MS-5210UD Control Communicator Operating - Fire

MS-5210UD Control Communicator
Operating Instructions
DISPLAYS
NORMAL - Only the GREEN A.C. POWER LED is on. All
other LEDs are off.
PANEL - The key to open the panel can be found at this
location.
WHEN AUDIBLE DEVICES ARE SOUNDING FOR AN ALARM:
1) Evacuate the protected area.
2) Notify the monitoring service and/or the Fire Department
immediately. Tell them briefly what happened and what your
current status is.
3) If the Fire Department is responding, be prepared to provide
directions to arriving firefighters.
FOR TROUBLE ONLY:
1) Notify the monitoring service and/or Fire Department if this
panel is connected to either one, and tell them what is
happening.
2) Silence audible devices by pressing the SILENCE key. The
yellow SYSTEM TROUBLE LED will remain on. Contact
authorized service personnel immediately!
To return to normal after an alarm
1) Do not enter the protected area until safe to do so.
2) Clear all initiating devices. Smoke detectors will not reset if
there is still smoke in the area.
3) Reset the control panel (press the RESET key).
Power failure or brownout - AC POWER LED will go out for AC
fail or brownout and the TROUBLE LED will come on. SYSTEM
TROUBLE LED and the panel buzzer will turn on for either
condition and any other audible trouble devices will sound.
Contact authorized service personnel immediately.
(Refer to Local Service Representative block below).
A n
AC
bELn
d bn
d n
drll
E n
F 85
F A
F E
F n
F P
Lo b
no b
no 1
no 2
PH 1
PH 2
PA n
rES
SILn
SU n
Alarm Zone # 'n' (n = 1 - 10)
AC Loss
Notification Appliance Circuit # 'n' Fault (n = 1- 4)
Bell 'n' Disabled (n = 1 - 4)
Zone 'n' Disabled (n = 1 - 10)
Fire Drill
Zone 'n' Enabled (n = 1 - 10)
Annunciator Bus Fault
Annunciator Fault
Earth Fault
Trouble Zone # 'n' (n = 1 - 10)
Printer Fault
Low Battery
No Battery
Primary Phone Line Voltage Low
Secondary Phone Line Voltage Low
Primary Number Communications Fault
Secondary Number Communications Fault
Processing Monitoring Alarm Zone 'n'
System Reset
NAC # 'n' Silenced (n = 1 - 4)
Supervisory Alarm Zone # "n" (n = 1 - 10)
INSTRUCTIONS
To clear alarm indications in panel after cause
of alarm has been corrected, press:
RESET
To turn off the local panel sounder and
silenceable notification appliance circuits,
press:
SILENCE
To perform a fire drill, press:
MODE
3
7
4
5
ENTER
STORE
The RESET key restores the panel to normal.
Alarm Silencing - Alarm Signaling Circuits may be silenced by
pressing the SILENCE key. The SILENCE LED will turn on.
Subsequent alarms will reactivate circuits. Press the RESET
key to clear the silenced condition.
NOTE: ALARM SILENCE may be disallowed for one minute if
programmed (see manual).
To test the lamps, press:
MODE
5
2
6
7
ENTER
STORE
Refer to the MS-5210UD Technical Manual
P/N 50193 for more details.
WARNING!
Do not allow trouble conditions to remain logged
in the system. Protection that the system offers
has been compromised, or eliminated when a
trouble condition exists.
Local Service Representative
Name:______________________________
Address:____________________________
Telephone:__________________________
Frame and mount adjacent to the control panel.
Document 50448 Rev. A ECN 96-073
2/28/96