50HG014-028
Single Package Rooftop Units
Electric Cooling with Electric Heat Option
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23
Step 1 — Provide Unit Support
. . . . . . . . . . . . . . . . . . . 1
• ROOF CURB
• ALTERNATE UNIT SUPPORT
Step 2 — Remove Shipping Rails
. . . . . . . . . . . . . . . . 3
Step 3 — Rig and Place Unit
. . . . . . . . . . . . . . . . . . . . . 3
• POSITIONING
• ROOF MOUNT
• INSTALLATION ONTO CURB
Step 4 — Field Fabricate Ductwork
. . . . . . . . . . . . . . . 8
Step 5 — Make Unit Duct Connections
. . . . . . . . . . . 8
Step 6 — Trap Condensate Drain
. . . . . . . . . . . . . . . . . 9
Step 7 — Make Electrical Connections
. . . . . . . . . . . 9
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
Step 8 — Install Outdoor-Air Hood
. . . . . . . . . . . . . . 20
Step 9 — Position Optional Power Exhaust or Barometric Relief Damper Hood
. . . . . . . . . . . . 22
Step 10 — Non-Fused Disconnect
. . . . . . . . . . . . . . . 22
Step 11 — Install All Accessories
. . . . . . . . . . . . . . . 23
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the units will automatically lock the compressor out of operation. Manual reset will be required to restart the compressor.
INSTALLATION
Step 1 — Provide Unit Support
ROOF CURB — Assemble or install accessory roof curb in accordance with instructions shipped with this accessory. See
Fig. 1. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb before unit is set in place. Curb must be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is
±
1
/
16
in. per linear ft in any direction. Refer to Accessory
Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering material.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions of replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket with the roof curb as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance.
ALTERNATE UNIT SUPPORT — When a curb cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Book 1
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
4
PC 111 Catalog No. 535-00092 Printed in U.S.A.
Form 50HG-7SI Pg 1 11-03 Replaces: 50HG-3SI
Tab 1b 6b
Fig. 1 — Roof Curb Details
2
Step 2 — Remove Shipping Rails —
Remove shipping rails prior to lowering unit onto roof curb. See Fig. 2. The rails are attached to the unit at both the return end and condenser end. Remove the screws from both ends of each rail. Be careful not to drop the rails onto any surface that could be damaged. Discard the rails. It is important to replace the screws into the unit to avoid any air or water leakage.
Do not allow the shipping rail to drop on the roof surface.
Damage to the roof surface may result.
Step 3 — Rig and Place Unit —
Inspect unit for transportation damage. See Table 1 for physical data. File any claim with transportation agency.
All panels must be in place when rigging. Unit is not designed for handling by fork truck. Damage to unit can result.
Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is ±
1
/
16
in. per linear ft in any direction. See
Fig. 3 for additional information. Unit rigging weight is shown in Fig. 3.
Four lifting holes are provided in the unit base rails as shown in Fig. 3. Refer to rigging instructions on unit.
POSITIONING — Maintain clearance, per Fig. 4, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
ROOF MOUNT — Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
INSTALLATION ONTO CURB — The 50HG units are designed to fit on either the accessory full perimeter curb or onto existing 48/50TJ,HJ or 48/50DP,DR curbs. In either case, correct placement of the unit onto the curb is critical to operating performance. To aid in correct positioning, 3 /
8
-in. diameter locating holes have been added to the unit base rails. When placing the unit, these holes should line up with the roof curb edge as shown in Fig. 5 and 6, to assure proper duct opening alignment. Select the alignment holes suited for the curb being used. For installation on the HJ/TJ/DP/DR curb use the alignment holes located approximately 20 in. from the end of the base rail on the return end of the unit. For placement on the HG curb, use the alignment holes located approximately 2-in. from the end of the base rail on the return end of the unit. See labels on the side of the unit for more details.
SHIPPING RAILS
Fig. 2 — Shipping Rail Removal
3
Fig. 3 — Rigging Details
4
Fig. 4 — Base Unit Dimensions
5
UNIT 50HG
VOLTAGE
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
50 SERIES (Cooling Only)
COMPRESSOR
Quantity
Number of Refrigerant Circuits
Oil (ounces) Ckt A...Ckt B...Ckt C
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb)
Circuit A
Circuit B
Circuit C
CONDENSER COIL
Rows...Fins/inch
Total Face area (sq. ft)
CONDENSER FAN
Nominal Cfm (Total, all fans)
Quantity...Diameter (in.)
Motor Hp...Rpm
Watts input (Total)
EVAPORATOR COIL
Rows...Fins/inch
Total Face area (sq. ft)
EVAPORATOR FAN
Quantity...Size
Type Drive
Nominal Cfm
Std Motor Hp
Alt Motor Hp
Motor Nominal Rpm
Std Maximum Continuous Bhp
Std Maximum Continuous Watts
Alt Maximum Continuous Bhp
Alt Maximum Continuous Watts
Motor Frame Size
Motor Frame Size
Fan Drive Rpm Range
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter
Motor Shaft Diameter (in.)
Motor Shaft Diameter (in.)
Belt, Quantity...Type...Length (in.)
Pulley center line distance (in.)
Speed change per full turn of moveable pulley flange (rpm)
Moveable pulley maximum (full turns from closed position)
Factory Pulley Setting
(turns from closed position)
Fan Shaft Diameter (in.)
Factory Speed Setting (rpm)
HIGH PRESSURE SWITCHES (psig)
Cutout
Reset (Auto)
OUTDOOR AIR INLET SCREENS
Quantity...Size (in.)
RETURN AIR FILTERS
Quantity...Size (in.)
