- Home
- Domestic appliances
- Small kitchen appliances
- Water dispensers
- Water Right
- Impression Series
- Troubleshooting guide
advertisement
Impression Series
® and
Impression Plus Series
®
Metered Water Softeners
TABLE OF CONTENTS
Preinstallation Instructions for Dealers . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Bypass Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
Programming Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8
Operating Displays and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-10
Start-up Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-15
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-25
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Quick Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
YOUR WATER TEST
Hardness
Iron pH
*Nitrates
Manganese gpg ppm number ppm
Sulphur
Total Dissolved Solids ppm yes/no
*Over 10 ppm may be harmful for human consumption. Water conditioners do not remove nitrates or coliform bacteria, this requires specialized equipment.
Your Impression Series water conditioners are precision built, high quality products. These units will deliver conditioned water for many years to come, when installed and operated properly. Please study this manual carefully and understand the cautions and notes before installing. This manual should be kept for future reference. If you have any questions regarding your water conditioner, contact your local dealer or Water-Right at the following:
Water-Right, Inc.
1900 Prospect Court • Appleton, WI 54914
Phone: 920-739-9401 • Fax: 920-739-9406
PREINSTALLATION INSTRUCTIONS FOR DEALERS:
The manufacturer has preset the water treatment unit’s sequence of cycles, cycle times, salt dose, exchange capacity and salt dose refill time.
The dealer should read this page and guide the installer regarding hardness, day override, and time of regeneration, before installation.
For the installer, the following must be used:
• Program Installer Settings: Hardness, Day Override (preset to 12 days), and Time of
Regeneration (preset to 2 a.m., with brine tank refill to occur four hours prior; see Operating
Displays and Instructions for more details)
• Read Normal Operating Displays
• Set Time of Day
• Read Power Loss & Error Display
For the homeowner, please read operating displays and instructions.
WATER SOFTENERS:
During operation, the normal user displays are time of day or gallons remaining before regeneration will occur.
Days remaining is an optional display but is not normally used. Each of these can be viewed by pressing
NEXT to scroll through them. When stepping through any displays or programming, if no buttons are pressed within 5 minutes, the display returns to a normal user display. Any changes made prior to the
5 minute time out are incorporated.
To quickly exit any Programming, Installer Settings, etc., press SET CLOCK . Any changes made prior to the exit are incorporated. If desired, two regenerations within 24 hours are possible with a return to the preset program. To do a double regeneration:
1. Press the REGEN button once. “REGEN TODAY” will flash on the display.
2. Press and hold the REGEN button for three seconds until a regeneration begins.
Once the valve has completed the immediate regeneration, the valve will regenerate one more time at the preset.
BYPASS VALVE:
The bypass valve is typically used to isolate the control valve from the plumbing system’s water pressure in order to perform control valve repairs or maintenance. The 1" full flow bypass valve incorporates four positions, including a diagnostic position that allows a service technician to have pressure to test a system while providing untreated bypass water to the building. Be sure to install bypass valve onto main control valve, before beginning plumbing. Or, make provisions in the plumbing system for a bypass. The bypass body and rotors are glass-filled Noryl ® and the nuts and caps are glass-filled polypropylene. All seals are self-lubricating EPDM to help prevent valve seizing after long periods of non-use. Internal “O” Rings can easily be replaced if service is required.
The bypass consists of two interchangeable plug valves that are operated independently by red arrow shaped handles. The handles identify the direction of flow. The plug valves enable the bypass valve to operate in four positions.
3
1. NORMAL OPERATION POSITION: The inlet and outlet handles point in the direction of flow indicated by the engraved arrows on the control valve. Water flows through the control valve for normal operation of a water softener. During the regeneration cycle this position provides regeneration water to the unit, while also providing untreated water to the distribution system (Fig. 1).
2. BYPASS POSITION: The inlet and outlet handles point to the center of the bypass. The system is isolated from the water pressure in the plumbing system. Untreated water is supplied to the building
(Fig. 2).
3. DIAGNOSTIC POSITION: The inlet handle points toward the control valve and the outlet handle points to the center of bypass valve. Untreated supply water is allowed to flow to the system and to the building, while not allowing water to exit from the system to the building (Fig. 3). This allows the service technician to draw brine and perform other tests without the test water going to the building.
NOTE: The system must be rinsed before returning the bypass valve to the normal position.
4. SHUT OFF POSITION: The inlet handle points to the center of the bypass valve and the outlet handle points away from the control valve. The water is shut off to the building. The water treatment system will depressurize upon opening a tap in the building. A negative pressure in the building combined with the softener being in regeneration could cause a siphoning of brine into the building.
If water is available on the outlet side of the softener, it is an indication of water bypassing the system (Fig. 4) (i.e. a plumbing cross-connection somewhere in the building).
NORMAL OPERATION POSITION BYPASS POSITION
Figure 1
DIAGNOSTIC POSITION
Figure 2
SHUT OFF POSITION
Figure 3
4
Figure 4
INSTALLATION:
GENERAL INSTALLATION & SERVICE WARNINGS
The control valve, fittings and/or bypass are designed to accommodate minor plumbing misalignments.
There is a small amount of “give” to properly connect the piping, but the water softener is not designed to support the weight of the plumbing.
Do not use Vaseline, oils, other hydrocarbon lubricants or spray silicone anywhere. A silicone lubricant may be used on black “O” Rings, but is not necessary. Avoid any type of lubricants, including silicone, on red or clear lip seals.
Do not use pipe dope or other sealants on threads. Teflon ® tape must be used on the threads of the 1" NPT inlet and and outlet, the brine line connection at the control valve, and on the threads for the drain line connection. Teflon ® tape is not used on the nut connections or caps because “O” Ring seals are used.
The nuts and caps are designed to be unscrewed or tightened by hand or with the special plastic Service
Wrench, #CV3193-01. If necessary, pliers can be used to unscrew the nut or cap. Do not use a pipe wrench to tighten nuts or caps. Do not place screwdriver in slots on caps and/or tap with a hammer.
