M-Series Single Zone Systems
MSZ-GE wall-mount HEAT pump systems
1.indoor units.................................................................................................................................................MSZ-GE-2
2.Outdoor units.............................................................................................................................................MSZ-GE-3
3.SYSTEM............................................................................................................................................................MSZ-GE-4
3-1. Specifications...................................................................................................................................MSZ-GE-4
3-2. External Dimensions...................................................................................................................... MSZ-GE-11
3-3. Center of Gravity............................................................................................................................MSZ-GE-16
3-4. Electrical Wiring Diagrams.............................................................................................................MSZ-GE-17
3-5. Refrigerant System Diagrams........................................................................................................MSZ-GE-23
3-6. Capacity Correction Curve by Temperature...................................................................................MSZ-GE-28
3-7. Capacity Correction Table by Temperature....................................................................................MSZ-GE-30
3-8. Capacity Correction Curve by Refrigerant Piping Length..............................................................MSZ-GE-34
3-9. Capacity Correction Table by Refrigerant Piping Length...............................................................MSZ-GE-35
3-10. Charge Calculations.....................................................................................................................MSZ-GE-37
3-11. Air Flow Data................................................................................................................................MSZ-GE-38
3-12. Sound Pressure Levels................................................................................................................MSZ-GE-39
3-13. Standard Operation Range..........................................................................................................MSZ-GE-49
3-14. Accessories..................................................................................................................................MSZ-GE-50
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-1
1. INDOOR UNITS
•MSZ-GE06NA-8*
•MSZ-GE09NA-8
•MSZ-GE12NA-8
•MSZ-GE15NA-8
•MSZ-GE18NA-8
•MSZ-GE24NA
*The MSZ-GE06NA-8 is only compatible with the multi-split MXZ heat pump systems.
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-2
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
2. OUTDOOR UNITS
•MUZ-GE09NA
•MUZ-GE12NA
•MUZ-GE15NA-1
•MUZ-GE18NA-1
•MUZ-GE24NA
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-3
3-1. SPECIFICATIONS
• Wall-mounted indoor unit for residential application
• Standard Hybrid Catechin Prefilter and anti-allergy enzyme filter for high air-purification abilities
• Quiet operation
• Updated sleek, compact indoor unit design
• Integrated i-see Sensor automatically adjusts the unit’s operation according to the temperature differences detected
between the floor and the intake air, ensuring optimum comfort and energy usage
• Base heater is available as an option
• Auto fan speed control: Quiet, Low, Medium, High, and Super High
• Hand-held Wireless Remote Controller
• Advanced microprocessor control
• Auto restart following a power outage
• Anti-allergy Enzyme Filter
• Limited warranty: five years parts and seven years compressor
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-4
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS
MSZ-GE06NA-8 MSZ-GE09NA-8 MSZ-GE12NA-8 MSZ-GE15NA-8 MSZ-GE18NA-8
MSZ-GE06NA-8
Model name
Power supply
MSZ-GE09NA-8
V, phase, Hz
208/230, 1, 60
Max. fuse size (time delay)/ Disconnect switch
A
15
Min. circuit ampacity
A
1.0
Blower Motor (ECM)
F.L.A
0.76
Airflow
Super High - High - Med. Low - Quiet
COOL Dry CFM
(Wet)
HEAT Dry
Moisture removal
399-321-237-170-145
(364-286-201-134-109)
CFM
406-321-233-170145
pt./h
–
1.5
2.5
0.82
0.74
0.80
Sensible Heat Factor
Sound level
Cooling
Super High - High - Med. Low - Quiet
Heating
dB(A)
Cond. drain connection O.D.
in.
406-321-237-170-145
45-37-30-22-19
43-37-30-22-19
dB(A)
43-37-30-22-19
5/8
W
Dimensions
MSZ-GE12NA-8
31-7/16
D
in.
9-1/8
H
11-5/8
Weight
Ib.
22
External finish
Munsell 1.0Y 9.2/0.2
Control voltage (by built-in transformer)
12 - 24 VDC
MSZ-GE15NA-8
Model name
Power supply
V, phase, Hz
MSZ-GE18NA-8
208/230, 1, 60
Max. fuse size (time delay)/ Disconnect switch A
15
Min. circuit ampacity
A
1.0
Blower Motor (ECM)
F.L.A
0.76
COOL Dry
Airflow
(Wet)
Super High - High - Med. Low - Quiet
HEAT Dry
CFM
533-420-335-272-205
(498-385-300-237-170)
533-420-339-275-230
( 498-385-304-240-194)
CFM
463-367-304-247-205
512-431-339-275-230
Moisture removal
pt./h
2.7
4.6
0.71
0.75
Sensible Heat Factor
Sound level
Cooling
Super High - High - Med. Heating
Low - Quiet
dB(A)
49-44-38-32-26
49-44-38-33-28
dB(A)
46-40-35-30-26
48-43-38-33-28
Cond. drain connection O.D.
in.
