APC 3000 Power Supply User`s manual

Add to my manuals
23 Pages

advertisement

APC 3000 Power Supply User`s manual | Manualzz

APC Smart-UPS

Uninterruptible Power Supply

Model 5000RMB

User’s Manual

990-7080B 09/00

Entire contents copyright ©2000 by American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited. Smart-UPS is a registered trademark of APC. All other trademarks are the property of their respective owners.

990-7080B 09/00

Smart UPS Safety Guide English

This Safety Guide contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries.

It is intended for APC customers who setup, install, relocate, or maintain APC equipment.

Handling Safety

Be careful. Do not lift heavy loads without assistance.

Þ <18 kg (<40 lb)

32-55 kg (70 – 120 lb)

Þ 18 – 32 kg (40 – 70 lb)

.

>55 kg (>120 lb)

Equipment with casters is built to move on a smooth surface without any obstacles.

Do not use a ramp inclined at more than 10

°

.

This equipment is intended for installation in a temperature-controlled indoor area (

0 to 40

§C (+32 to +104§F)

), free of conductive contaminants.

Electrical Safety

Do not work alone under hazardous conditions.

High short circuit current through conductive materials could cause severe burns.

A licensed electrician is required to install permanently wired equipment.

Check that the power cord(s), plug(s), and sockets are in good condition.

To reduce the risk of electric shock when grounding cannot be verified, disconnect the equipment from the AC power outlet before installing or connecting to other equipment. Reconnect the power cord only after all connections are made.

Do not handle any kind of metallic connector before the power has been removed.

Use one hand, whenever possible, to connect or disconnect signal cables to avoid a possible shock from touching two surfaces with different electrical grounds.

Connect the equipment to a three wire AC outlet (two poles plus ground). The receptacle must be connected to appropriate branch circuit/mains protection (fuse or circuit breaker). Connection to any other type of receptacle may result in a shock hazard.

In order to maintain compliance with the EMC directive, output cords attached to the UPS should not exceed 10 meters in length.

CAUTION! Deenergizing Safety

If the equipment has an internal energy source (the battery), the output may be energized when the unit is not connected to an AC power outlet.

To deenergize pluggable equipment: first press the Off button for more than one second to switch the equipment off. Next disconnect the equipment from the AC power outlet. Finally, disconnect the battery.

To deenergize permanently wired equipment: set the power switch to standby . Next set the AC circuit breaker to standby . Then disconnect the batteries (including any expansion units). Finally, disconnect the AC power from the building power supply.

Pluggable equipment includes a protective earth conductor which carries the leakage current from the load devices (computer equipment). Total leakage current must not exceed 3.5 mA.

Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly effect its safety or effectiveness is not recommended.

WARNING! Battery Safety

This equipment contains potentially hazardous voltages. Do not attempt to disassemble the unit. The only exception is for equipment containing batteries. Battery replacement using the procedures below is permissible. Except for the battery, the unit contains no user serviceable parts. Repairs are performed only by factory trained service personnel.

Batteries must be recycled. Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new battery’s packing material. See the new battery instructions for more information.

Do not dispose of batteries in a fire. The batteries may explode.

Do not open or mutilate batteries. They contain an electrolyte which is toxic and harmful to the skin and eyes.

To avoid personal injury due to energy hazard, remove wrist watches and jewelry such as rings when replacing the batteries. Use tools with insulated handles.

Replace batteries with the same number and type of batteries as originally installed in the equipment.

Replacement and Recycling of Batteries

See your dealer or the Battery Replacement section of this User’s Manual for information on replacement battery kits and battery recycling.

990-7080B 09/00

Table of Contents

Introduction.............................................................................................................................................................................1

Unpacking ...............................................................................................................................................................................1

Installation ..............................................................................................................................................................................2

Initial Startup ..........................................................................................................................................................................7

Operating Instructions.............................................................................................................................................................8

Replacing the Battery............................................................................................................................................................10

Storage ..................................................................................................................................................................................11

User Configuration Items ......................................................................................................................................................11

On-Battery Run Time............................................................................................................................................................12

Specifications........................................................................................................................................................................13

Troubleshooting ....................................................................................................................................................................14

Service ..................................................................................................................................................................................15

APC Contact Information .....................................................................................................................................................15

Limited Warranty..................................................................................................................................................................15

Appendix A: Regulatory Agency Approvals........................................................................................................................16

200/208 Vac Units ................................................................................................................................................................16

230 Vac Units .......................................................................................................................................................................16

Appendix B: Transporting Your Smart-UPS .......................................................................................................................17

990-7080B 09/00

Introduction

This Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags and surges from reaching your computer and other valuable electronic equipment. This UPS also filters out small utility line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line, while supplying power from its internal batteries until the utility line returns to safe levels.

While running on battery, an internal alarm will sound (periodic beeps). The on/test button may be pressed to silence the

UPS alarm.

If the utility power does not return, the UPS will continue supplying power to the connected equipment until exhausted. A continuous beeping will sound two minutes before the UPS’s final low battery shutdown. If using a computer, you must manually save your files and power down before the UPS turns itself off, unless you are using PowerChute

interface software that provides automatic, unattended shutdown.

Unpacking

Inspection

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.

Contents

The shipping package contains the UPS, its batteries, and, for rack mount units, rails to hold the UPS in a rack. The 5000

VA unit ships with the batteries separate from the UPS case.

How to Unpack the SU 5000 UPS

Move the UPS, in its shipping package, as close to the desired location as possible. Then follow these instructions:

Use scissors or a knife to cut the plastic straps and open the package.

Read this User’s Manual for safety information and installation instructions.

Unpack the box containing the mounting rails.

Remove the foam spacers.

Lift off the cardboard box that covers the top and sides of the package. The bottom of the box is formed by a wooden pallet.

Lift the UPS up and out of the box.

Pull the plastic bag down to expose the

UPS.

Remove the batteries from the pallet.

Caution:

The UPS (without batteries installed) requires two people to install due to its weight.

1

Installation

Installing your UPS requires five steps:

1. Position and install the UPS in the rack. This step includes installing the rails into the rack.

2. Install and connect the batteries.

3. Connect equipment to the UPS.

4. Power up the UPS.

5. Install PowerChute® UPS monitoring software and accessories.

Each step is covered in a following section.

1.

Position the UPS

Placement

S m U P S S m U P

S

S m U P S

Install the UPS in a protected area that is free of excessive dust and has adequate air flow. Do not operate the UPS where the temperature and humidity are outside the specified limits.

Warning!

Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the warranty.

Installing the SU5000RMB

The rack mount UPS comes with standard 19-inch (46.5 cm) rack mount brackets (ears) installed. Mounting rails to support the unit are included. These supports may be used to ease installation for 19-inch or 23-inch racks.

Caution:

Two or more people are required to install the 5000 VA model due to its weight.

Mount the UPS in the rack before installing the batteries.

Installing the UPS in a rack involves a four-step process:

1. Determine the location of the UPS in the rack.

2. Install the mounting rails in the rack.

3. Load the UPS into the rack.

4. Attach the mounting brackets to the rack.

This section describes each step in detail.

Determine the Location of the UPS in the Rack

UPSs are heavy. Select a rack location sturdy enough to handle the weight. Mount the UPS at or near the bottom of the rack.

Select a rack location with adequate air flow that is free from excessive dust. Ensure that any air vents on the sides of the UPS are not blocked.

Do not operate the UPS where temperature or humidity are outside the limits listed under Specifications, page

13.

2

Install the Mounting Rails in the Rack

Œ

Left Front

Rack Post

1. Determine where in the rack you will mount the UPS. The

SU5000 requires a space of 5U. Some racks have tick marks to indicate the U-spaces.

2. Using the mounting template provided (part number 990-0195), identify and mark the correct mounting holes for the UPS mounting brackets.

3. Locate and mark the bottom hole in the designated U-space

Œ.

The bottom screw on the mounting rail will attach to the bottom hole in the U-space.

4. Repeat steps 2 and 3 for the remaining three rack posts.

5. Prepare the rack holes, if necessary. Racks with threaded holes require no preparation.

If your rack has round holes, insert clip nuts (provided) into the holes marked in step 2.

If your rack has square holes, insert either clip or cage nuts into the holes marked in step 2.

6. Align the bottom hole on the mounting rail with the bottom hole in the U-space (marked in step 3 above). Position the rails so that the lip of the rail is on the bottom.

Note: The rails are marked “L” and “R.” Mount the rail labeled

“L” on the left-hand side of the rack and the rail labeled “R” on the right-hand side of the rack.

Use the flat, Phillips head screws (10-32) and conical washers to attach the front rail to the rack. Attach the rails to the rack using three (3) screws per rail, as shown.

7. Expand the rails so that it spans from the front rack post to the back rack post.

Right Rear Rack Post

8. Attach the rail to the back rack post using the same hardware

(10-32 flat head screws and conical washers) used in step 6.

Repeat steps 6 through 8 for the other rails.

3

Load the UPS into the Rack and attach the Mounting Brackets

Caution:

The 5000 VA models (without batteries installed) require two people to lift due to its weight.

Attach the Rail Cleat

Attach a mounting cleat to each side of the UPS using two (2) flat head screws per cleat.

Load the UPS into the Rack

Supporting the UPS from the front and back, carefully align the cleat with the rails. Slide the

UPS into position.

Screws shown on the right rack post only.

Install four screws on the left rack post as well.

Attach the Mounting Brackets to the Rack

Use the eight ornamental screws (four per side), to attach the mounting brackets to the rack post. The figure displays the placement of four ornamental screws on the right rack post.

2. Connect Input Power to the UPS

208 Vac Units

1. Connect the UPS line cord (L6-30 plug) into an appropriate electrical outlet.

2. Ensure that all circuit breakers, located on the rear panel, are in the “On” (up) position. The following figure shows each circuit and its circuit breaker.

ON

ON

ON ON

230 Vac Units with Line Cord

Connect the UPS line cord (IEC-309 plug) into an appropriate electrical outlet.

4

230 Vac Units (for Hard Wire)

Caution:

The electrical connection must be made by an authorized electrician according to national and local regulations.

Verify that the supply line contains a 25 Amp circuit breaker BEFORE hardwiring the UPS.

Ensure that the batteries are not installed in the UPS until the hardwiring is complete.

Incorporate a readily accessible disconnect device in the fixed wiring design.

1. Select the appropriate wire size and connectors. For most applications, #10 AWG (5 sq. mm) wire should be sufficient.

2. The input wiring terminal is located on the rear panel of the UPS. Remove the access door

Πby unscrewing the single screw

 which holds it in place.

Œ 

Ž

3. Slide the wire input plate

Ž to the left to remove it. This will expose the input wiring terminal.

4. Use a screwdriver or any hard object to detach the circular knockout. You may need to use pliers to fully detach the knockout.

5. Feed the wire cable through the hole in the wire input plate. Using a threaded lock nut, fasten the plate to the selected cable or conduit connector.

6. Use a knife or pliers to strip off the plastic on the end of the cable to expose the copper wire. Strip all three wires.

7. Use a flathead screwdriver to connect the wires to the terminal block inside the UPS. Loosen the screw, then feed the copper wire into the terminal block and tighten the screw. Connect the protective earth ground to the terminal block at the position marked with the ground symbol ( ). The UPS wiring color code is:

GREEN for GROUND

WHITE for NEUTRAL

BLACK for HOT

8. Once all the wires are connected to the terminal block, reconnect the wire input plate to the UPS. Align the plate, position it into the grooves, and slide it to the right.

9. Inspect the connections and location of the excess wires before installing the access door.

10. Replace the access door and fasten with the screw (removed in step 2).

5

3. Install the Batteries

Note:

All UPSs ship with the batteries disconnected. In addition, 5000 VA units have the batteries shipped outside the

UPS case so you must install the batteries before connecting them.

If you need to ship the UPS you must disconnect the batteries prior to shipment in order to comply with U.S.

Federal Regulations. Refer to Appendix B: Transporting Your Smart-UPS, page 17, for details.

Graphics are not drawn to scale. They are shown for reference only.

1. Reach into the finger pull and open the front cover. Swing the cover open as shown.

Remove the front bezel by grasping the finger clips on the side of the bezel and carefully loosening the four (4) snaps. Skip to step 3.

2. Unhook the side of the cover from the chassis and lift it away to expose the battery door.

3. Use a screwdriver or a coin to remove the two (2) battery door screws and open the door.

4. To connect the battery (or set), press the gray connector into the plug at the top of the battery housing. You may see small sparks when connecting the battery.

Note:

There are four (4) battery packs that must be installed. Be careful lifting the batteries they are heavy. Support the bottom of the batteries as you move them.

5. Hold the battery pack so that the leads are on the right hand side.

Slide the battery pack into the UPS.

Press the gray connector into the plug at the right-hand side of the battery compartment.

Tuck the white cord (that serves as a handle for the connector) neatly to the side.

6. Repeat step 5 for the remaining three (3) battery packs.

7. Close the battery door, replace the screws, and replace the front cover.

4.

Connect Equipment to the UPS

Use your equipment’s power cords to connect to the UPS.

Caution:

DO NOT use a standard serial interface cable to connect to the Computer Interface Port on the UPS. Standard serial interface cables are incompatible with the UPS connector. Use the cable provided with your UPS.

Turn on all connected equipment.

5. Power up the UPS and Accessories

Press the UPS’s ON switch to turn on your UPS. This will power-up connected equipment.

The unit performs a self-test automatically when turned on, and every two weeks thereafter.

The UPS charges its battery whenever it is connected to utility power. The battery charges fully during the first four hours of normal operation. Do not expect full run time during this initial charge period.

6. Install PowerChute and Accessories

Note:

This UPS is equipped with a SmartSlot for accessories. See the APC Website (www.apcc.com) for available accessories. If a standard accessory is installed in this UPS, a User’s Manual for the accessory is included in the package.

For additional computer system security, install PowerChute UPS monitoring software. It provides automatic unattended shutdown capabilities on most major network operating systems. Once PowerChute is loaded, install the PowerChute® black communication cable between UPS and computer. See the Software Installation: Instruction Sheet for details.

6

Initial Startup

Rear View

200/208 Vac 230 Vac 230 Vac with line cord

Charge the battery

The UPS charges its battery whenever it is connected to utility power. The battery will charge fully during the first four hours of normal operation. Do not expect full runtime during this initial charge period.

Connect Computer Interface Port (Optional)

Power management software and interface kits can be used with this UPS. Use only kits supplied or approved by the manufacturer. If used, connect the interface cable to the 9-pin computer interface port on the back panel of the UPS.

Secure the connector’s screws to complete the connection.

Caution:

DO NOT use a standard serial interface cable to connect to the Computer Interface Port on the UPS. Standard serial interface cables are incompatible with the UPS connector. Use the cable provided with your UPS.

Connect Ground Leads to TVSS Connector (Optional)

The UPS features a TVSS connector for connecting the ground lead on transient voltage surge-suppression (TVSS) devices such as telephone and network line protectors. The TVSS connector provides grounding through the UPS’s power cord ground conductor. To make a connection to the TVSS connector, loosen the screw and connect the surge suppression device’s ground lead. Tighten the screw to secure the lead.

Voltage Sensitivity

The UPS detects line voltage distortions such as spikes, notches, dips, and swells, as well as distortions caused by operation with inexpensive fuel-powered generators. By default, the UPS reacts to distortions by transferring to on-battery operation to protect the loads. Where power quality is poor, the UPS may frequently transfer to on-battery operation. If the loads can operate normally under such conditions, battery capacity and service life may be conserved by reducing the sensitivity of the UPS.

To reduce UPS sensitivity, press the configuration button on the rear panel. Use a pointed object such as a pen to press the button. Press it once to set the UPS’s sensitivity to reduced. Press it again to set the sensitivity to low. Press the button a third time to reset normal sensitivity.

normal reduced low

When the UPS is set to normal sensitivity, the configuration LED is brightly lit.

When it is set to reduced sensitivity, the LED is dimly lit.

When it is set to low sensitivity, the LED is off.

Low Battery Warning Interval

By default, the low battery warning occurs when there are approximately two minutes of on-battery run time remaining.

This may not be enough time to gracefully shut down some protected computer systems.

To change the warning interval, press the rear panel configuration button while pressing and holding the front-panel on/test button.

2 min.

When the LED is brightly lit, the low battery warning interval is roughly 2 minutes. This is the initial setting.

5 min.

7 min.

When the LED is dimly lit, the low battery warning interval to approximately five minutes.

When the LED is off, the low battery warning interval is approximately seven minutes.

Press the button a third time to reset the interval to two minutes.

7

Operating Instructions

Switch On — Switch Off

With the UPS plugged in, press and release the large upper on/test button to supply power to the loads. The loads are immediately powered while the UPS beeps and performs a self-test.

Press and release the small, lower off button to turn off power to the loads. It may be convenient to use the UPS as a master on/off switch for the protected equipment.

Note:

Whenever the UPS is plugged in and utility voltage is present, the charger maintains battery charge.

The on-line LED illuminates when the UPS is supplying utility power to the loads.

On Battery

During on-battery operation, the on-battery LED illuminates and the UPS sounds an audible alarm consisting of four beeps every 30 seconds. The alarm stops when the UPS returns to on-line operation.

Battery Charge Bar Graph

100%

80%

60%

40%

20%

The 5-LED display on the right of the front panel shows the present charge of the UPS’s battery as a percentage of the battery’s capacity. When all five LEDs light, the battery is fully charged. The top LED goes out whenever the battery is not 100% charged. When the lowest LED is flashing, the battery can supply less than two minutes of run time for the load. The battery capacity threshold is shown in the figure to the left (values are not listed on the UPS).

Shutdown Mode

In shutdown mode the UPS stops supplying power to the load, waiting for the return of utility power. If there is no utility power present, external devices (e.g., servers) connected to the computer interface or the accessory slot can command the UPS to shut down. This is normally done to preserve battery capacity after the graceful shutdown of protected servers. The UPS will scroll the front panel indicators sequentially in shutdown mode.

Self-test

The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default). Automatic selftest eases maintenance requirements by eliminating the need for periodic manual self-tests.

During the self-test, the UPS briefly operates the loads on-battery. If the UPS passes the self-test, it returns to on-line operation.

If the UPS fails the self-test it immediately returns to on-line operation and lights the replace battery LED.

The loads are not affected by a failed test. Recharge the battery overnight and perform the self-test again. If the replace battery LED is still on, replace the battery using the procedure in Replacing the Battery, page 10.

Replace Battery

If the battery fails a self-test, the UPS emits short beeps for one minute and the replace battery LED illuminates. The UPS repeats the alarm every five hours. Perform the self-test procedure to confirm replace battery conditions. The alarm stops when the battery passes the self-test.

8

Load Bar Graph

85%

67%

50%

33%

17%

The 5-LED display on the left of the front panel represents the power drawn from the UPS as a percentage of total capacity. For example, if three LEDs are lit, the load is drawing between 50% and 67% of the UPS’s capacity. If all five LEDs light, thoroughly test your complete system to make sure that the UPS will not become overloaded.

In the graph to the left the load capacity threshold is listed next to the LED (values are not listed on the UPS).

Overload

When the UPS is overloaded (the connected loads exceed the maximum specified in the “maximum load” section under

Specifications, page 13), the overload LED comes on and the UPS emits a sustained tone. The alarm remains on until the overload is removed. Disconnect nonessential load equipment from the UPS to eliminate the overload.

SmartTrim

The SmartTrim LED comes on to indicate that the UPS is compensating for a high voltage.

SmartBoost

The SmartBoost LED comes on to indicate that the UPS is compensating for a low voltage.

Low Battery

When the UPS is operating on-battery and the energy reserve of the battery runs low, the UPS beeps continuously until the

UPS shuts down from battery exhaustion or returns to on-line operation.

Cold Start

When the UPS is off and there is no utility power, use the cold start feature to apply power to the loads from the UPS’s battery.

Note:

Cold start is not a normal condition.

Press and hold the on/test button until the UPS beeps.

Release the on/test button during the beep and the loads are powered within four seconds.

239

223

208

193

177

Utility Voltage Bar Graph

This UPS has a diagnostic feature that displays the utility voltage. With the UPS plugged into the normal utility power, press and hold the on/test button to see the utility voltage bar graph display. After approximately four seconds the 5-LED display on the right of the front panel shows the utility input voltage. Refer to the figure to the left for the voltage reading (values are not listed on the UPS).

The display indicates that the voltage is between the displayed value from the list and the next higher value. For example, with three LEDs lit, the input voltage is between 208 and 223 Vac.

If no LEDs come on and the UPS is plugged into a working AC power outlet, the line voltage is extremely low.

If all five LEDs come on, the line voltage is extremely high and should be checked by an electrician.

Note:

The UPS starts a self-test as a part of this procedure. The self-test does not affect the voltage display. The utility voltage bar graph has a margin of error of

±±±±

4%.

9

Replacing the Battery

This UPS has an easy to replace hot-swappable battery. Battery replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and loads on for the following procedure. See your dealer or call the number listed under

APC Contact Information, page 15, for information on replacement battery cartridges.

Note:

Please read the cautions in the Safety section at the beginning of this User’s Manual.

Once the battery is disconnected, the loads are not protected from power outages.

Model Number

SU5000RMB

Replacement Battery Cartridge (RBC) #

RBC 12 (two required)

Battery Replacement Procedure

1. Reach into the finger pull and open the front cover. Swing the cover open as shown.

Remove the front bezel by grasping the finger clips on the side of the bezel and carefully loosening the four (4) snaps. Skip to step 3.

2. Unhook the side of the cover from the chassis and lift it away to expose the battery door.

3. Use a screwdriver or a coin to remove the two (2) battery door screws and open the door.

4. Disconnect the front battery pack: grip the white cord on the front set of batteries and pull firmly to disconnect the connector.

5. Pull the front battery out of the UPS by pulling on the clear label, not the white cord.

Notes:

Be careful removing the batteries - they are heavy. Support the bottom of the batteries as you remove them. There are four sets of batteries

.

6. Reach into the battery compartment and grasp the white cord on the other battery connector.

Pull firmly to disconnect the connector and remove the rear set of batteries.

7. Slide the rear set of new batteries into the unit.

Hold the battery pack so that the leads are on the right-hand side.

Slide the battery pack into the UPS.

Press the gray connector into the plug at the bottom and to the right of the battery compartment. Tuck the white cord (that serves as a handle for the connector) neatly to the side.

8. Slide the front set of batteries in, then guide the connector over the batteries and press firmly to connect it to the front connector of the battery compartment.

Notes:

Repeat steps 4 through 9 for the second set of batteries.

Small sparks at the battery connectors are normal during connection.

9. Close the battery door, replace the screws, and replace the front cover.

Batteries must be recycled. Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new battery’s packing material. See the new battery instructions for more information.

10

Storage

Storage Conditions

Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least two hours. Remove any accessories in the accessory slot and disconnect any cables connected to the computer interface port to avoid unnecessarily draining the battery.

Extended storage

At -15 to +30

°

C (+5 to +86

°

F), charge the UPS’s battery every six months.

At +30 to +45

°

C (+86 to +113

°

F), charge the UPS’s battery every three months.

User Configuration Items

UPS ID

Function

Automatic Self-Test

Note: Setting these items requires optional software or hardware.

Factory

Default

Every 14 days (336

User Selectable

Choices

Every 7 days (168 hours), On Startup hours) Only, No Self-Test

UPS_IDEN Up to eight characters to define the UPS.

Description

Sets the interval at which the UPS will execute a self-test.

Use this field to uniquely identify the UPS for network management purposes.

Date of Last Battery

Minimum Capacity Before

Return from Shutdown

Sensitivity

Duration of Low Battery

Warning

Alarm Delay After Line

Fail

Shutdown Delay

Synchronized Turn-on

Delay

High Transfer Point

200/208 Vac

230 Vac

Low Transfer Point

200/208 Vac

230 Vac

Manufacture

0 percent

Normal

2 minutes

5 second delay

20 seconds

0 seconds

229

253

177

196

Date of Battery

15, 50, 90 percent

Reduced, Low

Reset this date on battery replacement.

The UPS will charge its batteries to the specified percentage before return from a shutdown.

Set lower than normal sensitivity to avoid lowered battery capacity and service life in situations where the load can tolerate minor power disturbances.

5, 7, 10 minutes

168, 172, 182

188, 204, 208

Sets the time before shutdown at which the

UPS issues a low battery warning. Set higher than the default only if the OS needs the time for graceful shutdown.

30 second delay, At To avoid alarms for minor power glitches,

Low Battery set the alarm delay.

C di i Al

Sets the interval between when the UPS receives a shutdown command and when shutdown occurs.

60, 180, 300 seconds

224, 234, 239

264, 271, 280

To avoid branch circuit overload, the UPS will wait the specified time after the return of utility power before turn-on.

To avoid unnecessary battery usage, set the

High Transfer Point higher if the utility voltage is chronically high and the load is known to work well under this condition.

Set the Low Transfer Point lower if the utility voltage is chronically low and the load can tolerate this condition.

11

On-Battery Run Time

Note:

UPS battery life differs based on usage and environment.

APC recommends that the battery/batteries be changed once every two years.

Typical On-Battery Run Time Versus Load, in Hours

Load (VA)

100

Run Time (hours)

7.17

150

200

300

400

5.95

5.04

3.88

2.96

1600

2000

2200

2500

3000

3500

500

600

800

1000

1200

1400

4000

4500

5000

0.13

0.11

0.09

0.54

0.39

0.33

0.26

0.19

0.16

2.37

1.92

1.40

1.06

0.83

0.65

12

Specifications

Acceptable input voltage

Input voltage (on-line operation)

208 volt output range

Nominal input frequency

Input protection

Frequency limits (on-line operation)

Transfer time

Maximum load, total

On-battery output voltage

On-battery frequency

On-battery waveshape

Overload protection (on-battery)

Overload protection (on-line)

Surge energy rating

(one time, 10/1000

æs waveform)

Surge current capability

(one time, 8/20

æs waveform)

Surge response time

200/208 Vac 230 Vac

0 – 325 Vac

160 – 253 Vac

177 – 229 Vac

50 or 60 Hz, autosensing

Resettable circuit breaker

174 – 286 Vac

196 – 253 Vac

47 to 63 Hz

3 ms typical, 6 ms maximum

5000 VA/3750 W

208 Vac 220, 225, 230, or 240 Vac

50 or 60 Hz,

ñ0.1 Hz; unless synchronized to utility during brownout

Low-distortion sine wave

Overcurrent and short-circuit protected, latching shutdown on overload

2 pole, 20 A UL certified input circuit breaker

Not applicable

1120 J

Surge voltage let-through

(percentage of applied ANSI C62.41

Cat. A

ñ6 kV test waveform)

Noise filter

Battery type

Typical battery life

Typical recharge time

Operating temperature

Storage temperature

Operating and storage relative humidity

Operating elevation

Storage elevation

Electromagnetic Compatibility (EMC)

Audible noise at 1 m (3 ft.)

Safety approvals

Size (W x H x D)

Weight - net (shipping)

6500 A maximum

0 ns (instantaneous) normal mode;

<5 ns common mode

0.30%

Normal and common mode EMI/RFI suppression,

100 kHz to 10 MHz

Spill proof, maintenance free, sealed lead-acid

3 to 6 years, depending on number of discharge cycles and ambient temperature

2 to 5 hours from total discharge

0 to 40

§C (+32 to +104§F)

-15 to +45

§C (+5 to +113§F)

0 to 95%, non-condensing

0 to +3,000 m (0 to +10,000 ft.)

0 to +15,000 m (0 to +50,000 ft.)

61000-4-2, 61000-4-3, 61000-4-4,

61000-4-5

61000-2-2, 61000-3-2,

EN61000-4-1, EN61000-4-11

FCC/DOC Class A verified

<55 dBA

EN55022 Class A, EN50091-2

Listed to UL 1778, certified to CSA

107.1

GS licensed by VDE to

EN50091-1-1 and EN60950

17.0 x 8.7 x 24.5 in.

43.2 x 19.6 x 62.2 cm

225 (245) lb

102 (111) kg

13

Troubleshooting

Use the chart below to solve minor UPS installation problems. Contact APC Technical Support Staff for assistance with complex UPS problems. See

APC Contact Information, page

15

,

for a location near you.

Problem and Possible Cause

UPS will not turn on.

ON button not pushed.

UPS not connected to AC power supply.

Solution

Press the ON button once to power the UPS and the load.

UPS input circuit breaker tripped.

Very low or no utility voltage.

Check that the power cable from the UPS to the power supply is securely connected at both ends.

Reduce the load on the UPS by unplugging equipment and reset the circuit breaker (on back of UPS) by pressing the plunger back in.

Check the AC power supply to the UPS with a table lamp. If very dim, have the utility voltage checked.

Confirm the battery connections.

Battery not connected properly.

UPS will not turn off.

Internal UPS fault.

Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.

UPS operates on-battery although normal line voltage exists.

UPS’s input circuit breaker tripped.

Reduce the load on the UPS by unplugging equipment and reset the circuit breaker (on back of UPS) by pressing the plunger back in.

Very high, low, or distorted line voltage.

Inexpensive fuel powered generators can distort the voltage.

Move the UPS to a different outlet on a different circuit.

Test the input voltage with the utility voltage display. If acceptable to the load, reduce the UPS’s sensitivity. Refer to Voltage

Sensitivity, page 7, for instructions.

UPS beeps occasionally.

Normal UPS operation.

UPS does not provide expected backup time.

The UPS’s battery is weak due to recent outage or is near the end of its service life.

The UPS is overloaded.

None. The UPS is protecting the load.

Charge the battery. Batteries require recharging after extended outages. Also, they wear faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet lit.

Check the UPS’s load display. Unplug less needed equipment, such as printers.

Front panel indicators flash sequentially.

The UPS has been shut down by remote control.

None. The UPS will restart automatically when utility power returns.

All indicators are lit and UPS emits a constant beeping.

Internal UPS fault.

Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.

All indicators are off and UPS is plugged into wall outlet.

The UPS is shut down and the battery is discharged from an extended outage.

None. The UPS will return to normal operation when the power is restored and the battery has a sufficient charge.

The replace battery light is lit.

Weak batteries.

Replacement batteries not connected properly.

Do another self test to see if it clears.

Confirm the battery connections.

14

Service

If the UPS requires service do not return it to the dealer! Follow these steps:

1. Review the problems discussed in Troubleshooting, page 14, to eliminate common problems.

2. Verify that no circuit breakers are tripped. A tripped circuit breaker is the most common UPS problem!

3. If the problem persists, call customer service or visit the APC Internet Website (www.apcc.com).

Note the model number of the UPS, the serial number, and the date purchased. A technician will ask you to describe the problem and try to solve it over the phone, if possible. If this is not possible the technician will issue a Return Merchandise Authorization Number (RMA#).

If the UPS is under warranty, repairs are free. If not, there is a repair charge.

4. Pack the UPS in its original packaging. If the original packing is not available, ask customer service about obtaining a new set.

Note:

Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging. Damage sustained in transit is not covered under warranty.

Refer to Appendix B: Transporting Your Smart-UPS, page 17, for important shipping information.

5. Mark the RMA# on the outside of the package.

6. Return the UPS by insured, prepaid carrier to the address given to you by Customer Service.

APC Contact Information

Internet

: http://www.apcc.com/contact

North America

Phone

Fax

1.800.800.4272

1.401.788.2743

Latin America

Argentina 0800.9.APCC (0800.9.2722)

Brazil

Colombia

Email

0800.12.72.21

980.15.39.47

[email protected]

Mexico

Uruguay

Venezuela

95.800.804.4283

000.413.598.2139

8001.2544

Limited Warranty

American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. To obtain service under warranty you must obtain a Returned Material

Authorization (RMA) number from customer support (see Service, page 15). Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment which has been damaged by accident, negligence, or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.

EXCEPT AS PROVIDED HEREIN, AMERICAN POWER CONVERSION MAKES NO WARRANTIES,

EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A

PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.

EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL APC BE LIABLE FOR DIRECT, INDIRECT, SPECIAL,

INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF

ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, APC is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.

15

Appendix A: Regulatory Agency Approvals

200/208 Vac Units

®

LISTED 42C2

E95463

LR63938

Radio Frequency Interference

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the

FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.

Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Shielded signal cables must be used with this unit to ensure compliance with the Class A FCC limits.

230 Vac Units

B

N 394

geprüfte

Sicherheit

ME 61

16

Appendix B: Transporting Your Smart-UPS

Follow these guidelines if you need to ship the UPS to another location. These guidelines apply whether you are transporting the UPS alone, rack mounted in an equipment cabinet, or installed in a system.

Caution:

Always DISCONNECT THE BATTERIES before shipping the UPS to avoid damage during transport.

(U.S. Federal Regulation requires that batteries be disconnected during shipment.) The batteries may remain in the UPS; they do not have to be removed.

This requirement applies whether the UPS is shipped alone or installed in an equipment rack or system.

Note:

Graphics are not drawn to scale. They are shown for reference only.

The battery compartment is accessed from the front panel of the UPS. The SU5000 unit, shown as an example, has four battery packs (each with four individual batteries).

Note:

Remove batteries to reduce UPS weight.

1. Remove the front bezel by grasping the finger clips on the side of the bezel and carefully loosening the four (4) snaps.

2. Use a screwdriver or coin to remove the two battery door screws and open the door.

3. Disconnect the front battery pack. Grasp the white cord on the first front set of batteries and pull firmly to disconnect the connector from the battery compartment.

4. Tuck the white cord (that serves as a handle for the connector) neatly to the side.

5. Disconnect the remaining battery packs by repeating steps 3 and 4.

6. Once all the batteries have been disconnected, close the battery door and replace the two (2) screws removed in step 2.

7. Align the front bezel with the opening on the front of the UPS and snap it into place.

Note:

Remember to connect the batteries once the UPS has arrived at its destination.

17

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement