Baldor MN894 Remote Starter Installation & Operating Manual

Add to my manuals
66 Pages

advertisement

Baldor MN894 Remote Starter Installation & Operating Manual | Manualzz
Multipurpose
Soft Starter
Sizes 8 to 840 AMP
Installation & Operating Manual
9/06
MN894
Table of Contents
Section 1
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-6
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-7
Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8
Section 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Receiving, Inspection and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Physical Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
AC Main Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Power Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Non-Motor and Special Motor Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4
Section 3
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
Types of Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
Start Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Ramp Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Torque Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Current Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Stop Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Ramp Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Torque Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Run Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Current Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Current Calibration Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Operating Parameters Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
CLOSE TO RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
START/RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
SHUNT TRIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
RAMP END . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
TACH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
MTR PWR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
CUR MON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
MN894
Table of Contents i
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6
Power On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6
Over Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6
Motor Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6
Summary of Start and Stop Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6
Section 4
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Start-up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Recommended Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Quick Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2
Starting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4
Variable Load with Voltage Ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4
High Friction Load with Voltage Ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5
Inertial Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
Tachometer Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7
Start-up Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8
Section 5
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
Power Off Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
Blocking Voltage Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
SCR Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
Full Voltage Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
Resistance Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
SCR Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4
Logic Control Module Resistance Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5
Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6
Reset the Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-8
Reset an Overload Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9
Fuse Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9
ii Table of Contents
MN894
Section 6
Specifications and Product Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
Three Phase Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2
Three Phase Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2
Wire Size & Tightening Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4
Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-5
Open Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-5
NEMA 1, 3R and 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-6
Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7
MA Style 8, 16 and 30 AMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7
MB Style 8, 16 and 30 AMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8
MA Style 55 and 80 AMP NEMA 1 and Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-9
MB Style 55 and 80 AMP NEMA 1 and Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-10
NEMA 1 & Panel Mounted Size 160−840 AMP Control Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-11
NEMA 1 & Panel Mounted Size 160−840 AMP Combination & Noncombination . . . . . . . . . . . . . . . . . . . .
6-12
NEMA 12 Size 160−840 AMP Combination & Noncombination Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-13
Appendix A
Reference Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-1
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-1
Current Calibration Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-1
Quick Reference Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-3
Overload Relay Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-4
Appendix B
Circuit Breaker Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B-1
MN894
Table of Contents iii
iv Table of Contents
MN894
Section 1
General Information
Introduction
Three phase multipurpose soft starter control provides reduced voltage, three phase
motor starting. Ramp up and extended ramp down features provide an effective means
to start and stop material handling equipment and pumping equipment to minimize
spillage and water hammer problems. Adjustable current limit allows constant current
starting of high inertia loads such as chippers, centrifuges and compressors. It also
reduces the peak demand of power required from utility companies or generating
equipment.
Tachometer feedback may be used to provide consistent starting and stopping times with
linear acceleration and deceleration. This is especially important under varying load
conditions like: textile, material handling and pumping equipment.
Six SCR (silicon controlled rectifier) devices are connected in three sets of inverse
parallel configuration to provide full wave voltage and current control of the three phase
AC motor. MOV (metal oxide varistors) provide surge voltage protection at the AC input
to the starter.
Several product features make this soft start control easy to use:
MN894
S
S
S
S
S
Two selectable starting methods.
S
Bar graph display provides a visual representation of motor current to assist in
set-up and troubleshooting. (0 to 400% FLA).
S
S
S
Tachometer input.
Individual ramp up and ramp down adjustments.
Flexible yet simple setup with switch selections and potentiometer adjustments.
Simple onboard current calibration.
Indicator lights and status contacts providing information about the starting,
running and stopping conditions.
Five output relay contacts.
Built-in protection features to reduce down time.
General Information 1-1
Figure 1-1 Layout and Identification
T1
T2 T3
GND
CPT
F1
F2
F3
L1
L2 L3
CB
Shunt
Trip
CT3
CT4
CT2
OL
CT1
MOV
R1
R2
TB1
LCM
PC1
PC2
PC3
Overtemperature
Switch
Snubber
Capacitor
Snubber
Resistor
Fan
Legend:
CB CPT CT1, 2, 3, 4 F1, F2, F3 GND LCM MOV OL PC1, 2, 3 R1, R2
TB1, 2 -
Fan
Fan
Motor Circuit Protector or fusible disconnect
Control transformer (control voltage)
Current Transformer
Control transformer fuses
Ground connection
Logic control module
Metal oxide varistors
Overload relay (electronic)
Power Cell
Control Relays
Terminal block
1-2 General Information
MN894
Figure 1-2 Logic Control Module Block Diagram
O
N
Ramp
Mode
Select
123456
RDD
CM
OC
TACH
CL
BP
1
2
3
4
5
6
Reset
Logic
Gates & Sync.
S2 OFF ON
User
Adjustment
RU
TU
CL
PT
S
T
A
R
T
RD
TD
S
T
O
P
Current
Transformer
Tachometer
Input
Close To
Run
C
U
R
R
E
N
T
C
A
L
I
B
R
A
T
I
O
N
4 +
5 -
MN894
Overcurrent Trip
12
OC
M
O
T
O
R
400
C
U
R
R
E
N
T
200
300
Status
Lights
100
0
%FLA
Current Monitor
Motor Power
Ramp End
Shunt Trip
Start/Run
13
Legend:
BP CL CM OC PF PT RD RDD RU S1 −
TACH TD TU -
1
2
3
4
5
6
7
8
PWR
Control Power
S1 OFF ON
123456 78
x
Logic &
Firing
Control
MIN MAX
O
N
x
Power Cell
Gates and
Cathodes
+
-
R
U
N
CM
PF
115 /230 VAC
Power Input
Power
Supply
1
2
3
6
7
8
9
10
11
Relay
Outputs &
Status
Close To Run
Bypass
Current Limit
Current Monitor
Overcurrent
Power Factor
Pulse Time
Ramp Down
Ramp Down Disable
Ramp Up
Calibration Switch
Tachometer
Torque Down
Torque Up
General Information 1-3
Major Components
(Refer to Figures 1-1 and 1-2).
Logic Control Module (LCM)
The LCM (Logic Control Module) operates in the voltage ramp mode or current limit
mode during ramp up and ramp down (if ramp down is selected). The LCM controls the
amount of current that the power cells deliver to the motor during ramp up and ramp
down. It uses gates and synchronous timing circuits to control the firing times of the
SCR’s in the power cells. The current transformer provides the LCM with motor current
information. The on board current calibration switches (S1-1 thru S1-8), place burden
resistors in parallel with the current transformer to calibrate the LCM to the correct FLA
(full load amperes) of the motor being used.
Current Transformer
(CT1) provides starting, stopping and running current information to the LCM. This
information is used to control starting and stopping current, current limit, current monitor
and over current shutdown, power factor effect and motor current bar graph indicator.
(CT2) is required only for sizes 160 through 840 amps. It steps down current to match
primary rating of CT1 transformer.
8, 16 and 30 amp models - CT1 is mounted inside the LCM housing.
55 and 80 amp models - CT1 is mounted externally on the panel.
160 to 840 amp models - CT1 and CT2 are mounted externally on the panel.
CT1 ratio is 6000:1
CT2 ratio is 500:5 for 160, 250 and 420 Amp models.
CT2 ratio is 1000:5 for 600 and 840 Amp models.
Power Cells (PC)
Power cells control the voltage delivered to the motor during ramp up and ramp down (if
ramp down is enabled). The LCM controls the duty cycle of the SCR’s in the power cells
(“on” time versus “off” time of each SCR). A power cell contains two silicon controlled
rectifiers (SCR’s). The SCR’s are solid state switches that are able to control large
amounts of current with a small amount of gate current supplied by the LCM.
8, 16 and 30 amp models - six SCR’s are mounted inside the LCM housing.
55 and 80 amp models - SCR’s are mounted in an isolated package containing two
SCR’s for each power cell. With this type of package, three power cells are mounted to a
single heat sink at ground potential. A temperature switch is provided in each cell to
protect the power cell from overheating.
160 to 840 amp models - Each SCR is a disk type package containing one SCR. Two
SCR’s are clamped between two heat sinks. A temperature switch is provided to protect
the SCR assembly from overheating. Heat sinks are mounted on an insulated base with
a terminal block and snubber network. The snubber network is a capacitor resistor series
circuit wired in parallel with the disk type SCR’s. The snubber network enhances the
electrical characteristics of the SCR’s and provides transient voltage protection. This
arrangement makes up one power cell. The power cell is at line potential for both line
and load terminals when line voltage is applied.
Protection Devices
Metal Oxide Varistors (MOV)
An MOV provides voltage surge protection. Voltage surges also called high voltage
spikes are caused by a number of sources. Short duration high voltage spikes caused by
starting and stopping other motor loads or switching On and Off capacitor banks may
appear on the incoming lines. Transients can occur from lightning storms or from other
lightly loaded devices on the same line, such as motors, transformers, or solenoids.
Electrical noise can be caused by lightning, arc welders and heat exchange equipment on
the same transformer bus line.
An MOVs provide protection by absorbing or clamping these transient energy levels.
High energy transients that exceed the MOV rating may damage the MOV and the
multipurpose starter.
1-4 General Information
MN894
Snubber Network
160 through 840 amp models only. A resistor and capacitor series circuit (snubber) is
wired in parallel with each disk type SCR. The RC network enhances the electrical
characteristics of the SCR and provides high voltage transient protection.
Shorted SCR Detection:
If a shorted SCR condition is detected while starting, running or stopping, the SHUNT
TRIP contact will close and the SHUNT TRIP light will indicate the condition.
The SHUNT TRIP contact is used to open the circuit breaker via a shunt trip device.
Also, the shunt trip contact from the LCM module can be used to activate other circuit
interrupting device to remove the motor and control from the AC power line.
When a bypass contactor is used, the shunt trip circuit is disabled when the bypass
contactor is closed. This is accomplished by switching switch BP S2-6 On.
Over Current Shut Down: The control module has an over current detection circuit to trip and shut down the control
if motor current exceeds 450% FLA. To restart, open the Close To Run circuit, then close
it.
Current Monitor:
When the motor is at speed (End of Ramp light is “ON”), the current monitor can detect
over current or overload motor conditions. This warning can alert an operator or be used
to stop a motor. It can also be used for indications of jams or blockages.
Motor Overload Protection: Class 30 motor overload protection is required to protect the control and the motor from
repetitive or extended starting conditions, as well as running during an overload condition.
Class 10 or 20 overloads may trip when starting high inertia loads or when operating in
current limit starting mode.
Over Temperature Switch: Power cells have over temperature switches to detect an overheating condition. The
switch is an isolated bimetallic, normally closed contact. If loss of cooling causes a power
cell to overheat, the temperature switch contact will open and shut down the control
circuit.
Note: When a temperature switch opens, the control shuts down. It must be reset
manually to restart the control.
Figure 1-3 Starter Diagram
L1
L2
Combination Starter
L3
Non-Combination Starter
Circuit
Breaker or
Fusible
Disconnect
MN894
Soft
Start
Control
(Control only)
Overload
Relay
General Information 1-5
Configurations
Control Only: Soft start control, without motor overload protection or branch circuit
protection circuit breaker or fusible disconnect switch. Suitable for installation with a
series contactor or as a retrofit for an existing motor starter.
Non-combination Starter: Soft start control with motor overload protection, less branch
circuit protection circuit breaker or fusible disconnect switch. Installation with existing
branch circuit protection would use this configuration.
Combination Starter: Soft start control with motor overload protection and branch circuit
protection and branch circuit protection circuit breaker or fusible disconnect switch. Only
push buttons are required to complete the system. New installations with no existing
control equipment would use this configuration.
Bypass System, Control Only: Soft start control without overload protection and branch
protection. Includes a bypass contactor to shunt the power cells after the control is in the
full run mode to eliminate heat generation across the power cells. Allows installation in a
NEMA 4 or NEMA 12 enclosure.
Bypass System, Non-combination: Soft start control noncombination system with
motor overload protection, less branch circuit protection. Includes a bypass contactor to
shunt the power cells after the starter is in the full run mode to eliminate heat generation
across the power cells. Allows installation in a NEMA 4 or NEMA 12 enclosure.
Bypass System, Combination: Soft start control combination system with motor
overload protection and branch circuit protection circuit breaker or fusible disconnect
switch. Includes a bypass contactor to shunt the power cells after the starter is in the full
run mode to eliminate heat generation across the power cells. Allows installation in a
NEMA 4 or NEMA 12 enclosure.
Enclosures and Ventilation: Soft start controls are available in panel mount or in NEMA
type 1, 12, 3R enclosures. The control will generate approximately 3.3 watts of heat per
running ampere during operation. All factory supplied enclosures are designed to
dissipate this heat under maximum specified operating conditions. If the multipurpose
control is mounted in an enclosure not supplied by the factory, this heat dissipation must
be considered. Adequate ventilation or convection cooling should be provided unless a
bypass contactor is used.
Panel Mount: Soft start control mounted on a panel with provisions for wall or enclosure
installation.
NEMA Type 1 (IP23): Soft start control mounted in a ventilated NEMA type 1 panel
enclosure. Intended for indoor use primarily to provide a degree of protection against
contact with enclosed electrical components. Available for all sizes and configurations.
NEMA 12/3R (IP65/IP32): NEMA 12 enclosure provides protection from dust, dirt, oil
and water. NEMA 3R outdoor installation protects from rain, sleet and snow. A NEMA
12/3R is shipped as a NEMA 12 and to convert to NEMA 3R, remove the drain screw at
the bottom of the enclosure.
1-6 General Information
MN894
Limited Warranty
For a period of two (2) years from the date of original purchase, BALDOR will
repair or replace without charge controls and accessories which our
examination proves to be defective in material or workmanship. This
warranty is valid if the unit has not been tampered with by unauthorized
persons, misused, abused, or improperly installed and has been used in
accordance with the instructions and/or ratings supplied. This warranty is in
lieu of any other warranty or guarantee expressed or implied. BALDOR
shall not be held responsible for any expense (including installation and
removal), inconvenience, or consequential damage, including injury to any
person or property caused by items of our manufacture or sale. (Some
states do not allow exclusion or limitation of incidental or consequential
damages, so the above exclusion may not apply.) In any event, BALDOR’s
total liability, under all circumstances, shall not exceed the full purchase
price of the control. Claims for purchase price refunds, repairs, or
replacements must be referred to BALDOR with all pertinent data as to the
defect, the date purchased, the task performed by the control, and the
problem encountered. No liability is assumed for expendable items such as
fuses.
Goods may be returned only with written notification including a BALDOR
Return Authorization Number and any return shipments must be prepaid.
MN894
General Information 1-7
Safety Notice
This equipment contains voltages that may be as high as 600 volts! Electrical shock can
cause serious or fatal injury. Only qualified personnel should attempt the start-up
procedure or troubleshoot this equipment.
This equipment may be connected to other machines that have rotating parts or parts
that are driven by this equipment. Improper use can cause serious or fatal injury. Only
qualified personnel should attempt the start-up procedure or troubleshoot this equipment.
PRECAUTIONS
WARNING: Do not touch any circuit board, power device or electrical connection before you
first ensure that power has been disconnected and there is no high voltage present
from this equipment or other equipment to which it is connected.
Electrical shock can cause serious or fatal injury.
WARNING: Be sure that you are completely familiar with the safe operation of this equipment.
This equipment may be connected to other machines that have rotating parts or
parts that are controlled by this equipment. Improper use can cause serious or
fatal injury. Only qualified personnel should attempt the start-up procedure or
troubleshoot this equipment.
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC
power before you ensure that all grounding instructions have been followed.
Electrical shock can cause serious or fatal injury.
Caution:
To prevent equipment damage, be certain that the electrical service is not capable
of delivering more than the maximum line short circuit current amperes listed for
the control rating.
Caution:
Do not “Megger” test the motor while it is connected to the control. Failure to
disconnect motor will result in extensive damage to the control. The control is
tested at the factory for high voltage / leakage resistance as part of Underwriter
Laboratory requirements. Do not megger any part of the control.
Caution:
Do not connect power factor correction capacitors to motor terminals. If power
factor correction capacitors are necessary, contact Baldor.
Caution:
If a brake motor is used, the initial starting voltage may not be sufficient to release
the brake. It may be necessary to provide separate power for the brake and soft
start control.
Caution:
Do not connect AC incoming line power to the Motor terminals T1, T2 and T3.
Connecting AC power to these terminals may result in damage to the control.
Caution:
Do not supply any power to the “Close To Run” terminals. Power on these leads
can damage the control. Use a dry contact type that requires no external power to
operate.
Caution:
Do not change the position of any switch while power is applied. Changing the
position of a switch during operation can damage the control and cause erratic
behavior of the load.
Caution:
To prevent equipment damage, be certain that the electrical service is not capable
of delivering more than the maximum line short circuit current amperes rating.
Caution:
This equipment is shipped as a multipurpose apparatus. Before power is applied,
the line voltage selection and the full load current calibration must be correctly set.
Failure to select the proper line voltage or to calibrate the full load current may
cause damage.
1-8 General Information
MN894
Section 2
Installation
Receiving, Inspection and Storage
When you receive your control, there are several things you should do immediately.
1.
Observe the condition of the shipping container and report any damage
immediately to the commercial carrier that delivered your control.
2.
Remove the control from the carton. Inspect for shipping damage and report
any damage immediately to your commercial carrier.
3.
Verify that the part number of the control you received is the same as the part
number listed on your purchase order.
4.
If the control is to be stored for several weeks before use, be sure that it is
stored in a location that is clean, dry and free from corrosives and
contaminants. Storage temperatures must not exceed 140°F (60°C).
Be sure to read an become familiar with the safety notices in Section 1 of this manual.
Failure to observe the product safety notices can result in injury or equipment damage.
If you have questions, please contact your Baldor distributor. Do not proceed unless you
understand the installation and operation requirements and safety notices.
Physical Location
The location of the soft start control is important. It should be installed in an area that is
protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic
particles, and vibration. Exposure to these elements can reduce the operating life and
degrade performance of the control.
Several other factors should be carefully evaluated when selecting a location for
installation:
AC Main Circuit
Protection Devices
Power Disconnect
MN894
1.
For effective cooling and maintenance, the control should be mounted vertically
on a flat, smooth, non-flammable vertical surface. Heat dissipation of 3.3 watts
per running FLA of the motor must be provided. All factory supplied enclosures
provided adequate heat dissipation.
2.
If the control is mounted in an enclosure, sufficient air flow must be provided.
The fan or blower must be rated for at least 0.8 cubic feet per minute for each
ampere of motor FLA rating.
3.
Keep high voltage and low voltage wiring separated. If the conduits must
cross, be sure that they cross at 90° angles only.
1.
Motor overload protection is required for starters that do not have an overload
protection device.
2.
The multipurpose soft starter is suitable for use on a circuit capable of
delivering no more than the short circuit ARMS listed in Table 2-1.
3.
A short circuit current and overcurrent devices are required for soft start
controls that do not have a circuit breaker or fusible disconnect switch.
Be sure a suitable input power protection device is installed. Use the recommended circuit
breaker or fuses listed in Table 2-1. Wire sizes and protective device specifications are based
on the maximum output power rating of the control.
A power disconnect should be installed between the input power service and the control for
a fail safe method to disconnect power. The control will remain in a powered-up condition until
all input power is removed from the control and internal voltages are depleted.
Installation 2-1
Table 2-1 Three Phase
Rating
(AMPS)
8
16
30
55
80
160
250
420
600
840
Fuse
Amps
Class
100
100
200
100
175
175
400
400
800
800
1200
J
J
J
RK1
J
J
RK5
RK5
L
L
L
MCP (GE)
Short Circuit
ARMS
5,000
5,000
5,000
5,000
42,000
42,000
100,000
100,000
100,000
100,000
100,000
Amps
Type
20
20
50
50
100
100
300
300
600
600
600
SELA
SFLA
SGLA
SKLA
Short Circuit
ARMS
5,000
5,000
5,000
,
10,000
10,000
42,000
42,000
42,000
42,000
42,000
Note: Maximum recommended fuses/breakers are based on 25°C ambient, maximum continuous current.
Figure 2-4 Multipurpose Control Terminal Locations
(A) Line Input
(C) Control Connections
L1
L2
L3
(D) GND
T1
T2
T3
(D) GND
(A) Motor Output Load
2-2 Installation
MN894
Installation
1.
2.
3.
4.
5.
6.
7.
8.
9.
Mount the panel or enclosure to the mounting surface. The panel or enclosure must be
securely fastened to the mounting surface. Refer to the mounting dimensions in Section 6 of
this manual.
Ground the panel and control per NEC article 250 as well as state and local codes.
Use copper wire rated for at least 75°C. Refer to Figure 2-4 and Table 2-2 for wire size
recommendations.
Connect the incoming AC power wires from the power disconnect and/or protection devices to
L1, L2 and L3 terminals. Tighten each terminal as specified in Figure 2-4 and Table 2-2.
* Connect earth ground to the “GND” of the control. Be sure to comply with local codes.
Verify the input line voltage is correct.
For MA#−XX models, verify the line voltage selection jumpers on the LCM module are properly
set. For MB#−XX models, verify the control transformer primary taps are connected for the line
voltage applied.
Connect the three phase power leads of the AC motor to terminals T1, T2, and T3 of the Main
Circuit Terminals.
* Connect motor ground wire to the “GND” of the control. Be sure to comply with all applicable
codes.
Caution:
Do not supply any power to the “Close To Run” terminals. Power
on these leads can damage the control. Use a dry contact type that
requires no external power to operate.
10. Connect the remaining control terminals as required for your installation. Refer to Figure 2-4 and
Table 2-2 for wire size and terminal torque specifications.
*
Grounding by using conduit or panel connection is not adequate. A separate conductor of the
proper size must be used as a ground conductor.
Table 2-2 Recommended Wire Size and Tightening Torque
Terminal
Starter Rating
A
B
C
D
A
B
C
D
8 16 and 30 AMPS
8,
55 through 840 AMPS
Torque
lb-in
20
35
12
45
Note 1
Note 1
12
45
Nm
2.5
4
1.4
5.1
Note 1
Note 1
1.4
5.1
Wire Size
AWG
10-16
8
12-22
6-14
Note 2
Note 2
12-22
6-14
mm2
6-1.5
10
4-0.34
16-2.5
Note 2
Note 2
4-0.34
16-2.5
All wire sizes based on 75°C copper wire, 3% line impedance.
Higher temperature smaller gauge wire may be used per NEC and local codes.
Note1: Refer to the label on the equipment panel for line and load tightening torque values.
Note2: Line and Load wires sizes for 55 through 840 AMP models are as follows:
AMPS
55
80
160
250
420
600
840
MN894
Wire Size
AWG
4
3
3/0
350 mcm
2x 300 mcm
2x 500 mcm
3x 500 mcm
mm2
25
30
95
185
2x 150
2x 240
2x 240
Installation 2-3
Non-Motor and Special Motor Applications
Non-motor load:
The multipurpose control is designed to provide reduced starting voltage for standard
three phase induction motors. The control may also start non-motor loads for controlled
inrush current applications with resistive or inductive loads. Consult Baldor if the control
is to be used with a non-motor load.
Wye-Delta or
Part Winding Starter:
The multipurpose control can replace an existing wye-delta or part winding starter.
Begin by removing the existing contactors. Wire the motor in its “RUN” delta
configuration and connect the motor to the control. The control can be used as if it were
controlling a standard design B motor.
Wound Rotor Motors:
Consult Baldor if the control is to be used with a wound rotor or slip ring type motor. This
type of load produces high starting torque with reduced starting current and speed. The
multipurpose control provides low starting current and low starting torque. The
multipurpose control can be used for applications that do not require high starting torque
and a continuous speed reduction.
High Slip Motors:
The multipurpose control can be used with high slip motors, such as design D. These
motors are used with large inertial loads that require extended starting times. Reduced
starting voltage will reduce the starting current and extend the starting time. Long starting
times may require using slow trip overloads. However, the thermal capabilities of the
motor and control must be evaluated before extending the overload trip times.
Reversing Applications:
For reversing applications, two multipurpose controls can be used or a reversing
contactor can be used. Consult Baldor for more information.
Multispeed Motors:
Consult Baldor if the control is to be used with a multispeed motor. The control can
be used with a multispeed motor if a multispeed starter is connected between the control
and the motor. In this case, an additional MOV must be connected to the terminal side of
the control. Switching is normally done be auxiliary contacts from the multispeed starter
that are connected to the control circuit of the multipurpose control.
Motors on Grounded and A multipurpose starter should not be used with “Delta” or “Open” ground systems.
open delta systems:
Without a proper ground, the circuit to detect a shorted SCR condition may malfunction or
may not be able to detect a shorted SCR condition.
2-4 Installation
MN894
Section 3
Operation
Types of Starting
Voltage Starting (S2-4 = OFF)
During start the initial voltage (TU) is set to a level where the
motor will begin to turn when power is applied. The ramp time
(RU) is adjustable to provide a smooth start. The pulse time
(PT) is used for high friction loads to break loose “frozen” loads
with up to 400% FLA.
If a ramp down function is needed, the initial voltage TD setting
is used to lower voltage to a level where the motor will begin to
slow down when the stop button is pushed. Ramp down (RD)
can only extend motor stopping time preventing sudden stopping
problems such as water hammer.
Current Limit Starting (S2-5 = ON)
If current limit starting is selected the starter will operate similar
to voltage starting. On high inertia loads such as chippers and
grinders the Current Limit (CL) setting is what determines the
starting time. The starter will provide that current regardless of
the ramp time setting. The CL setting must be high enough to
provide enough starting current in all starting conditions. Ramp
down (RD) can only extend motor stopping time preventing
sudden stopping problems such as water hammer.
Voltage
Ramp
% Line
Voltage
RU
100
PT
TD
75
CL
50
25
TU
0
Current
Limit
% FLA
400
Time
PT
300
200
CL
RD
100
0
Tach Feedback Starting (S2-4 = ON)
Tach feedback starting/stopping uses a 0-10 VDC Tach signal.
The control will provide voltage to the motor to generate a
smooth linear starting even under cycling load conditions. Ramp
down (RD) can only extend motor stopping time preventing
sudden stopping problems such as water hammer.
RD
Time
RUN
Tach
% Full
Speed
100
RD
RU
75
50
25
0
MN894
Time
Operation 3-1
Start Adjustments (Refer to Figure 3-1).
Ramp Up
Ramp up time (RU) is adjustable from 3 to 50 seconds. RU adjusts the voltage ramp or
the tachometer starting ramp time. For voltage starting, RU adjusts the time it takes the
motor to reach full voltage. Actual acceleration time to full speed depends upon the
motor load and the setting of the additional start adjustments.
For Tach feedback starting, RU adjusts the motor starting time independent of the load
when used with a 0 to 10 VDC tachometer feedback signal. Smooth linear speed ramp
up with constant acceleration is achieved.
Torque Up
The initial starting torque (TU) for ramp up is enabled only in the voltage ramp mode.
Usually set high enough to start the motor slowly turning the instant the start button is
pressed.
Pulse Time
Starting pulse time (PT) is adjustable from 0 to 1.5 seconds in the voltage ramp mode.
When the start button is pressed, the initial motor voltage depends on the setting of TU.
One second after the start button is pressed, a pulse of approximately 400% FLA will
occur; the duration will depend upon the setting of PT.
Current Limit
Current limit (CL) is adjustable from 75 to 400% of FLA. It can be used in both the
voltage and tachometer ramp modes of operation. When CL is enabled (S2-5=ON),
motor starting and stopping current will not exceed the set point of CL, except during PT.
Note: CL must be set high enough to allow the motor to start under maximum load
conditions. In the Tach feedback mode, CL will affect linearity and start and
stop times. The current is held at the CL limit until the motor current
decreases to less than the CL setting, regardless of the RU setting.
Figure 3-1
RU
TU
CL
PT
S
T
A
R
T
Stop Adjustments (Refer to Figure 3-2).
Ramp Down
Ramp downtime (RD) extends the stopping time from 5 to 50 seconds. RD can be used
in both the voltage and tachometer modes.
In the tachometer mode, when used with a 0 to 10 VDC tachometer feedback signal, RD
will adjust the actual stopping time independent of motor load condition. Smooth linear
speed ramp down with constant deceleration is achieved.
In the voltage mode, RD adjusts the time it takes to reach minimum motor voltage and
turn off. The actual stopping time will depend on the motor load condition.
Note: Ramp down mode is not suitable for coasting or inertial loads that require
braking. Ramp down will only extend the stopping time.
Torque Down
Torque down advance (TD) is adjustable from 0 to 100% advance. TD sets the initial
torque or voltage which ramp down starts and can be used in both voltage and
tachometer modes.
In ramp down mode, when the stop button is pressed, voltage will immediately decrease
to the set point of TD. Control will continue to ramp down to zero speed or voltage,
depending upon RD setting, then the control will turn off.
Figure 3-2
RD
TD
3-2 Operation
S
T
O
P
MN894
Run Adjustments (Refer to Figure 3-3).
Current Monitor
Current monitor set point (CM) is adjustable from 50 to 400% FLA to monitor the running
current after the motor reaches the full run condition.
With CM enabled (S2-2=ON), if the running current exceeds the CM set point, the control
will shut down, the CUR MON contact will close, and the light will illuminate.
With CM disabled (S2-2=OFF), if motor current exceeds CM set point, the control will not
shut down, the CUR MON contact will close and the light will illuminate.
Power Factor
Power factor effect (PF) is adjustable from 0 to 100%. PF is used to adjust the maximum
voltage applied to the motor under lightly loaded conditions to minimize motor current
with minimum motor load.
PF is enabled after the motor reaches full on condition.
PF should be turned off (CCW) if more than one motor is used with one control or if a
by-pass contactor is used.
Note: PF adjustment has no effect in bypass mode.
Figure 3-3
CM
PF
R
U
N
MIN MAX
Current Calibration Switch Refer to the multipurpose control Current Calibration Chart in Appendix A. Set switches
S1 to the motor FLA rating. Calibration is based on the motor nameplate full load
amperes (FLA), not necessarily actual running current. Motors with more than 6 times
locked rotor current may require a higher setting to start properly.
Operating Parameters Switch (Refer to Figure 3-4).
Switches S2-1 thru S2-6 select the operating modes that best fit the application.
S2-1 Ramp Down Disable (RDD).
In the “On” position: When the stop button is pressed, the control will immediately turn off.
User stop adjustments RD (ramp down time) and TD (ramp down initial starting torque)
are disabled.