SITE REQUIREMENTS
• water pressure – 25-100 psi
• water temperature – 33-100°F (0.5-37.7°C)
• electrical – 115/120V, 60Hz uninterrupted outlet
• the tank should be on a firm level surface
• current draw is 0.5 amperes
• the plug-in transformer is for dry locations only
WELL WATER INSTALLATION MUNICIPAL INSTALLATION
1. The distance between the drain and the water conditioner should be as short as possible.
2. Since salt must be periodically added to the brine tank, it should be located where it is easily accessible.
3. Do not install any water conditioner with less than 10 feet of piping between its outlet and the inlet of a water heater.
4. Do not locate unit where it or its connections (including the drain and overflow lines) will ever be subjected to room temperatures under 33° F.
5. Do not subject the tank to any vacuum, as this may cause an “implosion” and could result in leaking. If there is a possibility a vacuum could occur, please make provision for a vacuum breaker in the installation.
5
6. INLET/OUTLET PLUMBING: Be sure to install Bypass Valve onto main control valve before beginning plumbing. Make provisions to bypass outside hydrant and cold hard water lines at this time. Install an inlet shutoff valve and plumb to the unit’s bypass valve inlet located at the right rear as you face the unit. There are a variety of installation fittings available. They are listed under Installation Fitting Assemblies, page 24-25.
When assembling the installation fitting package (inlet and outlet), connect the fitting to the plumbing system first and then attach the nut, split ring and “O” Ring. Heat from soldering or solvent cements may damage the nut, split ring or “O” Ring. Solder joints should be cool and solvent cements should be set before installing the nut, split ring and “O” Ring. Avoid getting solder flux, primer, and solvent cement on any part of the “O”
Rings, split rings, bypass valve or control valve. If the building’s electrical system is grounded to the plumbing, install a copper grounding strap from the inlet to the outlet pipe. Plumbing must be done in accordance with all applicable local codes.
7. DRAIN LINE: First, be sure that the drain can handle the backwash rate of the system. Solder joints near the drain must be done prior to connecting the drain line flow control fitting. Leave at least 6" between the drain line flow control fitting and solder joints. Failure to do this could cause interior damage to the flow control.
Install a 1/2" I.D. flexible plastic tube to the Drain Line Assembly or discard the tubing nut and use the 3/4"
NPT fitting for rigid pipe (recommended). If the backwash rate is greater than 7 gpm, use a 3/4" drain line.
Where the drain line is elevated but empties into a drain below the level of the control valve, form a 7" loop at the discharge end of the line so that the bottom of the loop is level with the drain connection on the control valve. This will provide an adequate anti-siphon trap. Piping the drain line overhead
<10 ft is normally not a problem. Be sure adequate pressure is available (40-60
Typical Drain Line Installations
psi is recommended). Where the drain empties into an overhead sewer line, a sink-type trap must be used with appropriate air gap (see drawing). Run drain tube to its discharge point in accordance with plumbing codes. Pay special attention to codes for air gaps and anti-siphon devices.
8. BRINE TANK CONNECTION: Install the 3/8" O.D. polyethylene tube from the Refill Elbow to the Brine
Valve in the brine tank.
9. OVERFLOW LINE CONNECTION: An overflow drain line is recommended where a brine overflow could
damage furnishings or the building structure. Your softener is equipped with a brine tank safety float which greatly reduces the chance of an accidental brine overflow. In the event of a malfunction, however, an
overflow line connection will direct the “overflow” to the drain instead of spilling on the floor where it could cause considerable damage. This fitting is an elbow on the side of the brine tank. Attach a length of 1/2" I.D.
tubing to fitting and run to drain. Do not elevate overflow line higher than 3" below bottom of overflow fitting.
Do not “tie” this tube into the drain line of the control valve. Overflow line must be a direct, separate line from overflow fitting to drain, sewer, or tub. Allow an air gap as per the drain line instructions.
CAUTION: Never insert a drain line into a drain, sewer line, or
trap. Always allow an air gap between the drain line and the wastewater to prevent the possibility of sewage being back-siphoned into the conditioner.
6
PROGRAMMING PROCEDURES:
1. Set time of day:
Time of day should only need to be set after extended power outages or when daylight saving time begins or ends. If an extended power outage occurs, the time of day will flash on and off indicating that the time should be reset.
STEP 1 – Press SET CLOCK .
STEP 2 – CURRENT TIME (HOUR): Set the hour of the day using + or — buttons.
AM/PM toggles after 12. Press NEXT to go to step 3.
STEP 3 – CURRENT TIME (MINUTES): Set the minutes using + or — buttons. If it is desired to back up to the previous step press REGEN button once. Pressing NEXT will exit SET CLOCK and return to the general operating display (page 10).
1 2 3
2. Programming:
NOTE: The manufacturer has preset the unit so that the gallons between regenerations will be automatically calculated after the hardness is entered.
STEP 1 – Press NEXT and + simultaneously for 3 seconds.
STEP 2 – HARDNESS: Set the amount of hardness in grains per gallon (default 20) using the + or — buttons. The allowable range is from 1 to 150 in 1 grain increments.
Note: Increase the grains per gallon if soluble iron is present (1ppm = 4 gpg). This display will show “–nA– (not available)” if “FILTER” is selected or if “AUTO” is not factory set.
Press
NEXT to go to step 3. Press
REGEN if you want to exit.
STEP 3 – DAY OVERRIDE: The manufacturer has factory set 12 DAYS as the default.
This is the maximum number of days between regenerations. If this is set to “OFF”, regeneration initiation is based solely on gallons used. If any number is set (allowable range from 1 to 28), a regeneration initiation will be called for on that day even if a sufficient number of gallons were not used to call for a regeneration.
Set Day Override using + or — buttons (12 is recommended):
• set number of days between regeneration (1 to 28); or
• set to “OFF”.
Press
NEXT to go to step 4. Press
REGEN if you need to return to the previous step.
1 2 3
7
2. Programming cont’d:
STEP 4 – REGENERATION HOUR: The manufacturer has factory set 2:00 A.M. as the default. This is the hour of day for regeneration and can be reset by using + or — buttons. “AM/PM” toggles after 12. The default time is 2:00 a.m. (recommended for a normal household).
Press NEXT to go to step 5. Press REGEN if you need to return to the previous step.
STEP 5 – REGENERATION MINUTES: Set the minutes using + or — buttons. Press
NEXT to exit installer programming. Press REGEN if you need to return to the previous step. To initiate an immediate manual regeneration, press and hold the REGEN button for three seconds.