W
Dimensions
D
31-7/16
in.
H
Weight
5/8
9-1/8
11-5/8
Ib.
External finish
22
Munsell 1.0Y 9.2/0.2
Control voltage (by built-in transformer)
12 - 24 VDC
NOTE: Test conditions are based on ARI 210/240.
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-5
3-1. SPECIFICATIONS
MSZ-GE24NA
MSZ-GE24NA
Model name
Power supply
V, phase, Hz
208/230, 1, 60
Max. fuse size (time delay)/ Disconnect switch
A
20
Min. circuit ampacity
A
1.0
Blower Motor (ECM)
F.L.A
0.76
COOL Dry
(Wet)
CFM
738-628-469-388
(661-562-420-347)
HEAT Dry
CFM
406-321-237-170-145
pt./h
5.1
Airflow
Super High - High - Med. Low - Quiet
Moisture removal
Sensible Heat Factor
0.75
Sound level
Super High - High - Med. - Cooling
Low - Quiet
Heating
Cond. drain connection O.D.
dB(A)
53-49-41-34
dB(A)
52-49-41-32
in.
W
Dimensions
D
43-5/16
in.
H
Weight
5/8
9-3/8
12-13/16
Ib.
External finish
37
Munsell 1.0Y 9.2/0.2
Control voltage (by built-in transformer)
12 - 24 VDC
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency
2:
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
Maximum frequency
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-6
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS
MUZ-GE09NA-1 MUZ-GE12NA
Model name
MUZ-GE09NA
MUZ-GE12NA
Cooling 1
Btu/h
9,000
( 3,800 ~ 12,200 )
12,000
( 3,800 ~ 13,600 )
Heating 47 1
Btu/h
10,900
( 4,500 ~ 14,100 )
14,400
( 5,500 ~ 18,100 )
Capacity
Heating 17 2
Btu/h
8,700
11,200
Power consumption
Cooling 1
W
660 (205~1,200)
960 (205~1,300)
Rated (Minimum~Maximum)
Heating 47 1
W
760 (255~1,200)
1,170 (340~1,660)
Power consumption
Heating 17 2
W
950
1,200
EER 1 [SEER] 3
Cooling
13.6 [ 21.0 ]
12.5 [ 20.5 ]
Heating
10.0
10.0
Heating 1
4.20
3.61
Capacity
Rated (Minimum~Maximum)
HSPF IV
4
COP
Power supply
V , phase , Hz
Max. fuse size (time delay)
A
Min. circuit ampacity
A
Fan Motor (ECM)
F.L.A
15
12
12
0.50
KNB073FQDHC
KNB092FQAHC
R.L.A
6.6
6.6
L.R.A
8.2
8.2
Model
Compressor
208/230 , 1 , 60
Refrigeration oil cc.
(Model)
320 (NEO22)
Refrigerant control
Sound level 1
Linear expansion valve
Cooling
dB(A)
46
49
Heating
dB(A)
50
51
W
in.
31-1/2
D
in.
11-1/4
H
in.
21-5/8
Defrost method
Dimensions
Reverse cycle
Weight
Ib.
66
External finish
Munsell 3Y 7.8/1.1
Remote controller
Wireless type
Control voltage (by built-in transformer)
VDC
12 - 24
Refrigerant piping
Refrigerant pipe size
(Min. wall thickness)
Connection method
Between the indoor &
outdoor units
77
Not supplied
Liquid
in.
1/4 (0.0315)
Gas
in.
3/8 (0.0315)
Indoor
Flared
Outdoor
Flared
Height difference
ft.
40
Piping length
ft.
65
Refrigerant charge (R410A)
1 lb. 12 oz.
2 lb. 9 oz.
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency
2:
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
Maximum frequency
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-7
3-1. SPECIFICATIONS
MUZ-GE15NA-1 MUZ-GE18NA-1
Model name
MUZ-GE15NA-1
MUZ-GE18NA-1
Cooling 1
Btu/h
14,000
( 3,100 ~ 18,200 )
17,200
( 3,700 ~ 18,700 )
Heating 47 1
Btu/h
18,000
( 4,800 ~ 20,900 )
21,600
( 3,500 ~ 25,200 )
Capacity
Heating 17 2
Btu/h
15,900
17,200
Power consumption Rated
Cooling 1
W
1,080 (160 ~ 2,000)
1,640 (240 ~ 2,070)
(Minimum~Maximum)
Heating 47 1
W
1,600 (270 ~ 2,010)
1,900 (230 ~ 2,680)
Power consumption
Heating 17 2
W
1,950
2,080
EER 1 [SEER] 3
Cooling
13.0 [ 21.0 ]
10.5 [19.2]
HSPF IV 4
Heating
10.0
10.0
COP
Heating 1
3.30
3.33
Capacity
Rated
(Minimum~Maximum)
Power supply
V , phase , Hz
Max. fuse size (time delay)
A
Min. circuit ampacity
A
Fan Motor (ECM)
F.L.A
208/230 , 1 , 60
15
12
14
0.50
0.93
Model
Compressor
SNB130FQBH
R.L.A
7.4
10.0
L.R.A
9.3
12.5
Refrigeration oil cc.
(Model)
450 (NEO22)
Refrigerant control
Sound level 1
Linear expansion valve
Cooling
dB(A)
49
54
Heating
dB(A)
51
56
W
in.
31-1/2
33-1/16
D
in.
11-1/4
13
H
in.
21-5/8
33-7/16
Ib.
80
119
Defrost method
Reverse cycle
Dimensions
Weight
External finish
Munsell 3Y 7.8/1.1
Remote controller
Wireless type
Control voltage (by built-in transformer)
VDC
12 - 24
Refrigerant piping
Not supplied
Refrigerant pipe size Liquid
(Min. wall thickness) Gas
Connection method
Between the indoor
& outdoor units
in.
1/4 (0.0315)
in.
1/2 (0.0315)
Indoor
Flared
Outdoor
Flared
Height difference
ft.
40
50
Piping length
ft.
65
100
2 lb. 9 oz.
3 lb. 7 oz.
Refrigerant charge (R410A)
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency
2:
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
Maximum frequency
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-8
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS
MUZ-GE24NA
MUZ-GE24NA
Model name
Capacity
Rated
(Minimum~Maximum)
Cooling 1
Btu/h
22,500
( 8,200 ~ 31,400 )
Heating 47 1
Btu/h
16,000 (24,600)
Capacity
Heating 17 2
Btu/h
1,800 (570 ~ 3,580)
Power consumption Rated (Minimum~Maximum)
Cooling 1
W
16,000 (24,600)
Heating 47 1
W
2,340 (520 ~ 3,650)
Power consumption
Heating 17 2
W
1,770 (3,290)
EER 1 [SEER] 3
Cooling
HSPF IV 4
Heating
10.0
COP
Heating 1
3.46
Power supply
12.5 [19.0]
V , phase , Hz
208/230 , 1 , 60
Max. fuse size (time delay)
A
20
Min. circuit ampacity
A
17.1
Fan Motor (ECM)
F.L.A
0.93
Model
SNB172FQKMT
Compressor
R.L.A
12.9
L.R.A
16.1
Refrigeration oil cc.
(Model)
0.40 (FV50S)
Refrigerant control
Sound level 1
Linear expansion valve
Cooling
dB(A)
55
Heating
dB(A)
55
Defrost method
Dimensions
Reverse Cycle
W
in.
33-1/16
D
in.
13
H
in.
34-5/8
Ib.
119
Weight
External finish
Munsell 3Y 7.8/1.1
Remote controller
Wireless type
Control voltage (by built-in transformer)
VDC
Refrigerant piping
Refrigerant pipe size
(Min. wall thickness)
Connection method
Between the indoor
& outdoor units
12 - 24
Not supplied
Liquid
in.
3/8 (0.0315)
Gas
in.
5/8 (0.0315)
Indoor
Flared
Outdoor
Flared
Height difference
ft.
50
Piping length
ft.
100
Refrigerant charge (R410A)
4 lb. 3 oz.
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency
2:
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
Maximum frequency
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-9
3-1. SPECIFICATIONS
EFFICIENCY RATINGS
Outdoor Unit
Indoor Unit
SEER
EER
HSPF
COP
COP
Energy
@ 47° F @ 17° F
Star
Tax
Credit
Most
Efficient
WALL-MOUNT HEAT PUMP
MUZ-GE09NA
MSZ-GE09NA-8
21
13.6
10
4.2
2.76
Yes
Yes
Yes
MUZ-GE12NA
MSZ-GE12NA-8
20.25
12.5
10
3.6
2.86
Yes
Yes
Yes
MUZ-GE15NA-1 MSZ-GE15NA-8
21
13
10
3.3
2.88
Yes
Yes
Yes
MUZ-GE18NA-1 MSZ-GE18NA-8
19.2
10.5
10
3.32
2.7
19
12.5
10
3.46
2.64
Yes
Yes
MUZ-GE24NA
MSZ-GE24NA
Note:
Efficiency values based on AHRI 210/240 test method.
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-10
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
2- 5/16
1-3/4
2-3/4
3/16
2-3/16
6 - 1/4
9-1/8
3/4
1-15/16
11-5/8
1-11/16
2-3/16
24-3/8
31-7/16
30-15/16
1-15/16
5-1/8
Indoor unit
2-3/8
Air out
5/16
8-3/8
1-5/8
1/4
3-15/16
Installation plate
1-5/8
3-1/8
Air in
13-5/16
4-3/8
4/3/16
6-1/8
8-7/8
13-9/16
1-5/8
Piping
3-1/8
7/8
Drain hose
Wall hole ø2-9/16
2-1/8
9-15/16
10
7/16×13/16 Oblong hole
Installation plate
6-1/8
8-7/8
2-3/16
2-11/16
8-5/16
1/8
1-5/8
© 2013 Mitsubishi Electric US, Inc.
9-1/8
7/16×1 Oblong hole
3-2. EXTERNAL DIMENSIONS
MSZ-GE09NA-8 MSZ-GE12NA-8 MSZ-GE15NA-8 MSZ-GE18NA-8
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
MSZ-GE-11
12-13/16
2-5/16
2-3/16
3/4
31-1/8
43-5/16
Wireless remote controller
6-1/4
9-15/16
1-7/8
10-1/4
16-5/16
Air out
Air in
3-7/8
3-7/8
Installation plate
1/8
Insulation ø1-1/8
Drain hose ø5/8
(Connected part O.D)
{
6-13/16
5/16
Liquid line ø1/4 19-11/16
Gas line ø5/8 16-15/16
Insulation ø1-15/16 O.D
ø1-1/4 I.D
Installation plate
3/16
Wall hole ø3
16-5/16
6-13/16
Indoor unit
10-1/16
1-7/8
MSZ-GE-12
12-3/8
42-1/16
3-2. EXTERNAL DIMENSIONS
MSZ-GE24NA
Unit: inch
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
11-1/32
handle
7/8
Air in
1-3/4
13/32
5-15/16
31-1/2
19-11/16
11-29/32
Air out
Air in
15-3/4
1-5/8
13-9/16
11/16
13/16 Oval hole
1-9/16
2- 3/8
Drain hole
12 ~ 12-3/4
2-23/32
2
© 2013 Mitsubishi Electric US, Inc.
5-7/8
29/32
6-23/32
11-1/4
8
re
r mo
in. o
:1/4 (flared)
:3/8 (flared) (GE09/12)
1/2 (flared) (GE15)
.o
4 in
r mo
re
14
in.
or
mo
re
Basically open 4 inch or more
without any obstruction in front
and on both sides of the unit.
Open two sides of left,
right, or rear side.
re
mo
Liquid pipe
Gas pipe
17/32
. or
4 in
REQUIRED SPACE
3-2. EXTERNAL DIMENSIONS
MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA-1
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
MSZ-GE-13
21-5/8
33-7/16
13
Air in
Drain 3 holes
(ø1-5/16)
2
16-15/16
11-25/32
2-19/32
Air in
4-25/32
33-1/16
Air out
19-11/16
20-9/32
3-3/16
. or
4 in
re
mo
Liquid:1/4(flared)
Gas :1/2(flared)
14
in.
or
mo
re
4 inch or more/
8 inch or more if
there are obstacles
to both sides
MUZ-GE18NA-1
8-11/32
Open as a rule
20 inch or more if the back,
both sides and top are open
14-3/16
4-3/8 × 13/16 slot
1-9/16
REQUIRED SPACE
30°
35°
MSZ-GE-14
2-9/16
3-9/16
Open as a rule
20 inch or more if
the front and both
sides are open
3-2. EXTERNAL DIMENSIONS
Unit: inch
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
1-11/32
33-7/16
Air in
2
16-15/16
33-1/16
4-25/32
Air out
19-11/16
Air in
20-9/32
11-25/32
2-19/32
14-3/16
re
mo
Open as a rule
20 inch or more if the back,
both sides and top are open
. or
4 in
13/16 Oval hole
13
3-3/16
4-3/8
1-9/16
Drain hole ø1-5/8
6-1/28
3-17/32
7-25/32
ore
Gas refrigerant
pipe joint
Refrigerant pipe
(flared) ø5/8
Liquid refrigerant
pipe joint
Refrigerant pipe
(flared) ø1/4
rm
in.
o
Service panel
14
4 inch or more /
8 inch or more if
there are obstacles
to both sides
Open as a rule
20 inch or more if
the front and both
sides are open
30°
© 2013 Mitsubishi Electric US, Inc.
35°
REQUIRED SPACE
3-2. EXTERNAL DIMENSIONS
MUZ-GE24NA
Unit: inch
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
MSZ-GE-15
3-3. CENTER OF GRAVITY
MSZ-GE09NA-8 MSZ-GE12NA-8 MSZ-GE15NA-8
MSZ-GE18NA-8 MSZ-GE24NA
Model name
C
a
c
B
A
b
A
B
C
a
b
c
3-3/4
(95)
7-1/2
(190)
31-7/16
(798)
9-1/8
(232)
11-5/8
(295)
17-11/16 4-5/16
(450)
(110)
6-5/16
(160)
42-1/16
(1100)
10-1/4 12-13/16
(261)
(325)
MSZ-GE09NA-8
MSZ-GE12NA-8 13-7/16
MSZ-GE15NA-8 (340)
MSZ-GE18NA-8
MSZ-GE24NA
Unit: inch(mm)
MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA-1
MUZ-GE18NA-1 MUZ-GE24NA
Model name
c
C
a
B
A
MUZ-GE09NA
11-1/16
MUZ-GE12NA
(280)
MUZ-GE15NA-1
MUZ-GE18NA-1
A
MUZ-GE24NA
Unit: inch(mm)
11-13/16
(300)
B
C
a
b
c
5-9/16
(140)
9-1/2
(240)
31-1/2
(800)
11-1/4
(285)
21-5/8
(550)
5-7/8
(150)
13-3/8
(340)
33-1/16
(840)
13
(330)
33-7/16
(850)
b
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-16
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-4. ELECTRICAL WIRING DIAGRAMS
MSZ-GE09NA-8 MSZ-GE12NA-8 MSZ-GE15NA-8 MSZ-GE18NA-8
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-17
3-4. ELECTRICAL WIRING DIAGRAMS
MSZ-GE24NA
MSY-GE24NA
MSZ-GE24NA
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-18
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-4. ELECTRICAL WIRING DIAGRAMS
MUZ-GE09NA MUZ-GE12NA
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-19
3-4. ELECTRICAL WIRING DIAGRAMS
MUZ-GE15NA-
1
11
MUZ-GE15NA-1
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-20
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-4. ELECTRICAL WIRING DIAGRAMS
MUZ-GE18NA-
1
13
MUZ-GE18NA-1
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-21
3-4. ELECTRICAL WIRING DIAGRAMS
MUZ-GE24NA
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-22
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-5. REFRIGERANT SYSTEM DIAGRAMS
MSZ-GE09NA-8 MSZ-GE12NA-8 MSZ-GE15NA-8 MSZ-GE18NA-8
Refrigerant pipe ø3/8 (MSZ-GE06/09/12NA, MSY-GE09/12NA)
ø1/2 (MSZ-GE15/18NA, MSY-GE15/18NA)
(with heat insulator)
Indoor
heat
exchanger
Indoor coil
thermistor
RT12 (main)
Flared connection
Indoor coil
thermistor
RT13 (sub)
Room temperature
thermistor
RT11
Flared connection
Refrigerant pipe ø1/4
(with heat insulator)
Refrigerant flow in cooling
Refrigerant flow in heating
MSZ-GE24NA
Refrigerant pipe ø5/8
(with heat insulator)
Indoor
heat
exchanger
Indoor coil
thermistor
RT12 (main)
Distributor
Flared connection
Indoor coil
thermistor
RT13 (sub)
Room temperature
thermistor
RT11
Flared connection
Refrigerant pipe ø1/4
(with heat insulator)
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-23
MSZ-GE-24
Refrigerant pipe ø1/4
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe ø3/8
(with heat insulator)
Stop valve
(with strainar)
Capillary tube
O.D. 0.118 × I.D. 0.079
× 9-7/16
LEV
(ø3.0 × ø2.0 × 240)
Ambient
temperature
thermistor
RT65
R.V. coil (MUZ)
heating ON
cooling OFF
Strainer
#100
Outdoor
heat
exchanger
Outdoor heat
exchanger
temperature
thermistor
RT68
Refrigerant flow in cooling
Refrigerant flow in heating (MUZ)
Defrost
thermistor
RT61
(MUZ)
Muffler
Discharge
temperature
thermistor
Service port
RT62
Compressor
Service port
Stop valve
(with service port)
Muffler
4-way valve
3-5. REFRIGERANT SYSTEM DIAGRAMS
MUZ-GE09NA
Unit: inch
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
© 2013 Mitsubishi Electric US, Inc.
Refrigerant pipe ø1/4
(with heat insulator)
Flared connection
Flared connection
Stop valve
(with strainar)
Capillary tube
O.D. 0.118 × I.D. 0.079
LEV
× 9-7/16
(ø3.0 × ø2.0 × 240)
Defrost
thermistor
RT61
(MUZ)
Compressor
Service port
Muffler
Ambient
temperature
thermistor
RT65
Outdoor heat
exchanger
temperature
thermistor
RT68
Refrigerant flow in cooling
Refrigerant flow in heating (MUZ)
R.V. coil (MUZ)
heating ON
cooling OFF
Strainer
#100
Outdoor
heat
exchanger
Capillary tube
O.D. 0.118 × I.D. 0.071
× 23-5/8
(ø3.0 × ø1.8 × 600) (×2)
Discharge
temperature
thermistor
RT62
4-way valve
Service port
Stop valve
(with service port)
Refrigerant pipe ø3/8 (GE12NA)
Refrigerant pipe ø1/2 (GE15NA)
(with heat insulator)
Muffler
3-5. REFRIGERANT SYSTEM DIAGRAMS
MUZ-GE12NA MUZ-GE15NA-1
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
MSZ-GE-25
MSZ-GE-26
Refrigerant pipe ø1/4
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe ø1/2
(with heat insulator)
Stop valve
(with strainar)
Receiver
Service port
Stop valve
(with service port)
Strainer
#100
(ø3.6×ø2.4×50)
O.D. 0.142 × I.D. 0.094
× 1-31/32
Capillary tube
LEV
Ambient
temperature
thermistor
RT65
R.V. coil (MUZ)
heating ON
cooling OFF
Outdoor heat
exchanger
temperature
thermistor
RT68
Outdoor
heat
exchanger
Refrigerant flow in cooling
Refrigerant flow in heating (MUZ)
(MUZ)
Defrost
thermistor
RT61
Service port
Compressor
Discharge
temperature
thermistor
RT62
Muffler
4-way valve #100
3-5. REFRIGERANT SYSTEM DIAGRAMS
MUZ-GE18NA-1
Unit: inch
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
© 2013 Mitsubishi Electric US, Inc.
Refrigerant pipe ø1/4
(with heat insulator)
Flared connection
Flared connection
Stop valve
Strainer
#100
Service
port
O.D. 0.142 × I.D. 0.094
× 1-31/32
(ø3.6 × ø2.4 × 50)
LEV
Compressor
Capillary tube
Strainer
Receiver #100
Service
port
Discharge
temperature
thermistor
RT62
Muffler
4-way valve #100
Stop valve
(with service port)
Refrigerant pipe ø5/8
(with heat insulator)
Ambient
temperature
thermistor
RT65
Refrigerant flow in cooling
Outdoor heat
exchanger
temperature
thermistor
RT68
Outdoor
heat
exchanger
3-5. REFRIGERANT SYSTEM DIAGRAMS
MUZ-GE24NA
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
MSZ-GE-27
3-6. Capacity correction curve by temperature
MUZ-GE09NA
MUZ-GE12NA
SHF at rating condition = 0.76
Airflow = 307 CFM
ke air
11
WB t
empe
10
rature
(°F)
9
71
67
63
8
Total power consumption
(kW)
7
0.7
0.6
e air
r intak
Indoo
rature
mpe
WB te
(°F)
71
67
63
0.5
65
75
85
95
105
Outdoor intake air DB temperature (°F)
115
SHF at rating condition = 0.80
Airflow = 498 CFM
ke air
WB t
empe
Total power consumption
(kW)
11
rature
71
67
63
(°F)
1.3
71
67
63
1.2
1.1
1.0
65
e air W
r intak
Indoo
°F)
ture (
pera
B tem
75
85
95
105
Outdoor intake air DB temperature (°F)
115
Total capacity
( 103 Btu/h)
r inta
B te
mpe
ratu
12
re (°
F)
11
10
71
67
63
1.2
1.1
1.0
0.9
air
take
r in
Indoo
)
re (°F
eratu
emp
WB t
71
67
63
0.8
0.7
65
75
85
95
105
Outdoor intake air DB temperature (°F)
115
SHF at rating condition = 0.71
Airflow = 498 CFM
20
19
18
Indoo
17
r inta
16
ke air
WB te
mper
15
ature
14
Total power consumption
(kW)
Total capacity
( 103 Btu/h)
Indoo
12
0.8
air W
21
15
0.9
13
22
16
13
take
9
17
14
or in
14
MUZ-GE18NA-1
MUZ-GE15NA-1
18
Indo
15
r inta
Total capacity
( 103 Btu/h)
12
Indoo
Total power consumption
(kW)
Total capacity
( 103 Btu/h)
13
SHF at rating condition = 0.73
Airflow = 350 CFM
71
67
(°F)
63
1.9
71
67
63
1.8
1.7
1.6
1.5
1.4
65
ea
r intak
Indoo
1.3
75
85
95
)
re (°F
peratu
tem
ir WB
105
Outdoor intake air DB temperature (°F)
115
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-28
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-6. Capacity correction curve by temperature
MUZ-GE24NA
DUE TO CONTINUING RESEARCH AND PRODUCT IMPROVEMENT,
SPECIFICATIONS AND DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-29
MSZ-GE-30
Due to continuing improvement, above specification may be subject to change without notice.
11.0
10.4
9.8
14.7
13.9
13.1
17.2
16.2
15.3
21.1
20.0
18.7
67
63
71
67
63
71
67
63
71
67
63
TC
71
IWB (˚ F)
15.8
14.2
12.2
14.2
13.0
11.4
11.4
10.3
8.9
9.4
8.6
7.6
SHC
75
1.31
1.38
1.46
0.86
0.91
0.96
0.77
0.81
0.85
0.53
0.55
0.59
TPC
17.4
18.6
19.7
14.1
15.1
16.0
12.1
13.0
13.7
9.1
9.7
10.3
TC
NOTE: 1. IWB:Intake air wet-bulb temperature
TC: Total Capacity (×103 Btu/h)
SHC:Sensible Heat Capacity (×103 Btu/h)
TPC: Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor Intake air DB temperature.
MUZ-GE18NA-1
MUZ-GE15NA-1
MUZ-GE12NA
MUZ-GE09NA
Model
Indoor air
1) COOLING CAPACITY
14.7
13.2
11.4
13.2
12.1
10.7
10.6
9.6
8.3
8.7
8.0
7.1
SHC
85
1.45
1.52
1.60
0.96
1.00
1.05
0.85
0.89
0.94
0.58
0.61
0.64
TPC
16.2
17.2
18.5
13.2
14.0
15.1
11.3
12.0
12.9
8.5
9.0
9.7
TC
13.6
12.2
10.7
12.3
11.2
10.0
9.9
8.9
7.8
8.1
7.4
6.6
SHC
95
1.57
1.64
1.72
1.03
1.08
1.13
0.92
0.96
1.01
0.63
0.66
0.69
TPC
14.7
16.0
17.2
12.0
13.0
14.0
10.3
11.2
12.0
7.7
8.4
9.0
TC
Outdoor intake air DB temperature (˚F)
12.4
11.4
9.9
11.2
10.4
9.3
9.0
8.3
7.3
7.3
6.9
6.2
SHC
105
1.67
1.74
1.81
1.10
1.14
1.19
0.98
1.02
1.06
0.67
0.70
0.73
TPC
13.4
14.7
15.8
10.9
12.0
12.9
9.4
10.3
11.0
7.0
7.7
8.3
TC
11.3
10.4
9.1
10.2
9.6
8.6
8.2
7.6
6.7
6.7
6.3
5.7
SHC
115
1.74
1.82
1.89
1.14
1.20
1.24
1.02
1.07
1.10
0.70
0.73
0.76
TPC
3-7. Capacity correction table by temperature
(1) MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA-1 MUZ-GE18NA-1
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
© 2013 Mitsubishi Electric US, Inc.
10.3
65
9.1
75
9.8
9.0
65
70
8.6
7.9
75
70
7.2
65
6.3
75
6.8
5.5
65
70
5.2
4.8
TC
70
75
IDB (˚ F)
5
0.59
0.62
0.64
0.57
0.60
0.63
0.63
0.66
0.69
0.41
0.43
0.45
TPC
13.0
12.7
11.9
11.3
11.1
10.4
9.1
8.9
8.4
6.9
6.7
6.3
TC
0.75
0.78
0.81
0.73
0.76
0.79
0.81
0.84
0.87
0.52
0.55
0.57
TPC
15
16.2
15.5
14.9
14.1
13.5
13.1
11.3
10.8
10.4
8.6
8.2
7.9
TC
18.8
18.2
17.8
16.5
15.9
1.56
13.2
12.7
12.5
10.0
9.6
9.4
TC
1.01
1.04
1.06
0.98
1.01
1.03
1.08
1.11
1.14
0.70
0.72
0.74
TPC
35
21.2
20.6
20.1
18.5
18.0
17.6
14.8
14.4
14.0
11.2
10.9
10.6
TC
1.06
1.09
1.12
1.03
1.06
1.09
1.14
1.17
1.20
0.74
0.76
0.78
TPC
43
21.8
21.2
20.7
19.1
18.5
18.1
15.3
14.8
14.5
11.6
11.2
11.0
TC
1.08
1.11
1.13
1.05
1.08
1.10
1.16
1.19
1.22
0.75
0.78
0.79
TPC
45
24.5
24.0
23.5
21.4
21.0
20.5
17.1
16.8
16.4
13.0
12.7
12.4
TC
1.13
1.16
1.18
1.10
1.12
1.14
1.22
1.24
1.26
0.79
0.81
0.82
TPC
55
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or
EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on the
remote controller.