In the “Off” position: When the stop button is pressed, the control will ramp down. In the
voltage mode of operation, ramp down time depends on RD and TD settings and the load
condition.
S2-2 Current Monitor (CM) “On” position: If the motor running current exceeds the Current Monitor (CM) setting, the
control will shut down. The shut down condition is indicated by the current monitor light
and the closure of the current monitor contact. The current monitor is typically used to
shut the control down when a jam occurs. To restart the control, press stop, then start; or
open the close to run circuit, then close it.
“Off” position: If motor running current exceeds the current monitor setting, the current
monitor light and contact will indicate this condition but the control will not shut down.
The current monitor can be used as an over and under current monitor.
S2-3 Over Current Indicator (OC).
“On” position: If an over current trip occurs (current exceeds 450% FLA), the control will
shut down and the condition will be indicated by the OC light and CM light and the
closure of the current monitor contact. To restart the control, press stop then start; or
open the close to run circuit, then close it.
“Off” position: An over current trip is indicated by the over current light and will not affect
the current monitor. The control will shut down.
MN894
Operation 3-3
S2-4 Tachometer and Voltage Ramp Select (TACH)
“On” position: The control is in the tachometer ramp mode during start and stop. Starting
and stopping times are independent of the load conditions. Ramp up (RU) is dependent
on the ramp up and current limit (CL) settings. RD is dependent on the RD and CL
settings.
Note: Current limit is disabled if S2-5 is “Off”. Operation in the tachometer mode
requires an isolated input tach signal of 0 to 10 volts DC with a 10 msec
response time or better. Tachometers with other voltage ranges may be used
with this control. Consult the factory for instructions.
If the tachometer full speed voltage is less than 10 volts DC, the starting and stopping
times will be proportionally shorter. For example, if the starting and stopping times are
adjusted to 20 seconds with a 0 to 10 volt DC tachometer signal; for a 0 to 5 Volt DC
tachometer signal with the same setting, the time will be 10 seconds.
“Off” position: The control is operating in the voltage ramp mode during start and stop (if
ramp down is selected using S2-1). All user settings for start, stop and run can be used
to set up the control to meet the application requirements. Starting and stopping times
are dependent on the actual load condition and control settings.
S2-5 Current Limit Enable (CL)
“On” position: Starting and stopping current will not exceed the setting of the current limit
setting, except during PT, if pulse start is being used. Current limit must be set high
enough to allow the motor to start under maximum load conditions.
“Off” position: Current limit is disabled. Maximum motor current is then limited by the
over current shutdown circuit to 450% FLA, preset at the factory.
S2-6 By-Pass Select (BP)
“On” position: When the end of ramp contact closes, the circuit breaker shunt trip circuit
(the Shunt Trip contact on the Multipurpose control module) is disabled after the starter is
in the full run condition. This allows the use of a by-pass contactor without tripping the
circuit breaker when the power cells are bypassed.
“Off” position: the Shunt Trip circuit is enabled at all times.
Figure 3-4
3-4 Operation
OFF
1 2 3 4 5 6
S2
O
N
RDD
CM
OC
TACH
CL
BP
1
2
3
4
5
6
ON
MN894
Control Connections (Refer to Figure 3-5).
CLOSE TO RUN
Close to Run terminals 12 and 13. Close to run contact must be closed to initiate ramp
up and run. Close to Run contact must be opened to initiate ramp down to stop. Close to
run contact must be dry and electrically isolated contact. If a voltage is applied to these
terminals, the control may be damaged.
When the Close to Run circuit is closed, the Start/Run light will be on and the contact will
close. This normally open contact is typically used to seal in the start button circuit.
START/RUN
Start/Run light and contact terminals 10 and 11. As long as the Closed to Run circuit
remains closed, the Start/Run light and contact will remain activated. This condition also
applies to an over current or a current monitor shutdown.
SHUNT TRIP
Shunt Trip light and contact terminals 8 and 9. If the control detects a shorted SCR condition,
the shunt trip light will be on and the contact will close. The shunt trip contact is used to
operate a Shunt Trip device in the circuit breaker or similar disconnection means to remove
the motor and controller from the line should a shorted SCR condition occur.
The shunt trip circuit may also detect loss of phase or low voltage on a phase. The circuit
may not work properly on grounded delta systems or open delta systems. The Shunt Trip
circuit will trip when energized on single phase or an unbalanced line voltage.
RAMP END
Ramp End light and contact terminals 6 and 7. In the voltage or the tachometer modes,
when the starting ramp is completed and the control is in the full run mode, the ramp end
light will be on and the contact will close. The starting current limit is then disabled and
CUR MON (running current monitor) is enabled.
Note: Since most loads do not require full voltage and torque to reach full speed,
when control is in the voltage ramp mode, the motor will reach full speed
before the ramp end contact and light are activated. Ramp end will only be
activated after the motor and control reach full voltage.
The ramp end contact can be used to turn on other equipment. The ramp end contact
can be used to close the bypass contactor to reduce heat dissipation of the SCRs.
TACH
Tachometer input terminals 4 and 5. The TACH input is used in the tachometer mode
(S2-4=ON). The input required for TACH feedback is a 0 to 10 volt DC signal with a
maximum 10 ms response time.
MTR PWR
Motor Power light and contact at terminals 2 and 3. Indicates that voltage and current are
supplied to the motor. If a current monitor or an over current shut down condition occurs,
the contact is deactivated and the light is turned off.
CUR MON
Current Monitor light and contact terminals 1 and 2. A user adjusted monitor. Maximum
running current is adjustable from 50% to 400% FLA. Switch S2-2 controls the CM
monitor.
S2-2 “On” position: If motor current exceeds the CUR MON setting, the light will be on
and the contact will close. In addition, the motor power and ramp end LEDs will be off
and their contacts will open. The control will shut down. The Start/Run light will stay on
and the contact will remain closed. Typically used to shut down the control in case of a
mechanical jam. To restart a CUR MON shutdown, press stop then start; or open the
close to run circuit, then close it.
S2-2 “Off” position: If current exceeds the CUR MON setting, the light will be on and the
contact will close for the duration of the over current. The control will not shut down. In
this mode, the CUR MON monitor can be used as an over and under current monitor.
Figure 3-5
+
CUR
MON
MN894
MTR
PWR
−
Tach
Ramp
End
SHUNT
TRIP
START
/ RUN
CLOSE
TO RUN
Operation 3-5
Indicators
Power On
The PWR light indicates that power is supplied to the internal power supply of the control.
WARNING: If the power light is not illuminated, it does not necessarily mean
that the line voltage is off. Electrical shock hazard may exist.
Measure the voltage at the line terminals before service.
Over Current
OC over current shutdown LED. If the control shuts down due to an over current
condition (motor current is greater than 450% FLA), the OC light will be on. To restart the
control, press stop, then start; or open the close to run circuit, then close it.
Motor Current
The Motor Current display is a 10 segment bar graph representation of motor current
from 0 to 400% FLA. Used to check ramp up, run and ramp down current conditions
while the control is in operation.
Summary of Start and Stop Sequences
To Start the Motor: Close 12 - 13 (Close to Run) and the following occurs:
1.
10 - 11 close to confirm start command.
2.
2 - 3 close when power is applied to motor. Ramp up cycle begins.
3.
6-7 close at the end of ramp up cycle.
To Stop the Motor: Open 12 - 13 (Close to Run) and the following occurs:
1.
10 - 11 open to confirm stop command.
2.
6-7 opens immediately.
3.
2 - 3 operation depend on ramp down mode selection:
With Ramp Down: 2 - 3 opens when ramp down is complete.
Without Ramp Down: 2 - 3 opens immediately.
Shunt Trip:
During normal operation, detection of a shorted SCR, misfiring SCR will
cause the following:
1.
8 - 9 close immediately.
2.
Shunt Trip light turns ON.
3.
The shunt trip breaker is immediately tripped and all power is removed from the
control and motor.
Note: The shunt trip breaker will only trip if it is connected to the shunt trip contact at
terminals 8 & 9.
3-6 Operation
MN894
Section 4
Start-up
Safety Notice
Be sure to read and understand all notices, warning and caution statements in Section 1
of this manual. If you have any questions about the safe operation of this equipment,
please contact your Baldor representative before you proceed.
Start-up Checklist
Recommended Equipment
Overview
Caution:
Volt meter (20kW per volt or better, true RMS meter).
Clamp on ammeter (5 times FLA full scale).
Adjustment wand (provided with multipurpose soft start control).
The following adjustment procedures are examples and are intended to be used as a
guideline to match motor starting characteristics to the load. Actual loads may be
characterized by one or more of the examples. These procedures are intended to help
you design your own procedure for your specific application.
Keep in mind that reducing the starting current by one half will reduce the starting torque
by one fourth. This will cause the motor to take four times longer to reach full speed. In
situations where overloads tend to trip because of long starting times, increase the
starting current and decrease the ramp up time (RU) to help eliminate nuisance trips.
The potentiometer adjustments have a maximum span of 270°. Use the adjustment
wand (provided) to adjust these devices and do not force the adjustments beyond their
mechanical stops.
This equipment is shipped as a multipurpose apparatus. Before power is applied,
the line voltage selection and the full load current calibration must be correctly set.
Failure to select the proper line voltage or to calibrate the full load current may
cause damage.
Switches S1 and S2 as well as all potentiometer adjustments are not factory preset.
These will be set during the example procedures given in this section.
Before you apply Power
- Verify the installation procedure has been performed correctly.
- Know if your application is one of the “Non-motor and Special Motor
Applications” described in Section 2.
- Verify the wiring to the motor does not have any short circuits.
- Verify the motor is properly connected. Verify the voltage and full load amp
rating on the motor nameplate.
Note: A load must be connected to the control for testing. If the actual load cannot
be connected, connect any small motor temporarily for testing.
Verify that the control transformer is properly jumpered for the line voltage at
your location. (MB#−XXX models).
- Verify that the control module jumper is correctly set for the line voltage.
(MA#−XXX models).
- Set S1 to the motor nameplate FLA value.
- Set S2 for the type of application.
- Set potentiometers as suggested.
- Verify the overload setting corresponds to the full load current range on the
calibration label.
After you apply Power
- Verify the input voltage to the starter and the 115VAC from the control
transformer (if a control transformer is installed).
- Verify the PWR light is on. (If not, refer to troubleshooting).
- Verify the shunt trip light is OFF. If it is ON, verify the motor is connected and
all three motor phases are present. If the motor is connected and the shunt trip
light is on, do not attempt to start the control. A short in the motor or wiring may
exist.
- Perform the starting procedure for your application.
-
MN894
Start-up 4-1
Quick Set-Up
1.
Check continuity of the motor wiring and check for phase to phase and
phase to ground short circuits.
2.
Connect the control wiring for your application.
(Refer to section 2 for wire size and torque specifications).
3.
For MB#−XXX models, verify the control transformer is set for the line voltage.
For MA#−XXX models, verify proper voltage jumper selection on LCM models.
4.
Calibrate S1. Refer to Appendix A for switch settings.
Voltage Ramp Starting - (Fans or lightly loaded motors)
5.
Set for ramp up with ramp down as follows:
S2-1 = OFF Ramp down disable
S2-2 = OFF Current monitor
S2-3 = OFF Over current shut down
S2-4 = OFF Tachometer enable
S2-5 = OFF Current limit enable
S2-6 = OFF Bypass contactor
Set RU, TU, PT and PF fully CCW.
Set RD and RT at mid point.
6.
Set for ramp up with no ramp down as follows:
S2-1 = ON
Ramp down disable
S2-2 = OFF Current monitor
S2-3 = OFF Over current shut down
S2-4 = OFF Tachometer enable
S2-5 = OFF Current limit enable
S2-6 = OFF Bypass contactor
Set RU, TU, PT and PF fully CCW.
Note: If the control OC trips, use Current Ramp Starting.
7.
Continue with step 14.
Current Ramp Starting - (High inertial loads)
8.
Set for ramp up with ramp down as follows:
S2-1 = OFF Ramp down disable
S2-2 = OFF Current monitor
S2-3 = OFF Over current shut down
S2-4 = OFF Tachometer enable
S2-5 = ON
Current limit enable
S2-6 = OFF Bypass contactor
Set RU, TU, PT and PF fully CCW.
Set RD and RT at mid point.
9.
Set for ramp up with no ramp down as follows:
S2-1 = ON
Ramp down disable
S2-2 = OFF Current monitor
S2-3 = OFF Over current shut down
S2-4 = OFF Tachometer enable
S2-5 = ON
Current limit enable
S2-6 = OFF Bypass contactor
Set TU, PT, RD, TD and PF fully CCW.
Set RU fully CW.
Set CL to midpoint.
10. Continue with step 14.
4-2 Start-up
MN894
Tach Feedback Starting
11. Set for ramp up with ramp down as follows:
S2-1 = OFF Ramp down disable
S2-2 = OFF Current monitor
S2-3 = OFF Over current shut down
S2-4 = ON
Tachometer enable
S2-5 = OFF Current limit enable
S2-6 = OFF Bypass contactor
Set RU, TU, PT and PF fully CCW.
Set RD and RT at mid point.
12. Set for ramp up with no ramp down as follows:
S2-1 = ON
Ramp down disable
S2-2 = OFF Current monitor
S2-3 = OFF Over current shut down
S2-4 = ON
Tachometer enable
S2-5 = OFF Current limit enable
S2-6 = OFF Bypass contactor
Set RU, TU, PT and PF fully CCW.
13. Continue with step 14.
WARNING: Be sure the system is properly grounded before applying power.
Do not apply AC power before you ensure that all grounding
instructions have been followed. Electrical shock can cause
serious or fatal injury.
WARNING: Improper operation of control may cause violent motion of the
motor shaft and driven equipment. Be certain that unexpected
motor shaft movement will not cause injury to personnel or damage
to equipment. Certain failure modes of the control can produce
peak torque of several times the rated motor torque.
14. Confirm the Close to Run contact is open.
15. Turn Power ON.
16. Close the Run contact.
17. The motor should just begin to rotate when power is applied and reach Ramp
End in a minimum starting time. The control is properly set if the motor starts
smoothly when power is applied and comes to speed as quickly as possible.
Be sure CL is set high enough so the motor can start with a full load. The
control is finished starting when the Ramp End light is ON.
18. If motor operation is not correct, perform one or more of the following
adjustments:
If the motor
Starts abruptly (jerks)
Starts too slowly
Starts too quickly
Is connected to a high inertial
load or a high slip motor is used
Is not starting properly
MN894
Remedy
Decrease TU by turning it CCW.
Increase CL by turning it CW. Then decrease ramp time RU by turning it CW.
Decrease CL by turning it CCW. Then increase ramp time RU by turning it CCW.
It may be necessary to increase S1 setting to allow more motor current for faster
starting.
Refer to detailed starting instructions for your application for more information on
starting adjustments. Also, refer to start-up troubleshooting.
Start-up 4-3
Starting Instructions
Choose one of the following examples that best matches your application. Read the
procedure and set the control according to the procedure or use the steps to develop
your own procedure.
Variable Load with Voltage Ramp (S2-2=OFF, S2−4=OFF)
Typically used for non-inertial loads, loads that increase with speed and changing loads,
such as axial fans and pumps.
1.
Set RU, TU, PT, RD, TD and PF fully counterclockwise CCW).
2.
Set CL and CM fully clockwise (CW).
3.
Adjust TU clockwise sufficiently to start load slowly moving at moment of
switching.
4.
Adjust RU clockwise to achieve desired starting time with normal load
conditions.
Note: Proceed to “Running Adjustment Procedure” if ramp down is not used.
5.
Adjust TD clockwise sufficiently to cause the load to slow down soon after the
stop button is pressed, with normal load conditions.
6.
Adjust RD clockwise to achieve desired stopping time with normal load
conditions.
Running Adjustment Procedure:
After adjusting the starting and stopping characteristics, current monitor/trip (CM)
and power factor adjustments can be made. If the power factor circuit is not used,
turn the PF adjustment fully counterclockwise.
Power Factor Correction Adjustment (PF):
1.
Use an ammeter to measure motor running current.
2.
With the motor at full speed, minimum load and the “Ramp End” light ON,
adjust PF clockwise to minimize running current without oscillation. If there is
no noticeable drop in current, repeat this step while measuring motor voltage.
Current Monitor/Trip (CM):
1.
Set S2-2=OFF.
2.
Press start and allow the motor to reach full speed and the “Ramp End” light to
turn ON.
3.
Adjust CM to desired threshold by observing the “CUR MON” light.
4.
The “CUR MON” contact can be used to indicates this threshold, or by setting
the S2-2=ON, the starter will shut down. Press stop to reset the shutdown and
trip condition.
Post Adjustment Check List:
4-4 Start-up
1.
Check fans for proper operation.
2.
If bypass contactor is used, check that the contactor is closing at Ramp End.
3.
Using a current probe, measure current on all three motor phases. Be sure the
current is balanced during ramp on, run and ramp down.
4.
With the motor in run mode (Ramp End light “ON”), check phase current of all
three phases. Currents should be balanced and within nameplate FLA.
5.
Measure the line voltage at the control during ramp up to ensure voltage does
not drop below minimum operating voltage.
MN894
High Friction Load with Voltage Ramp (S2-2=OFF, S2-4=OFF)
Typically used for loads that require high breakaway torque and low acceleration torque;
i.e., conveyors in icy environment, equipment that resists starting due to lack of use,
traction loads, etc.
1.
Set RU, TU, PT, RD, TD and PF fully counterclockwise (CCW).
2.
Adjust PT clockwise sufficiently to start load slowly moving at moment of
switching.
3.
Adjust TU clockwise sufficiently to keep load moving after starting pulse.
4.
Adjust RU clockwise to achieve desired starting time with normal load
conditions.
Note: Proceed to “Running Adjustment Procedure” if ramp down is not used.
5.
Adjust TD clockwise sufficiently to cause the load to slow down soon after stop
button is pressed, with normal load conditions.
6.
Adjust RD clockwise to achieve desired stopping time with normal load
conditions.
Running Adjustment Procedure:
After adjusting the starting and stopping characteristics, current monitor/trip (CM)
and power factor adjustment can be made. If the power factor circuit is not used,
turn the PF adjustment fully counterclockwise.
1.
Use an ammeter to measure motor running current.
2.
With the motor at full speed, minimum load and “Ramp End” light on, adjust PF
clockwise to minimize running current without oscillation. If there is no
noticeable drop in current, repeat this step while measuring motor voltage.
Current Monitor/Trip (CM):
1.
Press start and allow the motor to reach full speed and the “Ramp End” light to
turn on.
2.
Adjust CM to desired threshold by observing the “CUR MON” light.
3.
The “CUR MON” contact can be used to signal this threshold, or by setting the
S2-2=ON, the starter will shut down. Press stop to reset the shutdown and trip
condition.
Post Adjustment Check List
MN894
1.
Check fans for proper operation.
2.
If bypass contactor is used, check to ensure that the contactor is closing at
Ramp End.
3.
Using a current probe, measure current on all three motor phases. Be sure the
current is balanced during ramp up, run and ramp down.
4.
With the motor in run mode (Ramp End light “ON”), check phase current of all
three phases. Currents should be balanced and within nameplate FLA.
5.
Measure the line voltage at the control during ramp up to ensure voltage does
not drop below minimum operating voltage.
Start-up 4-5
Inertial Load (S2-1=ON, S2-4=OFF, S2-5=ON)
Typically used on coasting and/or flywheel loads; i.e., chippers, centrifuges, compressors,
crushers, chillers, band saws, centrifugal fans and blowers.
Note: Ramp down and pulse start are not normally used with inertial loads.
1.
Set TU, PT, RD, TD and PF fully counterclockwise (CCW).
2.
Set RU approximately 90% clockwise.
3.
Set CL to midpoint.
4.
Set CM fully clockwise (CW).
5.
Adjust CL sufficiently to allow motor to reach full speed in desired time with
maximum normal load.
Running Adjustment Procedure:
After adjusting the starting and stopping characteristics, current monitor/trip (CM)
and power factor adjustment can be made. If the power factor circuit is not used,
turn the PF adjustment fully counterclockwise.
Power Factor Correction Adjustment (PF):
1.
Use an ammeter to measure motor running current.
2.
With the motor at full speed, minimum load and the “Ramp End” light ON,
adjust PF clockwise to minimize running current without oscillation. If there is
no noticeable drop in current, repeat this step while measuring motor voltage.
Current Monitor/Trip (CM):
1.
Set S2-2=OFF.
2.
Press start and allow the motor to reach full speed and the “Ramp End” light to
turn ON.
3.
Adjust CM to the desired threshold by observing the “CUR MON” light.
4.
The “CUR MON” contact can be used to signal this threshold, or by setting
S2-2=ON, the starter will shut down. Press stop to reset the shutdown and trip
condition.
Post Adjustment Check List:
4-6 Start-up
1.
Check fans for proper operation.
2.
If a bypass contactor is used, check that the contactor closes at ramp end.
3.
Using a current probe, measure current on all three motor phases. Be sure the
current is balanced during ramp up, run and ramp down.
4.
With the motor in run mode (ramp end light “ON”), check phase current of all
three phases. Currents should be balanced and within nameplate FLA.
5.
Measure the line voltage at the control during ramp up to ensure voltage does
not drop below minimum operating voltage.
MN894
Tachometer Mode (S2-4=ON, S2-5=OFF)
Typically used for changing loads that require consistent starting and stopping times,
independent of load condition, and pumping applications with severe head pressure to
reduce water hammer; i.e., pumps, conveyors, stackers and other material handling
equipment.
1.
Set RU, TU, PT, RD, TD and PF fully counterclockwise (CCW).
2.
Set CL and CM fully clockwise (CW).
3.
Adjust RU and RD for desired ramp up and ramp down time. RD is only
effective with S2-1=OFF.
Running Adjustment Procedure:
After adjusting the starting and stopping characteristics, the current monitor/trip (CM)
and power factor correction circuit (PF) can be adjusted. If the power factor circuit is
not used, turn the PF adjustment fully counterclockwise.
Power Factor Correction Adjustment (PF):
1.
Use an ammeter to measure motor running current.
2.
With the motor at full speed, minimum load and SSC “Ramp End” light ON,
adjust PF clockwise to minimize running current without oscillation. If there is
no noticeable drop in current, repeat this step while measuring motor voltage.
Current Monitor/Trip (CM):
1.
Set S2-2=OFF.
2.
Press start and allow motor to reach full speed and the “Ramp End” light to turn
ON.
3.
Adjust CM to the desired threshold by observing the “CUR MON” light.
4.
The “CUR MON” contact can be used to signal this threshold, or by setting the
S2-2=ON, the starter will shut down. Press stop to reset the shutdown and trip
condition.
Post Adjustment Check List:
MN894
1.
Check fans for proper operation
2.
If a bypass contactor is used, check to ensure that the contactor closes at ramp
end.
3.
Using a current probe, measure current on all three motor phases. Be sure the
current is balanced during ramp up, run and ramp down.
4.
With the motor in run mode (ramp end light “ON”), check phase current of all
three phases. Currents should be balanced and within nameplate FLA.
5.
Measure the line voltage at the control during ramp up to ensure voltage does
not drop below minimum operating voltage.
Start-up 4-7
Start-up Troubleshooting The Multipurpose Control module has 7 LEDs to help diagnose problems. There is a
summary of the functions and indications on pages 2-8 and 2-9. The Multipurpose starter
was tested under load with all SCR and electronic functions checked before shipping.
Note: To test the output of a soft starter a motor must be connected, even if it is a
1/2 HP motor on a 700 HP starter. Be careful not to start large motors
repeatedly without a cooling-down period.
No Power To The Motor
1.
Verify the PWR light is “ON”.
2.
Verify the Start/Run light is “OFF” and confirm terminals 12-13 on the control
module are open.
3.
Give the starter a start command by closing the start contact connected to
terminals 12 and 13 (verify the Start/Run light is “ON”).
If the Start/Run light is not ON, turn off power and connect terminals 12 and 13
together with a small piece of wire as the jumper. Turn power ON. The
Start/Run light should come “ON” then the MTR PWR light should come “ON”
with power going to the motor.
If this sequence occurs using the jumper, check the start circuit as to why it did
not close the terminals 12-13. If this sequence did not occur, check the voltage
going to the logic control module.
Motor Does Not Start or Motor Does Not Come Up To Speed or
The Motor Overload Overload Trips
Adjust the “CL” to the max. If the motor is still not starting, set the S1 switch for
current calibration to the max. for that control size. Setting the S1 switch to a higher
setting only effects the calibration of light bar current indicator.
Test:
Try restarting the motor while adjusting the “CL” pot during starting. During starting,
check that the incoming voltage is not dropping. If it fails to start at the max. S1
setting, record the line voltage during starting, the motor data including the lock rotor
amps and contact your local Baldor office.
Circuit Breaker is Tripping − On Power Up
The circuit breaker supplied by Baldor is a motor circuit protector (MCP). It is also
called an adjustable magnetic only breaker. This means it will only trip during a
short circuit or instantaneous overcurrent condition. Baldor also adds a shunt trip
module to the breaker. Isolate the problem by disconnecting the shunt trip circuit.
Test for short circuit before re-energizing.
Test:
After the shunt trip circuit has been disabled, apply power. Check the shunt trip light,
if it is “ON” it is detecting a shorted SCR, a loss of phase, a lack of a load or a
grounded delta system. If the SCR’s have been replaced, they may be miswired.
Do not attempt to start until the problem is found.
4-8 Start-up
MN894
Circuit Breaker is Tripping − During Starting
If the shunt trip light comes “ON” during starting it may detect a weak input phase.
This is typical of grounded delta and open delta power systems. For proper
operation, a four wire WYE system is recommended.
If the shunt trip light is ON and it is determined that input power is correct and there
is a motor load; Then, disable the shunt trip circuit and do an SCR resistance test.
1.
If the result of the SCR test shows the SCRE’s are in good condition, try
restarting. If the shunt trip light comes ON again, check the line voltage for a
weak phase.
2.
If the SCR’s test bad, find out why they failed.
SCR’s fail due to high voltage. Is there a capacitor bank or a contactor in the
circuit? Check MOV’s and line voltage. MOV’s may be shorted or open due to
clearing of previous voltage spike.
SCR’s fail due to high current or high temperature.
a.
Check the “T” leads for a phase to phase and phase to ground short
circuit.
b.
Check the motor winding.
c.
Check the voltage balance of power supply. If one leg is going to 25 - 30%
of nominal voltage or less during starting this will create high current on the
other phases.
d.
Make sure the cooling fans are working and the ambient temperature is
within specification.
All Baldor starters are tested under load before shipping for proper SCR
performance.
OC light Comes ON Shutting “OFF” The Starter
MN894
1.
If it trips during starting it may mean that S2-5 (CL) needs to be set to “ON”. If it
is already ON, be sure there are no capacitors or shorts in the motor leads.
2.
If it trips when the Ramp End light comes ON, make sure that S2-2 (CM) is
“OFF” or current monitor level is set properly for a given load.
3.
The control will turn OFF any time motor current exceeds 450% of the S1
current calibration setting.
Start-up 4-9
4-10 Start-up
MN894
Section 5
Troubleshooting
Safety Notice
Be sure to read and understand all notices, warning and caution statements in Section 1
of this manual. If you have any questions about the safe operation of this equipment,
please contact your Baldor representative before you proceed.
Preliminary Checks
In the event of trouble, disconnect all input power to the control and perform these
preliminary checks.
Power Off Checks
1.
2.
3.
4.
5.
6.
7.
Blocking Voltage Check
Check all connections for tightness and signs of overheating.
Check for cracked or damaged insulators and terminal blocks.
Ensure the correct setting of the overload relay.
Check the fuse in the control transformer.
Perform the SCR resistance test for all SCR’s.
If a shorted SCR is suspected, check for possible shorted connections, system
grounds or any other condition which may cause the short circuit condition.
Replace the SCR pack or power cell if no other causes were found. However,
installing a new SCR pack or power cell without determining the cause of failure
can result in repeated failure of the SCR’s. Refer to SCR replacement
procedure in this manual.
This check need only be performed if the resistance checks of the power cells or SCR
packs (55 and 80 amps) are inconclusive.
WARNING: Before power is applied to the control, be sure there is no danger to
personnel or equipment if the motor shaft rotates when power is
applied. A shorted SCR or damaged control can cause abnormal
operation of the motor.
1.
2.
3.
4.
5.
6.
7.
8.
MN894
Be sure power is off. Disconnect the load from the motor shaft if possible.
The T1, T2 and T3 motor leads should be connected to the control for this test.
Disconnect one of the wires at the shunt trip contact on the control to prevent
operation of the disconnect circuit during this test.
Apply power to the control.
Measure the voltage from the line terminal to the load terminal on each of the
power phases. The voltage should be about 0.58 times the input line to line
voltage. If the voltage on any power cell or SCR pack is significantly less than
this value, one or both SCR’s in the power cell or SCR pack may be shorted.
Remove all power to the control.
If a shorted SCR is suspected, check for possible shorted connections, system
grounds or any other condition which may cause the short circuit condition.
Replace the SCR pack or power cell if no other causes were found. However,
installing a new SCR pack or power cell without determining the cause of failure
can result in repeated failure of the SCR’s. Refer to SCR replacement
procedure in this manual.
Troubleshooting 5-1
SCR Tests
Inspection
Full Voltage Test
5-2 Troubleshooting
If the SCR devices are suspected of failure, these tests can be used to test the SCR’s.
Be sure the physical condition of components is correct. Refer to Figure 5-1.
1.
Be sure power is off.
2.
Inspect power cell connections for tightness and signs of overheating.
3.
Replace snubber capacitors if there is any sign of oil or fluid leaking.
Snubbers are not used on size 55 and 80 amp power cells.
4.
Inspect SCR clamp insulator for cracks.
5.
SCR clamps should be tightened evenly.
(Use clamp gauge available from Baldor).
6.
Inspection and resistance test should be performed when system has
experienced:
Logic Control Module failure
MOV failure
Starting or running current imbalance
SCR replacement
Phase loss or single phasing
7.
Heat sinks and insulating surfaces must be clean and unobstructed.
8.
Size 55 and 80 amp power cells do not have snubber networks, SCR clamps or
insulating base.
After the motor reaches rated speed and the control is no longer in current limit, the
SCR’s turn full on and deliver full voltage to the motor. When power factor correction
(PF) is used, the control will reduce the voltage to the motor. For this reason, the PF
adjustment should be set to “OFF” during this test. Refer to Figure 5-1.
1.
Set the PF adjustment should be set fully CW (OFF) during this test.
2.
Turn power on. Wait for the motor to reach full speed.
3.
With the control in the run mode, measure the voltage across the line side to
the load side on each control power cell or SCR pack. The voltage should be
about 2 to 20 VAC. The voltage reading will vary depending upon the motor
and the type of meter used. Voltage readings must be balanced on all three
phases.
4.
If the voltage is higher across one or two power cells or SCR packs, not all
SCR’s are firing properly.
5.
If all three cells or SCR packs have approximately the same voltage drop
across line to load when the motor is up to speed and motor current is
unbalanced, the cause is the motor or unbalanced line voltage.
MN894
Resistance Test
Disconnect the power cell or SCR pack from all external wiring before you perform a
resistance check. Use an ohmmeter with 20,000 ohms per volt or greater impedance for
the resistance measurements. Refer to Table 5-1 and Figure 5-1.
1.
Be sure power is OFF.
2.
Remove all wiring from the power cell or SCR pack.
3.
Sizes 55 and 80 amps have three SCR packs, one for each phase mounted on
a single ground potential heatsink. Check all three SCR packs. For example
L-GL must be measured from L1-GL1, L2-GL2 and L3-GL3. Circuit SA-SB
requires only one measurement.
4.
Sizes 160 through 840 amps have a separate power cell for each phase.
Check all three power cells.
5.
If any of the resistance measurements are incorrect, the power cell or SCR
pack should be repaired or replaced before operating the starter.
Table 5-1
Circuit
L-A
T-B
SA-SB
A-B
L-GL
T-GT
Resistance
Less than 5 Ohms
Greater than 10k Ohms
5 to 100 Ohms
Note: Results from the resistance measurements can be satisfactory and the power
cells may still be bad if the power cell is breaking down under voltage.
If resistance checks are not conclusive, perform Blocking Voltage Check and SCR Full
Voltage Test.
Figure 5-1 Power Cell Configurations
MN894
Troubleshooting 5-3
SCR Replacement
Figure 5-2 shows the polarity and wire colors for correct SCR installation. It also shows
the locations of the tightening bars.
SCR Polarity
Figure 5-2 SCR Polarity
M160 / M250
M420 / M600 / M840
Cathode
Terminals GT, T, GL and L.
Tightening Bar
Gate (White wire)
Cathode (Red wire)
White wire to GL terminal,
Red wire to L terminal
White wire to GT terminal,
Red wire to T terminal
Anode
Anode
Tightening Bar
Cathode
Cathode
Tightening Bar
White wire to GL terminal,
Red wire to L terminal
Cathode
Tightening Bar
White wire to GT terminal,
Red wire to T terminal
Anode
Cathode
Anode
Terminals GT, T, GL and L.
Figure 5-3 shows how the pressure gauge is used.
SCR Pressure Gauge
Figure 5-3 SCR Tightening Pressure Gauge
4°
3°
3°
VE3000
VE2500
VE1000
VE2000
VE3500
VE5500
Calibration
SCR Mounting Kit Number
ÎÎÎÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎÎÎÎ
True Flat Surface
Tightening Bar
VE3000
VE2500
VE1000
VE2000
VE3500
VE5500
Calibration
ÎÎÎÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎÎÎÎ
Tightening Bar
Surface Deflection Measurement
Continued on next page.
5-4 Troubleshooting
MN894
With the SCR device installed with the tightening bar and bolts (Figure 5-2), tighten the
bolts as follows: (see Figure 5-3)
1.
Tighten the nuts evenly until finger tight.
2.
Tighten bolts in 1/4 turn increments.
3.
Use the SCR tightening pressure gauge and measure the deflection of the
Tightening bar. The middle and both ends of the gauge must be in solid contact
with the bar for an accurate reading. Correct pressure is indicated when the
gauge notch for the tightening kit number align.
Note: An anti-seize compound may be used on the bolt heads and threads to
reduce the torque required to obtain the correct mounting pressure.
Logic Control Module Resistance Test Refer to Figures 5-1 and 5-4.
This test will verify resistance measurements within the control.
1.
Be sure power is OFF.
2.
Disconnect the logic module from all external wiring before conducting
resistance checks.
3.
Use an ohmmeter with 20,000 ohms per volt greater.
4.
Compare the measured values with the values shown in Table 5-2.
Table 5-2
Line/Load
Circuit
Resistance
L1-L2
L1-L3
L2-L3
T1-T2
Greater than
T1-T3
500k Ohms
T2-T3
L1-T1
L2-T2
L3-T3
MB
Gates
Circuit
Resistance
L1-GL1
L2-GL2
L3-GL3
6.5 Ohms to
T1-GT1
8.5 Ohms
T2-GT2
T3-GT3
MB
Control Power Input
Circuit
Resistance
14-15
130 to
16-17
180 Ohms
MA
Control Power Input
Circuit
Resistance
14-15
220 - 240
14-16
260 - 560
14-17
615 - 910
14-18
1150 - 1180
Figure 5-4
Logic Control Module
L1 L2 L3
T1 T2 T3
MN894
Troubleshooting 5-5
Table 5-3 Troubleshooting Chart
Symptom
MCP trips as it is
cclosed
osed (a
(also
so see
Shunt Trip
p light
g
comes ON)
MCP trips
t i as the
th
motor is started
(also see Shunt
Trip light comes
ON)
MCP trips
p after
th motor
the
t is
i
running (also see
Shunt Trip light
comes ON)
Starter does
nothing when
start button is
pressed.
Control does not
accelerate motor
to full speed
(Stalls)
Insufficient torque
available from
current limit CL.
Motor
accelerates too
slowly.
Motor
accelerates too
quickly.
Motor current
and voltage
oscillates after
start
Motor is noisy or
vibrates when
starting
Cause
Motor is not connected.
ST contact on control is always closed.
Improper input voltage.
Shorted SCR.
Control transformer (if equipped) set for wrong
voltage.
MCP trip setting is too low.
Line voltage decreases during motor starting.
Motor or wiring is defective.
Capacitors on output of control.
Logic control module is defective.
Improper current calibration.
PF set too high.
Occasional line imbalance.
Ground or motor fault.
S2-6=ON but no bypass contactor is installed.
No line voltage.
Overload is open.
No contact closure across terminals 12 and 13.
Current trip occurs.
Control module has no power.
CL set too low.
Corrective Action
Connect motor to T1, T2 and T3 of control.
Repair or replace logic control module.
Obtain the correct source voltage at L1, L2 and L3.
Replace SCR or power cell.
Change tap connections for correct voltage.
Line voltage decreases to less than minimum
operating voltage during motor starting.
Fix incoming power regulation problem.
Improper current feedback.
Verify S1 settings for motor nameplate FLA rating.
CL set too low.
Increase CL adjustment (rotate CW).
Ramp up (RU) time set too long.
Decrease RU (rotate CCW).
Improper current feedback.
Verify S1 settings for motor nameplate FLA rating.
Current limit (CL) set too high.
Ramp up time (RU) set too short.
Initial pulse time (PT) set too long.
Improper current feedback.
Light or no load (is dependent on motor load).
A lightly loaded motor will reach full speed with
low starting current or voltage. Motor may
require the use of a tachometer.
Power factor correction set too high.
Reduce CL (rotate CCW).
Increase RU (rotate CW).
Reduce PT (rotate CCW).
Verify S1 settings for motor nameplate FLA rating.
Decrease TU, increase RU or install tachometer.
Line voltage decreases to less than minimum
operating voltage during motor starting.
Single phasing due to an open phase.
Single phasing or unbalanced current due to a
non-firing SCR.
Single phasing or unbalanced current due to a
defective logic control module.
Defective motor.
Fix incoming power regulation problem.
5-6 Troubleshooting
Increase MCP Trip setting.
Fix incoming power problem.
Check terminal and motor wiring.
Remove capacitors or move to line side of control.
Replace logic control module.
Verify S1 settings for motor nameplate FLA rating.
Reduce PF adjustment (rotate CCW).
Set S2-6 =ON to disable shunt trip while running.
Check motor wiring.
Check setting of S2-6. Should be Off.
Restore line voltage.
Reset overload.
Check start circuit.
Check S1 settings for correct current calibration.
Check control transformer jumper.
Increase CL adjustment (rotate CW).
Reduce PF setting (rotate CCW) until oscillation
stops.
Check wiring and overload heaters.
Check for shorted SCR and replace.
Repair or replace the logic control module.
Check motor for shorts, opens or grounds.
MN894
Table 5-3 Troubleshooting Chart Continued
Symptom
Overload relay
trips when starting
Overload relay
trips when running
Motor decelerates
too quickly
(RDD=OFF)
Motor decelerates
too slowly
(RDD=OFF)
Erratic operation
Shunt trip light
comes ON
Cause
Incorrect heater size or setting.
Loose or burned heater.
Long starting time. (high inertia loads may
require slow trip overloads.
Mechanical failure within the load.
Single phasing or unbalanced start circuit.
Excessive starting time (CL too low).
Incorrect heater size or setting.
Loose or burned heater.
Mechanical failure within the load.
Single phasing or unbalanced start circuit.
Ambient temperature too high.
Ramp down time (RD) set too short.
Corrective Action
Check overload relay heater table in Appendix A.
Tighten or replace heater.
Evaluate the thermal capabilities of the motor
before extending the overload trip time.
Check machinery for binding or excessive loading.
Refer to “Motor is noisy or vibrates when starting”.
Increase CL (rotate CW).
Check overload relay heater table in Appendix A.
Tighten or replace heater.
Check machinery for binding or excessive loading.
Refer to “Motor is noisy or vibrates when starting”.
Use ambient compensated overload relay.
Decrease RD (rotate CW).
Ramp down time (RD) set too long.
Decrease RD (rotate CCW).
Loose connections.
No load attached.
Loss of phase or low input voltage to starter.
Bad or misfiring SCR.
Grounded delta power source.
Check all connections.
Connect a motor to T1, T2 and T3 terminals.
Repair the input voltage problem.
Check resistance and replace SCR if defective.
Shunt trip is not effective.
Note: If the MCP is tripping, remove the relay or disconnect the wires from terminals 8 and 9.
You can then determine if the MCP is tripping or if the module is opening the MCP.
MN894
Troubleshooting 5-7
The control panel is intended to provide years of trouble free service with appropriate
cooling and protection from the elements. Should trouble occur, refer to the appropriate
control manual for control and motor troubleshooting information.
Reset the Circuit Breaker
If the circuit breaker is tripped, it must be reset to restore power. The breaker is tripped if
the handle is in the “Tripped” position as indicated in Figure 5-5.
Before the breaker is reset, locate the source of electrical trouble.
1.
Check for phase-to-phase and phase-to-ground shorts.
2.
Check for loose connections at power connectors (L1, L2, L3 and Earth as well
as T1, T2, T3 and Motor Ground).
3.
If all checks in steps 1 and 2 are OK, move the breaker handle all the way down
to the “Reset” position then move the handle to the “ON” position to restore
power. (In the “Reset” position, a click sound will be heard.)
4.
Verify that an overcurrent condition is tripping the circuit breaker (not a shunt
trip). If the circuit breaker shunt trip was energized, the trip was caused by the
LCM soft start module shunt trip feature. Eliminate the cause of the shunt trip.
Figure 5-5 Magnetic Circuit Breaker
ON
Tripped
OFF
Reset
Handle
Shunt Trip Device
Manual Trip
Shunt Trip Wires to
LCM soft start module
5-8 Troubleshooting
Trip Level
Rating Plug
MN894
Reset an Overload Relay
If the Overload relay is tripped, the tripped indicator (Reset Button of Figure 5-6) will be in
the “Tripped” position.
1.
Verify that the overload condition has been cleared to allow restart.
2.
Verify motor lead connections are tight.
3.
Allow time for the overload to cool.
4.
Press the “Reset Button” (Figure 5-6).
Figure 5-6 Overload Relay
Reset
Button
Fuse Replacement
Reset
Button
If the control circuit voltage drops to zero volts, the control power transformer fuses
(Figure 5-7) should be inspected. If a fuse is opened, perform the following steps:
1.
Check for line-to-ground short circuit condition and repair if necessary.
2.
Check control wiring and control devices (timers, relays, terminal blocks, wire
terminations, etc.) for signs of damage, overheating, or loose connections and
repair if necessary.
3.
Replace the fuse with the same fuse class, type, rating and interrupting
capacity.
Figure 5-7 Control Transformer with Fuses
MN894
Troubleshooting 5-9
5-10 Troubleshooting
MN894
Section 6
Specifications and Product Data
Identification
Three Phase Starters
M B 7 − 030 − C B − *
Control Type
M- Multipurpose
Control Group
A - Self powered logic control module
B - Logic control modules that require
115 or 230VAC.
Input Voltage Code
7208/230/460VAC (60Hz)
8230/460/575VAC (60Hz)
MA9220/380/415 (50Hz)
MB9380/400/415VAC (50Hz)
Ampere Rating
008- 8 Amp
016- 16 Amp
030- 30 Amp
055- 55 Amp
080- 80 Amp
160- 160 Amp
250- 250 Amp
420- 420 Amp
600- 600 Amp
840- 840 Amp
MN894
*
Bypass Contactor
0 − Normally not shown unless a
reduced size bypass is used.
A − First size smaller bypass.
B − Second size smaller bypass.
C − Third size smaller bypass.
Disconnect Size
0 − Normally not shown unless a
reduced size disconnect is used.
1 − Reduced size disconnect used:
i.e. 800 amp breaker on a 840amp
control instead of a 1000 amp
breaker.
Enclosure
A- Open
B- NEMA1 (IP32)
C- NEMA12 (IP65)
P- Panel Mount
Configuration
A - Combination with overload & circuit
breaker).
B - Non-combination (with overload).
C - Starter only.
D - Combination with fuse disconnect.
G - Bypass, combination starter.
H - Bypass, non-combination starter.
J - Bypass, starter only.
K - Bypass combination starter with
fuse disconnect.
Specifications and Product Data 6-1
Multipurpose Control Specifications
Three Phase Starters
Input
Voltage
VAC
3PH 60Hz
HP
IC
HP
IC
HP
IC
230
460
575
2
8
5
8
5
10
10
16
10
20
25
30
MA7-008
MA8-008
Input
Voltage
VAC
3PH 60Hz
HP
208
230
460
575
15
20
40
50
MB7-055
MB8-055
MA7-016
MA8-016
MB7-080
MB8-080
IC
HP
55
25
30
60
75
MA7-030
MA8-030
MB7-160
MB8-160
IC
HP
80
50
60
125
150
MB7-250
MB8-250
IC
HP
160
75
100
200
250
MB7-420
MB8-420
IC
HP
250
150
150
350
400
MB7-600
MB8-600
IC
HP
IC
420
200
250
500
600
600
MB7-840
MB8-840
HP
300
700
800
IC
840
IC = Continuous Current Rating
Input Ratings
Input Frequency
60/50 HZ ± 5%
Input Voltage
+10% to −15% of Voltage Rating (except 575 VAC, max= 620VAC)
Overload Rating
Continuous 115% of FLA; 400% for 30 seconds.
Phase
Three Phase
Duty
Continuous
Storage Conditions
Ambient Temperature:
-4 to 140°F (-20 to 60 °C)
Humidity:
0 - 95% RH Non-Condensing
Operating Conditions
Enclosure:
Open Panel
NEMA 1
NEMA 12
NEMA 4
(Indoor)
(Industrial indoor, general purpose)
(Industrial indoor, dust proof)
(Outdoor)
The SCR’s generate about 3.3 watts of heat per running amp (motor FLA). If the control
is mounted in an enclosure, the installer must provide fans or blower with sufficient ventilation. Fan or blower should be rated for at least 0.8 CFM per ampere of motor FLA rating.
Baldor provided enclosures are designed to dissipate the heat from the SCR’s.
Humidity:
0 - 95% RH Non-Condensing
Control Heat Loss
3.3 Watt per running ampere of input current
Ambient Operating Temperature:
32-113°F (0 to +45 °C) enclosed
32-122°F (0 to +50 °C) open panel
Altitude:
Sea level to 3300 Feet (1000 Meters)
Derate 1% per 330 Feet (100 Meters) above 3300 Feet
Derating
Derate Amp rating 1% per 330 Feet (100 Meters) above 3300 Feet
Derate Amp rating 1.5% per °C over 45 °C to 55 °C Max
6-2 Specifications and Product Data
MN894
Control Specifications
Control Method
6 SCR’s connected in inverse parallel for full-wave 3 phase control
Peak Inverse Voltage
208/230
460
575
1200VAC minimum
1200VAC minimum
1600VAC
Start Time
Adjustable range 3-50 seconds (current limit starting is not timed).
Stop Time
Adjustable range 5-50 seconds (can only extend stop time).
Initial Torque
Adjustable range: Starting 40-75%, Stopping 0-100%.
Current Limit (Selectable)
Adjustable range 75-400% of FLA (full load amperes).
Pulse Time (Selectable)
Adjustable range 0.1-1.5 seconds.
Current Monitor (Selectable)
Adjustable range 50-400% of FLA. Causes contact closure or control shut
down when current level is reached (after starting).
Power Factor
Adjustable for maximum reduced motor voltage, dependent on load.
Tach input (Selectable)
0-10VDC (maximum 10msec response time from tach).
Control module power
12VA at 115/230VAC ±5%
Status Contacts
125VAC at 0.5A, normally open. 60VA maximum rating.
Agency Listings
UL (Underwriters Laboratory) and cUL (Canada)
Rated Storage Temperature:
−40 °F to +140 °F (− 40 °C to +60 °C)
Note: A minimum inductance of 0.01 Henry is require for the SCR’s to commutate. Some large horsepower motors may
not have enough inductance and require adding inductors between the motor and control.
SCR Specifications
Overcurrent
Over current shut down at 450% of motor FLA nameplate rating.
Shorted SCR detection
Shunt Trip contract.
Protective Features
Overload
Electronic overload class 30.
SCR Thermostat
Trips on overtemperature of heatsink (sizes 55 amps and larger only).
Phase Loss
Shunt Trip contact (sizes 55 amps and larger only) active only at power-up.
Voltage Transient
MOV (metal oxide varistor).
Indicator LEDs
Power ON
Ramp End
Over Current
Shunt Trip
Current Monitor
Start/Run
Motor Power
Motor Current
MOV Devices Four varistors connected in wye configuration with one to ground.
MOV505EL
Max line volts=510VAC
Watts = 1.0
Max one time surge of 6500A @ 8V/20ms
MN894
MOV620E
Max line volts=625VAC
Watts = 1.0
Max one time surge of 6500A @ 8V/20ms
Specifications and Product Data 6-3
Wire Size & Tightening Torque Specifications
Combination Starter and Non-Combination Starter
and Control Only
8, 16 Amp Control Only
(A) Line Input
TB1
(C)
Control Connections
Line Input
(B)
(D)
GND
(C)
(D)
GND
OR
GND
Control
(D)
GND
Motor Output Load
(A)
(B)
(D)
Motor Output Load
Wire Size Torque Specifications Size 8,16
Terminal
(Identifier)
A
B
C
D
Amps
8, 16
30
55
80
160
250
420
600
840
All
8, 16, 30
55
80
160
250
420
600
840
6-4 Specifications and Product Data
Wire Size
AWG
10 - 16
8 - 18
4
3
3/0
350 KCMIL
(2) 300 KCMIL
(2) 500 KCMIL
(3) 500 KCMIL
12 - 22
6-14
Note 2
Note 2
Note 2
Note 2
Note 2
Note 2
Note 2
Torque
lb-in
20
35
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
12
45
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Note1: Refer to the label on the
equipment panel for line and
load tightening torque values.
Note2: Refer to the label on the
equipment panel for ground
wire sizes.
MN894
Mounting Dimensions
Open Panel
B
d
Dia
h
A
w
Open/Panel Dimensions
Amp
p
R ti
Rating
8
16
30
55
80
160
250
420
600
840
MN894
A
12.25
12.25
12.25
21.00
21.00
39.00
39.00
45.00
57.00
57.00
B
10.25
10.25
10.25
21.00
21.00
27.00
27.00
33.00
33.00
33.00
Control Only
h
w
11.63 9.63
11.63 9.63
11.63 9.63
19.24 19.24
19.24 19.24
31.24 25.24
31.24 25.24
43.24 31.24
55.24 31.24
55.24 31.24
d
10.16
10.16
10.16
12.62
12.62
9.35
11.35
13.35
13.35
13.35
Dia
0.25
0.25
0.25
0.50
0.50
0.50
0.50
0.50
0.50
0.50
A
21.00
21.00
21.00
21.00
21.00
39.00
39.00
45.00
57.00
57.00
Non-Combination Starter
B
h
w
d
14.50 19.50 13.00 10.16
14.50 19.50 13.00 10.16
14.50 19.50 13.00 10.16
21.00 19.24 19.24 12.62
21.00 19.24 19.24 12.62
27.00 31.24 25.24 9.35
27.00 31.24 25.24 11.35
33.00 43.24 31.24 13.35
33.00 55.24 31.24 13.35
33.00 55.24 31.24 13.35
Dia
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
A
21.00
21.00
21.00
21.00
21.00
39.00
39.00
45.00
57.00
57.00
Combination Starter
B
h
w
d
14.50 19.50 13.00 10.16
14.50 19.50 13.00 10.16
14.50 19.50 13.00 10.16
21.00 19.24 19.24 12.62
21.00 19.24 19.24 12.62
27.00 31.24 25.24 9.35
27.00 31.24 25.24 11.35
33.00 43.24 31.24 13.35
33.00 55.24 31.24 13.35
33.00 55.24 31.24 13.35
Dia
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
Specifications and Product Data 6-5
Mounting Dimensions Continued
NEMA 1, 3R and 12
B
d
Dia
h
A
w
NEMA 1 Dimensions
Amp
p
R ti
Rating
8
16
30
55
80
160
250
420
600
840
A
14.00
14.00
14.00
24.00
24.00
42.00
42.00
48.00
60.00
60.00
B
12.00
12.00
12.00
24.00
24.00
30.00
30.00
36.00
36.00
36.00
Control Only
h
w
11.00 11.00
11.00 11.00
11.00 11.00
25.24 18.00
25.24 18.00
37.24 24.00
37.24 24.00
49.24 30.00
61.24 30.00
61.24 30.00
B
16.00
16.00
16.00
24.00
24.00
36.00
36.00
36.00
48.00
48.00
Control Only
h
w
d
21.24 10.00 11.35
21.24 10.00 11.35
21.24 10.00 11.35
31.24 18.00 11.35
43.24 18.00 11.35
43.24 30.00 9.35
43.24 30.00 11.35
61.24 30.00 13.35
61.24 42.00 13.35
61.24 42.00 13.35
d
11.35
11.35
11.35
12.62
12.62
9.35
11.35
13.35
13.35
13.35
Dia
0.28
0.28
0.28
0.44
0.44
0.44
0.44
0.44
0.44
0.44
A
24.00
24.00
24.00
24.00
24.00
42.00
42.00
48.00
60.00
60.00
Non-Combination Starter
B
h
w
d
16.00 21.88 11.00 11.35
16.00 21.88 11.00 11.35
16.00 21.88 11.00 11.35
24.00 25.24 18.00 12.62
24.00 25.24 18.00 12.62
30.00 37.24 24.00 9.35
30.00 37.24 24.00 11.35
36.00 49.24 30.00 13.35
36.00 61.24 30.00 13.35
36.00 61.24 30.00 13.35
Dia
0.31
0.31
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
A
24.00
24.00
24.00
24.00
24.00
42.00
42.00
48.00
60.00
60.00
Combination Starter
B
h
w
d
16.00 21.88 11.00 11.35
16.00 21.88 11.00 11.35
16.00 21.88 11.00 11.35
24.00 25.24 18.00 12.62
24.00 25.24 18.00 12.62
30.00 37.24 24.00 9.35
30.00 37.24 24.00 11.35
36.00 49.24 30.00 13.35
36.00 61.24 30.00 13.35
36.00 61.24 30.00 13.35
Dia
0.31
0.31
0.31
0.44
0.44
0.44
0.44
0.44
0.44
0.44
Dia
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
A
24.00
24.00
24.00
30.00
30.00
42.00
42.00
60.00
60.00
60.00
Combination Starter
B
h
w
d
20.00 25.24 14.00 11.35
20.00 25.24 14.00 11.35
20.00 25.24 14.00 11.35
24.00 31.24 18.00 11.35
24.00 31.24 18.00 11.35
36.00 43.24 30.00 9.35
36.00 43.24 30.00 11.35
36.00 61.24 30.00 13.35
48.00 61.24 42.00 13.35
48.00 61.24 42.00 13.35
Dia
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
NEMA 12/3R Dimensions
Amp
p
R ti
Rating
8
16
30
55
80
160
250
420
600
840
A
20.00
20.00
20.00
30.00
30.00
42.00
42.00
60.00
60.00
60.00
6-6 Specifications and Product Data
Dia
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
A
20.00
20.00
20.00
30.00
30.00
42.00
42.00
60.00
60.00
60.00
Non-Combination Starter
B
h
w
d
16.00 21.24 10.00 11.35
16.00 21.24 10.00 11.35
16.00 21.24 10.00 11.35
24.00 31.24 18.00 11.35
24.00 31.24 18.00 11.35
36.00 43.24 30.00 9.35
36.00 43.24 30.00 11.35
36.00 61.24 30.00 13.35
48.00 61.24 42.00 13.35
48.00 61.24 42.00 13.35
MN894
Connection Diagrams
MA Style 8, 16 and 30 AMP Combination and Non-Combination Starter and Control only
(Three Wire)
Start
(Hand - Off - Auto)
Two Wire
Control Device
H
Stop
O
Caution: Read Note (Two Wire)
A
R
TB1 11
12
13
TB1 11
14
12
13
14
11
TB1
12
13
Line Input
L2
L1
L3
14
CB
X
A
F3
B
A
F1
B
A
F2
B
MOV
115VAC
CB
Shunt
Trip
97
98
OL
96
OL
14
13
12
11
10
9
8
7
6
5
4
3
2
1
15
Close
To Run
Start /
Run
16
60Hz
Shunt
Trip
50Hz
18
Ramp
End
Tach
Input
MTR
PWR
CUR
MON
LCM
CT Input
19
Legend:
CB F1, F2 F3 LCM MOV OL RTB1 X-
17
220 208
380 230
415 460
N.A. 575
95
Shunt trip motor circuit protector or fuse disconnect.
Control transformer fuses.
Control branch circuit fuse.
Logic control module - type M.
Metal oxide varistors.
Overload relay (electronic).
Run relay (customer provided).
Terminal block.
Control transformer (control voltage).
L1
L2
L3
T1
T2
T3
20
Caution:
To avoid equipment damage, jumper
terminal 14 to the appropriate terminal
that matches the line voltage.
LCM
Terminals
14-15
14-16
14-17
14-18
Voltage
60Hz
50Hz
208VAC 220VAC
230VAC 380VAC
460VAC 415VAC
575VAC
−−
OL
T1
T2
T3
To Motor
Notes:
Control transformer must be properly connected for line voltage (see transformer nameplate).
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.
Motor must be connected before power is applied. Otherwise, the shunt trip will will trip the motor circuit
protector.
Tachometer is only required when LCM is used in Tach Feedback mode.
Motor circuit protector and this circuit are not provided with the non−combination starters, control only and fuse
disconnect versions.
MN894
Specifications and Product Data 6-7
Section 1
General Information
Connection Diagrams Continued
MB Style 8, 16 and 30 AMP Combination and Non-Combination Starter and Control only
(Three Wire)
Start
(Hand - Off - Auto)
Two Wire
Control Device
H
Stop
O
Caution: Read Note (Two Wire)
A
R
TB1 11
12
13
TB1 11
14
12
13
14
11
TB1
12
13
Line Input
L2
L1
L3
14
CB
X
A
F3
B
A
F1
B
A
F2
B
MOV
115VAC
95
CB
Shunt
Trip
97
98
OL
96
OL
13
12
11
10
9
8
7
6
5
4
3
2
1
14
15
14
15
16
Shunt
Trip
230VAC
16
17
Ramp
End
Tach
Input
MTR
PWR
CUR
MON
LCM
CT Input
19
Legend:
CB F1, F2 F3 LCM MOV OL RTB1 X-
17
Close
To Run
Start /
Run
Shunt trip motor circuit protector or fuse disconnect.
Control transformer fuses.
Control branch circuit fuse.
Logic control module - type M.
Metal oxide varistors.
Overload relay (electronic).
Run relay (customer provided).
Terminal block.
Control transformer (control voltage).
L1
L2
L3
T1
T2
T3
20
OL
T1
T2
T3
To Motor
Notes:
Control transformer must be properly connected for line voltage (see transformer nameplate).
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.
Motor must be connected before power is applied. Otherwise, the shunt trip will will trip the motor circuit
protector.
Tachometer is only required when LCM is used in Tach Feedback mode.
Motor circuit protector and this circuit are not provided with the non−combination starters, control only and fuse
disconnect versions.
6-8 Specifications and Product Data
MN894
Section 1
General Information
Connection Diagrams Continued
MA Style 55 and 80 AMP NEMA 1 and Panels Combination and Non-Combination Starter and Control only
(Three Wire)
(Hand - Off - Auto)
Start
Two Wire
Control Device
H
Caution: Read Note O
Stop
Line Input
L2
A
L1
1 2
TB1
3
4
5
6
7
8
96
10
9
95
1 2
TB1
R1
OL
13
3
5
4
6
7
8
14
F3
B
X
115VAC
CF
R1
R1
12
R2
9
CB
8
13 14
5
97
98
OL
R2
Shunt Trip
13
12
11
10
9
8
7
6
5
4
3
2
1
14
15
Close
To Run
Start /
Run
60Hz
50Hz
17
Ramp
End
Tach
Input
MTR
PWR
CUR
MON
A
F1
B
A
F2
B
MOV
18
Shunt
Trip
LCM
CT Input
19
Legend:
CB CF CT1 F1, F2 F3 LCM MOV OL PC1 R1 R2 SSCR TB1 X-
16
220 208
380 230
415 460
N.A. 575
5
10
CB
A
9
9
L3
L1
L2
L3
GL1
GL2
GL3
GT1
GT2
GT3
T1
T2
T3
L3
L2
L1
T1
T2
T3
SA
PC1
GL3
SCR
SCR
GL2
GL1
GT3
SCR
GT2
GT1
SB
S
20
CT1
OL
Shunt trip motor circuit protector or fuse disconnect.
Power cell cooling fan.
LCM current transformer.
Control transformer fuses.
Control branch circuit fuse.
Logic control module - type M.
Metal oxide varistors.
Overload relay (electronic).
SCR power cell.
Run relay, DPDT.
Shunt trip relay, DPDT.
SCR overtemperature switch.
Silicon controlled rectifier.
Terminal block.
Control transformer (control voltage).
Caution:
T1
To avoid equipment damage, jumper
terminal 14 to the appropriate terminal
that matches the line voltage.
LCM
Terminals
14-15
14-16
14-17
14-18
T2
To Motor
T3
Voltage
60Hz
50Hz
208VAC 220VAC
230VAC 380VAC
460VAC 415VAC
575VAC
−−
Notes:
Control transformer must be properly connected for line voltage (see transformer nameplate).
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.
Motor must be connected before power is applied. Otherwise, the shunt trip will will trip the motor circuit
protector.
Tachometer is only required when LCM is used in Tach Feedback mode.
Motor circuit protector and this circuit are not provided with the non−combination starters and fuse disconnect
versions.
MN894
Specifications and Product Data 6-9
Section 1
General Information
Connection Diagrams Continued
MB Style 55 and 80 AMP NEMA 1 and Panels Combination and Non-Combination Starter and Control only
(Three Wire)
(Hand - Off - Auto)
Start
Two Wire
Control Device
H
Caution: Read Note O
Stop
Line Input
L2
A
L1
1 2
TB1
3
4
5
6
7
8
96
10
9
95
1 2
TB1
R1
OL
13
3
4
5
6
7
8
14
F3
B
X
115VAC
5
CF
R1
R1
12
R2
9
CB
8
13 14
5
97
98
OL
R2
Shunt Trip
13
12
11
10
9
8
7
6
5
4
3
2
1
14
Close
To Run
Start /
Run
15
14
15
Ramp
End
MTR
PWR
CUR
MON
LCM
CT Input
A
F1
B
A
F2
B
MOV
17
230VAC
19
Legend:
CB CF CT1 F1, F2 F3 LCM MOV OL PC1 R1 R2 SSCR TB1 X-
16
Shunt
Trip
Tach
Input
10
CB
A
9
9
L3
16
17
L1
L2
L3
GL1
GL2
GL3
GT1
GT2
GT3
T1
T2
T3
L3
L2
L1
T1
T2
T3
SA
PC1
GL3
SCR
SCR
SCR
S
GL2
GL1
GT3
GT2
GT1
SB
20
CT1
OL
Shunt trip motor circuit protector or fuse disconnect.
Power cell cooling fan.
LCM current transformer.
Control transformer fuses.
Control branch circuit fuse.
Logic control module - type M.
Metal oxide varistors.
Overload relay (electronic).
SCR power cell.
Run relay, DPDT.
Shunt trip relay, DPDT.
SCR overtemperature switch.
Silicon controlled rectifier.
Terminal block.
Control transformer (control voltage).
T1
T2
To Motor
T3
Notes:
Control transformer must be properly connected for line voltage (see transformer nameplate).
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.
Motor must be connected before power is applied. Otherwise, the shunt trip will will trip the motor circuit
protector.
Tachometer is only required when LCM is used in Tach Feedback mode.
Motor circuit protector and this circuit are not provided with the non−combination starters and fuse disconnect
versions.
6-10 Specifications and Product Data
MN894
Section 1
General Information
Connection Diagrams Continued
NEMA 1 & Panel Mounted Size 160−840 AMP Control Only
(Hand - Off - Auto)
Enclosure
Fan
(Three Wire)
O
Start
Stop
3
4
1 2
TB1
5
6
8
7
4
5
6
7
8
13
14
F3
B
X
115VAC
CF
CF
CF
R1
12
8
13
12
11
10
9
8
7
6
5
4
3
2
1
Power cell cooling fan.
Snubber capacitor.
LCM current transformer.
Primary current transformer.
Control transformer fuses.
Control branch circuit fuse.
Logic control module - type M.
Metal oxide varistors.
A
F1
B
A
F2
B
3
5
4
6
7
8
9
10
Line Input
L2
L3
MOV
15
14
16
Close
To Run
Start /
Run
Shunt
Trip
Ramp
End
LCM
Tach
Input
MTR
PWR
CUR
MON
CT Input
19
Legend:
CF CS CT1 CT2 F1, F2 F3 LCM MMOV -
M
1 2
TB1
10
L1
A
9
5
9
Caution: Read Note TB1
10
9
3
R1
R1
115VAC
Line Starter
Control Circuit
OL
OL
OL
2
(Line Switched)
Enclosure
Fan
A
Enclosure
Fan
1
Two Wire
Control Device
H
17
L1
L2
L3
GL1
GL2
GL3
GT1
GT2
GT3
T1
T2
T3
PC1/L
PC2/L
PC1
Line
PC2
Line
PC3
Line
PC3/L
PC1/GL
PC2/GL
PC3/GL
PC1/GT
PC2/GT
PC3/GT
L1
GL1
GT1
T1
S1A
S1B
L
GL
GT
T
SA
SB
SC
L2
GL2
RS
S
PC1/T
GT2
T2
S2A
S2B
L
GL
GT
T
SA
SB
SC
L3
GL3
RS
S
GT3
T3
S3A
S3B
Load
L
GL
GT
T
SA
SB
SC
RS
S
Load
Load
PC2/T
PC3/T
20
OL Overload relay (electronic).
T1
PC1,2,3 - SCR power cells.
R1 Run relay, DPDT.
RS Snubber resistor.
SSCR overtemperature switch.
SCR - Silicon controlled rectifier.
TB1 Terminal block.
XControl transformer (control voltage).
CT1
CT2
T2
CT1
MBX140 = 8 Turns
MBX160 = 8 Turns
MBX250 = 4 Turns
MBX420 = 4 Turns
MBX600 = 4 Turns
MBX840 = 4 Turns
T3
To Motor
4 Turns (3 Loops)
Notes:
Control transformer must be properly connected for line voltage (see transformer nameplate).
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.
Number of cooling fans depends on the FLA rating.
Tachometer is only required when LCM is used in Tach Feedback mode.
MOVs are connected in parallel for greater energy absorption for control sizes above 420Amp FLA.
For factory supplied enclosure fans only.
MN894
Specifications and Product Data 6-11
Section 1
General Information
Connection Diagrams Continued
NEMA 1 & Panel Mounted Size 160−840 AMP Combination & Noncombination
(Hand - Off - Auto)
Two Wire
Control Device
H
O
Enclosure
Fan
(Three Wire)
A
Caution: Read Note Start
Stop
Enclosure
Fan
1
2
1 2
TB1
3
4
5
6
8
7
5
4
6
8
7
9
95
96
10
TB1
CB
R1
OL
13
14
A
F3
B
X
115VAC
9
5
CF
CF
CF
R2
9
97
OL
Line Input
L2
L1
3
R1
10
9
CB
F1
B
A
F2
B
MOV
14
R1
12
13 14
Shunt Trip R2
A
5
98
8
13
12
11
10
9
8
7
6
5
4
3
2
1
L3
15
16
Close
To Run
Start /
Run
Shunt
Trip
Ramp
End
LCM
Tach
Input
MTR
PWR
CUR
MON
CT Input
19
17
L1
L2
L3
GL1
GL2
GL3
GT1
GT2
GT3
T1
T2
T3
PC1/L
PC2/L
PC1
Line
PC2
PC3/L
PC1/GL
PC2/GL
PC3/GL
PC1/GT
PC2/GT
PC3/GT
L1
GL1
GT1
T1
S1A
S1B
L
GL
GT
T
SA
SB
SC
L2
GL2
GT2
RS
S
T2
S2A
S2B
PC1/T
L
GL
GT
T
SA
SB
Line
PC3
SC
L3
L
GL
GT
T
SA
SB
GL3
GT3
RS
S
T3
S3A
S3B
Load
Line
SC
RS
S
Load
Load
PC2/T
PC3/T
CT2
20
OL
CT3
CT4
OL
OL
CT1
Legend:
CB Shunt trip motor circuit protector or fuse disconnect..
OL Overload relay (electronic).
CF Power cell cooling fan.
PC1,2,3 - SCR power cells.
CS Snubber capacitor.
T1
R1 Run relay, DPDT.
CT1 LCM current transformer.
R2 Shunt trip relay, DPDT.
CT2,3,4 - Overload current transformer.
RS Snubber resistor.
F1, F2 - Control transformer fuses.
SSCR overtemperature switch.
F3 Control branch circuit fuse.
SCR - Silicon controlled rectifier.
LCM - Logic control module - type M.
TB1 Terminal block.
MOV - Metal oxide varistors.
XControl transformer (control voltage).
T2
CT1
MBX140 = 8 Turns
MBX160 = 8 Turns
MBX250 = 4 Turns
MBX420 = 4 Turns
MBX600 = 4 Turns
MBX840 = 4 Turns
T3
To Motor
4 Turns (3 Loops)
Notes:
Control transformer must be properly connected for line voltage (see transformer nameplate).
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.
Number of cooling fans depends on the FLA rating.
Tachometer is only required when LCM is used in Tach Feedback mode.
MOVs are connected in parallel for greater energy absorption for control sizes above 420Amp FLA.
Motor circuit protector and this circuit are not provided with the non−combination starters and fuse disconnect
versions.
For factory supplied enclosure fans only.
6-12 Specifications and Product Data
MN894
Section 1
General Information
Connection Diagrams Continued
NEMA 12 Size 160−840 AMP Combination & Noncombination Bypass
O
Enclosure
Fan
Start
Two Wire Control Device
H
(Hand - Off - Auto)
(Three Wire)
A
Caution: Read Note Stop
Enclosure
Fan
1
2
3
5
4
1 2
TB1
6
8
7
9
95
96
10
3
4
5
9
5
R2
97
98
OL
OL
13
MOV
14
A1
12
13 14
BP
5
F3
B
X
A
A
F1
B
F2
B
14
R1
R2
13 14
A2
R3
8
13
12
11
10
9
8
7
6
5
4
3
2
1
L3
CB
R1
CF
CF
Shunt
Trip
R3
9
Line Input
L2
CB
5
10
9
TB1
115VAC
CF
9
8
7
L1
A
R1
6
15
16
Close
To Run
Start /
Run
Shunt
Trip
Ramp
End
LCM
Tach
Input
MTR
PWR
CUR
MON
CT Input
19
17
BP
L1
L2
L3
GL1
GL2
GL3
GT1
GT2
GT3
T1
T2
T3
PC1/L
PC2/L
PC1
PC2
Line
PC3/L
PC1/GL
PC2/GL
PC3/GL
PC1/GT
PC2/GT
PC3/GT
L1
GL1
GT1
T1
S1A
S1B
L
GL
GT
T
SA
SB
SC
L2
GL2
GT2
RS
S
T2
S2A
S2B
PC1/T
L
GL
GT
T
SA
SB
PC3
Line
SC
L3
GL3
GT3
RS
S
T3
S3A
S3B
Load
L
GL
GT
T
SA
SB
Line
SC
RS
S
Load
Load
PC2/T
PC3/T
20
OL
CT2
Legend:
BP BYPASS Contactor.
CB Shunt trip motor circuit protector or fuse disconnect..
CF Power cell cooling fan.
OL Overload relay (electronic).
CS Snubber capacitor.
PC1,2,3 - SCR power cells.
CT1 LCM current transformer.
T1
R1 Run relay, DPDT.
CT2,3,4 - Overload current transformer.
R2 Shunt trip relay, DPDT.
F1, F2 - Control transformer fuses.
RS Snubber resistor.
F3 Control branch circuit fuse.
SSCR overtemperature switch.
LCM - Logic control module - type M.
SCR - Silicon controlled rectifier.
MOV - Metal oxide varistors.
TB1 Terminal block.
XControl transformer (control voltage).
OL
CT1
CT3
T2
CT1
MBX140 = 8 Turns
MBX160 = 8 Turns
MBX250 = 4 Turns
MBX420 = 4 Turns
MBX600 = 4 Turns
MBX840 = 4 Turns
OL
CT4
T3
To Motor
4 Turns (3 Loops)
Notes:
Control transformer must be properly connected for line voltage (see transformer nameplate).
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.
Number of cooling fans depends on the FLA rating.
Tachometer is only required when LCM is used in Tach Feedback mode.
MOVs are connected in parallel for greater energy absorption for control sizes above 420Amp FLA.
Motor circuit protector and this circuit are not provided with the non−combination starters and fuse disconnect
versions.
For factory supplied enclosure fans only.
MN894
Specifications and Product Data 6-13
Section 1
General Information
6-14 Specifications and Product Data
MN894
Appendix A
Reference Information
Glossary
BP
CC
CCW
CL
CM
CS & RS
Bypass Contactor
Current Calibrator
Counterclockwise
Current Limit
Current Monitor
Resistor & Capacitor series
circuit
Current Monitor
Current Transformer
Clockwise
Full Load Amperes (Motor)
Logic Control Module
Light Emitting Diode
Motor Circuit Protector
Metal Oxide Varistor
Motor Power
Over Current Shutdown
Overload Relay
Power Cells
CUR MON
CT
CW
FLA
LCM
LED
MCP
MOV
MTR PWR
OC
OL
PC
PF
PIV
PT
PWR
Ramp End
RD
RDD
RMS
RU
SCR
Shunt Trip
SSC
TACH
TD
Power Factor Correction
Peak Inverse Voltage
Starting Pulse Time
Power
End of Voltage Ramp
Ramp Down Time
Ramp Down Disable
Root Means Squared
Ramp Up Time
Silicon Controlled Rectifier
Shorted SCR Detection
Soft Start Control
Tachometer
Reduced torque value at start
of Ramp Down Time
Initial starting torque at Ramp
Up Time
Control Transformer
TU
X
Current Calibration Chart
Caution:
Size 008
Motor
M
t FLA
1.0−1.1
1.1−1.2
1.2−1.3
1.3−1.4
1.4−1.5
1.5−1.6
1.6−1.7
1.7−1.8
1.8−1.9
1.9−2.1
2.1−2.3
2.3−2.5
2.5−2.7
2.7−3.0
3.0−3.3
3.3−3.6
3.6−3.9
3.9−4.4
4.4−4.8
4.8−5.2
5.2−5.6
5.6−6.0
6.0−6.4
6.4−6.8
6.8−7.4
7.4−8.0
Settings for S1 are based on motors with 600% locked rotor amps. Motors with locked
rotor amps greater than 600% should use a higher setting. Baldor Super-ER motors on
high inertia loads should be set 1 or 2 settings higher than the suggested S1 setting. If a
load takes too long to start, use the next higher setting.
Select the table that matches you starter size only. Do not use the switch settings for a starter
size that is different than the one you are setting up. Using the wrong switch setting can damage
the Multipurpose Soft Starter control.
1
1
0
0
0
0
0
1
0
0
0
1
0
0
0
0
1
0
0
1
1
1
1
0
0
0
1
2
1
0
0
0
1
0
0
1
0
0
0
1
1
1
1
0
0
0
1
0
1
0
1
0
1
1
S1 Switch
3
1
0
0
0
1
1
0
1
1
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
1
Position and
4
5
0
0
0
1
1
1
0
0
0
0
1
0
0
1
0
1
1
1
0
0
0
0
1
0
1
0
0
1
0
1
1
1
1
1
0
0
0
0
0
0
0
0
1
0
1
0
1
0
1
0
1
0
Setting
6
0
0
0
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
7
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Size 016
Motor
M
t FLA
6.0−6.5
6.5−7.0
7−8
8−9
9−10
10−11
11−12
12−13
13−14
14−16
Size 030
Motor
M
t FLA
12−13
13−14
14−15
15−16
16−18
18−20
20−22
22−24
24−27
27−30
1
1
0
1
1
1
1
1
0
0
1
2
0
0
1
0
1
0
1
0
1
1
S1 Switch
3
0
1
1
0
0
1
1
0
0
0
Position and
4
5
0
0
0
0
0
0
1
0
1
0
1
0
1
0
0
1
0
1
0
1
Setting
6
1
1
1
1
1
1
1
1
1
1
7
1
1
1
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
2
0
1
0
1
0
1
0
1
0
1
S1 Switch
3
0
0
1
1
0
0
1
1
0
0
Position and
4
5
0
0
0
0
0
0
0
0
1
0
1
0
1
0
1
0
0
1
0
1
Setting
6
1
1
1
1
1
1
1
1
1
1
7
1
1
1
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
1
1
1
Note: 0=Off, 1=On
MN894
Appendix A-1
Size 055
Motor
M
t FLA
24−26
27−30
31−34
35−38
39−42
43−45
46−48
49−51
52−55
Size 080
M t FLA
Motor
44−46
47−52
53−58
59−64
65−69
70−75
76−80
Size 140
Motor
M
t FLA
58−63
64−70
71−78
79−86
87−95
96−105
106−120
121−128
129−140
Size 160
Motor
M
t FLA
65−70
71−78
79−87
88−97
98−108
109−120
121−135
136−148
149−160
2
1
0
0
1
0
1
1
0
0
S1 Switch
3
0
1
0
0
1
1
1
0
0
Position and
4
5
0
0
0
0
1
0
1
0
1
0
1
0
1
0
0
1
0
1
Setting
6
1
1
1
1
1
1
1
1
1
1
0
0
1
1
0
1
0
2
1
0
0
1
0
0
1
S1 Switch
3
1
0
0
0
1
1
1
Position and
4
5
1
0
0
1
0
1
0
1
0
1
0
1
0
1
Setting
6
1
1
1
1
1
1
1
7
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
200−214
215−234
235−249
250−274
275−299
300−329
330−361
362−390
391−420
1
0
1
1
0
0
0
1
1
0
2
1
0
1
0
1
0
1
0
0
S1 Switch
3
0
0
1
1
1
0
0
0
0
Position and
4
5
0
0
0
1
1
1
1
0
0
1
0
0
1
0
0
1
1
1
Setting
6
1
1
1
0
0
1
1
1
1
7
1
1
1
0
0
0
0
0
0
8
0
0
0
1
1
1
1
1
1
Size 600
Motor
M
t FLA
1
1
1
0
1
0
1
0
1
1
2
0
1
0
1
1
1
0
1
0
S1 Switch
3
0
1
1
1
0
0
1
0
0
Position and
4
5
0
1
1
1
1
0
0
1
0
0
1
0
0
1
1
1
0
0
Setting
6
1
1
0
0
1
1
1
1
0
7
1
1
0
0
0
0
0
0
1
8
0
0
1
1
1
1
1
1
1
1
0
1
0
0
0
0
1
0
1
7
1
1
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
1
1
Size 250
Motor
M
t FLA
108−113
114−127
128−144
145−161
162−180
181−201
202−224
225−250
Size 420
Motor
M
t FLA
320−340
341−360
361−390
391−430
431−470
471−520
521−570
571−600
Size 840
Motor
M
t FLA
471−520
521−570
571−630
631−690
691−740
741−800
801−840
1
1
0
0
1
0
1
0
0
2
1
1
0
1
0
1
1
0
S1 Switch
3
0
0
1
0
0
0
1
0
Position and
4
5
0
1
0
0
0
1
0
0
0
1
1
1
0
0
0
1
Setting
6
0
1
1
0
0
0
1
1
7
1
1
1
0
0
0
0
0
8
0
0
0
1
1
1
1
1
1
1
0
1
1
0
1
0
0
0
2
1
1
0
1
0
1
0
0
0
S1 Switch
3
0
0
0
1
1
0
0
1
0
Position and
4
5
0
0
1
0
0
1
0
1
1
1
0
0
1
0
1
0
0
1
Setting
6
1
1
1
1
1
0
0
0
0
7
0
0
0
0
0
1
1
1
1
8
1
1
1
1
1
1
1
1
1
1
1
0
0
1
1
0
1
1
2
1
1
1
1
1
1
0
1
S1 Switch
3
0
0
0
0
0
0
0
1
Position and
4
5
1
0
0
1
1
1
0
0
1
0
0
1
1
1
1
1
Setting
6
0
0
0
1
1
1
1
1
7
0
0
0
0
0
0
0
0
8
1
1
1
1
1
1
1
1
1
0
1
1
0
1
1
0
2
1
0
1
1
0
0
0
S1 Switch
3
0
0
1
1
0
1
0
Position and
4
5
0
1
1
1
1
1
0
0
1
0
1
0
0
1
Setting
6
1
1
1
0
0
0
0
7
0
0
0
1
1
1
1
8
1
1
1
1
1
1
1
Note: 0=Off, 1=On
A-2 Appendix
MN894
Quick Reference Chart
RU
+−
TU
−+
50
3
40
75
S
T
A
CL
−+
75
400
R
T
PT
−+
RD
+−
0
5
TD
−+
0
CM
− +
Torque Up (40-75% voltage)
Tachometer:
Disabled.
Voltage:
Initial starting voltage for ramp.
Current Limit (75-400% FLA)
Tachometer or voltage: Enabled by S2-5=ON. Maximum current during ramp up and ramp down.
Pulse Time (0-1.5 sec.)
Tachometer:
Disabled.
Voltage:
Duration of 400% FLA starting pulse.
1.5
S
50
Ramp Up Time (3-50 sec.)
Tachometer:
Time to reach full speed.
Voltage:
Time to reach full speed.
100
T
O
P
R
50
400
0
100
PF
− +
U
N
Ramp Down Time (5-50 sec.) − (Disabled with S2-1=ON)
Tachometer:
Time to reach zero speed.
Voltage:
Time to reach zero speed.
Torque Down Advance (0-100%) − (Disabled with S2-1=ON)
Tachometer or voltage: Percentage reduction from full motor voltage for starting ramp down to zero volts.
Current Monitor (50-400% FLA) Enabled at end of start cycle.
S2-2=ON:
If motor current exceeds CM value, control will shutdown, CUR MON contact will close and
CUR MON light is ON.
CUR MON:
Indicates CM or CL have been exceeded.
S2-2=OFF:
Control will not shutdown, contact
will close, LED is ON.
MTR PWR:
Indicates voltage is applied to motor
during start, run & ramp down.
Power Factor
(0-100%)
TACH:
Tachometer input (0-10VDC).
0 to maximum allowable motor voltage
RAMP END:
End of start ramp (full run condition).
reduction to improve power factor.
SHUNT TRIP:
Shunt trip due to shorted SCR.
START/RUN:
Confirm Close to Run contact is closed.
CLOSE TO RUN: Start contact is closed.
Power applied to control.
Overcurrent shut down
(450% FLA)
CUR
MON
S1
MTR
PWR
TACH
RAMP
END
SHUNT
TRIP
START/
RUN
CLOSE
TO RUN
Current Calibration and “Motor Current” bar graph. S1 selects 255 calibration points for motor FLA.
See “Current Calibration Chart” in this section for the proper setting.
Bar Graph, displays the value of motor current during operation.
RDD: S2-1, Ramp Down Disable.
ON
Control is immediately disabled when the “Close to Run” input is opened.
OFF
Control will ramp down when the “Close to Run” input is opened.
CM:
S2-2, Current Monitor Trip.
ON
Control will disable and CUR MON light and contact will indicate an overcurrent condition.
OFF
CUR MON light and contact will indicate an overcurrent condition.
OC:
S2-3, Over current shut down.
ON
Overcurrent shutdown will turn on CUR MON light and close the CUR MON contact.
OFF
Overcurrent shutdown will disable control with no affect to CUR MON light and contact.
TACH: S2-4, Tachometer input enable.
ON
Control is in tachometer feedback ramp mode.
OFF
Control is in voltage ramp mode.
CL:
S2-5, Current Limit enable.
ON
Current will not exceed Current Limit adjustment during ramp up and down except during pulse start.
OFF
Current Limit adjustment has no effect.
BP:
S2-6, Bypass contactor enable.
ON
Shunt trip circuit is disabled during full on condition for bypass contactor to be used.
OFF
Shunt trip circuit is enabled in all conditions.
MN894
Appendix A-3
Overload Relay Adjustment
A class 30 electonic relay is provided with combination and non-combination starters.
Read the FLA from the motor nameplate and set the overload dial to the correct ampere
setting. Refer to the table that represents the starter size.
Caution:
Select the table that matches you starter size only. Do not use the
switch settings for a starter size that is different than the one you
are setting up. Using the wrong switch setting can damage the
Multipurpose Soft Starter control.
Caution:
For starters size 8, 16 and 30A is direct reading. Using the wrong
setting may damage the multiputpose soft start control.
Overload Relay - Electronic Class 30
Size 055# Passes
through the window
1 (Straight through)
2 (1 loop)
3 (2 loop)
Size 080# Passes
through the window
1 (Straight Through)
2 (1 loop)
Dial Setting / Amps
45
22.5
11
50
25
12.5
45
22.5
50
25
9
160
128
112
10
−
143
125
Size 420
# Passes
Pa
th
through
h th
the window
i d
A-4 Appendix
80
40
20
10
333
250
200
70
35
80
40
Dial Setting / Amps
4
5
133
167
100
125
80
100
67
83
11
−
157
137
3
300
150
100
75
1 (Straight Through)
2 (1 loop)
3 (2 loop)
4 (3 loop)
9
300
225
180
60
30
3
100
75
60
50
3 (2 loops)
4 (3 loops)
5 (4 loops)
6 (5 loops)
# Passes
3 (2 loops)
4 (3 loops)
5 (4 loops)
70
35
17.5
90
45
22.5
Dial Setting / Amps
Size 160
# Passes
Pa
th
through
h th
the window
i d
# Passes
6 (5 loops)
7 (6 loops)
8 (7 loops)
60
30
15
Size 250
# Passes
Pa
th
through
h the
th window
i d
12
−
−
150
14
−
−
−
16
−
−
−
Dial Setting / Amps
4
5
400
500
200
250
133
167
100
125
11
366
275
220
12
400
300
240
14
−
350
280
16
−
400
320
90
45
6
−
150
120
100
18
−
−
−
3
150
100
75
60
2 (1 loop)
3 (2 loop)
4 (3 loop)
5 (4 loop)
# Passes
5 (4 loops)
6 (5 loops)
7 (6 loops)
9
180
166
126
10
200
185
140
Size 840
# Pa
Passes th
through
h th
the window
i d
# Passes
3 (2 loops)
4 (3 loops)
5 (4 loops)
9
600
450
360
11
220
203
154
3
600
300
150
1 (Straight Through)
2 (1 loop)
3 (2 loop)
10
667
500
400
Dial Setting / Amps
4
5
200
250
133
167
100
125
80
100
12
240
216
168
14
−
−
196
16
−
−
224
Dial Setting / Amps
4
5
800
1000
400
500
200
250
11
734
550
440
12
800
600
480
14
−
700
560
16
−
800
640
6
−
200
150
120
18
−
−
254
6
−
600
300
18
−
−
720
6
−
300
200
150
18
−
−
360
1 Pass (Straight Through)
2 Pass (1 Loop)
MN894
Appendix B
Circuit Breaker Adjustments
Circuit Breaker Adjustment (Inrush current estimation)
Mechanical adjustment of the trip setting may be necessary if the circuit breaker is
replaced. The first step of this adjustment procedure is to determine the motor inrush
current (in amperes). Inrush current is also called “Locked Rotor AMPS” or “LRA”.
In soft start applications, the initial voltage applied to the motor is reduced to
approximately 40% to 70% of nominal line voltage. It is necessary to set set the trip
current for the circuit breaker to the proper inrush current value. This inrush current is
determined by motor horsepower and motor design characteristics. To define inrush
characteristics, code letters are used. This code letter defines both the low voltage and
high voltage inrush values for dual voltage motors. Table B-1 shows these code letters.
(KVA = Kilovolt-Amperes; HP = Horsepower).
KVA/HP Calculation of motor
Table B-1 Code Letter Definition
Code Letter
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
KVA/HP
Range
KVA/HP
Mid-Range Value
0.00 - 3.14
3.15 - 3.54
3.55 - 3.99
4.00 - 4.49
4.50 - 4.99
5.00 - 5.59
5.60 - 6.29
6.30 - 7.09
7.10 - 7.99
8.00 - 8.99
9.00 - 9.99
10.00 - 11.19
11.20 - 12.49
12.50 - 13.99
14.00 - 15.99
1.6
3.3
3.8
4.3
4.7
5.3
5.9
6.7
7.5
8.5
9.5
10.6
11.8
13.2
15.0
3 Phase Inrush Current Calculation (Use mid range value for KVA/HP)
Inrush AMPS +
MN894
ǒ
HP
KVA
mid range value
Ǔ x HP x 577
Rated Volts
Adjustments B-1
Section 1
General Information
Example: 3 phase Motor rated at 50 HP at 460VAC, 65 amps (continuous), code letter J.
I Inrush +
50 x 577Ǔ
ǒ7.5 x 460
+ 470Amperes
Circuit Breaker Adjustment The calculated Inrush Amps value is used to initially set the breaker. If the circuit breaker
trips during use, the trip level is increased. Refer to Figure B-1.
Caution:
The trip level of the circuit breaker must remain as low as possible
to avoid damage to equipment. If set too high, the circuit breaker
may not trip during a high overcurrent condition.
1.
Refer to the manufacturers literature or the rating label on the circuit breaker.
Determine the correct setting of the Trip Level adjustment based on the
calculated Inrush Amps. Set the Trip Level adjustment to this initial level.
2.
Turn on power and start the motor.
3.
If the breaker trips and the shunt trip indicator on the LCM soft start control
module is OFF, the circuit breaker tripped for an overcurrent condition. Turn
power off and set the Trip Level to the next greater setting.
4.
Turn on power and start the motor.
5.
If the breaker trips, repeat steps 3 and 4. If the Trip Level adjustment is at the
maximum setting and you have verified there is no phase to phase or phase to
ground shorts, perform step 6. If the shunt trip causes the breaker to trip, refer
to Troubleshooting Section 5 of this manual.
6.
If the breaker continues to trip due to inrush current (and not a short circuit) the
Rating Plug may be replaced with one that has a greater current rating. Refer
to the circuit breaker manufacturers information and ratings.
Figure B-1 Magnetic Circuit Breaker
ON
Tripped
OFF
Reset
Handle
Shunt Trip Device
Manual Trip
Shunt Trip Wires to
LCM soft start module
B-2 Adjustments
Trip Level
Rating Plug
MN894
Baldor District Offices
BALDOR ELECTRIC COMPANY
P.O. Box 2400
Ft. Smith, AR 72901−2400
(479) 646−4711
Fax (479) 648−5792
© Baldor Electric Company
MN894
Printed in USA
9/06

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement