Data, installation, operation and maintenance
1 & 2 Zone Fire Panels
Zircon range
BARDIC
by Honeywell
Battery
24 Hour standby
1 x 12 V 2.6 Ah (minimum) or 3.3Ah
(maximum)
Fuse rating - F1.6A
Weight
4.2 Kg (including 2.6 Ah battery & carton) approx.
Detection Circuits
20 smoke or heat detectors maximum per zone. (A maximum
quiescent current of 1.2mA is allowed per zone circuit)
30 Call Points maximum per zone.
Alarm Sounder Circuits
300mA total through 2 circuits.
Nominal Voltage 25.3V (+2.7V / -1V)
Fuse rating - F315mA
FIRE
To reset from alarm enter code
and press
SOUNDERS ON/OFF
followed by
RESET
Auxiliary 24V Supply
POWER ON
GENERAL FAULT
FIRE
SYSTEM FAULT
FAULT / DISABLED
TEST
LED flashing LED Continuous
DISABLED
FAULT
1
ZONE
DISABLE
This is specifically not for fire protection devices.
2
POWER FAULT
SOUNDER
FAULT/DISABLE
SUPERVISOR
MODE
1
2
3
4
5
50mA maximum.
Nominal Voltage 25.3V (+2.7V / -1V)
Sounders
ON/OFF
Mute
Panel
Reset
Advance
Select /
Lamp Test
These instructions cover the:
ZIRCONLC1 :
One-Zone Conventional Fire Panel
ZIRCONLC2 :
Two-Zone Conventional Fire Panel
The panels are designed to meet the requirements of
EN54-2:1996 & EN54-4:1996
General Description
Options included that are covered by EN54
¨ Test Condition (10.0)
¨ Fire Alarm Devices (7.8)
Fuse rating - F125mA
Auxiliary Relay
Volt free change over contacts rated at 1A 30VDC Fuse Rating
1A
Note, the Auxiliary relay is configured as a fault relay, as
standard (EN54 requirement), however the relay can be
configured as an auxiliary fire relay, by moving a jumper link
from the fault position to the fire position on the back of the PCB.
Auxiliary relay
1
2
3
Fault
NC
C
NO
Fire
NO
C
NC
The N/C and N/O contacts change position, when the jumper is
moved to the fire position.
Class Change
Ancillary functions provided but not required by EN54
¨ Class change
¨ Repeater
Technical Specifications
Power Supply requirements
230Vac +10 - 15% 50Hz
Maximum Power consumption 50VA
Fuse rating - T125mA
The mains supply should be carefully wired using flat twin and
earth of not less than 1mm2 between the mains connector block
and an externally mounted secure switched fused spur outlet
with contact separation of at least 3mm. The switched spur unit
should be fused with a 2A fuse.
61640610 issue 8_6/07_Zircon 1 & 2 zone fire panels
Activated by using volt free N/O contacts between the -ve of
AUX 24V output and the CLASS CHANGE output.
Cabling
Unless otherwise recommended, and taking into account voltage
drop, not less than 1mm2 is recommended. Sounder circuits
should use cable that is fire proof. All cabling should be earthed
to the metal back box via the cable gland. Conductors carrying
fire alarm power signals should be separated from conductors
used for carrying other systems.
1
Installation instructions
Zircon 1 & 2 zone fire panels
Installation information
Mounting instructions
Installation of this product must be carried out using the
information given in this leaflet by a qualified electrician.
PCB TERMINAL
BLOCKS
BATTERY
&
Before installation ensure the electrical
supply is isolated.
Installation of this product must be carried out in accordance with
the requirements of BS5839 Pt1 and EN54.
Mounting location considerations
The fire alarm control panel should be mounted near to a
permanent, low fire risk, Entry / Exit, for easy access by the
Emergency Services. The panel should not be mounted in direct
sunlight, or in a place where the ambient temperature is above
30 ºC (86 ºF).
Mains must not be capable of being accidentally disconnected
and the isolating switch should clearly state:
TOP
COVER
FIXING
POINTS
METAL
HOUSING
SECONDARY
TRANSFORMER
WIRES
BOTTOM
COVER
FIXING
POINTS
Figure 1 Panel with top cover removed
In order to minimise the installation time, it is strongly
recommended, that the following procedure is followed:
1
Remove plastic fascia by removing the two screws from the
top plastic cover.
2
Disconnect the two secondary transformer wires from the
terminals marked ‘AC~’ on the PCB. These are located on
the right-hand side of the fire panel.
3
Remove the two screws that hold the bottom plastic cover in
place, then lift away from fire panel housing. Store cover
assembly in a safe place to prevent damage during initial
installation.
FIRE ALARM - DO NOT SWITCH OFF
&
CABLE ENTRY
POINTS TOP AND REAR
Caution: Anti static precautions should be
taken when installing the panel.
NOTE: DO NOT REMOVE THE PCB FROM THE PLASTIC
MOULDING.
Figure 2
Terminals and
fuses
4
Using the back box as a Drill template, mark through fixing
positions, prepare the fixing holes, and fit onto wall using an
appropriate mounting system.
Ensure the back box is not contaminated with drilling debris,
e.g. brick dust, as this can adversely affect the electronic
circuitry.
5
Prepare cable entries via the 20mm knockouts provided in
the top and rear of back box using appropriate glanding
system.
6
Remove any debris from the back box.
Battery
leads
Locating points
for enclosure tabs
(In two positions)
System
fuses
Transformer
AC low volts
input
1.6A
315mA
315mA
1A
125mA
8K2
E.O.L
resistors
Lower PCB cover
2
61640610 issue 8_6/07_Zircon 1 & 2 zone fire panels
Zircon 1 & 2 zone fire panels
Installation instructions
Wiring mains and battery
External wiring
1
The external wiring should now be connected to the fire panel.
Configure the Auxiliary relay link for fire or fault operation.
The factory default setting is activation on fault.
Battery
leads
red
black
View on back of pcb
(Some components not shown for clarity)
Locating
points for
enclosure
tabs
(In two positions)
PCB
FAULT/FIRE
AUXILIARY RELAY
(Shown in default “FAULT” position)
The fire panel is supplied with End Of Line Resistors for the zone
and sounder circuits, these must be transferred to the last device
in the circuit.
The End Of Line Resistor must be replaced with Active End Of
Line device if removable smoke/heat detectors are used on the
zone circuit.. Please note these units are polarised.
1
DISCONNECT MAINS SUPPLY & BATTERY.
2
Connect the zone wiring, one zone at a time, transferring
either the End Of Line Resistor or Active End Of Line Device,
if removable smoke/heat detectors are being employed. The
active end-of-line devices are polarised and should be
connected with Red/Orange wire to the +ve and Black to the
–ve.
Sounder
Figure 3 Setting the auxiliary relay operation
2
3
4
Connect mains wiring to terminal block in the back box as
marked. NOTE: AN EARTH CONNECTION MUST BE
MADE TO THE TERMINAL BLOCK AS MARKED.
Active end of line
device
2
With the mains supply isolated, replace the lower plastic
cover assembly containing the PCB. Ensure the battery
wires are routed to the top left-hand side of the back box and
the transformer secondary wires are routed towards the right
hand side. The PCB locating holes should engage on the
metal mounting tabs.
Reconnect the transformer secondary wires to the PCB
terminals marked ‘AC’.
Note: Polarisation of this connection is unimportant
7
7
2
red or
orange
4
5
black
5
4
Base for new range of detectors
-
+
1
DETECTOR
ZONE
FIRE PANEL
Remote
LED
+-
+ve
5
6
7
Fit and tighten the two securing screws that hold the PCB
moulding in place. Ensure that the moulding has properly
engaged at the bottom of the metal back box. Do not over
tighten two retaining screws.
DC +ve
DC -ve
Fit battery into left-hand side of the back box and connect
battery using leads supplied. Ensure correct polarity is
always observed.
The panel is now active and will indicate a ‘POWER
FAULT’ and “GENERAL FAULT” until the mains supply
is re-instated, and the panel ‘RESET’.
LED
module
3
4
2 7
5
-ve
Connecting LED to base
with LED Module fitted
Instate the mains supply, enter access code then press the
‘RESET’ button, see operating instructions.
L2
L2
DIODE
(SCHOTTKY)
DIODE
(SCHOTTKY)
L1 IN L1 OUT
L1 IN L1 OUT
Black
-Active
End of Line
+
Red or
Orange
Base of existing range of detectors
8
9
Check panel is operating normally. The panel should only
show the green “POWER ON” indicator.
You have now proved that the panel is free of faults.
-
+
1
DETECTOR
ZONE
FIRE PANEL
Figure 4 Connecting the Fire Detector and remote LED to a
zone circuit
61640610 issue 8_6/07_Zircon 1 & 2 zone fire panels
3
Installation instructions
Zircon 1 & 2 zone fire panels
Fit an active end of line if
detectors are also connected
to the zone circuit.
black
Active
end of line
red or
orange
8K2
Ohms
CALL POINT
-
CALL POINT
COMMON
COMMON
470 Ohms
470 Ohms
680 Ohms
680 Ohms
+
1
DETECTOR
ZONE
FIRE PANEL
Figure 5 Connecting the manual call points
3
Repeat the above procedure until all the required circuits are
connected.
4
Connect the sounder wiring one circuit at a time, transferring
the end of line resistor to the last sounder on that circuit.
END-OF-LINE
RESISTOR 8K2 Ohms
fitted to last sounder
-
-
+
+
+
+
2nd
SOUNDER
1st
SOUNDER
COMMON
Volume
END-OF-LINE RESISTOR
8K2 Ohms fitted to last sounder
-
+
-
2
1
SOUNDERS
-
-
-
-
+
+
+
+
Polarised and suppressed
sounders only
+
FIRE PANEL
Figure 6 Connecting the Sounder circuit
5
Repeat the above procedure until all the required sounder
circuits are connected.
6
Connect other external circuits as required
Non latching alarm
remotely set by
an external source
CLASS
CHANGE
-
+
AUX
24V
FIRE PANEL
Figure 7 Connecting the Class change circuit
7
Reinstate the mains supply, enter access code then press
the ‘RESET’ button.
8
Refit plastic fascia. Do not over tighten two retaining screws.
4
61640610 issue 8_6/07_Zircon 1 & 2 zone fire panels
Zircon 1 & 2 zone fire panels
Installation instructions
Operating instructions
Red indicators
Figure 8
Controls and
indicators
Green indicator
Amber indicators
FIRE
To reset from alarm enter code
and press
SOUNDERS ON/OFF
followed by
RESET
POWER ON
GENERAL FAULT
FIRE
SYSTEM FAULT
FAULT / DISABLED
TEST
1
ZONE
DISABLE
LED flashing LED Continuous
DISABLED
FAULT
2
POWER FAULT
SOUNDER
FAULT/DISABLE
SUPERVISOR
MODE
1
SOUNDERS MUTE
PANEL
ON/OFF
To operate this fire alarm control panel, it is necessary to gain
access to the “Supervisor Mode”, to do this enter the four digit
security password code, on the yellow push buttons. This
security code should have been given to the responsible person
on system hand over.
After entering the correct code the “Supervisor Mode” LED will
illuminate.
3
RESET
4
5
ADVANCE SELECT /
LAMP TEST
Control buttons
Amber indicators
Access to “SUPERVISOR MODE” for panel
operation
2
Test Zone
This feature allows one person to check the detectors and
sounders without having to return to the panel during the testing
routine. When the appropriate zone is in test mode and a
detector is activated, the sounder circuit/s will operate for a few
seconds and then automatically reset.
1
Enter the access code to get into “supervisor mode” if not
already entered.
2
Hold down the ‘ADVANCE’ push button for at least
2 seconds until you hear a double bleep.
3
The “Test” LED will light and the Zone 1 Fault LED will flash
at a fast rate (faster than the fault warning flash rate) the
flashing LED at this stage indicates that the zone is not in
test!
SOUNDER ON/OFF
4
If the panel is in alarm the sounders will sound, the sounder
circuits may be silenced by pressing this button. If the sounders
are silent by pressing this button they will be activated.
If you do not wish to test this zone then press ‘ADVANCE’ to
move on to the next zone.
5
To put the zone into “Test” press ‘SELECT / LAMPTEST’
(repeated pressing of this button will toggle the zone in and
out of test mode!).
6
After you have pressed the select button you will see that the
zone is now constantly lit, this indicates that the zone is now
in test!
7
Once the site tests have been completed you may find that
the keypad access timer has elapsed and that you will have
to repeat points 1-4 to get to the appropriate zone in test.
8
To cancel the test mode and return a zone back to normal
operation simply press ‘SELECT / LAMP TEST’ to toggle the
zone from constant to flashing.
The panel will time out of “Supervisor Mode” if the ‘RESET’ button
is pressed or 20 seconds have elapsed since the last button was
pressed.
The following functions can all be employed in the
“Supervisor Mode”.
RESET
This will cause all faults and fires conditions to be cancelled, if a
fault still exists then it will re-appear within 10 seconds of this
reset.
MUTE PANEL
To silence the panel’s internal buzzer press ‘MUTE PANEL’ push
button. The panel will continue to beep at a reduced rate until the
condition causing the buzzer to sound is rectified or reset.
SELECT - LAMP TEST
Hold down ‘SELECT / LAMP TEST’ push button for a minimum of
two seconds. Release once the test is complete.
Once you have returned the zone/zones to normal operation you
can then press reset to exit supervisor mode. Note: Pressing
reset whilst a zone is in test will not revert the panel to normal
operation!
61640610 issue 8_6/07_Zircon 1 & 2 zone fire panels
5
Installation instructions
Zircon 1 & 2 zone fire panels
Disable Zone
Disable Sounders
1
Repeat points 1-3 (from the Test zone procedure listed
above).
Repeatedly press the advance button until the test LED
extinguishes and the disabled LED illuminates and Zone 1
LED flashes at a fast rate (identical to the situation in point 3
of Test zone procedures listed above, with the exception of
the test LED!)
To disable and subsequently enable a zone follow the steps
detailed in points 5-8 listed above.
1
Once you have returned the zone/zones to normal operation you
can then press reset to exit supervisor mode.
4
2
3
&
Pressing reset whilst a zone is disabled
will not revert the panel to normal operation!
2
3
Repeat points 1-3 (from the Test zone), progressing through
all the Test & Disable zones features until the “Sounder
Fault/Disable” LED flashes (the flashing LED at this stage
indicates that the sounders are not disabled!).
To disable the sounders press the ‘SELECT/LAMP TEST’
push button to toggle the LED from flashing to constant.
Once the site tests have been completed you may find that
the keypad access timer has elapsed and you will have to
repeat point 1b to get to get back to sounder disable menu.
To cancel the disable mode and return the sounders back to
normal operation simply press ‘SELECT/LAMP TEST’ to
toggle the “Sounder Fault/Disable” from constant to flashing.
Once you have returned the sounders to normal operation you can
then press reset to exit supervisor mode.
"
Pressing reset whilst the sounders are
disabled will not revert the panel to normal operation!
Cause and Effect Chart
Buzzer
Code Entry Mode
Supervisor Mode
Test
Disabled
Power Fault
Power
System Fault
Sounder Fault / Disable
Zone Fault /Disable / Test
Zone Fault
General Fault
General Fire
Sounder
❍ = OFF ● = ON
= Pulsed on/off with equal
duty cycle ✪ = Pulsed intermittently every 8
seconds when alarm or fault indication has been
silenced: or for Test Mode this state occurs
10 minutes after last triggered zone under test, as a
reminder that the panel is still in Test Mode.
❍ ❍ ❍❍❍ ❍ ❍ ● ❍ ❍ ❍ ❍ ●❍
● ●
●
●
●
❍
●
Normal condition. System operating correctly in standby
mode.
● ✪ Fire condition. Detector or call point operated.
❍
●
✪
●
✪
●
●
●
●
●
● ●
● ●
●
●
✪
❍ ❍
❍
❍ ❍ ❍❍❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍
●
✪
●
✪
●
✪
●
✪
●
●
✪
●
6
●❍
Detector zone circuit fault. A detector has been removed
or circuit wiring open or short-circuited.
Alarm sounder circuit fault. Alarm circuit has been
disabled by engineer for maintenance or test purposes..
Disabled zone. Zone circuit has been disabled by
engineer for maintenance or test purposes.
Disabled sounder contacts. Contacts have been disabled
by engineer for maintenance or test purposes. Auxiliary
relay disabled.
ROM/RAM failure. Watchdog tripped.
Test mode. Selected zone is being tested.
Total power failure.
Partial power failure.
a) Battery flat / failed / disconnected or rupture of battery
cable or fuse (Fast flashing).
b) Mains supply faulty or charger fault.
c) 24V supply voltage faulty - used for detector and
alarm zones.
Auxiliary 24V supply voltage faulty or ruptured fuse.
System Failure.
Supervisor Mode (Resets after 20 seconds after last
button press)
61640610 issue 8_6/07_Zircon 1 & 2 zone fire panels
Zircon 1 & 2 zone fire panels
Installation instructions
Maintenance Information
All the components of this panel have been selected for the
intended purpose, and are expected to operate within their
specification when the environmental conditions outside the panel
comply with class 3k5 of IEC 721-3-3.
The battery has manufacturers recommended life expectancy of
3-5 years. We recommend that this control panel and all
associated equipment be periodically tested and inspected in
accordance with the relevant British Standards for the installation
and servicing of fire alarm equipment.
Fire Panel Log Book
Site name________________________________________________________________________________________________
Site address______________________________________________________________________________________________
________________________________________________________________________________________________________
________________________________________________________________________________________________________
Person(s) responsible________________________________Date__________________________________________________
System installed by__________________________________Telephone______________________________________________
Date installed________________________________________Date commissioned_____________________________________
Maintained under contract by________________________________________________________________________________
Service contact No.:___________________________________Until_________________________________________________
Type and Quantity
No
Detector
Location
Call point
Sounder
Qty
Zone 1
Zone 2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
61640610 issue 8_6/07_Zircon 1 & 2 zone fire panels
7
Installation instructions
Zircon 1 & 2 zone fire panels
Example of Logs
Events other than false alarms or maintenance work
Date
Time
Event
Zone
Device
Date completed Initials
Action
False Alarms
# Categories: Unwanted - unwanted false alarm, Equipment - equipment false alarm, Good intent - false alarm with good intent,
Malicious - malicious false alarm and Unknown - cause of alarm not known.
Date Time Device that triggered Cause (if Brief
Maintenance visit Finding of
Category Action
the alarm signal
known) circumstances required (yes/no) maintenance #
comple
ted
Maintenance Work
Date Time Zone
Device
Reason for
work
Work carried out
Further
work
required
Signature
WEEE Directive:
At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.
Do not dispose of with your normal household waste.
Do not burn.
At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.
Bardic by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.
BARDIC
by Honeywell
8
Waterside Road, Hamilton Industrial Park, Leicester LE5 1TN, UK
Technical support
Telephone (UK) +44 (0) 116 246 2225
Fax (UK): +44 (0)116 246 2493
Website: www.bardic.co.uk
Customer service
Enquiries telephone: +44 (0) 116 246 2212
Fax order line: +44 (0) 116 246 2210
61640610 issue 8_6/07_Zircon 1 & 2 zone fire panels
Open as PDF