advertisement
UNVENTED (VENT-FREE) GAS LOG HEATER
OWNER’S OPERATION AND INSTALLATION MANUAL
24" THERMOSTAT MODELS CDR3924NT AND CDR3924PT
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built fireplace, or in an listed ventless firebox enclosure. It is design-certified for these installations in accordance with
ANSI Z21.11.2. Exception: Do not install this appliance in a factory-built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs. For unmarked factory-built fireplaces, contact fireplace manufacturer if unsure of this application.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 5 of this manual.
2
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
TABLE OF CONTENTS
Safety Information ............................................... 3
Cleaning and Maintenance ................................ 19
Local Codes ........................................................ 4
Product Identification ........................................... 5
Unpacking ........................................................... 5
Product Features ................................................. 5
Air For Combustion and Ventilation ..................... 5
Troubleshooting ................................................. 20
Optional Positioning of Thermostat Sensing Bulb .. 24
Specifications .................................................... 25
Replacement Parts ............................................ 25
Service Hints ..................................................... 25
Installation ........................................................... 8
Operating Heater ............................................... 16
Inspecting Burners ............................................ 18
Accessories ....................................................... 25
Illustrated Parts Breakdown and Parts List ....... 26
Warranty Information ...........................Back Cover
Technical Service .............................................. 18 www.desatech.com
113183-01B
SAFETY INFORMATION
WARNING: This product contains and/or generates chemicals known to the State of California to cause cancer or birth defects, or other reproductive harm.
WARNING: This appliance is for installation only in a solid-fuel burning fireplace or approved ventless firebox enclosure.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate, or service this heater.
Improper use of this heater can cause property damage and serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
WARNING: Do not allow fans to blow directly into the fireplace.
Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning:
Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get
fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Natural and Propane/LP Gas:
Natural and propane/LP gases are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade.
Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Heater base assembly becomes very hot when running heater.
Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shutdown. Allow surface to cool before touching.
Carefully supervise young children when they are in the room with heater.
WARNING: Any change to this heater or its controls can be dangerous.
You must operate this heater with a fireplace screen in place.
Make sure fireplace screen is closed before running heater.
WARNING: Do not use a blower insert, heat exchanger insert, or other accessory not approved for use with this heater.
113183-01B
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
www.desatech.com
3
SAFETY INFORMATION
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in your building
• immediately call your gas supplier from a neighborʼs phone. Follow the gas supplierʼs instructions
• if you cannot reach your gas supplier, call the fire department
4. This heater shall not be installed in a bedroom or bathroom, unless installed as a vented appliance.
5. Before installing in a solid fuel burning fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney flue may create and distribute soot within the house.
Inspect chimney flue and firebox for damage. If damaged, repair flue before operating heater.
6. Do not burn solid-fuel in a masonry or UL127 factory-built fireplace in which a vent-free room heater is installed.
7. If fireplace has glass doors, never operate this heater with glass doors closed. If you operate heater with doors closed, heat buildup inside fireplace will cause glass to burst. Make sure there are no obstructions across openings of fireplace.
8. To prevent the creation of soot, follow the instructions in Cleaning and Maintenance, page 19.
9. Before using furniture polish, wax, carpet cleaner, or similar products, turn heater off.
If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS shuts down the heater if enough fresh air is not available. See Air for Combustion and
Ventilation, page 5. If heater keeps shutting off, see Troubleshooting, page 20.
11. Do not run heater
• where flammable liquids or vapors are used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn paper or any other type of solid fuels.
13. Do not use heater if any part has been exposed to or under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
14. Do not operate heater if any log is broken. Do not operate heater if a log is chipped (dimesized or larger).
15. Turn heater off and let cool before servicing, installing, or repairing.Only a qualified service person should install, service, or repair heater.
16. Operating heater above elevations of 4,500 feet may cause pilot outage.
17. To prevent performance problems with propane/LP models, do not use propane/LP fuel tank of less than 100 lb. capacity.
18. Provide adequate clearances around air openings.
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI
Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Note:
Where listed vented decorative logs are required, thermostat operation is not permitted.
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the
Commonwealth of Massachusetts.
4 www.desatech.com
113183-01B
PRODUCT
IDENTIFICATION
Log Set
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
IGNITION SYSTEM
This heater has an electronic ignitor to light heater fuel supply.
AIR FOR COMBUSTION
AND VENTILATION
Ignitor
Burner
Control Knob
Grate
Base
Assembly
Figure 1 - Product Identification
UNPACKING
1. Remove logs and heater base assembly from carton. Note: Do not pick up heater base assembly by burners. This could damage heater.
Always handle base assembly by the sides of assembly.
2. Remove all protective packaging applied to logs and heater for shipment.
3. Check all items for any shipping damage. If damaged, promptly inform dealer where you bought heater.
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
CAUTION: Do not remove the data plates from the base assembly. The data plates contain important warranty and safety information.
Todayʼs homes are built more energy efficient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by both realistic flames and glowing coals. This heater is designed for ventfree operation with flue damper closed. It has been tested and approved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit the use of vent-free heaters.
113183-01B
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,
Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 5 through 7 will help you classify your space and provide adequate ventilation. www.desatech.com
5
AIR FOR COMBUSTION
AND VENTILATION
Continued
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where: a. walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10
-11
kg per pa-sec-m
2
) or less with openings gasketed or sealed and b. weather stripping has been added on openable windows and doors and c. caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of these three criteria, you must provide additional fresh air. See Ventilation Air From Outdoors, page 7.
If your home does not meet all of the three criteria above, proceed to Determining
Fresh-Air Flow For Heater Location.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54
defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour
(4.8 m
3
per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu/Hr (4.8 m
3
per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
6
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space:
Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example:
Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space can support)
Example:
2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater
Gas water heater*
Gas furnace
___________ Btu/Hr
___________ Btu/Hr
___________ Btu/Hr
Vented gas heater
Gas fireplace logs
Gas water heater
___________ Btu/Hr
___________ Btu/Hr
__________ Btu/Hr
Other gas appliances* + __________ Btu/Hr
Total = __________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/Hr
Vent-free heater + __________ Btu/Hr
79,000
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________Btu/Hr (maximum the space can support)
_________Btu/Hr (actual amount of Btu/Hr used)
Example:
51,200 Btu/Hr (maximum the space can support)
79,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows: www.desatech.com
113183-01B
AIR FOR COMBUSTION
AND VENTILATION
Continued
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 7.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section 5.3 or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation for required size of ventilation grills or ducts.
Outlet
Air
Inlet
Air
Ventilation
Grills
Into Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
12"
12"
Ventilation Grills
Into Adjoining Room,
Option 2
Figure 2 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
IMPORTANT:
Do not provide openings for inlet or outlet air into attic if attic has a thermostatcontrolled power vent. Heated air entering the attic will activate the power vent.
Outlet
Air
Inlet Air
Ventilated
Attic
Ventilated
Crawl Space
To Attic
To
Crawl
Space
Figure 3 - Ventila tion Air from Outdoors
113183-01B www.desatech.com
7
8
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat.
Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
WARNING: Before installing in a solid fuel burning fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney flue may create and distribute soot within the house.
Inspect chimney flue and firebox for damage. If damaged, repair flue before operating heater.
WARNING: Seal any fresh air vents or ash clean-out doors located on floor or wall of fireplace. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not seal chimney flue damper.
WARNING: Never install the heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 42 inches from the front, top, or sides of the firebox opening
• in high traffic areas
• in windy or drafty areas
CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities
(such as, but not limited to, tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT:
Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air
for Combustion and Ventilation, page 5.
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
WARNING: This appliance is equipped for (natural or propane/LP) gas. Field conversion is not permitted.
www.desatech.com
113183-01B
INSTALLATION
Continued
INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
WARNING: Maintain the minimum clearances. If possible, provide greater clearances from floor, ceiling, and adjoining wall.
LOG SIZING REQUIREMENTS
Log Minimum Firebox
Size Height Depth Front Rear *
Width Width
24" 17" 14" 28" 20 1 /
4
"
24"
Minimum Firebox with Blower
17" 14" 34" 22
3
/
8
"
* Measured at 14" depth.
Carefully follow the instructions below. This will ensure safe installation into a masonry, UL127-listed manufactured fireplace, or listed vent-free firebox.
Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabinet to any combustible material and wall should follow diagram in Figure 4.
Example:
The face of a mantel, bookshelf, etc. is made of combustible material and protrudes 3
1
/
2
" from the wall. This combustible material must be 4" from the side of the fireplace cabinet (see Figure 4).
Note:
When installing your gas logs into a manufactured firebox, follow firebox manufacturerʼs instructions for minimum clearances to combustible materials.
B. Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.
Example
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note:
If using a mantel proceed to If Using Mantel.
If not using a mantel, follow the information on this page.
You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick.
With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up. If noncombustible material is less than 12", you must install the fireplace hood accessory. See Figure 5 for minimum clearances.
If Using Mantel
You must have noncombustible material(s) above the fireplace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8 inches up.
If noncombustible material is less than 12", you must install the fireplace hood accessory. Even if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and Figures 6 and
7, page 10, for minimum clearances.
IMPORTANT:
If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open.
Noncombustible Requirements for
Material Distance (A) Safe Installation
12" or more
Between 8" and 12"
Less than 8"
Noncombustible material okay.
Install fireplace hood accessory (GA6050,
GA6052, or GA6053 see
Accessories, page 25).
Noncombustible material must be extended to at least 8". See Between 8"
and 12", above. If you cannot extend material, you must operate heater with flue damper open.
*
*Minimum 16 inches from Side Wall
Figure 4 - Minimum Clearance for
113183-01B
Combustible to Wall
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
www.desatech.com
9
INSTALLATION
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clearances listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required.
Follow minimum clearances shown in Figure 7 when using hood.
NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation.
Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
Minimum Non-
Combustible
Material
10"
8"
6"
2 1/2 "
Mantel Shelf
(A)
12" 18" 20" 22" 24"
All minimum distances are in inches
Log Set
All Models
Minimum Non-
Combustible
Material Height
Distances to
Underside of
Mantel
Underside of
Mantel Shelf
Top of Fireplace
Opening
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Mantel Shelf
12"
10"
8"
6"
2 1/2 "
Underside of Mantel
Shelf
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18"
All minimum distances are in inches
20"
Top of
Fireplace
Opening
Hood
(GA6050,
GA6052 or
GA6053)
Distances to
Underside of
Mantel
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:
• operate the logs only with the flue damper open
• raise the mantel to an acceptable height
• remove the mantel
Figure 7 - Minimum Mantel Clearances
When Using Hood
14"
Min.
Combustible
Material
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
FLOOR CLEARANCES
A. If installing appliance on the floor level, you must maintain the minimum distance of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combustible flooring (see
Figure 9).
10
Hearth
5"
Min.
Combustible
Material
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
www.desatech.com
113183-01B
INSTALLATION
Continued
INSTALLING HEATER BASE
ASSEMBLY
WARNING: You must secure this heater to fireplace floor. If not, heater will move when you adjust controls. Moving heater may cause a gas leak.
WARNING: If installing in a sunken fireplace, special care is needed. You must raise the fireplace floor to allow access to heater control panel. This will insure adequate air flow and guard against sooting and controls being damaged. Raise fireplace floor with noncombustible material.
Make sure material is secure.
2. Locate two masonry screws in hardware package.
3. Place heater base in fireplace.
4. Place logs in their proper position on heater base (see Installing Logs, page 14).
5. Center heater base and logs front-to-back and side-to-side in fireplace.
6. Carefully remove logs without moving heater base.
7. Mark screw locations through one hole on each side of the mounting bracket (see Figure
11). If installing in a brick-bottom fireplace, mark screw locations in mortar joint of bricks.
8. Remove heater base from fireplace. If installing optional control accessories, do so at this time. Follow all directions provided with accessory.
9. Drill holes at marked locations using 3/16" drill bit.
10. Attach base assembly to fireplace floor using two masonry screws (in hardware package).
CAUTION: Do not pick up heater base assembly by burners. This could damage heater.
Only handle base assembly by sides of base.
IMPORTANT:
Make sure the heater burners are level. If heater is not level, heater will not work properly. Avoid damage to thermostat bulb. Avoid nicks or sharp bends in thermostat bulb wire. Keep thermostat bulb in mounting bracket until ready to mount base to floor. See Optional Positioning
of Thermostat Sensing Bulb, page 24.
Installation Items Needed
• hardware package (provided with heater)
• approved flexible gas hose and fitting (not provided) (if allowed by local codes)
• sealant (resistant to propane/LP gas, not provided)
• electric drill with 3/16" drill bit (metal or masonry as applicable)
• flathead screwdriver
1. Connect fitting to base as shown in Figure 10.
Connect approved flexible gas hose to fitting in base (see Figure 10).
IMPORTANT:
Hold gas fitting with wrench when connecting flexible gas hose.
Flexible Gas
Hose (if allowed by local codes)
Fitting
Figure 10 - Attaching Flexible Gas Hose to Heater
Mounting
Flange
Masonry
Screw
Figure 11 - Attaching Base Assembly to
Fireplace Floor
113183-01B www.desatech.com
11
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 1/2" NPT (National
Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualified service person must connect heater to gas supply. Follow all local codes.
CAUTION: For propane/LP gas, never connect heater directly to the propane/LP supply.
This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane/LP supply.
Installation Items Needed
Before installing heater, make sure you have the items listed below.
• external regulator for propane/LP only (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 25.
For propane/LP only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 12. Pointing the vent down protects it from freezing rain or sleet.
WARNING: For natural gas, never connect heater to private (non-utility) gas wells.
This gas is commonly known as wellhead gas.
CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of
1/2" inside diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13, page 13).
IMPORTANT:
Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check building codes for any special requirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Propane/LP
Supply Tank
Vent
Pointing
Down
External
Regulator
Figure 12 - External Regulator With Vent
Pointing Down
12 www.desatech.com
113183-01B
INSTALLATION
Continued
CHECKING GAS CONNECTIONS
We recommend that you install a sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater.
Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.
CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.
WARNING: Never use an open flame to check for a leak.
Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.
Propane/LP - From
External Regulator
(11" W.C.** to 14" W.C.
Pressure)
Natural - From Gas
Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Tee Cap Pipe
Joint Nipple
Sediment Trap
3"
Minimum
CSA Design-
Certified Equipment
Shutoff Valve With
1/8" NPT Tap*
CAUTION: Make sure external regulator has been installed between propane/LP supply and heater. See guidelines under Connecting to Gas Supply, page 12.
Approved Flexible
Gas Hose (if allowed by local codes)
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Gas
Regulator
Figure 13 - Gas Connection
* Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See
Accessories
, page 25.
**Minimum inlet pressure for purpose of input adjustment.
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system.
Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.
4. Check all joints of gas supply piping system.
Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.
113183-01B www.desatech.com
13
INSTALLATION
Continued
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 14).
2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.
3. Check all joints from gas meter for natural or propane/LP supply to equipment shutoff valve
(see Figure 15 or 16). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 14).
2. Open main gas valve located on or near gas meter for natural gas or open propane/LP supply tank valve.
3. Make sure control knobs of heater are in the
OFF position.
4. Check all joints from equipment shutoff valve to thermostat gas valve (see Figure 15 or 16).
Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
Open
Equipment
Shutoff
Valve
6. Light heater (see Operating Heater, page 16).
Check all other internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to Appli-
ance, page 17).
Equipment
Shutoff Valve
Thermostat Gas Valve or
Control Valve Location
Gas Meter
Figure 16 - Checking Gas Joints (Natural
Gas Only)
INSTALLING LOGS
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury.
Closed
Figure 14 - Equipment Shutoff Valve
Equipment Shutoff Valve
Propane/LP
Supply Tank
Thermostat Gas
Valve or Control
Valve Location
CAUTION: After installation and periodically thereafter, check to ensure that no yellow flame comes in contact with any log.
With the heater set to HI, check to see if flames contact any log. If so, reposition logs according to the log installation instructions in this manual. Yellow flames contacting logs will create soot.
It is very important to install the logs exactly as instructed. Do not modify logs. Only use logs supplied with heater. Before installing logs, make sure log alignment screws are in place and straight.
14
Figure 15 - Checking Gas Joints
(Propane/LP Gas Only)
www.desatech.com
113183-01B
INSTALLATION
Continued
1. Place middle log (#1) onto log alignment screw located near the center of base, and in place over log support bracket as shown in
Figures 17 and 18.
2. Place front log (#2) onto base. Position log onto two alignment screws to the front of base
(see Figure 18).
3. Place left side log (#3) onto two log alignment screws on left side of base (see Figure 18).
4. Place right side log (#4) onto two log alignment screws on right side of base (see Figure 18).
5. Place rear log (#5) onto two alignment screws to the rear of base (see Figures 17 and 19).
6. Place crossover log (#6) onto log alignment pin on middle log (#1) and rear log (#5) (see
Figure 19).
Left Log
Rear Log
Log Support
Bracket
Front
Log
Middle
Log
Right
Log
Front Log
Figure 17 - Log Alignment Screws
Middle
Log #1
Left Log #3
Crossover
Log #6
Rear
Log #5
Figure 19 - Installing Rear Log #5 and
Crossover Log #6
ATTACHING GRATE TO BASE
ASSEMBLY
Locate the two slots in the front of the base assembly. Carefully slide the decorative grate into these slots (see Figure 20).
Front
Log #2
Grate
Slots in Base
Figure 20 - Attaching Grate to Base
Assembly
Right
Log #4
ADDING LAVA ROCK
Place lava rock around base of heater if desired.
Be sure not to cover the control knobs or air inlet openings on the front of heater.
Figure 18 - Installing Middle Log #1, Front
Log #2, Left Log #3 and Right Log #4
113183-01B www.desatech.com
15
OPERATING HEATER
FOR YOUR SAFETY READ
BEFORE LIGHTING
LIGHTING
INSTRUCTIONS
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighborʼs phone. Follow the gas supplierʼs instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, donʼt try to repair it, call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
WARNING:
• If fireplace has glass doors, never operate this heater with glass doors closed. If you operate heater with doors closed, heat buildup inside fireplace will cause glass to burst. Also if fireplace opening has vents at the bottom, you must open the vents before operating heater.
• You must operate this heater with a fireplace screen in place. Make sure fireplace screen is closed before running heater.
NOTICE: During initial operation of new heater, burning logs will give off a paper-burning smell.
Orange flame will also be present. Open damper or window to vent smell. This will only last a few hours.
Note:
Home owners generally prefer to operate their heater with the chimney damper closed. This will put all the heat into the room.
However, there may be times you will desire the full flames of the HI heat setting but will find the heat output excessive. You can open the chimney damper (if you have one) fully or partially to release some of the heat.
WARNING: Damper handle will be hot if heater has been running.
1. STOP! Read the safety information column 1.
2. Make sure equipment shutoff valve is fully open.
3. Turn control knob clockwise to the
OFF position.
4. Wait five (5) minutes to clear out any gas.
Then smell for gas, including near the floor.
If you smell gas, STOP! Follow “B” in the safety information, column 1. If you donʼt smell gas, go to the next step.
16 www.desatech.com
113183-01B
OPERATING HEATER
Continued
5. Turn control knob counterclockwise to the PILOT position. Press in control knob for five (5) seconds (see Figure 21).
Note:
You may be running this heater for the first time after hooking up to gas supply. If so, the control knob may need to be pressed in for 30 seconds or more. This will allow air to bleed from the gas system.
6. With thermostat control knob pressed in, press and release ignitor button. This will light pilot. The pilot is attached to the front burner. If needed, keep pressing ignitor button until pilot lights.
Note:
If pilot does not stay lit, contact a qualified service person or gas supplier for repairs. Until repairs are made, light pilot with match. To light pilot with match, see
Manual Lighting Procedure.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
• If control knob does not pop out when released, contact a qualified service person or gas supplier for repairs.
Note:
If pilot goes out, repeat steps 3 through 7. This heater has a safety interlock system. Wait one (1) minute for system to reset before lighting pilot again.
8. Turn control knob counterclockwise to desired heating level. The front burner should light. Set control knob to any heat level between HI and LO.
9. To light the rear yellow flame burner, push in and turn rear burner control knob counterclockwise to the ON position.
CAUTION: Do not try to adjust heating levels by using the equipment shutoff valve.
Ignitor Button
Control Knob Rear Burner
Control Knob
Pilot Burner
Ignitor
Electrode
Pilot Burner
Thermocouple
Thermocouple
Figure 22 - Pilot
(Propane/LP)
Figure 23 - Pilot
(Natural)
TO TURN OFF GAS
TO APPLIANCE
Shutting Off Heater
1. Turn control knob clockwise to the
OFF position.
2. Turn rear burner control knob clockwise
to the OFF position.
Shutting Off Burners Only (pilot stays lit)
1. Turn control knob clockwise to the
PILOT position.
2. Turn rear burner control knob clockwise
to the OFF position.
THERMOSTAT CONTROL
OPERATION
The thermostat control knob can be set to any comfort level between HI and LO. The thermostat will gradually modulate the heat output and flame height from higher to lower settings, or pilot, in order to maintain the comfort level you select. The ideal comfort setting will vary by household depending upon the amount of space to be heated, the output of the central heating system, etc.
Note:
Selecting the HI setting with the control knob will cause the burner to remain fully on, without modulating down in most cases.
MANUAL LIGHTING
PROCEDURE
1. Follow steps 1 through 5 under Lighting
Instructions, starting on page 16.
2. Depress control knob and light pilot with match.
3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Now follow steps 8 and 9 under Lighting Instructions, column 1.
Figure 21 - Control Knob(s) and Ignitor
Button Locations
113183-01B www.desatech.com
17
INSPECTING BURNERS
Check pilot flame pattern and burner flame patterns often.
PILOT FLAME PATTERN
Figure 24 shows a correct pilot flame pattern.
Figure 25 shows an incorrect pilot flame pattern.
The incorrect pilot flame is not touching the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down.
If pilot flame pattern is incorrect, as shown in
Figure 25
• turn heater off (see To Turn Off Gas to Appli-
ance, page 17)
• see Troubleshooting, pages 20
Note:
The pilot flame on natural gas units will have a slight curve, but the flame should be blue and have no yellow or orange color.
Pilot Burner Thermocouple Pilot Burner
WARNING: If yellow tipping occurs, your heater could produce increased levels of carbon monoxide. If burner flame patterns show yellow tipping, follow instructions below. Yellow flame on rear burner is normal.
NOTICE: Do not mistake orange flames with yellow tipping. Dirt or other fine particles are burned by heater, causing brief patches of orange flame.
If burner flame patterns are incorrect, as shown in Figure 27
• turn heater off (see To Turn Off Gas to Appli-
ance, page 17)
• see Troubleshooting, page 20
(Natural Gas)
(Propane/LP Gas)
Figure 24 - Correct Pilot Flame Pattern
(Your pilot may vary from pilots shown)
Pilot Burner
Pilot Burner
Thermocouple
Figure 26 - Correct Burner Flame
Patterns
Yellow Tipping At
Top of Blue Flame
(Natural Gas)
(Propane/LP Gas)
Figure 25 - Incorrect Pilot Flame Pattern
(Your pilot may vary from pilots shown)
BURNER FLAME PATTERNS
Figure 26 shows correct burner flame patterns.
Figure 27 shows incorrect burner flame patterns.
The incorrect burner flame patterns show yellow tipping at top of blue flame.
Figure 27 - Incorrect Burner Flame
Patterns
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, contact DESA
Heating Productsʼ Technical Service Department at
1-866-672-6040. When calling, please have your model and serial numbers of your heater ready.
You can also visit DESA Heating Productsʼ technical services web site at www.desatech.com.
18 www.desatech.com
113183-01B
CLEANING AND
MAINTENANCE
WARNING: Turn off heater and let cool before cleaning.
CAUTION: You must keep control areas, burners, and circulating air passageways of heater clean.
Inspect these areas of heater before each use. Have heater inspected yearly by a qualified service person. Heater may need more frequent cleaning due to excessive lint from carpeting, pet hair, bedding material, etc.
particles of dust, dirt, lint, or pet hair with a soft cloth or vacuum cleaner nozzle.
5. Blow air into the primary air holes on the injector holders.
6. In case any large clumps of dust have now been pushed into the burner repeat steps 3 and 4.
Clean the pilot assembly also. A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly.
There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Figure 30). With the unit off, lightly blow air through the air inlet hole. The access hole for propane/LP pilot is on the front of the burner carriange as shown in Figure 30. The access hole for natural pilot is behind the pilot bracket on the top of burner carriage (see Figure 30). You may blow through a drinking straw if compressed air is not available.
Injector Holder
Burner
Tube
WARNING: Failure to keep the primary air opening(s) of the burner(s) clean may result in sooting and property damage.
Primary Air
Inlet Holes
BURNER INJECTOR HOLDERS AND
PILOT AIR INLET HOLES
The primary air inlet holes allow the proper amount of air to mix with the gas. This provides a clean burning flame. Keep these holes clear of dust, dirt, lint, and pet hair. Clean these air inlet holes prior to each heating season. Blocked air holes will create soot. We recommend that you clean the unit every three months during operation and have heater inspected yearly by a qualified service person.
We also recommend that you keep the burner tubes and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using compressed air no greater than 30 PSI. Your local computer store, hardware store, or home center may carry compressed air in a can. You can use a vacuum cleaner in the blow position. If using compressed air in a can, please follow the directions on the can. If you don't follow directions on the can, you could damage the pilot assembly.
1. Shut off the unit, including the pilot. Allow the unit to cool for at least thirty minutes.
2. Inspect burners, pilot, and primary air inlet holes on injector holder for dust and dirt (see
Figures 28 or 29).
3. Blow air through the ports/slots and holes in the burners.
4. Check the injector holders located at the end of the burner tubes again. Remove any large
113183-01B
Figure 28 - Injector Holder On Outlet
Burner Tube - Rear Burner
Ports/Slots
Primary Air Inlet Holes
Figure 29 - Injector Holder On Front
Outlet Burner Tube
Pilot
Bracket
Access
Hole for
Pilot
Assembly
Cleaning
Natural
Pilot
Access
Hole for
Cleaning
Propane/LP
Pilot
Injector Holder
Pilot Air Inlet Hole
Figure 30 - Cleaning Pilot Air Inlet Hole
(Your pilot may vary from pilots shown)
LOGS
• If you remove logs for cleaning, refer to Install-
ing Logs, page 14, to properly replace logs.
• Replace log(s) if broken or chipped (dime-sized or larger).
www.desatech.com
19
TROUBLESHOOTING
WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.
CAUTION: Never use a wire, needle, or similar object to clean
ODS/pilot. This can damage ODS/pilot unit.
Note:
All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
When ignitor button is pressed, there is no spark at ODS/pilot
POSSIBLE CAUSE
1. Ignitor electrode not connected to ignitor cable
2. Ignitor cable pinched or wet
3. Broken ignitor cable
4. Bad ignitor
5. Ignitor electrode positioned wrong
6. Ignitor electrode broken
7. Battery not installed, battery power low, or battery not installed correctly
REMEDY
1. Reconnect ignitor cable
2. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry
3. Replace ignitor cable
4. Replace ignitor
5. Replace pilot assembly
6. Replace pilot assembly
7. Install new alkaline battery in electronic ignitor. Verify battery is installed correctly
When ignitor button is pressed, there is spark at ODS/pilot but no ignition
1. Gas supply turned off or equipment shutoff valve closed
2. Control knob not in PILOT position
3. Control knob not pressed in while in PILOT position
4. Air in gas lines when installed
5. Depleted gas supply (propane/LP only)
6. ODS/pilot is clogged
7. Gas regulator setting is not correct
1. Turn on gas supply or open equipment shutoff valve
2. Turn control knob to PILOT position
3. Press in control knob while in
PILOT position
4. Continue holding down control knob. Repeat igniting operation until air is removed
5. Contact local propane/LP gas company
6. Clean ODS/pilot (see Cleaning
and Maintenance, page 19) or replace ODS/pilot assembly
7. Replace gas regulator
20 www.desatech.com
113183-01B
OBSERVED PROBLEM
ODS/pilot lights but flame goes out when control knob is released
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Control knob not fully pressed in
2. Control knob not pressed in long enough
3. Safety interlock system has been triggered
4. Equipment shutoff valve not fully open
5. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This problem could be caused by one or both of the following:
A) Low gas pressure
B) Dirty or partially clogged
ODS/pilot
6. Thermocouple connection loose at control valve
7. Thermocouple damaged
8. Control valve damaged
REMEDY
1. Press in control knob fully
2. After ODS/pilot lights, keep control knob pressed in 30 seconds
3. Wait one minute for safety interlock system to reset.
Repeat ignition operation
4. Fully open equipment shutoff valve
5. A) Contact local natural or propane/LP gas company
B) Clean ODS/pilot (see
Cleaning and Maintenance
, page 19) or replace ODS/pilot assembly
6. Hand tighten until snug, then tighten 1/4 turn more
7. Replace pilot assembly
8. Replace control valve
One or more burners do not light after ODS/pilot is lit
Delayed ignition of one or more burners
1. Inlet gas pressure is too low
2. Burner orifice(s) clogged
3. Mislocated crossover tube
1. Manifold pressure is too low
2. Burner orifice(s) clogged
3. Mislocated crossover tube
Burner backfiring during combustion
1. Burner orifice is clogged or damaged
2. Damaged burner
3. Gas regulator defective
Yellow flame in burner during burner combustion
1. Not enough air
2. Gas regulator defective
1. Contact local natural or propane/LP gas company
2. Clean burner(s) (see Cleaning
and Maintenance, page 19) or replace burner orifice(s)
3. Contact qualified service person
1. Contact local natural or propane/LP gas company
2. Clean burner(s) (see Cleaning
and Maintenance, page 19) or replace burner orifice(s)
3. Contact qualified service person
1. Clean burner (see Cleaning
and Maintenance, page 19) or replace burner orifice
2. Replace damaged burner
3. Replace gas regulator
1. Check burner(s) for dirt and debris. If found, clean burner(s) (see Cleaning and
Maintenance, page 19)
2. Replace gas regulator
113183-01B www.desatech.com
21
OBSERVED PROBLEM
Slight smoke or odor during initial operation
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Residues from manufacturing processes and logs curing
REMEDY
1. Problem will stop after a few hours of operation
Heater produces a whistling noise when burners are lit
1. Turning control knob to HI position when burners are cold
2. Air in gas line
3. Air passageways on heater blocked
4. Dirty or partially clogged burner orifice(s)
1. Turn control knob to LO position and let warm up for a minute
2. Operate burners until air is removed from line. Have gas line checked by local natural or propane/LP gas company
3. Observe minimum installation clearances (see pages 8 through 10)
4. Clean burners (see Cleaning
and Maintenance, page 19)
1. Turn heater off when using furniture polish, wax, carpet cleaners, or similar products
White powder residue forming within burner box or on adjacent walls or furniture
1. When heated, vapors from furniture polish, wax, carpet cleaners, etc. may turn into white powder residue
Moisture/condensation noticed on windows
1. Not enough combustion/ventilation air
Heater produces a clicking/ticking noise just after burners are lit or shut off
1. Metal expanding while heating or contracting while cooling
1. Refer to Air for Combustion
and Ventilation requirements
(page 5)
1. This is common with most heaters. If noise is excessive, contact qualified service person
22 www.desatech.com
113183-01B
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
IMPORTANT:
Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM
Heater produces unwanted odors
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in OFF position
POSSIBLE CAUSE
1. Heater burning vapors from paint, hair spray, glues, cleaners, chemicals, new carpet, etc. (See IMPORTANT statement above)
2. Low fuel supply (propane/LP only)
3. Gas leak. See Warning
statement at top of page
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Gas leak. See Warning
statement at top of page
2. Control valve defective
REMEDY
1. Open window to ventilate room. Stop using odor causing products while heater is running
2. Refill supply tank (propane/
LP only)
3. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 13)
1. Open window and/or door for ventilation
2. Contact local natural or propane/LP gas company
3. Clean ODS/pilot (see Cleaning
and Maintenance, page 19)
1. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 13)
2. Replace control valve
Gas odor during combustion 1. Foreign matter between control valve and burner
2. Gas leak. See See Warn-
ing statement at top of page
Log set cycles to pilot, but room temperature drops to a lower than ideal level before log set comes back on
1. Thermostat sensing bulb needs to be repositioned
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 13)
1. Reposition thermostat sensing bulb (see Optional Position-
ing of Thermostat Sensing
Bulb, page 24)
113183-01B www.desatech.com
23
OPTIONAL POSITIONING
OF THERMOSTAT
SENSING BULB
FOR MASONRY AND FACTORY-
BUILT METAL FIREPLACE
If your log set cycles to pilot, but the room temperature drops to a lower than ideal comfort level before the log set comes back on, you may want to reposition the thermostat sensing bulb.
The thermostat sensing bulb is located on the left side of the base assembly. This location allows the thermostat to keep the room temperature at an ideal comfort level for most fireplace applications. For positioning the thermostat sensing bulb elsewhere, an adhesive-backed mounting clip is available.
1. Locate the gas valve assembly and thermostat sensing bulb (see Figure 31).
2. Gently pull thermostat sensing bulb free from the retaining clamp.
IMPORTANT:
Do not force or bend the thermostat sensing bulb or capillary.
3. The thermostat sensing bulb may be located to the lower right front side of fireplace. Determine location of sensing bulb, but do not mount sensing bulb until step 4. If you have a masonry fireplace, see Figure 33 for location.
If you have a factory-built metal fireplace, see
Figure 34 for location.
If your fireplace has glass doors, position sensing bulb directly behind door gap on right bottom side (see Figure 35).
4. The mounting clip must be a minimum of 3" from bottom of fireplace to prevent crimping of capillary. Once you have decided on a location, clean the area thoroughly. Remove the paper backing from the adhesive on back of mounting clip. Press the clip into the new location so that the thermostat sensing bulb will be positioned vertically with the capillary at the bottom (see Figure 36). Slide the thermostat sensing bulb into the clip.
IMPORTANT:
Do not crimp capillary.
Figure 32 - Adhesive-backed Mounting Clip
Thermostat
Sensing Bulb
Adhesivebacked
Mounting Clip
Figure 33 - Locating Thermostat Sensing
Bulb on Masonry Fireplace
Thermostat
Sensing Bulb
Adhesive-backed
Mounting Clip
Figure 34 - Locating Thermostat Sensing
Bulb on Factory-built Metal Fireplace
Glass Door
Thermostat
Sensing
Bulb
Adhesivebacked
Mounting
Clip
Figure 35 - Installing Thermostat Sensing
Bulb Behind Glass Doors
Thermostat
Sensing Bulb
Adhesive-backed
Mounting Clip
Capillary
Do Not Crimp
Capillary
24
Thermostat
Sensing Bulb
Retaining
Clamp
Gas Valve
Assembly
Figure 31 - Location of Gas Valve
Assembly and Thermostat Sensing Bulb
Figure 36 - Positioning the Thermostat
Sensing Bulb in the Vertical Position with the Capillary at the Bottom
www.desatech.com
113183-01B
SPECIFICATIONS
CDR3924PT CDR3924NT
Btu (Variable)
Type Gas
Ignition
Manifold Pressure 8.0" W.C.
Inlet Gas Pressure (in. of water)
Maximum
Minimum*
11,000/39,000 11,000/39,000
Propane/LP Natural
Electronic Electronic
14"
11"
Shipping Weight 30 lbs.
* For purpose of input adjustment
3.6" W.C.
10.5"
5"
30 lbs.
REPLACEMENT PARTS
Note:
Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized dealers of this product. If they canʼt supply original replacement part(s), call DESA Heating Products' Technical Service
Department at 1-866-672-6040.
When calling DESA Heating Products, have ready
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
• type of gas used (propane/LP or natural gas)
• purchase date
Usually, we will ask you to return the part to the factory.
PARTS NOT UNDER WARRANTY
Contact authorized dealers of this product. If they canʼt supply original replacement part(s), call
DESA Heating Products at 1-866-672-6040 for referral information.
When calling DESA Heating Products, have ready
• model number of your heater
• the replacement part number
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• heater will not produce specified heat
• propane/LP gas supply may be low
You may feel your gas pressure is too low. If so, contact your local natural or propane/LP gas supplier.
ACCESSORIES
NOTICE: All accessories may not be available for all fireplace models.
Purchase these heater accessories from your local dealer. If they can not supply these accessories, call DESA Heating Products at 1-866-672-6040 for referral information. You can also write to the address listed on the back page of this manual.
EQUIPMENT SHUTOFF VALVE
GA5010
For all models. Equipment shutoff valve with
1/8" NPT tap. Fits 1/2" NPT pipe.
FIREPLACE HOOD
Black - GA6050
Brass - GA6052
Antique Brass - GA6053
For all models. Helps deflect heat away from mantel or wall above fireplace. Fits openings 28" to 48" wide.
CLEANING KIT - CCK/GCK
(Not Shown)
For all models. Your vent-free gas appliance requires regular cleaning and maintenance to prevent performance problems. This kit gives you the tools and instructions to make it easy to clean all critical areas of your appliance.
INFORMATION VIDEO - 108917-01
(Not Shown)
For all models. A care and maintenance video is available by calling 1-866-672-6040. You may also email your request to
.
LAVA ROCK - GA6060
(Not Shown)
For all models. Order when additional rock is desired. (3 lb. bag)
113183-01B www.desatech.com
25
ILLUSTRATED PARTS BREAKDOWN
MODELS CDR3924PT AND CDR3924NT
13
9
5
7
6
17
8
4
20
14 15
27
27
1
23
18
29
10
19
25
11
26
22
21
12
3
24
2
16
32
33
31
30
28
26 www.desatech.com
113183-01B
PARTS LIST
This list contains replaceable parts used in your heater. When ordering parts, follow the instructions listed under Replacement Parts on page 25 of this manual.
KEY PART NUMBER
NO. CDR3924NT CDR3924PT DESCRIPTION
4
5
6
7
8
1
2
3
** ** Dual Ramp Base
111331-16 113473-01 Rear Burner Tube
113474-01 113474-01 Front Burner Tube
111124-01 111124-01 Retainer Spring
113244-01 113244-01 Front Burner
113167-01 113167-01 Log Support Bracket
108105-02 108105-02 Rear Burner
107110-01 107110-01 Spacer
9 107485-01 104286-01 ODS Pilot
10 102394-02 102394-02 Control Bracket
11 099387-09 099387-09 Pilot Tube
12 108628-01 108628-01 Inlet Tube
13 114696-02 114696-01 Pilot Bracket
14 111435-01 111435-01 Electronic Ignitor
15 098271-10 098271-10 Ignitor Cable
16 099056-18 099056-19 Burner Orifice Injector, Rear
17 101004-12 101004-09 Burner Orifice Injector, Front
18 108111-01 108111-01 Cast Iron Grate
19 108692-06 108692-06 T-Stat Cover Plate
20 108692-05 108692-05 Ignitor Plate
21 099123-01 099123-01 Thermobulb Clip
22
___
098867-17
098867-18 Gas Regulator (Propane/LP)
___
Gas Regulator (Natural)
23 098522-25 098522-10 Thermostatic Gas Valve Kit
24 108106-01 108106-01 Manual Control Valve
25 099393-03 099393-03 Control Knob
26 098508-01 098508-01 Valve Retainer Nut
27 108631-01 108631-01 Log Alignment Screw
28 114959-01 114959-01 Front Log
29 114959-02 114959-02 Left Side Log
30 114959-03 114959-03 Right Side Log
31 114959-04 114959-04 Rear Log
32 114959-05 114959-05 Middle Log
33 114959-06 114959-06 Crossover Log
PARTS AVAILABLE — NOT SHOWN
100563-01 100563-01 Warning Plate
101054-05 101054-05 Lighting Instructions Plate
100639-03 100639-03 Caution Decal
GA6060 GA6060 Lava Rock
101449-08 101449-08 Control Position Decal
** Not a field replaceable part.
1
1
1
1
1
QTY.
12
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
113183-01B www.desatech.com
27
WARRANTY INFORMATION
KEEP THIS WARRANTY
Model
Serial No.
Date Purchased
Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied.
LIMITED WARRANTY
COMFORT GLOW VENT-FREE GAS LOG HEATERS
DESA Heating Products warrants this product to be free from defects in materials and components for two (2) year from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Heating
Products Authorized Service Center. Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA Heating Products who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE
OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED
WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO TWO (2) YEAR
ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA HEATING PRODUCTSʼ
LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA HEAT-
ING PRODUCTS SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING
INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
2701 Industrial Drive
P.O. Box 90004
Bowling Green, KY 42102-9004 www.desatech.com
113183 01
NOT A UPC
113183-01
Rev. B
08/04
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Safety Information
- 4 Local Codes
- 5 Product Identification
- 5 Unpacking
- 5 Product Features
- 5 Air For Combustion and Ventilation
- 8 Installation
- 16 Operating Heater
- 18 Inspecting Burners
- 18 Technical Service
- 19 Cleaning and Maintenance
- 20 Troubleshooting
- 24 Optional Positioning of Thermostat Sensing Bulb
- 25 Specifications
- 25 Replacement Parts
- 25 Service Hints
- 25 Accessories
- 26 Illustrated Parts Breakdown and Parts List
- 28 Warranty Information