E5AK/E5EK/E5CK Process Controllers

NO:
DATE:
TC-044
June 2011
PRODUCT: E5AK/E5EK/E5CK Process Cont.
TYPE:
Discontinuation Update
E5AK/E5EK/E5CK Process Controllers Discontinued
Immediately, Replace with E5_N-H/E5_N-HT Series
There are modifications in portions of product
discontinuation notice TC-042 May issue.
Changes marked in RED were made to the
following sections:
x Discontinuation date: Effective immediately
x Caution on recommended replacement
x Difference from discontinued product
x Product Discontinuation and recommended
replacement
x Output Specifications of E5ER-DRT in
Recommended replacement.
Omron Industrial Automation will migrate to the E5_N platform to consolidate functionality in a single
product family that shares common parts.
Cautions on Applying Recommended Replacement Models
ƒ
ƒ
ƒ
There is no plug-in SSR output unit for the recommended replacement. Please select the model
with SSR output or drive external SSR by voltage output.
The combination of the outputs on the DeviceNet type is limited to two kinds.
SSR driving output of the replacement of E5CK is NPN. Please do not mistake wiring.
Discontinued Products/Suggested Replacements
E5AK (1/4 DIN size)
Product discontinuation
E5AK-AA2
E5AK-AA2-K
E5AK-AA2-500
E5AK-AA2-K-500
E5AK-PRR2
E5AK-PRR2-K
E5AK-PRR2-500
E5AK-PRR2-K-500
E5AK-TAA2 AC100-240
E5AK-TAA2-500 AC100-240
E5AK-TAA2-K AC100-240
E5AK-TAA2-K-500 AC100-240
E5AK-TPRR2 AC100-240
E5AK-TPRR2-500 AC100-240
E5AK-TPRR2-K AC100-240
E5AK-TPRR2-K-500 AC100-240
Recommended replacement
E5AN-HAA2HBM-500 AC100-240
E5AN-HAA2HHBFM-500 AC100-240
E5AN-HPRR2BM-500 AC100-240
E5AN-HPRR2BFM-500 AC100-240
E5AN-HTAA2HBM-500 AC100-240
E5AN-HTAA2HHBFM-500 AC100-240
E5AN-HTPRR2BM-500 AC100-240
E5AN-HTPRR2BFM-500 AC100-240
1
E5EK (1/8 DIN size)
Product discontinuation
E5EK-AA2
E5EK-AA2-K
E5EK-AA2-500
E5EK-AA2-500-K
E5EK-AA2-DRT AC100-240
E5EK-AA2-DRT-K AC100-240
E5EK-AA2-DRT-500 AC100-240
E5EK-PRR2
E5EK-PRR2-K
E5EK-PRR2-500
E5EK-PRR2-500-K
E5EK-TAA2 AC100-240
E5EK-TAA2-K AC100-240
E5EK-TAA2-500 AC100-240
E5EK-TAA2-K-500 AC100-240
E5EK-TPRR2 AC100-240
E5EK-TPRR2-500 AC100-240
E5EK-TPRR2-K AC100-240
E5EK-TPRR2-K-500 AC100-240
Recommended replacement
E5EN-HAA2HBM-500 AC100-240
E5EN-HAA2HHBFM-500 AC100-240
E5ER-QTB-DRT AC100-240
E5ER-CTB-DRT AC100-240
E5EN-HPRR2BM-500 AC100-240
E5EN-HPRR2BFM-500 AC100-240
E5EN-HTAA2HBM-500 AC100-240
E5EN-HTAA2HHBFM-500 AC100-240
E5EN-HTPRR2BM-500 AC100-240
E5EN-HTPRR2BFM-500 AC100-240
E5CK (1/16 DIN size)
Product discontinuation
E5CK-AA1
E5CK-AA1-K
E5CK-AA1-500 AC100-240
E5CK-AA1-K-500
E5CK-TAA1 AC100-240
E5CK-TAA1-K AC100-240
E5CK-TAA1-500 AC100-240
E5CK-TAA1-K-500 AC100-240
Recommended replacement
E5CN-H__2M-500
__ means R, Q, C or V.
E5CN-HT__2M-500
__ means R, Q, C or V.
E53 Output units and Option units of E5AK, E5EK and E5CK series
Product discontinuation
E53-AKF
E53-AKF-K
E53-R4R4
E53-Q4R4
E53-Q4HR4
E53-C4R4
E53-C4DR4
E53-V44R4
E53-Q4Q4
E53-Q4HQ4H
E53-CK01
E53-CK03
E53-CKB
E53-CKF
E53-CKF-K
Recommended replacement
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
For E5_K series and E5_N-H series, option units or output units are necessary.
In another sheet "From E5_K to E5_N-H replace table", you can see replacement comparison
including option units or output units.
2
Detailed Comparison
Dimensions (mm)
Product discontinuation
Recommended replacement
Main Body
E5AK
Main Body
E5AN-H
E5EK
E5EN-H
E5ER-DRT
99
3
Product discontinuation
Recommended replacement
E5CK
E5CN-H
Ƒ48
Terminal Cover for E5AN-H/E5EN-H
E53-COV16
Terminal Cover for E5AK
E53-COV0809
:LWKULYHW
Terminal Cover for E5ER
E53-COV15
Terminal Cover for E5EK
E53-COV08
4
84
78
Product discontinuation
Terminal Cover for E5CK
E53-COV07
Recommended replacement
Terminal Cover for E5CN-H
E53-COV17
:LWKULYHW
Mounting Bracket (Prepackaged)
E5AK/E5EK
Mounting Bracket (Prepackaged)
E5AN-H/E5EN-H
Note: Mounting bracket for E5AK/E5EK can not be use for
E5_N-H.
Wire Connection
Product discontinuation
Terminal Arrangement
E5AK
Recommended replacement
Terminal Arrangement
E5AN-H
5
Product discontinuation
Terminal Arrangement
E5EK
Recommended replacement
Terminal Arrangement
E5EN-H
E5ER-DRT
,QSXWSRZHU
VXSSO\
,QSXWSRZHU
Input
power
VXSSO\
supply
Auxiliary
outputs
E5CN-H
E5CK
6
Product discontinuation
Recommended replacement
Types of Terminal Block
• Which way to pull out the wire: Horizontally against the block
Types of Terminal Block
• Which way to pull out the wire: with 15 degrees of
gradient against the block
Characteristics
Product discontinuation
Recommended replacement
Indication accuracy
E5AK/E5EK/E5CK
• Thermocouple:
(±0.3%PV or ±1°C)±1 digit
• Platinum resistance thermometer: Pt100, JPt100
(±0.2%PV or ±0.8°C) ±1 digit
• Analog input: ±0.2% FS ±1 digit
Indication accuracy
E5AN-H/E5EN-H/E5CN-H/E5ER-DRT
• Thermocouple:
(±0.1%PV or ±1°C)±1 digit
• Platinum resistance thermometer: Pt100, JPt100
(±0.1%PV or ±0.8°C) ±1 digit
• Analog input: ±0.1% FS ±1 digit
Output Specifications
E5AK/E5EK
ዘCurrent output
Resolution: Approx. 2600
ዘOutput unit (Order separately)
Output Specifications
E5AN-H/E5EN-H
ዘCurrent output
Resolution: Approx. 10000
ዘOutput unit (Order separately)
No.
1
2
3
4
5
6
7
8
9
Models
E53-R
E53-S
E53-Q
E53-Q3
E53-Q4
E53-C3
E53-C3D
E53-V34
E53-V35
Outp t Type
Relay
SSR
Voltage(for driving SSR)
Voltage(for driving SSR)
Voltage(for driving SSR)
Current (4 to 20mA)
Current (0 to 20mA)
Linear voltage(0 to 10V)
Linear voltage(0 to 10V)
No.
1
2
3
4
5
6
7
8
9
7
Models
E53-RN
None
E53-QN
E53-Q3
E53-Q4
E53-C3N
E53-C3DN
E53-V34N
E53-V35N
Output Type
Relay
SSR
Voltage(for driving SSR)
Voltage(for driving SSR)
Voltage(for driving SSR)
Current (4 to 20mA)
Current (0 to 20mA)
Linear voltage(0 to 10V)
Linear voltage(0 to 10V)
Product discontinuation
Output Specifications
E5CK
• Control output 1
Resolution for current/linear voltage output:
Approx. 2600
Load for current output: 500: max.
Linear current output: 4 to 20mA
Linear voltage output: 0 to 10 VDC, Load 1k: min
Voltage output: 12VDC, 20mA, NPN
Relay output: SPST-NO, 250VAC, 3A (resistive load)
• Control output 2
Voltage output: 12 VDC, 20mA, NPN
Relay output: SPST-NO, 250 VAC, 3A (resistive load)
• Auxiliary output
Relay output: SPST-NO, 250 VAC ,1A (resistive load)
(1 output)
Recommended replacement
Output Specifications
E5CN-H
• Control output 1
Resolution for current/linear voltage output:
Approx. 10000
Load for current output: 600: max.
Linear current output: 4 to 20mA
Linear voltage output: 0 to 10 VDC, Load 1k: min
Voltage output: 12 VDC, 21mA, PNP
Relay output: SPST-NO, 250 VAC, 3A (resistive load)
• Control output 2
Voltage output: 12 VDC, 21mA, PNP
Relay output: SPST-NO, 250 VAC, 3A (resistive load)
• Auxiliary output
Relay output: SPST-NO, 250 VAC ,3A (resistive load)
(2 outputs)
E5ER-DRT
• Control output
Resolution for current/linear voltage output:
Approx. 43000
Load for current output: 500˖ max.
Linear current output: 4 to 20mA
Voltage output: 12VDC, 40mA, PNP
Relay output: SPST-NO, 250VAC, 1A(inductive load)
ዘAuxiliary output
Relay output: SPST-NO, 250VAC, 1A(resistive load)
Transistor output: 30VDC, 50mA, NPN
Transfer output
E5AN-H/E5EN-H/E5CN-H
• Resolution: Approx. 10000
• Load: 600: max
E5ER-DRT
• Resolution: Approx. 43000
• Load: 500: max
Transfer output
E5AK/E5EK/E5CK
• Resolution: Approx. 2600
E5AK/E5EK
• Load: 600: max
E5CK
• Load: 500: max
Sampling period
E5AK/E5EK/E5CK
• Temperature input: 250ms
• Analog input: 100ms
Sampling period
E5AN-H/E5EN-H/E5CN-H
• Temperature input: 60ms
• Analog input: 60ms
E5ER-DRT
• Temperature input: 50ms
• Analog input: 50ms
Temperature effect on signal source resistance
E5AK/E5EK/E5CK
• Thermocouple (K, J ,T, E, L, N, U): 0.1qC/:
• Thermocouple (B, R, S): 0.2qC/:
• Platinum resistance thermometer: 0.4qC/:
Temperature effect on signal source resistance
E5AN-H/E5EN-H/E5CN-H
• Thermocouple: 0.1qC/:
• Platinum resistance thermometer: 0.1qC/:
Event input
E5AN-H/E5EN-H
• Event input: 4 max
E5CN-H
• Event input: 2 max
Event input
E5AK/E5EK/E5CK
• Event input: 2 max
8
Product discontinuation
Recommended replacement
Communications
E5AK/E5EK/E5CK
• Baud rate: 1200/2400/4800/9600/19200 bps
• Communication protocol: Sysway (For E5_K)
Sysway (X format)
Communications
E5AN-H/E5EN-H/E5CN-H
• Baud rate: 1200/2400/4800/9600/19200/38400/57600bps
• Communication protocol: Sysway (X format)
CompoWay/F, Modbus
Heater burnout, Heater overcurrent detection
E5AK/E5EK
• Heater burnout detection (For Single-phase)
Heater burnout, Heater overcurrent detection
E5AN-H/E5EN-H
• Heater burnout detection (For Three-phase)
• Heater overcurrent detection (For Three-phase)
E5CN-H
• Heater burnout detection (For Single-phase/Three-phase)
• Heater overcurrent detection
(For Single-phase/ Three-phase)
E5CK
None
Program capacity
E5AK-T
8 patterns, 16 steps
E5EK-T/E5CK-T
4 patterns, 16 steps
Program capacity
E5AN-HT/E5EN-HT/E5CN-HT
8 patterns, 32 steps
Program method
E5AK-T/E5EK-T/E5CK-T
Time or ramp setting method
Program method
E5AN-HT/E5EN-HT/E5CN-HT
Time or ramp setting method
9
Display and Operation Methods
Product discontinuation
Recommended replacement
Front panel
E5Aᨊ-H/E5EN-H
Front panel
E5AK/E5EK
/('GLVSOD\V
/('GLVSOD\V
/᧿ᨀ
/᧿ᨀ
0RGH
0RGH
$0
'RZQ
0RGHNH\
8SNH\
'RZQ
/HYHO
8SNH\
/HYHO
$0NH\
3) NH\
$0NH\
ᇳE5AK/E5EKᇴ
PV᧶4 digits (Red Constant),
Letter height: 15mm
SV᧶4 digits (Green Constant)
'RZQNH\
'RZQ
0RGH
8SNH\
ᇳE5Aᨊ/E5Eᨊᇴ
PV᧶5 digits (Red/Green/Orange Selectable)
Letter height: 15.8mm
SV᧶5 digits (Green constant)
MV᧶4 digits (Orange Constant)
10
8SNH\
3) NH\
$0NH\
Product discontinuation
Recommended replacement
Front panel
E5ER-DRT LCDGLVSOD\V
PV᧶5 digits (Red Const.)
Letter height 9.5mm
SV᧶5 digits (Green Const)
MV᧶4 digits (Orange Const.)
/HYHO
'RZQ
0RGH
8SNH\
PF key 1/
A/M key
Front panel
E5CK
PF key 2/
Channel key
Front panel
E5CN-H
/('GLVSOD\V
/&'GLVSOD\V
8SNH\
$0NH\
0RGH
8SNH\
'RZQNH\
/HYHO
0RGH
PV᧶4 digits (Red Constant), Letter height 12mm
SV᧶4 digits (Green Constant)
'RZQ
PV᧶5 digits (Red/Green/Orange Selectable), Letter height
12mm
SV᧶5 digits (Green Constant)
11
Product discontinuation
Recommended replacement
Body Draw out
E5EK
Body Draw out
E5EN-H
Tool insertion hole
E5ER-DRT
You do not need to draw out in standard use. Please draw
out by the method similar to E5AN-H/ E5EN-H when you
maintain it.
Body Draw out
E5CN-H
Body Draw out
E5CK
(1) Pull out the internal mechanism while pressing the hooks
on the left and right sides of the front panel.
(2) Draw out the internal mechanism towards you holding both
sides of the front panel.
(1) Insert a flat-blade screwdriver into the two tool insertion holes
(one on the top and one on the bottom) to release the hooks.
(2) Insert the flat-blade screwdriver in the gap between the front
panel and rear case, and pull out the front panel slightly. Hold the
top and bottom of the front panel and carefully pull it out toward you,
without applying unnecessary force.
(3) When inserting the body of the Digital Controller into the case,
make sure the PCBs are parallel to each other, make sure that the
sealing rubber is in place, and press the E5CN-H all the way to the
rear case. While pushing the E5CN-H into place, push down on the
hooks on the top and bottom surfaces of the rear case so that the
hooks are securely locked in place. Be sure that electronic
components do not come into contact with the case.
12
Product discontinuation
Recommended replacement
Jumper Settings
E5CK
• After setting the input type by jumper, parameter can be set
when an analog input is selected.
• Set the input type by jumper to any one of temperature input,
voltage input or current input matched to the sensor
connected to the input terminal.
Jumper Settings
E5CN-H
Setting the input type only by parameters due to no jumper.
Reference Documents
Description
E5_K Series Documents
E5AK/E5EK Data Sheet
E5CK Data Sheet
E5AK Users Manual
E5CK Users Manual
E5EK Users Manual
E5AK-T Users Manual
E5EK-T Users Manual
E5CK-T Users Manual
E5EK-DRT Users Manual
E5_N-H Series Documents
E5_N-H Data Sheet
E5_N-H Users Manual
E5_N-H Communications Manual
E5_N-HT Series Documents
E5AN-HT/E5EN-HT Data Sheet
E5CN-HT Data Sheet
E5_N-HT Users Manual
E5_N-HT Communications Manual
Media
Publication Number
PDF
PDF
PDF
PDF
PDF
PDF
PDF
PDF
PDF
H084-E1-05
H079-E1-06
H083-E1-03
H078-E1-03D
H085-E1-03
H088-E1-02
H089-E1-02
H090-E1-01B
H099-E1-02
PDF
PDF
PDF
H160-E1-01A
H157-E1-03
H159-E1-02
PDF
PDF
PDF
PDF
CSM_E5AN-HT_E5EN-HT_DS_E_1_1
CSM_E5CN-HT_DS_E_1_1
H169-E1-01
H170-E1-01
13
Open as PDF
Similar pages