Series 3100 Differential Pressure Transmitter

SUPERSEDES: April 1, 2012 EFFECTIVE: August 1, 2012

2

Table of Contents

Page

S

ection 1.0

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.1

Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.2

Overview of Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.3

Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Section 2.0

Handling Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2.1

Unpacking Transmitters and Specifications Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.2

Models and Specifications Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.3

Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.4

Selecting Installation Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.5

Calibration after Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.6

Pressure Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.7

Waterproofing Cable Conduit Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.8

Restrictions on Use of Radio Transceiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.9

Installation Resistance Test and Dielectric Strength Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.10 Explosion-Proof Transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.11 EMC Conformity Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Section 3.0

Transmitter Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3.2

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3.3

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3.4

Fail Mode Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3.5

EEProm-Write Enable/Disable Mode Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3.6

Configuration of Alarm and Security Jumper Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3.7

Configuration of Zero and Span Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.8

Commissioning on the Bench with HHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Section 4.0

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.2

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.3

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.4

Commissioning on the Bench with Hand-Held Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.5

General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.6

Electrical Considerations (Power Supply) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.7

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.8

Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

4.9

Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Section 5.0

On-line Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

5.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

5.2

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

5.3

Configuration Data Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

5.4

Configuration Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

5.5

Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

5.6

Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

5.7

Configuration Variables Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

5.8

Diagnostics and Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

5.9

Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Section 6.0

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

6.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

6.2

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

6.3

Hardware Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

6.4

Hardware Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Appendix 1 3100 Smart Pressure Transmitter LCD Display Code

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

3

1. INTRODUCTION:

The 3100 Smart Pressure Transmitter is calibrated at the factory before shipping. To ensure correct and efficient use of the instrument, please read the manual thoroughly and fully understand how to operate the instrument before operation.

The contents of this manual are subject to change without prior notice.

All rights are reserved. No part of this manual may be reproduced in any form without the written permission of Taco, Inc.

If any question arises, errors are found or if any information is missing from this manual, please inform Taco, Inc.

The specifications covered by this manual are limited to standard transmitters and do not cover custom-made instruments.

Please note that changes in the specifications, construction, or component parts of the instrument may not immediately be reflected in this manual at the time of change, provided that postponement of revisions will not cause difficulty to the user from a functional or performance standpoint.

1.1 Using This Manual:

The operating manual provides information on installing, operating, and maintaining the Taco Model 3100 Smart Pressure

Transmitter. The sections are organized as follows:

Section 2 – Handling Cautions

Section 2 provides instructions on commissioning and operating the Model 3100 Smart Pressure Transmitters. Informations on software functions, configuration parameters, and on-line variables are also included.

Section 3 – Transmitter Functions

Section 3 contains suggestions on handling the Model 3100

Smart Pressure Transmitter.

Section 4 – Installation

Section 4 contains mechanical, environment consideration and electrical installation instructions for the Model 3100 Smart

Pressure Transmitter.

Section 5 – On-line Operation

Section 5 describes how to configure the parameters of the

Model 3100 Smart Pressure Transmitter. See the following list for the details.

1. Regulations for circuit's Input/Output characteristics; Sensor or Output Trim

2. Changing the output characteristic; Range Configuration,

Output Type, Dampening, Unit

3. Changing the general data; Tag No., Date, Message etc.

Section 6 – Maintenance

Section 6 contains hardware diagnostics, troubleshooting and maintenance tasks.

1.2 Overview of Transmitter:

The Taco Smart Pressure Transmitter is a microprocessor based pressure transmitter with a capacitance sensor optimized for draft measurement. The Model 3100 has a true draft analog range from

0 to 20 mA. This transmitter is explosion-proof, high precision accuracy, reliability and has digital communication for remote communication system.

The Model 3100 is enabled with HART ® communication with Host,

HHT (HART ® Communicator) or PC Configurator. The transmitter’s various variables in host are able to be changed, configured and calibrated by users. The HART ® Communication between DC power supply and transmitter requires a 250 - 550 Ohm resistance.

1.3 Software Compatibility:

The Taco Smart Pressure Transmitter's software is implemented at the factory. The following functions can be configured using a

HHT (Hart ® Communicator).

FUNCTION

ZERO/SPAN

ZERO/TRIM

ZERO Adj

Units set

Range set

Dampening set

LCD decimal set

• – Supported

FUNCTION SUPPORTS

ZERO/SPAN

Button PC/PDA

HART

HHT

Rev. 58

– Supported but update required

2. HANDLING CAUTIONS:

This section consists of cautions for transmitter handling, storage, installation, insulation and explosion structure, etc.

JOB

Unpacking

JOB DETAILS

• Unpack transmitter packing.

INSTRUMENT

Model and

Specifications

Storage

• Make sure the transmitter nameplate matches the model number on the P.O.

• In a dry, non-vibration and non-impact area.

• Ambient temperature around 77°F (25°C) and 65% relative humidity.

Calibration

Installation

Locations

Mechanical

Considerations

• Configuration of the Range, Zero/Span,

Unit, Tag, Dampening Time, Transfer

Function, DA Trim and other parameters.

• Where ambient temperature is constant.

• Exposure to chemical corrosion, etc.

• Where shock and vibration are minimal.

• Where the area classification does not exceed the explosion-proof rating.

• Where maintenance is easy.

• Where the transmitter can be handled easily.

• Be cautious of process connections leaking.

Electrical

Considerations

• 24 VDC

(Power Supply is 11.9 VDC - 45 VDC).

• For HART ® communication, resistance on transmitter terminal loop should be between 250 -550 ohms.

Mounting and

Installation

Calibration on

Spot

Pressure

• When mounting the transmitter, an appropriate bracket should be used.

• The transmitter should be mounted securely to prevent swing.

• Sensor Zero Trim should be done ten seconds after differential pressure stabilizes.

• Make sure that PV value is zero and current is 4 mA.

• Do not apply a regulated differential pressure and line pressure.

• Close the equalizing valve on the 3 valve manifold and then open the valve on high and low side slowly and simultaneously.

HHT

Pressure Source

Galvanometer

(Engineering)

(Engineering)

(Engineering)

(Mounting and

Installation)

HHT or

Zero/Span

Button

(Applying

Pressure)

Operation • Make sure the instrument operates properly.

Eye or HHT

HART

®

is a registered Trademark of Hart

Communication Foundation.

4

2.1 Unpacking Transmitters:

When moving the transmitter to the installation site, keep it in the original packaging. Unpack the transmitter at the installation site to avoid damage on the way.

2.2 Model and Specifications Check:

The model number and specifications are indicated on the nameplate. Please check the specification and model number.

2.3 Storage:

The following precautions must be observed when storing the instrument, especially for a long period of time.

1. Select a storage area that meets the following conditions:

- is not exposed to rain or water

- minimal vibration and shock

- stored at normal temperature and humidity

(approx. 77°F (25°C), 65% RH)

The ambient temperature and relative humidity ratings are:

- Ambient Temperature:

-40 to 185°F (-40 to 85°C) (without LCD module)

-22 to 176°F (-30 to 80°C) (with LCD module)

- General Use: -4 to 140°F (-20 to 60°C)

- Relative Humidity: 5% - 98% RH at 104°F (40°C)

2. When storing the transmitter, repack it the way it was delivered from the factory.

3. If storing a used transmitter, thoroughly clean the diaphragm surfaces, so that no media remains. Make sure the transmitter assemblies are securely mounted before storing.

2.4 Selecting Installation Locations:

The transmitter is designed to withstand severe environmental conditions. However, to ensure stable and accurate operation, the following precautions must be observed when selecting an installation location.

1. Ambient Temperature

Avoid locations subject to wide temperature variations or a significant temperature gradient. If the location is exposed to radiant heat from plant equipment, provide adequate insulation or ventilation.

2. Ambient Atmosphere

Avoid installing the transmitter in a corrosive atmosphere. If the transmitter must be installed in a corrosive atmosphere, there must be adequate ventilation. Precautions must be put into place to prevent intrusion or stagnation of rainwater in conduits.

3. Shock and Vibration

Select an installation site with minimum shock and vibration

(although the transmitter is designed to be relatively resistant to shock and vibration).

4. Installation of Explosion-Proof Transmitters

Explosion-Proof transmitters can be installed in hazardous areas according to the gas types for which they are certified.

5. Select a place where the transmitter can be maintained easily.

2.5 Calibration after Installation:

Sensor Zero Trim should be done after transmitter is installed, because the zero point is not configured for mounting status.

When calibrating the Sensor Zero Trim apply a pressure for zero in advance, Sensor Zero Trim the sensor when the pressure is sufficiently stabilized (after approximately 10 seconds).

There are two ways to pressure zero. One way is to apply zero differential pressure (making pressure the same on both the high and low side). The other is to close High and Low side of a 3 valve manifold and open the equalizing valve.

Sensor Zero Trimming can also be done with the Zero/Span button or a HHT (HART ® Communicator), PC or PDA configurator.

Refer to On-line Operation for configuring other parameters.

2.6 Pressure Connections:

CAUTION: Instrument installed in the process under pressure. Never loosen or tighten as it may cause dangerous spouting of process fluid. If the process fluid is toxic or otherwise harmful, take appropriate care to avoid contact or inhalation of vapors even after disconnecting the instrument from process line for maintenance.

The following precautions must be observed in order to safely operate the transmitter under pressure.

1. Never apply a pressure higher than the specified maximum working pressure.

2. Confirm the option pressure of transmitter. It is necessary to use standardized and quality-approved parts.

3. There should be isolation valves in case of leakage.

2.7 Waterproofing Cable Conduit Connections:

Apply a non-hardening sealant (silicone or tape, etc.) to the threads to waterproof the transmitter cable conduit connections.

2.8 Restrictions on Use of Radio Transceivers:

WARNING: Although the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the transmitters external wiring, the transmitter may be affected by high frequency noise pickup. To test for such effects, bring the transceiver in slowly from a distance of several feet from the transmitter, and observe the measurement loop for noise effects.

Always use the transceiver outside the area affected by noise.

2.9 Installation Resistance Test and Dielectric Strength Test:

Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory, normally these tests are not required. However, if required, observe the following precautions in the test procedures.

1. Do not perform such tests more frequently than necessary. Even test voltages, that do not cause visible damage to the insulation, may degrade the insulation and reduce safety margins.

2. Never apply a voltage exceeding 500VDC for the insulation resistance test, or a voltage exceeding 500VAC for the dielectric strength test.

3. Before conducting these tests, disconnect all signal lines from the transmitter terminals. Perform the tests in the following procedures.

2.9.1 Insulation Resistance test:

1. Short-circuit the + and - SUPPLY terminals in the terminal box.

2. Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead-wire to the shorted SUPPLY terminals and the minus (-) lead wire to the grounding terminal.

3. Turn ON the insulation tester power and measure the insulation resistance. The voltage should be applied briefly to verify that insulation resistance is at least 20M

Ω.

4. After completing the test and being very careful not to touch exposed conductors, disconnect the insulation tester and connect a 100kW resistor between the grounding terminal and the short-circuiting SUPPLY terminals. Leave this resistor connected at least three seconds to discharge any static potential. Do not touch the terminal while it is discharging.

2.9.2 Dielectric Strength Test:

1. Short-circuit the + and - SUPPLY terminals in the terminal box.

2. Turn off the dielectric strength tester. Then connect the tester between the shorted SUPPLY terminal and the grounding ter-

5

minal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal.

3. Set the current limit on the dielectric strength tester to 10 mA, then turn on the power and gradually increase the tester voltage from ‘0’ to the specified voltage.

4. When the specified voltage is reached, hold it for one minute.

5. After completing this test, slowly decrease the voltage to avoid any voltage surges.

2.10 Explosion-Proof Rating:

2.10.1 FM Certification:

HAZARDOUS LOCATION ELECTRICAL EQUIPMENT

• Equipment Rating: Explosion-Proof for use in Class I,

Division 1, Groups A, B, C and D

• Dust- Ignition-Proof for Class II/III, Division 1, Groups E, F and G

• Nonincensive for use in Class I, Division 2, Groups A, B, C and D

• Suitable for use in Class II, Division 2, Groups E, F and G and Suitable for Class III, Division 1

• Hazardous (classified) location, indoor and outdoor (NEMA

Type 4X/IP67)

2.10.2 DEKRA/ATEX Certification:

• ATEX Certification number: DEKRA 11ATEX0192X

• CE 0344 II 2 G

3. Housing Ground must be followed to “local electrical codes”.

The most efficient ground procedure is to connect directly to the earth as least impedance.

4. How to install Housing Ground:

• Internal Ground Connection – Internal ground connection screw is located in terminal in housing. The screw can be identified as ground sign.

• External Ground Assembly – This is located in the right side of housing and identified by ground sign (grounding with a cable lug).

5. When use tubing, stopping boxes must be connected with the wall of housing directly.

6. Tubing is installed a minimum of 5 threads.

7. Sensor is to be threaded a minimum of 7 threads and prevented from turning by tightening the housing rotation set screw.

8. Do not disassemble flameproof joints but in an unavoidable case to disassemble it or need the specification of flameproof joints, contact the manufacturer before doing.

NOTICE

Operation

WARNING: Do not open when an explosive atmosphere may be present.

Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous location.

NOTICE

Model 3100 for Potentially Explosive Atmosphere

• d IIC T6...T4

• Operating Temperature: -20°C

≤ T amb

• T6 for process

≤ 85°C

≤ +60°C

• T5 for process ≤ 100°C

• T4 for process

≤ 130°C

NOTICE

Electrical Data

• Supply Voltage: 42 VDC Max

• Output Signal: 4 to 20 mA + HART

NOTICE

Maintenance and Repair

The instrument modification or parts replacement by other than authorized representative of Taco, Inc. is prohibited and will void

KEMA/ATEX explosion-proof/flame-proof.

2.11 EMC Conformity Standards:

• EMI (Emission): EN55011

• EMS (Immunity): EN50082-2

Taco, Inc. recommends customer use metal conduit wiring or twisted pair shield cable for signal wiring to conform with EMC regulation when installing the Taco 3100 transmitters.

NOTICE

Electrical Connection

• 2 x 1 ⁄

2

-14 NPT Female

NOTICE

3100 ATEX Certification Standards

• EN 60079-0: 2006

• EN 60079-1: 2007

NOTICE

Installation

1. All wiring shall comply with local installation requirement.

2. The cable glands and blanking elements shall be of a certified flameproof type, suitable for the condition of use and correctly installed. Also those devices should be endured at the 130°C.

3. TRANSMITTER FUNCTIONS:

3.1 Overview:

This section contains information on operating the Model 3100.

Tasks that should be performed on the bench prior to installation are explained in this section.

3.2 Safety Messages:

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Potential safety issues are indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.

3.3 Warning:

DANGER: Explosion can result in death or serious injury.

Do not remove the transmitter covers in explosion environments when the circuit is powered. Transmitter covers must be fully engaged to meet explosion-proof requirements.

6

WARNING: Electrical shock can result in serious injury.

Only qualified personnel can install the transmitter.

3.4 Fail Mode Alarm:

Taco Smart Pressure Transmitter automatically and continuously performs self-diagnostic test. If the self-diagnostic test detects a failure, the transmitter drives the output outside of the normal operation values. The transmitter will drive its output low (down) or high (up) based on the position of the failure mode alarm jumper. See Table 1 for output values.

Fail Mode Select

Jumber Switch

Table 1: STANDARD ALARM AND SATURATION VALUES

LEVEL

Low/Down

High/Up

4-20 mA SATURATION

3.9 mA

20.87 mA

4-20 mA ALARM

≤ 3.75 mA

≥ 21.75 mA

WARNING: Electrical shock can result in serious injury.

Avoid contact with the leads and terminals. High voltage, that may be present on leads can cause electrical shock.

Fail Safe mode can be set via Jumper switches provided on the

LCD module or the main CPU module. The jumper switch for an indicating transmitter, located on the LCD module, can be set to the right (fail down, i.e.

≤ 3.75 mA) or left (fail up, i.e. ≥ 21.75 mA).

For non-indicating transmitters the jumper switch is located on the main CPU module. It can be set up (fail up to

≥ 21.75 mA) or down (fail down to

≤ 3.75 mA). Refer to Table 2 for detailed summary of jumper settings for both CPU and LCD modules.

Table 2: CPU and LCD MODULE JUMPER SETTINGS

Select

Fail

Mode

Fail Down

Fail Up

Both LCD Module and CPU Module

CPU Module

Down

Down

Up

LCD Module

D

U

U or D

Only CPU

Module

CPU Module

D

U

Figure 1

Fail Safe Mode Selection (LCD and CPU Module)

1. WR_EN (EEPROM Write Enable)

DOWN: ENABLE

UP: DISABLE

2. Fail Mode (Alarm)

DOWN: LOW

UP: HIGH

Figure 3: Fail Mode Selection Jumper Switch for LCD Module

3.5 EEPROM - Write Enable / Disable Mode Switch:

EEPROM (Electrically Erasable Programmable ROM), included on the CPU module, is used by the transmitter to save/restore configuration variables. To protect the transmitter from any unauthorized changes, a hardware lockout feature can be implemented by using the Write-Protect mode jumper switch provided on the main

CPU Module. If the jumper switch is connected to DIS, this disables writing/changing of any data saved in the EEPROM. On the other hand, if the jumper switch is set to “EN”, changes can be made to the configuration data stored in the EEPROM. The factory default setting is “EN” (Enable) for all transmitters. The location of the Wire Protect Jumper Switch can be seen in Figure 4.

CPU Module

Jumber Switch

1) Fail Mode Selection

Figure 4: CPU Module Fail Mode

EEPROM - Write Selection Jumper Switch

The 3100 has two security settings.

1. Security Jumper - the transmitter configuration parameters are protected.

2. Physically removing Zero and Span Magnetic Buttons - you are unable to regulate zero and span locally.

3.5.1 Security Jumper (EEPROM Write Protect):

Prevents the transmitter’s configured parameters from being changed.

3.5.2 Zero and Span Buttons:

By removing the Magnetic Buttons, you can’t configure the transmitter using the Zero and Span locally.

3.6 Configuration of Alarm and Security Jumper Procedures:

Changing jumper position:

1. If the transmitter is installed, cutoff power.

2. Open the front cover. If the transmitter is powered, don’t open the cover.

3. Move the jumper to the preferred position.

4. Close the front housing covers. You must fully engage the cover to meet explosion-proof requirements.

Figure 2: Fail Mode and EEPROM - Write Selection Jumper Switch

7

3.7 Configuration of Zero and Span Procedures:

The ZERO and SPAN Buttons are under the transmitter’s nameplate. The ZERO, SPAN, ZERO TRIM, ZERO ADJ, Units, Range,

Dampening, LCD and decimal set functions are configurable using the ZERO / SPAN buttons.

3.7.1 Zero/Span Configuration Process:

Remove both nameplate screws on the upper part of transmitter.

Remove top nameplate to access the Zero and Span Buttons (see

Figure 5).

3. Moving to top menu: Zero+Span

• Press the button for 3 seconds to execute each function.

After 3 seconds press the Zero+Span buttons, the LCD display will change from Menu to Trim. To see the next menu, press the Zero button for 3 seconds. Use the Zero button to move down the directory.

• Use the Span button to select the displayed menu. The same procedure will be used for the sub menus.

The other functions supported by the ZERO / SPAN Buttons are as follows:

1. Moving between menus: Zero

2. Enter or moving to sub menu: Span

8

Zero/Span

Buttons

Figure 5: Transmitter Zero/Span Configuration Buttons

1. Zero Configurations – Set the current process value for Lower

Range Value (4 mA). Apply zero pressure for 10 seconds and push the Zero Button for 5 seconds. The LCD should display

“Zero”. Push the Zero button for 3 seconds, after 1 second the

LCD should display “-ZE-”. This message means the zero configuration is finished. If the zero configuration failed, the LCD will display “SPEr” or “SEtE”, try repeating the zero configuration steps.

2. Span Configurations – Apply the desired pressure for 10 seconds and push the Span Button for 5 seconds. The LCD should display “Span”. Push the Span button for 3 seconds, after 1 second the LCD should display “-SP-”. This message means that the span configuration is finished. If the span configuration failed the LCD will display “SPEr” or “SEtE”, try repeating the span configuration steps.

Please refer to Appendix 1 for the button error and LCD display message.

3.7.2 Menu Tree for Zero+Span Function:

CAUTION: After 30 seconds without any action, the button function will return to normal operation.

4. How to select a numerical value

(a) Functions use numerical values: 12 Zero Adjustment, 22

Change Upper Range Value, 23 Change Lower Range Value,

24 Dampening Second

(b)How to select numerical value: First, select an increasing rate

(10 n ), then change each decimal value to increase or decrease as wanted.

For example, select 3810:

Select increasing rate 1000 -> Increase 3 times ->

Select increasing rate 100 -> Increase 8 times ->

Select increasing rate as 10 -> Increase 1 time

(c) To select the increase / decrease steps: SelInc message will be displayed on the bottom of the LCD. Select parameter and press the Zero button : The decimal value will be changed when the Zero button is pressed. After set, press the span button to execute the parameter.

(d)To set the required values using Zero/Span buttons: VALUE message will be displayed on the bottom of the LCD.

1. Press the Zero button, the menu will increase 1 item.

2. Press the Span button, the menu will decrease 1 item.

3. After setting, save the parameter by pressing the

Zero+Span buttons.

(e) To set the final value, repeat (c) and (d).

(f) After setting the final parameter, exit the menu by pressing the Zero+Span buttons.

5. Exercises for each function

• ZERO TRIM

1. Access the menu by pressing the Zero+Span buttons.

2. Move to the sub directory using the Span button until the

1 TRIM message appears on the display.

3. Change the Zero Trim Function by using the Span button until the 11 Z-TRIM message appears on the display.

• ZERO ADJUSTMENT: Change the PV value to 14

1. Exit the menu by pressing the Zero+Span button.

2. Move through the sub directory using the Span button until

1 TRIM message appears.

3. Move through the sub directory using the Zero button until

11 Z-TRIM message appears.

4. Access the Zero Adjustment function by pressing the Span button until the 12 Z-ADJ message appears.

5. When the SelInc message appears, press the Zero button repetitively until the 10.0 message appears on the LCD.

Set the value by pressing the Span button.

6. When VALUE message appears, change the LCD value to

10.0 and press the Zero button, then press the Zero+Span buttons.

7. When Sellnc message appears, change the LCD value to

1.0 and press the Zero button, then set the value and press the Span button. Press the Zero+Span buttons after the

LCD value changes to 14.0.

8. To save the settings, press the Zero+Span buttons until the

SelInc message appears.

• CHANGE UNITS

1. Access the menu by pressing the Zero+Span buttons.

2. Move to next menu by pressing the Zero button until the

1 TRIM message appears.

3. Moving thru the sub directory press the Span button until the 2 SETUP message appears.

4. Press the Span button to access 21 UNIT, press Span again to access Change Unit.

5. Save the values by pressing the Span button when the desired value is displayed on the LCD.

• CHANGE UPPER RANGE VALUE

1. Access the menu by pressing the Zero+Span buttons.

2. Move to next menu by pressing the Zero button until the

1 TRIM message appears.

3. Press the Span button until the 2 SETUP message appears.

4. Press the Span button until the 21 Unit message appears.

5. Press the Zero button until the 22 U-RNG message appears.

6. Press the Span button until the Zero Adjustment message appears.

• CHANGE LOWER RANGE VALUE

1. Access the menu by pressing the Zero+Span buttons.

2. Move to next menu by pressing the Zero button until the

1 TRIM message appears.

3. Press the Span button until the 2 SETUP message appears.

4. Press the Span button until the 21 Unit message appears.

5. Press the Zero button until the 22 U-RNG message appears.

6. Press the Zero button until the 23 L-RNG message appears.

7. Press the Span button until the Change Lower Range

Value message appears.

• CHANGE LCD MODE (Cyclic or Fixed Display)

1. Enter programming menu by pushing both (ZERO+SPAN) button together for 5 seconds. Release buttons when LCD displays Menu and display will automatically change to

“1 TRIM” confirming access into programming menu.

2. Push (ZERO) button when “1 TRIM” message appears on

LCD. Release button when display changes to “2 SETUP”.

3. Push (Zero) button and release when display changes to

“3 LCD”.

4. To move into sub directory push (Span) button after

“3 LCD” message appears on display. Release button when 31 LCDMD message is displayed.

5. To enter this sub-menu, push (Span) button and release when display changes to 311. Bottom line of display will show current Mode setting (e.g. NOR-RO, NOR-PV. etc).

6. Push (Zero) button to cycle through available mode options and select desired LCD rotation mode. Options are

NOR-RO (rotate all PV, %, mA), NOR-PV (fixed PV),

NOR-% (fixed %), NOR-mA fixed, ENG-RO, ENG-PV,

ENG-% or ENG-mA

7. Push (Span) to save changes and EXIT programming mode.

• DECIMAL PLACE

1. Access the menu by pressing the Zero+Span buttons.

2. Move to next menu by pressing the Zero button until the

1 TRIM message appears.

3. Press the Span button until the 2 SETUP message appears.

4. Press the Span button until the 3 LCD message appears.

5. Press the Span button until the 31 DEC-PL message appears.

6. Press the Span button until the Decimal Place message appears. The decimal place will appear on the second line of the LCD as follows:

DISPLAY EXPLANATION

MAX.

VALUE

AUTO Target value will be displayed automatically 99999

5-0

4-1

3-2

2-3

1-4

No decimal place

Display one decimal place

Display two decimal places

Display three decimal places

Display four decimal places

99999

9999.9

999.99

99.999

9.9999

7. The first line on the LCD will display 0.0.

8. The Decimal Place can be changed by pressing the Zero button. Save the setting by pressing the Span button after the decimal place has been selected.

9. The set value will display the PV value and Engineering value.

10. The LCD will display LCD_OV and the saved Unit when the pressure is over or under a set value.

3.8 Commissioning on the Bench with HHT:

The 3100 Pressure Transmitter can be commissioned using an

HHT before or after installation.

Connect an HHT (HART ® HANDHELD Communicator) across the

COMM pins for HART ® communication. The TEST pin connections can be used for connecting a multimeter to measure the output current directly from the transmitter. Since the 3100 is a two wire loop powered transmitter, it requires an external loop power supply (11.9V to 45VDC) to enable HART ® communication. Any

HART ® communication via HHT (or PC based configurator) requires a minimum 250 - 550 (max) ohm loop resistance.

POWER/SIGNAL CONNECTIONS

1. HHT (HART Communicator) or PC Configurator may be connected at any terminal point in the signal loop.

2. HART Communication requires a loop resistance between 250 and 550 ohm

(24 VDC).

3. Transmitters operate on 11.9 to 45.0 VDC terminal voltage.

Applied Power:

• 11.9 - 45.0 VDC for general operation

• 17.4 - 45.0 VDC for HART Communication

Figure 6: Connecting the Transmitter to HHT

9

4. INSTALLATION:

4.1 Overview:

The information in Chapter 4 explains installation.

4.2 Safety Messages:

Procedures and instructions in this chapter may require special safety measures to ensure the safety of the personnel performing the operation. Potential installation safety issues are indicated by a safety alert symbol ( ). Refer to the following safety messages before installing the 3100 pressure transmitter.

4.3 Warning:

DANGER: Explosion can result in death or serious injury. Do not remove the transmitter covers in an explosion-proof environment when the circuit is powered. Both transmitter covers must be fully engaged to meet the explosion-proof requirements.

WARNING: Electrical shock can result in serious injury. Only qualified personnel can wire the pressure transmitter.

WARNING: Process leaks can cause death or serious injury. Install and tighten before applying pressure. If you don’t, it can cause process leaks.

DANGER: Electrical shock can result in death or serious injury. Avoid contact with the leads and terminals.

4.4 Commissioning on the Bench with Hand-Held Terminal:

The 3100 Pressure Transmitter can be commissioned before and after installation. Commissioning is easier if the transmitter is configured on a bench with an HHT before installation.

4.5 General Considerations:

The transmitter can be mounted near the process to minimize piping. Keep in mind that easy access is required for personnel, field calibration, and installation. Install the transmitter in an area with minimal vibration, shock, and temperature fluctuations.

NO

START

DO YOU WANT

YES

BASIC SETUP

A) UNIT SETUP

B) RANGE SETUP

C) DAMPENING SETUP

D) TRANSMITTER FUNCTION SETUP

VERIFY

A) PRESSURE SUPPORT

DO YOU

SATISFY SPEC

FIELD INSTALL

A) JUMPER/SWITCH SETUP

B) TRANSMITTER TAKES UP

C) TRANSMITTER LEADS

D) TRANSMITTER FOR POWER SUPPLY

MAINTENANCE

4.6 Electrical Considerations (Power Supply):

The transmitter housing is composed of two parts. One side is electronics, and the other side is terminal block. The terminal block side is the transmitter’s front side and is labeled “Field

Terminal” on the housing. The terminal block can be accessed by removing the front cover. When wiring the power supply to the transmitter make sure the positive and negative wires are connected correctly.

A HHT configurator can be connected directly across the (COMM) pin terminal located just below the power supply (PWR) terminal block connections.

4.6.1 Power Supply:

The 3100 Pressure Transmitter requires an 11.9 – 45 VDC power supply. A 250 ~ 550 Ω (24 VDC) loop resistance is recommended for HART ® communication. Loop resistance is the sum of the resistance in the loop.

Max. Loop Resistance [ Ω] = (E-11.9) [vdc] / 0.022 [mA]

4.7 Wiring:

4.7.1 Wiring Caution:

1. Install the signal cables away from potential sources of electrical noise such as transformers, electrical motors, etc.

2. Before wiring, remove electrical conduit cap.

3. All screwed connections on the housing must be sealed with waterproof sealant. We recommend use of silicone based sealants to minimize post-hardening.

4. Avoid running DC signal and AC power cables in the same ducts/cable conduits to avoid signal noise issues.

5. All explosion-proof transmitters must meet the wiring and installation requirements specified within the applicable electrical codes.

4.7.2 Selecting the Wiring Materials:

1. Use 600V shielded PVC wire or standard wire of the same class. (To ensure proper communication use 24 AWG or larger wire, and do not exceed 5000 feet)

2. Use shielded wire in areas with electrical noise.

3. In areas with high or low ambient temperatures, use wire or cable that is rated for the extreme temperatures.

4. If the wire or cable is going to be used in oil, solvent, toxic gas or liquid, make sure it is rated accordingly.

5. Process wire or cable must not be soldered to the terminal lug.

Spade connectors are recommended to connect the process wires to the transmitter.

4.7.3 Connecting External Wires to Transmitter Terminal Box:

1. Open the cover indicated "FIELD TERMINAL". Do not open the cover if the transmitter is located in an explosion-proof area and powered. Connect the power supply to the terminal indicated "+PWR"(left terminal) and "-" in the central terminal. Do not connect "+" power supply to "+" terminal "TEST". It will damage the test diode.

2. Seal and close the conduit connection to prevent humidity and explosion-proof atmosphere from entering the housing.

3. Transmitter power is supplied by signal wire. Do not install near high voltage wires or high voltage equipment.

4. Close the transmitter cover. To meet the explosion-proof ratings make sure the covers are fully engaged.

NOTE: Do not power the transmitter with high voltage (AC). It can damage the transmitter.

5. You must connect a 250~550 Ohm Resistor in Current Loop

(between Power Supply and Transmitter) for HART ®

Communication. See Figure 8.

END

Figure 7: Installation Flow Chart

10

Figure 8: Wiring the 3100 Pressure Transmitter

4.7.4.2 Wiring Installation:

General use (see Figure 11):

Use metallic conduit or waterproof cable glands for wiring.

Apply non-hardening sealant to the terminal box and the threads on the flexible metal conduit for waterproofing.

Figure 9: Picture of Transmitter Wiring Terminal

4.7.4 Wiring (Loop Configuration):

DANGER: Explosion can result in death or serious injury. Do not remove the transmitter covers in an explosion-proof environment when the circuit is powered. Both transmitter covers must be fully engaged to meet explosion-proof requirements.

4.7.4.1 Loop Configuration:

The Taco 3100 Pressure Transmitters use a two-wire system for power, 4~20mA analog signal transmission and HART ® digital transmission.

A DC Power Supply is required for the transmitter loop. The transmitter and power supply should be connected as shown below.

See Figure 10.

Figure 11: Typical Mounting using Flexible Metal Conduit

Explosion-proof metal conduit wiring (see Figure 12):

A seal fitting must be installed near the terminal box port.

Apply a non-hardening sealant to the threads of the terminal connection box.

Flameproof heavy gauge steel conduit

Apply a nonhardening sealant to the threads of these fittings for waterproofing.

Figure 10

11.9 - 45 VDC

Figure 12: Typical Wiring using Explosion-Proof Conduit

4.7.5 Grounding:

Grounding should satisfy KS requirements (grounding resistance should be 10 ohm or less). Grounding is required for explosionproof applications and the ground resistance must be below 10 ohms.

NOTE: In case of Built-in Lightning Protector, Grounding should satisfy Special KS requirements (grounding resistance, 10 ohm or less).

11

Figure 13: 3100 Smart Pressure Transmitter

Internal and External Ground Terminal

There are ground terminals on the inside and outside of the transmitter. Either of these terminals may be used.

Use 600V insulated PVC wire for grounding.

4.7.6 Power Supply Voltage and Load Resistance:

When configuring the loop, make sure that the external load resistance is within the range (see Figure 14 below).

The transmitter supply voltage should be:

• Standard: 11.9 to 45 Vdc

• HART Communication: 17.4 to 45 Vdc

Maximum loop current is 24mA.

Load resistance R = (E-11.9) / 0.022 (E = Power Supply Voltage)

Figure 15: Model 3100 Outline Dimension Drawing

R=(E-11.9)/0.022

HART Communication

Applicable Range

Figure 14

4.8 Mechanical Considerations:

Figure 15 is a dimensional drawing for the 3100. Figure 16 shows how the A-630 angle bracket is mounted to a pipe.

4.8.1 Mounting:

Avoid installing transmitters in environments with excessive vibration. If it cannot be avoided it is highly recommended to provide adequate support when mounting.

4.8.2 Transmitter Access:

When selecting the installation location, accessibility must be taken into consideration.

• Housing rotation: The housing can be rotated 90°.

• Wiring terminals: The cover and wiring terminals are easily accessible.

• LCD/Circuits: Install the transmitter in a location where it can be seen. For transmitters without an LCD, the cover and jumpers are easily accessible.

Figure 16: A-630 Mounting Bracket

4.9 Environmental Considerations:

4.9.1 Ambient Temperature:

The transmitter ambient temperature range is 4 to 180°F (-20 to

60°C). If the ambient temperature is going to exceed the temperature range, precautions must be taken to keep the temperature within the temperature limits.

4.9.2 Toxic and Moist Environments:

The 3100 housing will protect the transmitter against moisture or toxic material. The electronic circuit is separated from the terminals. The housing covers have o-rings that seal the housing, but moisture can penetrate the housing through the conduit. The transmitter should be mounted in a position to prevent moisture from entering the housing through the conduit.

4.9.3 Installation in Hazardous Location:

The transmitter is designed with an explosion-proof housing.

Installation environment must not exceed the explosion-proof rating.

5. ON-LINE OPERATION:

5.1 Overview:

This chapter describes how to configure the 3100 Smart Pressure

Transmitter. The transmitter can be configured in On-Line or Off-

Line mode. In On-Line Mode a compatible HHT or PC configuration device must be used.

5.2 Safety Messages:

For added operator safety please pay specific attention to procedures outlined in this manual listed under the warning symbol

( ).

12

5.2.1 Warning:

DANGER: Explosion can result in death or serious injury. Do not remove the transmitter covers in explosion-proof environments when the circuit is powered. Both transmitter covers must be fully engaged to meet explosion-proof requirements.

DANGER: Electrical shock can result in serious injury. When installing transmitters in close proximity of high voltage sources (near power lines) the transmitter leads can be subject to high voltages.

Avoid contact with the leads and terminals.

5.2.2 Current to Passive Mode Configuration:

For multi-drop mode the current output must be configured as passive mode. Please disregard any other messages shown on HHT.

5.3 Configuration Data Review:

Before operating the transmitter make sure the configuration data on the nameplate matches the application.

5.4 Configuration Verification:

Before the transmitter is ready for service, the configuration must be checked to confirm the settings are configured for the application.

5.4.1 Process Variable:

There are two process variables in the 3100 Smart Pressure

Transmitter. The primary variable and temperature compensated SV

(Second Variable), the PV value outputs the 4~20mA analog value.

5.5 Basic Setup:

The correlation variable must be configured before operating the transmitter.

5.5.1 Select Sensor Range:

The pressure range must be selected when ordering the pressure transmitter.

5.5.2 Set Output Units:

Select from the following engineering units:

Volumetric Flow Unit -

CubicFeet/min, Gallons/min, Liters/min,

ImperialGallons/min, CubicMeter/hr, Ft/s, meters/s,

Gallons/s, mGallons/day, Liters/s, mLiters/day, CubicFeet/s,

CubicMeter/s, CubicMeter/day, ImperialGallons/hr,

ImperialGallons/day, NormalCubicMeter/hr, NormalLiter/hr,

StandardCubicFeet/min, CubicFeet/hr, CubicFeet/day,

CubicMeters/min, Barrels/s, Barrels/min, Barrels/hr,

Barrels/day, Gallons/hr, ImperialGallons/s, Liters/hr,

Gallons/day

Mass Flow -

Grams/s, Grams/min, Grams/hr, Kilograms/s,

Kilograms/min, Kilograms/hr, Kilograms/day,

MetricTons/min, MetricTons/hr, MetricTons/day, Pounds/s,

Pounds/min, Pounds/hr, Pounds/day, ShortTons/min,

ShortTons/hr, ShortTons/day, LongTons/hr, LongTons/day

Pressure kPa, mmH2O, InH2O, InHg, FtH2O, mmHg, psi, bar, mbar, g/cm 2 , Kg/cm 2 , Pascals, MPa, torr, ATM

Miscellaneous -

%

Time -

Min, sec, hr, days

Mass -

Grams, kilograms, metric tons, pounds, short tons, long tons, ounce

Volume -

Gallons, liters, imperial gallons, cubic meters, barrels, bushels, cubic yards, cubic feet, cubic inches, bbl liq, normal cubic meter, normal liter, standard cubic feet, hectoliters

5.5.3 4-20mA Configuration:

Set the Zero and Span for the 4~20mA analog output.

5.6 Detailed Setup:

5.6.1 Set Fail Mode:

When the sensor or microprocessor is not operating properly, the transmitter will output 3.75mA or 21.75mA based on the Fail

Mode setting.

5.6.2 Set Dampening Time:

The Dampening Seconds value changes the response time of the transmitter to smooth out variations caused by rapid process changes. Determine the appropriate dampening setting based on the required response time, signal stability, and other requirements of your system.

The Dampening Seconds can be set from 0-60 seconds; the default dampening value is 1.0 second.

Figure 17

5.7 Configuration of Information Variable:

5.7.1 Set Tag:

Tags are an easy way to classify transmitters in multi transmitter application. Tags can use 8 words/numbers.

5.7.2 Set Messages:

When using several transmitters, the user can define each transmitter by using 32 words/numbers. This message is saved in EEPROM.

5.8 Diagnostics and Service:

5.8.1 Loop Test:

The Loop Test verifies the output of the transmitter, the integrity of the loop, and the operations of any recorders or similar devices installed in the loop. The following procedures are required for a loop test.

• Connect a reference meter to the transmitter.

• Select the Loop Test on the HHT and operate the Loop Test.

• Select current output (4mA/20mA/etc.)

• If the readings match, then the transmitter and the loop are configured and functioning properly. If the readings do not match, then you may have the current meter attached to the wrong loop, there may be a fault in the wiring, the transmitter may require an output trim, or the current meter may be malfunctioning.

5.9 Calibration:

The scale is implemented by calibrating the transmitter. Trim function has several calibration functions. Smart transmitters operate differently than analog transmitter. A smart transmitter uses a microprocessor that contains information about the sensor's specific characteristics in response to pressure and temperature for calculating the process variable. 4-20mA configuration sets the

13

transmitter’s analog output to a selected upper and lower range and can be done with or without an applied pressure. 4-20mA configuration does not change the factory characterization curve stored in the microprocessor. Sensor trimming requires an accurate pressure input and adds additional compensation that adjusts the factory characterization curve to optimize transmitter performance over a specific pressure range. 4-20mA configuration provides the ability to readjust the 4~20mA sensor inputs without an applied pressure. Reranging does not change the factory or characterization curve stored in the microprocessor.

Sensor trimming requires an accurate pressure input and adds additional compensation to the factory characterization curve to optimize transmitter performance over a specific pressure range. Rerange provides ability to readjust the 4~20 mA points sensor inputs.

5.9.1 Sensor Trim:

The Sensor trim function adjusts the A/D signal conversion within the transmitter sensor electronics and determines how it digitally interprets any pressure changes applied to the sensor inputs. It is highly recommended to perform a sensor trim when first commissioning the transmitter on site. There are three ways to trim the sensor: Sensor zero trim, full trim and zero adjustment. Sensor zero trim is a one-point adjustment typically used to compensate for the mounting position. Two point trim is a full sensor trim, in which two accurate pressures are applied (equal to or greater than the range values), and the output is linear. You should always adjust the low trim value first to establish the correct offset.

5.9.2 D/A (Digital to Analog) Trim:

The D/A trim function makes minor adjustments to the analog

(4- 20mA) output scaling from the transmitter. It is recommended to do a D/A trim on both hi (20mA) & low (4mA) values for best results. This function corrects any minuscule offsets within the

D/A conversion of the transmitter.

6. MAINTENANCE:

6.1 Overview:

This chapter describes diagnostic and maintenance.

6.2 Safety Messages:

When the transmitter is in operation, operators should follow all safety messages. Potential safety issues are indicated by a safety alert symbol ( ). Refer to the following safety messages before performing any operation proceeded by a ( ) symbol.

6.2.1 Warning:

DANGER: Explosion can result in death or serious injury. Do not remove the transmitter covers in explosion-proof environments when the circuit is powered. Both transmitter covers must be fully engaged to meet explosion-proof requirements.

DANGER: Electrical shock can result in serious injury. When installing transmitters in close proximity of high voltage sources (near power lines) the transmitter leads can be subject to high voltages.

Avoid contact with the leads and terminals.

6.3 Hardware Diagnostics:

If there is a failure despite a diagnostic message on the HHT, Table

6.1 can help troubleshoot the problem.

SYMPTOM

Transmitter does not

Communicate with HART ®

Communicator

TABLE 8.1

POTENTIAL

SOURCE

CORRECTIVE ACTION

Loop

Wiring

Check for a 250-550 ohm resistance between the power supply and HHT.

Check for adequate voltage to the transmitter (the transmitter requires

11.9-45 VDC).

Check for intermittent shorts, open circuits and multiple grounds.

Sensor

Input

Failure

Loop

Wiring

Connect HHT and enter the transmitter test mode to isolate a sensor failure.

Check for dirty or defective terminals, interconnecting pins or receptacles.

High Output

Erratic Output

Low Output or No Signal

Power

Supply

Electronics

Module

Loop

Wiring

Electronics

Module

Sensor

Element

Loop

Wiring

Electronics

Module

Check the output voltage of the power supply at the transmitter terminals. It should be 11.9 to 45 VDC.

Connect HHT and enter the transmitter test mode to isolate module failure.

Check the sensor limits to ensure the calibration adjustments are within the sensor range.

Check the output voltage of the power supply at the transmitter terminals. It should be 11.9 to 45 VDC.

Check for intermittent shorts, open circuits and multiple grounds.

Check for proper polarity at the signal terminals.

Connect HHT and enter the transmitter test mode to isolate an electronics mode failure.

Connect HHT and enter the transmitter test mode to isolate a sensor failure.

Is the PV out of range?

Check for adequate voltage to the transmitter (the transmitter requires

11.9-45 VDC).

Check for intermittent shorts, open circuits and multiple grounds.

Check polarity of signal terminal.

Check the loop impedence.

Connect HHT and check the sensor limits to ensure the calibration adjustments are within the sensor range.

WARNING: Electrical shock can result in death or serious injury. Only qualified personnel can configure and wire the 3100 Smart Pressure Transmitter.

14

6.4 Hardware Maintenance:

The Taco 3100 Smart Transmitter has no moving parts and requires little maintenance. If a transmitter fails, it must be returned to Taco, Inc. for inspection, repair, or replacement.

6.4.1 Test Terminals:

The test terminals are marked TEST on the terminal block. The test and negative terminals are connected to the power terminals.

So long as the voltage across the receptacles are below the diode threshold voltage, no current will pass through the diode. To ensure that current isn’t leaking through the diode, test the reading with an indicating meter. The test connection should not exceed 10 ohms. A resistance value of 30 ohms will cause an approximate 10 percent of reading error.

6.4.2 Disassembling the Housing:

The transmitter is designed with dual-compartment housing; one contains the electronics module, and the other contains all wiring terminals and communication terminal.

Figure 19: Structure of Housing

6.4.3 Fail Mode Jumper Switch and EEPROM-Write:

Fail-mode jumper switch and EEPROM-Write is located behind the front cover.

Figure 18: Test Terminals

Figure 20: Structure of Electronics Module

APPENDIX 1 – 3100 SMART PRESSURE TRANSMITTER - LCD DISPLAY CODE:

MESSAGE

ADJ-U

ADJ-L

ZERO

DESCRIPTION

Zero adjustment value – used to configure transmitter when it is out of range (on higher side)

Zero adjustment value – used to configure transmitter when it is out of range (on low side)

Initial message when using Zero button

SPAN Initial message when using Span button

BT-ERR

P-LOCK

Button Sequence error

Button input error - Protect Locked

ZT-ERR

-TR-

ZR-ERR

SP-ERR

-ZR-

-SP-

Zero Trim value is over limit (10%)

Zero Trim done

Setting Limit error when executing Zero button function

Setting Limit error when executing Span button function

Zero button function done

Span button function done

-ZA-

DONE

RNGOVR

LCD_OV

Zero Adjustment done

Configuration completed using buttons

Limit error when executing other setting function

Over Values for LCD

-AC-

S-FL

S-OP

AEP-RF

TS-FL

AEP-WF

EOSC

FAVE

MESSAGE

SCD-ER Sensor Code Error

DESCRIPTION

F-RST

F-LOCK

Flash Setting Data Reset

Flash Setting Data Reset, Protect Locked

F-FAIL

-FR-

A-RST

A-STOR

A-FAIL

Flash Setting Data Reset Failure

Flash Reset done

Analog EEPROM Initializing Start

Analog EEPROM Stored

Failure in writing configuration values on to the EEPROM of transmitter CPU

Analog EEPROM Configuration done

Sensor Fail

Sensor Overpressure

Check error with EEPROM on CPU board

Temperature Sensor Error

Analog EEPROM write fail

Crystal Element Defect Alarm

Flash Acess Violation

15

16

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.

TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436.

Visit our web site at: http://www.taco-hvac.com