resistance is 100 ohms, 50 ohms per side.
• Initiating circuits are compatibility ID “A”.
14
Figure 12: Zone Adder Module (ZA-42) Terminal Connections
Wire devices to terminals as shown below in Figure 12. See Wiring Tables on page 20 for wiring instructions, Appendix A on page 33 for compatible devices, and Appendix C on page 37 for Module specifi cations.
STYLE D
INI4
STYLE D
INI3
NAC 4-(Y/Z)
NAC 4- (Z)
NAC 4+ (Z)
NAC 4+ (Y/Z)
NAC 3- (Y/Z)
NAC 3- (Z)
NAC 3+ (Z)
NAC 3+ (Y/Z)
INI8-
INI8+
INI7-
INI7+
INI6-
INI6+
INI5-
INI5+
CLASS A / STYLE D NOTE:
INITIATING CIRCUITS MUST BE ALL EITHER STYLE B OR
D. IF STYLE D IS SELECTED, THE NUMBER OF CIRCUITS
IS CUT IN HALF.
SUPERVISED NAC #4
(POWER LIMITED) REGULATED 24 FWR
EXAMPLES OF BOTH CLASS A AND B WIRING ARE SHOWN, BUT
ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION.
SUPERVISED NAC #3
(POWER LIMITED) REGULATED 24 FWR
SUPERVISED INITIATING CIRCUIT #8
(SHOWN AS SUPV ZONE, POWER LIMITED)
SUPERVISED INITIATING CIRCUIT #7
(SHOWN AS ALARM ZONE, POWER LIMITED)
EXAMPLES OF BOTH CLASS A AND B WIRING ARE SHOWN, BUT
ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION.
SUPERVISED INITIATING CIRCUIT #3
(POWER LIMITED)
CLASS B /
STYLE Y
WIRING
CLASS A /
STYLE Z
WIRING
CLASS B /
STYLE B
WIRING
CLASS B /
STYLE B
WIRING
CLASS A /
STYLE D
WIRING
LEGEND: See Appendix A for compatible devices.
SMOKE DETECTOR
SUPERVISORY OR
WATERFLOW
SWITCH (NO)
BELL, HORN, OR STROBE
HEAT DETECTOR
PULL STATION
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
Note:
• All terminals are shown from the back of the main fi re alarm board assembly.
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
•
•
Initiating circuits are fully supervised and rated for 26 VDC, 3 ma standby, 2.2 Vp-p ripple, 50 mA max. alarm. They may be confi gured as required. Maximum loop resistance is 100 ohms, 50 ohms per side.
Initiating circuits are compatibility ID “A”.
15
Figure 13: Relay Module (ARM-4 or ARM-8) Terminal Connections
Note that only relays #1 to #4 are present on the ARM-4.
RELAY #1
NO
NC
COM
RELAY #2
NO
NC
COM
RELAY #3
NO
NC
COM
RELAY #4
NO
NC
COM
RELAY #5
NO
NC
COM
RELAY #6
NO
NC
COM
RELAY #7
NO
NC
COM
RELAY #8
NO
NC
COM
Note:
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable. Must be connected to a listed power limited source of supply.
16
UDACT / DACT (UDACT-9100) Terminal Connections
The following diagram shows the wiring connection for the UDACT-9100, refer to LT-888POT for more details.
Wire the two telephone lines to RJ31X Connector terminals as shown in Figure 14 below. The UDACT-9100 terminals are located on the top left hand corner of the board. If using a cellular or wireless service, use the Line interface connection only.
Note:
Most AHJs do not allow the connection of premise telephones. See Wiring Tables on page 20 and Appendix C page 37 for more information.
Figure 14: UDACT-9100 Wiring Diagram
UDACT-9100
17
Polarity Reversal and City Tie Module (Model:PR-5100) Terminal Connections
See Appendix C on page 37 for module specifi cations. Wire as shown in Figure 15 below using proper wire gauges. Refer to
LT-877POT for more details.
Note that for use in the USA, the installer must add an Atlantic Scientifi c (Tel. 407-725-8000) Model #24544 Protective Device, or similar ULI-Listed QVRG Secondary Protector, as shown. For use in Canada, the protective device is still recommended, but the PR-5100 may be connected directly to polarity reversal and city tie wiring.
If UDACT-9100 and PR-5100 are used then
Protector not needed. UDACT-9100 has integral protector and PR-5100 is plugged into it.
Notes:
• The terminal blocks are “depluggable” for ease of wiring.
• The city tie interface is not power limited.
• Use either the PR-5100’s City Tie or Reverse Polarity Interface Module - not both.
Figure 15: PR-5100 Polarity Reversal and City Tie Module Terminal Connections
PR-5100
PROTECTOR
1
1
+
+
CITY TIE LOCAL ENERGY
RATED 24 VDC FILTERED
TRIP COIL 14 OHMS,
250mA, 5mV RIPPLE
-
POWER LIMITED
S
2
2
S
-
USE A SHORTING WIRE WHEN
THE CITY TIE IS NOT IN USE.
+
POLARITY REVERSAL ALARM
24VDC OPEN
12VDC AT 3.5 mA
8 mA MAX SHORT
POWER LIMITED
1
2
S
+
-
POLARITY REVERSAL SUPV
24VDC OPEN
12VDC AT 3.5 mA
8 mA MAX SHORT
2
S
1
1
+
2
S
DIN RAIL CONNECTION
TO EARTH GROUND
PROTECTOR
1
-
CONFORMS TO NEMA STANDARD
SB3-1969 INTENDED FOR
CONNECTION TO POLARITY
REVERSAL CIRCUIT OF A REMOTE
STATION RECEIVING UNIT HAVING
COMPATIBLE RATINGS.
+
2
-
S
1
1
2
S
2
S
POWER LIMITED CABLE TYPE FPL,
FPLR OR FPLP MUST BE USED FROM
PR-5100 TO PROTECTORS
DIN RAIL CONNECTION
TO EARTH GROUND
When wiring devices, please keep in mind the following:
•
•
•
Plug PR-5100 ribbon cable (P1) into the main fi re alarm module.
All circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.
For polarity reversal operation, short the city tie connection.
18
Power Supply Connections
The power supply is part of the main fi re alarm module and the chassis. The ratings are:
Model Branch Circuit Ratings
PFC-5002, PFC-5004 120 V 60Hz 1A / 240V 50 Hz 0.5A
PFC-5004E, PFC-5008 120 V 60Hz 2.0A / 240V 50 Hz 1.0A
•
•
Do not exceed power supply ratings:
To prevent sparking, connect batteries after the systems main A.C. power is turned on.
Figure 16: Power Supply Connections
TO 24 VDC
BATTERY
MAIN FIRE ALARM MODULE
P5 P4 P3 P2
-
BAT
+
GREEN EARTH GROUND
WIRE SOLDERED ONTO MAIN
FIRE ALARM MODULE PCB.
BLACK
RED
TO DEDICATED
BRANCH CIRCUIT
L L N G
EARTH GROUND
DIMPLE ON
ENCLOSURE,
FOR
GROUNDING
WIRES AND
SCREW.
GREEN
19
Wiring Tables
Table 1: Wiring Table for Initiating Circuits
Wire Gauge Maximum Wiring Run to Last Device (ELR)
(AWG) ft.
m
22
20
18
2990
4760
7560
910
1450
2300
16
14
12
12000
19000
30400
3600
5800
9200
Note:
Maximum loop resistance should not exceed 100 Ohms. Wire size less than 18AWG is not recommended for initiating or notifi cation circuits.
Table 2: Wiring Table for NAC Circuits
Main board and ZA-42 NAC circuits are rated for 1.7 amps each.
Total
Signal
Load
Amperes
0.06
0.12
0.30
0.60
0.90
1.20
1.50
1.7
ft.
2350
1180
470
235
156
118
94
78 m
716
360
143
71
47
36
29
24
Maximum Wiring Run to Last Device (ELR) ft.
3750
1850
150
375
250
185
150
125
Note:
Maximum voltage drop should not exceed 1.8 volts.
m
1143
567
229
114
76
56
46
38 ft.
6000
3000
1200
600
400
300
240
200 m
1829
915
366
183
122
91
73
61 ft.
8500
4250
1900
850
570
425
343
285 m
2591
1296
579
259
174
129
105
87
RS-485 Wiring: See the wiring information for the remote annunciator being used.
4-Wire Smoke Wiring: The maximum allowable current is 0.1 amperes. The maximum allowed voltage drop is 1 volt. Refer to
Table 2: Wiring for NAC Circuits above.
Max Loop
Resistance
Ohms
30
15
6
3
2
1.5
1.2
1.0
20
System Checkout
Before Turning The Power On...
1. To prevent sparking, do not connect the batteries. Connect the batteries after powering the system from the main AC supply.
2. Check that all modules are installed in the proper location with the proper connections.
3. Check all fi eld (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged-in properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to Earth Ground (cold water pipe).
8. Make sure to close the front cover plate before powering the system from main AC supply.
Power-up Procedure
1. After completing the System Checkout procedures, power-up the panel. The “AC-ON” green LED should illuminate, the
“Common Trouble” LED should illuminate, and the buzzer should sound.
2. Press the System Reset button. Since the batteries are not connected, the “Battery Trouble” LED should illuminate, and the buzzer should sound intermittently, and the Common Trouble LED should fl ash.
3. Connect the batteries while observing correct polarity; the red wire is positive (+) and black wire is negative (-). All indicators should extinguish except for normal power “AC-ON” green LED.
4. Confi gure the fi re alarm control panel as described in the System Confi guration section on page 28.
Troubleshooting
Message Description
Circuit Trouble Normally when a circuit trouble occurs, its designated trouble indicator will be illuminated, as well as the
Common Trouble indicator and Trouble buzzer. To correct the fault, check for open wiring on that particular circuit loop or see if the circuit disconnect switch is in the ON or CLOSED position. Note: disconnecting a circuit will cause a system trouble (off-normal position).
Remote Fail
Ground Fault
The panel will display a Remote Fail for any failure reported by, or failure to communicate with a remote annunciator, UDACT-9100, or PR-5100.
The PFC-5000 panel has a Common Ground Fault Detector. To correct the fault, check for any external wiring touching the chassis or other earth ground connection.
Battery Trouble Check for the presence of batteries and their conditions. Low voltage (below 20.4V) will cause a battery trouble with steady yellow illumination of “Battery Trouble” indicator. If battery trouble condition persists, replace the batteries as soon as possible.
Charger Trouble Internal Battery Charger fault is indicated with a slow fl ash of “Battery Trouble” indicator. This fault will require factory repair.
Common Trouble Initiating Circuit, Auxiliary power, or 4-wire positive terminal shorts to negative power supply will result in a common trouble only. There are no individual indicators for these trouble types. If UDACT is used only common trouble is reported, there are no unique UDACT reporting codes.
21
Indicators, Controls, & Operation
Refer to Figure 17 below for LED Indicators and control switch locations.
Figure 17: Indicators and Control Location
SIGNAL
SILENCE
FIRE
DRILL
AUXILIARY
DISC.
A.C
ON
COMMON
ALARM
COMMON
SUPERVISORY
COMMON
TROUBLE
BATTERY
TROUBLE
GROUND
FAULT
REMOTE
TROUBLE
TEST
ZONE 1
ZONE 2
ZONE 3
ZONE 4
DISC 1
DISC 2
DISC 3
DISC 4
SYSTEM
RESET
BUZZER
SILENCE
LAMP
TEST
TROUBLE
TROUBLE
ZONE 5
ZONE 6
DISC 1
DISC 2
ZONE 7
DISC 3
ZONE 8
DISC 4
TROUBLE
TROUBLE
Indicators
Buzzer
The buzzer is activated by any of the following:
• Fire alarm: steady
• Supervisory alarm: fast fl ash rate of 120 beeps per minute
• Trouble: slow fl ash rate of 20 beeps per minute
If the buzzer turns on in response to a non-latching trouble or supervisory, it will be turned off if the condition causing it goes away and there is no other reason for it to be on.
AC On LED
The green AC On LED illuminates steadily while the main AC power is within acceptable levels. It turns off when the level falls below the power-fail threshold and the panel switches to standby (battery) power.
Common Alarm LED
The Common Alarm indicator turns on steady red whenever the panel is in alarm as a result of an alarm on any initiating circuit.
Since all alarms are latched until the panel is reset, the indicator will remain on until reset.
22
Common Supervisory LED (PFC-5004 or PFC-5004E/PFC-5008 only)
The amber Common Supervisory LED illuminates steadily when there is a supervisory alarm in the panel resulting from any latching or non-latching supervisory circuit. The LED turns off if all non-latching supervisory circuits are restored and there are no active latching supervisory circuits. Latching supervisory alarms remain active until the panel is reset.
Common Trouble LED
The Common Trouble indicator fl ashes amber (at 20 fl ashes per minute) when the panel detects any trouble condition. It turns off when all non-latching troubles are cleared.
Remote Trouble LED (PFC-5004 or PFC-5004E/PFC-5008 only)
The Remote Failure indicator illuminates amber if the panel detects trouble at a city tie or DACT module, or communication or local trouble with a remote annunciator. It turns off once these conditions return to normal.
Fire Drill LED
The amber Fire Drill LED illuminates steadily while fi re drill is active.
Auxiliary Disconnect LED
The Auxiliary Disconnect Indicator fl ashes amber (20 fl ashes per minute) when the Auxiliary Disconnect switch is activated. It turns off when the switch is activated a second time. When on, the Auxiliary Disconnect LED indicates that common alarm and common supervisory relays, and any ARM-4 / ARM-8 relays are not activated. The trouble relay is activated. If installed, DACT or polarity reversal and city tie modules are also inactive, causing a trouble condition.
Signal Silence LED
The amber Signal Silence LED fl ashes at the trouble fl ash rate when indication circuits are silenced either by the Signal Silence button or by the Auto Signal Silence timer. It turns off when the signals are re-sounded by a subsequent alarm.
Battery Trouble LED
The Battery Trouble LED turns on steady when the battery is either low (below 20.4 VDC) or disconnected. It fl ashes amber at the trouble fl ash rate if there is a Battery Charge trouble.
Ground Fault LED
The Ground Fault LED fl ashes amber at the trouble fl ash rate when the Ground Fault Detector detects a ground fault on any fi eld wiring. It turns off when the ground fault is cleared.
Test LED
The Test LED illuminates amber when the fi re alarm panel is in walk test mode.
Circuit Status LEDs
These LEDs indicate the status of initiating circuits. They illuminate
•
•
•
•
Alarm: Steady red
Alarm Verifi cation or waterfl ow retard in progress: fast fl ashing red (120 fl ashes per minute)
Pending Alarm: (see Circuit Disconnect Switches on the following page) fast fl ashing red (120 fl ashes per minute)
Supervisory: Steady amber
Circuit Trouble LEDs
These LEDs indicate trouble for initiating and NAC circuits. They fl ash (20 fl ashes per minute) for any fi eld wiring fault, or if the circuit has been disconnected.
23
Controls
System Reset Switch
The System Reset momentary switch resets the fi re alarm control panel and all circuits:
• Resets all latching trouble conditions
• Resets four-wire smoke supply
• Turns off Signal Silence
• Stops and resets all timers
• Aux Disconnect is not affected
• Resets all initiating circuits
• Turns off all NAC circuits
• Turns off Fire Drill
• Processes inputs as new events
Signal Silence Switch
Activating the Signal Silence momentary switch when the panel is in alarm turns on the signal silence indicator and deactivates any silenceable NAC circuits. Non-silenceable circuits are unaffected. Signals will re-sound upon any subsequent alarm. This switch does not function during any confi gured Signal Silence Inhibit timer period. It also does not function if the NAC circuits are active as the result of a fi re drill.
Fire Drill Switch
The Fire Drill momentary switch activates all non-disconnected NAC circuits, but does not transmit any alarms via the DACT, city tie, or common alarm relay, nor are any ARM-4 or ARM-8 relays activated. The fi re drill is cancelled by activating the switch again, or if the panel goes into a real alarm.
Auxiliary Disconnect Switch
Activating the Auxiliary Disconnect momentary switch activates the auxiliary disconnect function. Activating the switch again de-activates the function. When auxiliary disconnect is active, common alarm and common supervisory relays, and any ARM-4 /
ARM-8 relays are not activated. The trouble relay is activated. If installed, DACT or polarity reversal and city tie modules are also inactive, causing a trouble condition.
Lamp Test Switch
Activation of the Lamp Test momentary switch turns all front panel Indicators and the buzzer on.
Buzzer Silence Switch
Activation of the Buzzer Silence momentary switch while the Buzzer is sounding silences the Buzzer. The Buzzer will resound if there is a subsequent event. Switch activation will also silence the buzzer on all attached annunciators.
Circuit Disconnect Switches
Activation of these non-momentary switches disconnects the respective Initiating Circuit, and causes a Circuit Trouble for that
Initiating Circuit while active. If the disconnect switch is turned off (to its normal position) while there is an Alarm condition in that circuit, the respective circuit Status LED will fl ash at a rate of 120 fl ashes per minute to indicate a Pending Alarm, for 5 seconds. If the disconnect switch is not turned back on, an Alarm will be processed normally. To enable Circuit Disconnect feature, confi guration DIP switch 9 #3 must be set to “ON”.
24
Operation
All alarm inputs are treated in a similar manner. Alarm inputs include non-verifi ed or verifi ed alarms, and water-fl ow alarms.
Activation of any alarm input when the panel is not already in alarm cause the following:
•
•
•
•
•
•
•
•
The buzzer sounds steadily
If fi re drill is active, it is cancelled
The Common Alarm indicator turns on
The common alarm relay activates if aux disconnect is not active
The Auto Signal Silence timer, if confi gured, starts
The Signal Silence Inhibit timer, if confi gured, starts
ARM-4 / ARM-8 relays are activated as confi gured, provided that aux disconnect is not active
Signals and strobes are activated
Subsequent Alarms when the panel is already in alarm, cause the following:
•
•
•
The buzzer sounds steadily
If signals have been silenced as a result of the signal silence button or the auto signal silence timer, signals are resounded as they were before signal silence, the signal silence indicator is turned off, and the auto signal silence timer, if confi gured, is restarted
Signals and strobes are activated
Circuit Types
The term circuits refers to an actual electrical interface, either initiating (detection) or NAC (signal). The term zone is a logical concept for a fi re alarm protected area, and will consist of at least one circuit. Often the terms zone and circuit are used interchangeably, but in this manual the term circuit is used.
25
Initiating (Detection) Circuit Types
Circuit Type
Non-Verifi ed Alarm
Description
This is a “normal” type of alarm which may have pull stations, smoke detectors, or heat detectors attached. Any activation of these devices will immediately result in an alarm condition in the fi re alarm control panel. An alarm condition causes the associated circuit Status LED and the Common Alarm
LED to illuminate red.
These alarms are verifi ed by a reset and timing procedure, and may have pull stations, smoke detectors, or heat detectors attached. Any activation of pull stations or heat detectors will result in an alarm condition in the fi re alarm control panel within four seconds. Smoke detectors will be verifi ed for a real alarm within 60 seconds depending upon the startup time of the smoke detectors being used. If four seconds is too long a response time for pull stations, then they should be wired separately on a nonverifi ed alarm circuit. An alarm condition causes the associated circuit Status LED and the Common
Alarm LED to illuminate red.
Verifi ed Alarm
Water-Flow Alarm
Non-Latching
Supervisory
Latching Supervisory
Any subsequent alarms on other circuits (whether verifi ed or not) is deemed a “verifi cation” on the fi rst activation of a verifi ed circuit and will result in immediate panel alarm, bypassing any remaining verifi cation time.
Any open troubles that occur on a Verifi ed Alarm circuit after initial activation will cause that circuit to alarm immediately. This is a fail-safe operation that handles any fi re induced wiring faults.