LEGEND
Bhp —
Brake Horsepower
TXV —
Thermostatic Expansion Valve
Table 1 — Physical Data
Standard
Alternate
Std motor/Std drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Std drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Standard
Alternate
Std motor/Std drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Std drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
2...17
57.78
14,000
4...22
1
/
4
...1100
1400
3...15
23.33
2...15x11
Belt
5000
3.7
5
1725
4.25
3171
5.75
4290
56HZ
S184T
485-613
618-789
778-1021
1000-1227
Ball
1400
3.7-4.7
3.4-4.4
3.1-4.1
4.3-5.3
7
/
8
1 1 /
8
1...BX...51
1...A...45
1...BX...38
1...B...38
11.3-12.3
21
29
41
38
6
2...17
57.78
14,000
4...22
1
/
4
...1100
1400
3...15
23.33
2...15x11
Belt
5000
3
5
1725
3.45
2574
5.75
4290
56H
184T
472-619
609-778
778-1021
1000-1227
Ball
1400
3.1-4.1
3.4-4.4
3.1-4.1
4.3-5.3
7
/
8
1 1 /
8
1...BX...48
1...A...45
1...BX...38
1...B...38
11.3-12.3
25
28
41
38
6
208/230 and 460
12.5
014
575
12.5
2017
208/230 and 460
15
016
2111
575
15
2111
208/230 and 460
17.5
020
2139
575
17.5
2139 2017
2
2
2
2
3
3
3
3
3
3
3
3
72...72...NA
72...72...NA
68...68...68
68...68...68
68...68...72
68...68...72
R-22
TXV TXV TXV TXV TXV TXV
19.6
18.3
NA
19.6
18.3
NA
13.2
12.2
15.4
13.2
12.2
15.4
13.1
12.7
15.2
13.1
12.7
15.2
2...17
57.78
2...17
57.78
14,000
4...22
1
/
4
...1100
1400
14,000
4...22
1
/
4
...1100
1400
Face Split
3...15
23.33
3...15
23.33
2...15x11
Belt
6000
3.7
5
1725
4.25
3171
5.75
4290
56HZ
S184T
618-789
485-613
778-1021
1000-1227
Ball
1400
3.4-4.4
3.7-4.7
3.1-4.1
4.3-5.3
7
/
8
1 1 /
8
1...A...45
1...BX...51
1...BX...38
1...B...38
11.3-12.3
29
21
41
38
6
2...15x11
Belt
6000
3
5
1725
3.45
2574
5.75
4290
56H
184T
609-778
472-619
778-1021
1000-1227
Ball
1400
3.4-4.4
3.1-4.1
3.1-4.1
4.3-5.3
7
/
8
1 1 /
8
1...A...45
1...BX...48
1...BX...38
1...B...38
11.3-12.3
28
25
41
38
6
2...17
57.78
14,000
4...22
1
/
4
...1100
1400
3...15
23.33
2...15x11
Belt
7000
5
7
1
/
2
1725
5.75
4290
8.63
6438
S184T
S213T
658-808
794-974
949-1145
1126-1328
Ball
1400
4.3-5.3
4.3-5.3
5.4-6.6
5.5-6.5
1
1
/
8
1 3 /
8
1...BX...46
1...BX...42
1...BX...46
1...BX...42
10.0-12.2
25
30
33
34
6
2...17
57.78
14,000
4...22
1
/
4
...1100
1400
3...15
23.33
2...15x11
Belt
7000
5
7
1
/
2
1725
5.75
4290
8.63
6438
184T
S213T
658-808
794-974
949-1145
1126-1328
Ball
1400
4.3-5.3
4.3-5.3
5.4-6.6
5.5-6.5
1
1
/
8
1 3 /
8
1...BX...46
1...BX...42
1...BX...46
1...BX...42
10.0-12.2
25
30
33
34
6
1
3
3
/
16
549
426
320
3...20x25
9...16x25
1
3
3
/
16
546
426
320
3...20x25
9...16x25
1
3
3
/
16
704
426
320
3...20x25
9...16x25
1
3
3
/
16
694
426
320
3...20x25
9...16x25
1
3
3
/
16
733
426
320
3...20x25
9...16x25
1
3
3
/
16
733
426
320
3...20x25
9...16x25
6
UNIT 50HG
VOLTAGE
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
50 SERIES (Cooling Only)
COMPRESSOR
Quantity
Number of Refrigerant Circuits
Oil (ounces) Ckt A...Ckt B...Ckt C
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb)
Circuit A
Circuit B
Circuit C
CONDENSER COIL
Rows...Fins/inch
Total Face Area (sq. ft)
CONDENSER FAN
Nominal Cfm (Total, all fans)
Quantity...Diameter (in.)
Motor Hp...Rpm
Watts input (Total)
EVAPORATOR COIL
Rows...Fins/inch
Total Face Area (sq. ft)
EVAPORATOR FAN
Quantity...Size
Type Drive
Nominal Cfm
Std Motor Hp
Alt Motor Hp
Motor Nominal Rpm
Std Maximum Continuous Bhp
Std Maximum Continuous Watts
Alt Maximum Continuous Bhp
Alt Maximum Continuous Watts
Motor Frame Size
Motor Frame Size
Fan Drive Rpm Range
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter
Motor Shaft Diameter (in.)
Motor Shaft Diameter (in.)
Belt, Quantity...Type...Length (in.)
Table 1 — Physical Data (cont)
Pulley center line distance (in.)
Speed change per full turn of moveable pulley flange (rpm)
Moveable pulley maximum (full turns from closed position)
Factory Pulley Setting
(turns from closed position)
Fan Shaft Diameter (in.)
Factory Speed Setting (rpm)
HIGH PRESSURE SWITCHES (psig)
Cutout
Reset (Auto)
OUTDOOR AIR INLET SCREENS
Quantity...Size (in.)
RETURN AIR FILTERS
Quantity...Size (in.)
LEGEND
Bhp —
Brake Horsepower
TXV —
Thermostatic Expansion Valve
Standard
Alternate
Std motor/Std drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Std drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Standard
Alternate
Std motor/Std drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
Std motor/Std drive
Std motor/Alt drive
Alt motor/Std drive
Alt motor/Alt drive
208/230 and 460
20
024
2187
3
3
72...72...72
TXV
13.8
13.9
15.5
2...17
57.78
14,000
4...22
1
/
4
...1100
1400
4...15
23.33
2...15x11
Belt
8000
5
7
1
/
2
1725
5.75
4290
8.63
6438
S184T
S213T
658-808
794-974
949-1145
1126-1328
Ball
1400
4.3-5.3
4.3-5.3
5.4-6.6
5.5-6.5
1
1
/
8
1 3 /
8
1...BX...46
1...BX...42
1...BX...46
1...BX...42
10.0-12.2
25
30
33
34
6
575
20
2187
3
3
72...72...72
R-22
TXV
13.8
13.9
15.5
2...17
57.78
14,000
4...22
1
/
4
...1100
1400
Face Split
4...15
23.33
2...15x11
Belt
8000
5
7
1
/
2
1725
5.75
4290
8.63
6438
184T
S213T
658-808
794-974
949-1145
1126-1328
Ball
1400
4.3-5.3
4.3-5.3
5.4-6.6
5.5-6.5
1
1
/
8
1 3 /
8
1...BX...46
1...BX...42
1...BX...46
1...BX...42
10.0-12.2
25
30
33
34
6
1
3
3
/
16
733
426
320
3...20x25
9...16x25
1
3
3
/
16
733
426
320
3...20x25
9...16x25
028
ALL
25
2446
2
2
110...110...NA
TXV
23.9
21.5
NA
2...17
66.67
21,000
6...22
1
/
4
...1100
2100
4...15
27.22
2...15x11
Belt
10,000
7 1 /
2
10
1725
8.63
6438
11.50
8579
S213T
S215T
799-965
939-1152
945-1187
1152-1366
Ball
1400
5.4-6.6
4.2-5.2
4.2-5.2
5.2-6.2
1
3
/
8
1 3 /
8
1...BX...50
2...AX...38
2...BX...38
2...BX...38
9.6-12.0
28
36
40
36
6
1
3
3
/
16
882
426
320
3...20x25
9...20x25
7
ALIGNMENT
HOLE
(IN BASE RAIL)
ALIGNMENT
HOLE SHOULD
LINE UP WITH
ROOF CURB
EDGE FLANGE
EDGE FLANGE
Fig. 5 — Alignment Hole Details
HORIZONTAL APPLICATIONS — Horizontal units are shipped with outer panels that allow for side by side horizontal duct connections. If specified during ordering, the unit will be shipped with the vertical duct openings blocked off from the factory, ready for side supply installation. If the horizontal option was not specified at time of ordering the unit, a fieldinstalled accessory kit is required to convert the vertical unit into a horizontal supply configuration.
Installation of the duct block-off covers should be completed prior to placing the unit unless sufficient side clearance is available. A minimum of 66-in. is required between the unit and any obstruction to install the duct block-off covers. Side supply duct dimensions and locations are shown on Fig. 4.
Connect ductwork to horizontal duct flange connections on side of unit.
ALIGNMENT
HOLES FOR
HJ, TJ, DP, DR
CURB-BOTH
SIDES
RETURN
OPENING
SUPPLY
OPENING
ALIGNMENT
HOLES FOR HG
CURB-BOTH
SIDES
CURB
RETURN
OPENING
ROOF CURB
CURB
SUPPLY
OPENING
Fig. 6 — Alignment Hole Location
Step 4 — Field Fabricate Ductwork —
Secure all ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
Step 5 — Make Unit Duct Connections
VERTICAL CONFIGURATION — Unit is shipped for thruthe-bottom duct connections. Ductwork openings are shown in
Fig. 1 and 4. Duct connections for vertical supply and return configuration are shown in Fig. 7. Field fabricated concentric ductwork may be connected as shown in Fig. 8 and 9. The unit is designed to attach the ductwork to the roof curb. Do not attach duct directly to the unit basepans.
