Digital Panel Meters
Modular Indicator and Controller
Type UDM40
• The alarm status can be coupled to the different colour of the display
• Linearization of V and A inputs up to 16 points
• Multi-input modular instrument 4 dgt LED
• 0.1% RDG basic accuracy
• TRMS AC current and voltage measurements
• AC/DC current measurements; selectable full scales
(200µA to 5A)
• AC/DC voltage measurements; selectable full scales
(200mV to 500V)
• °C or °F temperature measurements
(Pt100-250-500-1000, Ni100, TC J-K-S-T-E)
• Resistance measurements; selectable full scales
(20
Ω to 20kΩ)
• Up to 4 independent alarm set-points (optional)
• 20mA/10VDC analog output (optional)
• Serial port RS485 or RS232 (optional)
• MODBUS, JBUS communication protocol
• Front protection degree: IP67, NEMA4x
• LED display, selectable colour (red, amber, green)
Product Description
µp-based digital panel meter, 4-dgt LED indicator, for current, voltage, temperature and resistance measurements. Measuring ranges and functions easily programmable from the keypad or from the PC by means of optional UdmSoft software. UDM
40 includes storage min-max functions and double level protection password. Housing for panel mounting with front protection degree: IP67, NEMA4x.
How to order
UDM40 XXX XX XX X XX
Model
Slot A
Slot B
Slot C
Slot D
Options
How to order
UdmSoft-kit
UdmSoft-kit: software plus “UCOM1” communication cable for programming UDM40 by means of PC .
Type Selection
Slot A (measuring inputs) Slot B (communication) Slot C (communication and alarm) Slot D (power supply)
LSX:
signal inputs:
0.2-2-20mA DC/AC;
0.2-2-20V DC/AC
LSE/
LSF:
signal inputs: + AUX:
0.2-2-20mA DC/AC;
0.2-2-20V DC/AC
HSX:
signal inputs:
0.2-2-5A DC/AC;
20-200-500V DC/AC
TRX:
signal inputs: TC temperature probes (J-K-
S-T-E, Pt100-250-500-
1000) and resistance
(0.02-0.2-2-20k
Ω)
XX:
None
SX:
Serial port RS485
SY:
Serial port RS232
AV(*): Single analogue output,
0 to 20mA DC and
0 to 10V DC
(*):
The two analogue outputs cannot be used at the same time. It is possible to plug in only one module by instrument.
XX:
None
R1:
Single relay output,
(AC1-8AAC, 250VAC)
R2:
Dual relay output,
(AC1-8AAC, 250VAC)
R4:
Dual relay output, (AC1-
8AAC, 250VAC) + dual open collector output
(NPN, 100mA)
R5:
4 relay outputs
(AC1-5AAC, 250VAC)
AV(*): Single analogue output,
0 to 20mA DC and
0 to 10V DC
Input Specifications
Analogue inputs
BQ LSX module
BQ LSE/LSF module
BQ HSX module
BQ TRX module
BQ TRX module
Digital inputs
Number of inputs
Use
Channels and variable
1, mA and V DC/AC
1, mA and V DC/AC + AUX
1, A and V DC/AC
1, temperature
1, resistance
Incl. in the measuring module
1 (voltage-free) key-pad lock
Display hold
Reset of latch alarms
Contact reading signal
Close contact resistance
Open contact resistance
Insulation
Accuracy (display, RS485)
H:
L:
Options
90 to 260V AC/DC
18 to 60V AC/DC
XX:
None
TX:
Tropicalization
BQ xxx: <0.1mA, <3,5V DC
BQ LSE/BQ LSF: <2.5mA,
<14V DC
Max 1k
Ω
Min 500k
Ω
Non-insulated
See table “Measuring accuracy”, temperature drifts and minimum-maximum indications”
Specifications are subject to change without notice UDM40DS 040706
1
UDM40
Input specifications (cont.)
Additional errors
Humidity
Input frequency
Magnetic field
Temperature drift
Sampling rate
Display refresh time
Display
Colour
Max and min indication
Measurements
0.3% RDG, 60% to 90% R.H.
0.4% RDG, 62 to 440 Hz
0.5% RDG @ 400 A/m
See table “Measurement accuracy, temperature drifts, and max/min indications”
500 samples/s @ 50 Hz
200 msec @ 50Hz
4 DGT,
7 segments height 14.2 mm
Selectable (red, amber, green)
See table “Measurement accuracy, temperature drifts and max min indications”
Current, voltage, temperature and resistance. For the current and voltage measurements: TRMS measurement
Coupling type
Crest factor
Input impedance
Frequency
Overload
Compensation
RTD
TC of distorted sine waves.
