- Home
- Domestic appliances
- Large home appliances
- Water heaters & boilers
- American Water Heater
- U273-1373(01)
- User manual
advertisement
▼
Scroll to page 2
Gas Pressure Setting Gas Pressure Setting NOTE: For additional installation and commissioning information refer to the Operation and Installation Manual. High Pressure Potentiometer Burner test point SW1 Table 1 LPG 5"W.C. 8"W.C. 150 PSI /10.5"W.C. /13.5"W.C. 0.67"W.C. 0.83"W.C. 3.0"W.C. 3.7"W.C. 2 3 ANTI-FROST HEATER AC120V HOT NEUTRAL GROUND W W W W D6 W W W 1 GND W BK D1 SURGE PROTECTOR W BK 1 GND G/Y 3 (CN3) FLAME ROD H7 Y O P R Y Y W O BK O Y R W BK H2 MODULATING SOLENOID VALVE POV O O H3 P MAIN SOLENOID VALVE SV0 BK H4 SOLENOID VALVE 1 SV1 R BK (CENTER) H5 SOLENOID VALVE 2 SV2 O BK (LEFT) H6 SOLENOID VALVE 3 SV3 Y BK (RIGHT) R W FM H1 OVERHEAT SWITCH RR WATER FLOW CONTROL DEVICE THERMAL FUSES R BL BR Y GY F5 E1 COMBUSTION FAN GY R BL Y BR W W W W W W F4 F3 G R W P OUTGOING WATER WATER THERMISTOR DO NOT adjust the other dip switches unless specifically instructed to do so. Incorrect Dip Switch Settings can cause the water heater to operate in an unsafe condition and may damage the water heater and void the warranty. FREEZE PROTECTION (OPTIONAL) 1 2 3 4 5 6 W Y BK R ON F6 R W 13 R Y (CN12) 4 RBK G/Y 1 BK W D C (CN1) B H (CN2) E 1 12 (CN5) 1 GY F (CN7) GND 1 3 1 2 3 4 5 6 O F F (CN9) A O F F 1 2 3 4 5 6 7 8 WARNING SW No. 1 W RBK 1 2 3 4 5 6 ON O F F 1 G O F F BR O Y R W The original PC boards on the water heaters do not have the bank of 6 dip switches. Only spare PC boards have this bank. 1 2 3 4 5 6 7 8 5 ON ON O F F G1 Adjust switches 2 and 3 in the bank of 8 depending on your altitude according to the table below. WY O RBR 705(Indoor) 705(Indoor-ASME) LPG NAT.G BY-PASS FLOW CONTROL DEVICE Dip Switches Settings High Altitude MIN MAX Flame Rod: Place one lead of your meter to the flame rod and the other to ground. With the unit running you should read between 5-150 VAC. Set your meter to the µ amp scale and series your meter in line with the flame rod. You should read 1 µ amp or greater for proper flame circuit. In the event of low flame circuit remove the flame rod and check for carbon or damage. Dip SW2 1 This unit has one inline (3) amp glass fuses. Remove the fuse and check continuity through it. If you have continuity through the fuse then it is good. Otherwise the fuse is blown and must be replaced. W BK D 2 Amp Fuses: IG This unit has frost protection heaters mounted at different points to protect the water heater from freezing. The heaters located on the hot water outlet line should have a resistance reading of 180-207 ohms through each of these heaters. The heater located on the heat exchanger piping should have a resistance reading of 156-180 ohms and the one located in the water flow sensor valve should have a resistance reading 24-28 ohms. FUSE (3A) 1-3 Frost Protection: (FM) Combustion Fan Motor: Red - Black 6 ~ 45 VDC N/A E1 1-2 White - Black 5 ~ 10 VDC 9.2 ~ 9.4 K ohms E1 2-4 Yellow - Black 11 ~ 13 VDC 3.5 ~ 3.9 K ohms E1 2-3 Set your meter to the hertz scale. Reading across the white and black wires at terminals 2 and 4 you should read between 60 and 420 hertz. Thermal Fuse / Overheat Switch: F6 Red - White 11 ~ 13 VDC Below 1 ohms F6 - H12 H1 flame at flame rod. • Measure micro amp output of sensor circuit with flame present. • Replace flame rod. IGNITER B sand paper. • Check inside burner chamber for any foreign material blocking (CN4) 1-3 1-3 1.5 ~ 3.0 K ohms • Ensure flame rod is touching flame when unit fires. • Check all wiring to flame rod for damage. • Remove flame rod and check for carbon build-up; clean with W W N/A N/A WW 1-2 10 ~ 13 VDC 72 Flame Sensing Device Fault Wiring Diagram P BL BR C1 3 - 11 HEAT EXCHANGER WATER THERMISTOR (IG) Ignition System: Grey - Grey 90 ~ 110 VAC See example above F3 1 2 3 4 5 6 7 8 1-5 2-5 3-5 4-5 3-4 O F F G1 G1 G1 G1 Remote Controls: Terminals B1 connections. • Measure resistance of each solenoid valve coil. 1 By-pass Flow Control: Brown - White Orange - White 2 ~ 6 VDC 15 ~ 35 ohms (Unit in operating mode) Yellow - White Red-White - Ground See example above F4 • • • With the power off you can check the continuity through the surge protector. Place a meter lead on the top pin #1 of the surge protector and pin #3 on the bottom of the surge protector. Check across the top pin #3 and bottom pin #1. If you read continuity across these two points then the surge protector is good. If you do not get continuity then replace the surge protector. 1-3 2-3 • Check wiring harness to all solenoids for damage and/or loose LC Scale Build-up in Heat Exchanger (when checking used. maintenance code history “00” is substituted for “LC”) Check for restrictions in air flow around unit and vent terminal. • Flush heat exchanger. Refer to instructions in manual. Check for low water flow in a circulating system causing shortcycling. • Replace heat exchanger. Ensure dip switches are set to the proper position. No Code (Nothing happens when water flow is activated.) Check for foreign materials in combustion chamber and/or • Clean inlet water supply filter. exhaust piping. • On new installations ensure hot and cold water lines are not Check heat exchanger for cracks and/or separations. reversed. Check heat exchanger surface for hot spots which indicate • Check for bleed over. Isolate unit from building by turning off blockage due to scale build up. Refer to instructions in manual hot water line to building. Isolate the circulating system if for flushing heat exchanger. present. Open your pressure relief valve; if unit fires, there is Measure resistance of safety circuit. bleed over in your plumbing. Ensure high fire and low fire manifold pressure is correct. • Ensure you have at least the minimum flow rate required to fire Check for improper conversion of product. unit. • Ensure turbine spins freely. • Measure the resistance of the water flow control sensor. • Remote control does not light up but you have 12 VDC at the terminals for controls. 3 5.5 ~ 6.2 K ohms F2 1 ~ 1.4 Mega ohms F2 71 SV0, SV1, SV2, and SV3 Solenoid Valve Circuit Fault D5 • • 221°F = 0.6 ~ 0.8K D2 D1 If blank screen is present on remote control then the flow control has shorted out. Unplug flow control. If remote lights up and unit starts operating then replace flow control assembly. GY GY 9 - 10 5-7 5-8 65 Water Flow Servo Faulty (does not stop flow properly) R Y BK (M) Water Flow Control Device Servo or Geared Motor: Red - Blue 11 ~ 13 VDC 22 ~ 28 ohms F5 Grey - Brown 4 ~ 6 VDC N/A F5 Grey - Yellow N/A N/A F5 NOTE: The grey wire listed above turns to black at F connector on the PCB. Outgoing Water Thermistor: White - White N/A Heat Exchanger Temperature Thermistor: Pink - White N/A Surge Protector: Black - White 108 ~ 132 VAC Black - White 108 ~ 132 VAC connections. • Measure resistance of motor winding. GY GY Fig. 6 86°F = 6.4 ~ 7.8K 113°F = 3.6 ~ 4.5K (SV1, SV2, SV3 and POV) Gas valve and Modulating solenoids: (Set meter above 2K) Wire color Voltage Resistance Connector # Pin #'s (Main) Pink - Black 11 ~ 13 VDC 24 ~ 28 ohms H3 6-7 (SV1) Black - Red 11 ~ 13 VDC 37 ~ 43 ohms H4 5-6 (SV2) Black - Orange 11 ~ 13 VDC 37 ~ 43 ohms H5 4-6 (SV3) Black - Yellow 11 ~ 13 VDC 37 ~ 43 ohms H6 3-6 (POV) Orange - Orange 2 ~ 15 VDC 67 ~ 81 ohms H2 9 - 10 N/A • • Check all thermistors by inserting meter leads into each end of the thermistor plug. Set your meter to the 20 K scale and read resistance. Applying heat to the thermistor bulb should decrease the resistance. Applying ice to the thermistor bulb should increase the resistance. See below for examples of typical temperatures and resistance readings. 59°F = 11.4 ~ 14K 140°F = 2.2 ~ 2.7K Example: There are a number of (live) tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact with energized components inside the water heater. Only trained and qualified service technicians should attempt to repair this product. Before checking for resistance readings, disconnect the power source to the unit and isolate the item from the circuit (unplug it). • Ensure fan will turn freely. • Check wiring harness to motor for damaged and/or loose D4 Troubleshooting 61 Combustion Fan Failure • Check gas type of unit and ensure it matches gas type being • • Fig. 5 or damage terminals. meter. Check for obstructions in the flue outlet. Ensure gas line, meter, and/or regulator is sized properly. Ensure gas type and pressure is correct. Bleed all air from gas lines. Ensure proper venting material was installed. Ensure condensation collar was installed properly. Ensure vent length is within limits. Verify dip switches are set properly. Ensure appliance is properly grounded. Disconnect keypad. Disconnect multi-unit connections to isolate the problem. Check power supply for loose connections. Check power supply for proper voltage and voltage drops. Ensure flame rod wire is connected. Check flame rod for carbon build-up. Disconnect and re-connect all wiring harnesses on unit and PC board. • Check all components for electrical short. • Check gas solenoid valves for open or short circuits. • Remove burner plate and inspect burner surface for condensation or debris. Fig. 4 Heat Exchanger and Outgoing Water Temperature Thermistors: Important Safety Notes (QS) Water Flow Sensor: Black - Red 11 ~ 13 VDC Yellow - Black 4 ~ 7 VDC Fig. 3 • Check modulating gas solenoid valve wiring harness for loose W W With all gas appliances in operation at maximum gas rate, the flowing inlet pressure at the incoming test point on the Rinnai water heater should read 5" W.C. - 10.5" W.C. on natural gas and 8" W.C. - 13.5" W.C. on propane gas. If the pressure is lower, the gas supply is inadequate and the unit will not operate to specification. Check the gas meter regulator and pipework for correct operation/sizing and correct as required. 52 Modulating Solenoid Valve Signal Abnormal 14 Thermal Fuse Regulator adjustment screw access plug Commissioning Check for restrictions in air flow around unit and vent terminal. Check sensor wiring for damage. Measure resistance of sensor. Clean sensor of scale build up. Ensure fan blade is tight on motor shaft and is in good condition. • Replace sensor. • • • • • • • • • • • • • • • R Y BK NAT.G • • • • • • Check that the gas is turned on at the water heater and gas QS LPG 34 Combustion Air Temperature Sensor Fault 12 Flame Failure WATER FLOW SENSOR NAT.G Forced High Check sensor wiring for damage. Measure resistance of sensor. Clean sensor of scale build up. Replace sensor. • Measure resistance of valve coil. Dip SW1 LPG Forced Low or cylinder. Ensure gas type and pressure is correct. Ensure gas line, meter, and/or regulator is sized properly. Bleed all air from gas lines. Verify dip switches are set properly. Ensure appliance is properly grounded. Disconnect multi-unit connections to isolate the problem. Ensure igniter is operational. Check igniter wiring harness for damage. Check gas solenoid valves for open or short circuits. Remove burner cover and ensure all burners are properly seated. • Remove burner plate and inspect burner surface for condensation or debris. • • • • • • • • • • F1 705(Indoor-ASME) Fig. 2 • Check that the gas is turned on at the water heater, gas meter, F2 NAT.G 705(Indoor) Fig. 1 Gas Inlet Min./Max Water Inlet Max. SW2 Spare Parts Only • • • • 11 No Ignition COLOR CODING APPLIANCE OPERATING PRESSURES 1 33 Heat Exchanger Outgoing Temperature Sensor Fault WW This appliance must be installed, serviced and removed by a trained and qualified person. During pressure testing of the consumer piping, ensure gas valve is turned off before unit is shut off. Failure to do so may result in serious injury to yourself or damage to the unit. Check sensor wiring for damage. Measure resistance of sensor. Clean sensor of scale build up. Replace sensor. D3 WARNING • • • • W W To turn the sound off (mute), press and hold both the and thermostat buttons until a “beep” is heard (about 5 seconds). 32 Outgoing Water Temperature Sensor Fault Ensure approved venting materials are being used. Check that nothing is blocking the flue inlet or exhaust. Check all vent components for proper connections. Ensure vent length is within limits. Ensure condensation collar was installed correctly. Verify dip switches are set properly. Check fan for blockage. SPARK ELECTRODE To Turn Off the Controller Sound (Mute) • • • • • • • C1 With the water heater turned off, press and hold the ON/OFF button until the display changes to the other temperature scale (about 5 seconds). 10 Air Supply or Exhaust Blockage FROST SENSING SWITCH To Change the Temperature Scale (ºF / ºC) exhaust piping. • Check for clogged heat exchanger. BL BL 1. To display error codes, press the ON/OFF button followed by the thermostat button to cycle through the error codes. 2. To display the water flow through the water heater, press the thermostat button (hold for 2 seconds) and then press the ON/OFF button while continuing to hold the thermostat button. 3. To display the outlet water temperature, press the thermostat button (hold for 2 seconds) and then press the ON/OFF button while continuing to hold the thermostat button. • Turn off all hot water taps. Press ON/OFF twice. REMOTE CONTROLLER Diagnostic Use of the Controller • Check for foreign materials in combustion chamber and/or B1 ON/OFF Button cycling. power returns) MODULATING VALVE CURRENT ADJUSTING Thermostat Turn OFF the gas supply. Turn OFF the 120 V power supply. Remove the front panel from the appliance. Check the gas type using the data plate on the side of the unit. If using a spare PC board, check that the gas type switches are in the correct position (dip switch 1 of SW2: ON for natural gas, NG, and OFF for propane, LPG). See dip switch settings section below. (ON is towards the right and OFF is towards the left.) 5. Attach the pressure gauge to the burner test point, located on the gas control (Fig. 2). 6. Turn ON the gas supply. 7. Turn ON the 120 V power supply. 8. If a controller is installed, turn the unit ON with the controller. Select the maximum delivery temperature and open all available hot water taps at full. 9. Set the unit to ‘Forced Low’ combustion by setting No. 7 dip switch of the SW1 set to ON (Fig. 3). 10. Check the burner test point pressure. 11. Remove the rubber access plug and adjust the regulator screw on the modulating valve (Fig. 4) as required in Table 1. Replace the rubber access plug. 12. Set the unit to ‘Forced High’ combustion by setting both No. 7 and No. 8 dip switches of the SW1 set to ON (Fig. 5). Ensure maximum water flow. 13. Check the burner test point pressure. 14. Adjust the high pressure potentiometer (POT) on the PC board as required to the pressure shown in Table 1. 15. Return the unit to normal operation by setting dip switches 7 and 8 of the SW1 set back to OFF (Fig. 6). Close all water taps. 16. Turn OFF the gas supply and 120 V power supply. 17. Remove the pressure gauge and install sealing screw. 18. Turn ON the gas supply and 120 V power supply. 19. Operate the unit and check for gas leaks at the test point. 20. Install the front panel. 03 Power interruption during Bath fill (Water will not flow when BK BK Priority Button When no water is being supplied, pressing this button allows this controller to set the water temperature. 1. 2. 3. 4. • Check for restrictions in air flow around unit and vent terminal. • Check for low water flow in a circulating system causing short- • Service Call A1 2-Unit Connection (Optional) Temperature Display Indicates temperature setting or flashes error code. 16 Over Temperature Warning 02 No burner operation during freeze protection mode Gas type Spare Parts Only Priority Indicator Indicates that this controller is setting the water temperature. Error Codes Gas pressure In Use Indicator Indicates that hot water is being supplied. Ensure gas pressure check under Commissioning has been completed first! The regulator is electronically controlled and factory pre-set. Under normal circumstances it does not require adjustment during installation. Make adjustments only if the unit is not operating correctly and all other possible causes for incorrect operation have been eliminated. W :White BK:Black BR:Brown R :Red BL:Blue Y :Yellow P :Pink O :Orange G :Green GY:Gray Controller NOTES High Altitude Off Off Level 0 0-2000 ft (0-610 m) Off On Level 1 2001-5200 ft (610-1585 m) On Off Level 2 5201-7700 ft (1585-2347 m) On On Level 3 7701-10200 ft (2347-3109 m) 705 Indoor 070 00012 36676 0 U273-1373(01) EXPLODED VIEW - CABINET EXPLODED VIEW - INTERNALS REMOTE CONTROLLER EXPLODED VIEW - INTERNALS EXPLODED VIEW - ELECTRICAL 703 Number 001 002 004 005 007 010 011 012 013 014 015 017 018 019 020 021 022 100 101 102 103 103 104 104 113 114 115 116 117 118 121 122 123 124 125 125 Description Casing Assembly Heat Protection Plate Front Panel Assembly Remote Controller Packing Wall Fitting Bracket Front Panel Packing-Top Front Panel Packing-Side Connection Reinforcement Panel Bag for Installation Manual Seal Packing Rubber Bushing Rubber Bushing Reinforcement Plate Air Intake Vent ϕ 100 Seal Plate Duct Bracket Fan Rectifier Gas Connection (3/4"NPT) Screw Gas Control Kit Manifold Assembly-A (LPG) Manifold Assembly-B (Nat.G) Burner Unit Assembly(Nat.G) Burner Unit Assembly(LPG) Combustion Chamber Front Plate Combustion Chamber Front Plate Packing Electrode Kit Flame Rod Kit Electrode Packing Electrode Holder Electrode Sleeve Solenoid Valve Cover Upper Combustion Chamber Packing Lower Combustion Chamber Packing Heat Exchanger Kit Heat Exchanger Kit(ASME) Quantity 705 705 (Indoor) (Indoor-ASME) Parts Number 701022-150 1 1 701022-154 1 1 701022-155 1 1 701022-159 1 1 701022-160 2 2 701022-162 2 2 701022-163 2 2 701022-164 1 1 701022-165 1 1 701022-023 1 1 701022-008 1 1 701022-020 1 1 701022-166 1 1 701022-167 1 1 701022-168 1 1 701022-169 2 2 701022-170 1 1 701022-027 1 1 701022-171 2 2 701022-172 1 1 701022-173 1 1 701022-174 1 1 701022-175 1 1 701022-153 1 1 701022-182 1 1 701022-183 1 1 701022-036 1 1 701022-184 1 1 701022-185 1 1 701022-039 1 1 701022-093 1 1 701022-186 1 1 701022-187 1 1 701022-188 1 1 701022-189 1 701022-158 1 - Quantity 705 705 (Indoor-ASME) (Indoor) Parts Number 701022-191 1 1 701022-192 1 1 701022-193 2 2 701022-194 1 1 701022-195 1 1 701022-197 1 1 701022-198 1 1 701022-199 1 1 701022-069 1 1 701022-200 1 1 701022-082 1 1 701022-203 1 1 701022-204 1 1 701022-074 1 1 701022-075 2 2 701022-205 1 1 701022-206 1 1 701022-207 1 1 701022-081 1 1 701022-208 1 1 701022-209 1 1 701022-210 1 1 701022-211 1 1 701022-088 1 1 701022-213 1 1 701022-091 1 1 701022-214 1 1 701022-215 1 1 701022-216 1 1 701022-102 2 2 701022-151 2 2 701022-218 1 1 701022-219 2 2 701022-221 1 1 701022-222 9 9 701022-120 2 2 PARTS LIST Number 131 132 133 150 151 153 154 155 400 401 402 405 406 407 408 409 410 411 412 413 700 701 702 703 704 705 706 707 708 709 710 711 712 714 715 716 Description Flue Outlet Vent Packing Flue Outlet Vent Assembly ϕ 100 Packing Blower Motor Fan Casing Assembly Fan Connecting Bracket Fan Connecting Packing ϕ 39 Bell Mouth Water Inlet (3/4"NPT) Plug Band Water Filter Assembly Water Flow Control Assembly Kit Rectifier Bypass-Servo Assembly Stop Bracket Water Flow Servo Cover Hot Water Outlet (3/4"NPT) Plug Band Drain Valve Stop Bracket PCB Surge Protector PCB Cover-Front PCB Cover-Side Ignitor Bracket Ignitor High Tension Cord Ignitor Cover 120V Anti Frost Heater Assembly Anti Frost Heater Clip Anti Frost Heater Clip Anti Frost Heater Clip 120V Valve Heater Assembly Thermal Fuse Harness Thermal Fuse Clip Thermistor Number 717 718 720 721 722 723 724 725 726 800 801 802 803 804 805 806 807 808 809 810 811 812 813 814 815 816 817 820 821 822 823 824 888 889 - Description Thermistor Clip Frost Sensing Switch Fuse Harness Power Supply Harness Ignitor Harness Sensor Harness Power Cord Remote Controller Remote Controller Bracket Screw Washer Screw Washer Screw Screw Screw Screw Screw Screw Screw O-ring O-ring O-ring O-ring O-ring O-ring Packing Screw Screw Screw Screw Screw Manual Installation Manual (Tech Sheet) Package Spec Sheet Manual 3/4" Gas Control Valve Parts Number 701022-095 701022-223 701022-224 701022-226 701022-227 701022-228 701022-107 701022-229 701022-231 701022-122 701022-232 701022-233 701022-128 701022-234 701022-121 701022-235 701022-236 701022-237 701022-238 701022-125 701022-137 701022-133 701022-134 701022-135 701022-136 701022-130 701022-239 701022-240 701022-241 701022-141 701022-242 701022-142 315897-000 701022-244 701022-246 701022-247 Quantity 705 705 (Indoor) (Indoor-ASME) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 4 4 4 2 2 7 7 10 10 8 8 1 1 5 5 2 2 3 3 1 1 1 1 3 3 1 1 2 2 1 1 2 2 1 1 2 2 1 1 4 4 2 2 3 3 1 1 1 1 1 1 1 1
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project