The system will begin to regenerate immediately. The control may be manually stepped through the regeneration cycles by pressing REGEN .
4 5
OPERATING DISPLAYS AND INSTRUCTIONS:
1. GENERAL OPERATION: When the system is operating, one of three displays may be shown. Pressing NEXT will alternate between the displays. One of the displays is always the current time of day. The second display shows the current treated water flow rate through the system in Gallons Per
Minute. The third display is one of the following: days remaining or volume remaining. Days remaining is the number of days left before the system goes through a regeneration cycle. Capacity remaining is the gallons that will be treated before the system goes through a regeneration cycle. The user can scroll between the displays as desired.
GENERAL OPERATION DISPLAYS
If the system has called for a regeneration that will occur at the preset time of regeneration, the words “REGEN
TODAY” will appear on the display.
If a water meter is installed, the word “Softening” or “Filtering” flashes on the display when water is being treated (i.e. water is flowing through the system).
2. REGENERATION MODE: Typically a system is set to regenerate at a time of no water use. If there is a demand for water when the system is regenerating, untreated water will be delivered. When the system begins to regenerate, the display will change to include information about the step of the regeneration process and the time remaining for that step to be completed. The system runs through the steps automatically and will reset itself to provide treated water when the regeneration has been completed.
8
REGENERATION
MODE
3. MANUAL REGENERATION: Sometimes there is a need to regenerate before the control valve calls for it. This may be needed if a period of heavy water use is anticipated or when the system has been operated without salt.
• To initiate a manual regeneration at the next
preset regeneration time, press and release
REGEN . The words “REGEN TODAY” will flash on the display to indicate that the system will regenerate at the next regeneration time (set in
Programming, steps 4 and 5). If you pressed the
REGEN button in error, pressing the button again will cancel the command.
• To initiate a manual regeneration immediately, press and hold the REGEN button for three seconds. The system will begin to regenerate immediately. This command cannot be cancelled.
MANUAL REGENERATION
Once a manual regeneration is initiated, the unit will go into the FILL position. This position allows water to enter the brine tank until it reaches the proper level. Once this position is complete, you will notice a 240
Minute (4 hours) SOFTENING position. This 4-hour window allows the salt to dissolve and achieve proper brine strength. During these FILL and SOFTENING positions, you will have softened water available for use. Once the unit advances to the BACKWASH position and subsequent positions thereafter (see Start Up
Instructions for regeneration sequence), the water softener will deliver water, but it will be untreated.
IMPORTANT: With the Dry Salt Storage Feature, the brine tank will refill 4 hours before the actual regeneration occurs. You may experience a small amount of noise for a short period of time at 10:00 p.m.
(with typical setting) on the night that regeneration is to occur. This noise is only the brine tank filling and at no time during this process will you be without treated water.
4. POWER LOSS AND BATTERY REPLACEMENT:
The AC transformer comes with a 15 foot power cord and is designed for use with the control valve; the transformer should only be used in a dry location.
In the event of a power outage that is less than 24 hours, the control valve will remember all settings and time of day. After 24 hours, the only item that needs to be reset is the time of day and will be indicated by the time of day flashing. All other settings are permanently stored in the nonvolatile memory.
If a power loss occurs that is less than 24 hours and the time of
day flashes, this indicates that the battery is depleted. The time of day should be reset and the non-rechargeable battery should be replaced. The battery is a 3 Volt Lithium Coin Cell type 2032 and is readily available at most stores. To access battery location, remove front cover (see diagram on page 14 for battery location).
BATTERY REPLACEMENT
9
5. ERROR MESSAGE: If the word “ERROR” and a number are alternately flashing on the display record the number and contact the dealer for help. This indicates that the control valve was not able to function properly.
ERROR
6. BRINE TANK MAINTENANCE AND SALT: Refill the brine tank as necessary, making sure at least 1/3 of the brine tank is full at all times. Without proper salt levels, the water softener may not operate properly.
Because “typical” settings of this water softener include a dry salt storage feature (no water in brine tank between regeneration), the manufacturer recommends the use of solar salt for best results. The brine tank is manufactured for the use of solar, pellets or rock salt. If pellet or rock salt is used, a cleaning of the brine tank every six months is recommended. If the dry salt storage feature is not being utilized, block salt may be used.
CAUTION:
The manufacturer does not recommend the use of any resin cleaners, nor placement of any resin cleaners into the brine tank. This may be harmful to the water softener and for human consumption. Consult dealer for proper cleaning instructions.
10
START-UP INSTRUCTIONS:
• After installation is complete, rotate bypass handles to bypass mode (see Fig.2 on page 4).
• Turn on water and check for leaks.
• Fully open a cold water faucet — preferably a laundry sink or bathtub without an aerator.
• Allow water to run until clear to rid pipes of debris which may have occurred during installation.
System regeneration sequence is in the following order. (If it is desired to change this sequence, please refer to the Dealer Manual or contact the manufacturer.)
1) BRINE TANK REFILL
2) 4 HOURS (240 minutes) OF SOFTENING MODE WHILE SALT IS DISSOLVING
3) BACKWASH
4) BRINE DRAW AND SLOW RINSE
5) FAST RINSE
6) END (return to service)
The system is now ready for filling with water and for testing.
1. With the softener in the bypass mode (Fig. 2 on page 4) and the control valve in normal operation where the display shows either the time of day or the gallons remaining, manually add 3" of water to the regenerant tank.
NOTE: If too much water is put into the brine tank during softener start up, it could result in a
“salty water” complaint after the first regeneration.
During the first regeneration the unit will draw out the initial volume of brine/regenerant and refill it with the correct preset amount.
2. With the softener in bypass mode, press and hold the REGEN button until the motor starts. Release button.
The display reads “FILL” and the remaining time in this step is counting down. Since the regenerant tank was already filled in Step 1 press REGEN again and the display will read SOFTENING 240 (During a full regeneration this will be a 4 hour period for salt to dissolve). Press REGEN again to put the valve into
“BACKWASH.” Once valve has stopped in position, unplug the transformer so that the valve will not cycle to the next position. Open the inlet handle of the bypass valve very slightly allowing water to fill the tank slowly in order to expel air.