An alarm for water-fl ow sensors. These alarms are identical to normal non-verifi ed alarms except that any NAC circuits programmed to these circuits (all are by default) are non-silenceable. Also, if waterfl ow retard operation is enabled, then these circuits are sampled every one second; if ten samples are active within any 15 second interval, the water-fl ow alarm is confi rmed and processed. An alarm condition causes the associated circuit Status LED and the Common Alarm LED to illuminate red.
Note: Do not use the retard operation with any external retarding device; maximum retard may not exceed 90 seconds.
These alarms are for supervisory devices. An activation on these circuits will cause the Circuit Status
LED and the Common Supervisory LED to illuminate amber. The buzzer will sound at fast buzzer rate.
If the circuit activation is removed, the supervisory condition will clear (so long as there are no other supervisory conditions in the system) and the circuit Status LED will extinguish.
These alarms are for supervisory devices. An activation on these circuits will cause the Circuit Status
LED and the Common Supervisory LED to illuminate amber. The buzzer will sound continuously. If the circuit activation is removed, the Supervisory condition will not clear. Installations according to
ULC-S524 should be set for Latching Supervisory.
26
NAC (Signal) Circuits Types
Circuit Type Description
Silenceable Signal For audible devices such as bells and piezo mini-horns that may be silenced either manually or automatically. While sounding, these follow the pattern appropriate for the condition: the confi gured evacuation code (default is temporal code) during single-stage alarm, or two stage general alarm, or the alert code during a two stage system’s alert (fi rst) stage.
Non-Silenceable Signal For audible devices such as bells and piezo mini-horns that may not be silenced either manually or automatically. While sounding, these follow the pattern appropriate for the condition: the confi gured evacuation code (default is temporal code) during single-stage alarm, or two-stage general alarm, or the alert code during a two stage system’s alert (fi rst) stage.
Silenceable Visual For visual devices such as strobes that use no code pattern (they are continuous).
Non-Silenceable Visual Same as previous, but is non-silenceable.
Evacuation Codes
Single stage codes
Continuous
Temporal Code
March Code
California Code
On 100% of the time
3 of 0.5 second on, 0.5 second off then, 1.5 second pause
0.5 second on, 0.5 second off
5 seconds on, 10 seconds off
Figure 18: Evacuation Codes
CONTINOUS
0.5s
0.5s
0.5s
0.5s
5s 10s
1.5s
TEMPORAL CODE
MARCH CODE
CALIFORNIA CODE
0.5s
2.5s
ALERT CODE
27
System Confi guration
Main Fire Alarm Board
Confi guration of the PFC-5000 Series is accomplished simply by DIP Switch Settings on the Main Fire Alarm Board. For DIP
Switches, 0 = switch “off”, 1 = Switch “on’). The DIP switches are located on the bottom left side of the main fi re alarm board.
C
O
M
-
N
O
N
C
C
O
M
N
O
N
C
C
O
M
N
O
N
C
C
O
M
NA C2 (IND2) N 1 (IND1) INI4 INI3 INI2 INI1
- + - + - + - + T
R
B
T
R
L
C
O
M
+
RS-485
S - +
4 WIRE
- +
A B A B
MANU CTURER USE
28
Table 3: Confi guration DIP Switch Functions on Main Fire Alarm Board
Function
NAC Circuit #1
Audible Device (Bell) Only
NAC Circuit #2
Audible or Visual Device
# Remote Annunciators
Manual Signal Silence
Fire Dril
Aux. Disconnect
Initiating Circuit #1
Alarm Only
Initiating Circuit #2
Alarm Only
Initiating Circuit #3
Alarm or Waterfl ow
DIP Switch
Switch 13, #1
Switch 13, #2
Switch 13, #3
Switch 13, #4
Switch 13, #5
Switch 13, #6
Switch 13, #7
Switch 13, #8
Switch 11, #1
Switch 11, #2
Switch 11, #3
Switch "Off"
Silenceable
Silenceable Non-Silenceable
Audible Device (Bell) Visual Device (Strobe)
5 off, 4 off = None 5 off, 4 on = One
5 on, 4 off = Two 5 on, 4 on = Three
Disabled
Disabled
Disabled
Normal Alarm
Enabled
Enabled
Enabled
Verifi ed Alarm
Normal Alarm
Switch "On"
Non-Silenceable
Verifi ed Alarm
Initiating Circuit #4
Alarm or Supervisory
Switch 11, #4
Switch 11, #5
Switch 11, #6
Switch 11, #7
Application of AC Power Fail Delay Switch 11, #8
Signal Code Switch 9, #1
Switch 9, #2
Zone Disc Switches
Auto Signal Silence
Signal Silence Inhibit
Switch 9, #3
Switch 9, #4
Switch 9, #5
Initiating Circuit Style / Class
Aux. Devices
AC Power Fail Delay to
Aux. Devices
Switch 9, #6
Switch 9, #7
Switch 9, #8
Normal
Alarm
Normal
Alarm
Verifi ed Alarm / Retarded
Waterfl ow
Waterfl ow
Verifi ed Alarm (no effect on Supv.)
Supervisory
Non-Latching Supervisory
(No effect on Alarm)
No AC Power Fail Delay
Latching Supervisory
(No effect on Alarm)
Apply AC Power Fail Delay
2 off, 1 off = Temporal Code 2 off, 1 on = Continuous
2 on, 1 off = March Time 2 on, 1 on = California Code
3 off = Disabled 3 on = Enabled
4 off = Disabled 4 on= 20 Minutes
None 1 Minute
Class B (Style B)
Non-Silenceable
24 Hour Standby
Standard
Class A (Style D)
Silenceable
60 Hour Standby
Standard
Note:
• After you change any confi guration switches, perform a system hard reset or power off/on sequence. If this is not done, then a Switch Tamper Trouble will occur. Perform a hard reset by pressing SW0 push button switch on back of main panel pcb.
• Do not use retard operation with any external retarding device; maximum retard may not exceed 90 seconds.
29
When confi guring the PFC-5000 main board, keep in mind the following information:
• Only NAC circuit 2 may be confi gured for visual devices.
•
•
•
•
•
If initiating circuit 3 is confi gured as waterfl ow, the corresponding verifi ed selection becomes a retard selection.
If initiating circuit 4 is confi gured as alarm, the corresponding latching selection has no effect.
If initiating circuit 4 is confi gured as supervisory, the corresponding verifi ed selection has no effect.
The selection of Class A/B (Style Z/Y) NAC circuits is only a matter of how they are wired. See connection information on page 13.
If Class A (Style D) initiating circuits are selected, JW1 and JW2 jumpers must also be set. Class B initiating circuits 1 and 2 combine to create Class A Circuit #1, and Class B initiating circuits 3 and 4 combine to create Class A Circuit #2. DIP switches for circuits 3 and 4 are ignored except for an PFC-5004E with a ZA-42 Adder Module. LED indicators for circuits
3 and 4 are non-functional except for an PFC-5004E with a ZA-42 Adder Module.
ZA-42 Module
On the ZA-42 Zone Adder Module the DIP switches are located on the bottom right-hand corner.
30
Table 4: Confi guration DIP Switch Functions on ZA-42 Module
Function
NAC Circuit #3
Audible Device (Bell) Only
NAC Circuit #4
Audible or Visual Device
Not Used
Initiating Circuit #5
Alarm Only
Initiating Circuit #6
Alarm Only
Initiating Circuit #7
Alarm or Waterfl ow
DIP Switch on ZA-42
Module
Switch 6, #1
Switch 6, #2
Switch 6, #3
Switch 6, #4
Switch 5, #1
Switch 5, #2
Switch "Off"
Silenceable
Silenceable
Audible Device (Bell)
-----------------
Normal Alarm
Normal Alarm
Switch "On"
Non-Silenceable
Non-Silenceable
Visual Device (Strobe)
-----------------
Verifi ed Alarm
Verifi ed Alarm
Initiating Circuit #8
Alarm or Supervisory
Switch 5, #3
Switch 5, #4
Switch 5, #5
Switch 5, #6
Switch 5, #7
Normal
Alarm
Normal
Alarm
Non-Latching Supervisory (No effect on Alarm)
-----------------
Verifi ed Alarm / Retarded
Waterfl ow
Waterfl ow
Verifi ed Alarm
(No effect on Supervisory)
Supervisory
Latching Supervisory
(No effect on Alarm)
----------------Not Used Switch 5, #8
Note:
• After you change any confi guration switches, perform a system hard reset or power off/on sequence. If this is not done, then a Switch Tamper Trouble will occur. Perform a hard reset by pressing SW0 push button switch on back of main panel pcb.
• Do not use retard operation with any external retarding device; maximum retard may not exceed 90 seconds.
When confi guring the ZA-42, keep in mind the following information:
• Only NAC Circuit #4 may be confi gured for visual devices.
•
•
•
•
•
If Initiating Circuit #7 is confi gured as waterfl ow, the corresponding verifi ed selection becomes a retard selection.
If Initiating Circuit #8 is confi gured as alarm, the corresponding latching selection has no effect.
If Initiating Circuit #8 is confi gured as supervisory, the corresponding verifi ed selection has no effect.
The selection of Class A/B (Style Z/Y) NAC circuits is only a matter of how they are wired. See connection information on page 15.
If Class A (Style D) initiating circuits are selected, JW2 and JW3 jumpers must also be set. Class B initiating circuits 5 and 6 combine to create Class A Circuit #3, and Class B initiating circuits 7 and 8 combine to create Class A Circuit #4. DIP switches for circuits 5 to 8 are ignored, and led indicators for circuits 5 to 8 are non-functional.
31
Walk Test Operation
A walk test allows an installer to verify the Initiating Circuit wiring in a system. To enter walk test, press and hold both the Buzzer
Silence and Lamp Test momentary switches for at least one second. You can identify circuits to be tested using the Circuit
Disconnect slide switches. Confi guration SW9 #3 Zone Disconnect Enable/Disable must be set to “ON” to allow Walk Test
Operation. Activation of any initiating circuit that has been selected for the walk test will cause the audible NAC circuits to activate briefl y for a number of short bursts corresponding to the circuit number. Any subsequent activations on the same initiating circuit will activate the audible NAC circuit only once. If another initiating circuit is activated then the audible NAC circuits will activate for a number of short bursts corresponding to the circuit number of the new zone being walk-tested, and so on.
For example, if Initiating Circuit #3 is fi rst activated, the indication circuits will sound for three bursts. Any subsequent activations of Initiating Circuit #3 will sound for one burst. The initial burst interval denoting the count of the circuit number is one second on followed by 1/2 second off. The subsequent burst interval denoting additional activations on the same initiating circuit is 1/2 second on then off. After the sounding pattern has been sent on the NAC circuits, the initiating circuit is reset and tested again. If it is still active (in alarm) the pattern will be re-sent. Trouble on any initiating circuit when in walk test mode causes all NAC circuits to be activated continuously for fi ve seconds.
Alarm verifi cation and water-fl ow alarm retard operations are disabled on circuits being walk tested. All circuits not selected for walk-test continue to function normally. The walk test operation is disabled if the fi re alarm control panel is in alarm or goes into alarm while walk-test is active. It will also time out after 60 minutes of no activity.
32
Appendix A: Compatible Devices
(ULC) Canadian: Two-wire Smoke Detector Control Panel Compatibility
Note:
Whether mixing different models of compatible smoke detectors or using the same model on the same circuit, the total standby current of all detectors must not exceed 3 mA.
Make Model/Base
Potter
PS-24 / SB93
IS-24 / SB93
PS-24H / SB93
BPS-2
Hochiki
DCD-135/NS6-220
DCD-135/NS4-220
DCD-135/HSC-220R
DCD-190/NS6-220
DCD-190/NS4-220
DCD-190/HSC-220R
SIJ-24/NS6-220
SIJ-24/NS4-220
SIJ-24/HSC-220R
SLR-24/NS6-220
SLR-24/NS4-220
SLR-24/HSC-220R
SLR-24H/NS6-220
SLR-24H/NS4-220
SLR-24H/HSC-220R
SLR-835/NS6-220
SLR-835/NS4-220
SLR-835/HSC-220R
SLR-835B-2
System Sensor
1400-A
2400-A
1451-A/B401B
Make Model / Base
1451-A/B406B
2451-A/B401B
2451-A/B406B
1451DH/DH400A
2451-A/DH400A
Edwards
6249C
6250C
6264C
6266C
6269C
6270C
6269C-003
6270C-003
Cerberus Pyrotronics
D1-2
D1-3/DB-3S
Mircom
MIR-525
MIR-525T
Mirtone
73471
73494
73575
73495/73486
73495/73487
73595/73486
73595/73497
73594/73400
Make Model / Base
73405/73400
73594/73401
73405/73401
Fenwal
PSD-7131/70-201000-001
PSD-7131/70-201000-002
PSD-7131/70-201000-003
PSD-7131/70-201000-005
PSD-7130/70-201000-001
PSD-7130/70-201000-002
PSD-7130/70-201000-003
PSD-7130/70-201000-005
PSD-7128/70-201000-001
PSD-7126/70-201000-002
PSD-7126/70-201000-003
PSD-7126/70-201000-005
PSD-7129/70-201000-000
PSD-7125/70-201000-001
PSD-7126/70-201000-002
PSD-7125/70-201000-003
PSD-7125/70-201000-005
CPD-7021/70-201000-001
CPD-7021/70-201000-002
CPD-7021/70-201000-003
CPD-7021/70-201000-005
Napco
FW-2
Simplex
2098-9110
33
(UL) United States: Two-Wire Smoke Detector Control Panel Compatibility
Note:
• Whether mixing different models of compatible smoke detectors or using the same model on the same circuit, total standby current of all detectors must not exceed 3 mA.
• The below listed smoke detectors are compatible with initiating circuits having Compatibility Identifi er “A”.
Smoke Detector
Make Model / Base
Compatibility
Identifi er Head / Base
Rated Standby
Current
Smoke Detector
Make Model / Base
Compatibility
Identifi er Head / Base
Rated Standby
Current
Potter
PS-24
IS-24
PS-24H
BPS
HD-3/HB-72
HD-3/HB-72
HD-3/HB-3
HD-3/HB-3
0.045mA
0.040mA
0.045mA
0.045mA
System Sensor
1100
1151/ B110LP
1151/ B116LP
1400
1451/B401
1451/ B401B
A - N/A
A - A
A - A
A - N/A
A - A
A - A
0.12 mA
0.12 mA
0.12 mA
0.10 mA
0.12 mA
0.12 mA
Hochiki
DCD-135/NS6-220
DCD-135/NS4-220
DCD-135/HSC-220R
DCD-190/NS6-220
DCD-190/NS4-220
DCD-190/HSC-220R
SIJ-24/NS6-220
SIJ-24/NS4-220
SIJ-24/HSC-220R
SLR-24/NS6-220
SLR-24/NS4-220
SLR-24/HSC-220R
SLR-24H/NS6-220
SLR-24H/NS4-220
SLR-24H/HSC-220R
SLR-835/NS6-220
SLR-835/NS6-220
SLR-835/NS4-220
SLR-835/HSC-220R
SLR-835B-2
429CRT
711U/701E, 701U,
702E, 702U
712U / 701E, 701U,
702E, 702U
713-5U / 701E, 701U,
702E, 702U
713-6U / 701E, 701U,
702E, 702U
721U / 702E, 702U
721UT / 702E, 702U
722U / 702E, 702U
731U / 702E, 702U,
702RE, 702RU
732U / 702E, 702U,
702RE, 702RU
HD-3/HB-3
HD-3/HB-3
HD-3/HB-3
HD-3/HB-72
HD-3/HB-3
HD-3/HB-3
HD-3/HB-3
HD-3/HB-72
HD-6
S11A - N/A
S10A - S00
HD-3/HB-72
HD-3/HB-3
HD-3/HB-3
HD-3/HB-3
HD-3/HB-3
HD-3/HB-3
HD-3/HB-72
HD-3/HB-3
HD-3/HB-3
HD-3/HB-72
HD-3/HB-3
S10A - S00
S10A - S00
S10A - S00
S10A - S00
S10A - S00
S10A - S00
S11A - S00
S11A - S00
0.045mA
0.045mA
0.045mA
0.045mA
0.045mA
0.045mA
0.045mA
0.045mA
55ua @ 24VDC
0.10 mA
0.10 mA
0.035mA
0.035mA
0.035mA
0.035mA
0.035mA
0.035mA
0.040mA
0.040mA
0.040mA
0.045mA
0.045mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
1451/ B406B
1451DH/ DH400
2100
2100T
2151/ B110LP
2151/ B116LP
2400
2400TH
2400AT
2400AIT
2451 / B401B
2451 / B406B
2451 / DH400
2451TH / B406B
2451 / B401
2451TH / B401
4451HT / B401B
4451HT / B406B
4451HT / B401
5451 / B401B
5451 / B401
5451 / B406B
Sentrol - ESL
429C
429CT
429CST
Detection Systems
DS250
DS250TH
DS282
A - A
A - N/A
A - A
A - A
A - A
A - A
A - A
A - A
A - A
A - A
A - A
A - A
A - A
A - N/A
A - N/A
A - A
A - A
A - N/A
A - N/A
A - N/A
A - N/A
A - A
S10A - N/A
S10A - N/A
S11A - N/A
B - N/A
B - N/A
B - N/A
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
DS282TH B - N/A 0.10 mA Mircom
MIR-525U
MIR-525TU
FDT-1
FDT-1
0.10 mA
0.10 mA
Napco
FW-2 HD-6 55uA @ 24VDC
34
(UL) United States: 4-Wire Smoke Detector Control Panel Compatibility
Mircom
Sentrol - ESL
System Sensor
MIR-545U
541C
741U WITH 702U or
702E Base
1424
DH400ACDCI
MIR-545TU
449AT, 449C, 449CT, 449CRT, 449CST, 449CSTE, 449CSRT, 449CSRH,
449CSST, 449CSSTE, 449CTE, 449CLTCSLT
6424
DH400ACDCP
6424A
DH400ACDCIHT
A77-716B
(UL) United States: Signalling Device Control Panel Compatibility
System Sensor - SpecrAlert
P2415 P2415W
P2475W
S241575
S24110W
P24110
S241575W
H12/24
P241575
P24110W
S2475
H12/24W
Wheelock
AS-2415W-24-FR
AS-2415C-FW
AH-24-WP-R
NS-24110W-FR
AS-241575W-FR
AS-2430C-FW
NS-2415W-FR
NS4-2415W-FR
AS-2430W-FR
AS-2475C-FW
NS-241575W-FR
NS4-241575W-FR
NS4-24110W-FR
RSS-2430W-FR
RSS-2475C-FW
RS-2415W-FR
RSS-2475W-FR
RSS-24100C-FW
RSS-241575W-FR
RSS-24110W-FR
MT-12/24-ULC
AMT-12/24-R-ULC AMT-24-LS-VFR-ULC MB-G6-24-R
DSM-12/24-R
Gentex
AVP-4-15-1
GXS-4-15/75-W
GX90S-4-15/75-W
SHG15/75-W
GOS24-15-1
GMH-24
GMS-24-110-1
AVP-4-15/75
GXS-4-30/75-W
GX90S-4-30/75W
SHG24-30/75-W
GOS24-15/75
GMS-24-15-1
WGMS-4/75
AVP-4-30/75
GXS-4-15/75-C
GX90S-4-15/75-C
SHG24-15/75-C
GOS24-15/75
GMS-24-15/75-W
P241575W
S2415
S2475W
MDL
AVP-4-110-1
GXS-4-110-1
GX90S-4-110-1
SHG24-110-1
GOS24-30/75
GMS-24-30/75-W
P2475
S2415W
S24110
MDLW
AS-2475W-FR
AS-24100C-FW
NS-2430W-FR
NS4-2430W-FR
AS-24110W-FR
AH-24-R
NS-2475W-FR
NS4-2475W-FR
RSS-2415W-FR
RSS-2415C-FW
RSS-241575W-FR
RSS-2430C-FW
MT-24-LS-VFR-ULC MT-24-WS-VFR-ULC
MB-G10-24-R SM-12/24-R
GXS-4-15-1
GX90S-4-15-1
SHG24-15-1
GOT24
GOS24-110-1
GMS-24-15/75-C
35
Appendix B: Remote Annunciators
The RA8F Eight Zone Remote Annunciator mounts in an electrical box. It provides annunciation for the PFC-5004, PFC-5008, or PFC-5004E’s full complement of 8 Initiating circuits.
For more detailed information see Potter Document #8900103 PFC-5004 bulletin, #8900104 PFC-5004E/PFC-5008 bulletin,
#8910202 RA8F bulletin.
36
Appendix C: Module Specifi cations And Features
PFC-5002 Fire Alarm Control Panel PFC-5004E/PFC-5008 Fire Alarm Control Panel
General
Two supervised Class B (Style B) or one Class A (Style D)
Initiating circuits; confi gurable (normal or verifi ed, and for
Class B there may be one waterfl ow and one supervisory).
[Compatibility ID “A”]
Two Class A/B (Style Y/Z) NAC circuits; confi gurable as strobes or audibles.
Power limited: 24 VDC unfi ltered
1.7 A per circuit (2.0 a total)
Initiating circuit disconnect switch.
Optional UDACT or city tie adder module.
Optional ARM-4 / ARM-8 Relay Module.
Resettable four-wire smoke supply.
Power Limited: 28VDC, 100mA max, 1.5Vp-p ripple
Aux power supply.
Power limited: 24VDC, 300mA max, special application for
RTI or remote annunciators.
1 RTI Interface for connection to an RTI Remote Trouble
Indicator.
Auxiliary relays (resistive loads):
Common Alarm: Form C, 1Amp, 28VDC
Common Trouble:Form C, 1Amp, 28VDC
DIP switch confi gurable.
Walktest function.
Electrical ratings
AC Line Voltage: 120V 0.74A 60Hz / 240V 0.34A 50/60Hz
Two amps (inline fuse on transformer primary)
Power supply ratings: 2.4 amps. max. (secondary)
For NAC circuits: 24VDC unfi ltered 2.0 amps. max.
Battery: 24VDC, gel-cell/sealed lead-acid
Charging capability: 4 to 24 AHr batteries
(cabinet will hold up to 8AH)
Current consumption: standby: 110 mA / alarm: 220 mA
PFC-5004 Fire Alarm Control Panel
Same as PFC-5002, except ...
Only has four supervised Class B (Style B) or two Class A (Style
D) initiating circuits; confi gurable (normal or verifi ed).
[Compatibility ID “A”]
Zone 3 confi gurable as Waterfl ow
Zone 4 confi gurable as Supervisory
General
Four supervised Style B (Class B) or 2 Style D (Class A) initiating circuits; confi gurable. [Compatibility ID “A”]
Power limited:26VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA max. (alarm)
Two Class A/B (Style Y/ Z) NAC circuits; confi gurable as strobes or audibles.
Power limited:24 VDC unfi ltered
1.7 A per circuit (5A total)
One ZA-42 Zone Adder Module may be added.
Initiating circuit disconnect switches.
Optional DACT or city tie adder module.
Optional ARM-4 / ARM-8 Relay Module.
Resettable four-wire smoke supply.
Power limited: 28VDC, 100mA max, 1.5Vp-p ripple
Aux power supply.
Power limited: 24VDC, 300mA max, special application for RTI or Remote Annunciators
1 RS-485 connection for up to 3 RA8F Remote Annunciators.
1 RTI interface for connection to an RTI Remote Trouble Indicator.
Auxiliary relays (resistive loads):
Common Alarm: Form C, 1Amp, 28VDC
Common Trouble: Form C, 1Amp, 28VDC
Common Supervisory: Form C, 1Amp, 28VDC
DIP switch confi gurable.
Walktest function.
Electrical ratings:
AC Line Voltage:120V 1.65A 60Hz / 240V 0.64A 50/60Hz
Power supply ratings: 6 amps max. (secondary)
For NAC circuits: 24VDC unfi ltered, 5 amps max.
Battery: 24VDC, Gel-Cell/Sealed Lead-Acid
Charging capability: 4 to 24 AH batteries
(cabinet will hold up to 12AH)
Current consumption: standby: 110 mA / alarm: 220 mA
37
ZA-42 Zone Adder Module
May be added to PFC-5004E.
4 supervised Class B (Style B) or 2 Class A (Style D) initiating circuits; confi gurable. [Compatibility ID “A”]
Power limited: 22VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA max. (alarm)
2 Class B or A (Style Y or Z) NAC circuits; confi gurable as strobes or audibles.
Power limited: 24 VDC unfi ltered, 1.7A per Circuit
Current consumption:
standby: 45 mA
alarm: 120 mA
ARM-4/ARM-8 Relay Module
Four or eight relays: Form C, 1A (resistive), 28 VDC per contacts
Each individual relay can be relay per zone, common alarm, common supervisory
Current Consumption:standby: 5 mA
alarm: 160 mA
Polarity Reversal and City Tie Module (PR-5100)
Supervised city tie:not power limited
24VDC unfi ltered, 210 mA max., Trip coil: 14 ohms
Polarity reversal: power limited
24VDC open, 12VDC @ 3.5 mA, 8 mA max. (shorted)
Current consumption: standby: 35 mA
alarm: 300 mA
Miscellaneous
Remote Trouble Indicator (RTI-1)
Trouble LED and Buzzer
End-of-line resistor plates (MP-300, MP-300R).
Internal 3.9 Kohm, ½ Watt, 5% resistor.
Ground Fault Impedance = 13.5 Kohm
System model: PFC-5000 Fire Alarm Control Panel
System type: Local, auxiliary (using PR-5100), remote station protected premises (using UDACT-9100 or PR-5100), central station protected premises (using UDACT-9100).
Type of service: A, M, WF, SS (SS is only local or with UDACT-9100)
Type of signalling: Non-Coded
Equipment standards: UL-864 - Rev.9, ULC S-527-99
Installation Standards: NFPA 70 and 72, ULC-S524, CEC Part-1 C22.1
Inspection and Testing Standard: ULC-S536
38
Appendix D: Power Supply & Battery Calculations
Use the form below to determine the required main chassis and secondary power supply (batteries).
The main AC branch circuit connection for Fire Alarm
Control Unit must provide a dedicated continuous power without provision of any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes. Refer to Appendix C on page 38 for specifi cations.
Model
Number
PFC-5002,
PFC-5004,
PFC-5004E
PFC-5008
Description
Panel
ZA-42
ARM-4/
ARM-8
Zone Adder
Module
Relay Module
PR-5100
Polarity Reversal and City Tie
Module
UDACT-9100 DACT Module
Power Requirements (All currents are in amperes)
Qty Standby
Total
Standby
Fire Alarm Control
X
X
X
0.110
0.045
0.005
0.035
0.045
=
=
=
=
=
RA8F
RTI-1
Remote
Annunciator
Remote Trouble
Indicator
Two-Wire Smoke Detectors
Four-Wire Smoke Detectors
Signal Load (bells, horns, strobes, and etc.)
X
Auxiliary Power Supply for Remote Annunciators
Total currents (Add above currents)
♦
0.035
0.035
0.0001
STANDBY
=
=
=
=
(A)
Alarm
0.220
0.120
0.160
0.300
0.120
0.090
=
=
=
=
=
=
Total
Alarm
0.035
=
* 0.090
= 0.090
=
=
Alarm =
(B)
Total Current Requirement
ALARM (B)______ Amps.
Battery Capacity Requirement
([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [
♣ Alarm in Hr.] _____) = (C) ______AH
* Assuming two NAC
circuits in alarm.
♣ Use 0.084 for fi ve minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier fi gure.
♦ Using the 1400-A 2-wire smoke detector. See Appendix A on page 33 for other available smoke detectors.
Total Alarm Current
• Must be 2.4 amperes or less for PFC-5002, and PFC-5004. NAC Circuits not to exceed 2.0 amperes.
• Must be 6 amperes or less for PFC-5004E/ PFC-5008. NAC Circuits not to exceed 5 amperes.
Battery Selection
• Multiply (C) by 1.20 to derate battery.
•
•
The PFC-5000 Series will charge BT-40 (4 AHr), BT-80 (8 AHr), BT-120 (12 AHr), BT-180 (18 AHr) or BA-240 (24
AHr)batteries (2 required)
The BT-180 and the BA-240 require a Listed Battery Cabinet.
39
WARRANTY INFORMATION
The essential purpose of any sale or contract for sale of any of the products listed in the POTTER catalog or price list is the furnishing of that product. It is expressly understood that in furnishing said product, POTTER does not agree to insure the Purchaser against any losses the Purchaser may incur, even if resulting from the malfunction of said product.
POTTER warrants that the equipment herein shall conform to said descriptions as to all affi rmation of fact and shall be free from defects of manufacture, labeling and packaging for a period of one (1), one and one half (1.5), three (3), or fi ve (5) year'(s), depending on the product, from the invoice date to the original purchaser, provided that representative samples are returned to POTTER for inspection. The product warranty period is stated on the exterior of the product package. Upon a determination by POTTER that a product is not as warranted, POTTER shall, at its exclusive option, replace or repair said defective product or parts thereof at its own expense except that Purchaser shall pay all shipping, insurance and similar charges incurred in connection with the replacement of the defective product or parts thereof. This Warranty is void in the case of abuse, misuse, abnormal usage, faulty installation or repair by unauthorized persons, or if for any other reason POTTER determines that said product is not operating properly as a result of causes other than defective manufacture, labeling or packaging.
The Aforesaid Warranty Is Expressly Made In Lieu Of Any Other Warranties, Expressed Or Implied, It
Being Understood That All Such Other Warranties, Expressed Or Implied, Including The Warranties Of
Merchantability And Fitness For Particular Purpose Are Hereby Expressly Excluded. In No Event Shall
Potter Be Liable To Purchaser For Any Direct, Collateral, Incidental Or Consequential Damages In
Connection With Purchaser’s Use Of Any Of The Products Listed Herein, Or For Any Other Cause Whatsoever
Relating To The Said Products. Neither Potter Nor Its Representatives Shall Be Liable To The Purchaser
Or Anyone Else For Any Liability, Claim, Loss, Damage Or Expense Of Any Kind, Or Direct Collateral,
Incidental Or Consequential Damages Relative To Or Arising From Or Caused Directly Or Indirectly By Said
Products Or The Use Thereof Or Any Defi ciency, Defect Or Inadequacy Of The Said Products. It Is Expressly
Agreed That Purchaser’s Exclusive Remedy For Any Cause Of Action Relating To The Purchase And/or Use
Of Any Of The Products Listed Herein From Potter Shall Be For Damages, And Potter's Liability For Any And
All Losses Or Damages Resulting From Any Cause Whatsoever, Including Negligence, Or Other Fault, Shall
In No Event Exceed The Purchase Price Of The Product In Respect To Which The Claim Is Made, Or At The
Election Of Potter, The Restoration Or Replacement Or Repair Of Such Product.
40
POTTER ELECTRIC SIGNAL COMPANY, LLC
St. Louis, MO
(866) 956-1211 • (314) 595-6900 • FAX (314) 595-6999 www.pottersignal.com
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 Introduction
- 5 About this Manual
- 5 About the PFC
- 5 Technical Support
- 6 Document Conventions
- 6 Circuits and Zones
- 6 Wiring Styles
- 8 Circuit Adder Modules
- 8 Auxiliary Models
- 8 PFC-5000 Accessories
- 9 Mechanical Installation and Dimensions
- 11 Modules Mounting Locations
- 13 Module Settings
- 13 Main Fire Alarm Module
- 14 Zone Adder Module (Model ZA-42)
- 14 Relay Modules (Models ARM-4 or ARM-8)
- 15 UDACT / DACT (Model UDACT-9100)
- 15 Polarity Reversal and City Tie Module (Model: PR-5100)
- 16 Field Wiring
- 16 General Field Wiring Considerations
- 17 Main Fire Alarm Module Terminal Connections
- 19 Figure 12: Zone Adder Module (ZA-42) Terminal Connections
- 20 Figure 13: Relay Module (ARM-4 or ARM-8) Terminal Connections
- 21 UDACT / DACT (UDACT-9100) Terminal Connections
- 22 Polarity Reversal and City Tie Module (Model:PR-5100) Terminal Connections
- 23 Power Supply Connections
- 24 Wiring Tables
- 25 System Checkout
- 25 Before Turning The Power On
- 25 Power-up Procedure
- 25 Troubleshooting
- 26 Indicators, Controls, & Operation
- 26 Indicators
- 28 Controls
- 29 Operation
- 29 Circuit Types
- 30 Initiating (Detection) Circuit Types
- 31 NAC (Signal) Circuits Types
- 32 System Confi guration
- 32 Main Fire Alarm Board
- 34 ZA-42 Module
- 36 Walk Test Operation
- 37 Appendix A: Compatible Devices
- 37 (ULC) Canadian: Two-wire Smoke Detector Control Panel Compatibility
- 38 (UL) United States: Two-Wire Smoke Detector Control Panel Compatibility
- 39 (UL) United States: 4-Wire Smoke Detector Control Panel Compatibility
- 39 (UL) United States: Signalling Device Control Panel Compatibility