Schneider Electric TSXETG100 User manual
Add to my manuals
19 Pages
Schneider Electric TSXETG100 gives you the ability to integrate serial devices to an Ethernet network by using Modbus TCP/IP protocol. Some common applications include interfacing serial programmable logic controllers (PLCs), remote terminal units (RTUs), and other devices that communicate via Modbus over RS485 or RS232 to an Ethernet network.
advertisement
Instruction Bulletin
ConneXium Ethernet Gateway TSXETG100
User’s Guide
Instrucciones en Español: página 19
Instructions en Français: page 39
Anweisungen auf Deutsch: Seite 59
Retain for future use.
TABLE OF CONTENTS
63230-319-211A1
2/2006
INTRODUCTION ........................................................................................ 2
Supported Ethernet Protocols..................................................................... 2
ACCESSING THE ETG OVER A NETWORK............................................ 3
ETG USER INTERFACE OVERVIEW........................................................ 4
SETUP ........................................................................................................ 5
Ethernet and TCP/IP Settings..................................................................... 5
Duplicate IP Address Detection............................................................. 6
Master Mode Device List Setup ............................................................ 8
Slave Mode Device List Setup .............................................................. 9
DIAGNOSTICS ......................................................................................... 14
FIRMWARE .............................................................................................. 18
Finding the Firmware Version ................................................................... 18
Updating the Firmware File....................................................................... 18
1
ConneXium
™ Ethernet Gateway
Introduction
INTRODUCTION
Supported Ethernet Protocols
63230-319-211A1
2/2006
This manual is to be used with a ConneXium
™
ETG100 with firmware version 2.0 or higher. For installation information, see the installation guide.
The ETG100 is a communications device that provides connectivity between Ethernet (Modbus TCP/IP) and serial line devices, allowing
Modbus TCP/IP clients to access information from serial slave devices. It also allows serial master devices to access information from slave devices distributed across an Ethernet network.
The ETG supports the following Ethernet protocols:
•
Modbus TCP/IP: Modbus TCP/IP is a combination of the Modbus
protocol, which provides master-slave communication between devices, and TCP/IP, which provides communications over an Ethernet connection. Modbus TCP/IP is used to exchange data between the ETG and other compatible Modbus TCP/IP devices via TCP port 502.
•
Hypertext Transfer Protocol (HTTP): HTTP is a network protocol that
handles the delivery of files and data on the World Wide Web. It provides web server functionality via TCP port 80. Remote configuration of the ETG and the viewing of diagnostic data is possible using a web browser.
•
File Transfer Protocol (FTP): FTP is a network protocol that provides
the ability to transfer files over the Internet from one computer to another. FTP is used to transfer firmware updates to the ETG via TCP port 21.
•
Simple Network Management Protocol (SNMP): Based on MIB2
format, SNMP provides the ability to store and send identifying and diagnostic information used for network management purposes via UDP port 161 .
•
Address Resolution Protocol (ARP): ARP is used to convert IP
addresses to Ethernet addresses. ARP requests are sent by the ETG to
determine if its address is a duplicate IP address (see “Duplicate IP
Address Detection” on page 6).
Hardware
RJ45 Ethernet port
Control power
LEDs for Ethernet and serial communications
Power and
Status LED
RS485 serial port
Bias, termination, and 2-wire/4-wire jumper switches
Reset button
RS232 serial port
(RJ45 connector)
2
© 2006 Schneider Electric. All Rights Reserved.
63230-319-211A1
2/2006
Additional Resources
ACCESSING THE ETG OVER A
NETWORK
ConneXium
™ Ethernet Gateway
Accessing the ETG Over a Network
Documentation and Firmware: Go to www.telemecanique.com, select
Products > Products index > Systems and architectures > Connexium.
After you set up the Ethernet parameters (see the installation guide), you can access the ETG over an Ethernet LAN using Internet Explorer 6.0 or higher.
Logging into the ETG
Action Result
1. Launch Internet Explorer 6.0 or higher.
2. In the Address text box, type the address of your ETG (169.254.0.10 is the default), then press Enter.
Opens Internet Explorer.
Opens the Login dialog box.
3. Type your user name (Administrator is the default) and password (Gateway is the default) into the text boxes, then click OK.
Enters the user name and password, then opens the ETG home page.
4. Click Setup to access the ETG setup page, or click Diagnostics to access the ETG diagnostics page.
Opens the Setup or Diagnostics pages.
Figure 1: The ETG Home Page
Menu bar
Logging Out
We recommend logging out whenever you do not need access to the ETG.
To log out of the ETG configuration session, click Log Out to end your session.
© 2006 Schneider Electric. All Rights Reserved.
3
ConneXium
™ Ethernet Gateway
ETG User Interface OVERVIEW
ETG USER INTERFACE
OVERVIEW
63230-319-211A1
2/2006
The ETG ships with seven pre-installed web pages used for ETG setup and
configuration. See Table 1 for a description of each web page.
Table 1: ETG static web pages
ETG Web Page Description
See
Page
Setup
Ethernet & TCP/IP
Serial Port
Device List
User Accounts
➀
Web Page Access
➀
Modbus TCP/IP Filtering
➀
SNMP Parameters
➀
Configure Ethernet and TCP/IP communication settings.
Set up or change serial communication parameters.
Identify serial devices on the daisy chain.
Create and edit groups and users.
Select web page access rights for each user group.
Set up which IP addresses can access the ETG through
Modbus TCP/IP.
Enable and configure the Simple Network Management
Protocol (SNMP), which allows the ETG to identify itself to network devices requesting SNMP data.
Diagnostics
Statistics Displays diagnostic data used to troubleshoot network problems. This page also contains information about your specific ETG, including the serial number, manufacturing date, and Media Access Control (MAC) address.
Read Device Registers Allows ETG administrators to read register data from a serial device connected to the ETG.
➀
Accessible by administrator only
4
© 2006 Schneider Electric. All Rights Reserved.
63230-319-211A1
2/2006
SETUP
Ethernet and TCP/IP Settings
ConneXium
™ Ethernet Gateway
Setup
To access the Setup web page links, click Setup on the ETG menu bar.
Action
1. From the Setup page, click Ethernet &
TCP/IP.
2. Select your frame format and media type.
Contact your network administrator if you do not know.
3. Enter your IP address, subnet mask, and default gateway address assigned to your
ETG by your network administrator.
4. Click Apply.
Result
Opens the Ethernet & TCP/IP page.
Selects the frame format and media type.
Enters the Ethernet parameters for the ETG.
NOTE: If you enter an IP address that is used by another device, you will be prompted to
select a new IP address. See “Duplicate IP
Updates the ETG Ethernet and TCP/IP settings.
* See Table 2 on page 5 for a list of options.
NOTE: After making changes to the Ethernet parameters and clicking
Apply, the ETG will reboot.
Figure 2: Ethernet & TCP/IP Page
© 2006 Schneider Electric. All Rights Reserved.
Table 2: ETG Ethernet and TCP/IP Settings
Option Description Setting
Frame Format
Media Type
IP Address
Used to select the format for data sent over an Ethernet connection.
Ethernet II, 802.3 SNAP
Default: Ethernet II
Used to define the physical Ethernet connection or media type.
•
•
10T/100Tx Auto
10BaseT-HD
• 10BaseT-FD
• 100BaseTX-HD
• 100BaseTX-FD
Default: 10T/100Tx Auto
Used to enter the static IP address of the
ETG.
0.0.0.0 to 255.255.255.255
Default: 169.254.0.10
Subnet Mask Used to enter the Ethernet IP subnet mask address of your network.
0.0.0.0 to 255.255.255.255
Default: 255.255.0.0
Default Gateway Used to enter the gateway (router) IP address used for wide area network (WAN) communications.
0.0.0.0 to 255.255.255.255
Default: 0.0.0.0
5
ConneXium
™ Ethernet Gateway
Setup
Duplicate IP Address Detection
63230-319-211A1
2/2006
While connected to your network, the ETG publishes its IP address. To avoid any duplicate IP address conflicts, the ETG uses the Address
Resolution Protocol (ARP) to see if any other device on your network is
using the same IP address. Table 3 below explains how the ETG handles a
duplicate IP address when it is detected.
Table 3: Duplicate IP Detection Scenarios
Scenario Duplicate IP Detected Power/Status LED
Boot Process /
Power Restore
Ethernet Link Detected
Reverts to the default ETG IP address, subnet mask, and gateway address. ARP requests are sent every
15 seconds until the IP address is available. When the IP address becomes available, the ETG will use it.
Four blinks, pause pattern
Manual Address Change ETG keeps it’s previous IP address and displays a message indicating that the IP address is already in use by another device.
Receives an ARP request Reverts to the default ETG IP address, subnet mask, and gateway address if a connected device sends four ARP requests for the ETG’s IP address. The ETG will send ARP requests every 15 seconds until the
IP address is available again. When the IP address becomes available, the ETG will use it.
Four blinks, pause pattern
6
© 2006 Schneider Electric. All Rights Reserved.
63230-319-211A1
2/2006
Serial Port
ConneXium
™ Ethernet Gateway
Setup
Action
1. From the Setup page, click Serial Port.
2. Select your mode, physical interface, transmission mode, baud rate, parity, and
response timeout (see Table 4 on page 7).
3. If you select Slave mode, enter the IP addresses for the remotely connected
devices (see Table 4 on page 7).
4. Click Apply.
Result
Opens the Serial Port page.
Selects the serial port options.
Enters the IP addresses of the remote devices.
Updates the ETG Serial Port settings.
Figure 3: Serial Port Page
Table 4: Serial Port Settings
Option Description Setting
Mode Used to select how the COM port on the
ETG is utilized (master or slave).
NOTE: When the Mode is changed, the
ETG reboots.
Physical Interface Used to select how the ETG serial port is physically wired.
Transmission
Mode
Baud Rate
Parity
Master, Slave
Default: Master
RS485 4-wire, RS485 2-wire, or RS232
Default: RS485 2-wire
Used to select how data is transmitted over a serial connection.
Modbus RTU, Modbus ASCII
Default: Modbus RTU
Used to select the data transmission speed over a serial connection.
2400, 4800, 9600, 19200,
38400, 56000*, 57600*
Default: 19200
Used to select if data is checked for accuracy using a parity bit.
Even, None
Default: Even
Response Timeout Used to select how long the ETG will wait to receive a response from a serial device.
0.1 to 10 seconds
Default: 3 seconds
Remote Modbus
TCP/IP
Connections
(Slave mode only)
Used to define a list of Modbus TCP/IP addresses for the ETG to use during slave mode communications.
—
* Available only if the physical interface and transmission mode is RS232/Modbus ASCII.
© 2006 Schneider Electric. All Rights Reserved.
7
ConneXium
™ Ethernet Gateway
Setup
Device List
Master Mode Device List Setup
63230-319-211A1
2/2006
Before you begin, keep in mind the following:
For master mode usage of the COM port:
•
Modbus devices do not have to be defined in the Device List, but it helps you manage your system.
Figure 4: Master Mode Topology
Ethernet
Connection
ETG in master mode
RS485 connection
Up to 128 serial slave devices using repeaters
Serial Slave Devices
If you selected Master mode on the Serial Port page, follow the steps below to set up the device list:
Action Result
1. From the Setup page, click Device List.
Opens the Device List page.
2. Select the number of viewable devices (1 to
128), then click Apply.
Selects the number of viewable locations that can be used to define serial slave devices connected to the ETG.
Enters the local address of the device.
3. In the Local ID text box, type the local ID
(address) of the serial slave device.
4. Repeat step 3 until all of the devices are entered.
5. Click Apply.
Enters all of the connected devices.
Updates the Device List settings.
Figure 5: Device List Page in Master Mode
8
© 2006 Schneider Electric. All Rights Reserved.
63230-319-211A1
2/2006
Slave Mode Device List Setup
ConneXium
™ Ethernet Gateway
Setup
Serial port slave mode allows serial Modbus master devices to access
information from serial slave devices across a TCP/IP network. Figure 6
below illustrates how the devices are connected using the device list
Figure 6: Slave Mode Topology
ETG in master mode
IP address:
169.254.0.28
RS485 connection
2 5
Serial Slave Devices
Ethernet
Connection
Up to 16 remote IP connections with up to 128 serial slave devices are possible
ETG in slave mode
ETG in master mode
IP address:
169.254.0.75
RS485 connection
RS232 or RS485 connection
2 3 4 5 6 7
Serial Slave Devices
If you selected Slave mode on the Serial Port page, follow the steps below to set up the device list:
Action Result
1. From the Setup page, click Device List.
Opens the Device List page.
2. Select the number of viewable devices (1 to
128), then click Apply.
Selects the number of viewable locations that can be used to define remote Modbus TCP/IP devices.
3. In the Local ID text box, type the local ID
(address) of the serial slave device.
4. In the Remote ID text box, type the remote
ID (address) of the serial slave device.
Enters the serial slave address of the remotely connected device.
5. Select the Connection.
Enters the address of the device that the local
Modbus master device will use to access the remote device.
6. Repeat steps 3 through 5 until all of the devices are entered.
7. Click Apply.
Selects the Modbus TCP/IP address to associate with the remote ID.
Enters all of the mapping information for the
ETG to communicate to the remote devices.
Updates the Device List settings.
Figure 7: Device List Page in Slave Mode
© 2006 Schneider Electric. All Rights Reserved.
9
ConneXium
™ Ethernet Gateway
Setup
User Accounts
63230-319-211A1
2/2006
ETG users are assigned user names and passwords. Each user belongs to a group, and each group has access rights to the ETG Web pages assigned by the ETG administrator.
NOTE: There are two default user accounts: Administrator (password is
Gateway) and Guest (password is Guest).
Action Result
1. From the Setup page, click User
Accounts.
Opens the User Accounts page.
2. If you want to change a group name, type a new name in one of the Groups text boxes
(the Administrator group name cannot be changed).
Enters a new group name.
3. In the Users section, enter a Name (1 to 24 characters) and Password (0 to 12 characters) for a new user.
Enters the name and password for a user.
NOTE: User names and passwords are case-sensitive and can contain only alphanumeric characters.
4. Select a group and the default language for the new user.
Selects the group and language for a user.
Continues adding users.
5. Repeat steps 3 and 4 for each additional user you want to add.
6. Click Apply.
Saves all of the user account settings.
Table 5: ETG accounts and passwords
Account Default Password
Administrator
Guest
Gateway
Guest
User-defined accounts (up to 11 accounts possible) No default –Password is user-defined
Figure 8: User Accounts Page
10
© 2006 Schneider Electric. All Rights Reserved.
63230-319-211A1
2/2006
Web Page Access
ConneXium
™ Ethernet Gateway
Setup
Action Result
1. From the Setup page, click Web Page
Access.
3. To allow Guest access to the web page, select Read-only under the Guest column.
NOTE: If the Guest group is Read-only, other groups may only be set to Read-only or Full.
Opens the Web Page Access page.
2. In the Ethernet & TCP/IP row, select the access level (None, Read-only, or Full) that each user group will have for the Ethernet &
TCP/IP web page.
See Table 6 below for an explanation of access
levels for each group.
Allows the default Guest group to access the web page.
4. Repeat steps 2 and 3 for the Serial Port,
Device List, Statistics, and Read Device
Registers rows.
5. Click Apply.
Selects the access level for each web page.
Saves the password settings.
Table 6: Group Access
Group
Administrator
Guest
Three user-defined groups
Access
Full access to all web pages
NOTE: We recommend that you change the default administrator password for system security the first time you log in.
Read-only access to selected web pages.
Choosing from the following options, the administrator assigns web page access for each group. Access levels are as follows:
• None: a group has no access to selected web page
• Read-only: password grants a group read-only access to the selected web page
• Full: a group has the same access as the Administrator group to the selected web page
Figure 9: Web Page Access Page
© 2006 Schneider Electric. All Rights Reserved.
11
ConneXium
™ Ethernet Gateway
Setup
Modbus TCP/IP Filtering
63230-319-211A1
2/2006
This function allows the administrator to specify Modbus TCP/IP client devices that have or do not have access to serial slave devices connected to the ETG.
NOTE: There is an anonymous Modbus TCP/IP address (***.***.***.***) that can be set to Read-only or None. Setting it to Read-only allows any
Modbus TCP/IP client not in the filtered list to access serial slave devices with read-only access. Setting it to None blocks all Modbus TCP/IP clients not in the filtered list.
Action
1. From the Setup page, click Modbus
TCP/IP Filtering.
2. Check Enable Filtering.
3. In the IP address column, enter the
Modbus TCP/IP client address
4. In the Access Level column, select Readonly or Full.
5. Repeat steps 3 and 4 to add more IP addresses.
6. Click Apply.
Result
Opens the Modbus TCP/IP Filtering page.
Activates filtering.
Enters an IP address for a Modbus TCP/IP client that will have access to the serial devices connected to the ETG.
Selects the access level for the corresponding
IP address. When set to Read-only, only the following Modbus TCP/IP function codes are allowed:
Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24,
43, 100
Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C,
11, 14, 18, 2B, 64
Continues adding IP addresses for filtering.
Saves the Modbus TCP/IP address filtering list.
Figure 10: Modbus TCP/IP Filtering Page
12
© 2006 Schneider Electric. All Rights Reserved.
63230-319-211A1
2/2006
SNMP Parameters
ConneXium
™ Ethernet Gateway
Setup
The ETG supports SNMP, allowing a network administrator to remotely access an ETG with an SNMP manager and view the networking status and diagnostics in the MIB2 format.
Action Result
1. From the Setup page, click SNMP
Parameters.
Opens the SNMP Parameters page.
2. Check Enable SNMP to turn ON the simple network management protocol.
Activates SNMP.
NOTE: If you uncheck Enable SNMP and
click Apply, the ETG will reboot and SNMP
functionality will be turned OFF.
3. Enter the system contact, system name, system location, read-only community name, and the read-write community name.
Enters the SNMP system information and community access names.
4. Click Apply.
Saves the SNMP settings.
Figure 11: SNMP Parameters Page
© 2006 Schneider Electric. All Rights Reserved.
13
ConneXium
™ Ethernet Gateway
Diagnostics
DIAGNOSTICS
63230-319-211A1
2/2006
To access the Diagnostics web page links, click Diagnostics on the ETG
menu bar.
Statistics
Figure 12: Statistics Page
Reading with Serial Port in MASTER MODE
Action
1. From the Diagnostics page, click
Statistics.
2. View the data.
3. Click Reset.
Result
Opens the Statistics page (see Figure 12).
NOTE: The Statistics page displays data based
on the mode selected in “Serial Port” on page 7.
See “Interpreting Statistics”below.
Resets the ETG cumulative diagnostic data to
0.
NOTE: This page will show accumulated readings since the ETG was last activated. If power to the ETG is lost, all cumulative values reset to zero.
Reading with Serial Port in SLAVE MODE
14
© 2006 Schneider Electric. All Rights Reserved.
63230-319-211A1
2/2006
Interpreting Statistics
© 2006 Schneider Electric. All Rights Reserved.
ConneXium
™ Ethernet Gateway
Diagnostics
Statistic Description
Ethernet
Link Status
Frames Transmitted OK
Collisions
Excessive Collisions
Frames Received OK
CRC Errors
Alignment Errors
Frames Too Long
Frames Too Short
A status string that represents the speed and duplex setting being used to communicate with the linking partner.
A counter that increments each time a frame is successfully transmitted.
A counter that increments each time a frame is retransmitted due to collision detection.
A counter that increments each time a frame is not able to be sent due to reaching the maximum collision status based on the
Truncated Binary Exponential Backoff algorithm.
A counter that increments each time a frame is successfully received.
A counter that increments each time a frame is received that has a checksum/CRC that does not match what is calculated.
A counter that increments each time a frame is received that has a checksum/CRC error and does not end on an 8-bit frame boundary.
A counter that increments each time a frame is received that is larger than the allowed maximum size defined in the standards (frames larger than 1518 bytes).
A counter that increments each time a frame is received that is smaller than the allowed minimum size defined in the standards (frames smaller than 64 bytes).
Modbus TCP/IP
Frames Sent
Frames Received
A counter that increments each time a frame is sent.
A counter that increments each time a frame is received.
Protocol Errors A counter that increments each time an ill-formed message is received.
Active Connections c
A status value that represents the number of connections that are active at the moment the diagnostics page is refreshed. A maximum of
32 connections are supported. Clicking Active
Connections opens a new window with a list of all of the active client connections.
Accumulative Connections c
A counter that increments each time a connection is made to the ETG.
Maximum Connections c
A status value that represents the maximum number of connections that were active at any given moment.
Inbound Read Messages c
A counter that increments each time a read request message is received.
Outbound Read Messages d
A counter that increments each time a read request message is sent.
Inbound Write Messages c
A counter that increments each time a write request message is received.
Outbound Write Messages d
A counter that increments each time a write request message is sent.
Inbound Reply Messages d
A counter that increments each time a reply message is received.
Outbound Reply Messages c
A counter that increments each time a reply message is sent.
c
Available when the serial port is in Master mode.
d
Available when the serial port is in Slave mode
15
ConneXium
™ Ethernet Gateway
Diagnostics
63230-319-211A1
2/2006
Statistic Description
Serial Port
Frames Sent
Frames Received
CRC Errors
Protocol Errors
Timeouts
Inbound Read Messages d
Outbound Read Messages
Inbound Write Messages d
Outbound Write Messages c c
A counter that increments each time a frame is sent.
A counter that increments each time a frame is received.
A counter that increments each time a message is received that has a CRC that does not match what is calculated. Typically the result of wiring issues.
A counter that increments each time an illformed message is received.
A counter that increments each time a request message is sent without receiving a corresponding response message within the allowed time. Timeouts are typically the result of configuration errors or a non-responsive device.
A counter that increments each time a read request message is received.
A counter that increments each time a read request message is sent.
A counter that increments each time a write request message is received.
A counter that increments each time a write request message is sent.
Gateway Information
Firmware Version
System Idle Time
The firmware version that is installed on the
ETG.
A percentage from 0% to 100% indicating the average processor time that is not being used.
MAC Address
Serial Number
Model Number
The unique Ethernet hardware address of an
ETG.
The serial number of the ETG.
The ETG model number (100).
Hardware Version ETG hardware version.
Manufacture Date Date the ETG was manufactured.
c
Available when the serial port is in Master mode.
d
Available when the serial port is in Slave mode
16
© 2006 Schneider Electric. All Rights Reserved.
63230-319-211A1
2/2006
Read Device Registers
ConneXium
™ Ethernet Gateway
Diagnostics
Action Result
1. From the Diagnostics page, click Read
Device Registers.
2. Enter the device ID, starting register number, and the number of registers to read.
3. Click Read Holding Registers or Read
Input Registers.
Opens the Read Device Registers page.
Enters the values to begin reading registers for the specified device.
Displays the values for the listed registers.
4. To change how the data is displayed in the
Value column, select Decimal,
Hexadecimal, Binary, or ASCII.
Selects how the data values are displayed.
Table 7: ETG Read Device Register Settings
Option Description
Device ID
Starting Register
Number of Registers
Register column
The address of the device that registers are read.
The first register to read.
The number of registers to read (1 to 10).
Lists the register numbers
Value column
Decimal, Hexadecimal,
Binary, or ASCII options
Lists the data stored in a register.
Select an option to specify how the Value column data is displayed.
Figure 13: Read Device Registers Page
Default
1
1000
10
—
—
Decimal
© 2006 Schneider Electric. All Rights Reserved.
17
ConneXium
™ Ethernet Gateway
Instruction Bulletin
FIRMWARE
Finding the Firmware Version
Getting New Firmware
Updating the Firmware File
www.schneider-electric.com
www.telemecanique.com
63230-319-211A1
2/2006
Firmware on the ETG can be updated using File Transfer Protocol (FTP).
Check www.telemecanique.com or with your local sales representative for the latest firmware update.
Action Result
1. Log into the ETG.
2. Locate the firmware version on the bottom-left corner of the page.
Opens the ETG home page.
Determines the firmware version of the ETG.
NOTE: If you recently updated your firmware, press F5 to refresh the web page and update the displayed firmware number.
3. Alternatively, you can select Diagnostics >
Statistics to find the firmware version in the
Gateway Information section.
Also determines the firmware version of the
ETG.
Action Result
1. Launch Internet Explorer, type
www.telemecanique.com in the Address text box, then press Enter.
Opens the Telemecanique web site.
2. Select Products, then click Product Index. Opens the Products page.
3. Select Systems and architectures.
Displays the Systems and architectures card.
4. Click ConneXium.
Opens the ConneXium systems and architectures page.
Opens the software/firmware page.
5. Click Software/firm.
6. Click the firmware file link (eg#####.bin, where ##### is the firmware number), then click Save.
Opens the File Download dialog box, then saves the firmware file.
Action Result
1. Launch Internet Explorer, type ftp:// and the
IP address of the ETG in the Address text box (for example, ftp://169.254.0.10), then press Enter.
Opens the Log On As dialog box.
Opens an FTP session with the ETG.
2. Type the user name Administrator and the administrator password in the text boxes, then click Log On.
3. Locate the saved firmware file on your computer, select it, then press CTRL+C.
Copies the firmware file to the clipboard.
4. Right-click in the Internet Explorer window, then click Paste.
Copies the firmware to the ETG, and the ETG reboots.
NOTE: Instead of copying and pasting the firmware file, you can drag-and-drop the firmware file into Internet Explorer.
5. Click the Close button on the Internet
Explorer window.
Closes Internet Explorer and ends the FTP connection to the ETG.
6. To verify that the firmware version was updated successfully, follow the steps in
“Finding the Firmware Version” on page 18.
Verifies the updated firmware version.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified electrical personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
© 2006 Schneider Electric. All Rights Reserved.
ConneXium
™ Ethernet Gateway
Handbuch
63230-319-211A1
2/2006
Maßnahme
5. Schließen Sie das Internet Explorer-
Fenster.
6. Um zu kontrollieren, ob die Firmware-
Version erfolgreich aktualisiert wurde,
befolgen Sie die Schritte unter „Firmware-
Version feststellen“ auf Seite 77.
Ergebnis
Schließen von Internet Explorer und Beenden der FTP-Verbindung zum ETG
Überprüfung der aktualisierten Firmwareversion www.schneider-electric.com
www.telemecanique.com
eine Marke von
Elektrisches Gerät sollte stets von qualifizierten Elektrikern installiert, betrieben und gewartet werden. Schneider Electric übernimmt keine Verantwortung für jegliche
Konsequenzen, die sich aus der Verwendung dieses Gerãts ergeben könnten.
© 2006 Schneider Electric.
Alle Rechte vorbehalten.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 INTRODUCTION
- 2 Supported Ethernet Protocols
- 2 Hardware
- 3 Additional Resources
- 3 ACCESSING THE ETG OVER A NETWORK
- 3 Logging into the ETG
- 3 Logging Out
- 4 ETG USER INTERFACE OVERVIEW
- 5 SETUP
- 5 Ethernet and TCP/IP Settings
- 6 Duplicate IP Address Detection
- 7 Serial Port
- 8 Device List
- 8 Master Mode Device List Setup
- 9 Slave Mode Device List Setup
- 10 User Accounts
- 11 Web Page Access
- 12 Modbus TCP/IP Filtering
- 13 SNMP Parameters
- 14 DIAGNOSTICS
- 14 Statistics
- 15 Interpreting Statistics
- 17 Read Device Registers
- 18 FIRMWARE
- 18 Finding the Firmware Version
- 18 Getting New Firmware
- 18 Updating the Firmware File