CAUTION: If water flows too rapidly, there will be a loss of media to the drain.
3. When the water is flowing steadily to the drain without the presence of air, slowly open the inlet valve.
Restore power and momentarily press the REGEN button to advance the control to the “BRINE” position.
4. The bypass is now in the diagnostic mode (Fig. 3 on page 4). Check to verify that water is being drawn from regenerant tank with no air leaks or bubbles in the brine line. There should be a slow flow to the drain.
5. Momentarily press REGEN again until the display reads “RINSE.” There should be a rapid flow to the drain. Unplug transformer to keep the valve in the “RINSE” position. Allow to run until steady, clear and without air. While the unit is rinsing, load the brine tank with water softener salt (refer to
page 9, Brine Tank Maintenance and Salt). Restore power.
6. Place bypass valve in the normal operating mode (Fig. 1 on page 4) by opening the outlet bypass handle. Press
REGEN and the unit will return to the service position with time of day being displayed.
11
TROUBLESHOOTING GUIDE:
PROBLEM
1. No display on
PC board
2. PC board does not display correct time of day
4. Control valve regenerates at wrong time of day
CAUSE
A. No power at electric outlet
B. Control valve power adapter not plugged into outlet or power cord end not connected to PC board connection
C. Improper power supply
D. Defective power adapter
E. Defective PC board
A. Power adapter plugged into electric outlet controlled by light switch
B. Tripped breaker switch and/or tripped GFI
C. Power outage
D. Defective PC board
A. Bypass valve in bypass position
3. Display does not indicate that water is flowing. Refer to user instructions for how the display indicates water is flowing.
B. Meter is not connected to meter connection on
PC board
C. Restricted/stalled meter turbine
D. Meter wire not installed securely into three pin connector
E. Defective meter
F. Defective PC board
A. Power outage
B. Time of day not set correctly
C. Time of regeneration set incorrectly
D. Control valve set at “on 0” (immediate regeneration)
E. Control valve set at “NORMAL + on 0”
(delayed and/or immediate)
5. Time of day flashes on and off
A. Power outage
6. Control valve does not regenerate automatically when the correct button(s) is depressed and held.
For timeclock valves the buttons are ▲ & ▼.
For all other valves the button is REGEN.
A. Broken drive gear or drive cap assembly
B. Broken piston rod
C. Defective PC board
CORRECTION
A. Repair outlet or use working outlet
B. Plug power adapter into outlet or connect power cord end to PC board connection
C. Verify proper voltage is being delivered to
PC board
D. Replace power adapter
E. Replace PC board
A. Use uninterrupted outlet
B. Reset breaker switch and/or GFI switch
C. Reset time of day. If PC board has battery back up present the battery may be depleted.
See front cover and drive assembly drawing for instructions.
D. Replace PC board
A. Turn bypass handles to place bypass in service position
B. Connect meter to three pin connection labeled
METER on PC board
C. Remove meter and check for rotation or foreign material
D. Verify meter cable wires are installed securely into three pin connector labeled METER
E. Replace meter
F. Replace PC board
A. Reset time of day. If PC board has battery back up present the battery may be depleted.
See front cover and drive assembly drawing for instructions.
B. Reset to correct time of day
C. Reset regeneration time
D. Check programming setting and reset to
NORMAL (for a delayed regen time)
E. Check programming setting and reset to
NORMAL (for a delayed regen time)
A. Reset time of day. If PC board has battery back up present the battery may be depleted.
See front cover and drive assembly drawing for instructions.
A. Replace drive gear or drive cap assembly
B. Replace piston rod
C. Defective PC board
12
PROBLEM
A. Bypass valve in bypass position
7. Control valve does not regenerate automatically but does when the correct button(s) is depressed and held. For timeclock valves the buttons are ▲ & ▼.
For all other valves the button is REGEN.
B. Meter is not connected to meter connection on
PC board
C. Restricted/stalled meter turbine
D. Incorrect programming
E. Meter wire not installed securely into three pin connector
F. Defective meter
G. Defective PC board
A. Bypass valve is open or faulty
B. Media is exhausted due to high water usage
8. Hard or untreated water is being delivered
9. Control valve uses too much regenerant
B. Improper program settings
C. Control valve regenerates frequently
10. Residual regenerant being delivered to service
11. Excessive water in regenerant tank
CAUSE
C. Meter not registering
D. Water quality fluctuation
E. No regenerant or low level of regenerant in regenerant tank
F. Control fails to draw in regenerant
G. Insufficient regenerant level in regenerant tank
H. Damaged seal/stack assembly
I. Control valve body type and piston type mix matched
J. Fouled media bed
A. Improper refill setting
A. Low water pressure
B. Incorrect injector size
C. Restricted drain line
A. Improper program settings
B. Plugged injector
C. Drive cap assembly not tightened in properly
D. Damaged seal/stack assembly
E. Restricted or kinked drain line
F. Plugged backwash flow controller
G. Missing refill flow controller
CORRECTION
A. Turn bypass handles to place bypass in service position
B. Connect meter to three pin connection labeled
METER on PC board
C. Remove meter and check for rotation or foreign material
D. Check for programming error
E. Verify meter cable wires are installed securely into three pin connector labeled METER
F. Replace meter
G. Replace PC board
A. Fully close bypass valve or replace
B. Check program settings or diagnostics for abnormal water usage
C. Remove meter and check for rotation or foreign material
D. Test water and adjust program values accordingly
E. Add proper regenerant to tank
F. Refer to Troubleshooting Guide number 12
G. Check refill setting in programming. Check refill flow control for restrictions or debris and clean or replace
H. Replace seal/stack assembly
I. Verify proper control valve body type and piston type match
J. Replace media bed
A. Check refill setting
B. Check program setting to make sure they are specific to the water quality and application needs
C. Check for leaking fixtures that may be exhausting capacity or system is undersized
A. Check incoming water pressure – water pressure must remain at minimum of 25 psi
B. Replace injector with correct size for the application
C. Check drain line for restrictions or debris and clean
A. Check refill setting
B. Remove injector and clean or replace
C. Retighten the drive cap assembly
D. Replace seal/stack
E. Check drain line for restrictions or debris and or unkink drain line
F. Remove backwash flow controller and clean or replace
G. Replace refill flow controller
13
TROUBLESHOOTING GUIDE cont’d:
PROBLEM
12. Control valve fails to draw in regenerant
13. Water running to drain
14. E1, Err – 1001,
Err – 101 =
Control unable to sense motor movement
15. E2, Err – 1002, Err –
102 = Control valve motor ran too short and was unable to find the next cycle position and stalled
CAUSE
A. Injector is plugged
B. Faulty regenerant piston
C. Regenerant line connection leak
D. Drain line restriction or debris cause excess back pressure
E. Drain line too long or too high
F. Low water pressure
A. Power outage during regeneration
CORRECTION
A. Remove injector and clean or replace
B. Replace regenerant piston
C. Inspect regenerant line for air leak
D. Inspect drain line and clean to correct restriction
E. Shorten length and or height
F. Check incoming water pressure – water pressure must remain at minimum of 25 psi
A. Upon power being restored control will finish the remaining regeneration time. Reset time of day. If PC board has battery back up present the battery may be depleted. See front cover and drive assembly drawing for instructions.
B. Replace seal/stack assembly
C. Replace piston assembly
D. Retighten the drive cap assembly
B. Damaged seal/stack assembly
C. Piston assembly failure
D. Drive cap assembly not tightened in properly
A. Motor not inserted full to engage pinion, motor wires broken or disconnected
B. PC board not properly snapped into drive bracket
C. Missing reduction gears
A. Disconnect power, make sure motor is fully engaged, check for broken wires, make sure two pin connector on motor is connected to the two pin connection on the PC board labeled
MOTOR. Press NEXT and REGEN buttons for
3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
B. Properly snap PC board into drive bracket and then Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
C. Replace missing gears
A. Foreign material is lodged in control valve
B. Mechanical binding
C. Main drive gear too tight
D. Improper voltage being delivered to PC board
A. Open up control valve and pull out piston assembly and seal/stack assembly for inspection. Press NEXT and REGEN buttons for
3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
B. Check piston and seal/stack assembly, check reduction gears, check drive bracket and main drive gear interface. Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
C. Loosen main drive gear. Press NEXT and
REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
D. Verify that proper voltage is being supplied.
Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for
5 seconds and then reconnect.
14
PROBLEM CAUSE
A. Motor failure during a regeneration
16. E3, Err – 1003, Err –
103 = Control valve motor ran too long and was unable to find the next cycle position
B. Foreign matter built up on piston and stack assemblies creating friction and drag enough to time out motor
C. Drive bracket not snapped in properly and out enough that reduction gears and drive gear do not interface
17. E4, Err – 1004, Err –
104 = Control valve motor ran too long and timed out trying to reach home position
A. Drive bracket not snapped in properly and out enough that reduction gears and drive gear do not interface
A. Control valve programmed for ALT A or B, nHbP, SEPS, or AUX MAV with out having a MAV or NHBP valve attached to operate that function 18. Err -1006, Err – 106,
Err - 116 = MAV/
SEPS/ NHBP/ AUX
MAV valve motor ran too long and unable to find the proper park position
B. MAV/NHBP motor wire not connected to
PC board
Motorized Alternating
Valve = MAV
Separate Source = SEPS
No Hard Water Bypass =
NHBP
Auxiliary MAV = AUX
MAV
C. MAV/NHBP motor not fully engaged with reduction gears
D. Foreign matter built up on piston and stack assemblies creating friction and drag enough to time out motor
19. Err – 1007, Err – 107,
Err - 117 = MAV/
SEPS/NHBP/AUX
MAV valve motor ran too short (stalled) while looking for proper park position
A. Foreign material is lodged in
MAV/NHBP valve
Motorized Alternating
Valve = MAV
Separate Source = SEPS
No Hard Water Bypass =
NHBP
Auxiliary MAV = AUX
MAV
B. Mechanical binding
CORRECTION
A. Check motor connections then Press NEXT and
REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
B. Replace piston and stack assemblies. Press
NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
C. Snap drive bracket in properly then Press
NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
A. Snap drive bracket in properly then Press
NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
A. Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for
5 seconds and then reconnect. Then reprogram valve to proper setting
B. Connect MAV/NHBP motor to PC board two pin connection labeled DRIVE. Press NEXT and
REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
C. Properly insert motor into casing, do not force into casing Press NEXT and REGEN buttons for
3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
D. Replace piston and stack assemblies. Press
NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
A. Open up MAV/NHBP valve and check piston and seal/ stack assembly for foreign material.
Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for
5 seconds and then reconnect.
B. Check piston and seal/stack assembly, check reduction gears, drive gear interface, and check MAV/NHBP black drive pinion on motor for being jammed into motor body.
Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for
5 seconds and then reconnect.
15
REPLACEMENT PARTS:
4
5
2
3
6
7
Item No.
1
FRONT COVER AND DRIVE ASSEMBLY
Part No.
Description
CV3540-A
CV3540-W-A
Black Impression ® cover
Gray Impression ® cover
CV3540P-A Black Impression Plus ® cover
CV3540P-W-A Gray Impression Plus ® cover
CV3107-1
CV3106-1
CV3579WI
CV3110
CV3109
Motor
Drive bracket & spring clip
PC board, CC
Drive gear, 12 x 36
Drive gear cover
CV3002CC
CV3186
CV3543
Drive assembly, CC
Transformer, 110V-12V
Optional weather cover
Qty.
1
3
1
1
1
1
1
1
1
1
-
1
NOTE: Battery Location
1
4
5
6
3
7
2
16
REPLACEMENT PARTS:
1
13
14
5
4 7 9
3
2 8
10
11
9
10
11
12
7
8
5
6
Item No.
1
2
3
4
13
13
14
Part No.
PISTON ASSEMBLY
Description
CV3005
CV3430
CV3004
CV3135
1" spacer stack assembly
1.25" spacer stack assembly
Drive cap assembly
O-ring 228
CV3011 1" piston assembly downflow
CV3011-01 1" piston assembly upflow
CV3407
CV3174
1.25" piston assembly downflow
Regenerant piston
CV3180
CV3105
O-ring 337
O-ring 215
CV3556 Screw, 1/4 - 20x1-1/2 18-8SS
CCI-00318337 Nut, 1/4 - 20 HEX 18-8SS
CV3016
CV3452
QC2 clamp assembly (includes screw & nut)
O-ring 230
CV3015 WS1 QC2 Tank adapter assembly (includes O-rings)
CV3001-04 1" body assembly downflow
CV3001-04UP 1" body assembly upflow
CV3001 1" body assembly downflow
CV3001UP 1" body assembly upflow
CV3020 1.25" body assembly downflow
CV3541 Drive backplate
17
Qty.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
12
6
7
NOTE: For Impression Plus
®
Models only. Not
available
For Impression Plus ® Models Only
REPLACEMENT PARTS:
Item No.
5
6
7
8
9
10
1
2
3
4
BYPASS VALVE
Part No.
CV3151
CV3150
CV3105
CV3145
CV3146
CV3147
CV3148
CV3152
CV3155
CV3156
Description
Nut, 1" quick connect
Split ring
O-ring 215
Bypass rotor, 1"
Bypass cap
Bypass handle
Bypass rotor seal retainer
O-ring 135
O-ring 112
O-ring 214
Qty.
2
2
2
2
2
2
2
2
2
2
18
REPLACEMENT PARTS:
INJECTOR ASSEMBLIES
Item No.
3
2
1
4
5
not shown not shown
Part No.
CV3170
CV3171
Description
CV3176
CV3152
Injector cap
O-ring 135
CV3177-01 Injector screen
CV3010-1Z Injector assembly plug
CV3010-1A A injector assembly,
BLACK
CV3010-1B B injector assembly, BROWN
CV3010-1C C injector assembly, VIOLET
CV3010-1D D injector assembly, RED
CV3010-1E E injector assembly,
WHITE
CV3010-1F F injector assembly,
BLUE
CV3010-1G G injector assembly, YELLOW
CV3010-1H H injector assembly, GREEN
CV3010-1I
CV3010-1J
I injector assembly,
J injector assembly,
ORANGE
LIGHT BLUE
CV3010-1K K injector assembly,
LIGHT GREEN
O-ring 011, lower
O-ring 013, upper
Qty.
1
1
1
1
1
*
*
* The injector plug and the injector each use one lower and one upper o-ring
Item No.
4
3
2
1
6
5
BRINE ELBOW ASSEMBLY
Part No.
Description
CV3195-01 Refill port plug assembly
CH4615 Elbow locking clip
CS1197 Tube insert, 3/8"
CJCPG-6PBLK Nut, 3/8"
CH4613 Elbow cap, 3/8"
CV3163 O-ring 019
Qty.
1
1
1
1
1
1
19
REPLACEMENT PARTS:
DRAIN LINE ASSEMBLY 3/4"
Item No.
Part No.
Description Qty.
3
4
1
2
5
6
7
CH4615
CPKP10TS8-BULK
CV3192
CV3158-01
CV3163
CV3159-01
CV3162-007
CV3162-010
CV3162-013
CV3162-017
CV3162-022
CV3162-027
CV3162-032
CV3162-042
CV3162-053
Elbow locking clip
Optional insert, 5/8" tube
Optional nut, 3/4" drain elbow
Drain elbow, 3/4" NPT with O-ring
O-ring 019
DLFC retainer assembly
0.7 DLFC for 3/4" elbow
1.0 DLFC for 3/4" elbow
1.3 DLFC for 3/4" elbow
1.7 DLFC for 3/4" elbow
2.2 DLFC for 3/4" elbow
2.7 DLFC for 3/4" elbow
3.2 DLFC for 3/4" elbow
4.2 DLFC for 3/4" elbow
5.3 DLFC for 3/4" elbow
1
1
1
1
1
1
1
8 CV3331 Drain elbow and retainer assembly
Items 2 and 3, nut and insert are only used with 1/2" I.D.
by 5/8" O.D. polytubing. For other piping material, the
3/4" NPT is used.
3/4" NPT
Proper DLFC orientation directs water flow towards the washer face with rounded edge and lettering.
Water
Flow
20
REPLACEMENT PARTS:
Item No.
3
4
1
2
5
6
WATER METER & METER PLUG
Part No.
CV3151
CV3003
CV3118-01
CV3105
CV3003-01
CV3013
Description
Nut, 1" QC
Meter assembly, includes items 3 & 4
Turbine assembly
O-ring 215
Meter plug assembly
Optional mixing valve
Qty.
1
1
1
1
1
1
SERVICE WRENCH - CV3193-02
Although no tools are necessary to assemble or disassemble the valve, the Service Wrench,
(shown in various positions on the valve) is available to aid in assembly or disassembly.
21
REPLACEMENT PARTS:
BRINE TANK ASSEMBLY
Item No.
Part No.
Description
1
2
3
CG2191- 84
CG2180
CH1072-01
CH1080
Brine tank cover, injection molded WR
Brine tank cover, standard
Optional 18" diameter salt grid
Optional 24" diameter salt grid
CG21833CB1C00 18" x 33" brine tank, black
CG21840CB1C00 18" x 40" brine tank, black
CG22441CB1C00 24" x 41" brine tank, black
4
5
6
7
8
9
10
CH1030-27
CH1030-34.5
CH1018
CH4500-48
CH4640-32
CH4600-50
CH7016
CH4626
4" x 27" brine well (18 x 33 BT)
4" x 34.5" brine well (18 x 40, 24 x 40 BT’s)
2 piece overflow set
474 air check assembly, 1/2" x 48"
474 float assembly, 32" w/ 2 grommets
474 safety brine valve w/ .5 gpm glow control
Cap 4" brine well
Nut safety brine valve stand off
ASSEMBLIES
CH4700-27WR-1 .5 gpm safety float assembly, 18" x 33"
11
CH4700-34.5WR-1 .5 gpm safety float assembly, 18" x 40"
1
Qty.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
5
2
3
4
1
Item No.
1
2
3
4
5
6
SAFETY FLOAT BRINE ELBOW
Part No.
CH4655
CV3163
CH4613
CH4612
CH4615
CJCPG-5PBLK
CJCPG-8PBLK
FP10332
Description
474 .5 gpm flow control
O-Ring 019
3/8" elbow cap
1/2" elbow cap
Elbow locking clip
3/8" compression nut
1/2" compression nut
Poly tube insert
6
3
Qty.
1
1
1
1
1
1
1
1
22
10
6
5
4
7
11
9
8
REPLACEMENT PARTS:
Item No.
1
2
3
CABINET BRINE TANK ASSEMBLY
Part No.
Description
CG 2197-01 Salt and tank cover (must be ordered together
CG2724HP-01 Windsor cabinet, white with black lids
CH1090-01
CH1090-02
Optional salt grid for 8" diameter tank and 4" brine well
Optional salt grid for 9" diameter tank and 4" brine well
CH1090-03 Optional salt grid for 10" diameter tank and 4" brine well
Qty.
1
1
1
1
1
1
See opposite page for safety float system parts.
3
2
23
INSTALLATION FITTING ASSEMBLIES:
Item
No.
1
2
3
4
1" PVC MALE NPT ELBOW
Part No.
Description
CV3007
CV3151
CV3150
CV3105
CV3149
1" PVC male NPT elbow assembly
Nut, 1" quick connect
Split ring
O-ring 215
Fitting
Qty.
2
2
2
2
2
3
4
1
2
Item
No.
3/4" & 1" PVC SOLVENT ELBOW
Part No.
Description Qty.
CV3007- 01 3/4" & 1" PVC solvent elbow assembly 2
CV3151 Nut, 1" quick connect 2
CV3150
CV3105
CV3189
Split ring
O-ring 215
Fitting 2
2
2
3
4
1
2
Item
No.
1" BRASS SWEAT
Part No.
Description
CV3007- 02 1" brass sweat assembly
CV3151 Nut, 1" quick connect
CV3150
CV3105
CV3188
Split ring
O-ring 215
Fitting
Qty.
2
2
2
2
2
2
1
3
4
Item
No.
Part No.
3/4" BRASS SWEAT
Description
CV3007- 03 3/4" brass sweat assembly
CV3151 Nut, 1" quick connect
CV3150
CV3105
Split ring
O-ring 215
CV3188-01 Fitting
Qty.
2
2
2
2
2
1
2
3
4
Item
No.
1" PLASTIC MALE NPT
Part No.
Description
CV3007- 04 1" plastic male NPT assembly
CV3151 Nut, 1" quick connect
CV3150
CV3105
CV3164
Split ring
O-ring 215
Fitting
Qty.
2
2
2
2
2
24
2
1
3
4
Item
No.
1-1/4" PLASTIC MALE
Part No.
Description
CV3007- 05 1-1/4" plastic male assembly
CV3151 Nut, 1" quick connect
CV3150
CV3105
CV3317
Split ring
O-ring 215
Fitting
Qty.
2
2
2
2
2
1
2
3
4
Item
No.
1-1/4" & 1-1/2" BRASS SWEAT
Part No.
Description Qty.
CV3007- 09 1-1/4 & 1-1/2" brass sweat assembly 2
CV3151 Nut, 1" quick connect 2
CV3150
CV3105
CV3375
Split ring
O-ring 215
Fitting 2
2
2 3
4
1
2
Item
No.
1-1/4" & 1-1/2" PVC SOLVENT
Part No.
Description Qty.
CV3007- 07 1-1/4" & 1-1/2" PVC solvent assembly 2
CV3151 Nut, 1" quick connect 2
CV3150
CV3105
CV3352
Split ring
O-ring 215
Fitting 2
2
2
1
2
3
4
Item
No.
3/4" BRASS SHARK BITE
Part No.
Description
CV3007-12 3/4" brass Shark Bite assembly
CV3151 Nut, 1" quick connect
CV3150
CV3105
CV3628
Split ring
O-ring 215
Fitting
Qty.
2
2
2
2
2
3
4
1
2
Item
No.
1" BRASS SHARK BITE
Part No.
Description
CV3007- 13 1" brass Shark Bite assembly
CV3151 Nut, 1" quick connect
CV3150
CV3105
CV3629
Split ring
O-ring 215
Fitting
Qty.
2
2
2
2
2
1
2
3
4
Item
No.
3/4" JOHN GUEST ELBOW
Part No.
Description
CV3007-15 3/4" John Guest elbow assembly
CV3151
CV3150
Nut, 1" quick connect
Split ring
CV3105
CV3790
O-ring 215
Fitting
Qty.
2
2
2
2
2
25
SPECIFICATIONS:
CAPACITY SPECIFICATIONS
MODEL
IM-844 IM-1044 IM-1054 IM-1354 IM-1465
IM-1465-
1.25"
IM-1665
IM-1665-
1.25"
IMC-835 IMC-1035
1 Capacity:
(Grains/Lbs. NaCI)
Maximum
Medium
Minimum
25,600 @ 9.0 32,000 @ 15.0 48,800 @ 21.0 72,800 @ 24.0 91,000 @ 30.0 91,000 @ 30.0 120,000 @ 39.0 120,000 @ 39.0 21,100 @ 9.0 32,000 @ 15.0
21,600 @ 6.0 28,400 @ 9.0 44,400 @ 15.0 64,200 @ 18.0 85,500 @ 24.0 85,500 @ 24.0 107,000 @ 30.0 107,000 @ 30.0 18,000 @ 6.0
28,400 @ 9.0
15,600 @ 3.0 23,600 @ 6.0 35,400 @ 9.0 53,000 @ 12.0 70,600 @ 16.0 70,600 @ 16.0 88,000 @ 20.0 88,000 @ 20.0 13,600 @ 3.0
23,600 @ 6.0
0.85
1.0
1.5
2.5
3.0
3.0
4.0
4.0
0.66
1.0
2
Amount of Media (Cu. Ft.)
Maximum Water Hardness (GPG)
Maximum Iron (PPM)
Minimum pH Required
3 Peak Flow Rate (GPM @ P-PSI)
Continuous Flow Rate (GPM @ P-PSI)
Water Pressure Range (PSI)
Water Temp. (ºF)
Electrical Requirements (volts-hertz)
Pipe Size
Total Dimensions: Media Tank
11.4 @ 15.0
5.0 @ 5.4
25-100
33-100
110-50/60
1"
17.1 @ 15.0
14.3 @ 15.0
5.0 @ 2.8
25-100
33-100
110-50/60
1"
5.0 @ 3.8
25-100
33-100
110-50/60
1"
18.5 @ 15.0
19.0 @ 15.0
5.0 @ 2.4
25-100
33-100
110-50/60
1"
5.0 @ 1.7
25-100
33-100
110-50/60
1"
8"W X 52"H 10"W X 52"H 10"W X 62"H 13"W x 62"H 14"W x 73"H
33 @ 25.0
24 @ 15.0
25-100
33-100
110-50/60
1.25"
19.2 @ 15.0
5.0 @ 1.6
25-100
33-100
110-50/60
1"
14"W x 73"H 16"W x 73"H
36 @ 25.0
25 @ 15.0
25-100
33-100
110-50/60
1.25"
16"W x 73"H
Brine Tank 18"W X 33"H 18"W X 33"H 18"W X 33"H 18"W x 40"H 18"W x 40"H 18"W x 40"H 24"W x 41"H 24"W x 41"H
Depth
50
1.0
7
75
1.0
7
100
1.0
7
100
1.0
7
100
1.0
7
100
1.0
7
100
1.0
7
100
1.0
7
50
1.0
7
12.2 @ 15.0
5.8 @ 5.4
25-100
33-100
110-50/60
1"
13.5"W x
42.5"H
22.5"
75
1.0
7
17.1 @ 15.0
5.0 @ 2.8
25-100
33-100
110-50/60
1"
13.5"W x
42.5"H
22.5"
1 All Impression units are factory set for Medium Salting.
2 Iron removal may vary depending on form of iron, pH, and other local conditions.
3 The peak flow rates listed above do not represent the maximum service flow rate used for determining the softener capacity and efficiency ratings. Continuous operation at flow rates greater than the maximum service flow rate may affect capacity and efficiency performances.
26
Water Conditioner Limited Warranty
Congratulations. You have purchased one of the finest water treatment systems available. In the unlikely event of a problem due to defects in material and workmanship, we proudly warrant our water conditioners to the original owner, when installed in accordance with Water-Right ® from the date of original installation for: specifications. This warranty is effective
A period of TEN YEARS: Fiberglass mineral tank except for damages due to freezing, high pressure (120 PSI and above), extreme temperature
(100°F and above) or a vacuum on the system.
A period of FIVE YEARS:
A period of ONE YEAR:
The control valve and all internal components.
The salt storage container.
All other conditioner components.
Any part found defective within the terms of this warranty will be repaired or replaced by the dealer. You pay only freight from our factory and local dealer charges. To obtain local warranty service, contact original dealer or an authorized service dealer. If no authorized dealer is located in your area, please ship defective part or component freight prepaid to Water-Right, Inc., 1900 Prospect Ct., Appleton, Wisconsin 54914. Water-Right, at its discretion, will repair or replace the part or component at its expense and return part freight collect.
The above provisions of the warranty are valid as long as the unit is connected in compliance with local plumbing codes and in an equivalent manner and condition of the original installation and is owned by the original owner.
This warranty does not cover damages due to accident, fire, flood, freezing, or any other Act of God.
We are not responsible for damages due to change in water conditions, misapplication, misuse, neglect, vacuum, oxidizing agents, alteration, or lack of maintenance. No responsibility is assumed for loss of use of the unit, inconvenience, loss or damage to real or personal property or any incidental or consequential damages. Furthermore, we assume no liability and extend no warranties, express or implied, for the use of this product with a non-potable water source. To the extent permitted by law, Water-Right disclaims all implied warranties, including without limitation warranties of merchantability and fitness for particular purpose; to the extent required by law, any such implied warranties are limited in duration to the aforementioned period specified above.
Some states do not allow the exclusion of implied warranties or limitations on how long an implied warranty lasts. Consequently, the above limitation may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
27
QUICK REFERENCE GUIDE:
GENERAL OPERATION
When the system is operating, one of three displays will be shown: time of day, gallons of treated water available, or gallons per minute.
Pressing
NEXT will toggle between the three choices.
TO SET TIME OF DAY
In the event of a prolonged power outage, time of day flashes, indicating that this needs to be reset. All other information will be stored in memory no matter how long the power outage. Please complete the steps as shown to the right.
To access this mode, press SET CLOCK .
1. Accessed by pressing
SET CLOCK
2. Adjust hours with
+ and — buttons,
AM/PM toggles at 12
3. Press
NEXT
4. Adjust minutes with
+ and — buttons
5. Press
NEXT to complete and return to normal operation
MANUAL REGENERATION
NOTE: For softeners, if brine tank does not contain salt, fill with salt and wait at least two hours before regeneration. If you need to initiate a manual regeneration, either immediately, or the same night at the preprogrammed time for regeneration (typically 2:00
AM), complete the following steps.
For Immediate Regeneration:
Press and hold
REGEN until valve motor starts (typically 3 seconds).
For Regeneration the same night:
Press and release REGEN (notice that flashing “REGEN TODAY” appears).
ERROR
If the display toggles between “Error” and an error code (i.e. a number), call a service technician and report the error code.
ADJUST HARDNESS, DAYS BETWEEN REGENERATION,
OR TIME OF REGENERATION
For initial set-up or to make adjustments, please complete the steps as shown to the right. Access this mode by pressing
NEXT and + button simultaneously.
NOTE: Hardness display shows
“-nA-” if used as a filter. If other displays do not appear, refer to manual.
1. Accessed by pressing
NEXT and + button simultaneously
2. Adjust hardness using + and — buttons
3. Press
NEXT
4. Adjust days between regenerations using
+ and — buttons
5. Press NEXT
6. Adjust time of regeneration hour with + and — buttons, AM/PM toggles at 12.
7. Press
NEXT
8. Adjust time of regeneration minutes with + and — buttons
9. Press
NEXT to complete and return to normal operation.
BYPASS VALVE OPERATION
To shut off water to the system, position arrow handles as shown in the bypass operation diagram below. If your valve doesn’t look like the diagram below, contact your service technician for instructions on how to shut off water.
NORMAL OPERATION BYPASS OPERATION
1900 Prospect Court • Appleton, WI 54914
Phone: 920-739-9401 • Fax: 920-739-9406
© 2011 Water-Right, Inc. All rights reserved.
LIT-IM/IMP Man ROPU 10/11 3M
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project