CDL-BMS01 This interface is for connection to a Toshiba indoor unit

CDL-BMS01 Interface.
CDL-BMS01
This interface is for connection to a Toshiba indoor unit from the Digital Inverter, Super
Digital Inverter or VRF range of units.
One interface with four options.
Remote ON / OFF.
Remote Controller Locking, (Wired versions only).
Indication of Operation
Indication of “Lock Out” (Stopping) Fault
The interface connects to the CN61 socket on the indoor printed circuit board, the installer
is then required to provide and connect to other switching or display devices.
Drawing No.
Revision No.
Drawn By.
Date.
CDL-BMS01 Interface.
C
N
6
1
ON/OFF Control
This will switch the individual indoor units on or off depending
Upon the status of the contact. N/C = ON, N/O = OFF
Red
Green
1
2
3
4
5
6
White
Yellow
Blue
Black
Cut “jumper” J01 /JP001 on indoor PCB
Switch a “Dry Contact” i.e. NO Volt. Across the
RED and GREEN Wires of the CDL-BMS01 interface.
Indoor PCB
1 2 3 4 5 6
CN61
C
N
6
1
System
ON
Red
Green
1
2
3
4
5
6
White
Yellow
Blue
Black
Field Supplied
Remote Controller Lock
This will display a “Locked” symbol on the remote controller
And prevent alterations from the previous operating condition.
J01 / JP001
Switch a “Dry Contact” i.e. NO Volt. Across the
GREEN and WHITE Wires of the CDL-BMS01 interface
C
N
6
1
System
Locked
Red
1
2
3
4
5
6
Green
White
Yellow
Blue
Black
Field Supplied
Remote ON/OFF With Remote Controller Lock
This will display a “Locked” symbol on the remote controller
And prevent alterations from the previous operating condition.
Cut “jumper” J01/JP001 on indoor PCB
Switch a “Dry Contact” i.e. NO Volt. Across the
RED and GREEN Wires of the CDL-BMS01 interface.
“Link” the GREEN and the WHITE together
Sample VRF PCB
Sample RAV SM
C
N
6
1
Red
Green
1
2
3
4
5
6
White
Yellow
Blue
Black
Link Green and White to Remove
Remote Controller ON/OFF function
NOTE 1
Extreme caution must be used when using this accessory, as incorrect
connection will result in damage to the indoor PCB.
Drawing No. CDL-BMS01
Revision No.
003
Drawn By.
PB
Date.
System
ON
21-07-15
Field Supplied
CDL-BMS01 Interface.
C
N
6
1
Red
Green
1
2
3
4
5
6
White
Yellow
Unit Operation Output (Note 1)
Blue
Black
Field Supplied
This output will be enabled when the unit is OPERATIONAL
Indoor PCB
1 2 3 4 5 6
CN61
Connect a “LOW CURRENT - 12VDC 20mA” relay coil.
Across the YELLOW and BLUE Wires of the CDL-BMS01 interface
N/O
N/C
12VDC 20mA
C
N
6
1
J01 / JP001
Red
1
2
3
4
5
6
Green
White
Yellow
-Ve
Blue
Black
+Ve
Unit Error Output (Note 1)
Field Supplied
This output will be enabled when the unit has a “Lock Out” fault.
N/O
Connect a “LOW CURRENT - 12VDC 20mA” relay coil.
Across the BLACK and BLUE Wires of the CDL-BMS01 interface
N/C
12VDC 20mA
C
N
6
1
Sample VRF PCB
Red
1
2
3
4
5
6
Green
White
Yellow
Blue
-Ve
Sample RAV SM
NOTE 1
Extreme caution must be used when using this accessory, as incorrect
connection will result in damage to the indoor PCB.
Drawing No. CDL-BMS01
Revision No.
003
Drawn By.
PB
Date.
+Ve
Black
21-07-15
CDL-BMS01
Interface.
Contact Details.
Cool Designs Ltd – North East
Unit 8, North Hylton Enterprise Park
Hepworth Road
North Hylton
Sunderland
SR5 3JT
Cool Designs Ltd – North West
Unit 16, Cranford Court
Hardwick Grange
Woolston
Warrington
WA1 4RX
Tel: 0191 549 6964
Fax: 0191 549 6969
Tel: 01925 820 000
Fax: 01925 820 011
Email: sales@cooldesignsltd.co.uk
Web:
nwsales@cooldesignsltd.co.uk
www.cdlweb.info
Cool Designs Ltd – Scotland
Unit 3 Glenburn Court
College Milton
East Kilbride
G74 5BA
Tel: 01355 234 776
Fax: 01355 571 260
Drawing No.
Revision No.
Drawn By.
Date.
Open as PDF
Similar pages