Direct
≤
3; A
Pmax
=1.7In; V
Pmax
=1.7Un
See table “input impedances and overloads”
40 to 440 Hz
See table “input impedances and overloads”
Only temperature measurement module.
- For Pt 100-250-500-1000,
3-wire connection: up to 10
Ω
- For resistance measur. with
20
Ω range: up to max 0.1Ω
- For resistance measurements with
≥200Ωrange: up to max 10Ω
Internal cold junction, within temperature range from
0 to +50°C.
Automatic or manual com-
Measurement accuracy, temp. drifts, max and min indications
All accuracies and min/max indications are referred to an ambient temp. range of 25°C ±5°C, rel. humidity
≤60% and scale ratio (electrical/displayed scale) equal to 1. The conversion into °F is obtained acting on the electrical/displayed scale ratio.
Min. indication (
<
) Max. indicat. (
<
) Module
BQ LSX/
BQ LSE/
BQ LSF
BQ HSX
BQ TRX
Thermocouple
Inputs Type Accuracy
-200µA to +200µA
-2mA to +2mA
-20mA to +20mA
-200mV to +200mV
-2V to +2V
-20V to +20V
DC/AC
DC: ±(0.1%RDG+3DGT)
0% to 25% FS;
±(0.1%RDG+2DGT)
25% to 110% FS.
TRMS (da 45 a 65Hz)*:
±(0.3%RDG+3DGT)
0% to 25% FS;
±(0.3%RDG+2DGT)
25% to 110% FS.
-200mA to +200mA
-2A to +2A
-5A to +5A
-20V to +20V
-200V to +200V
-500V to +500V
DC/AC
-50°C to +760°C
-58 °F to +1400 °F
-200°C to +1260°C
-328 °F to +2300°F
-200°C to +1000°C
-328°F to +1832°F
-50°C to +1750°C
-58°F to +3182°F
-200°C to +400°C
-328°F to +752°F
J
J
K
K
E
E
S
S
T
T
DC: ±(0.1%RDG+3DGT)
0% to 25% FS;
±(0.1%RDG+2DGT)
25% to 110% FS.
TRMS (45 to 65Hz)*:
±(0.3%RDG+3DGT)
0% to 25% FS;
±(0.3%RDG+2DGT)
25% to 110% FS.
±(0.2%RDG+1DGT)
±(0.2%RDG+2DGT)
±(0.2%RDG+2DGT)
±(0.2%RDG+4DGT)
±(0.2%RDG+2DGT)
±(0.2%RDG+4DGT)
±(0.2%RDG+2DGT)
±(0.2%RDG+4DGT)
±(0.2%RDG+2DGT)
±(0.2%RDG+4DGT)
Temp. drift
±150 ppm/°C
±150 ppm/°C
±150 ppm/°C
- 200.0
- 2.000
- 20.00
- 200.0
- 2.000
- 20.00
- 200.0
- 2.000
- 5.000
- 20.00
- 200.0
- 500.0
- 50°C
- 58°F
- 200°C
- 328°F
- 200°C
- 328°F
- 50°C
- 58°F
- 200°C
- 328°F
+ 200.0
+ 2.000
+ 20.00
+ 200.0
+ 2.000
+ 20.00
+ 200.0
+ 2.000
+ 5.000
+ 20.00
+ 200.0
+ 500.0
+ 760°C
+ 1400°F
+ 1260°C
+ 2300°F
+ 1000°C
+ 1832°F
+ 1750°C
+ 3182°F
+ 400°C
+ 752°F
*
<45Hz >65Hz= ±(0.5%RDG+3DGT) 0% to 25% FS; ±(0.5%RDG+2DGT) 25% to 110% FS.
(
<
)
The min. indication for TRMS measurement (AC or DC) is 0; it is possible to modify the decimal point position.
2
Specifications are subject to change without notice UDM40DS 040706
UDM40
Measurement accuracy, temp. drifts, min max indications (cont.)
All accuracies and min/max indications refer to an ambient temperature range of 25°C ±5°C, relevant humidity
≤60% and scale ratio (electrical scale / displayed scale) equal to 1. The conversion into °F is obtained acting on the electrical/displayed scale ratio.
Module Inputs Type Accuracy Temp. Drift Min. Indication Max. Indication
BQ TRX
Thermoresistance
BQ TRX
Resistance
-200°C to +850°C
-328°F to +1562°F
-200.0°C to +200.0°C
-328°F to+392°F
-200.0°C to +200.0°C
-328°F to +392°F
-200.0°C to +200.0°C
-328°F to +392°F
-200.0°C to +200.0°C
-328°F to +392°F
-60°C to +180°C
-76°F to +356°F
0 to 20
Ω
0 to 200
Ω
0 to 2000
Ω
0 to 20.00k
Ω
Pt100
Pt100
Pt100
Pt100
Pt250
Pt250
Pt500
Pt500
Pt1000
Pt1000
Ni100
Ni100
Ω
±(0.2%RDG +2DGT)
±(0.2%RDG +4DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +1DGT)
±(0.5%RDG +2DGT)
±(0.2%RDG+2DGT)
25% to 110% FS
±(0.2%RDG+3DGT)
0% to 25% FS
(
< ) It is possible to modify the decimal point position.
Input impedances and overloads
±150 ppm/°C
±150 ppm/°C
Module
BQ LSX/
BQ LSE/
BQ LSF
BQ HSX
BQ TRX
Thermocouple
BQ TRX
Thermoresistance
BQ TRX
Resistance
Inputs
-200µA to +200µA
-2mA to +2mA
-20mA to +20mA
-200mV to +200mV
-2V to +2V
-20V to +20V
-200mA to +200mA
-2A to +2A
-5A to +5A
-20V to +20V
-200V to +200V
-500V to +500V
-50°C to +760°C
-58 °F to +1400 °F
-200°C to +1260°C
-328 °F to +2300°F
-200°C to +1000°C
-328°F to +1832°F
-50°C to +1750°C
-58°F to +3182°F
-200°C to +400°C
-328°F to +752°F
-200°C to +850°C
-328°F to +1562°F
-200.0°C to +200,0°C
-328°F to +392°F
-200.0°C to +200,0°C
-328°F to +392°F
-60°C to +180°C
-76°F to +356°F
0 to 20
Ω
0 to 200
Ω
0 to 2000
Ω
0 to 20.00k
Ω
Type
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
E
S
S
T
T
K
K
J
J
E
Pt100
Pt100
Pt250/Pt100
Pt250/Pt100
Pt1000/Pt500
Pt1000/Pt500
Ni100
Ni100
Ω
Impedance Overload (continuous)
≤2,2kΩ
≤22Ω
≤22Ω
≥2,2kΩ
≥200kΩ
≥200kΩ
≤1Ω
≤0.012Ω
≤0.012Ω
≥2MΩ
≥2MΩ
≥2MΩ
5mA
50mA
50mA
10V
50V
50V
0.8A
7.5A
7.5A
750V
750V
750V
I
LK
<0.5µA
800µA (*)
800µA (*)
90µA (*)
90µA (*)
800µA (*)
800µA (*)
800µA (*)
800µA (*)
800µA (*)
90µA (*)
800µA (*)
90µA (*)
(*) Maximum measuring current generated for resistance equal to 0
Specifications are subject to change without notice UDM40DS 040706
Max 5V
Max 5V
Max 5V
- 200
- 328
- 200.0
- 328.0
- 200.0
- 328.0
- 200.0
- 328.0
- 200.0
- 328.0
- 60
- 76
0
0
0
0
+ 850
+ 1562
+ 200.0
+ 392.0
+ 200.0
+ 392.0
+ 200.0
+ 392.0
+ 200.0
+ 392.0
+ 180
+ 356
20.00 ( <
)
200.0 ( <
)
2000 ( <
)
20.00 (
<
)
Overloads (1s)
10mA
150mA
150mA
20V
100V
100V
1A
100A
100A
1000V
1000V
1000V
Max 10V
Max 10V
Max 10V
3
UDM40
4
Output specifications
Serial output
LED
Connections
Distance
Terminalization
Module: BR SX
Bidirectional (static and dynamic variables).
Display of data reception/transmission
Multidrop, 2 or 4 wires,
1000 m
Directly on the module
Addresses by means of jumper
1 to 255, selectable by means of key-pad
MODBUS RTU/JBUS Protocol
Data (bidirectional)
Dynamic (reading only) Measurement, min value max value
Static (reading/writing)
Data format
Baud rate
Insulation alarm status
All programming parameters, min max reset reset of latch alarm
8 data bit, no parity,
1 stop bit selectable 4800, 9600,19200 and 38400 bit/s
By means of opto-couplers
4000 V rms output to measuring inputs
4000 V rms output to power supply input
RS232
Serial output
Connections
Distance
Data format
Baud rate
Other features
(on request)
Module: BR SY
Bidirectional (static and dynamic variables)
3 wires, max. 15m
1 start bit, 8 data bit, no parity, 1 stop bit
Selectable 4800, 9600,
19200 and 38400 bit/s
Same as RS422/485
Alarm outputs
Alarm type
Alarm set-point
Hysteresis
On-time delay
Off-time delay
Output status
Display colour for alarms
Min response time
Output channels
(on request)
Over-range alarm, up alarm, down alarm, down alarm with start-up deactivation up alarm with latch, down alarm with latch
Adjustable from 0 to 100% of displayed electric range
0 to 100% of displayed range
0 to 255 s
0 to 255 s
Selectable: normally energized
/de-energized
Three available coloures
(green, amber, red) can be coupled to the alarm status (traffic-light function).
500 ms, with filter excluded, without alarm activation delay
1 with module BO R1
(relay output).
Relay output BO R1, R2, R4
Relay output BO R5
Insulation
Open collector output
Range
Insulation
Analogue output
Scaling factor
Accuracy
Response time
Termperature drift
Load: 20 mA output
10 V output
Insulation
Notes:
Excitation output
BQ LSE Module
Voltage
BQ LSF Module
Voltage
Insulation
2, independent with module
BO R2 (2 relay outputs).
4, independent with module
BO R4 (2 relay outputs +
2 open collector outputs).
BO R5 (4 relay outputs)
Type SPDT
AC 1: 8A, 250VAC
DC 12: 5A, 24VDC
AC 15: 2.5A, 250VAC
DC 13: 2.5A, 24VDC
Type SPST (NO)
AC 1: 5A, 250VAC
DC 12: 3A, 24VDC
AC 15: 1,5A, 250VAC
DC 13: 1,5A, 24VDC
4000 V
RMS output to measuring input,
4000 V
RMS output to power supply input.
NPN transistor type
V
ON
1.2 VDC/ max. 100 mA
V
OFF
30 VDC max.
By means of opto-couplers
4000 V
RMS output to measuring input
4000 V
RMS output to power supply input
(on request)
Module: BO AV
0 to 20 mADC, 0 to 10 VDC
Programmable within the entire retransmission range; allows to manage the retransmission of all the values from
0 to 20 mA / 0 to 10V
± 0.2% FS (@ 25°C ± 5°C)
≤
10 ms
± 200 ppm/°C
≤
700
Ω
≥
10 k
Ω
By means of opto-couplers
4000V rms output to measuring input
4000V rms output to power supply input
The two outputs cannot be used at the same time.
(on request)
13 VDC ±10% max. 50 mA
25 VDC ±10% max. 25 mA
25V rms output to measuring input
4000 V rms output to power supply input
Specifications are subject to change without notice UDM40DS 040706
UDM40
Software functions
Min / Max storage
Password
1st level
2nd level
Measurement selection
Automatic storage
(in the EEPROM) of the minimum and maximum measured value from the previous memory reset
Numeric code max 4 dgt
2 levels of data protection.
0 to 4999 completly protected.
5000 to 9999 access to programming is protected .
Alarm set-points are directly programmable from the measuring mode.
Depending on the module: measuring range and type of probe (resistance, RTD thermoresistance, TC thermocouple) or measuring type (TRMS or DC).
Integration time selection
Scaling factors
Operating mode Electrical scale compression, displayed scale compression/expansion
(max. 2 without filter, up to
Electrical range
10 with filter)
Programmable within the whole measuring range
Programmable within the Decimal point position display range
Displayed range of the variable Programmable within the display range
Diagnostics
Automatic or from 100.0 to
999.9 ms only in the current and voltage measurement.
Burn-out:
The display flashes when the limits of the display range are exceeded and the data are updated up to 20% of the rated display range.
Only temperature inputs
RTD
Digital filter
Filter operating range
Filtering coefficient
Scaling
Linearization
Points
Input range
Output range
UdmSoft
General Specifications
Operating temperature
Storage temperature
Insulation reference voltage
Insulation
Dielectric strength
Rejection
NMRR
CMRR
EMC
0° to 50°C (32° to 122°F)
(H.R. < 90% non-condensing)
-10° to 60°C (14° to 140°F)
(H.R. < 90% non-condensing)
300 V
RMS to ground
(500V input)
See table “Insulation between inputs and outputs”
4000 V
RMS for 1 minute
Safety Standards
Safety
Connections
Wire section
Housing
Dimensions
Material
Protection degree
Weight
40 dB, 40 to 60 Hz
100 dB, 40 to 60 Hz
Approvals
EN61000-6-2, IEC61000-6-2
EN61000-6-3, IEC61000-6-3
Specifications are subject to change without notice UDM40DS 040706 connection: EEE indication
Opening of probe’s connection: EEE indication probe’s short circuit:
-EEE indication.
0 to 9999
1 to 32
Selection of min value of the input range.
Selection of max value of the input range.
Selection of decimal point position.
Selection of min display value.
Selection of max display value.
Up to 16
Selectable by every single point
Selectable by every single point
Software for programming UDM40 by means of PC (Windows 95,
98se, ME, XP) by means of serial port RS485 and relevant connection cable.
The software is available in
English, Spanish, Italian,
German, French. See also
“Programming of
UDM40 by means of PC” .
EN 61010-1, IEC 61010-1
Screw type
Max 2.5mm
2
1/8 DIN, 48 x 96 x 105 mm
PC-ABS, self-extinguishing: UL 94 V-0
Front: IP67, NEMA4x
Connections: IP20
520 g approx (included all modules and packing)
CE, UR, CSA
5
UDM40
Supply Specifications
AC/DC voltage
90 to 260V (standard)
18 to 60V (on request)
Energy consumption
≤
30VA/12W (90 to 260V)
≤
20VA/12W (18 to 60V)
Excitation output
0
30
V
15
10
25
20
5
Continuous
BQ
LSF
BQ LSE max. 30 s.
10 20 30 40 50 60 mA
Insulation between inputs and outputs
Meas.
inputs
Relay output
Static output
Analogue output
Serial
Port
AUX p.supply
90-260VAC/
DC p. supply
18-60VAC/
DC p.supply
Meas.
inputs
Relay
Output
Static
Output
Analogue
Output
Serial
Port
AUX p.supply
90-260VAC/
DC p..supply
18-60VAC/
DC p. supply
-
4kV
4kV
4kV
4kV
25V
4kV
4kV
4kV
-
2kV
4kV
4kV
4kV
4kV
4kV
4kV
2kV
-
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
-
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
-
4kV
4kV
4kV
25V
4kV
4kV
4kV
4kV
-
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
-
-
4kV
4kV
4kV
4kV
4kV
4kV
-
-
Available modules Possible module combinations
Type
UDM40 main unit
DC/AC input: 200µA , 2mA, 20mA,
200mA, 2V, 20V
DC/AC input: 200µA , 2mA, 20mA,
200mA, 2V, 20V + excitation output
DC/AC input: 200mA, 2A, 5A,
20V, 200V, 500V
Input: 20Ω, 200Ω, 2kΩ, 20kΩ
TC: J-K-S-T-E, Pt100-250-500-1000
Analogue output 0 to 20mA, 0 to 10VDC
Relay output
Relay output
Outputs: 2 relays + 2 open collectors
Relay output
RS485 Serial Port
RS232 Serial Port
Power supply 18 to 60V AC/DC
Power supply 90 to 260V AC/DC
N. of channels
1
1
1
1
2
4
1
1
1
4
1
1
6
Ordering code
BD 40
BQ LSX
BQ LSE/
BQ LSF
BQ HSX
BQ TRX
BQ TRX
BO AV
BO R1
BO R2
BO R4
BO R5
BR SX
BR SY
BP L
BP H
Basic Unit
Measuring inputs:
LSX, LSE, LSF, HSX, TRX
RS485 Serial port: SX
RS232 Serial port: SY
Analogue output: AV (*)
Relay outputs and/or open collector: R1, R2, R4, R5
Power supply: H, L
(*) Up to 1 module max.
Slot A Slot B Slot C Slot D
Used calculation formulas
Only for TRMS Measurements
Instantaneous effective voltage (TRMS)
V
1
=
1
n
×
å
n
1
(
V
1
)
i
2
Instantaneous effective current (TRMS)
A
1
=
1
n
×
å
n
1
(
A
1
)
i
2
Specifications are subject to change without notice UDM40DS 040706
UDM40
Wiring diagrams
Process signal wiring diagrams
BQ LSX/LSE/LSF
Fig. 1
BQ LSX/LSE/LSF
Fig. 2
BQ LSE/LSF
Fig. 3
BQ LSE
/LSF
+
˜
Voltage measurements
˜
-
˜
+
Fig. 4
BQ LSE
/LSF
Voltage measurements
4-wire connection to probe
-
-
+
+ Vdc
Fig. 5
BQ LSE
/LSF
Fig. 6
Voltage measurements
3-wire connection to probe
-
+
+ Vdc
Current measurements
4-wire connection to probe
-
-
+
+ Vdc
Current measurements
3-wire connection to probe
-
+
+ Vdc
BQ LSE
/LSF
Fig. 7
Wirings for high-level signals
BQ HSX
Fig. 8
BQ HSX
Fig. 9
+
+ Vdc
Current measurements
2-wire connection to probe Current measurements
˜
+
˜
-
Specifications are subject to change without notice UDM40DS 040706
Voltage measurements
˜
+
˜
-
7
UDM40
Wiring diagrams (cont.)
Wiring diagrams for temperature measurements
BQ TRX
Fig. 10
BQ TRX
Fig. 11
BQ TRX
Fig. 12
Temp. measur. from thermocouple
Temp. measur. from thermoresistance
Wiring diagrams for power supply
BP H: power supply
Resistance measurements
BP L: power supply
F1= 630mA T
250V 5x20mm
F1= 3.15A T
250V 5x20mm
Wiring diagrams of optional modules
8
BO AV: analogue output
(10V, 20mA DC)
BO R1: 1 relay output BO R2: 2 relay outputs
BO R5: 4 relay outputs
Specifications are subject to change without notice UDM40DS 040706
UDM40
Wiring diagrams of optional modules (cont.)
SY
LED
BO SY: RS232 direct connection to PC by means of COM port.
RS232 has no terminalization.
Vcc
GND
RX
TX
3
2
1
5
2
3
5
9 6
1
BO R4: dual relay output + dual open collector output: the load resistances (Rc) must be designed so that the close contact current is lower than 100mA; the VDC voltage must be lower than or equal to 30VDC.
VDC: power supply output
Vo+: positive output (open collector transistor).
GND: ground collector (open collector transistor).
RS1,2,3...N
NON terminalized network
Terminalized network
BR SX: RS485 4-wire connection: additional devices provided with RS485 port (indicated as RS1,2,3...N) are connected in parallel. The termination of the serial port is carried out only on the last instrument of the network. The serial module is provided with a jumper for the termination of the RS485 network as shown in the figure above.
Note: particular types of cables or plants may require an external termination. For the network connections use twisted cable type AWG26.
Programming UDM40 by means of PC
To UDM
1
2
UDM40 is programmable by PC by means of the UdmSoft software (available on request). The user can program all parameters of UDM40 that will be subsequently uploaded and set in the instrument by the RS485 network (BR SX).
Should UDM40 be without the RS485 serial module, all programming parameters will be uploaded and set in the instrument by the RS232 auxiliary serial connection (1) located on the side of the measuring input module using the special connection cable (2) available on request, as shown in the figures on the left. It is also possible to program the instrument using the dot connector (1) by means of the HyperTerminal Windows functions of a PC.
Note: the RS232 auxiliary port IS NOT insulated from the measuring inputs.
Ordering code of the cable (2): UCOM1
To PC
Specifications are subject to change without notice UDM40DS 040706
9
UDM40
Front panel description
:
- to program values;
- to select functions;
- to scroll display pages.
: for special functions.
4 3
2
1
1. Key-pad
The programming of the configuration parameters and the display may be easily controlled by means of the 4 function keys.
: to enter the programming phase and to confirm the password.
2. Display
Instantaneous measurements:
- 4 digit (max display 9999).
Alphanumeric indications by means of LED display for:
- Display of configuration parameters;
- The measured variable.
3. Alarm status LED
Display any alarm condition
4. Engineering unit
The instrument is supplied with a complete set of self-sticking labels with the main engineering units.
Dimensions Engineering Units
11mm
105mm
48mm
96mm
45mm -0,3/+0,6
92mm -0,3/+0,8
10
Panel depth: 8mm.
Specifications are subject to change without notice UDM40DS 040706
UDM40
Modules
Input modules Output modules
Scale 1:1
BQ LSX, BQ LSE, BQ
LSF, BQ HSX, BQ TRX
Measuring inputs
BO AV
Single analogue output 10V, 20mA DC
Output modules
BO R1
Single relay output
BO R2
Dual relay output
BO R4
Dual relay output +
Dual open collector
BO R5
4 relay outputs
Serial port modules
Power supply modules
BR SX
RS485 Serial port
BR SY
RS232 Serial port
Specifications are subject to change without notice UDM40DS 040706