SEI DC-UPS Series Specifications

Add to my manuals
16 Pages

advertisement

SEI DC-UPS Series Specifications | Manualzz
Installation and Operations Manual
SEI DC-UPS SERIES
SEI Incorporated
5115 Pegasus Court, Suite Q
Frederick, Md 21704
Phone 301-694-9601
Fax
301-694-9608
Email [email protected]
Web
http://www.seipower.com
TABLE OF CONTENTS
Table of Contents............................................................................................... 1
Description......................................................................................................... 2
Technical Specifications.................................................................................... 3
Environmental Specifications............................................................................ 4
Safety Information ............................................................................................. 4
Installation Instructions...................................................................................... 5
Startup and Checkout…………………………………………………………7
Theory of Operation........................................................................................... 8
Remote Alarm Option ………………………………………………………10
Power Management Package Option ................................................................ 10
Repair and Maintenance ................................................................................... 11
Output Module –A…………………………………………………………..13
Output Module –M…………………………………………………………..14
Output Module –P…………………………………………………………..14
1
DESCRIPTION
The SEI DC-UPS series is a compact unit designed to service a wide range of
customer equipment requiring battery-backed 48 VDC power. The DC-UPS series
comes equipped with up to 750 Watts of rectifier power using parallel 250Watt
rectifiers for reliability. The distribution is provided on the right side of the unit.
Commercial power is applied to the left side of the unit. The SEI DC-UPS can be
mounted on a wall, a 19-inch rack or an optional DIN Rail mount. Optionally,
SNMP communications via the Power Management Package is available. Two
Alarm Contacts are standard.
The DC-UPS series offers three different models with a range of output current:
•
SEI-250 – 4.5 Amps (250Watts)
•
SEI-500 – 9.0 Amps (500 Watts)
•
SEI-750 – 13.5 Amps (750 Watts)
Three output distribution modules are available. The ‘M’ module contains two,
individually fused 8-pin Molex Minifit connectors. The ‘A’ module contains
two, individually fused 2-pin AMP Mat-N-Lok connectors. The ‘P’ module
features two individually fused binding posts. The 250 houses one output
distribution module, the 500, two modules, and 750 accommodates three output
distribution modules. Customer-specified output modules are available.
The DC UPS comes equipped with field replaceable, non spillable sealed lead
acid battery packs. Circuitry within the DC UPS monitors and periodically tests
the condition of the batteries and displays the results via external LED’s as well as
over the network when equipped with the optional Power Management Package.
The DC UPS also utilizes a Low Voltage Disconnect, (LVD), circuit that prevents
damage to the Battery Packs during an extended AC outage
2
TECHNICAL SPECIFICATIONS
SEI-250
Electrical Specifications
Input
Voltage
Frequency
Current
Output
Voltage
Current
Mechanical Dimensions
Width
Depth
Height
Weight
120 +10/-15% VAC
50-60 Hz
3 amps Max
42-56VDC
4.5 amps
19.00 Inches
5.00 Inches
14.00 Inches
32 lbs
SEI-500
Electrical Specifications
Input
Voltage
Frequency
Current
Output
Voltage
Current
Mechanical Dimensions
Width
Depth
Height
Weight
120 +10/-15% VAC
50-60 Hz
6 amps Max
42-56VDC
9 amps
19.00 Inches
5.00 Inches
20.00 Inches
34 lbs
SEI-750
Electrical Specifications
Input
Voltage
Frequency
Current
Output
Voltage
Current
Mechanical Dimensions
Width
Depth
Height
Weight
120 +10/-15% VAC
50-60 Hz
9 amps Max
42-56VDC
13.5amps
19.00 Inches
5.00 Inches
20.00 Inches
36 lbs
3
ENVIRONMENTAL SPECIFICATIONS
Temperature
Operating
Storage
0 °C to +40 °C
-20 °C to +50 °C
Humidity
0-95% non-condensing
Thermal Load
SEI-250
SEI-500
SEI-750
190 BTU/hr max
380 BTU/hr max
570 BTU/hr max
SAFETY INFORMATION
Always insure that the person assigned to the job can perform the job safely.
Always lift all equipment properly.
Always disconnect commercial power and remove the battery fuse before working
on the unit.
Always replace the batteries with batteries of the same type and style.
DO NOT work on this equipment during an electrical storm.
DO NOT work in locations where there is condensing moisture or standing water.
Service to the DC UPS should be performed by a qualified technician.
4
INSTALLATION INSTRUCTIONS
GENERAL
The installation section of this manual will provide all the necessary
information for room requirements, proper inspection, and installation.
Inspection
The equipment has been fully tested and inspected prior to shipment.
Although the unit has been packed in accordance with good commercial
practices, it does not preclude damage in transit.
The following actions should be taken on receipt of the equipment:
Visually inspect the shipping container for damage. If damaged,
request that the carrier inspect the shipment.
Unpack the inner container from the shipping container and remove
the unit from the packaging. Inspect the unit for visible damage.
If a claim for damages is to be made, it should be filed promptly with the
transportation company. In addition, notify SEI within two days of delivery.
SEI will advise the customer of any further procedures that may be
required, including an RMA number in the event that the unit has to be
returned to the factory for repair.
Make sure the following items are included inside the package:
One SEI DC-UPS Unit.
One AC Power Cord.
One warranty card.
One Installation and Operations Manual.
5
Room Requirements
Electrical Requirements
•
•
•
All units are shipped from the factory for use with 120 VAC. In the event that
operations at 240 VAC is required, please notify the factory.
Each unit requires a separate NEMA 5-15R receptacle protected by a 15 Amp circuit
breaker.
A standard 7 foot 6 inch power cord with a molded NEMA 5-15 plug is supplied
with each unit.
Mounting Instructions
•
The SEI DC-UPS weighs between 32 and 36 lbs, depending upon the model.
•
The SEI DC-UPS is designed to mount to a rack or wall without further
requirements for additional mounting kits. For wall mounting, a user supplied 3/4inch plywood backboard or equivalent is required. The DC-UPS should be fastened
to the backboard using number ten wood screws. A number 27drill can be used to
provide a pilot hole for the screws. All of the screws should be tightened with a
torque of 30 in/lb minimum and 34 in/lb maximum.
•
The unit should be mounted vertically in a clean dry area where the ambient
temperature does not exceed 40°C (104° F)
•
It is important that ventilation for the unit be provided. Leave adequate space above
and below the unit so that unrestricted airflow is allowed to the unit. It is suggested
that 5 inches of space be allocated around the top of the unit.
•
The DC-UPS is supplied with mounting angles suitable for 19" standard, racks or
wall mounting.
•
The mounting slots on each rack adapter are spaced in conformance with EIA
standard RS-310-B.
6
START UP AND CHECKOUT
Power On Checkout.
•
Once the unit is properly mounted, you may begin the checkout procedure. First,
insure that all the equipment to be powered by the unit is installed.
•
Install the provided battery fuse and fuse holder cap. The fuse holder is on the right
side panel of the SEI-250. The fuse holder is on the left side panel of the SEI-500
and SEI-750.
•
Attach the optional SNMP Network cable, or alarm contacts cable if so optioned.
•
Attach the supplied AC power cord to the left side of the DC-UPS.
•
Plug in the DC-UPS power cord into the commercial AC outlet made available for
this unit.
•
When power is first applied, the unit should display a flashing green Battery Charge
Status LED and a solid green Battery Test Status LED.
•
Connect the user equipment to the DC-UPS output connectors located on the right
side of the unit.
•
Verify that the connected equipment is receiving power.
•
If you have a specific question not addressed in this manual, please call 1-800-7654SEI (1-800-4734), for technical support.
7
THEORY OF OPERATION
Theory of Operation
The following will provide you with an outline of operations and a list of modules found in
the DC-UPS.
Modules
• Rectifiers
• System Controller/LVD
• Battery Module
• Distribution and Connectors
RECTIFIER(S)
SYSTEM
CONTROLLER
DISTRIBUTION
MODULE(S)
BATTERY
PACK
Functional Block Diagram DC-UPS
Figure 1
Rectifier
The rectifier converts AC input power to regulated DC output power. Each DC-UPS
rectifier provides up to 250 watts of power. The SEI-250 has one 250W rectifier; the SEI500 has two rectifiers and the SEI-750 contains 3 rectifiers. The input of each rectifier is
fused for protection...
System Controller/LVD
The System Controller has the following functions:
•
•
•
•
•
•
Distribution of the DC power
Battery charge voltage and current control and monitoring
Battery Low Voltage Disconnect Function (LVD)
Battery charge and test status indicators
Automatic and manual battery test
Local and Remote Alarms (optional)
LED Indicators
8
There are two LED indicators on the front of the unit; Battery Charge Status and Battery
Test Status. The functions of these indicators are as follows:
Battery Charge Status:
Constant Green – Fully Charged
Flashing Green – Charging
Constant Red – On Battery
Fast Flash Red- Adjust rectifier
Battery Test Status:
Constant Green – Battery Good
Fast Flash Red – Wait, Then Test
Slow Flash Red – Replace Battery
Manual Battery Test Switch –Push to Test
NOTE: The Manual Battery Test switch is
disabled when the battery is charging. Also,
to prevent unnecessary battery discharge, the
Manual Battery Test is disabled for 5 minutes
following a Battery Test. In both cases, the
Wait, Then Test indication is displayed.
Low Voltage Disconnect Function
The low voltage disconnect function will disconnect the battery when the battery voltage
drops below a 42 Vdc. This is done to prevent deep discharge of the batteries, which can
adversely affect battery life. Both internal and external batteries are disconnected.
External Connectors
•
•
•
AC power is connected via a standard IEC connector located on the left side wall.
The mating connector should be an IEC female connector three-conductor power
cord.
External Batteries are connected through a two pin locking connector. Two of these
connectors are located on the right side wall.
Distribution Module – See Appendix
9
Remote Alarm Option
The DC-UPS Remote Alarm Option provides relay contacts to remotely monitor the status
of the unit. These alarms will indicate either an AC Fail or a Battery Test Fail condition.
Both normally open and normally closed contacts are provided to suite the user’s external
monitoring circuitry. The alarm contacts have a 2 Amp rating. The NO and NC contacts will
change state when an alarm condition occurs.
The alarm contacts are accessible via an RJ45 connector on the side panel of the DC-UPS.
The Alarm Contact connector pinouts are shown in Figure 2
Pin #
1
2
3
4
5
6
7
8
Function
Battery Test Fail NC
Battery Test Fail Common
Battery Test NO
No connection
No connection
AC Fail NC
AC Fail Common
AC FAIL NO
Comment
Battery OK
Battery has failed
AC Failure has occurred
Operating Normally
Alarm Contact pinouts
Figure 2
Power Management Package
SEI’s Power Management Package (PMP) for the SEI-DC-UPS provides a variety of
functions necessary to monitor and control output power to DC powered devices, as well
as maximize the efficiency and reliability of the power systems and battery backup.
Ethernet communication is accessed via a panel mounted standard RJ45 connector. Two
Ethernet interfaces are provided to monitor and control the DC-UPS. A web page
interface that can be viewed with any Internet browser is available for easy system status
checks and fast system configuration tasks. An SNMP interface provides the ability to
continuously monitor the DC-UPS status with a Network Management System (NMS)
and to receive instantaneous notification of DC UPS status changes and alarms via
SNMP traps.
10
REPAIR AND MAINTENANCE
Repair and Maintenance
The SEI DC-UPS is engineered to operate unattended and with low maintenance
overhead for extended periods of time. Although the electronics within the DC-UPS
require no routine maintenance, the battery charge voltage may drift with time and
operating temperature. The DC-UPS continuously monitors the battery charge
voltage. If the battery charge voltage is out of adjustment, the Battery Charge Status
indicator will flash red.
Tools and Test Equipment
No special tools other than those normally contained in an electronic technicians
toolkit are required to service the DC-UPS. To check the system voltage and reset as
necessary, it is recommended that a quality digital voltmeter (DVM) be used.
Rectifier Adjustment Procedure
The rectifier should only be adjusted with the nominal system load connected.
Connect a DVM to one of the external battery connectors. Measure the voltage; it should
be between 54.0 and 55.5 volts. If the measured voltage is outside of this range, perform
the following steps:
SEI-250
1. Remove the battery fuse located on the right side panel. Disconnect any
external battery packs.
2. Loosen the front panel mounting screws and remove the front panel.
3. Connect the digital voltmeter to one of the external battery (2 pin)
connectors of the unit
4. Locate the blue potentiometer in the center of the right edge of the
rectifier. Adjust the potentiometer on the power supply until the voltmeter
reading is 54.8 Vdc.
5. Replace the front panel.
6. Re-install the internal battery fuse and re-connect any external
battery packs.
SEI-500 and SEI-750
1. Remove the battery fuse on the side panel. Disconnect any external
battery packs.
2. Loosen the front panel mounting screws and remove the front panel.
3. Using the digital voltmeter, measure the sense voltage on each of the
power supplies. The sense voltage is measured on the power supply
connector, between the pin with the red wire and the pin with the black
wire. Adjust the potentiometer on each power supply until the voltmeter
reading is 56.2 Vdc.
11
Note: When setting sense voltages, always adjust the potentiometer until
the sense voltage reading changes, and then set it to the desired voltage.
Additionally, anytime one power supply is adjusted, all other power supply
sense voltages must be re-checked.
4. Once the sense voltages have been balanced, connect the digital voltmeter
to the external battery connector. Verify that voltmeter reading is 54.8
Vdc.
5. If the voltmeter reading is not correct, tweak each of the power supplies
until the voltage reading at the external battery connector is 54.8 Vdc.
Then re-measure the sense voltage on each of the power supplies. Adjust
the power supplies such that the sense voltages are equal by adjusting any
unit with a lower sense voltage up. Once the sense voltages have been
balanced, connect the voltmeter to the external battery connector and
verify the voltmeter reading is 54.8 Vdc.
NOTE: The final value of the power supply sense voltage is not important. As
long as the sense voltages on all power supplies are equal and the voltage
reading at the external battery connector is correct, the unit is properly
adjusted.
7. Replace the front panel.
8. Re-install the battery fuse and re-connect any external battery packs.
12
Appendix
Output Module –A
The –A version output module contains two individually fused TYCO/AMP Mat-NLok connectors.
Mating Connector:
Mating Pin:
Wire Gauge:
1-480698-0
350873-3
14-18 AWG
Fuse:
PORT 1, PORT2
GMT-7.5A, Cooper Bussmann or Equivalent.
PORT3, PORT4, PORT 5, PORT6
GMT-15A, Cooper Bussmann or Equivalent
Note: The fuse is sized to provide full output power from each connection. If multiple
connections are used, the fuse can be re-sized to limit current at a lower value.
+48V
+48V RTN
FUSE 1
FUSE 2
OUTPUT MODULE –A
Layout and Polarity
13
Output Module –M
The –M version output module contains two eight pint, individually fused MOLEX Minifit connectors.
Mating Connector:
Mating Pin:
Strain relief
Wire Gauge:
39-01-2085
39-00-0078
15-04-9343
14-18 AWG
Fuse:
PORT 1, PORT2
GMT-7.5A, Cooper Bussmann or Equivalent.
PORT3, PORT4, PORT 5, PORT6
GMT-15A, Cooper Bussmann or Equivalent
Note: The fuse is sized to provide full maximum power from each connection. If
multiple connections are used, the fuse can be re-sized to limit current at a lower value.
OUTPUT MODULE M
Layout and Polarity
14
Output Module –P
Each port contains two ¼ -20 terminal posts suitable for ring lug connection. The
48VRTN connection of each port is fused.
Fuses:
Ports 1-2
3AG 6A, 0312006 Littlefuse or Equivalent.
Ports 3-6
3AG 15A, 326015 Littlefuse or Equivalent.
Note: The fuse is sized to provide maximum output power from each connection. If
multiple connections are used, the fuse can be re-sized to limit current at a lower value.
PORT 1
+48V
48VRTN
PORT 2
+48V
48VRTN
OUTPUT MODULE P
Layout and Polarity
15

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement