product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Lutron Thermostat Controls are the perfect
complement to light and shade / drapery
systems. Add Lutron Thermostat Controls
to your light and shade / drapery systems
for convenient control of all aspects of an
environment - lights, shades / draperies, and
temperature - from the touch of a button. Lutron
Thermostat Controls allow heating and cooling
systems to integrate seamlessly with Lutron
systems and must be located within 30 ft (9 m)
of an RF signal repeater.
Lutron Thermostat Controls put temperature
control and measurement where it makes
sense and allows the ability to adjust heating
and cooling systems any time of the day - even
when you’re away from home.
HVAC Controller
Lutron Thermostat Controls help optimize
energy savings without complicated
programming. Conveniently press the “eco”
button to trim HVAC settings automatically. The
“eco” button trim is controlled by RadioRA® 2
systems.
Lutron Thermostat Controls are easy to use and
provide superior product quality and aesthetics.
Model Numbers
LR-HVAC-1-WH*
HVAC Controller
LRD-WST-F-XX**
seeTempTM Wall Display (°F)
LRD-WST-C-XX**
seeTemp Wall Display (°C)
LRF2-TWRB-XX*** Wireless Temperature
Sensor
seeTemp Wall Display
*Only available in White (WH).
**Available in 26 colors. Please see page 10 for color selections.
***Available in Snow (SW) and Midnight (MN).
Wireless Temperature
Sensor
www.lutron.com
Lutron® | 1
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Specifications
Model Numbers
HVAC Controller: LR-HVAC-1-WH
seeTempTM Wall Display: LRD-WST-F-XX, LRD-WST-C-XX
Wireless Temperature Sensor: LRF2-TWRB-XX
Power
HVAC Controller: 24 V
NEC® Class 2 / PELV
50 / 60 Hz or 24 V NEC Class 2 / PELV
seeTemp Wall Display: 120 V
Wireless Temperature Sensor: 3 V
(one CR2450 battery included –
5 year lifetime)
Typical Power
Consumption
HVAC Controller: 3 W; Test conditions: one LED on
seeTemp Wall Display: 1 W (120 V ), 0.5 W (24 V ); Test conditions:
all backlights on medium intensity, two LEDs on
Regulatory Approvals
HVAC Controller: UL, cUL, FCC, and SCT
seeTemp Wall Display: UL, cUL, FCC, and SCT
WirelessTemperature Sensor: UL, FCC, and IC
Environment
HVAC Controller:
Ambient operating temperature: 32 °F to 160 °F (0 °C to 71 °C),
0% to 90% humidity, non-condensing. Indoor use only.
seeTemp Wall Display and Wireless / Wired Temperature Sensor:
Ambient operating temperature: 32 °F to 104 °F (0 °C to 40 °C),
0% to 90% humidity, non-condensing. Indoor use only.
Communications
Thermostat controls communicate with the system through Radio Frequency
(RF) and must be located within 30 ft (9 m) of a signal repeater. System
devices operate on frequencies between 431.0 MHz and 437.0 MHz.
ESD Protection
Tested to withstand electrostatic discharge without damage or memory
loss, in accordance with IEC 61000-4-2.
Surge Protection
Tested to withstand surge voltages without damage or loss of operation,
in accordance with IEEE C62.41-1991 Recommended Practice on
Surge Voltages in Low-Voltage AC Power Circuits.
Power Failure
Power failure memory: should power be interrupted, the thermostat
controls will return to their previous state when power is restored.
Mounting
HVAC Controller: Mount on a wall, ceiling, or level surface using the two
#6 (M3) screws included.
seeTemp Wall Display: U.S. wallbox 3 ½ in (89 mm) deep
recommended, 2 ¼ in (57 mm) deep minimum.
Wireless Temperature Sensor: One 3MTM CommandTM adhesive strip
is provided for temporary mounting and testing. One wall anchor and
screw provided for permanent mounting.
Wired Temperature Sensor: Mount in return duct using the supplied screws.
Wiring
HVAC Controller: Requires transformer common NEC Class 2 / PELV,
22 AWG (0.5 mm2) to 18 AWG (0.75 mm2) solid wiring.
seeTemp Wall Display: 120 V requires hot and neutral wiring;
24 V requires transformer common NEC Class 2 / PELV, 22 AWG
(0.5 mm2) to 18 AWG (0.75 mm2) solid wiring.
Wired Temperature Sensor: NEC Class 2 / PELV, 22 AWG (0.5 mm2) to
18 AWG (0.75 mm2) solid wiring. Maximum wire length is 100 ft (30.5 m).
Warranty
1 Year Limited Warranty if installed by climate control specialist.
http://www.lutron.com/resiinfo
2 | Lutron®
24/7 Technical Support—800.523.9466
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Design Features
HVAC Controller
Connects to mechanical HVAC equipment.
•
Uses RF to communicate to the Wireless
Temperature Sensors, seeTempTM Wall
Displays, and other Lutron wireless devices. •
Use up to 4 HVAC Controllers per RadioRA® 2
Main Repeater.
Wireless Temperature Sensor
Flexible mounting options require no wiring.
•
5 year battery life.
•
Use up to 4 Wireless Temperature Sensors per
HVAC Controller.
•
•
Multiple sensor averaging possible.
•
Communicates to Wireless Temperature
Sensors, seeTempTM Wall Displays, and other
Lutron wireless devices.
•
Requires 24 V
transformer.
•
wiring from HVAC equipment
Requires 1 Wired Temperature Sensor per
HVAC Controller as a backup sensor. Wired
Temperature Sensor is included with the HVAC
Controller and should be mounted in the return
air duct.
•
seeTemp Wall Display
Designer style opening that can be ganged
with other devices like dimmers and keypads.
•
Installs in a standard wallbox for low-profile
appearance.
•
Celsius and Fahrenheit models available.
•
Multiple seeTemp Wall Displays can be used
to control 1 HVAC Controller from multiple
locations.
•
“eco” button saves energy by trimming the
temperature a programmed amount (default is
+/- 2 degrees.)
•
120 V
•
wiring requires hot and neutral wiring.
24 V wiring requires 24 V and common
wiring from HVAC equipment transformer or
other 24 V NEC® Class 2 / PELV transformer.
•
www.lutron.com
Lutron® | 3
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Compatability
HVAC Type
Compatible?
Single Stage Cool
Yes
Two Stage Cool
Yes
Single Stage Heat
Yes
Two Stage Heat
Yes
Packaged Roof Top Units
Yes
Heat Pump with Changeover to Cool
Yes
Heat Pump with Changeover to Heat
Yes
Geothermal Heat Pump
Yes
Heat Pump with Auxiliary Heat
Yes
Typical Variable Speed Fan (Equipment
Controlled)
Yes
Multi-Zone Systems (Controllable Dampers)
Yes - Requires a separate Zone Controller
(not sold by Lutron)
In-Floor Radiant Heat
Yes
Line Voltage Electric Baseboard
No
Mili-Volt System
No
Proprietary Control systems
No
Variable Speed Fan (Independent Relays)
No
Humidity Control
No
Humidity Sensing
No
Outdoor Temperature Sensing
No
4 | Lutron®
24/7 Technical Support—800.523.9466
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Dimensions
All dimensions are shown as in unless otherwise noted.
(mm)
seeTempTM Wall Display
HVAC Controller
Front View
Side
View
6 1⁄4
(159)
Side
View
Front
View
HVAC Controller
Room Set
80°
75°
4 11⁄16
(119)
HVAC System Status
O/B
W1 W2 G
5 ⁄4
(133)
1
Y1
Y2
1/4
(6)
Wireless Sensor Status
Active
Low
Battery
Test
Link
Setup
2 3⁄4
(70)
Equipment Type
J1 J2
O/B
C Rc Rh W1 W2 G Y1 Y2
2 1
RS485
Mounting Holes
3 3⁄4
(95)
eco
60°
2 15⁄16
(75)
Wired
Sensor
R1 R2
65°
LUTRON
Off Off
Conventional - Gas/Oil
Off On
Conventional - Electric
Heat Pump - Changeover Cool On Off
Heat Pump - Changeover Heat On On
Rc/Rh Power HVAC Out
Jumper 24 V
70°
1 1⁄4
(31)
5/16
(8)
1 1⁄16
(27)
4 1⁄4
(108)
Wireless Temperature Sensor
Side View
Front View
Wired Temperature Sensor
Front View
13/16
(21)
9/16
(15)
Test
Link
1 5⁄8
(41)
Side View
3/4
(18)
2 1⁄4
(58)
12 ft
(3.7 m)
1/4 (6)
www.lutron.com
Lutron® | 5
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Mounting and Parts Identification
HVAC Controller
Vertical
Horizontal
Ceiling
Wall
#6 (M3) screw
recommended
(2 included)
Level Surface
seeTempTM Wall Display
Adapter
seeTemp
Mounting Wallplate Mounting Wallplate
Screws Adapter Screws
Wallbox
seeTemp
Wall
Display
Wallplate Adapter / Wallplate
purchased separately.
Wireless Temperature Sensor
Sensor
Link
Mounting
Bracket
Screw
Wired Temperature Sensor
Mounting
Bracket
Mounting
Flange
Sensor
Test
Mounting
Holes
6 | Lutron®
24/7 Technical Support—800.523.9466
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Operation
HVAC Controller
HVAC System Status LEDs
Indicate the status of the control outputs. When an LED is lit the
corresponding relay is closed.
W1 - Heat stage 1, auxiliary heat
W2 O/B - Heat stage 2, changeover valve
G - Fan
Y1 - Compressor stage 1
Y2 - Compressor stage 2
HVAC Controller
Controller
HVAC
HVAC System Status
HVACO/B
System Status
W1
W1 W2
W2 GG Y1Y1 Y2Y2
O/B
Wireless Sensor Status
Remote Sensor Status
Low
Active
Setup
Setup
Battery
Active
Battery Low
HVAC System Status
Link
Link
Test
Equipment Type
O/B
W1 W2 G
2 1
Off Off
Conventional - Gas/Oil
Off On
Conventional - Electric
Heat Pump - Changeover Cool On Off
Heat Pump - Changeover Heat On On
HVAC Out
Out
Rc/Rh Power
Power HVAC
Rc/Rh
Jumper2424
Jumper
VV
J1 J2
O/B
O/B
W2 G Y1 Y2
C Rc Rh W1
C Rc Rh W1 W2 G Y1 Y2
Setup
Wired
Remote
Sensor
Sensor
R1 R2
R1 R2
Y2
Y1
RS485
RS485
Wireless Sensor Status
S1 S2
Low
Battery
Active
Setup
Test
Link
Wireless Sensor Status LEDs
Active - LED flashes slowly if at least 1 Wireless Temperature Sensor
is active. LED is on solid if all Wireless Temperature Sensors are active.
Low Battery - LED flashes slowly to indicate that at least one
associated Wireless Temperature Sensor has a low battery.
Test and Link Buttons
Press and hold to troubleshoot (Test) and
set up (Link) the RF connection.
Test and Link LEDs
Flashes green to indicate that the system
is in Test mode or Link mode.
seeTempTM Wall Display
Room Temperature LEDs
Column of red LEDs that display
the current room temperature.
Set Temperature LEDs
Column of green LEDs that display the
current temperature set point. Set LED
turns off when system is turned off.
Room Set
System Buttons
Indicates the current system
setting. When selected, buttons
will light up according to the
following:
Heat - Red
Cool - Blue
Auto - Orange
Off - Orange
80°
Raise/Lower Rocker
Press to raise the Set temperature.
75°
70°
Press to lower the Set temperature.
65°
Eco Button
Press to toggle Eco mode on/off.
eco
60°
Heat
Cool
Auto
Off
Fan
On
Auto
Fan Buttons
Indicates the current fan setting. Button will light
up orange when selected.
On - Fan is constantly on.
Auto - Fan is on only when Heat/Cool is active.
Flip-Down Door
Covers the System and Fan
Buttons. Opens 180°.
Wireless Temperature Sensor
Link Button
Press and hold to assign a
seeTemp Wall Display.
www.lutron.com
Link
Test
Test Button
Press to test system functionality
Lutron® | 7
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Wiring Diagrams
HVAC Controller
Relay Contact Ratings
Voltage
Note: HVAC Controller must be wired by a
qualified HVAC climate control specialist.
Power 24 V (from HVAC
system transformers)
NEC® Class 2 / PELV cable
Heat Transformer - Rh
Cool Transformer - Rc
Common - C
Up to 24 V
Resistive
Load
1A
Inductive
Load
0.1 A
HVAC Out
Terminal connections for connecting to
the HVAC system
W1 - Heat stage 1, auxiliary heat
W2 O/B - Heat stage 2, changeover valve
G - Fan
Y1 - Compressor stage 1
Y2 - Compressor stage 2
Rc/Rh Jumper
Required in single
transformer systems
Wired Sensor
Connection for required wired sensor.
Maximum 100 ft (30.5 m)
RS485 Connector
Lutron use only.
ON
On
1 2
Off
Contact Closure Terminal Blocks
NEC Class 2 / PELV cable Maximum 1000 ft (305 m)
Each terminal holds one 22 AWG
(0.5 mm2) to 18 AWG (0.75 mm2) wire.
HVAC Setup
2 dipswitches for selecting
HVAC system type
Equipment Type
Conventional - Gas/Oil
Conventional - Electric
Heat Pump - Changeover Cool
Heat Pump - Changeover Heat
2
Off
Off
On
On
1
Off
On
Off
On
Continued on next page...
8 | Lutron®
24/7 Technical Support—800.523.9466
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Wiring Diagrams (continued)
Conventional Systems
Conventional Gas/Oil Heat System • 1 Stage Heat / 1 Stage Cool
Transformer
Jumper
Fan Relay
Compressor
Off
Heat
Stage 1
Off
ON
1 2
Rc Rh
C Rc Rh W1 W2 G Y1 Y2
S2 S1
Conventional Electric Heat System • 1 Stage Heat / 1 Stage Cool
Transformer
Jumper
Fan Relay
Compressor
Off
Heat
Stage 1
On
ON
1 2
Rc Rh
C Rc Rh W1 W2 G Y1 Y2
S2 S1
Conventional Gas/Oil Heat System • 2 Stage Heat / 2 Stage Cool
Heat
Stage 1
Heat
Stage 2
Transformer
Compressor
Stage 1
Fan Relay
Compressor
Stage 2
Off
Off
Jumper
ON
C Rc Rh W1 W2 G Y1 Y2
1 2
Rc Rh
S2 S1
Continued on next page...
www.lutron.com
Lutron® | 9
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Wiring Diagrams (continued)
Conventional Systems (continued)
Conventional Electric Heat System • 2 Stage Heat / 2 Stage Cool
Heat
Stage 1
Heat
Stage 2
Compressor
Stage 1
Transformer
Compressor
Stage 2
Fan Relay
Off
On
Jumper
ON
1 2
Rc Rh
C Rc Rh W1 W2 G Y1 Y2
S2 S1
Conventional Gas/Oil Heat System • 1 Stage Heat / 1 Stage Cool, 2 Transformers
Cool
Transformer
Heat
Transformer
Heat
Stage 1
Compressor
Fan Relay
Off
Off
ON
1 2
Rc Rh
C Rc Rh W1 W2 G Y1 Y2
S2 S1
Conventional Electric Heat System • 1 Stage Heat / 1 Stage Cool, 2 Transformers
Cool
Transformer
Heat
Transformer
Heat
Stage 1
Compressor
Fan Relay
Off
On
ON
C Rc Rh W1 W2 G Y1 Y2
1 2
Rc Rh
S2 S1
Continued on next page...
10 | Lutron®
24/7 Technical Support—800.523.9466
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Wiring Diagrams (continued)
Conventional Systems (continued)
Conventional Gas/Oil Heat System • 2 Stage Heat / 2 Stage Cool, 2 Transformers
Cool
Transformer
Heat
Transformer
Heat
Stage 1
Heat
Stage 2
Fan Relay
Compressor
Stage 2
Compressor
Stage 1
Off
Off
ON
1 2
Rc Rh
C Rc Rh W1 W2 G Y1 Y2
S2 S1
Conventional Electric Heat System • 2 Stage Heat / 2 Stage Cool, 2 Transformers
Cool
Transformer
Heat
Transformer
Heat
Stage 1
Heat
Stage 2
Fan Relay
Compressor
Stage 2
Compressor
Stage 1
Off
On
ON
C Rc Rh W1 W2 G Y1 Y2
1 2
Rc Rh
S2 S1
Continued on next page...
www.lutron.com
Lutron® | 11
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Wiring Diagrams (continued)
Heat Pump Systems
Single Stage Heat Pump (Changeover = Cool)
Transformer
Changeover
Valve
Compressor
Fan Relay
On
Off
Jumper
ON
1 2
Rc Rh
C Rc Rh W1 W2 G Y1 Y2
S2 S1
Single Stage Heat Pump (Changeover = Heat)
Transformer
Changeover
Valve
Compressor
Fan Relay
On
On
Jumper
ON
1 2
Rc Rh
C Rc Rh W1 W2 G Y1 Y2
S2 S1
Single Stage Heat Pump w/ Auxiliary Heat (Changeover = Cool)
Transformer
Changeover
Valve
Auxilary
Heat
Fan Relay
Compressor
On
Off
Jumper
ON
C Rc Rh W1 W2 G Y1 Y2
1 2
Rc Rh
S2 S1
Continued on next page...
12 | Lutron®
24/7 Technical Support—800.523.9466
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Wiring Diagrams (continued)
Heat Pump Systems (continued)
Single Stage Heat Pump w/ Auxiliary Heat (Changeover = Heat)
Transformer
Changeover
Valve
Auxilary
Heat
Fan Relay
Compressor
On
On
Jumper
ON
1 2
Rc Rh
C Rc Rh W1 W2 G Y1 Y2
S2 S1
2 Stage Heat Pump w/ Auxiliary Heat (Changeover = Cool)
Transformer
Changeover
Valve
Auxilary
Heat
Fan Relay
Compressor
Stage 2
Compressor
Stage 1
On
Off
Jumper
ON
1 2
Rc Rh
C Rc Rh W1 W2 G Y1 Y2
S2 S1
2 Stage Heat Pump w/ Auxiliary Heat (Changeover = Heat)
Transformer
Changeover
Valve
Auxilary
Heat
Fan Relay
Compressor
Stage 2
Compressor
Stage 1
On
On
Jumper
ON
C Rc Rh W1 W2 G Y1 Y2
1 2
Rc Rh
S2 S1
Continued on next page...
www.lutron.com
Lutron® | 13
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Wiring Diagrams (continued)
seeTempTM Wall Display
120 V
Wiring
NOTE: Orientation arrow MUST point UP.
Black
Hot/Live
Green
Ground
Room Set
80°
75°
120 V
50 / 60 Hz
70°
65°
eco
60°
LUTRON
Neutral
24 V
White
Wiring
24 V
From HVAC
Equipment
NOTE: Orientation arrow MUST point UP.
Black
Green
*
Room Set
80°
*Cap ground wire for 24 V
75°
24 V
50 / 60 Hz
wiring applications.
70°
65°
eco
60°
LUTRON
Common
White
Wired Temperature Sensor
24 AWG (0.25 mm2)
stranded wire.
1/4
(6)
14 | Lutron®
24/7 Technical Support—800.523.9466
product specifications
369-272a
12.02.10
Lutron Thermostat Controls
Colors and Finishes
Gloss Finishes
Satin Finishes
White
WH
Ivory
IV
Hot
HT
Merlot
MR
Plum
PL
Turquoise
TQ
Almond
AL
Light
Almond
LA
Taupe
TP
Eggshell
ES
Biscuit
BI
Snow
SW
Gray
GR
Brown
BR
Palladium
PD
Midnight
MN
Sienna
SI
Terracotta
TC
Greenbriar
GB
Bluestone
BG
Mocha
Stone
MS
Goldstone
GS
Desert Stone
DS
Stone
ST
Limestone
LS
Black
BL
• D
ue to printing limitations,
colors and finishes shown
cannot be guaranteed
to perfectly match actual
product colors.
• Color chip keychains are
available for more precise
color matching:
Gloss Finishes- DG-CK-1
Satin Finishes - SC-CK-1
Metal Finish (wallplate only)
When using Stainless Steel wallplates,
it is recommended to order the controls
in Black (BL) or Midnight (MN).
Stainless
Steel SS
www.lutron.com
Lutron® | 15