advertisement
Prodigy Series Modular Cuber
Technical Service Manual
Models C0322, C0522, C0722, C0330, C0530,
C0630, C0830, C1030, C1448, C1848 and
C2148 also includes CB0522, CB0330, CB0530,
CB0630, CB0830 and CB1030
Introduction
This technical manual covers the Prodigy line, excluding the Eclipse remote low side models.
All are shipped with an Installation and User's manual, which can be referred to separately.
General installation information is included in this manual.
Model Number Description . . . . . . . . . page 2
Water . . . . . . . . . . . . . . . . . . . . page 3
General Installation - Air or Water Cooled . page 4
Water purge setting . . . . . . . . . . . . page 8
General Installation - Remote . . . . . . . page 9
Pre-Charged Tubing Coupling Connections page 17
General Installation - Remote . . . . . . . page 18
Adjustments . . . . . . . . . . . . . . . . page 20
Prodigy Cuber System Information. . . . . page 21
Controller Information . . . . . . . . . . . page 22
How It Works - Air Cooled . . . . . . . . . page 24
How It Works - Water Cooled . . . . . . . page 25
How It Works - Remote. . . . . . . . . . . page 26
Electrical Sequence - Air or Water Cooled . page 27
Electrical Sequence - Remote Cooled . . . page 29
Remote Schematics . . . . . . . . . . . . page 31
Electrical Component Details . . . . . . . page 32
Refrigeration . . . . . . . . . . . . . . . . page 35
Water System . . . . . . . . . . . . . . . page 36
Control Operation . . . . . . . . . . . . . page 37
Control Safeties . . . . . . . . . . . . . . page 38
Restarts. . . . . . . . . . . . . . . . . . . page 39
Control Button Use (from standby) . . . . . page 40
Control Button Use - continued . . . . . . page 41
Diagnostics – Air Cooled . . . . . . . . . . page 42
Low Ice Making Capacity - Air Cooled . . . page 45
Makes Excessive Noise - Air Cooled. . . . page 46
Table of Contents
Diagnostics - Water Cooled . . . . . . . . page 47
Low ice Making Capacity - Water Cooled . page 50
Makes Excessive Noise - Water Cooled . . page 51
Diagnostics - Remote Air Cooled . . . . . page 52
Low Ice Making Capacity - Remote . . . . page 55
Makes Excessive Noise - Remote . . . . . page 56
Test Procedures - Sensors . . . . . . . . . page 57
Ice Thickness Sensor . . . . . . . . . . . page 58
Water Level Sensor . . . . . . . . . . . . page 59
Temperature Sensors . . . . . . . . . . . page 60
Test Procedures - Loads . . . . . . . . . . page 61
Compressor Electrical Chart . . . . . . . . page 62
Refrigerant Charges . . . . . . . . . . . . page 63
Test Procedures - Loads . . . . . . . . . . page 64
Technical Information . . . . . . . . . . . page 72
Heat Load & Condenser Water GPM . . . page 73
Controller Differences . . . . . . . . . . . page 74
Thermistor Values . . . . . . . . . . . . . page 75
Performance Data . . . . . . . . . . . . . page 76
Performance Data - Remotes . . . . . . . page 87
Wiring Diagrams . . . . . . . . . . . . . . page 95
Wiring Diagram . . . . . . . . . . . . . . . page 103
Repair Procedures . . . . . . . . . . . . . page 108
Refrigeration Removal and Replacement Procedures
. . . . . . . . . . . . . . . . . . . . . . . page 116
Optional add-on control information . . . . page 121
Selected Prodigy Cuber Suction Graphs. . page 126
Wiring Diagram - 50 Hz . . . . . . . . . . page 129
May 2011 Page 1
Model Number Description
Example:
• C0530SA-1C
• C= cuber. CB = Prodigy Advanced Sustainability Cuber
• 05= nominal ice capacity in 100s of pounds
• 30= nominal width of cabinet. Other sizes are 22 and 48.
• S= Cube size. S=small or half dice cube. M=medium or full dice cube
• A=Condenser type. A=air cooled. W=water cooled. R = Remote
• -1=Electrical code. -1=115 volts. -32=208-230 single phase. -3=208-230 three phase.
-6=230 50 Hz
• C=Series revision code. C=third series
Note: In some areas of this manual model numbers may include only the first five characters of the model number, meaning that the cube size, condenser type and voltage differences are not critical to the information listed there.
Scotsman reserves the right to make design changes and/or improvements at any time.
Specifications and design are subject to change without notice.
September 2011 Page 2
Water
The quality of the water supplied to the ice machine will have an impact on the time between cleanings and ultimately on the life of the product. There are two ways water can contain impurities: in suspension or in solution. Suspended solids can be filtered out. In solution or dissolved solids cannot be filtered, they must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters have treatment in them for suspended solids. Check with a water treatment service for a recommendation.
RO water. This machine can be supplied with Reverse Osmosis water, but the water conductivity must be no less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast or similar material can result in the need for more frequent sanitation cleanings due to the tendency of these materials to contaminate the machine. Most water filters remove chlorine from the water supply to the machine which contributes to this situation. Testing has shown that using a filter that does not remove chlorine, such as the Scotsman Aqua Patrol, will greatly improve this situation, while the ice making process itself will remove the chlorine from the ice, resulting in no taste or odor impact.
Additionally, devices intended to enhance ice machine sanitation, such as the Scotsman Aqua
Bullet, can be placed in the machine to keep it cleaner between manual cleanings.
Water Purge
Cube ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to be drained out every cycle to reduce the amount of hard water scale in the machine. That’s known as water purge, and an effective purge can increase the time between needed water system cleaning.
In addition, this product has the capability to automatically vary the amount of water purgeed based on the purity of the water supplied to it. The water purge rate can also be set manually.
Adjustments of purge due to local water conditions are not covered by warranty.
October 2012 Page 3
General Installation - Air or Water Cooled
Location Limitations:
The product is designed to be installed indoors, in a controlled environment. Air cooled models discharge very warm air into the room out the back. Space must be allowed at the left side and back for air intake and discharge. Water cooled models discharge warm water into the building’s drain. Space needs to be provided on both sides and above for service access.
Space Limitations
Note: Although the machine will function, ice capacity of air cooled machines will be significantly reduced with minimal clearance at the sides, back and top. Some space is recommended for service and maintenance purposes on all models.
6" of space at the sides and back are required for adequate operation. To get the most capacity, locate the machine away from heat producing appliances and heating ducts.
22 and 30 inch wide models: Airflow is in the left side, out the back (as viewed from the front).
48 inch wide models: Air flow is in the front and left side and out the back.
Environmental Limitations
Air temperature
Water temperature
Water pressure
Minimum
50 o
F.
40 o
F.
20 psi
Maximum
100 o
F.
100 o
F.
80 psi
Power supply – acceptable voltage ranges
115 volt model
208-230 volt model
Minimum
104 volts
198 volts
Maximum
126 volts
253 volts
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material or workmanship. It does not cover maintenance, corrections to installations, or situations when the machine is operated in circumstances that exceed the limitations printed above.
October 2012 Page 4
General Installation - Air or Water Cooled
Plumbing Requirements
All models require connection to cold, potable water. A hand actuated valve within site of the machine is required. Air cooled models have a single 3/8” FPT inlet water connection.
Water cooled models have the same inlet fitting plus an additional 3/8” FPT condenser inlet water connection.
Water Filters
If connecting to water filtration, filter only the water to the reservoir, not to the condenser.
Install a new cartridge if the filters were used with a prior machine.
All models require drain tubing to be attached to them. Air cooled models have a single ¾”
FPT drain fitting in the back of the cabinet. Water cooled models have the same fitting plus an additional ½” FPT drain fitting in the back of the cabinet.
Install new tubing when replacing a prior ice machine, as the tubing will have been sized for the old model and might not be correct for this one.
Note: This NSF listed model has a 1" anti-back flow air gap between the water inlet tube end and the highest possible reservoir water level, no back flow device is required for the potable water inlet.
Drain Tubing:
Use rigid drain tubes and route them separately – do not Tee into the bin’s drain and, if water cooled, do not Tee the condenser drain into the reservoir or bin drain.
Vent the reservoir drain. A vertical vent at the back of the drain, extended about 8 – 10” will allow the gravity drain to empty and also keep any surges during draining from discharging water out the vent..
Horizontal runs of drain tubing need a ¼” fall per foot of run for proper draining.
Follow all applicable codes.
August 2013 Page 5
General Installation - Air or Water Cooled
Electrical
See the spec sheet or User's Manual for Minimum Circuit Ampacity or Maximum Fuse Size ratings.
The machine is not supplied with a power cord, one must either be field installed or the machine hard-wired.
The dataplate on the back of the cabinet details the power requirements, including voltage, phase, minimum circuit ampacity and maximum fuse size. HACR type circuit breakers may be used in place of fuses. Extension cords are not permitted. Use of a licensed electrician is recommended.
Electrical connections are made inside the junction box in the back panel of the ice machine.
Follow all applicable local, state and national codes.
October 2012 Page 6
General Installation - Air or Water Cooled
Adjustments
Note: Indentations may be deeper on C0322 and C0330
1/8" indentation
Ice Bridge Thickness
Caution: Do not make the bridge too thin or the machine will not harvest properly. Bridge thickness adjustments are not covered by warranty.
1/8-3/16" bridge
Shut machine off.
Access the ice thickness sensor.
Check gap between metal tip and evaporator grid. Small cube standard gap is 3/16 inch, medium cube standard gap is 7/32 inch. To set, place a 3/16" (small cube) or 7/32"
(medium cube) drill bit between sensor tip and evaporator to check. Adjust gap using adjustment screw.
Restart unit and check ice bridge. Repeat as needed.
Too Big Just Right
Too Small
Ice Bridge Thickness Measurement
Adjustment
Screw
Gap
Ice Thickness Sensor Adjustment
Evaporator
Ice Thickness Sensor
Gap
Side View of Evaporator and Ice Thickness
Sensor
October 2012 Page 7
Water purge setting
The water purge is factory set to the Automatic setting. The setting can be changed to one of 5 manual settings or placed on automatic. The purge setting shows in the Code Display.
purge setting
Water
Type
1 -
Minimum
2 -
Moderate
RO water or equivalent,
TDS less than 35
Low TDS non - RO water
3 -
Standard
Setting for typical water
4 -
Heavy
High
TDS water
5 -
Maximum
Very high
TDS water, greater than
256
A - Automatic
Any with conductivity not less than
10 microSiemens/ cm
To set:
Switch the machine OFF by holding the Off button in until a number or the letter A shows on the display.
Press and release the On button repeatedly until the number on the display corresponds to the desired setting.
Press and release the Off switch again to return to the normal control state.
October 2012 Page 8
General Installation - Remote
Location Limitations
This ice system is made up of three parts, the ice making machine, or head; the remote condenser; and the interconnecting tubing. The ice making machine must be installed indoors, in a controlled environment. Space must be provided near the machine for service access. The remote condenser may be installed above or below the ice machine, per the limits stated later in this manual. The remote condenser may be installed outdoors within the temperature limits listed below. The interconnecting tubing must be installed per the directions stated in this manual, and the amount of tubing exposed to uncontrolled temperatures must be minimized.
Space Limitations
Although the machine will function with no clearance to the top and sides, some space must be allowed for service access. Building the machine in with no access will cause higher service cost, in many cases this extra cost may not be covered by warranty.
Environmental Limitations, ice machine:
Air temperature
Water temperature
Water Pressure
Minimum
50 o
F.
40 o
F.
20 psi
Maximum
100 o
F.
100 o
F.
80 psi
Environmental Limitations, remote condenser
Air temperature
Minimum
-20 o
F.
Maximum
120 o
F.
Power Supply
115 volt model
208-230 volt model
Minimum
104 volts
198 volts
Maximum
126 volts
253 volts
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material and workmanship. It does not cover maintenance, corrections to installations, or situations when the ice machine is operated in circumstances that exceed the limitations printed above.
October 2012 Page 9
General Installation - Remote
Product Description and Electrical Requirements
- See spec sheet or User's Manual for Minimum Circuit Ampacity or Maximum Fuse SIze
Dimensions w” x d” x h”
22 x 24 x 23 same
30 x 24 x 23 same same
30 x 24 x 29 same same same
48 x 24 x 29 same same same same same
Model
C0522SR-1 same
C0530SR-1 same
C0630SR-32
C0830SR-32
C0830SR-3
C1030SR-32
C1030SR-3
C1448SR-32
C1448SR-3
C1848SR-32
C1848SR-3
C2148SR-32
C2148SR-3
Electrical
115/60/1 same
115/60/1 same
208-230/60/1
208-230/60/1
208-230/60/3
208-230/60/1
208-230/60/3
208-230/60/1
208-230/60/3
208-230/60/1
208-230/60/3
208-230/60/1
208-230/60/3
Use condenser
ERC111-1
ERC211-1**
ERC111-1
ERC211-1**
ERC311-32
ERC311-32
ERC311-32
ERC311-32
ERC311-32
ERC311-32
ERC311-32
ERC611-32
ERC611-32
ERC611-32
ERC611-32
** ERC211 has two circuits, when two C0522s or C0530s are connected to it, fan motor relay kit KCMR120 must be used to control the fan motor.
Ratings include the remote condenser motor, as it is designed to be powered by the ice machine. If connecting remote condenser independently of the ice machine, use the information on the condenser's dataplate for fuse and wire sizes.
Table notes: Medium cube models have the same electrical characteristics as Small. Series revision code omitted. All the listed condensers include a headmaster valve.
October 2012 Page 10
General Installation - Remote
Central Condenser Coils
The ice machine may be connected to a central condenser coil. The requirements are:
• Coil – not previously used with mineral oil system. Virgin coil preferred.
• Correct size (internal volume) and capacity (BTUH).
• Includes a headmaster valve for discharge pressure control. Headmaster kit available for certain MAC condensers, kit number is
RCKCME6GX
.
• Fan motor on all the time or controlled to be on whenever the ice machine is operating.
• Non-Scotsman condensers must have prior Scotsman Engineering approval for warranty coverage to be in effect.
Precharged tubing kits:
The ice making head’s and the remote condenser’s refrigeration circuits must be connected.
They are designed to be connected using precharged refrigerant tubing, supplied in kits of liquid and discharge tubes. Several lengths are available, order the one that just exceeds the length needed for the site.
10”
RTE10
25’
RTE25
40’
RTE40
75’
RTE75
No additional refrigerant is required. Note: Refrigerant charge is supplied with the ice machine.
January 2009 Page 11
General Installation - Remote
Water
The quality of the water supplied to the ice machine will have an impact on the time between cleanings and ultimately on the life of the product. There are two ways water can contain impurities: in suspension or in solution. Suspended solids can be filtered out. In solution or dissolved solids cannot be filtered, they must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters have treatment in them for suspended solids. Check with a water treatment service for a recommendation.
RO water. This machine can be supplied with Reverse Osmosis water, but the water conductivity must be no less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast or similar material can result in the need for more frequent sanitation cleanings due to the tendency of these materials to contaminate the machine. Most water filters remove chlorine from the water supply to the machine which contributes to this situation. Testing has shown that using a filter that does not remove chlorine, such as the Scotsman Aqua Patrol, will greatly improve this situation, while the ice making process itself will remove the chlorine from the ice, resulting in no taste or odor impact.
Additionally, devices intended to enhance ice machine sanitation, such as the Scotsman Aqua
Bullet, can be placed in the machine to keep it cleaner between manual cleanings.
Water purge
Cube ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to be drained out every cycle to reduce the amount of hard water scale in the machine. That’s known as water purge, and an effective purge can increase the time between needed water system cleaning.
In addition, this product is designed to automatically vary the amount of water purged based on the purity of the water supplied to it. The water purge rate can also be set manually.
Adjustments of purge due to local water conditions are not covered by warranty.
October 2012 Page 12
General Installation - Remote
Remote Condenser Location
Use the following for planning the placement of the condenser relative to the ice machine - see illustration on the following page.
Location Limits - condenser location must not exceed ANY of the following limits:
• Maximum rise from the ice machine to the condenser is 35 physical feet
• Maximum drop from the ice machine to the condenser is 15 physical feet
• Physical line set maximum length is 100 feet.
• Calculated line set length maximum is 150.
Calculation Formula:
• Drop = dd x 6.6 (dd = distance in feet)
• Rise = rd x 1.7 (rd = distance in feet)
• Horizontal Run = hd x 1 (hd = distance in feet)
• Calculation: Drop(s) + Rise(s) + Horizontal Run = dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.
Do NOT:
• Route a line set that rises, then falls, then rises.
• Route a line set that falls, then rises, then falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally. 35 x 1.7 =
59.5. 59.5 +100 = 159.5. 159.5 is greater than the 150 maximum and is NOT acceptable.
Operating a machine with an unacceptable configuration is misuse and will void the warranty.
October 2012 Page 13
General Installation - Remote
For The Installer: Remote Condenser
Locate the condenser as near as possible to the interior location of the ice machine.
Note: The location of the condenser is relative to the ice machine is LIMITED by the specification on the prior page.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
rd
Max
35'
Remote
Condenser
Locate ABOVE dd
Max
15'
Remote
Condenser
Locate BELOW
October 2012 Page 14
Condenser
Distance &
Location
General Installation - Remote
Precharged Line Routing
Do not connect the precharged tubing until all routing and forming of the tubing is complete.
See the Coupling Instructions for final connections.
1. Each set of pre-charged tubing lines contains a 3/8” diameter liquid line, and a 1/2” diameter discharge line. Both ends of each line have quick connect couplings, the end without access valves goes to the ice maker.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 1 3/4”. Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible. Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.
If the excess tubing is cut out, after re-brazing the tubing must be evacuated prior to connection to the ice maker or condenser.
Note brazing requires a nitrogen purge.
If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.
5. Have the roofing contractor seal the holes in the roof per local codes
October 2012 Page 15
General Installation - Remote
Coupling Instructions
The couplings on the ends of the pre-charged line sets are self-sealing when installed properly.
Follow these instructions carefully.
These steps must be performed by an EPA Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to remove any possible foreign matter.
2. Lubricate the inside of the couplings, especially the O-rings, with refrigerant oil.
3. Position the fittings on the correct connections on the condenser and ice machine.
• The 1/2" discharge line (schrader valve end) goes to the remote condenser fitting marked
“discharge line”.
• The 3/8" liquid line (schrader valve end) goes to the remote condenser fitting marked
“liquid line”.
• The 1/2" discharge line goes to the ice maker fitting marked “discharge line”.
• The 3/8" liquid line goes to the ice maker fitting marked “liquid line”.
Final Connections:
4a. Begin by tightening the couplings together by hand until it is certain that the threads are properly engaged.
4b. Then using two wrenches tighten the coupling until it bottoms out or a definite increase in resistance is felt.
It is important that ONLY the nut on the pre-charged tube be turned, or the diaphragms will be torn out by the piercing knives and they will be loose in the refrigeration system. Note: As the couplings are tightened, the diaphragms in the quick connect couplings will begin to be pierced. As that happens, there will be some resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it bottoms out or a very definite increase in resistance is felt (no threads should be showing).
5. Use a marker or pen to mark a line on the coupling nut and unit panel. Then tighten the coupling nut an additional one-quarter turn. The line will show the amount that the nut turns.
Do NOT over tighten.
6. After all connections have been made, and after the receiver valve has been opened (open at Initial Start Up), check the couplings for leaks.
October 2012 Page 16
Pre-Charged Tubing Coupling Connections
Inspect couplings, wipe clean and lubricate both parts with polyolester refrigerant oil.
Hand tighten to be sure threads are properly engaged.
Use two wrenches and continue tightening the couplings. As the diaphragms being to pierce, the couplings will be harder to turn. Be sure only the swivel nut is rotated.
Continue tightening until the swivel nut feels like it is tight, then go to the next step. No threads will be seen when the couplings are tight.
After the swivel nut feels like it is tight, mark the nut and the panel. Then tighten one quarter turn more. That ensures that there is a brass-to-brass joint inside the coupling.
October 2012 Page 17
General Installation - Remote
Plumbing Requirements
All models require connection to cold, potable water. A hand actuated valve within site of the machine is required.
Water Filters
Install a new cartridge if the filters were used with a prior machine.
All models require drain tubing to be attached to them. There is a single ¾” FPT drain fitting in the back of the cabinet.
Install new tubing when replacing a prior ice machine, as the tubing will have been sized for the old model and might not be correct for this one.
Connect water supply to water inlet fitting.
Note: This NSF listed model has a 1" anti-back flow air gap between the potable water inlet tube end and the highest possible reservoir water level, no back flow device is required.
Connect drain tubing to drain fitting.
Route the drain tubing to building drain. Follow local codes for drain air gap.
Use rigid drain tubes and route them separately – do not Tee into the bin’s drain.
Vent the reservoir drain. A vertical vent at the back of the drain, extended about 8 – 10” will allow the gravity drain to empty and also keep any surges during draining from discharging water.
Horizontal runs of drain tubing need a ¼” per fall per foot of run for proper draining.
Follow all applicable codes.
August 2013 Page 18
General Installation - Remote
Electrical
The machine is not supplied with a power cord, one must either be field installed or the machine hard-wired.
The dataplate on the back of the cabinet details the power requirements, including voltage, phase, minimum circuit ampacity and maximum fuse size. HACR type circuit breakers may be used in place of fuses. Extension cords are not permitted. Use of a licensed electrician is recommended.
The ice maker is designed to operate on its own electrical circuit and must be individually fused. Voltage variation must not exceed the limits listed earlier.
The remote condenser is designed to be powered from the ice machine. A separate knockout hole has been provided in the ice maker electrical junction box.
Electrical connections are made inside the junction box in the back panel of the ice machine.
Remove the junction box cover and route the power cord through the access hole and properly attach the power supply wires to the leads in the junction box.
Attach the remote condenser fan motor wires to the wires in the junction box tagged “fan motor leads”.
Install field supplied strain reliefs per code. Attach a ground wire to the ground connection in the junction box.
Check voltage when complete.
Return the junction box cover to its original position and secure with the original screws.
Follow all applicable local, state and national codes.
October 2012 Page 19
Adjustments
Bridge Thickness - For the Service Tech
Only
Push and hold Off till the machine stops.
Access ice thickness sensor.
Adjustment
Screw
Check gap between metal tip and evaporator grid. Small cube standard gap is 3/16 inch, medium cube standard gap is 7/32 inch. To set, place a 3/16" (small cube) or 7/32"
(medium cube) drill bit between sensor tip and evaporator to check. Adjust gap using adjustment screw.
Gap
Restart unit and check ice bridge. Repeat as needed
Caution: Do not make the bridge too thin or the machine will not harvest properly. Bridge thickness adjustments are not covered by warranty.
Water purge setting
The water purge is factory set to Automatic. The setting can be changed to one of 5 manual settings or left on automatic.
purge setting
Water
Type
1 -
Minimum
RO water or equivalent,
TDS less than 35
2 -
Moderate
Low TDS non - RO water
3 -
Standard
Setting for typical water
4 -
Heavy
High
TDS water
5 -
Maximum
Very hHigh
TDS water, greater than 256
A - Automatic
Any with conductivity not less than 10 microSiemens/ cm
To set:
Switch the machine OFF by holding the Off button in until a number or the letter A shows on the display.
Press and release the On button repeatedly until the number on the display corresponds to the desired setting.
Press and release the Off switch again to return to the normal control state.
October 2012 Page 20
Prodigy Cuber System Information
Overall System Type:
• Refrigeration: Mechanical, either air cooled, water cooled or remote cooled.
• Water System: Inlet water solenoid valve fills reservoir once per cycle. Purge solenoid valve opens to discharge some reservoir water once per cycle.
• Control System: Electronic
• Harvest cycle sensor: Conductivity probe
• Water full/empty sensor: Conductivity probe
• Bin Control: Curtain Switch
• Ice type: Unified
• Harvest system: Hot gas defrost with mechanical assist
Electrical Components:
• Compressor
• Contactor
• Water Pump
• Inlet Water Solenoid Valve
• Purge or purge Valve
• Fan Motor(s)
• Fan motor pressure control
• High pressure cut out – certain AC models only
• Harvest Assist Solenoid(s)
• Hot Gas Valve(s)
• Controller
• Transformer – 12v AC for the controller only
• Water Level Sensor
• Ice Thickness Sensor
• Curtain Switch(es)
October 2012 Page 21
Controller Information
Machine Indicator Lights
• Power
• Status
• Water
• Clean
Code Display
Main codes - automatically displayed
F . . . . . . . Freeze Cycle
F flashes . . Freeze Cycle is Pending
H . . . . . . . Harvest Cycle
H flashes . . Manual Harvest
b . . . . . . . Bin is Full
C . . . . . . . Clean Cycle
L . . . . . . . Board Locked
d . . . . . . . Test Mode
O . . . . . . . Off
E . . . . . . . Self Test Failed
1
flashes . . Max Freeze - Retrying
1 . . . . . . . Max Freeze Time Shut Down
2 flashes . . Max Harvest - Retrying
2 . . . . . . . Max Harvest Time Shut Down
3 . . . . . . . Slow Water Fill
4 . . . . . . . High Discharge Temp
5 . . . . . . . Sump Temp Sensor Failure
7 . . . . . . . Discharge Temp Sensor Failure
8
flashes . . Short Freeze - Retrying
8 . . . . . . . Short Freeze - Thin ice
Setting Codes - requires push button sequence
Water Purge Settings
A, 1, 2, 3, 4, 5
De-Scale notification
- see table to the right
Change De-Scale Notification Interval -
This feature is accessible only from standby (Status Light Off).
1. Press and hold harvest button for 3 seconds.
This starts the Time to Clean
Adjustment Mode and displays the current time to clean setting.
2. Press the clean button repeatedly to cycle through the 4 settings:
Prior
3 months
4 months
5 months
Effective 11/6/08
1 year
0 or disabled
4 months
6 months (default) 6 months (default)
3. Push Off to confirm the selection.
November 2008 Page 22
Controller Information
Component Indicator Lights
• Condenser Fan / Aux (Aux = liquid line solenoid when a remote condenser model)
• Water Pump
• Purge Valve
• Water Solenoid
• Hot Gas
• Compressor
• Ready to Harvest
• Sump Empty
• Sump Full
• Curtain SW1
• Curtain SW2
Component Indicator Lights
October 2012 Page 23
How It Works - Air Cooled
Freeze Cycle. At start up the controller drains and refills the reservoir. The reservoir refills when the mid length water level sensor probe is uncovered and continues to fill until the top probe is in contact with water. When the reservoir has filled, the compressor and water pump start. After the discharge pressure has increased past the cut in point of the fan pressure control, the fan motor(s) will begin to operate and warm air will be discharged out the back of the cabinet. The fan motor will switch on and off as the discharge pressure rises and falls.
Water flows over the evaporator as the refrigeration system begins to remove heat. When the water temperature falls to a preset point, as measured by the water temperature sensor, the controller shuts off the water pump for 30 seconds. The freeze cycle resumes when the pump restarts and ice begins to form on the evaporator. As it forms, the water flowing over the ice moves closer and closer to the metal tip of the ice thickness sensor. When it comes into contact with the sensor for a few continuous seconds, that signals the controller that the freeze cycle is complete.
The controller may shut the air cooled fan motor off for a variable period of time to build up heat for harvest. This is dependant upon the temperature of the discharge line sensor.
Harvest Cycle. When the harvest cycle begins, the controller shuts off the fan motor, switches on the hot gas valve, and through a parallel circuit, the harvest assist solenoid. After a few seconds the purge valve opens and water is drained from the reservoir. Based on either the automatic purge or manual purge setting, the pump and purge valve will be switched off at a time determined to have drained enough water for that setting. The inlet water valve will open to fill the reservoir anytime the mid length probe is uncovered, which occurs during the reservoir drain cycle. Harvest continues as the hot discharge gas flows into the evaporator serpentine, heating up the evaporator. At the same time the harvest assist solenoid is pushing against the back of the ice slab. When the ice releases from the evaporator, it harvests as a unit, and the harvest assist probe provides some additional force to push it off. When the ice falls off it will force the curtain(s) open. An open curtain during the harvest cycle signals the controller that the evaporator has released its ice. If this is a single evaporator machine the controller will terminate harvest. If it is a two evaporator machine, the controller will continue harvest until both curtains have opened. If one curtain remains open, the controller will shut the machine down on bin full. Anytime harvest is complete the hot gas valve and harvest assist solenoid are shut off. The harvest assist solenoid pin returns to its normal position by spring pressure.
If the curtain(s) re-close after harvest, the freeze cycle will restart.
October 2012 Page 24
How It Works - Water Cooled
Freeze Cycle. At start up the controller drains and refills the reservoir. The reservoir refills when the mid length water level sensor probe is uncovered and continues to fill until the top probe is in contact with water. When the reservoir has filled, the compressor and water pump start. After the discharge pressure has increased past the set point of the water regulating valve, the water regulating valve will open and warm water will be discharged out the condenser drain. The water regulating valve will modulate to maintain a relatively constant discharge pressure. Water flows over the evaporator as the refrigeration system begins to remove heat. When the water temperature falls to a preset point, as measured by the water temperature sensor, the controller shuts off the water pump for 30 seconds. The freeze cycle resumes when the pump restarts and ice begins to form on the evaporator. As it forms, the water flowing over the ice moves closer and closer to the metal tip of the ice thickness sensor.
When it comes into contact with the sensor for a few continuous seconds, that signals the controller that the freeze cycle is complete.
Harvest Cycle. When the harvest cycle begins, the controller switches on the hot gas valve, and through a parallel circuit, the harvest assist solenoid. After a few seconds the purge valve opens and water is drained from the reservoir. Based on either the automatic purge or manual purge setting, the pump and purge valve will be switched off at a time determined to have drained enough water for that setting. The inlet water valve will open to fill the reservoir anytime the mid length probe is uncovered, which occurs during the reservoir drain cycle.
Harvest continues as the hot discharge gas flows into the evaporator serpentine, heating up the evaporator. At the same time the harvest assist solenoid is pushing against the back of the ice slab. When the ice releases from the evaporator, it harvests as a unit, and the harvest assist probe provides some additional force to push it off. When the ice falls off it will force the curtain(s) open. An open curtain during the harvest cycle signals the controller that the evaporator has released its ice. If this is a single evaporator machine the controller will terminate harvest. If it is a two evaporator machine, the controller will continue harvest until both curtains have opened. If a curtain remains open, the controller will shut the machine down on bin full. Anytime harvest is complete the hot gas valve and harvest assist solenoid are shut off. The harvest assist solenoid pin returns to its normal position by spring pressure.
If the curtain(s) re-close after harvest, the freeze cycle will restart.
January 2010 Page 25
How It Works - Remote
Freeze Cycle. At start up the controller drains and refills the reservoir. The reservoir refills when the mid length water level sensor probe is uncovered and continues to fill until the top probe is in contact with water. When the reservoir has filled, the liquid line valve, compressor and water pump are switched on. After the discharge pressure has increased past the set point of the headmaster in the condenser, the headmaster will direct refrigerant gas into the condenser and warm air will be discharged out of the condenser. The headmaster will modulate to maintain a minimum discharge pressure. Water flows over the evaporator as the refrigeration system begins to remove heat. When the water temperature falls to a preset point, as measured by the water temperature sensor, the controller shuts off the water pump for 30 seconds. The freeze cycle resumes when the pump restarts and ice begins to form on the evaporator. As it forms, the water flowing over the ice moves closer and closer to the metal tip of the ice thickness sensor. When it comes into contact with the sensor for a few continuous seconds, that signals the controller that the freeze cycle is complete.
Harvest Cycle. When the harvest cycle begins, the controller switches on the hot gas valve, and through a parallel circuit, the harvest assist solenoid. After a few seconds the purge valve opens and water is drained from the reservoir. Based on either the automatic purge or manual purge setting, the pump and purge valve will be switched off at a time determined to have drained enough water for that setting. The inlet water valve will open to fill the reservoir anytime the mid length probe is uncovered, which occurs during the reservoir drain cycle.
Harvest continues as the hot discharge gas flows into the evaporator serpentine, heating up the evaporator. At the same time the harvest assist solenoid is pushing against the back of the ice slab. When the ice releases from the evaporator, it harvests as a unit, and the harvest assist probe provides some additional force to push it off. When the ice falls off it will force the curtain(s) open. An open curtain during the harvest cycle signals the controller that the evaporator has released its ice. If this is a single evaporator machine the controller will terminate harvest. If it is a two evaporator machine, the controller will continue harvest until both curtains have opened. If a curtain remains open, the controller will shut the machine down. Anytime harvest is complete the hot gas valve and harvest assist solenoid are shut off.
The harvest assist solenoid pin returns to its normal position by spring pressure.
If the curtain(s) re-close after harvest, the freeze cycle will restart.
Shut down occurs when a curtain remains open after a harvest cycle. The controller will switch off the liquid line solenoid valve and operate the compressor for 30 seconds, then shut it off.
November 2006 Page 26
Electrical Sequence - Air or Water Cooled
Power connected, unit previously switched Off.
Control board does a self check. If the self check fails, the unit displays an E and no further action will occur.
If the self check passes, the controller will display a 0, the curtain light(s) will be ON and the
Power and Sump Empty lights will be ON.
Pushing and releasing the On button will start the ice making process.
The display will begin to blink F. The component indicator lights will switch on and off to match the following process:
The purge valve opens and the water pump starts to empty the reservoir. This is done to discharge any excess water from ice melting into the reservoir.
The hot gas valve and the harvest assist solenoid are energized.
The inlet water valve will open to fill the reservoir. The water valve can open any time the water level is low.
After a few seconds the purge valve closes and the pump shuts off.
When the reservoir is full the inlet water valve stops and the compressor switches on. Five seconds after the compressor starts the hot gas valve and the harvest assist solenoid are de-energized.
Light Information: The display shows a non-blinking F. The Power and Status Lights will be Green. The compressor, fan motor, water pump, sump full and one or two curtain switch lights will be ON.
The air cooled model's fan motor will start to turn when the discharge pressure has built up to the fan pressure control's cut in point. This is about 15 seconds after the compressor starts.
The Freeze cycle continues. The compressor, water pump, fan motor and curtain indicator lights will be ON. When the reservoir water temperature falls to a certain preset point, the water pump will shut off for 30 seconds. This is the anti-slush period. At this time the controller checks the conductivity of the water in the reservoir for the auto-purge feature. After the water pump restarts the Sump Full light will go out and neither sump lights will be on for the rest of the freeze cycle.
When the ice has built up enough so that the water flowing over the evaporator comes into continuous contact with the ice level sensor, the Ready to Harvest light will begin to blink on and off. When it has been On continuously for 5 seconds, the controller will switch the machine into a Harvest cycle.
October 2012 Page 27
Electrical Sequence - Air or Water Cooled
Indicator Information: The display shows a non-blinking H. The Power and Status Lights will be Green.
The compressor, hot gas valve and one or two curtain switch lights will be ON. After a few seconds the water pump, purge valve and inlet water valve lights will come on.
The fan motor(s) shut off and remain off throughout the harvest cycle.
The harvest assist solenoid is connected in parallel with the hot gas valve. Although it is energized throughout the harvest cycle, its piston does not move until the ice has become partially loosened from the evaporator plate by the action of the hot refrigerant gas passing through the evaporator serpentine.
The water pump and purge valve will shut off when the purge level setting time has been reached, either the manual time or the automatic time. The inlet water valve will remain on until it fills the reservoir. The Ready to Harvest light will switch Off when the ice falls from the evaporator.
Harvest continues until the ice slab is ejected from the evaporator and falls, opening the curtain. When the curtain opens, the magnetic reed curtain switch opens, breaking the circuit to the controller. If the curtain re-closes within 30 seconds, the controller switches the machine back into another freeze cycle. If the curtain switch remains open, the controller shuts the machine down and puts it into a standby position.
October 2012 Page 28
Electrical Sequence - Remote Cooled
Power connected, unit previously switched Off.
Control board does a self check. If the self check fails, the unit displays an E and no further action will occur.
If the self check passes, the controller will display a 0, the curtain light(s) will be ON and the
Power and Sump Empty lights will be ON.
Pushing and releasing the On button will start the ice making process.
The display will begin to blink F. The component indicator lights will switch on and off to match the following process:
The purge valve opens and the water pump starts to empty the reservoir. This is done to discharge any excess water from ice melting into the reservoir.
The hot gas valve and the harvest assist solenoid are energized.
The inlet water valve will open to fill the reservoir. The water valve can open any time the water level is low.
After a few seconds the purge valve closes and the pump shuts off.
When the reservoir is full the inlet water valve stops, the liquid line valve is opened and the compressor switches on. Five seconds after the compressor starts the hot gas valve and the harvest assist solenoid are de-energized.
Light Information: The display shows a non-blinking F. The Power and Status Lights will be Green. The compressor, fan motor, water pump, sump full and one or two curtain switch lights will be ON.
The Freeze cycle continues. When the reservoir water temperature falls to a certain preset point, the water pump will shut off for 30 seconds. This is the anti-slush period. At this time the controller checks the conductivity of the water in the reservoir for the auto-purge feature. After the water pump restarts the Sump Full light will go out and neither sump lights will be on for the rest of the freeze cycle.
When the ice has built up enough so that the water flowing over the evaporator comes into continuous contact with the ice level sensor, the Ready to Harvest light will begin to blink on and off. When it has been On continuously for 3 seconds, the controller will switch the machine into a Harvest cycle.
Indicator Information: The display shows a non-blinking H. The Power and Status Lights will be Green.
The compressor, hot gas valve and one or two curtain switch lights will be ON. After a few seconds the water pump, purge valve and inlet water valve lights will come on.
October 2012 Page 29
Electrical Sequence - Remote Cooled
The harvest assist solenoid is connected in parallel with the hot gas valve. Although it is energized throughout the harvest cycle, its piston does not move until the ice has become partially loosened from the evaporator plate by the action of the hot refrigerant gas passing through the evaporator serpentine.
The remote condenser fan motor is powered by the compressor contactor, so it will be operating during the harvest cycle.
The water pump and purge valve will shut off when the purge level setting time has been reached, either the manual time or the automatic time. The inlet water valve will remain on until it fills the reservoir. The Ready to Harvest light will switch Off when the ice falls from the evaporator.
Harvest continues until the ice slab is ejected from the evaporator and falls, opening the curtain. When the curtain opens, the magnetic reed curtain switch opens, breaking the circuit to the controller. If the curtain re-closes within 30 seconds, the controller switches the machine back into another freeze cycle. If the curtain switch remains open, the controller shuts the machine down and puts it into a standby position.
October 2012 Page 30
Remote Schematics
Remote Condenser
Head
Pressure
Control
Valve
Discharge Line
Receiver
Hot Gas
Valve
TXV
Liquid Line Valve
Heat
Exchange
Suction
Compressor
C0522R, C0530R, C0630R and C1030R
Remote Condenser
Hot Gas
Valve
Head
Pressure
Control
Valve
TXV
Evaporator
Discharge Line
Receiver
Liquid Line Valve
Suction
Hot Gas
Valve
Evaporator
TXV
Compressor
Heat
Exchange
Suction
Accumulator
C1448R, C1848R and C2148R
October 2012 Page 31
Evaporator
Electrical Component Details
Compressor
• Operated by the compressor contactor. Single phase self contained models have PTCR and run capacitor.
Contactor
• Operated by the controller and the high pressure cut out switch. Line voltage coil. When energized the Compressor indicator light will be ON.
Water Pump
• Operated by the controller. When energized, the Water Pump indicator light will be ON.
Inlet Water Solenoid Valve
• Operated by the controller. Line voltage coil. When energized, the Water Solenoid indicator light will be ON.
Purge Valve
• Operated by the controller. Line voltage coil. When energized, the Purge Valve indicator light will be ON. Energized for a time during harvest.
Fan Motor(s)
• Operated by the controller and the fan pressure control. Can cycle on and off in the freeze cycle, always off during harvest. When the controller has energized it, the indicator light will be ON but the fan will not turn unless the discharge pressure is high enough to close the high pressure control.
• Fan(s) may shut off near the end of the freeze cycle to build up heat for harvest. Time of shut off depends upon available heat, as measured by the discharge temperature.
High pressure cut out
• Some air cooled and all remote and all water cooled models have a high pressure cut out switch that shuts the power off to the compressor contactor if the discharge pressure is too high. It is an automatic reset.
Harvest Assist Solenoid(s)
• Operated by the controller in parallel with the hot gas valve. Cycles on and off at the beginning of a restart. Energized throughout the harvest cycle. Line voltage coil.
October 2012 Page 32
Electrical Component Details
Liquid Line Valve
• Remote only. Opened by the controller to start a freeze cycle. Closed to shut unit off. Line voltage coil.
Hot Gas Valve(s)
• Operated by the controller in parallel with the harvest assist solenoid. Cycles on and off at the beginning of a restart. Energized throughout the harvest cycle. Line voltage coil.
Controller
• Senses ice thickness, water level, water temperature, discharge temperature. Controls compressor contactor, fan motor, water pump, inlet water valve, hot gas valve, purge valve, harvest assist solenoid. Indicates status and component operation. 12 volt.
Transformer
• 12 volt secondary, supplies power to controller only.
Water Level Sensor
• Three probe conductivity sensor. Bottom probe is common, mid probe is refill sump, top probe is full sump. Refill can occur at any time.
Ice Thickness Sensor
• Single wire conductivity sensor. Circuit made from controller to ground to controller when water contacts a probe suspended over ice plate. Signals ready for harvest.
Curtain Switch(es)
• Magnetic reed switch. Normally open, switch is closed when magnet is nearby. Models with two evaporators have two curtain switches. Single switch can be connected to either
J8 or J7 of controller. Curtains may be removed in the freeze cycle without affecting controller operation. A curtain removed during harvest will cause the controller to terminate harvest and shut the unit off. Two curtain models require both curtains to open to terminate harvest, and if either one remains open for 30 seconds that signals the controller to shut the unit off on bin full.
Water temperature sensor.
• Thermistor inserted into the water pump discharge hose. Reported temperature used by the controller to determine anti-slush cycle start time.
January 2010 Page 33
Electrical Component Details
Discharge temperature sensor.
• Thermistor attached to the discharge line near the compressor. Reported temperature used by the controller to determine end-of-cycle-fan-off-delay time. If discharge temperature exceeds a preset maximum, controller will shut the machine off.
Note: Controller will operate machine in a default mode with thermistors disconnected from the controller. Diagnostic code #5 or 7 will be displayed during that time.
Component Indicator Light Table
System
Condenser Fan or Liquid Line
Valve
Water Pump
Purge Valve
Inlet Water Solenoid Valve
Hot Gas
Compressor Contactor
Ready to Harvest
Sump Empty
Sump Full
Curtain Switch
Indicator Light ON
Fan Motor Powered or LLV open
Pump Motor Powered
Purge Valve Opens
Inlet Water Valve Opens
Hot Gas Valve Opens
Contactor Closes
Water contacting ice thickness sensor probe
Open between mid sensor and common
Closed between top probe and mid probe
Curtain open
Component Indicator Lights
October 2012 Page 34
Refrigeration
Refrigerant: R-404A
Compressors: Copeland or Tecumseh hermetic by model
Expansion valves: Non adjustable, internally equalized, one per evaporator.
Hot gas valves: Pilot operated, line voltage coils. One per plate.
Condensers: Forced draft air, counterflow water. All air cooled models have left side air inlet.
48” wide air cooled models also have front air inlet. All air cooled models exhaust air out the back.
Air filters: Surface mounted to panels. Filter media removable without removing panels.
Fan blades: Reduced vibration blades in most air cooled models.
Remote Systems: Head pressure control valves in condenser. No check valves. Headmaster protected by filters (not filter driers). Controller pumps unit down by closing the liquid line valve and keeping the compressor on for a fixed time period at shut down.
Fan pressure control. All AC. Controls fan motor operation in the freeze cycle.
High pressure cut out. WC, RC, AC with Tecumseh compressors.
Evaporator: Unified cell plate. Nickel plated copper. Three heights: 6”, 12” and 18”. Small cube = half dice, medium cube = full dice.
Small cube: 7/8" high x 7/8" deep x 3/8" high
Medium cube: 7/8" high x 7/8" deep x 7/8" high
October 2012 Page 35
Water System
Batch type. Insulated water reservoir contains full water charge for each ice making cycle.
Water valve: Solenoid type. Opens to fill reservoir when mid sensor probe no longer makes a circuit to the bottom probe. Closes when reservoir is full and top probe makes circuit to mid probe.
Pump: Unsealed pedestal type, twist-release mounting
Water purge valve: Solenoid type. Opens to purge water during harvest cycle.
Water Level Sensor: Three probe conductivity.
Distributor: ABS plastic. Evenly distributes water over the evaporator surface. Slides off the evaporator top. Removable cover for ease of cleaning.
Water Distributor Removal
October 2012 Page 36
Control Operation
Standard control:
• Electronic controller operating from a 12 AC volt power supply. Will operate within a voltage range between 10 and 15.5.
• User’s Indicator lights, four front visible: Power, Status, Water, De-scale/Sanitize.
• Accessible On switch.
• Accessible Off switch.
• Code Display: Displays letters and numbers to indicate cycles and diagnostic codes.
• Manual Harvest switch: Use to trigger harvest at any time.
• Clean switch: Use to initiate and finish the de-scale or sanitizing cycles.
• Component Operation Indicator Lights: Indicate the status of certain components; water level; ready for harvest; curtain switch position.
• Power Light: On when power is being supplied to the controller.
• Status Light: Green when machine is in ice making mode and is operating correctly. Blinks red when a machine malfunction has been detected.
• Water Light: Blinks red when reservoir does not fill with allowed time period.
• De-scale / sanitize: Yellow when the controller has determined it is time to de-scale and sanitize the machine. Use clean process to reset light. Time is determined by power up time and controller's setting. Standard setting is 6 months. See adjustment process
Controller Connections:
• J1 – Ground and Power Supply
• J2 – High voltage power harness to loads
• J3 – Factory use
• J4 – Optional board connector
• J5 - Communications port
• J6 – Thermistor connection
• J7 – Curtain switch
• J8 – Curtain switch
• J9 – Water level sensor
• J10 – Ice thickness sensor
• J11 – Bin thermostat. Use with NO thermostat (closes on temperature fall) & specified harness.
October 2012 Page 37
Control Safeties
Max freeze time – 45 minutes
When exceeded, the controller will attempt another freeze cycle. If the next cycle's freeze time is less than maximum, the control will continue normal ice making. If the next freeze cycle was too long, the control will again attempt another freeze cycle. If the freeze cycle is too long three consecutive cycles, the controller will shut the unit off and it must be manually reset.
Min freeze time – 6 minutes
If the controller switches the machine into harvest within 20 seconds of the minimum freeze time, the controller will harvest for a preset time and does not stop if the curtain switch opens.
If this occurs again in the next three cycles, the machine will shut down and must be manually reset.
Max harvest time – 3.5 minutes
If the harvest cycle has continued for 3.5 minutes without the curtain opening, the controller will shut the machine off for 50 minutes and then restart. If there is another the machine will shut the machine off for another 50 minutes and then restart. If it fails a third consecutive time the controller will shut the machine down and must be manually reset.
• Time between resets – 50 minutes
• Number of automatic resets – 2
• Max water fill time – 5 minutes. Machine will attempt a restart every 20 minutes.
• Max discharge temp – 250 degrees F.
• Time interval between cleanings – 6 months power on time - adjustable in one month increments, can be set at 6, 5, 4 or 3 months of power up time.
• Manual harvest time – 3 minutes
• Pump down interval – remote only. 12 hours. Pump down is 30 seconds of compressor only on time.
• Minimum compressor off time – 4 minutes
• Continuous Run Time Maximum Cycles - 200
October 2006 Page 38
Restarts
Power Interruption
The controller will automatically restart the ice machine after adequate voltage has been restored.
• H blinks on code display
• Status indicator light blinks
• Reservoir is drained and refilled
Default harvest is initiated. The curtain switch does not have to open to terminate harvest, harvest will continue until the default harvest time expires. Default harvest time is 3 minutes.
The machine will then return to a normal freeze cycle.
Water Interruption
• The controller will attempt to fill the reservoir every twenty minutes until it is successful.
On-Off Switch Access
All models ship with the On and Off switches front accessible. If desired, the On and Off switches can be covered by changing the bezel in the front panel’s trim strip. A cover-up bezel ships loose with the machine.
October 2012 Page 39
Control Button Use (from standby)
Set purge level, 1-5 (1 is minimum, 5 is maximum) or Automatic:
• Hold off button in for 3 seconds. Release.
• Press and release the On button to cycle through and select one of the five purge settings or to use the Automatic setting.
Recall diagnostic code:
• Hold off button in for 3 seconds. Release.
• Press and release the Harvest button to cycle through each of the last 10 error codes from most recent to oldest.
Clear diagnostic code:
• Hold Clean and Harvest buttons in for 3 seconds to clear all prior codes.
Reset control:
• Depress and release Off, then depress and release On
Start Test Mode:
• Hold Off button in for 3 seconds. Release.
• Hold Clean button in for 3 seconds. Release.
Lock / Unlock control:
• Hold On button in for 3 seconds, keep holding then press and release Off twice.
Empty reservoir:
• Hold Clean button in for 3 seconds. Release. Pump and purge valve will be ON for 30 seconds. Repeat as needed.
Test Mode: See next page for Air and Water Cooled mode.
• Depress Off for 3 seconds, release. Then depress Clean for 3 seconds.
• The sump will fill the first 30 seconds of the test. If the sump is full it will overflow into the bin. At 30 seconds the WIV will shut off and the WP will turn on. You will be able to see and hear the water running over the plates. After 10 seconds the PV and HGV will turn on. Water will be purging from the machine. After 10 more seconds the compressor will start. 5 seconds later the HGV will close. The compressor will run for a total of 20 seconds. After which everything will turn off for 5 seconds. After that time the HGV will open and you’ll be able to hear the hissing as the pressure is equalized. 10 seconds later the fan will turn on (if air cooled and fan control jumped). After 10 seconds all will be off and the output test will be complete.
October 2012 Page 40
Control Button Use - continued
Change De-Scale Notification Interval
Like the others, this feature is accessible only from standby (Status Light Off).
1. Press and hold harvest button for 3 seconds.
Starts the Time to Clean Adjustment State and displays the current time to clean setting.
2. Press the clean button repeatedly to cycle through the 4 possible settings:
Rev 5 and up (10/08 production start)
• 1 year (8760 hours)
• 0 (disabled)
• 4 months (2920 hrs)
• 6 months (4380 hours) (default)
Prior
• 6 months
• 5 months
• 4 months
• 3 months
3. Press Off or leave untouched for 60 seconds to select the displayed interval
Test Mode Sequence Table - Air or Water Cooled
50
55
70
75
85
95
Time (seconds)
0
30
40
On
WIV - 30 seconds
Off
WP, HGV, Comp, Fan, PV
WP - 10 seconds WIV, HGV, Comp, Fan, PV
WP, PV, HGV - 10 seconds WIV, Comp, Fan
HGV, Comp - 5 seconds
Comp - 15 seconds
None - 5 seconds
HGV - 10 seconds
Fan - 10 seconds
None
WIV, WP, Fan, PV
WIV, HGV, WP, Fan, PV
All
WIV, WP, Comp, Fan, PV
WIV, HGV, WP, Comp, PV
All – Test Complete
October 2008 Page 41
Diagnostics – Air Cooled
No ice
Problem
No power to unit
No power to controller
Shut down on maximum water fill time
Likely Cause
Power disconnected
Transformer open
Water shut off
Water leak
Air filters clogged
Dirty condenser
Restricted location, intake air too hot
Ice thickness sensor dirty or disconnected
Water distributor dirty
Inlet water valve leaks through during freeze
Shut down on maximum freeze time
Connected to hot water
Incomplete harvest
High pressure cut out opened
Fan motor pressure control open
Fan motor not turning
Water pump not pumping
Probable Solution
Check breaker or fuse. Reset or replace, restart and check
Replace transformer
Restore water supply
Check purge valve, curtain, sump, pump hose
Clean air filters
Clean condenser
Have machine moved
Check ice thickness sensor probe
Remove and clean water distributor
Check inlet water valve
Check for bleed thru from / missing check valve in building water supply
Check harvest system
Check fan motor pressure control, check fan motor, check controller using test mode
Check fan pressure control
Check fan motor, check fan blade, check controller using test mode
Check pump motor, check controller using test mode
October 2012 Page 42
Diagnostics – Air Cooled
Problem
Shut down on maximum freeze time
Likely Cause
Pump hose disconnected
Compressor not operating
Low refrigerant charge
Hot gas valve leaks through during freeze
Thermostatic expansion valve bulb loose
Thermostatic expansion valve producing very low or very high superheat
Compressor inefficient
Probable Solution
Check hose
Check compressor contactor, check controller using test mode
Check compressor start components, check PTCR resistance and temperature
Check compressor voltage
Check compressor windings
Add some refrigerant and restart unit. If cycle time improves, look for leak.
Check hot gas valve for hot outlet during freeze
Check bulb
Check evaporator superheat, change TXV if incorrect
Check compressor amp draw, if low and all else is correct, change compressor
October 2012 Page 43
Diagnostics – Air Cooled
Problem
Shut down on maximum harvest time
Shut down on minimum freeze time
Likely Cause
Ice bridge thickness too small, not enough ice to open curtain
Ice bridge thickness too large, ice frozen to evaporator frame
Purge valve does not open, water melts ice bridge, not enough ice to open curtain
Incomplete ice formation
Curtain out of position
Curtain switch does not open when curtain does
Machine in very cold ambient
Hot gas valve does not open
Harvest assist probe out of position – ejector pin not retracted
Damaged evaporator
Fan motor stays on during harvest
Grounded ice thickness sensor
Probable Solution
Check and adjust if needed
Check and adjust if needed
Check purge valve
Check water distributor for partially plugged holes
Check curtain for swing restriction
Check switch with ohmmeter
Move machine to a warmer location
Check hot gas valve, check controller using test mode
Check harvest assist mechanism – spring should retract pin
Check evaporator surface
Check controller using test mode
Check sensor for dirt and position. Clean and check gap to evaporator surface.
October 2012 Page 44
Low Ice Making Capacity - Air Cooled
Problem
Long freeze cycle
Long Harvest Cycle
False bin full signal
Likely Cause Probable Solution
Dirty air filters
Dirty condenser
Hot ambient
Water leak
Water inlet valve leaks through
Low on refrigerant
Incorrect superheat
Fan(s) cycle on and off
Clean filters
Clean condenser
Reduce room air temperature
Check purge valve, check curtain
Check inlet valve
Add refrigerant, if cycle time drops, check for leak
Check evaporator superheat, if significantly low or high, replace TXV
Check pressures fans cycle at.
Replace fan pressure switch if too low
Dirty evaporator
No harvest assist
De-scale water system
Check harvest assist solenoid
Bridge thickness too big
Check and adjust bridge thickness
Increase room temperature Machine in very cool ambient
Ice jammed in between curtain and sump
Clear ice away
Curtain does not close correctly Check curtain for proper swing
October 2012 Page 45
Makes Excessive Noise - Air Cooled
Problem
Fan blade vibrates
Compressor vibrates
Water pump vibrates
Panels vibrate
Likely Cause
Blade is bent
Fan motor mount is broken
Mounting bolts loose
Pump bearings worn
Mounting screws loose
Probable Solution
Replace fan blade
Replace motor mount
Tighten bolts
Replace pump
Tighten screws
October 2012 Page 46
Diagnostics - Water Cooled
No Ice
Problem
No power to unit
No power to controller
Shut down on maximum water fill time
Likely Cause
Power disconnected
Transformer open
Water shut off
Water leak
Ice thickness sensor dirty or disconnected
Water distributor dirty
Inlet water valve leaks through during freeze
Shut down on maximum freeze time
Connected to hot water
Incomplete harvest
High pressure cut out opened
Water pump not pumping
Pump hose disconnected
Compressor not operating
Probable Solution
Check breaker or fuse. Reset or replace, restart and check
Replace transformer
Restore water supply
Check purge valve, curtain, sump, pump hose
Check ice thickness sensor probe
Remove and clean water distributor
Check inlet water valve
Check for bleed thru from / missing check valve in building water supply
Check harvest system
Water supply cut off, restore water supply to condenser
Check pump motor, check controller using test mode
Check hose
Check compressor contactor, check controller using test mode
Check compressor start components, check PTCR resistance and temperature
Check compressor voltage
Check compressor windings
October 2012 Page 47
Diagnostics - Water Cooled
Problem
Shut down on maximum freeze time
Shut down on maximum harvest time
Likely Cause
Low refrigerant charge
Hot gas valve leaks through during freeze
Thermostatic expansion valve bulb loose
Thermostatic expansion valve producing very low or very high superheat
Probable Solution
Add some refrigerant and restart unit. If cycle time improves, look for leak.
Check hot gas valve for hot outlet during freeze
Check bulb
Compressor inefficient
Check evaporator superheat, change TXV if incorrect
Check compressor amp draw, if low and all else is correct, change compressor
Check and adjust if needed
Ice bridge thickness too small, not enough ice to open curtain
Ice bridge thickness too large, ice frozen to evaporator frame
Purge valve does not open, water melts ice bridge, not enough ice to open curtain
Incomplete ice formation
Check and adjust if needed
Check purge valve
Curtain out of position
Curtain switch does not open when curtain does
Machine in very cold ambient
Hot gas valve does not open
Harvest assist probe out of position – ejector pin not retracted
Damaged evaporator
Check water distributor for partially plugged holes
Check curtain for swing restriction
Check switch with ohmmeter
Move machine to a warmer location
Check hot gas valve, check controller using test mode
Check harvest assist mechanism – spring should retract pin
Check evaporator surface
October 2012 Page 48
Diagnostics - Water Cooled
Problem
Shut down on minimum freeze time
Likely Cause
Grounded ice thickness sensor
Probable Solution
Check sensor for dirt and position. Clean and check gap.
Test Mode Sequence: - Air or Water Cooled
55
70
75
85
95
Time (seconds)
0
30
40
50
On
WIV - 30 seconds
WP - 10 seconds
HGV, Comp - 5 seconds
Comp - 15 seconds
None - 5 seconds
HGV - 10 seconds
Fan - 10 seconds
None
Off
WP, HGV, Comp, Fan, PV
WIV, HGV, Comp, Fan, PV
WP, PV, HGV - 10 seconds WIV, Comp, Fan
WIV, WP, Fan, PV
WIV, HGV, WP, Fan, PV
All
WIV, WP, Comp, Fan, PV
WIV, HGV, WP, Comp, PV
All – Test Complete
October 2012 Page 49
Low ice Making Capacity - Water Cooled
Problem
Long freeze cycle
Long Harvest Cycle
False bin full signal
Likely Cause Probable Solution
Water leak
Check purge valve, check curtain
Water inlet valve leaks through Check inlet valve
Low on refrigerant
Incorrect superheat
Add refrigerant, if cycle time drops, check for leak
Check evaporator superheat, if significantly low or high, replace TXV
Dirty evaporator
No harvest assist
De-scale water system
Check harvest assist solenoid
Bridge thickness too big
Check and adjust bridge thickness
Increase room temperature Machine in very cool ambient
Ice jammed in between curtain and sump
Clear ice away
Curtain does not close correctly Check curtain for proper swing
October 2012 Page 50
Makes Excessive Noise - Water Cooled
Problem
Compressor vibrates
Water pump vibrates
Panels vibrate
Likely Cause
Mounting bolts loose
Pump bearings worn
Mounting screws loose
Probable Solution
Tighten bolts
Replace pump
Tighten screws
October 2012 Page 51
Diagnostics - Remote Air Cooled
No Ice
Problem
No power to unit
No power to controller
Shut down on max.
water fill time
Shut down on maximum freeze time
Likely Cause
Power disconnected
Transformer open
Water shut off
Water leak
Dirty condenser
Restricted location, intake air too hot
Ice thickness sensor dirty or disconnected
Water distributor dirty
Inlet water valve leaks through during freeze
Connected to hot water
Incomplete harvest
High pressure cut out opened
Fan motor not turning
Water pump not pumping
Pump hose disconnected
Liquid line valve does not open
Compressor not operating
Probable Solution
Check breaker or fuse. Reset or replace, restart and check
Replace transformer
Restore water supply
Check purge valve, curtain, sump, pump hose
Clean condenser
Have condenser moved
Check ice thickness sensor probe
Remove and clean water distributor
Check inlet water valve
Check for bleed thru from / missing check valve in building water supply
Check harvest system
Check check fan motor
Check quick connects for complete piercing
Check fan motor, check fan blade
Check pump motor, check controller using test mode
Check hose
Check coil of valve, check controller using test mode.
Check compressor contactor, check controller using test mode
October 2012 Page 52
Diagnostics - Remote Air Cooled
Problem Likely Cause
Compressor not operating
(continued)
Low refrigerant charge
Shut Down on
Maximum Freeze Time
(continued)
Hot gas valve leaks through during freeze
Thermostatic expansion valve bulb loose
Thermostatic expansion valve producing very low or very high superheat
Probable Solution
Check compressor start components, check PTCR resistance and temperature
Check compressor voltage
Check compressor windings
Add some refrigerant and restart unit. If cycle time improves, look for leak.
Check hot gas valve for hot outlet during freeze
Check bulb
Compressor inefficient
Debris in refrigeration system
Check evaporator superheat, change TXV if incorrect
Check compressor amp draw, if low and all else is correct, change compressor
Recover charge. Open quick connects, check for loose or missing foil. Open liquid line and hot gas valves. Check for debris.
Replace drier, evacuate and weigh in nameplate charge.
Check and adjust if needed
Shut down on maximum harvest time
Ice bridge thickness too small, not enough ice to open curtain
Ice bridge thickness too large, ice frozen to evaporator frame
Purge valve does not open, water melts ice bridge, not enough ice to open curtain
Incomplete ice formation
Check and adjust if needed
Check purge valve
Curtain out of position
Check water distributor for partially plugged holes
Check curtain for swing restriction
October 2012 Page 53
Diagnostics - Remote Air Cooled
Problem
Shut down on maximum harvest time
(continued)
Shut down on minimum freeze time
Likely Cause
Curtain switch does not open when curtain does
Machine in very cold ambient
Hot gas valve does not open
Harvest assist probe out of position – ejector pin not retracted
Damaged evaporator
Grounded ice thickness sensor
Probable Solution
Check switch with ohmmeter
Move machine to a warmer location
Check hot gas valve, check controller using test mode
Check harvest assist mechanism – spring should retract pin
Check evaporator surface
Check sensor for dirt and position. Clean and adjust gap to evaporator surface using
13/64” drill bit as a gauge
October 2012 Page 54
Low Ice Making Capacity - Remote
Problem
Long freeze cycle
Long Harvest Cycle
False bin full signal
Likely Cause Probable Solution
Dirty condenser
Hot ambient
Water leak
Water inlet valve leaks through
Clean condenser
Check condenser inlet temp.
Check purge valve, check curtain
Check inlet valve
Low on refrigerant
Incorrect superheat
Add refrigerant, if cycle time drops, check for leak
Check evaporator superheat, if significantly low or high, replace TXV
Fan(s) cycle on and off
Check pressures fans cycle at.
Replace fan pressure switch if too low
De-scale water system Dirty evaporator
No harvest assist
Bridge thickness too big
Check harvest assist solenoid
Check and adjust bridge thickness
Increase room temperature Machine in very cool ambient
Ice jammed in between curtain and sump
Clear ice away
Curtain does not close correctly Check curtain for proper swing
October 2012 Page 55
Makes Excessive Noise - Remote
Problem
Fan blade vibrates
Compressor vibrates
Water pump vibrates
Panels vibrate
Likely Cause
Blade is bent
Fan motor mount is broken
Mounting bolts loose
Pump bearings worn
Mounting screws loose
Probable Solution
Replace fan blade
Replace motor mount
Tighten bolts
Replace pump
Tighten screws
Off
WP, HGV, Comp, BV, PV
WIV, HGV, Comp, BV, PV
WIV, Comp, BV
WIV, WP, BV, PV
WIV, HGV, BV, WP, PV
All
WIV, WP, Comp, BV, PV
WIV, HGV, WP, Comp, PV
All – Test Complete
October 2012 Page 56
Test Procedures - Sensors
All electrical components in this ice machine can be diagnosed with a volt-ohmmeter.
Curtain Switch:
1. Test using the controller’s indicator lights. Observe SW1 and SW2. Open and close the curtain in question. When the curtain is opened, the SW light will be ON. When the curtain gets to within a half inch of closing (at the switch) the SW light will go OUT.
2. Test with an ohmmeter. Disconnect electrical power. Open the control box cover. Unplug the curtain switch lead from the controller. Connect an ohmmeter to the leads of the switch. Open and close the curtain. When the curtain is closed, the switch is closed and there will be continuity. When the curtain is open, the switch is open and the circuit will be open.
3. Test the controller’s curtain switch circuit by jumping the connectors on J1 or J2 together.
Reconnect electrical power. When jumped, the matching SW light will go out. When unplugged or open, the SW light will be ON.
Curtain Switch
Indicator Lights
Light is ON when curtain is OPEN
Single curtain models have one indicator light ON all the time.
October 2012 Page 57
Curtain
Switch
Ice Thickness Sensor
1. Test using the controller’s indicator light. Observe the Ready To Harvest light. Shut the machine off. Use a wire to connect the metal part of the Ice Thickness sensor to the evaporator or simply remove the Ice Thickness Sensor and touch its metal surface to the metal control box wall. The Ready for Harvest light should go ON.
2. Test with an Ohmmeter. Disconnect electrical power. Open the control box cover. Unplug the ice thickness sensor lead from the controller. Connect an ohmmeter lead to the ice thickness sensor lead, touch the other ohmmeter lead to the ice machine chassis. There must be an open circuit. If there is continuity, the sensor must be replaced. If there is no continuity, touch the ohmmeter lead to the metal part of the ice thickness sensor. There should be continuity. If open, check the ice thickness sensor for scale build up. Clean and recheck. If still open, replace the ice thickness sensor.
3. Test the controller’s ice thickness sensor circuit by connecting a wire from J10 to ground.
Reconnect electrical power. The Ready for Harvest light should go ON.
Ready To Harvest light is ON when water contacts ice thickness sensor.
Ice
Thickness
Sensor
October 2012 Page 58
Water Level Sensor
1. Test using the controller’s indicator lights (sump empty and sump full). Unit must be powered up and there must be water in the sump. Add some manually if needed. Locate water level sensor. Release from sump cover and slowly lift up until the mid-length probe is out of the water. The sump empty light should come on, and if the unit is on the inlet water solenoid valve will open to fill the reservoir. Return the water level sensor to its normal position. If the unit is on and calling for ice the water will fill until the top probe is in contact with it, at that time the sump full light will switch ON.
2. Test with an ohmmeter. Disconnect electrical power. Open the control box cover. Unplug the connector at J9. Locate water level sensor and remove it from the sump cover. Test 1: Place one lead of the ohmmeter on the longest probe and the other on the controller end of the red wire, there should be continuity. Test 2: Place one lead on the controller end of the white wire and the other on the mid-length probe, there should be continuity. Test 3: Place on lead on the controller end of the black wire and the other on the shortest probe, there should be continuity.
If not, clean the probes and recheck.
3. Test the controller’s water level sensor circuit. Reconnect electrical power. Unplug harness from water level sensor, the sump empty light should be ON. Jump harness wires white and black. The sump full light should be ON. Jump harness wires white and red, the sump full and sump empty lights will be
OFF. Check harness wire by wire for continuity if there is no reaction from the controller during this test.
Sump
Empty Light
Sump Full
Light
December 2008 Page 59
Temperature Sensors
1. Check controller. If the sensor calibration is completely out of range, the code display will read either 5 or 7.
2. Check with an ohmmeter. Open control box cover, unplug sensor from J6. Water temperature probe: Measure the temperature of the water. Push and release the clean button.
Wait one minute. Measure the resistance of the water probe (two leads next to the open socket) and compare to the resistance in the chart for that temperature. Any reading within
1000 ohms is acceptable. Discharge sensor: Measure the temperature of the discharge line as close to the sensor as possible. Measure the resistance of the discharge temperature sensor
(two leads farthest away from the open socket on the harness connector) and compare to the resistance in the chart for that temperature. Any reading within 1000 ohms is acceptable.
3. Alternate procedure: Remove both water and discharge sensors from their places on the ice machine. Put both into a container of ice water. Put a thermometer in the water. When the thermometer is at 32 degrees F., check the resistance of each sensor. The resistance should be within 1000 ohms of 32649.
Water
Temperature
Sensor Set
Back of Controller
October 2012 Page 60
Discharge
Temperature
Sensor Set
Test Procedures - Loads
Compressor
Failure to start.
Single phase models. All have resistance start, capacitor run type motors. Check voltage to compressor at the contactor. Compare the idle voltage (compressor off) to the active voltage
(compressor starting). The supply voltage must not be less than the lowest rated voltage for the ice machine. If the voltage is correct, proceed to the next step.
Check starting components. Most models use a PTCR to cut power to the start winding after the compressor has started. Check the PTCR for resistance. The resistance check must be when the PTCR is at room temperature – any temperature between 50 and 100.
At that temperature resistance should be very low between 25 and 50 ohms. Also check resistance to ground, it should be infinite. If the PTCR is good, check the compressor windings.
Measure resistance from Common to ground. It should be infinite. Measure resistance from
Common to Run – compare to the chart. Measure resistance from Common to Start – compare to the chart.
Compressor check for high amp draw. Measure amp draw of starting circuit. If it does not drop off immediately after start up, the PTCR should be replaced. It is not practical to check a PTCR for resistance at high temperatures as the resistance drops very fast as the PTCR’s temperature falls. If the compressor is drawing excessive amps but is operating, the run capacitor may be open. Disconnect electrical power, discharge the capacitor and measure its resistance. If open, replace it. If shorted to ground, replace it.
Any time the compressor is replaced, the PTCR and run capacitor should also be replaced, or if the model was equipped with a potential relay, start capacitor and run capacitor, those should be replaced with the compressor. Most Scotsman service compressors include those parts.
Some systems use a potential start relay and start capacitor in place of the PTCR.
Potential relay. If the compressor will not start, check the amp draw of the starting circuit. If very low, the potential relay contacts or start capacitor may be open. Measure the resistance of the potential relay contacts and the start capacitor. If either is open it should be replaced. If the compressor starts but draws very high amps from the starting circuit, the potential relay may not switch off. In that case the relay should be replaced.
October 2012 Page 61
Ice Machine
C0322 or
C0330-1
C0330-6
C0330-32
C0522 or
C0530-1 A or B
C0530-6 A or B
C0530-32 A or B
C0530 -1 C
C0530 - 6 C
C0530 - 32 C
C0722 or
C0630-32
C0630-6
C0830-32
C0830-6
C0830-3
C1030-32
C1030-6
C1030-3
C1448-32
C1448-6
C1448-3
C1848-32
C1848-6
C1848-3
C2148-32 WC
C2148-6 WC
C2148-3 WC
C2148-32 R
C2148-6 R
C2148-32 R
Compressor Electrical Chart
Resistance reading tolerance is +- 10%
115/60/1
230/50
208-230/60/1
115/60/1
230/50
208-230/60/1
115/60/1
230/50/1
208-230/60/1
208-230/60/1
230/50
208-230/60/1
230/50
208-230/60/3
208-230/60/1
230/50
208-230/60/3
208-230/60/1
230/50
208-230/60/3
208-230/60/1
230/50
208-230/60/3
208-230/60/1
230/50
208-230/60/3
208-230/60/1
230/50
208-230/60/3
Voltage/Hz/Phase Compressor
AKA9438ZXA
AKA9438ZXC
AKA9468ZXD
AKA9451ZXA
AKA9451ZXC
AKA9451ZXD
RST45C1E-CAA
RST45C1E-CAB
RST45C1E-CAV
AJA7490ZXD
AJA7490ZXC
CS10K6EPFV
CS10K6EPFJ
CS10K6ETF5
CS12K6EPFV
CS12K6EPFJ
CS12K6ETF5
CS14K6EPFV
CS14KSEPFJ
CS14K6ETF5
CS20K6EPFV
CS20K6EPFZ
CS20K6ETF5
CS24K6EPFV
CS24K6EPFZ
CS24K6ETF5
CS27K6EPFV
CS27K6EPFZ
CS27K6ETF5
Start Winding
Ohms
4.22
7.11
10.43
5.95
7.11
10.43
Run Winding
Ohms
.59
2.69
1.77
.69
2.69
1.77
2.74
2.23
3.10
3.79
3.10
-
3.79
-
2.66
2.64
2.37
-
2.35
2.35
-
-
-
.53
.53
-
-
-
1.52
2.02
1.16
1.39
1.77
1.16
1.39
1.77
1.08
1.4
.65
-
October 2012 Page 62
Refrigerant Charges
C0722A
C0830A
C0830W
C0830R
C1030A
C1030W
C1030R
C1448A
C1448W
C1448R
C1848A
C1848W
C1848R
C2148W
C2148R
Model
C0322A
C0322W
C0330A
C0330W
C0522A
C0522W
C0522R
C0530A (A or B series)
C0530A C series
C0530W (A thru C series)
C0530R (A thru C series)
C0630A
C0630W
C0630R
48
38
208
62
17
46
34
208
56
256
62
63
320
69
320
160
36
14
160
160
22
21
11
14
11
17
14
R-404A in ounces
14
11
October 2012 Page 63
Test Procedures - Loads
Fan motor
1. Test using the controller’s indicator lights.
Note: Fan pressure control connection must be jumped to perform this test.
Put the controller into test mode (depress Off for 3 seconds then depress Clean for 3 seconds). At the end of the test cycle, the fan motor will be powered and the Condenser Fan motor indicator light will be on. The fan motor should start and run at that time. If it does not, repeat the test but check the voltage to the fan motor, it must receive full voltage at the fan motor lead connection at the end of the test. If there is voltage and the motor does not operate, replace the motor. If there is no voltage, check the controller high voltage harness connection.
The fan motor lead is the top wire. Check voltage from it to ground, at the end of the test, when the fan motor indicator light is On, there must be voltage from this pin to ground. Note: high voltage power is supplied to the bottom pin from the contactor line. Refer to the machine wiring diagram as needed.
2. Test using an ohmmeter. Disconnect electrical power. Unplug fan motor from harness.
Measure fan motor winding resistance. If open, replace the fan motor.
This light is ON when the fan motor should be in operation.
October 2012 Page 64
Fan Pressure Control must CLOSE to operate fan motor.
Test Procedures - Loads
Water Pump
1. Test using the controller’s indicator lights. Check the indicator light during the freeze cycle.
The light will be On for all but the 30 second anti-slush period, so observe the light for one minute. When it is On, check the water pump, it should be operating. If not, check voltage to the pump. If low check the voltage from the controller to ground. The water pump pin is number 6. If there is voltage at that pin to ground, but very low voltage at the pump motor, there must be a broken wire in the harness. If the voltage is low at pin 6, the controller should be replaced.
2. Test using an ohmmeter. Disconnect electrical power. Unplug the water pump motor leads from the harness. Measure the resistance of the motor windings. If open, replace the pump.
Measure resistance to ground. If there is any, replace the pump.
Water pump light is ON when pump is in operation.
October 2012 Page 65
Test Procedures - Loads
Purge valve
1. Test using the controller’s indicator lights. Shut unit off by holding the Off button for 3 seconds. Wait four minutes. Push and release the On button, observe the Purge Valve indicator light. As the unit drains the reservoir, the purge valve will be powered. When it gets power, the indicator light will be ON. If the purge valve does not open to drain the reservoir when its indicator light is on, do a voltage check. Shut the unit down by holding the Off button in for 3 seconds. Unplug the harness connection from the purge valve. Wait four minutes. Push and release the On button to restart the machine. As the unit drains the reservoir, the purge valve connection should receive full voltage. If it does, the purge valve should be replaced. If there is no voltage, check voltage from the controller to ground. The purge valve pin is 3 (dump valve on wiring diagram). If there is voltage from that pin to ground, but low voltage at the valve harness connection, the harness has a broken wire or poor connection and must be replaced.
If the voltage to ground is low, the controller should be replaced.
Note: The coil of this valve is internally rectified, and will normally show infinite resistance when tested with an ohmmeter.
This light will be ON when the Purge Valve is in operation.
October 2012 Page 66
Test Procedures - Loads
Compressor contactor
1. Test using the controller’s indicator lights. When the unit is in ice making mode the compressor contactor will have power. Check the Compressor indicator light, when it is on the compressor contactor will have pulled in. If it is not, do a voltage check. Place voltmeter leads on the coil of the contactor. There should be full voltage . If there is full voltage present and the contactor has not pulled in, replace the contactor. If there is no voltage check if the high pressure cut out is open. If the high pressure cut out is closed, check for voltage from the controller to ground. The contactor pin is 4. Check from 4 to ground when the compressor indicator light is on. There should be voltage. If not, replace the controller. If there is voltage at the controller but not at the contactor coil, the harness wires or connectors are damaged and must be replaced.
2. Test using an ohmmeter. Test the coil of the contactor for continuity or shorts to ground.
Replace if open or shorted.
3. Check connections and contacts. Be sure connections are tight and that the contacts are not burnt. Replace any contactor with burnt contacts.
This light will be ON when the compressor contactor is powered.
October 2012 Page 67
Test Procedures - Loads
Pressure switches
There are two pressure switches: Fan and High Pressure cut out.
Fan. The fan pressure switch will open to shut the fan motor off at a certain pressure and re-close at a preset higher pressure.
High pressure cut out. The high pressure cut out switch will open at a preset pressure, shutting off power to the compressor contactor. After the pressure has fallen to another preset level, the switch will re-close and the contactor coil will be engergized.
To Test Fan Pressure Switch:
A. Attach refrigeration gauge set to high side port.
B. Unplug both wires from fan pressure control. Be SURE the wire's terminals are wrapped
in electrical tape to prevent short circuits to ground during the test.
C. Connect ohmmeter to terminals of fan pressure control..
D. Switch ice machine on, observe pressure that the pressure control closes at, compare to spec. Switch unit off, allow system to equalize, observe pressure the pressure control opens at, compare to spec.
To Test High Pressure Switch:
A. Attach refrigeration gauge set to high side port.
B. Unplug fan motor or shut water off if water cooled.
C. Measure voltage between contactor side terminal of high pressure control and ground.
D. Switch ice machine on, observe pressure that the pressure control opens at, compare to spec. Allow system to equalize, observe the pressure that the pressure control closes at, compare to spec.
Transformer
Check secondary voltage, it must be between 10 and 15.5 AC volts. Replace if no voltage is output or if above or below the acceptable voltage..
Controller
The controller’s software operation is confirmed if it is functioning. Execute the test to confirm its operation of the loads. Illumination of a diagnostic code (other than E) is not an indication of controller failure. Each code requires its own diagnosis.
October 2012 Page 68
Test Procedures - Loads
Liquid Line Solenoid (remote only)
1. Test using the controller’s indicator lights. Put the controller into test mode (depress Off for 3 seconds then depress Clean for 3 seconds). At the end of the test cycle, the liquid line valve will be powered and the Condenser Fan motor indicator light will be on. The liquid line valve should be open at that time. If it is not, repeat the test but check the voltage to the liquid line valve coil, it must receive full voltage at the liquid line lead connection at the end of the test. If there is voltage and the valve does not operate, replace the valve coil. If there is no voltage, check the controller high voltage harness connection. The liquid line solenoid lead is the top wire. Check voltage from it to ground, at the end of the test, when the Condenser Fan indicator light is On, there must be voltage from this pin to ground. Note: high voltage power is supplied to the bottom pin from the contactor line. Refer to the machine wiring diagram as needed.
2. Test using an ohmmeter. Disconnect electrical power. Unplug liquid line coil from harness.
Measure liquid line coil resistance. If open, replace the liquid line valve coil.
This light will be ON when the liquid line solenoid has power.
October 2012 Page 69
Test Procedures - Loads
Inlet Water Solenoid Valve
1. Test using the controller’s indicator lights. Shut unit off by holding the Off button for 3 seconds. Wait four minutes. Push and release the On button, observe the Water Solenoid indicator light. After the unit drains the reservoir, the inlet water valve will be powered to refill the reservoir. When it gets power, the indicator light will be ON. If the water valve does not open to fill the reservoir when its indicator light is on, do a voltage check. Shut the unit down by holding the Off button in for 3 seconds. Unplug the harness connection from the inlet water valve. Wait four minutes. Push and release the On button to restart the machine. After the unit drains the reservoir, the inlet water valve connection should receive full voltage. If it does, the inlet water valve should be replaced. If there is no voltage, check voltage from the controller to ground. The inlet water solenoid valve pin is 7. If there is voltage from that pin to ground, but low voltage at the valve harness connection, the harness has a broken wire or poor connection and must be replaced. If the voltage to ground is low, the controller should be replaced.
2. Test using an ohmmeter. Disconnect electrical power. Unplug coil from harness. Measure coil resistance. If open, replace the inlet water solenoid.
Light is ON when inlet water solenoid is in operation.
October 2012 Page 70
Test Procedures - Loads
Harvest assist solenoid
1. Test using the controller’s indicator lights. Push and release the Harvest button. The Hot
Gas indicator light will be on. At the same time the Harvest Assist Solenoid will be powered. If the ice on the evaporator is thin, the solenoid will extend. If the ice is nearly full sized, the solenoid will press against the ice until it releases from the evaporator, then the solenoid probe will extend. If the probe extends, the solenoid is good. If not, do a voltage check. Unplug the high voltage harness from the harvest assist solenoid. Attach a voltmeter to the harness connector. Push and release the Harvest button. There should be full voltage at the connector.
If there is and the solenoid does not extend, replace the solenoid. If full voltage is not present, check voltage at the controller. If there is no voltage, check voltage from the controller to ground. The hot gas / harvest assist pin is 5. If there is voltage from that pin to ground, but low voltage at the solenoid harness connection, the harness has a broken wire or poor connection and must be replaced. If the voltage to ground is low, the controller should be replaced.
Note: The coil of this valve is internally rectified, will normally show infinite resistance when tested with an ohmmeter.
This light will be ON during harvest.
Both the Hot Gas Valve coil and the
Harvest assist solenoid coil will have power when this light is ON.
Hot Gas or Vapor Valve
1. Test using the controller’s indicator lights. If the unit is running, or has been off for more than 4 minutes, push and release the Harvest button. The Hot Gas indicator light will be on and the hot gas valve will be energized. The compressor will force discharge gas into the evaporator inlet, warming it. If the evaporator inlet does not warm up, do a voltage check. Shut the unit off by holding the Off button in for 3 seconds. Unplug the high voltage harness from the hot gas solenoid. Attach a voltmeter to the harness connector. Wait 4 minutes. Push and release the Harvest button. There should be full voltage at the connector. If there is and the solenoid does not open, replace the solenoid coil. If full voltage is not present, check voltage at the controller. If there is no voltage, check voltage from the controller to ground. The hot gas pin is 5. If there is voltage from that pin to ground, but low voltage at the solenoid harness connection, the harness has a broken wire or poor connection and must be replaced. If the voltage to ground is low, the controller should be replaced.
2. Test with an ohmmeter. Disconnect electrical power. Unplug high voltage harness from hot gas or vapor valve. Measure resistance of hot gas or vapor valve coil. If open, replace the coil.
October 2012 Page 71
Technical Information
Pressure Switches Cut In, Cut Out
Fan Pressure Control, 22" and 30"
Fan Pressure Control, 48"
High Pressure Cut Out AC
High Pressure Cut Out WC
High Pressure Cut Out, Remote
Cut In (PSIG)
240
280
390
300
350
Compressor Amp Draws
- amps peak and then decline during each cycle
C0322
C0522
C0330
C0330 C
115
230
115
230
115
Voltage
115
230
115
230
C0530 A or B
C0530 C
C1848
C2148 W
C2148R
230
115
230
C0722 or C0630 230
C0830 single phase
C1030 three phase single phase three phase
C1448 single phase three phase single phase three phase single phase three phase single phase three phase
Brand
Tecumseh
Base Model
AKA9438 same
AKA9451 same
Copeland
AKA9438 same
RST45 same
AKA9451
Tecumseh
Copeland
Copeland same
RST45
RST45
Tecumseh AJA7490
CS10 same
CS12 same
CS14 same
CS20 same
CS24 same
CS27 same
October 2012 Page 72
Freeze
7.3 - 4.8
7.9 - 6.5
6 - 4.5
6.2 - 4.8
7 - 5.3
8 - 6.5
6.9 - 5.5
3 - 2.2
5.8 - 5.0
6.4 - 5.3
4.5 - 3.5
7.3 - 4.8
4.4 - 3.2
12.5 - 7.6
7.2 - 4.5
16 - 10
14 - 8
18 - 12
10.5 - 7.2
20 - 14
13.5 - 8
Cut Out (PSIG
190
220
500
400
450
Harvest
6.2
7.2
6
5.7
6.4 - 7
9.3
6.6 - 7.0
2.5
6.8
6.6
5
6.2
5.5
9.2
5.5 - 5.7
15
10
18
14
19.6 - 16
13 - 12
Heat Load & Condenser Water GPM
Air Cooled - Average heat load for air conditioning unit sizing
Model
C0322
C0522
C0330
C0530
C0630
C0722
C0830
C1030
C1448
C1848
BTUH
5200
7900
5200
7900
12700
12700
13700
16200
20000
27400
C0322
C0522
C0330
C0530
C0630
C0803
C1030
C1448
C1848
C2148
Water Cooled Water Use - condenser only,
Model
.4
.4
.3
.4
.3
.1
GPM, 45 o
F.
water inlet temp
.2
.6
1.0
1.0
GPM, 70 o
F. water inlet temp
.7
.8
1.0
1.1
1.8
2.0
.3
.5
.3
.7
October 2012 Page 73
Controller Differences
The controllers are programmed at the factory for the model they are installed on, they cannot be moved from one model to another due to differences in:
• Water purge time per setting
• Maximum harvest time
• Number of evaporator plates
The service controller has a selector switch that allows it to be used as a replacement part in any of the Prodigy models in production at the time the controller was manufactured. As new
Prodigy models are introduced, those models will be added to the list of models new service controllers will work with.
The Service Controller includes a selector switch. The switch must be set to the model the controller is being installed on. As new models are introduced, their setting will be added to service controllers produced after that point.
October 2012 Page 74
Thermistor Values
Deg. F . . Ohms
0. . . . . . 85325
1. . . . . . 82661
2. . . . . . 80090
3. . . . . . 77607
4. . . . . . 75210
5. . . . . . 72896
6. . . . . . 70660
7. . . . . . 68501
8. . . . . . 66415
9. . . . . . 64400
10. . . . . 62453
11. . . . . 60571
12. . . . . 58752
13. . . . . 56995
14. . . . . 55296
15. . . . . 53653
16. . . . . 52065
17. . . . . 50529
18. . . . . 49043
19. . . . . 47607
20. . . . . 46217
21. . . . . 44872
22. . . . . 43571
23. . . . . 42313
24. . . . . 41094
25. . . . . 39915
26. . . . . 38774
27. . . . . 37669
28. . . . . 36600
29. . . . . 35564
30. . . . . 34561
31. . . . . 33590
32. . . . . 32649
33. . . . . 31738
34. . . . . 30855
35. . . . . 30000
36. . . . . 29171
37. . . . . 28368
38. . . . . 27589
39. . . . . 26835
40. . . . . 26104
41. . . . . 25395
42. . . . . 24707
43. . . . . 24041
44. . . . . 23394
45. . . . . 22767
46. . . . . 22159
47. . . . . 21569
48. . . . . 20997
49. . . . . 20442
50. . . . . 19903
51. . . . . 19381
Deg. F . . Ohms
52. . . . . 18873
S3. . . . . 18381
54. . . . . 17903
55. . . . . 17439
56. . . . . 16988
57. . . . . 16551
58. . . . . 16126
59. . . . . 15714
60. . . . . 15313
61. . . . . 14924
62. . . . . 14546
63. . . . . 14179
64. . . . . 13823
65. . . . . 13476
66. . . . . 13139
67. . . . . 12812
68. . . . . 12494
69. . . . . 12185
70. . . . . 11884
71. . . . . 11592
72. . . . . 11308
73. . . . . 11031
74. . . . . 10763
75. . . . . 10502
76. . . . . 10247
77. . . . . 10000
78. . . . . 9760
79. . . . . 9526
80. . . . . 9299
81. . . . . 9077
82. . . . . 8862
83. . . . . 8652
84. . . . . 8448
85. . . . . 8250
86. . . . . 8056
87. . . . . 7868
88. . . . . 7685
89. . . . . 7507
90. . . . . 7333
91. . . . . 7164
92. . . . . 6999
93. . . . . 6839
94. . . . . 6683
95. . . . . 6530
96. . . . . 6382
97. . . . . 6238
98. . . . . 6097
99. . . . . 5960
100. . . . 5826
101. . . . 5696
102. . . . 5569
103. . . . 5446
Deg. F. . Ohms Deg. F. . Ohms
120. . . . 3757
121. . . . 3678
122. . . . 3601
123. . . . 3526
124. . . . 3452
125. . . . 3381
126. . . . 3311
127. . . . 3243
128. . . . 3176
129. . . . 3111
130. . . . 3047
131. . . . 2985
132. . . . 2924
133. . . . 2865
134. . . . 2807
135. . . . 2751
104. . . . 5325
105. . . . 5208
106. . . . 5093
107. . . . 4981
108. . . . 4872
109. . . . 4766
110. . . . 4663
111. . . . 4562
112. . . . 4463
113. . . . 4367
114. . . . 4273
115. . . . 4182
116. . . . 4093
117. . . . 4006
118. . . . 3921
119. . . . 3838
136. . . . 2696
137. . . . 2642
138. . . . 2589
139. . . . 2537
140. . . . 2487
141. . . . 2438
142. . . . 2390
143. . . . 2343
144. . . . 2297
145. . . . 2252
146. . . . 2208
147. . . . 2165
148. . . . 2123
149. . . . 2082
150. . . . 2042
151. . . . 2003
152. . . . 1965
153. . . . 1927
154. . . . 1890
155. . . . 1855
October 2012 Page 75
172. . . . 1350
173. . . . 1326
174. . . . 1302
175. . . . 1279
176. . . . 1256
177. . . . 1234
178. . . . 1212
179. . . . 1190
180. . . . 1169
181. . . . 1149
182. . . . 1129
183. . . . 1109
184. . . . 1090
185. . . . 1071
186. . . . 1052
187. . . . 1034
156. . . . 1819
157. . . . 1785
158. . . . 1752
159. . . . 1719
160. . . . 1687
161. . . . 1655
162. . . . 1624
163. . . . 1594
164. . . . 1565
165. . . . 1536
166. . . . 1508
167. . . . 1480
168. . . . 1453.
169. . . . 1427
170. . . . 1401
171. . . . 1375
188. . . . 1016
189. . . . 998
190. . . . 981
191. . . . 965
192. . . . 948
193. . . . 932
194. . . . 916
195. . . . 901
196. . . . 885
197. . . . 871
198. . . . 856
199. . . . 842
200. . . . 828
201. . . . 814
202. . . . 800
203. . . . 787
204. . . . 774
205. . . . 761
206. . . . 749
207. . . . 737
Deg. F. . Ohms
224. . . . 560
225. . . . 551
226. . . . 543
227. . . . 534
228. . . . 526
229. . . . 518
230. . . . 510
231. . . . 502
232. . . . 495
233. . . . 487
234. . . . 480
235. . . . 472
236. . . . 465
237. . . . 458
238. . . . 451
239. . . . 444
208. . . . 724
209. . . . 713
210. . . . 701
211. . . . 690
212. . . . 679
213. . . . 668
214. . . . 657
215. . . . 646
216. . . . 636
217. . . . 626
218. . . . 616
219. . . . 606
220. . . . 597
221. . . . 587
222. . . . 578
223. . . . 569
240. . . . 438
241. . . . 431
242. . . . 425
243. . . . 419
244. . . . 412
245. . . . 406
246. . . . 400
247. . . . 394
246. . . . 389
249. . . . 383
250. . . . 377
Performance Data
C0322A
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
C0322W
10-12
11-12
12-13
13-14
26
105
235
150
70
Ambient Air Temp., Degrees F.
80 90
12-13
13-14
14+
14-15
13-14
14-16
15-16
16-17
32
130
250
200
70
Ambient Air Temp., Degrees F.
80 90
Cycle Time
(minutes)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
Suction Pressure
(PSIG)
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle weight: 2-4 to 2.6 lb.
9-11
11+
12+
12-13
32
95-100
245
140
11+
12+
13+
13-14
10-11
10-12
12-13
13+
32
100-110
245
150
October 2012 Page 76
Performance Data
C0522A
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
C0522W
11-13
13
14
15
32
105
228
180
70
Ambient Air Temp., Degrees F.
80 90
13
14
15
16
16
16-18
18
19
34
120
270
210
70
Ambient Air Temp., Degrees F.
80 90
Cycle Time
(minutes)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
Suction Pressure
(PSIG)
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle weight: 4.5 to 5 lb.
13-15
15
16
16-17
23
85
235
115
15
16
17
17
14
14-15
15
16
36
110
245
200
October 2012 Page 77
Performance Data
C0722A
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle weight: 7.3 to 7.5 lb
13
13-14
14-15
15-16
30
92-94
240-250
150-155
70
Ambient Air Temp., Degrees F.
80 90
13-14
14
15
17
17
17-18
19-20
21-22
33
15-120
310-330
190-+200
October 2012 Page 78
Performance Data
C0330A
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
C0330W
9-10
10-11
11-12
12-13
28
110
200
150
70
Ambient Air Temp., Degrees F.
80 90
10-11
11-12
12-13
13-14
11-12
12-13
13-14
14-15
70
Ambient Air Temp., Degrees F.
80 90
Cycle Time
(minutes)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
Suction Pressure
(PSIG)
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle weight: 2.4 to 2.6 lb
8-10
10
11
11
33
95
235
130
10
11
11
11
10
10-11
11
12
35
110
235
150
October 2012 Page 79
Performance Data
C0530A
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
C0530W
13
14
15
16
33
95
230
130
70
Ambient Air Temp., Degrees F.
80 90
14
15
16
17
16
17
18
19
32
105
260
190
70
Ambient Air Temp., Degrees F.
80 90
Cycle Time
(minutes)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
Suction Pressure
(PSIG)
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle weight: 4.5 to 5 lb
10
11
12
13
33
100
235
140
12
13
13
13
12
13
13
14
34
110
235
150
October 2012 Page 80
Performance Data
C0630A
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
C0630W
9-10
10-11
11-12
12-13
21
85
200
160
70
Ambient Air Temp., Degrees F.
80 90
10-11
11-12
12-13
13-14
10-11
11-12
12-13
13-14
27
115
255
200
70
Ambient Air Temp., Degrees F.
80 90
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle weight: 4.5 to 5 lb
9
10
11
11
25
75
235
140
10
11
11
11
10
11
12
13
22
80
235
155
October 2012 Page 81
Performance Data
C0830A
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
C0830W
11
12
13
14
26
80
204
160
70
Ambient Air Temp., Degrees F.
80 90
12
13
14
15
13
14
15
16
30
100
260
195
70
Ambient Air Temp., Degrees F.
80 90
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle weight: 7 - 7.3 lb
11
12
13
14
30
85
235
175
12-13
13-14
13-14
14
13
13
14
15
31
90
237
178
October 2012 Page 82
Performance Data
C1030A
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
C1030W
9-10
10-11
11-12
10-13
26
80
210
165
70
Ambient Air Temp., Degrees F.
80 90
10-11
11-12
12-13
13-14
11-12
12-13
13
14-15
30
90
260
190
70
Ambient Air Temp., Degrees F.
80 90
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle weight: 7 - 7.3 lb
10
11
11-12
12
26
70
240
145
11
11-12
12
12-13
11
11
12
13
30
75
240
155
October 2012 Page 83
Performance Data
C1448A
70
Ambient Air Temp., Degrees F.
80 90
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
C1448W
12-13
13-14
14-15
15-16
38
100
250
150
13-14
14-15
15-16
16-17
14-15
15-16
16-17
17-18
40
100
270
160
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
13-14
14-15
15-16
15-16
36
105
235
170
70
Ambient Air Temp., Degrees F.
80 90
14-15
15-16
15-16
15-16
15-16
15-16
16-17
17-18
35
100
235
165
October 2012 Page 84
Performance Data
C1848A
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
C1848A
10-11
11-12
12-13
13-14
30
90
227
170
70
Ambient Air Temp., Degrees F.
80 90
11-12
12-13
13-14
14-15
12-13
13-14
14-15
15-16
32
100
285
195
70
Ambient Air Temp., Degrees F.
80 90
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
14 lb / cycle.
10-11
11-12
12-13
12-13
30
80
240
155
11-12
12-13
12-13
12-13
11-12
11-12
12-13
13-14
30
85
240
165
October 2012 Page 85
Performance Data
C2148W
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
Ice weight per cycle: 14.2
9-10
10-11
11-12
11-12
27
75
235
160
70
Ambient Air Temp., Degrees F.
80 90
10-11
11-12
11-12
11-12
11
11
12
13
27
75
240
160
October 2012 Page 86
Performance Data - Remotes
C0522R
-20
Condenser Intake Air Temp., Degrees F.
70 80 90 120
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle, 4.4 to 4.6 lb
10
Min 205
12-13
13-14
14-15
15-16
35
85
230
215
13-14
13-14
14-15
17-18
14
14-15
15-16
18-19
35
90
245
225
23
Peak at
360
October 2012 Page 87
Performance Data - Remotes
C0530R
-20
Condenser Intake Air Temp., Degrees F.
70 80 90 120
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
10
207 min
11-13
14
15
16
30
145
230
200
13-14
14-15
15-16
17-18
13-14
14
15-16
17-18
35
100
245
220
27
Peaks at
350
October 2012 Page 88
Performance Data - Remotes
C0630R
-20
Condenser Intake Air Temp., Degrees F.
70 80 90 120
Cycle Time
(minutes)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
7-8
Min 204
9
9-10
10-11
12
30
110
240
200
9
9-10
11-12
14
9-10
10
11
13-14
30
120
245
220
16-17
Peaks at
370
October 2012 Page 89
Performance Data - Remotes
C0830R
-20
Condenser Intake Air Temp., Degrees F.
70 80 90 120
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
8-9
Min at
205
9-11
11
12-13
13-14
32
100
240
200
10-11
11-12
12-13
15
12
13
13-14
16-17
32
110
245
210
21-22
Peak at
360
October 2012 Page 90
Performance Data - Remotes
C1030R
-20
Condenser Intake Air Temp., Degrees F.
70 80 90 120
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
9
Min 207
10-11
11
12-13
13-14
28
95
230
200
11
11-12
12-13
15-16
12-13
12-13
14
16-17
27
100
240
215
20-21
Peaks at
380
October 2012 Page 91
Performance Data - Remotes
C1448R
-20
Condenser Intake Air Temp., Degrees F.
70 80 90 +120
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle, 12 lb.
9
Min 207
11
11-12
13
14
40
100
240
150
11-12
11-12
13
15-16
14-15
14-15
16
18-19
40
125
270
200
22
Peak at
405
October 2012 Page 92
Performance Data - Remotes
C1848R
-20
Condenser Intake Air Temp., Degrees F.
70 80 90 120
Cycle Time
(minutes)
Water Temp
50
70
80
90
Suction
Pressure (PSIG)
End of Freeze
Harvest
Discharge
Pressure (PSIG)
End of Freeze
Harvest
9
Min 210
10-11
11-12
13
14
32
85
240
170
11-12
12
13-14
16
13
13
14-15
17
33
105
245
205
19
Peak at
370
Ice per cycle 14 lb.
August 2011 Page 93
Performance Data - Remotes
C2148R
-20
Condenser Intake Air Temp., Degrees F
70 80 90 120
Cycle Time
(minutes)
Suction Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water Temp
50
70
80
90
End of Freeze
Harvest
End of Freeze
Harvest
Ice per cycle, 14-15 lb.
9
Min 217
10
9-10
11-12
12-13
24
80
240
190
10
10
11
14
11
12
13
15-16
24
95
250
220
18-19
Peaks at
410
October 2012 Page 94
Wiring Diagrams
C0322, C0522, C0722, C0330, C0530, C0630, C0830, C1030 - Single Phase
October 2012 Page 95
Wiring Diagrams
C0530 C Air or Water Cooled 60 Hz
May 2011 Page 96
Wiring Diagram
C0830, C1030 - Three Phase
October 2012 Page 97
Wiring Diagram
C0522R, C0530R, C0630R, C0830R, C1030R - Single Phase
October 2012 Page 98
Wiring Diagrams
C0530R C
May 2011 Page 99
Wiring Diagram
C0522R, C0530R, C0630R, C0830R, C1030R Single Phase after 9/09
September 2009 Page 100
Wiring Diagram
C0522R, C0530R, C0630R, C0830R, C1030R - Three Phase
October 2006 Page 101
Wiring Diagram
C0522R, C0530R, C0630R, C0830R, C1030R Three Phase after 9/09
September 2009 Page 102
Wiring Diagram
C1448, C1848, C2148 Single Phase
October 2012 Page 103
Wiring Diagram
C1448, C1848, C2148 - three phase
March 2007 Page 104
Wiring Diagram
C1448R, C1848R, C2148R - single phase
October 2012 Page 105
8 7 6
J2
5 4 3 2 1
4 3 2
J6
1
Wiring Diagram
C1448R, C1848R. C2148R - three phase
October 2006 Page 106
Wiring Diagram
C1448R-63 230/380-420/50/3
June 2008 Page 107
Repair Procedures
Inlet Water Solenoid Valve
1 Disconnect electrical power
2 Shut off the water supply.
3 Remove front and left side panels.
4 Unplug wire from coil.
5 Disconnect water supply tube from the inlet of the valve.
Electrical Shock Hazard.
Disconnect electrical power before beginning.
6 Disconnect the water outlet tube.
7 Remove the two mounting screws holding the valve to the back panel.
8 Pull the valve forward and out of the machine.
Fan Blade or Motor
1 Push and release the Off button
2 Disconnect electrical power.
3 Remove front panel, sound shield and left side panel.
4 Unplug fan motor wire leads.
5 Remove fan motor mounting brackets from shroud. Note: Fastener size is 3/8” hex
6 Carefully remove fan motor and blade assembly from machine cabinet.
7 Loosen set screw, pull fan blade from motor shaft.
8 If the blade is the only part being changed, reverse to reassemble. Note: blade mounts purge to end of motor shaft.
9 If the motor will be changed, remove mounting brackets from fan motor. Note: Fastener size is ¼” hex.
10 Reverse to reassemble.
October 2012 Page 108
Harvest Assist Solenoid
1 Remove front panel.
2 Push and release Manual Harvest button
3 Disconnect electrical supply
Electrical Shock Hazard.
Disconnect electrical power before beginning.
4 Remove sound shield
5 Unplug wires from solenoid
6 Remove two screws and solenoid from cabinet
7 Reverse to reassemble.
Harvest Assist Solenoid
October 2012 Page 109
Repair Procedures
Ice thickness sensor
1 Push and release the Off switch.
2 Remove front and top panels.
3 Push and release the Harvest switch
4 Remove the evaporator cover.
5 Remove the sound shield.
6 Disconnect electrical power.
Electrical Shock Hazard.
Disconnect electrical power before beginning.
7 Open the control box.
8 Remove curtain.
9 Locate sensor, squeeze mounting legs together to release it from the mounting bracket.
10 Remove sensor, follow wire back to control box.
11 Disconnect from controller connection J10.
12 Remove sensor from machine.
13 Reverse to reassemble.
14 Set initial probe-to-evaporator-surface gap using a 7/32” drill bit as a gauge.
October 2012 Page 110
Repair Procedures
Capacitor (run)
1 Disconnect electrical power.
2 Remove front panel.
3
4
Open control box cover.
Remove right side of control box.
Electrical Shock Hazard.
Disconnect electrical power before beginning.
5 Remove metal barrier from control box
6 Remove screw holding strap to back of the control box.
7 Remove wires from capacitor
8 Connect wires to new capacitor, refer to wiring diagram as needed.
9 Reverse to reassemble.
Contactor
1 Disconnect electrical power.
2 Remove front panel.
3 Open control box cover.
4 Remove right side of control box.
5 Remove metal barrier from control box
6 Remove mounting screws holding contactor to control box.
7 Exchange wires from old controller to new. Refer to wiring diagram as needed.
8 Reverse to reassemble.
October 2012 Page 111
Repair Procedures
Controller
1 Disconnect electrical power.
Electrical Shock Hazard.
Disconnect electrical power before beginning.
2 Remove front panel.
3 Open control box door.
4 Unplug all wires from controller.
5 Remove screws holding controller to door
6 Push controller snaps down and pull controller from mounting bracket.
7 Before touching new controller, discharge any static electricity by touching the metal surface of the ice machine cabinet.
8 Rotate selector switch to the proper model number for the machine the controller is being installed on.
9 Install new controller on mounting bracket, secure with original screws.
10 Attach all wires removed.
11 Shut control box cover.
12 Switch on the electrical power.
Controller's Model Selector Switch
October 2012 Page 112
Repair Procedures
Curtain
1 Push and hold the Off button to shut the machine off.
2 Remove front panel.
3 Remove evaporator cover.
4 Push inside tab in to release front curtain pin from holder.
5 Pull curtain from machine.
6 Reverse to reassemble.
7 Push and release the ON button to restart the machine.
Curtain switch
1 Push and hold the Off button to shut the machine off.
2 Disconnect electrical power
Electrical Shock Hazard.
Disconnect electrical power before beginning.
3 Remove front panel.
4 Remove evaporator cover.
5 Remove sound shield
6 Open control box.
7 Locate curtain switch on evaporator mounting bracket. Pull switch from its snaps.
8 Dismount wires from sump cover and remove from J7 or J8 connector on control board.
9 Reverse to reassemble. Be sure wires are re-mounted to sump cover edge.
October 2012 Page 113
Repair Procedures
Purge valve
1 Push and hold the Off button to shut the machine off.
2 Disconnect electrical power.
3 Remove front panel.
4 Remove left side panel.
5 Unplug wires from valve coil.
Note: The coil can be removed from the valve body by rotating it 1/8 turn
CW. After removal of the coil the spring and plunger can be taken out.
6 Remove screws holding valve to mounting bracket.
7 Remove inlet and outlet hoses
8 Remove valve from cabinet.
9 Reverse to reassemble
1 Push and release the On button to restart the machine
Water level sensor
1 Push and hold the Off button until the machine shuts off.
2 Remove the front panel.
3 Remove the sound shield.
4 Locate water level sensor.
5 Squeeze the locking tabs together and pull the sensor up and out of the sump.
6 Unplug the electrical connection from the sensor.
7 Reverse to reassemble.
Electrical Shock Hazard.
Disconnect electrical power before beginning.
October 2012 Page 114
Repair Procedures
Water pump
1 Push and hold the Off button until the machine shuts off.
Electrical Shock Hazard.
Disconnect electrical power before beginning.
2 Remove the front panel.
3 Remove the sound shield.
4 Unplug the water pump
5 Rotate the pump CCW about 1/8 turn to release it.
6 Lift pump up and remove hose
7 Attach hose to new pump
8 Install in pump bracket.
9 Rotate CW about 1/8 turn to lock it in place.
10 Plug pump into harness
11 Return panels to their original positions and secure with the original screws.
12 Push and release the ON button to restart the machine.
October 2012 Page 115
Refrigeration Removal and Replacement Procedures
Evaporator
1 Remove front panel.
2 Remove evaporator cover.
3 Remove right side panel.
4 Remove top panel.
5 If the machine was in operation, push and release the Harvest button to warm up the evaporator.
6 Disconnect electrical power.
Electrical Shock Hazard.
Disconnect electrical power before beginning.
7 Remove harvest assist solenoid
8 Recover refrigerant.
9 Remove curtain
10 Remove water distributor
11 Release ice thickness sensor
12 Remove water distributor bracket from the top of the evaporator
13 Connect nitrogen bottle to discharge access port. Open both access valves.
14 Open nitrogen valve
15 Unsweat the inlet and outlet refrigerant tubes. Use caution when heating the tubing, do not damage the freezing compartment walls.
16 Shut nitrogen valve.
October 2012 Page 116
Refrigeration Removal and Replacement Procedures
17 Gain access to the right side of the unit. Remove mounting screws holding the evaporator to the freezing compartment wall. Note: fastener size is 5/16” hex.
18 Remove the evaporator from the ice machine.
19 Attach new evaporator to freezing compartment wall, but do not secure tightly at this time.
20 Install the harvest assist solenoid. Note location of ejector pin. Adjust position of the evaporator slightly to center the pin in the guide hole of the evaporator. When centered, tighten all evaporator fasteners.
21 Open nitrogen valve
22 Reconnect inlet and outlet tubes by brazing the copper tubes together.
23 Replace filter drier.
24 Shut access valves, remove nitrogen bottle.
25 Evacuate to at least 300 microns.
26 Weigh in the nameplate charge. Check for leaks.
27 Return ice thickness sensor bracket, ice thickness sensor, water distributor, curtain and evaporator cover to their original positions.
28 Reconnect electrical power.
29 Return sound shield and front panel to their original positions.
October 2012 Page 117
Refrigeration Removal and Replacement Procedures
Compressor
1 Remove front panel.
2 Remove sound shield
3 If the machine was in operation, push and release the Harvest button to shut it down.
Wait until the harvest cycle has ended so the evaporator has no ice on it.
4 Open the replacement compressor box. Check the compressor nameplate, be SURE that the replacement compressor is the correct one for the unit.
5 Disconnect electrical power.
Electrical Shock Hazard.
Disconnect electrical power before beginning.
6 Recover refrigerant.
7 Remove compressor terminal cover and disconnect electrical leads.
8 Remove all the mounting bolts.
9 Open both discharge and suction access valves
10 Connect nitrogen to discharge access valve.
11 Open nitrogen valve.
12 Unsweat the suction, discharge and process tubes.
13 Unsweat the drier from the liquid line. Remove it.
14 Shut the nitrogen valve.
15 Remove the compressor from the ice machine. Note: Some models may require the control box to be moved slightly to allow compressor replacement.
16 Immediately place new compressor in ice machine.
October 2012 Page 118
Refrigeration Removal and Replacement Procedures
17 Open nitrogen bottle and braze compressor suction, discharge and process joints together. Braze new drier into system.
18 Shut off nitrogen, shut access valves.
19 Evacuate to at least 300 microns.
20 Replace PTCR and run capacitor.
21 Weigh in the nameplate charge. Check for leaks.
22 Reconnect electrical leads.
23 Attach compressor terminal cover.
24 Reconnect electrical power.
25 Return sound shield and front panel to their original positions.
Note: If the compressor is being returned for warranty, braze the stubs shut and tag the compressor with the required information.
October 2012 Page 119
Refrigeration Removal and Replacement Procedures
Thermostatic Expansion Valve
1 Remove front panel.
2 Remove sound shield (when used)
3 If the machine was in operation, push and release the Harvest button to shut it down.
Wait until the harvest cycle has ended so the evaporator has no ice on it.
4 Disconnect electrical power.
5 Recover refrigerant.
6 Remove insulation covering expansion valve and bulb.
7 Remove strap securing bulb to suction line.
8 Open both discharge and suction access valves
9 Unsweat the expansion valve from the liquid line. Remove it.
10 Unsweat the drier from the liquid line. Remove it.
11 Connect nitrogen to discharge access valve.
12 Immediately place new valve in ice machine.
13 Open nitrogen bottle and braze expansion valve inlet and outlet joints together. Braze new drier into system.
14 Shut off nitrogen, shut access valves.
15 Evacuate to at least 300 microns.
16 Weigh in the nameplate charge. Check for leaks.
17 Attach bulb to suction line. Position at 4 or 8 o'clock on the tube. Secure tightly but do not crush the bulb with the strap.
18 Attach valve and bulb insulation.
19 Reconnect electrical power.
20 Return sound shield and front panel to their original positions.
October 2012 Page 120
Optional add-on control information
Vari-Smart™ Adjustable ice level option
The adjustable ice level control is an optional add-on system consisting of an control board, label and sensor.
The control board fits above the standard control and connects to it using connector J4. The sensor mounts to the base of the ice machine through a hole in the base.
The control has an adjustment knob. Rotating the knob CW lowers the maximum ice level that the ice machine will maintain in the bin or dispenser. When the ice level is at or above maximum for the setting, the bin full light on the ultrasonic board will be ON.
Ultrasonic Board and Cable
Back View of Ultrasonic Board
12
11
13
14
10
0
9
16
18
32
20
22
30
28
24
26
Ultrasonic ice level control settings
Ultrasonic control shown in its installed position, set at maximum fill.
0 = controlled by the curtain switch
October 2012 Page 121
Adjustable Ice Level System Information and Diagnosis
The ultrasonic sensor in the base of the ice machine is located to take advantage of the natural slope of the ice as it builds up in the bin. The numbers of the settings are from the sensor to the top of the ice pile directly under the sensor.
If the Vari-Smart system fails to shut off the machine and ice overfills the bin or dispenser, the curtain switch in the machine will switch the machine off, and will also restart the machine when ice is removed.
Note: Additional information on this option is included with the instructions provided with it.
October 2012 Page 122
Prodigy's Smart-Board™ - an Advanced Feature Control
An optional control is available that can provide users with more features. It is available either as a field installed option or as a data-logger that can be used by the service technician.
The kit number for the add on option is: KSBU
The kit number for the data logger version is: TPDL1 or TPDL2
The Smart-Board can be applied to most Prodigy models. It can be used:
• With the standard controller
• With the standard controller and the SmartLock device (KSL)
• With the standard controller and the Vari-Smart™ Ice Level Control (KVS)
• With the standard controller, and both the KSL and the KVS
Smart-Board abilities include:
• Ethernet connection
• USB connection to be used with Scotsman's Prodigy TechTool software
• Data Logging
• Data Display
The Smart-Board mounts to the control box door just below the main controller.
The cable connecting the two routes from the main controller Accessory connector to
J1 of the Smart-Board.
Vari-Smart
If the datalogger version is used, it plugs into the Accessory connector of the main controller.
If a SmartLock device is also connected, the SmartLock cable must be moved from the Accessory connector to the RLO connector of the SmartBoard.
Features and use instructions are included with either the KSB or the TPDL1.
Smart-Board
Cable Connects
Smart-Board
Back of Controller, with SmartBoard and
Vari-Smart Options installed.
October 2012 Page 123
Scroll Up
Button
Select
Button
Escape
Button
Display
Area
SmartBoard
™
Advanced Feature Control
34
SEL
ESC
ENTER
See Instructions for Available Features
Scroll
Down
Button
Enter
Button
USB
Connection
02-4293-01
Rev A.
Scroll Up: Changes the display to a menu item higher on the menu list or goes up one number on a setting
Scroll Down: Changes the display to a menu item lower on the menu list or goes down one number on a setting
Select Button: Use to make changes to settings.
Enter Button: Changes display to a sub menu list.
Escape Button: Changes display to the main menu.
The SmartBoard can display Alerts and Data.
Alerts:
• Service ice machine soon
• Slow water fill
• Long freeze cycle
• Long harvest cycle
• High discharge temperature
Note: Additional information on this option is included with the instructions provided with it.
October 2012 Page 124
Remote SmartLock (KSL)
The remote lock out feature can be added to any controller. The feature allows someone, using a special paging service and code to control the on and off operation of that ice machine.
When a controller is locked out, the machine will finish a cycle and then stop. Switching the power off and on, pushing any amount or combination of switches will not restart the machine.
It can only restart when it receives a clear signal from the remote lockout board.
The remote lock out consists of an antenna and cable. The antenna must be mounted onto the back of the ice machine cabinet. Two holes are provided for mounting. The connecting cable routes from the antenna through a hole in the back panel into the bottom of the control box.
Connect the antenna to the Accessory connector on the main board, or, if a SmartBoard has been installed on the machine, onto the RLO connector of the SmartBoard.
Due to the sensitive nature of this option, further information will only be supplied to registered users of a SmartLock device.
October 2012 Page 125
Selected Prodigy Cuber Suction Graphs
October 2012 Page 126
Selected Prodigy Cuber Suction Graphs
October 2012 Page 127
Selected Prodigy Cuber Suction Graphs
October 2012 Page 128
Wiring Diagram - 50 Hz
C0630R-6, C0830R-6, C1030R-6
October 2012 Page 129
Wiring Diagram - 50 Hz
C0530C 50 Hz
May 2011 Page 130
Index
B
Bridge Thickness . . . . . . . . . . . . . 7
C
Clear diagnostic code: . . . . . . . . . . . 40
Code Display . . . . . . . . . . . . . . . . 22
Component Indicator Light Table . . . . . . 34
Component Indicator Lights . . . . . . . . 23
Compressor . . . . . . . . . . . . . . . . 32
Contactor . . . . . . . . . . . . . . . . . . 32
Controller Connections: . . . . . . . . . . 37
Controller . . . . . . . . . . . . . . . . . . 33
Curtain Switch(es) . . . . . . . . . . . . . 33
D
Discharge temperature sensor.. . . . . . . 34
E
Electrical Components: . . . . . . . . . . . 21
Electrical Sequence - Air or Water Cooled . 27
Electrical Sequence - Remote Cooled . . . 29
Empty reservoir . . . . . . . . . . . . . . . 40
F
Fan Motor(s) . . . . . . . . . . . . . . . . 32
H
Harvest Assist Solenoid(s) . . . . . . . . . 32
High pressure cut out . . . . . . . . . . . . 32
Hot Gas Valve(s) . . . . . . . . . . . . . . 33
September 2006 Page 131
I
Ice Thickness Sensor. . . . . . . . . . . . 33
Inlet Water Solenoid Valve . . . . . . . . . 32
L
Limitations . . . . . . . . . . . . . . . . . 4
Liquid Line Valve . . . . . . . . . . . . . . 33
Lock / Unlock control:. . . . . . . . . . . . 40
M
Max freeze time – 45 minutes . . . . . . . 38
Max harvest time – 3 minutes . . . . . . . 38
Min freeze time – 6 minutes . . . . . . . . 38
Model Number . . . . . . . . . . . . . . . 2
P
Plumbing Requirements . . . . . . . . . . 5
Power Interruption . . . . . . . . . . . . . 39
Purge Valve . . . . . . . . . . . . . . . . 32
R
Recall diagnostic code: . . . . . . . . . . . 40
Refrigerant . . . . . . . . . . . . . . . . . 63
Remote Condenser Location . . . . . . . . 13
Remote Systems . . . . . . . . . . . . . . 35
Reset control:. . . . . . . . . . . . . . . . 40
S
Set purge level, . . . . . . . . . . . . . . 40
Setting Codes . . . . . . . . . . . . . . . 22
Start Test Mode: . . . . . . . . . . . . . . 40
T
Test Mode Sequence - Remote . . . . . . 56
Test Mode: . . . . . . . . . . . . . . . . . 40
Transformer . . . . . . . . . . . . . . . . 33
W
Warranty . . . . . . . . . . . . . . . . . . 4
Water Filters . . . . . . . . . . . . . . . . 5
Water Interruption . . . . . . . . . . . . . 39
Water Level Sensor . . . . . . . . . . . . 33
Water Level Sensor: . . . . . . . . . . . . 36
Water Pump . . . . . . . . . . . . . . . . 32
Water Purge . . . . . . . . . . . . . . . . 3
Water purge setting. . . . . . . . . . . . . 8
October 2012 Page 132
SCOTSMAN ICE SYSTEMS
775 Corporate Woods Parkway
Vernon Hills, IL 60061
800-533-6006 www.scotsman-ice.com
17-3141-01 Rev B.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project