October 29, 1999
H-220
FMM and FZM Series
Monitor Modules with FlashScan™
Section: Intelligent/Addressable Devices
GENERAL
Three different monitor modules are available for the
NOTIFIER AFC-600 to suit a variety of applications. Monitor
modules are used to supervise a circuit of dry-contact input
devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (FZM-1).
Approved
S3705
(FMM-1, FZM-1,FMM-101)
FMM-1 — The FMM-1 Monitor Module is a standard-sized
module (typically mounts to a 4" [101.6 mm] square box) that
supervises either a Class A (Style D) or Class B (Style B)
circuit of dry-contact input devices.
FMM-101 — The FMM-101 is a Miniature Monitor Module
(a mere 1.3" (33.02 mm) H x 2.75" (69.85 mm) W x 0.5" (12.70
mm) D) used to supervise a Class B (Style B) circuit. Its
compact design allows the FMM-101 to often be mounted in
a single-gang box behind the device it’s monitoring.
FlashScan (patent pending) is a new communication protocol developed by NOTIFIER Engineering that greatly enhances the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater
than five times that of other designs.
FlashScan™ is a trademark of NOTIFIER.
FMM-1 MONITOR MODULE
• Built-in type identification automatically identifies this device as a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional
power required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address (01-159).
• LED flashes green during normal operation (this is a programmable option), and latches on steady red to indicate
alarm.
The FMM-1 Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The FMM-1 can be used to replace MMX-1 modules in existing systems.
FMM-1 Applications — Use to monitor a zone of fourwire smoke detectors, manual fire alarm pull stations,
waterflow devices, or other normally-open dry-contact alarm
6724mod2.tif
FZM-1 — The FZM-1 Interface Module is a standard-sized
module used to monitor and supervise compatible two-wire,
24 volt, smoke detectors on a Class A (Style D) or Class B
(Style B) circuit.
FMM-1 and FZM-1
activation devices. May also be used to monitor normallyopen supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as
an NFPA Style B (Class B) or Style D (Class D) Initiating
Device Circuit. A 47K ohm End-of-Line Resistor (provided)
terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. Maximum IDC loop length is
2,500 ft./762 m (20 ohms maximum).
FMM-1 Operation — Each FMM-1 uses one of 159 available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the
status (open/normal/short) of its Initiating Device Circuit (IDC).
A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm
(subject to current limitations on the loop).
FMM-1 Specifications
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Average operating current: 400 µA (LED flashing).
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square
x 2.125" (53.975 mm) deep box.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
One Fire-Lite Place, Northford, Connecticut 06472
ISO-9001
Engineering and Manufacturing
Quality System Certified to
International Standard ISO-9001
Made in the U.S.A.
DN-6720 — Page 1 of 5
FZM-1 INTERFACE MODULE
• Built-in type identification automatically identifies this device as a monitor module to the AFC-600.
• Powered directly by two-wire FACP. No additional power
required.
• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct-dial entry of address (01-159).
The FMM-101 Mini Monitor Module can be installed in a
single-gang junction directly behind the monitored unit. Its
small size and light weight allow it to be installed without rigid
mounting. The FMM-101 is intended for use in intelligent,
two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire
initiating device circuit for normally-open-contact fire alarm
and security devices. The FMM-101 can be used to replace
MMX-101 module in existing systems.
• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power
source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address (01-159).
• LED flashes during normal operation (this is a programmable option).
• LED latches steady to indicate alarm on command from
control panel.
The FZM-1 Interface Module is intended for use in intelligent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor twowire conventional smoke detectors. It transmits the status
(normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. The
FZM-1 has a panel-controlled LED indicator and can be used
to replace MMX-2 modules in existing systems.
6720m101.wmf
FMM-101 MINI MONITOR MODULE
FZM-1 Applications — Use the FZM-1 to monitor a
zone of two-wire smoke detectors. The monitored circuit may
be wired as an NFPA Style B (Class B) or Style D (Class A)
Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor
(provided) terminates the end of the Style B or D (class B or
A) circuit (maximum IDC loop resistance is 25 ohms). Install
ELR across terminals 8 and 9 for Style D application.
FZM-1 Operation — Each FZM-1 uses one of 159 avail-
FMM-101 Applications — Use to monitor a single device or a zone of four-wire smoke detectors, manual fire
alarm pull stations, waterflow devices, or other normally- open
dry-contact devices. May also be used to monitor normallyopen supervisory devices with special supervisory indication
at the control panel. Monitored circuit/device is wired as an
NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm
End-of-Line Resistor (provided) terminates the circuit.
FMM-101 Operation — Each FMM-101 uses one of
159 available module addresses on an SLC loop. It responds
to regular polls from the control panel and reports its type
and the status (open/normal/short) of its Initiating Device
Circuit (IDC).
FMM-101 Specifications
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 375 µA maximum.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3" (33.02 mm) high x 2.75" (69.85 mm) wide
x 0.5" (12.70 mm) deep.
Wire length: 6" (152.4 mm) minimum.
Page 2 of 5 — DN-6720
able module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the
status (open/normal/short) of its Initiating Device Circuit (IDC).
A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm
(subject to current limitations on the loop).
FZM-1 Specifications
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Average operating current: 270 µA (LED flashing).
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):
DC voltage: 18 to 28 volts power limited. Ripple voltage:
0.1 VRMS maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square
x 2.125" (53.975 mm) deep box.
INSTALLATION
FMM-1 and FZM-1 modules mount directly to a standard 4"
(101.6 mm) square, 2.125" (53.975 mm) deep, electrical box.
They may also be mounted to the SMB500 surface-mount
box. Mounting hardware and installation instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regulations. These modules are intended for power-limited wiring only.
The FMM-101 module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances,
and regulations.
ARCHITECTS’/ENGINEERS’
SPECIFICATIONS
Model
FMM-1
FMM-101
FZM-1
SMB500
Description
Monitor Module.
Mini Monitor Module.
Two-Wire Detector Monitor Module.
Optional Surface-Mount Backbox.
6720mt2.wmf
Specifications of these and
all NOTIFIER products are
available from NOTIFIER.
PRODUCT LINE INFORMATION
6720mt1.wmf
MOUNTING
DIAGRAMS for
standard-sized
modules at right
WIRING DIAGRAMS
6724face.wmf
The following wiring diagrams are included:
1) FMM-101, typical two-wire Style B initiating device circuit configuration.
2) FMM-1, typical two-wire initiating circuit
configuration, NFPA Style B.
3) FMM-1, typical four-wire fault-tolerant
initiating circuit configuration, NFPA
Style D.
4) FMM-1, typical two-wire initiating circuit
configuration for security systems (with
alarm versus short capability).
5) FZM-1, interface two-wire conventional
detectors, NFPA Style B.
6) FZM-1, interface two-wire conventional
detectors, NFPA Style D.
7) FRM-1, relay control module used to disconnect a power supply.
Face Plate for FMM-1 and FZM-1
WIRING DIAGRAM: FMM-101
Fig. 1 FMM-101: Typical two-wire Style B
initiating device circuit configuration.
6720wir1.wmf
DN-6720 — Page 3 of 5
WIRING DIAGRAMS THIS PAGE: FMM-1
•
•
•
•
•
Connect modules to listed compatible NOTIFIER control panels only.
All wiring shown is supervised and power limited.
Install contact closure devices per manufacturers’ installation instructions.
Any number of UL-listed contact closure devices may be used.
DO NOT MIX fire alarm initiating, supervisory, or security devices on the same module.
Fig. 2 FMM-1: Typical two-wire initiating device circuit configuration, NFPA Style B.
6720wir2.wmf
Fig. 3 FMM-1: Typical four-wire fault-tolerant initiating circuit configuration, NFPA Style D.
6720wir3.wmf
Fig. 4 FMM-1: Typical two-wire initiating circuit configuration for security systems
(with alarm versus short capability).
6720wir4.wmf
Page 4 of 5 — DN-6720
•
•
•
•
•
•
•
Connect modules to listed compatible control panels only.
WIRING
Terminal wiring must be power limited.
DIAGRAMS
DO NOT MIX fire alarm initiating, supervisory, or security devices on the same module.
DO NOT LOOP wire under terminals. Break wire run to provide supervision of connections.
THIS PAGE:
Detectors must be UL listed compatible with module.
FZM-1, FRM-1
Install detectors per manufacturers’ installation instructions.
Power to the interface module must be externally switched to reset the detectors. An FRM-1 relay control module can be
used to switch power from a standard power supply; see Fig. 7 below.
Fig. 5 FZM-1: Interface two-wire conventional detectors, NFPA Style B.
6720wir5.wmf
Fig. 6 FZM-1: Interface two-wire conventional detectors, NFPA Style D.
6720wir6.wmf
Fig. 7 FRM-1: Relay control module used to disconnect a power supply.
6720wir7.wmf
DN-6720 — Page 5 of 5