- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- Emerson
- 2200
- User manual
Emerson 1000 Power Supply User Manual
Add to my manuals
32 Pages
Emerson 3000: Business-critical continuity with the Liebert PSI XR UPS. Advanced power protection for your critical equipment with scalable runtime and user-friendly interface. Ideal for small to medium data centers, server rooms, and network closets. Enables extended battery runtime with external battery cabinets. Provides voltage regulation, frequency regulation, and surge protection. User-friendly LCD display for status monitoring and configuration. Supports remote monitoring and management through Liebert MultiLink software.
advertisement
Liebert
®
PSI XR
™
User Manual–1000/1500/2200/3000, 120VAC
AC Power
For Business-Critical Continuity™
TABLE OF CONTENTS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
5.4
i
Table 1
FIGURES
Figure 1
TABLES
ii
I
MPORTANT
S
AFETY
I
NSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of the UPS.
• Intended for installation in a temperature-controlled, indoor area free of conductive contaminants.
• Maximum ambient temperature 104°F (40°C).
Read this manual thoroughly before attempting to install or operate this UPS.
The equipment can be installed and operated by individuals without previous training.
Size of Branch Circuit Overcurrent Protection
!
!
!
CAUTION
To reduce the risk of fire, connect PS3000RT3-120XR models only to a circuit provided with
30 amperes maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70. Other Liebert PSI models must be connected to a circuit with
20 amperes maximum branch circuit overcurrent protection.
WARNING
Operate the UPS only from a properly grounded (earthed) 110-127VAC, 50Hz or 60Hz AC supply.
Some components are live, even when AC power is disconnected. For service, contact a properly trained and qualified technician. Do not remove the cover; the UPS has no user-serviceable parts inside except the internal battery pack.
WARNING
Although the UPS has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following rules:
• Turn Off and unplug the UPS before cleaning it. Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
• Do not install or operate the UPS in or near water.
• Never block or insert any objects into the ventilation holes or other openings of the UPS.
Keep all vents free of dust accumulation that could restrict air flow.
• Do not place UPS power cord anywhere it might be damaged.
Battery Handling Precautions
!
WARNING
Batteries should be replaced only by properly trained and qualified personnel knowledgeable of batteries and required precautions.
A battery can present a risk of electrical shock and high short-circuit current. The following precautions must be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Do not dispose of the battery or batteries in a fire. The battery may explode.
• Do not open or mutilate the battery or batteries. Released electrolyte is toxic. It may cause injury to the skin and eyes.
• When replacing the battery, use the same type of battery as is listed in Table 5.
• Handle, transport and recycle batteries in accordance with local regulations.
1
CONDITIONS OF USE—The input supply outlet must be within 6 ft. (1.8m) of the UPS and be easily accessed.
This UPS provides conditioned power to connected equipment. It is not intended for use with life-support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. If uncertain, consult your local dealer, local Emerson Network Power representative or
Channel Support Applications.
When installing the UPS or making input and output connections, comply with all relevant safety codes and standards (e.g., UL 1778).
Placing magnetic storage media on top of the UPS may result in data corruption.
ELECTROMAGNETIC COMPATIBILITY—The Liebert PSI XR complies with part 15 of the FCC
Rules. Operation is subject to the following two conditions:
• This device may not cause harmful interference, and
• This device must accept any interference received, including interference that may cause undesired operation.
This equipment uses, generates and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference with radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the UPS and the receiver.
• Connect the UPS to an outlet on a circuit different from the one the receiver is connected to.
NOTICE
Do not connect equipment that could overload the UPS or demand half-wave rectification from the UPS, such as electric drills, vacuum cleaners, laserjet printers and hair dryers.
2
G
LOSSARY OF
S
YMBOLS
Risk of electrical shock
!
Indicates caution followed by important instructions
Indicates the unit contains a valve-regulated, lead-acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Manual Self-Diagnostic Test
OFF
Status Change Button
3
Introduction
1.0
I
NTRODUCTION
The Liebert PSI
™
XR is a 2U, line-interactive UPS that may be installed in a rack or used as a tower
UPS.
Status indicators on the front of the Liebert PSI XR display load level, battery level, buck/boost, sitewiring fault, overload, battery status and UPS operation. Controls include a combination On/Alarm
Silence/Manual Self-Diagnostic Test button, an Off button and a Status Change button.
The Liebert PSI XR has USB, DB-9 (contact closure) and Liebert IntelliSlot
®
ports. The DB-9 and
USB ports provide detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with Liebert MultiLink ™ software.
The Liebert PSI XR is compliant with the Restriction of Hazardous Substances Directive (ROHS), prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder.
Figure 1 Front view of UPS
Liebert PSI XR rack-mount configuration
Display rotates for use as tower
Liebert PSI XR tower configuration
Display rotates for use in rack
Figure 2 1000 and 1500—rear view
DB-9 Port
(Contact
Closure)
Liebert
IntelliSlot
Port
USB
Port
Input Circuit Breaker
(12A for 1000VA;
15A for 1500VA)
Output Circuit Breaker
(8A for 1000VA;
15A for 1500VA)
Receptacles
NEMA 5-15R
INPUT OUTPUT
EPO
EPO
FUNCTION
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
2 1
Voltage Configuration
DIP Switch
Network Surge
Protection
DC 24V
External Battery
Cabinet Connector
Power Cord; 5-15P
(not shown for clarity)
4
Introduction
Figure 3 2200—rear view
DB-9 Port
(Contact
Closure)
Power Cord; 5-20P
(not shown for clarity)
Liebert
IntelliSlot
Port
15A Output Circuit Breaker for Receptacles #3 & #4
30A Input
Circuit Breaker
Receptacles #1 and #2;
NEMA 5-20R T-Slot
Receptacles #3 and #4
NEMA 5-15R
Receptacles
#5 and #6
NEMA 5-15R
INPUT
EPO
FUNCTION
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
2 1
OUTPUT
DC 48V
EPO
USB Port
Voltage Configuration
DIP Switch
Network Surge
Protection
External Battery
Cabinet Connector
20A Input Circuit Breaker
Receptacles #1 and #2
15A Output Circuit Breaker for Receptacles #5 & #6
Figure 4 3000—rear view
Power Cord; L5-30P
(not shown for clarity)
NEMA L5-30R
Receptacle
15A Output Circuit Breaker for Receptacles #3 & #4
30A Input
Circuit Breaker
Receptacles #1 and #2;
NEMA 5-20R T-Slot
Receptacles #3 and #4
NEMA 5-15R
Receptacles
#5 and #6
NEMA 5-15R
DB-9 Port
(Contact
Closure)
Liebert
IntelliSlot
Port
INPUT
EPO
EPO
FUNCTION
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
2 1
OUTPUT
DC 48V
USB Port
Voltage Configuration
DIP Switch
Network Surge
Protection
External Battery
Cabinet Connector
15A Output Circuit Breaker for Receptacles #5 & #6
20A Output Circuit Breaker
Receptacles #1 and #2
5
What’s Included
2.0
W
HAT
’
S
I
NCLUDED
The Liebert PSI XR is shipped with the following items:
• Multi-Language User Manual on CD
• Liebert MultiLink Software and User Manual, downloadable at
multilink.liebert.com
• Contact Closure (ML9P9S) Cable
• USB Cable
• Tower Stands
• Mounting Hardware
• Rack-Mount Handles
• Fixed Mounting Rails
• EPO Connector
• Battery-UPS Tab
Figure 5 Accessories
Tower Stands
Contact Closure
(ML9P9S) Cable
6 ft (1.8m)
USB cable
6 ft (1.8m)
Rack-Mount
Handles
Mounting Hardware
(Screws and Washers)
Fixed
Mounting Rails
EPO
Connector
Battery-UPS Tab
6
Installation
3.0
I
NSTALLATION
3.1
Preparation
!
CAUTION
The UPS and battery cabinets are heavy (see Table 6 and Table 7). Take proper precautions
when lifting or moving either the UPS or battery cabinets.
The Liebert PSI XR may be installed in either a tower or rack configuration. Determine the method that suits the application and proceed.
Decide where to install the Liebert PSI XR. The UPS must be installed indoors in a controlled environment. Place it in an area with unrestricted airflow around the unit, away from water, flammable
liquids, gases, corrosives and conductive contaminants (see Figure 6).
Maintain a minimum clearance of 12 inches (305mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).
Figure 6 Placing the Liebert PSI XR
AIR
AI
R
32 F (0 C) 104 F (40 C)
IR
A
12 in
./305 mm
Relative humidity
(non-condensing)
0% ~ 90%
7
3.2
Tower UPS Installation
See Figure 7 when using the Liebert PSI XR in a tower configuration.
Figure 7 Tower configuration—attach Tower Stands
Step 2
Installation
Step 1
8
Installation
3.3
Rack-Mount UPS Conversion and Installation
same manner.
Figure 8 Convert the Liebert PSI XR for rack installation
Step 1 Step 2
Step 3
Step 4
Step 5
!
!
WARNING
Placing heavy equipment near the top of a rack may increase the risk of tipping. Place the
UPS, and battery cabinet if one is being used, in the bottom of the rack.
CAUTION
Lifting equipment into rack may be a two-person job, depending on weight of equipment.
NOTICE
When rack-mounted, the UPS must be supported by a shelf, slide rails, brackets or fixed rails on each side. The rack-mount handles WILL NOT support the weight of the UPS. They are used to move the UPS into and out of the rack.
9
Installation
3.4
Orient Display for Installation
The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installations.
To set the display for your installation, pull out on the display and rotate it until it is oriented correctly, then press it into the UPS until it is seated.
Figure 9 Orienting the UPS display
3.5
Charge Batteries and Perform Battery Startup
Before connecting input power or connecting the load, Emerson recommends these steps:
• Charge the battery for at least 8 hours.
• Start the UPS on battery to ensure the battery is fully functional and charged.
• Turn the unit Off and proceed to 3.6 - Connect Input Power and Load.
3.6
Connect Input Power and Load
Connect input power to the UPS, then plug the equipment into the outlets on the rear of the UPS.
These UPS outlets provide battery backup and surge protection to the equipment when utility power
fails, spikes or sags (see Figure 10).
Figure 10 Connect input power and load
10
Installation
3.7
Connect Network Surge protection
Connect a 10 base-T/100 network cable to the network surge protection IN jack on the rear of the
UPS. Connect from the OUT jack with network cabling to network equipment (see Figure 11).
Figure 11 Connect network surge protection
Network
Equipment
INPUT OUTPUT
EPO
FUNCTION
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
2 1
Network surge protection OUT jack
DC 24V
Network surge protection IN Jack
3.8
Connect Communication Interface
Determine what type of communication connection to use to manage the UPS. The Liebert PSI XR can be monitored with any of these communication methods:
• Contact closure
• USB
• SNMP (requires optional IS-WEBRT3 card)
Connect the appropriate, factory-supplied cable to the interface port on the rear of the UPS and to the computer interface port.
See 3.9 - Set Up Liebert MultiLink software for details and installation information. Also refer to
Figure 12 Connect communication interface
11
Installation
3.9
Set Up Liebert MultiLink software
To start using Liebert MultiLink (software and user manual available at
multilink.liebert.com
):
• Install the software.
See the Liebert MultiLink quick-start guide or user manual for installation instructions.
• Connect one end of the USB cable (supplied) to the USB port on the rear of the UPS. Connect the other end to a USB port on the computer.
See the Liebert MultiLink user manual for operating instructions.
NOTE
Emerson recommends connecting the USB cable directly to the computer WITHOUT using a
USB hub.
3.10 EPO Switch
The Liebert PSI XR is equipped with an Emergency Power Off (EPO) switch. The user must supply a means of interfacing with the EPO circuit to allow disconnecting the UPS input feeder breaker to interrupt all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.
Figure 13 EPO connection for normally open operation
Short Pin 1 and Pin 2 to enable the EPO function
2 = Ground
1 = EPO+
12
Installation
3.11 External Battery Cabinet Installation
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. The batteries have a maximum run time of three hours at full load.
Mount UPS Conversion and Installation).
2. Connect the external battery cabinet cable to the rear of the external battery cabinet, then to the
rear of the UPS (see Figure 15).
Figure 14 Install the external battery cabinet in tower installation
Connect the top of the UPS to the top of the battery cabinet with the Battery UPS Tab and hardware
If two or more battery cabinets are used in a tower setup, the tower stand must be extended with the spacers included with each battery cabinet.
Connect tower stand and set the UPS and battery cabinet in them; check to ensure stability
NOTICE
Table 1
External battery cabinet power connectors are color-coded as noted in Table 1. Do not try to
install external battery cabinets with connectors that are a different color from the battery connector on the UPS.
Battery cabinet connector color key
UPS Model
PS1000RT3-120XR
PS1000RT3120XRW
PS1500RT3-120XR
PS1500RT3120XRW
PS2200RT3-120XR
PS2200RT3120XRW
PS3000RT3-120XR
PS3000RT3120XRW
Nominal System Voltage (connector color) External Battery Cabine Model
24VDC (Red)
48VDC (Gray)
PSRT3-24VBXR
PSRT3-48VBXR
13
Figure 15 Connect battery cabinets to UPS
EPO
FUNCTION
VOLTAGE=120V
VOLTAGE=127V
2 1
INPUT OUTPUT
DC 24V
Installation
See Table 8 for approximate battery run times.
14
Controls and Indicators
4.0
C
ONTROLS AND
I
NDICATORS
Buttons on the front panel display control the Liebert PSI XR. Eight LEDs indicate the UPS’s status.
Refer to Figure 16 and Table 2.
Figure 16 Display and status indicators
1 2 3 4 5
Load Level
Battery Level
Table 2
Item
3
4
1
2
5
1 to 5
6
7
8
9
10
11
6 7 8 9 10 11
Display and status indicators function, legend
Name Status Indicators Description
LED 1
LED 2
LED 3
LED 4
AVR Boost
AVR Buck
LED 5 Overload
Load/Battery Level
Status Change Button
UPS Operation in AVR Boost Mode
UPS Operation in AVR Buck Mode
Battery Condition Battery Fault/Weak
Grounding/Site Wiring Fault UPS Grounding/Site Wiring Fault
UPS Overload
Indicate Load/Battery Level
Switches Display from Load Level Indicators to Battery Level Indicators
OFF Button
ON Button
LED 9 Normal Mode
LED 10 Battery Mode
LED 11 UPS Fault
UPS Off
Turn on UPS, Manual Self-Diagnostic (Normal Mode),
Silence Alarm (Battery Mode)
UPS Operation in Normal Mode
UPS Operation in Battery Mode
UPS Fault
15
Controls and Indicators
4.1
Control Buttons
4.1.1 On/Alarm Silence/Manual Self-Diagnostic Test
This button controls output power to connected load(s). It has three functions:
• On
• Alarm Silence
• Manual Self-Diagnostic Test
ON—Start the UPS by pressing this button for more than 3 seconds, then releasing the button (an alarm will sound briefly). If the ON button is pressed and utility is outside input parameters, the UPS will start on battery (dark start).
Alarm Silence—Silence a battery mode audible alarm by pressing this button for longer than one second, then releasing it.
Manual Self-Diagnostic Test—To initiate a Manual Self-Diagnostic, press this button for at least three (3) seconds while operating from utility power. UPS will switch to Battery Mode to detect battery voltage and whether the UPS is operating normally.
If LED indicates the battery is weak: Allow the UPS to recharge the batteries for 8 hours.
Retest the battery after recharge.
If LED still indicates the battery is weak after the battery has been retested, contact your local dealer, local Emerson representative or Channel Support Applications.
If LED indicates a Battery Fault: Contact your local dealer, local Emerson representative or
Channel Support Applications.
If LED indicates a UPS Fault: Remove the load, retest the self diagnostic test, if LED indicated
UPS Fault, Contact your local dealer, local Emerson representative or Channel Support Applications.
NOTE
Refer to Figure 16 and Table 2 for details about the LEDs’ meaning.
4.1.2 Off Button
When the UPS is operating in either Normal Mode or Battery Mode, pressing the Off button for more than three seconds will shut down the UPS.
4.2
Status Indicators
4.2.1 Status Change Button
The Status Change button determines the information displayed by the five LEDs on the front panel.
The default information shown by the LEDs is the load level on the UPS. Pressing the Status Change button while the UPS is On prompts the LED display to show battery capacity for 5 seconds. This
function assists in assessing the meaning of status indicators as described in 4.2.4 - UPS Status
Indicators. See Figure 16 and Table 2 for the Status Change button’s location.
4.2.2 Load Level Indicator
The five LEDs at the top of the front panel illuminate with a steady glow to indicate the load level on the output of the UPS. The LEDs show the load level as a range, ± 5%. The LEDs’ load level meanings and colors are:
LED 1
10-24% — Green
LED 2
25-49% — Green
LED 3
50-74% — Yellow
LED 4
75-99% — Yellow
LED 5
100% or greater — Red
16
Controls and Indicators
4.2.3 Battery Level Indicator
The five LEDs illuminate with a steady glow to indicate battery capacity. Battery capacity is shown for five seconds after the Status Change button is pressed. The LEDs show the battery capacity as a range, ± 5% The LEDs’ battery level meanings and colors are:
LED 1
100-76% — Green
LED 2
75-51% — Green
LED 3
50-26% — Yellow
LED 4
25-11% — Yellow
LED 5
10% or less — Red
4.2.4 UPS Status Indicators
LEDs on the display panel illuminate with a steady glow or flash to indicate the UPS’s status:
Normal Mode—The Normal Mode indicator illuminates (LED 9) with a steady glow when utility power is available and within the input specifications.
Battery Mode—The Battery Indicator illuminates (LED 10) with a steady glow when the UPS is operating on battery
AVR Boost, AVR Buck—When the UPS is in AVR Boost/Buck Mode, the LED display will indicate the relative load level on the output of the UPS and will flash LED 1 (boost) or LED 2 (buck) to indicate which mode the UPS is in.
Weak Battery—When the UPS battery voltage is low, the LED display will indicate the relative load level on the output of the UPS and LED 3 will flash as a warning.
Site-Wiring Fault—In case of a site-wiring fault, the LED display will indicate the relative load level on the output of the UPS and LED 4 will flash as a warning.
Overload—When UPS operates in overload status, the LED display will indicate the relative load level on the output of the UPS and LED 5 will flash as a warning.
Table 3 Status indicators—color, illumination mode
Status LED 1 LED 2 LED 3 LED 4 LED 5 LED 10 LED 11
Normal Mode
AVR Boost
AVR Buck
Green
Flashes
Green
Flashes
LED 9
Green
Steady
Green
Steady
Green
Steady
Battery Mode
(dark start)
Yellow
Steady
Weak Battery
Yellow
Flashes
Site-Wiring Fault
Yellow
Flashes
Overload
Red
Flashes
Battery Fault
Shutdown
Overload
Shutdown
UPS Output
Abnormal
Shutdown
Yellow
Steady
Red
Steady
Yellow
Steady
Red
Steady
Red
Steady
Red
Steady
17
Operational Modes
5.0
O
PERATIONAL
M
ODES
5.1
Normal Mode
When the UPS is in Normal Mode, the Normal Mode Indicator illuminates green.
5.2
Buck/Boost Mode
The Automatic Voltage Regulator (AVR) circuitry compensates for fluctuations in utility power, such as voltage surges and sags. When the Liebert PSI XR detects an abnormality, it raises the undervoltage (boost) or lowers the overvoltage (buck) as needed. The AVR operates automatically and maintains the output voltage to the connected equipment, without utilizing the batteries.
LED 1 flashes green and LED 9 illuminates steady green when the UPS is in Boost Mode. LED 2
flashes green and LED 9 illuminates steady green when the UPS is in Buck Mode (see 9.0 - Trouble-
5.3
Battery Mode
The UPS switches to Battery Mode in the event of an extreme input voltage/frequency condition or utility failure.
When the UPS is in Battery Mode, the Battery Indicator illuminates amber and an alarm sounds at two-second intervals. As capacity decreases, fewer indicators remain illuminated.
When a Low Battery condition occurs, the Battery Indicator flashes amber and an alarm sounds at
one-second intervals. Refer to Table 8 for approximate battery run times.
5.4
Battery Recharge Operation
Once utility power is restored, the UPS resumes normal operation and the Battery Charger begins recharging the batteries.
18
Communication
6.0
C
OMMUNICATION
6.1
DB-9 Connector
The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer running Liebert MultiLink software in contact closure mode. The connection provides On
Battery and Low Battery notification.
When power is interrupted and battery power is low, Liebert MultiLink software can signal the host computer to gracefully shut down the operating system.
Table 4 DB-9 pin assignment
DB-9 Pin Assignment Description
6
7
4
5
8
9
1
2
3
Low Battery (open collector)
UPS TxD (not used)
UPS RxD (not used)
Remote Shutdown (5-12V); on-battery operation
Common
Output Off, (short to Pin 5, non-latching); any mode operation
Low Battery (open emitter)
Utility Fail (open emitter)
Utility Fail (open collector)
Pin Assignment Collector to Emitter*
6 7 8 9
1 2 3 4 5
330 Ohms
(+)
Open
Collector
(-)
Open
Emitter
6.2
Remote Shutdown Via the DB-9 Connector
The Liebert PSI XR can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB-
9 connector.
6.2.1 Any Mode Shutdown Via Pins 5 & 6
When Pin 6 is shorted to Pin 5, the UPS output is shut Off no matter what mode the UPS is operating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS output can be enabled by pressing the ON/Alarm Silence/Manual Self-Diagnostic Test button.
6.2.2 Battery Mode Shutdown Via Pins 4 & 5
While the UPS is operating on battery, a 5-12VDC signal for 2 seconds or longer is required to signal a shutdown. Signals for less than 2 seconds are ignored.
After Pin 4 receives the shutdown signal, a 2-minute shutdown timer begins a countdown. The shutdown timer cannot be stopped: If utility power returns during the 2-minute countdown, the shutdown timer continues until the end of 2 minutes and the UPS turns Off. The UPS will restart 10 seconds after utility power returns.
6.3
Network Surge Protection Connectors
Network (in and out) connectors on the rear of the UPS provide transient voltage surge suppression
(TVSS) for network devices.
19
Communication
6.4
UPS Communications
The Liebert PSI XR is equipped with a Liebert IntelliSlot port to provide advanced communication and monitoring options.
Liebert MultiLink software continually monitors the UPS and can shut down your computer or server via USB, contact closure and SNMP (via IS-WEBRT3 card) in the event of an extended power failure.
The Liebert IS-WEBRT3 provides SNMP and Web-based monitoring and control of the UPS across the network.
NOTE
The USB, SNMP and contact closure communications can operate in parallel.
6.5
UPS Inverter/Transfer Voltage Configurations
A two-pin DIP switch on the rear of the PSI XR permits setting the UPS to operate at nominal voltages of 110V, 120V or 127V. This feature will change the high and low points at which the UPS switches to battery power. It also changes the UPS’ output voltage when the UPS is operating in battery mode. The factory default setting is 120 VAC.
Turn Off the UPS before making any changes to the voltage configuration.
Figure 17 DIP switch settings for 120V system
FUNCTION
Voltage = 110V
Voltage = 120V
Voltage = 120V
Voltage = 127V
2 1
Table 5 Voltage configurations
Setting
110
120
127
Input Voltage Range
83~138
90~150
96~159
Output Voltage (Battery Mode)
110VAC
120VAC
127VAC
20
Battery Maintenance
7.0
B
ATTERY
M
AINTENANCE
7.1
Battery Charging, Storage
The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The Liebert PSI XR continuously charges the batteries when connected to the utility supply, even while the UPS is switched Off.
If the Liebert PSI XR will be stored for an extended period, Emerson recommends connecting the UPS to input power for at least 8 hours every four to six months to keep the batteries charged.
Emerson recommends performing a monthly manual self-diagnostic test via the Web card or the front panel display.
7.2
Internal Battery Replacement Procedure
NOTICE
This UPS is equipped with internal batteries that the user can replace without shutting down the UPS or connected loads (hot swappable). Caution must be exercised when replacing the batteries because the load is unprotected from power fluctuations and power failures.
To replace the batteries:
1. Remove the two screws on the left side of the front bezel.
2. Pull the front bezel off the UPS.
3. Remove the screw on the battery connector holder.
4. Remove the two screws on the battery bracket.
5. Disconnect the two slotted, red/gray and black battery connectors.
6. Grasp the battery pack assembly by the handle and pull it out of the front of the UPS.
7. Unpack the new battery assembly, taking care not to destroy the packing.
8. Compare the new and old battery assemblies to make sure they are the same. If so, proceed with replacement. If they are different, STOP and contact your local dealer, local Emerson representative or Channel Support Applications.
9. Slide the new battery pack into the UPS.
10. Reattach the battery bracket with the two screws.
11. Reconnect the slotted, red/gray and black battery connectors.
12. Reinsert the screw on the battery connector holder.
13. Reattach the front bezel.
Figure 18 Battery replacement
Load Level
Battery Level
Load Level
Battery Level
Load L evel
Batter y Leve l
Load Level
Battery Level
21
Specifications
8.0
S
PECIFICATIONS
Table 6 Liebert PSI XR specifications
Model Number
Power Rating, VA/W
Dimensions, W x D x H, in (mm)
Unit
Shipping
PS1000RT3-120XR
PS1000RT3120XRW
1000VA/900W
PS1500RT3-120XR
PS1500RT3120XRW
1500VA/1350W
17.3 x 19.3 x 3.5 (440 x 490.5 x 88)
22 x 24.1 x 9 (560 x 612 x 228)
Weight, lb (kg)
Unit 56 (25)
64 (29)
62 (28)
70 (32) Shipping
Input AC Parameters
Surge Protection
PS2200RT3-120XR
PS2200RT3120XRW
570J
1920VA/1920W
*
PS3000RT3-120XR
PS3000RT3120XRW
3000VA/2700W
17.3 x 27.6 x 3.5 (440 x 700.5 x 88)
22 x 34.8 x 9.0 (560 x 884 x 228)
92 (42)
101 (46)
105 (48)
115 (52)
Voltage Range
Without Battery Operation
Frequency Range
Input Power Cord,
10ft (3m) attached
NEMA 5-15P plug
83-159 VAC (configurable)
45~65Hz, (±0.5Hz)
NEMA 5-20P plug NEMA L5-30P plug
Output Receptacles
Voltage (Normal Mode)
Voltage (Battery Mode)
Transfer Time
Battery Parameters
Waveform
Type
Quantity x Voltage x Ah
Recharge Time
Battery Backup Time
(6) NEMA 5-15R
(4) NEMA 5-15R
(2) NEMA 5-20R T-Slot, accepts15A Plug
(4) NEMA 5-15R
(2) NEMA 5-20R T-Slot, accepts15A Plug
(1) NEMA L5-30R
110/120/127 VAC (configurable)
110/120/127 VAC; ±5% before low-battery warning
4-6 ms typical
Sinewave
4 x 12 x 7.2
Valve-regulated, nonspillable, lead acid
4 x 12 x 9 8 x 12 x 7.2
8 x 12 x 9
5 hours to 90% of rated capacity, after full discharge into resistive load
5 minutes
10 minutes
Full Load
Half Load
Environmental
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Relative Humidity
Operating Altitude
Audible Noise
Agency
Safety
Surge
ESD
Susceptibility
Electrical Fast Transient
Emissions
Conducted Immunity
Harmonics
Network surge
Transportation
32 to 104 (0 to 40)
5 to 104 (-15 to 40)
0% to 90%, non-condensing
Up to 10,000 ft (3000m)
<45 dBA
UL 1778, c-UL Listed
ANSI C62.41 CatA Lev3 (surges) IEC61000-4-5
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
FCC Part 15, Class A
IEC61000-4-6
IEC61000-3-2
UL 497 B
ISTA Procedure 1A Certification
ROHS compliant
Environmental
* NEC limits the input current rating of the PS2200RT3-120XR and PS2200RT3120XRW models to 80% of the input plug's rating. Up to
2200VA/1980W is available by contacting a certified electrician to change the input plug to 30A plug. Emerson Network Power assumes no liability for damage caused by miswiring or misapplication of the input plug.
22
Table 7 Battery cabinet specifications
Model Number
Used w/UPS Model
Dimensions, W x D x H, in (mm)
Weight, lb (kg)
Unit
Shipping
Batteries
Type
Quantity x Voltage x Ah
Manufacturer
Environmental
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Relative Humidity
Maximum Operating Altitude
Agency
Unit
Shipping
Safety
Emissions
Transportation
Specifications
PSRT3-24VBXR
PS1000RT3-120XR
PS1000RT3120XRW
PS1500RT3-120XR
PS1500RT3120XRW
PSRT3-48VBXR
PS2200RT3-120XR
PS2200RT3120XRW
PS3000RT3-120XR
PS3000RT3120XRW
17.3 x 19.3 x 3.5 (440 x 490.5 x 88)
22 x 26.6 x 9 (560 x 675 x 228)
64 (29)
73 (33)
Valve-regulated, nonspillable, lead acid
8 x 12 x 7.2
8 x 12 x 7.2
CSB, YUASA or Equivalent
32 to 104 (0 to 40)
5 to 104 (-15 to 40)
0% to 90%, non-condensing
10,000 ft. (3000m)
UL 1778, c-UL Listed
FCC Part 15, Class A
ISTA Procedure 1A Certification
23
Table 8 Liebert PSI XR battery run times
Number of Batteries
Internal Battery
Internal battery
+ 1 External
Battery Cabinets
Internal battery
+ 2 External
Battery Cabinets
70
80
90
100
30
40
50
60
90
100
10
20
50
60
70
80
10
20
30
40
70
80
90
100
Load %
10
20
30
40
50
60
1000
83
52
31
18
15
12
11
9
7
6
263
165
120
95
73
62
54
48
43
32
439
275
200
157
129
110
96
80
71
65
Internal battery
+ 3 External
Battery Cabinets
50
60
70
80
10
20
30
40
614
385
280
220
181
154
134
119
492
291
207
160
131
111
95
79
90
100
106
96
71
64
53
48
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.
96
77
67
59
322
202
147
116
65
58
52
47
150
116
95
76
26
18
357
212
56
47
33
29
222
131
93
68
6
5
9
7
1500
82
48
28
17
13
11
50
44
32
29
111
82
68
57
17
15
242
152
45
31
27
18
161
101
69
55
7
5
9
8
2200
76
48
28
17
14
11
Specifications
33
30
26
18
92
68
56
47
14
12
205
127
32
27
18
16
73
62
54
47
267
166
120
94
43
31
143
83
60
47
6
5
9
7
3000
75
47
28
17
13
11
24
Table 8 Liebert PSI XR battery run times (continued)
Number of Batteries
Internal battery
+ 4 External
Battery Cabinets
10
20
30
40
70
80
90
100
Load %
10
20
30
40
50
60
965
605
440
346
172
152
137
124
1000
790
494
360
283
233
198
762
452
320
248
122
108
96
82
1500
627
371
264
204
167
141
Internal battery
+ 5 External
Battery Cabinets
90
100
10
20
50
60
70
80
265
242
211
186
167
151
1140
714
203
171
148
131
117
106
897
531
Internal battery
+ 6 External
Battery Cabinets
30
40
50
60
520
408
337
286
377
292
239
202
295
232
191
163
70
80
90
100
249
220
197
179
175
154
138
124
142
125
112
102
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.
98
84
644
405
167
142
124
110
564
354
258
203
106
94
79
72
2200
483
303
221
174
143
122
Specifications
97
81
72
65
204
160
131
112
62
56
454
281
113
96
79
70
392
243
176
138
66
59
52
48
3000
330
204
148
116
95
76
25
Troubleshooting
9.0
T
ROUBLESHOOTING
The information below indicates various symptoms a user may encounter if the Liebert PSI XR expe-
riences a problem. See Table 9 for suggested solutions.
1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for low battery, overload warning and fault.
2. One or more additional indicators will be illuminated to provide a diagnostic aid to the operator, as described below:
problem persists, refer to Table 9.
Table 9 Troubleshooting—problems, causes and solutions
Problem
UPS will not start
UPS starts on battery, but will not switch to AC (dark start)
UPS shuts down
Site Wiring Fault LED (LED 4) flashing
Battery weak LED (LED 3) flashing
Short circuit
Cause
Battery is disconnected or completely discharged
UPS not plugged in
Circuit breaker tripped
AC overvoltage
Short circuit or UPS output is abnormal; LED 10 and LED 11 illuminate and sound audible alarm
Overload; LED 5 and LED 11 illuminate and sound audible alarm
LED 3 and LED 11 illuminate and sound audible alarm
Liebert MultiLink software
Site Wiring Fault, UPS detected a line-to-neutral reversal or a loss of proper grounding.
Batteries weak
Batteries need to be replaced
Solution
Check the circuit breaker on the rear of the UPS.
If it is tripped, reset it and restart the
UPS. For help, contact your local dealer, local Emerson representative or Channel Support
Applications.
Check for proper connection of battery or batteries.
Plug in the power cord securely.
Reset the circuit breaker and restart the UPS.
Wait until voltage drops to an appropriate level or have the utility power checked by a properly trained and qualified electrician.
Remove the load and turn on the
UPS again. For help, contact your local dealer, local Emerson representative or Channel Support
Applications.
Check load level display and remove nonessential loads.
Recalculate the load and reduce equipment connected to UPS - the total wattage must not exceed the capacity of the UPS.
Recharge the battery for 8 hours, then turn ON the UPS.
Consult the Liebert MultiLink user manual or contact your LAN administrator.
Have the utility checked by a properly trained and qualified electrician.
Recharge batteries.
Replace batteries.
NOTE
The PS2200RT3-120XR UPS will sound an Overload alarm under certain Low Line conditions when it is fully loaded and it exceeds the input current rating. Unless the load is reduced, the condition will trip the branch circuit breaker.
26
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2008 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners.
SL-23315_REV03_07-09
Emerson Network Power.
The global leader in enabling Business-Critical Continuity.
AC Power
Embedded Computing
Connectivity Embedded Power
DC Power Monitoring
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877 [email protected]
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378 [email protected]
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F Dah Sing Financial Centre
108 Gloucester Road
Wanchai
Hong Kong
852 2572 2201
Fax: 852 2519 9210
Outside Plant
Power Switching & Controls
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets
Services
Surge Protection
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2008 Emerson Electric Co.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 11 Preparation
- 12 Tower UPS Installation
- 13 Rack-Mount UPS Conversion and Installation
- 14 Orient Display for Installation
- 14 Charge Batteries and Perform Battery Startup
- 14 Connect Input Power and Load
- 15 Connect Network Surge protection
- 15 Connect Communication Interface
- 16 Set Up Liebert MultiLink software
- 16 EPO Switch
- 17 External Battery Cabinet Installation
- 20 Control Buttons
- 20 On/Alarm Silence/Manual Self-Diagnostic Test
- 20 Off Button
- 20 Status Indicators
- 20 Status Change Button
- 20 Load Level Indicator
- 21 Battery Level Indicator
- 21 UPS Status Indicators
- 22 Normal Mode
- 22 Buck/Boost Mode
- 22 Battery Mode
- 22 Battery Recharge Operation