Unit basepans must be supported under the unit and around duct openings in order to prevent air leakage.
For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90-degree turn in the return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space.
Units with electric heat require a 1-in. clearance for the first
24 in. of ductwork. Outlet grilles must not lie directly below unit discharge.
NOTE: A 90-degree elbow must be provided in the supply ductwork to comply with UL (Underwriters’ Laboratories) codes for use with electric heat.
8
SEE
NOTE
SEE
NOTE
AIR
IN
AIR
OUT
NOTE: Do not drill in this area; damage to basepan may result in water leak.
Fig. 7 — Air Distribution —
Vertical Supply and Return
SEE
NOTE
ECONOMIZER
ECONOMIZER
SEE
NOTE
AIR OUT AIR IN
AIR OUT
NOTE: Do not drill in this area; damage to basepan may result in water leak.
Fig. 8 — Air Distribution — Concentric Duct
NOTE: Dimensions A, A
′
, B, and B
′ are obtained from field-supplied ceiling diffuser.
Shaded areas indicate block-off pans.
Fig. 9 — Concentric Duct Details
Step 6 — Trap Condensate Drain —
See Fig. 10 for drain location. One
3
/
4
-in. half coupling is provided outside unit evaporator section for condensate drain connection. A trap at least 4-in. deep must be used. See Fig. 11.
Step 7 — Make Electrical Connections
FIELD POWER SUPPLY — Unit is factory wired for voltage shown on unit nameplate.
When installing units, provide disconnect per NEC (National Electrical Code) of adequate size (MOCP [Maximum
Overcurrent protection] of unit is on the informative plate). See
Tables 2A and 2B. All field wiring must comply with NEC and local codes. Size wire based on MCA (Minimum Circuit
Amps) on the unit informative plate. See Fig. 12 for power wiring connections to the unit power terminal block and equipment grounds.
Route power and ground lines through control box end panel or unit basepan (see Fig. 4) to connections as shown on unit wiring diagram and Fig. 12.
The correct power phasing is critical to the operation of the scroll compressors. An incorrect phasing will result in an alarm being generated and compressor operation lockout.
Should this occur, power phase correction must be made to the incoming power.
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2%.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
FIELD CONTROL WIRING — Unit can be controlled with either a Carrier-approved accessory thermostat or a Carrierapproved space temperature sensor. Install thermostat according to the installation instructions included with accessory.
Locate thermostat assembly or space temperature sensor on a solid interior wall in the conditioned space to sense average temperature.
Route thermostat or space temperature sensor cable or equivalent single leads of colored wire from subbase terminals through conduit into unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 13 or 14.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C Minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.
Fig. 10 — Condensate Drain Details
The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (American National
Standards Institute/National Fire Protection Association).
Field wiring must conform to temperature limitations for type ‘‘T’’ wire. All field wiring must comply with NEC and local requirements.
NOTE: Dimensions in [] are in millimeters.
Fig. 11 — Condensate Drain Piping Details
9
Table 2A — Electrical Data (Units Without Optional Convenience Outlet)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
No. 2
OFM
No. 1 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
014
208/230
460
575
187
414
518
253
506
633
19.2
9.5
7.6
146.0
73.0
58.4
19.2
9.5
7.6
146.0
73.0
58.4
—
—
—
—
—
—
4.0
4.0
4.0
1
1
1
/
4
1.5
/
4
0.7
/
4
0.7
ELECTRIC kW
—
HEAT
FLA
—
12/16 33/ 38
19/25
38/50
—
15
25
50
—
16
25
48
52/ 60
104/120
—
18
30
60
—
15
24
46
Hp
IFM
FLA
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6 /9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
5.0
3.7
5.0
3.7
5.0
3.7
5.0
3.0
5.0
3.0
5.0
3.0
5.0
3.0
5.0
4.8
7.6
4.8
7.6
4.8
7.6
4.8
7.6
3.9
6.1
3.9
6.1
3.9
6.1
3.9
6.1
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
— —
FLA
(ea)
—
2 1.0
5.9
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
2 1.0
5.9
MCA MOCP*
60/ 59 70/ 70
72/ 71 90/ 80
66/ 64 80/ 80
78/ 76 90/ 90
60/ 60 70/ 70
72/ 74 90/ 80
66/ 67 80/ 80
78/ 81 90/ 90
78/ 87 80/ 90
93/102 100/110
— — — 86/ 94 90/100
2 1.0
5.9
101/109 110/110
— — — 143/132 150/150
2 1.0
5.9
158/147 175/150
— — — 151/139 175/150
2 1.0
5.9
166/154 175/175
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
29
35
32
38
29
36
35
40
40
45
35
40
35
43
38
45
62
70
65
73
26
32
24
31
26
34
66
74
70
77
24
30
32
40
44
51
47
55
35
45
40
50
70
80
70
80
30
35
30
35
30
35
80
80
80
80
30
35
40
45
45
60
50
60
DISCONNECT
SIZE
FLA
35
40
35
45
60
70
60
70
30
35
30
35
30
35
80
90
80
90
30
35
35
45
45
50
45
60
80/ 90
100/110
150/150
150/175
150/175
175/175
35
40
35
45
35
40
70/ 70
80/ 80
80/ 70
90/ 90
70/ 70
80/ 80
80/ 70
90/ 90
80/ 90
90/100
LEGEND
LEGEND AND NOTES FOR TABLES 2A AND 2B
FLA —
Full Load Amps
MCA —
Minimum Circuit Amps
HACR —
Heating, Air Conditioning and
MOCP —
Maximum Overcurrent Protection
IFM —
Refrigeration
Indoor (Evaporator) Fan Motor
LRA —
Locked Rotor Amps
NEC —
National Electrical Code
OFM
RLA
—
—
Outdoor (Condenser) Fan Motor
Rated Load Amps
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
*Fuse or HACR circuit breaker.
†208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable
2%.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
= 100 x max voltage deviation from average voltage average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired separately in the field.
4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v units, respectively.
5. The FLA load amps provided in the table for electric heaters are based on 208/240, 480 and 600 v.
6. MCA calculation for 50HG014-028 units with electric heaters over 50 kW is = 1.25 x
(IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA).
Average Voltage =
452 + 464 + 455
3
1371
=
3
= 457
10
Table 2A — Electrical Data (Units Without Optional Convenience Outlet) (cont)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
No. 2
OFM
No. 1 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
016
208/230
460
575
187
414
518
253
506
633
16.7
9.0
7.0
130.0
70.0
55.0
16.7
9.0
7.0
130.0
70.0
55.0
16.7
9.0
7.0
130.0
70.0
55.0
4.0
4.0
4.0
1
1
1
/
/
/
4
4
4
1.5
0.7
0.7
ELECTRIC kW
—
19/25
HEAT
FLA
—
52/ 60
38/50 104/120
56/75† 156/180
—
25
50
75
—
25
48
78
—
30
60
90
—
24
46
75
Hp
IFM
FLA
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
5.0
3.7
5.0
3.7
5.0
3.7
5.0
3.0
5.0
3.0
5.0
3.0
5.0
3.0
5.0
4.8
7.6
4.8
7.6
4.8
7.6
4.8
7.6
3.9
6.1
3.9
6.1
3.9
6.1
3.9
6.1
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
FLA
(ea)
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
MCA
71/ 70
83/ 82
77/ 75
89/ 87
78/ 87
93/102
86/ 94
2 1.0
5.9
101/109
— — — 143/132
2 1.0
5.9
158/147
— — — 151/139
2 1.0
5.9
166/154
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
MOCP*
71/ 70†
83/ 82†
77/ 75†
80/ 80†
90/ 90†
90/ 90†
89/ 87† 100/100†
37 45
43
40
50
45
46
44
51
47
55
50
45
60
50
60
80/ 80
90/ 90
90/ 90
100/100
80/ 90
100/110
90/100
110/110
150/150
175/150
175/150
175/175
35
43
38
45
62
70
65
73
80
88
83
90
66
74
70
77
96
104
100
107
29
36
32
38
35
45
40
50
70
80
70
80
90
100
90
100
80
80
80
80
110
110
110
125
35
40
35
40
DISCONNECT
SIZE
FLA
35
40
35
45
60
70
60
70
100
100
100
110
80
90
80
90
110
125
125
125
35
40
35
45
80/ 80†
100/ 90†
90/ 90†
100/100†
40
50
45
60
45
50
45
60
80/ 80
100/ 90
90/ 90
100/100
80/ 90
100/100
90/ 90
100/110
150/150
150/175
150/175
175/175
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
016
208/240
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
Min
187
Max
253
RLA
NA
LRA
NA
RLA
NA
LRA
NA
RLA
NA
LRA Qty Hp
FLA
(ea) kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP*
NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200
DISCONNECT
SIZE
FLA
200/225
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
016
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
208/230
VOLTAGE
RANGE
Min
187
Max
253
No. 1
RLA
16.7
LRA
130.0
COMPRESSOR
No. 2
RLA
16.7
LRA
130.0
No. 3
RLA
16.7
LRA
130.0
Qty Hp
4.0
OFM
1 /
4
FLA
(ea)
ELECTRIC kW
HEAT
FLA
1.5
56/75 156/180
Hp
IFM
FLA
3.7
10.6/ 9.6
5.0
16.7/15.2
POWER
EXHAUST
POWER
SUPPLY
Qty Hp
FLA
(ea)
MCA MOCP*
— 169/192 200/225 — —
2 1.0
5.9
184/207 200/225
— — — 177/199 200/225
2 1.0
5.9
192/214 200/225
See Legend and Notes on page 10.
DISCONNECT
SIZE
FLA
200/225
225/250
200/225
225/250
11
Table 2A — Electrical Data (Units Without Optional Convenience Outlet) (cont)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
No. 1
Min Max RLA LRA
COMPRESSOR
No. 2
RLA LRA
No. 3
RLA LRA
OFM
Qty Hp
FLA
(ea)
020
208/230
460
575
187
414
518
253
506
633
16.7
9.0
7.0
130.0
70.0
55.0
16.7
9.0
7.0
130.0
70.0
55.0
22.4
10.7
9.3
184.0
90.0
73.0
4.0
4.0
4.0
1
1
1
/
/
/
4
4
4
1.5
0.7
0.7
ELECTRIC kW
—
HEAT
19/25
FLA
—
52/ 60
38/50 104/120
56/75† 156/180
—
25
50
75
—
25
48
78
—
30
60
90
—
24
46
75
Hp
IFM
FLA
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
7.6
11.0
7.6
11.0
7.6
11.0
7.6
11.0
6.1
9.0
6.1
9.0
6.1
9.0
6.1
9.0
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
FLA
(ea)
— — —
2 1.0
5.9
— — —
MCA
84/ 83
96/ 94
92/ 89
2 1.0
5.9
104/101
— — — 86/ 94
2 1.0
5.9
101/109
— — — 95/103
2 1.0
5.9
110/117
— — — 151/139
2 1.0
5.9
166/154
— — — 160/148
2 1.0
5.9
175/162
MOCP*
— — —
2 1.0
5.9
— — —
84/ 83† 100/100†
96/ 94† 110/110†
92/ 89† 110/110†
2 1.0
5.9
104/101† 125/110†
— — — 42 50
2 1.0
3.1
— — —
48
45
50
50
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
51
47
55
51
59
60
50
60
60
60
100/100
110/110
110/110
125/110
100/100
110/110
110/110
125/125
175/150
175/175
175/150
200/175
38
45
41
49
65
73
69
77
83
90
86
94
70
77
74
82
100
107
104
112
35
41
37
44
40
50
45
50
70
80
70
80
90
100
100
100
80
80
80
90
110
125
125
125
40
50
45
50
DISCONNECT
SIZE
FLA
40
45
45
50
60
70
70
80
100
110
100
110
80
90
90
90
125
125
125
125
40
45
45
50
100/ 90†
110/110†
100/100†
125/110†
45
60
50
60
45
60
50
60
100/ 90
110/110
100/100
125/110
100/ 90
110/110
100/100
125/110
150/175
175/175
150/175
175/200
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
020
208/240
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
Min
187
Max
253
RLA
NA
LRA
NA
RLA
NA
LRA
NA
RLA
NA
LRA Qty Hp
FLA
(ea) kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP*
NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200
DISCONNECT
SIZE
FLA
200/225
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
020
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
208/230
VOLTAGE
RANGE
Min
187
Max
253
No. 1
RLA
16.7
LRA
130.0
COMPRESSOR
No. 2
RLA
16.7
LRA
130.0
No. 3
RLA
22.4
LRA
184.0
Qty Hp
4.0
OFM
1 /
4
FLA
(ea)
ELECTRIC kW
HEAT
FLA
1.5
56/75 156/180
Hp
IFM
FLA
5.0
16.7/15.2
7.5
24.2/22.0
POWER
EXHAUST
POWER
SUPPLY
Qty Hp
FLA
(ea)
MCA MOCP*
— 177/199 200/225 — —
2 1.0
5.9
192/214 200/225
— — — 186/208 200/225
2 1.0
5.9
201/222 225/225
See Legend and Notes on page 10.
DISCONNECT
SIZE
FLA
200/225
225/250
225/250
225/250
12
Table 2A — Electrical Data (Units Without Optional Convenience Outlet) (cont)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
No. 1
Min Max RLA LRA
COMPRESSOR
No. 2
RLA LRA
No. 3
RLA LRA
OFM
Qty Hp
FLA
(ea)
024
208/230
460
575
187
414
518
253
506
633
22.4
10.7
9.3
184.0
90.0
73.0
22.4
10.7
9.3
184.0
90.0
73.0
22.4
10.7
9.3
184.0
90.0
73.0
4.0
4.0
4.0
1
1
1
/
/
/
4
4
4
1.5
0.7
0.7
ELECTRIC kW
—
HEAT
19/25
FLA
—
52/ 60
38/50 104/120
56/75† 156/180
—
25
50
75
—
25
48
78
—
30
60
90
—
24
46
75
Hp
IFM
FLA
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
7.6
11.0
7.6
11.0
7.6
11.0
7.6
11.0
6.1
9.0
6.1
9.0
6.1
9.0
6.1
9.0
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
FLA
(ea)
MCA
— — — 96/ 94
2 1.0
5.9
107/106
— — — 104/101
2 1.0
5.9
115/113
— — — 96/ 94
2 1.0
5.9
107/109
— — — 104/103
2 1.0
5.9
115/117
— — — 151/139
2 1.0
5.9
166/154
— — — 160/148
2 1.0
5.9
175/162
MOCP*
— — — 96/ 94† 110/110†
2 1.0
5.9
107/106† 125/125†
— — — 104/101† 125/110†
2 1.0
5.9
115/113† 125/125†
— — — 45 50
2 1.0
3.1
— — —
51
49
60
50
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
55
47
55
51
59
60
50
60
60
60
110/110
125/125
125/110
125/125
110/110
125/125
125/110
125/125
175/150
175/175
175/150
200/175
39
45
42
49
65
73
69
77
83
90
86
94
70
77
74
82
100
107
104
112
39
45
42
48
45
50
50
50
70
80
70
80
90
100
100
100
80
80
80
90
110
125
125
125
45
50
50
50
DISCONNECT
SIZE
FLA
45
50
50
60
60
70
70
80
100
110
100
110
80
90
90
90
125
125
125
125
45
50
50
60
110/110†
125/125†
125/110†
150/125†
50
60
60
60
50
60
60
60
110/110
125/125
125/110
150/125
110/110
125/125
125/110
150/125
150/175
175/175
150/175
175/200
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
024
208/240
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
Min
187
Max
253
RLA
NA
LRA
NA
RLA
NA
LRA
NA
RLA
NA
LRA Qty Hp
FLA
(ea) kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP*
NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200
DISCONNECT
SIZE
FLA
200/225
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
024
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
208/230
VOLTAGE
RANGE
Min
187
Max
253
No. 1
RLA
22.4
LRA
184.0
COMPRESSOR
No. 2
RLA
22.4
LRA
184.0
No. 3
RLA
22.4
LRA
184.0
Qty Hp
4.0
OFM
1 /
4
FLA
(ea)
ELECTRIC kW
HEAT
FLA
1.5
56/75 156/180
Hp
5.0
16.7/15.2
7.5
IFM
FLA
24.2/22
POWER
EXHAUST
POWER
SUPPLY
Qty Hp
FLA
(ea)
MCA MOCP*
— 177/199 200/225 — —
2 1.0
5.9
192/214 200/225
— — — 186/208 200/225
2 1.0
5.9
201/222 225/225
See Legend and Notes on page 10.
DISCONNECT
SIZE
FLA
200/225
225/250
225/250
225/250
13
Table 2A — Electrical Data (Units Without Optional Convenience Outlet) (cont)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
No. 1
Min Max RLA LRA
COMPRESSOR
No. 2
RLA LRA
No. 3
OFM
RLA LRA Qty Hp
FLA
(ea)
028
208/230
460
575
187
414
518
253
506
633
47.1
19.6
15.8
245.0
125.0
100.0
47.1
19.6
15.8
245.0
125.0
100.0
—
—
—
—
—
—
6.0
6.0
6.0
1
1
1
/
/
/
4
4
4
1.5
0.7
0.7
ELECTRIC kW
—
19/25
HEAT
FLA
—
52/ 60
38/50 104/120
56/75† 156/180
—
25
50
75
—
25
48
78
—
30
60
90
—
24
46
75
Hp
7.5
10.0
30.8/28.0
7.5
24.2/22.0
10.0
30.8/28.0
7.5
10.0
30.8/28.0
7.5
24.2/22.0
10.0
30.8/28.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
IFM
FLA
24.2/22.0
24.2/22.0
11.0
14.0
11.0
14.0
11.0
14.0
11.0
14.0
9.0
11.0
9.0
11.0
9.0
11.0
9.0
11.0
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
FLA
(ea)
MCA
— — — 139/137
2 1.0
5.9
151/149
— — — 146/143
2 1.0
5.9
158/155
— — — 139/137
2 1.0
5.9
151/149
— — — 146/143
2 1.0
5.9
158/155
— — — 160/148
2 1.0
5.9
175/162
— — — 169/155
2 1.0
5.9
183/170
MOCP*
— — — 139/137† 175/175†
2 1.0
5.9
151/149† 175/175†
— — — 146/143† 175/175†
2 1.0
5.9
158/155† 200/200†
— — — 59 70
2 1.0
3.1
— — —
66
62
80
80
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
69
59
66
62
69
80
70
80
80
80
175/175
175/175
175/175
200/200
175/175
175/175
175/175
200/200
175/175
200/175
175/175
200/200
49
55
51
57
69
77
71
79
86
94
89
97
74
82
78
85
104
112
108
115
49
55
51
57
60
70
60
70
70
80
80
80
100
100
100
100
80
90
90
90
125
125
125
125
60
70
60
70
DISCONNECT
SIZE
FLA
60
60
60
70
70
80
70
80
100
110
100
110
90
90
90
100
125
125
125
150
60
60
60
70
150/150†
175/175†
175/175†
175/175†
70
70
70
80
70
70
70
80
150/150
175/175
175/175
175/175
150/150
175/175
175/175
175/175
150/175
175/200
175/175
175/200
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
028
208/240
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
Min
187
Max
253
RLA
NA
LRA
NA
RLA
NA
LRA
NA
RLA
NA
LRA Qty Hp
FLA
(ea) kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP*
NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200
DISCONNECT
SIZE
FLA
200/225
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
028
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
208/230
VOLTAGE
RANGE
Min
187
Max
253
No. 1
RLA
47.1
LRA
245.0
COMPRESSOR
No. 2
RLA
47.1
LRA
245.0
RLA
—
No. 3
LRA Qty Hp
— 6.0
OFM
1 /
4
FLA
(ea)
ELECTRIC kW
HEAT
FLA
1.5
56/75 156/180
Hp
IFM
FLA
7.5
24.2/22.0
10.0
30.8/28.0
POWER
EXHAUST
POWER
SUPPLY
Qty Hp
FLA
(ea)
MCA MOCP*
— 186/208 200/225 — —
2 1.0
5.9
201/222 225/225
— — — 195/215 225/225
2 1.0
5.9
209/230 225/250
See Legend and Notes on page 10.
DISCONNECT
SIZE
FLA
225/250
225/250
225/250
250/300
14
Table 2B — Electrical Data (Units With Optional Convenience Outlet)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
No. 2
OFM
No. 1 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
014
208/230
460
575
187
414
518
253
506
633
19.2
9.5
7.6
146.0
73.0
58.4
19.2
9.5
7.6
146.0
73.0
58.4
—
—
—
—
—
—
4.0
4.0
4.0
1
1
1
/
/
/
4
4
4
1.5
0.7
0.7
ELECTRIC kW
—
HEAT
12/16 33/ 38
19/25 52/ 60
38/50
—
15
25
50
—
16
25
48
FLA
—
104/120
—
18
30
60
—
15
24
46
Hp
IFM
FLA
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
5.0
3.7
5.0
3.7
5.0
3.7
5.0
3.0
5.0
3.0
5.0
3.0
5.0
3.0
5.0
4.8
7.6
4.8
7.6
4.8
7.6
4.8
7.6
3.9
6.1
3.9
6.1
3.9
6.1
3.9
6.1
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
FLA
(ea)
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
MCA
65/ 64
77/ 76
71/ 69
MOCP*
80/ 80
90/ 90
90/ 80
83/ 81 100/100
65/ 66 80/ 80
77/ 81 90/ 90
71/ 73 90/ 80
2 1.0
5.9
— — —
2 1.0
5.9
83/ 88 100/100
85/ 93 90/100
99/108 100/110
— — — 92/100 100/110
2 1.0
5.9
107/115 110/125
— — — 150/138 150/150
2 1.0
5.9
164/153 175/175
— — — 157/145 175/150
2 1.0
5.9
172/160 175/175
— — — 32 40
2 1.0
3.1
— — —
38
35
45
40
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
41
32
40
36
44
50
40
45
40
50
27
35
30
38
39
46
41
49
66
74
69
77
47
55
51
59
70
78
73
81
27
33
29
36
30
40
35
40
40
50
45
50
70
80
70
80
50
60
60
60
80
80
80
90
30
40
35
40
DISCONNECT
SIZE
FLA
30
35
30
35
35
40
35
45
60
70
60
70
45
50
45
60
80
90
80
90
30
35
30
35
150/150
150/175
150/175
175/175
35
40
35
45
35
40
35
45
70/ 70
80/ 80
80/ 70
90/ 90
70/ 70
80/ 80
80/ 70
90/ 90
80/ 90
90/100
80/ 90
100/110
See Legend and Notes on page 10.
15
Table 2B — Electrical Data (Units With Optional Convenience Outlet) (cont)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
No. 2
OFM
No. 1 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
016
208/230
460
575
187
414
518
253
506
633
16.7
9.0
7.0
130.0
70.0
55.0
16.7
9.0
7.0
130.0
70.0
55.0
16.7
9.0
7.0
130.0
70.0
55.0
4.0
4.0
4.0
1
1
1
/
/
/
4
4
4
1.5
0.7
0.7
ELECTRIC kW
—
19/25
HEAT
FLA
—
52/ 60
38/50 104/120
56/75† 156/180
—
25
50
75
—
25
48
78
—
30
60
90
—
24
46
75
Hp
IFM
FLA
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
10.6/ 9.6
5.0
16.7/15.2
3.7
5.0
3.7
5.0
3.7
5.0
3.7
5.0
3.0
5.0
3.0
5.0
3.0
5.0
3.0
5.0
4.8
7.6
4.8
7.6
4.8
7.6
4.8
7.6
3.9
6.1
3.9
6.1
3.9
6.1
3.9
6.1
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
FLA
(ea)
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
MCA
76/ 75
88/ 87
82/ 80
94/ 92
85/ 93
99/108
92/100
2 1.0
5.9
107/115
— — — 150/138
2 1.0
5.9
164/153
— — — 157/145
2 1.0
5.9
172/160
— — —
2 1.0
5.9
— — —
2 1.0
5.9
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
MOCP*
76/ 75† 90/ 90†
88/ 87† 100/100†
82/ 80† 90/ 90†
94/ 92† 110/100†
40 45
46
43
50
50
49
47
55
51
59
50
50
60
60
60
90/ 90
100/100
90/ 90
110/100
90/100
100/110
100/110
110/125
150/150
175/175
175/150
175/175
39
46
41
49
66
74
69
77
84
91
86
94
70
78
73
81
100
108
103
111
32
39
35
41
40
50
45
50
70
80
70
80
90
100
100
100
80
80
80
90
110
125
125
125
35
45
40
50
DISCONNECT
SIZE
FLA
35
40
35
45
60
70
60
70
100
100
100
110
80
90
80
90
110
125
125
125
35
40
35
45
80/ 80†
100/ 90†
90/ 90†
100/100†
40
50
45
60
45
50
45
60
80/ 80
100/ 90
90/ 90
100/100
80/ 90
100/100
90/ 90
100/110
150/150
150/175
150/175
175/175
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
016
208/240
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
Min
187
Max
253
RLA
NA
LRA
NA
RLA
NA
LRA
NA
RLA
NA
LRA Qty Hp
FLA
(ea) kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP*
NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200
DISCONNECT
SIZE
FLA
200/225
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
016
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
208/230
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
ELECTRIC kW
HEAT
FLA
187 253 16.7
130.0
16.7
130.0
16.7
130.0
4.0
1/4 1.5
56/75 156/180
Hp
IFM
FLA
3.7
10.6/ 9.6
5.0
16.7/15.2
POWER
EXHAUST
POWER
SUPPLY
Qty Hp
FLA
(ea)
MCA MOCP*
— 176/198 200/225 — —
2 1.0
5.9
190/213 200/225
— — — 183/205 200/225
2 1.0
5.9
198/220 200/225
See Legend and Notes on page 10.
DISCONNECT
SIZE
FLA
200/225
225/250
200/225
225/250
16
Table 2B — Electrical Data (Units With Optional Convenience Outlet) (cont)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
020
208/230
460
575
187
414
518
253
506
633
16.7
9.0
7.0
130.0
70.0
55.0
16.7
9.0
7.0
130.0
70.0
55.0
22.4
10.7
9.3
184.0
90.0
73.0
4.0
4.0
4.0
1
1
1
/
/
/
4
4
4
1.5
0.7
0.7
ELECTRIC kW
—
19/25
HEAT
FLA
—
52/ 60
38/50 104/120
56/75† 156/180
—
25
50
75
—
25
48
78
—
30
60
90
—
24
46
75
Hp
IFM
FLA
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
7.6
11.0
7.6
11.0
7.6
11.0
7.6
11.0
6.1
9.0
6.1
9.0
6.1
9.0
6.1
9.0
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
FLA
(ea)
MCA
— — — 89/ 88
2 1.0
5.9
101/ 99
— — — 97/ 94
2 1.0
5.9
109/106
— — — 92/100
2 1.0
5.9
107/115
— — — 102/109
2 1.0
5.9
116/124
— — — 157/145
2 1.0
5.9
172/160
— — — 167/154
2 1.0
5.9
181/169
MOCP*
— — — 89/ 88† 110/110†
2 1.0
5.9
101/ 99† 110/110†
— — — 97/ 94† 110/110†
2 1.0
5.9
109/106† 125/125†
— — — 45 50
2 1.0
3.1
— — —
51
48
60
50
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
54
51
59
55
63
60
60
60
60
70
110/110
110/110
110/110
125/125
110/110
110/125
110/110
125/125
175/150
175/175
175/175
200/175
41
49
45
53
69
77
73
80
86
94
90
98
73
81
78
85
103
111
108
115
38
44
40
47
45
50
45
60
70
80
80
90
100
100
100
100
80
90
80
90
125
125
125
125
45
50
45
50
DISCONNECT
SIZE
FLA
40
45
45
50
60
70
70
80
100
110
100
110
80
90
90
90
125
125
125
125
40
45
45
50
100/ 90†
110/110†
100/100†
125/110†
45
60
50
60
45
60
50
60
100/ 90
110/110
100/100
125/110
100/ 90
110/110
100/100
125/110
150/175
175/175
150/175
175/200
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
020
208/240
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
Min
187
Max
253
RLA
NA
LRA
NA
RLA
NA
LRA
NA
RLA
NA
LRA Qty Hp
FLA
(ea) kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP*
NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200
DISCONNECT
SIZE
FLA
200/225
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
020
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
208/230
VOLTAGE
RANGE
Min
187
Max
253
No. 1
RLA
16.7
LRA
130.0
COMPRESSOR
No. 2
RLA
16.7
LRA
130.0
No. 3
RLA
22.4
LRA
184.0
Qty Hp
4.0
OFM
1 /
4
FLA
(ea)
ELECTRIC kW
HEAT
FLA
1.5
56/75 156/180
Hp
IFM
FLA
5.0
16.7/15.2
7.5
24.2/22.0
POWER
EXHAUST
POWER
SUPPLY
Qty Hp
FLA
(ea)
MCA MOCP*
— 183/205 200/225 — —
2 1.0
5.9
198/220 200/225
— — — 193/214 200/225
2 1.0
5.9
207/229 225/250
See Legend and Notes on page 10.
DISCONNECT
SIZE
FLA
200/225
225/250
225/250
225/250
17
Table 2B — Electrical Data (Units With Optional Convenience Outlet) (cont)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
No. 1
Min Max RLA LRA
COMPRESSOR
No. 2
RLA LRA
No. 3
RLA LRA
OFM
Qty Hp
FLA
(ea)
024
208/230
460
575
187
414
518
253
506
633
22.4
10.7
9.3
184.0
90.0
73.0
22.4
10.7
9.3
184.0
90.0
73.0
22.4
10.7
9.3
184.0
90.0
73.0
4.0
4.0
4.0
1
1
1
/
/
/
4
4
4
1.5
0.7
0.7
ELECTRIC kW
—
HEAT
19/25
FLA
—
52/ 60
38/50 104/120
56/75† 156/180
—
25
50
75
—
25
48
78
—
30
60
90
—
24
46
75
Hp
IFM
FLA
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
16.7/15.2
7.5
24.2/22.0
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
5.0
7.5
7.6
11.0
7.6
11.0
7.6
11.0
7.6
11.0
6.1
9.0
6.1
9.0
6.1
9.0
6.1
9.0
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
FLA
(ea)
MCA
— — — 101/ 99
2 1.0
5.9
112/111
— — — 109/106
2 1.0
5.9
120/118
— — — 101/100
2 1.0
5.9
112/115
— — — 109/109
2 1.0
5.9
120/124
— — — 157/145
2 1.0
5.9
172/160
— — — 167/154
2 1.0
5.9
181/169
MOCP*
— — — 101/ 99† 110/110†
2 1.0
5.9
112/111† 125/125†
— — — 109/106† 125/125†
2 1.0
5.9
120/118† 125/125†
— — — 48 50
2 1.0
3.1
— — —
54
52
60
60
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
58
51
59
55
63
60
60
60
60
70
110/110
125/125
125/125
125/125
110/110
125/125
125/125
125/125
175/150
175/175
175/175
200/175
42
49
45
53
69
77
73
80
86
94
90
98
73
81
78
85
103
111
108
115
42
48
45
51
50
50
50
60
70
80
80
90
100
100
100
100
80
90
80
90
125
125
125
125
50
50
50
60
DISCONNECT
SIZE
FLA
45
50
50
60
60
70
70
80
100
110
100
110
80
90
90
90
125
125
125
125
45
50
50
60
110/110†
125/125†
125/110†
150/125†
50
60
60
60
50
60
60
60
110/110
125/125
125/110
150/125
110/110
125/125
125/110
150/125
150/175
175/175
150/175
175/200
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
024
208/240
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
Min
187
Max
253
RLA
NA
LRA
NA
RLA
NA
LRA
NA
RLA
NA
LRA Qty Hp
FLA
(ea) kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP*
NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200
DISCONNECT
SIZE
FLA
200/225
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
024
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
208/230
VOLTAGE
RANGE
Min
187
Max
253
No. 1
RLA
22.4
LRA
184.0
COMPRESSOR
No. 2
RLA
22.4
LRA
184.0
No. 3
RLA
22.4
LRA
184.0
Qty Hp
4.0
OFM
1 /
4
FLA
(ea)
ELECTRIC kW
HEAT
FLA
1.5
56/75 156/180
Hp
IFM
FLA
5.0
16.7/15.2
7.5
24.2/22.0
POWER
EXHAUST
POWER
SUPPLY
Qty Hp
FLA
(ea)
MCA MOCP*
— 183/205 200/225 — —
2 1.0
5.9
198/220 200/225
— — — 193/214 200/225
2 1.0
5.9
207/229 225/250
See Legend and Notes on page 10.
DISCONNECT
SIZE
FLA
200/225
225/250
225/250
225/250
18
Table 2B — Electrical Data (Units With Optional Convenience Outlet) (cont)
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
No. 1
Min Max RLA LRA
COMPRESSOR
No. 2
RLA LRA
No. 3
OFM
RLA LRA Qty Hp
FLA
(ea)
028
208/230
460
575
187
414
518
253
506
633
47.1
19.6
15.8
245.0
125.0
100.0
47.1
19.6
15.8
245.0
125.0
100.0
—
—
—
—
—
—
6.0
6.0
6.0
1
1
1
/
/
/
4
4
4
1.5
0.7
0.7
ELECTRIC kW
—
19/25
HEAT
FLA
—
52/ 60
38/50 104/120
56/75† 156/180
—
25
50
75
—
25
48
78
—
30
60
90
—
24
46
75
Hp
7.5
10.0
30.8/28.0
7.5
24.2/22.0
10.0
30.8/28.0
7.5
10.0
30.8/28.0
7.5
24.2/22.0
10.0
30.8/28.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
IFM
FLA
24.2/22.0
24.2/22.0
11.0
14.0
11.0
14.0
11.0
14.0
11.0
14.0
9.0
11.0
9.0
11.0
9.0
11.0
9.0
11.0
POWER
EXHAUST
POWER
SUPPLY
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
Qty Hp
FLA
(ea)
MCA
— — — 144/142
2 1.0
5.9
156/154
— — — 151/148
2 1.0
5.9
163/160
— — — 144/142
2 1.0
5.9
156/154
— — — 151/148
2 1.0
5.9
163/160
— — — 167/154
2 1.0
5.9
181/169
— — — 175/161
2 1.0
5.9
190/176
MOCP*
— — — 144/142† 175/175†
2 1.0
5.9
156/154† 200/200†
— — — 151/148† 175/175†
2 1.0
5.9
163/160† 200/200†
— — — 62 80
2 1.0
3.1
— — —
69
65
80
80
2 1.0
3.1
— — —
2 1.0
3.1
— — —
2 1.0
3.1
72
62
69
65
72
90
80
80
80
90
175/175
200/200
175/175
200/200
175/175
200/200
175/175
200/200
175/175
200/200
175/175
200/200
52
58
54
60
73
80
75
83
90
98
93
100
78
85
81
89
108
115
111
119
52
58
54
60
60
70
60
70
80
90
80
90
100
100
100
110
80
90
90
100
125
125
125
125
60
70
60
70
DISCONNECT
SIZE
FLA
60
60
60
70
70
80
70
80
100
110
100
110
90
90
90
100
125
125
125
150
60
60
60
70
150/150†
175/175†
175/175†
175/175†
70
70
70
80
70
70
70
80
150/150
175/175
175/175
175/175
150/150
175/175
175/175
175/175
150/175
175/200
175/175
175/200
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
028
208/240
VOLTAGE
RANGE
No. 1
COMPRESSOR
No. 2 No. 3
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
Min
187
Max
253
RLA
NA
LRA
NA
RLA
NA
LRA
NA
RLA
NA
LRA Qty Hp
FLA
(ea) kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP*
NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200
DISCONNECT
SIZE
FLA
200/225
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
UNIT
SIZE
50HG
028
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
208/230
VOLTAGE
RANGE
Min
187
Max
253
No. 1
RLA
47.1
LRA
245.0
COMPRESSOR
No. 2
RLA
47.1
LRA
245.0
RLA
—
No. 3
LRA Qty Hp
— 6.0
OFM
1 /
4
FLA
(ea)
ELECTRIC kW
HEAT
FLA
1.5
56/75 156/180
Hp
IFM
FLA
7.5
24.2/22.0
10.0
30.8/28.0
POWER
EXHAUST
POWER
SUPPLY
Qty Hp
FLA
(ea)
MCA MOCP*
— 193/214 200/225 — —
2 1.0
5.9
207/229 225/250
— — — 201/221 225/225
2 1.0
5.9
216/236 225/250
See Legend and Notes on page 10.
DISCONNECT
SIZE
FLA
225/250
225/250
225/250
250/300
19
LEGEND
EQUIP —
Equipment
GND —
Ground
NEC —
National Electrical Code
TB —
Terminal Board
NOTE: The maximum wire size for TB1 is 2/0.
Fig. 12 — Field Power Wiring Connections
THERMOSTAT ASSEMBLY
REMOVABLE JUMPER
RH RC Y1 Y2 W1 W2 G C
L
X
TB4
R
1
Y1
2
Y2
3
W1
4
W2
5
G
6
C
7
X
8
Fig. 13 — Field Control Thermostat Wiring
T-55 SPT
T1 T2 TH
T-56 SPT
COM SN
TB3 7 8 9
SPT —
Space Temperature Sensor
Fig. 14 — Field Control Space
Temperature Sensor Wiring
Set heat anticipator settings as shown in Table 3.
UNIT SIZE
50HG
014
016-028
Table 3 — Heat Anticipator Settings
ELECTRIC
HEAT (kW)
15
25
50
25
50
75
STAGE 1
(W1) ON
Voltage
STAGES 1 AND 2
(W1 and W2) ON
Voltage
208/240 480 600 208/240 480 600
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.4
0.4
0.4
0.4
0.2
0.4
0.4
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.8
0.4
0.8
0.8
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
Settings may be changed slightly to provide a greater degree of comfort for a particular installation.
Step 8 — Install Outdoor Air Hood —
Perform the following procedure to install the outdoor-air hood:
1. Remove blank panel from return end of unit (hood section). Save the screws. See Fig. 15 for shipping location of components.
2. Hood sides are fastened to sides of outdoor air opening.
Remove the hood sides and save the screws (3 each side).
20
3. Remove the bracket holding the bottom half of the hood in the shipping position. Remove the hood bottom half and filters (or manual dampers on units so equipped) from outdoor section.
NOTE: On units without economizers, the components are attached to the unit basepan. To access the components, remove the panel below the outdoor air intake section.
4. Remove inner filter track from shipping position in outdoor section. Position inner filter track so the track is facing outward from the unit. Install the filter track with
4 screws provided.
5. Apply seal strip (provided) to back flange of both hood sides where hood side connects to the unit back panel.
See Fig. 16.
6. Apply seal strip (provided) to top flange of both hood sides where hood sides connect to the hood top panels.
See Fig. 16.
7. Install hood sides to the back panels using the screws from
Step 2. The sloped flanges point outward. The drip edges of the side panels should face outward as well. The filter guides should face inward to hold the filters in place. See
Fig. 16.
8. Apply seal strip along the entire length of the bottom flange of the hood top. See Fig. 16.
9. Install the bottom part of the hood top using 4 screws provided. See Fig. 16.
10. Remove the packaging from filters (3) and install into the filter tracks. Slide the filters to the sides then place the last filter into the center of the filter track.
NOTE: For units with manual dampers, replace the end filters with the manual dampers. Install the filter in the center between the manual dampers.
11. Install the filter retainer track along the bottom edge of the outdoor air hood using 4 screws provided. See Fig. 16.
12. Install top section of the outdoor air hood using 9 screws provided. See Fig. 16. See Fig. 17 for a picture of the assembled outdoor air hood.
NOTE: For filter removal, remove the four screws holding the filter retainer. The filters can then be removed, cleaned, or replaced. Install the filters by reversing the procedure.
with manual dampers, the assembly process is similar to the outdoor air hood for units with economizers. There are two slide dampers shipped with the unit to allow for manual setting of the outside air volume. When assembling the hood, place one of the manual slide dampers in each of the end positions and the remaining filter in the center position. The manual dampers can then be moved to the appropriate position and then locked into place using the screws mounted in the adjustment slots. See
Fig. 18.
HOOD
SIDE
HOOD TOP
(BOTTOM HALF)
HOOD TOP
(TOP HALF)
HOOD
SIDE
RETURN AIR
SECTION
Fig. 15 — Outdoor-Air Hood Compartment
Shipping Location
SEAL
STRIP
LOCATION
BOTTOM
HOOD
SECTION
TOP HOOD
SECTION
HOOD
SIDE
ADD
SEAL
STRIP
ADD
SEAL
STRIP
INNER
FILTER
TRACK
ADD
SEAL
STRIP
ADD
SEAL
STRIP
FILTER
GUIDE
FILTER
RETAINER
MANUAL
DAMPER
(IF EQUIPPED)
FILTER
NOTE: Units with manual damper only use one filter.
Fig. 16 — Outdoor Air Hood Details
FILTER
GUIDE
HOOD
SIDE
UNIT
BACK
PANEL
Fig. 17 — Outdoor Air Hood Assembled
LOCKING SCREW
MOVEABLE DAMPER
AIR FILTER POSITION MOVEABLE DAMPER
Fig. 18 — Manual Damper Details
21
Step 9 — Position Optional Power Exhaust or
Barometric Relief Damper Hood —
The optional power exhaust or barometric relief dampers are shipped assembled and tilted back into the unit for shipping. Brackets and extra screws are shipped in shrink wrap around the dampers.
1. Remove 9 screws holding each damper assembly in place. See Fig. 19. Each damper assembly is secured with
3 screws on each side and 3 screws along the bottom.
Save screws.
Be careful when tilting blower assembly. Hoods and blowers are heavy and can cause injury if dropped.
2. Pivot the damper assembly outward until top edge of damper assembly rests against inside wall of unit.
3. Secure each damper assembly to unit with 6 screws across top (3 screws provided) and bottom (3 screws from Step 1) of damper.
4. With screws saved from Step 1, install brackets on each side of damper assembly. See Fig. 20.
5. Remove tape from damper blades.
Step 10 — Non-Fused Disconnect —
The handle for the factory-installed non-fused disconnect is shipped inside the unit to prevent the handle from damage during shipping.
Follow these steps to complete installation of the handle.
BE SURE POWER IS SHUT OFF TO THE UNIT FROM
THE BUILDING POWER SUPPLY.
1. Open the control box access door.
2. Remove the small cover plate located on the unit corner post near the control section.
3. Remove the inner control box cover. The handle and shaft are located in a plastic bag at the bottom of the control box.
4. Insert the square shaft into the disconnect with the pins vertical. On the 100 amp disconnect the shaft is keyed into the disconnect and can only be installed one way with the pins vertical.
5. Insert the handle through the corner post and onto the shaft with the handle positioned so that “OFF” is on top.
6. Rotate the handle to the “ON” position to lock the pins into the handle.
7. From the inside of the corner post, attach the handle mounting screws to the handle. Slide the shaft fully into the handle and tighten the set screws(s) on the disconnect to lock the shaft. Tighten the screws that attach the handle to the corner post.
8. Rotate the handle back to the “OFF” position.
9. Replace all panels and doors.
10. Restore power to unit.
Fig. 19 — Power Exhaust or Barometric Relief Damper Mounting Details
22
Fig. 20 — Bracket and Hood Positioning
Step 11 — Install All Accessories —
After all of the factory-installed options have been adjusted, install all field-installed accessories. Refer to the accessory installation instructions included with each accessory. Consult the Carrier
Price Pages for accessory package numbers for particular applications. The available field-installed accessories for the
Centurion units are:
• economizer
• power exhaust
• barometric relief damper
• 14-in. roof curb
• 24-in. roof curb
• electric heaters
• enthalpy control
• differential enthalpy control
• plugged filter indicator
• carbon dioxide detector
• smoke detector
• filter status switch
• fan status switch
• condenser hail guard
• horizontal duct accessory
• thermostats
• two-position damper
23
Copyright 2003 Carrier Corporation
Book 1
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
4 PC 111 Catalog No. 535-00092 Printed in U.S.A.
Form 50HG-7SI Pg 24 11-03 Replaces: 50HG-3SI