0.90
0.93
0.95
0.87
0.91
0.93
0.97
1.00
1.02
0.63
0.65
0.67
TPC
25
Outdoor intake air WB temperature (˚ F)
NOTE: 1. IDB: Intake air dry-bulb temperature
TC: Total Capacity (×103 Btu/h)
TPC: Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
MUZ-GE18NA-1
MUZ-GE15NA-1
MUZ-GE12NA
MUZ-GE09NA
Model
Indoor
air
2) HEATING CAPACITY
3-7. Capacity correction table by temperature
(2) MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA-1 MUZ-GE18NA-1
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
MSZ-GE-31
3-7. Capacity correction table by temperature
(3) M-SERIES COOLING CORRECTION
70
77
81
86
95
104
115
60
1.11
1.06
1.01
0.97
0.91
0.83
0.76
63
1.16
1.10
1.06
1.02
0.96
0.88
0.81
64
1.18
1.13
1.08
1.04
0.98
0.90
0.83
68
1.23
1.18
1.14
1.10
1.03
0.96
0.89
72
1.28
1.23
1.20
1.15
1.09
1.02
0.95
75
1.34
1.29
1.26
1.22
1.15
1.08
1.02
79
1.38
1.34
1.32
1.28
1.21
1.14
1.07
(4) M-SERIES DEFROST CORRECTION
Outdoor
intake
temperature
W.B. [° F]
Outdoor
intake
temperature
W.B. [° C]
Correction
factor
43
39
36
32
28
25
21
18
14
6
4
2
0
-2
-4
-6
-8
-10
1.00
0.80
0.82
0.84
0.87
0.90
0.93
0.96
1.00
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-32
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-7. Capacity correction table by temperature
(5) M-SERIES HEATING CORRECTION
Outdoor W.B. [° F]
-13
-4
5
14
23
32
41
50
0.81
0.95
0.99
1.03
1.07
1.07
Indoor
EAT DB
MUZ-GE24NA
60
MUZ-GE18NA-1
60
0.67
0.82
0.94
1.04
1.07
1.07
MUZ-GE15NA-1
60
0.77
0.93
0.99
1.01
1.07
1.07
MUZ-GE12NA
60
0.68
0.83
0.94
1.04
1.07
1.07
MUZ-GE09NA
60
0.69
0.85
0.98
1.07
1.07
1.07
0.97
1.01
1.05
1.05
Interpolated Data Between 60 and 65 Indoor EAT DB data sets
MUZ-GE24NA
63
0.80
0.93
MUZ-GE18NA-1
63
0.66
0.81
0.92
1.02
1.05
1.05
MUZ-GE15NA-1
63
0.75
0.91
0.97
0.99
1.05
1.05
MUZ-GE12NA
63
0.67
0.82
0.93
1.02
1.05
1.05
MUZ-GE09NA
63
0.68
0.83
0.96
1.05
1.05
1.05
MUZ-GE24NA
65
0.79
0.92
0.96
1.00
1.03
1.03
MUZ-GE18NA-1
65
0.65
0.80
0.91
1.00
1.03
1.03
MUZ-GE15NA-1
65
0.74
0.90
0.96
0.97
1.03
1.03
MUZ-GE12NA
65
0.66
0.81
0.91
1.01
1.03
1.03
MUZ-GE09NA
65
0.67
0.82
0.94
1.03
1.03
1.03
MUZ-GE24NA
70
0.76
0.89
0.93
0.96
1.00
1.00
MUZ-GE18NA-1
70
0.63
0.77
0.88
0.97
1.00
1.00
MUZ-GE15NA-1
70
0.72
0.87
0.93
0.94
1.00
1.00
MUZ-GE12NA
70
0.64
0.78
0.88
0.97
1.00
1.00
MUZ-GE09NA
70
0.65
0.79
0.91
1.00
1.00
1.00
MUZ-GE24NA
75
0.73
0.86
0.89
0.93
0.96
0.96
MUZ-GE18NA-1
75
0.61
0.74
0.85
0.93
0.96
0.96
MUZ-GE15NA-1
75
0.69
0.84
0.90
0.91
0.96
0.96
MUZ-GE12NA
75
0.61
0.75
0.85
0.94
0.96
0.96
MUZ-GE09NA
75
0.62
0.77
0.88
0.96
0.96
0.96
MUZ-GE24NA
80
0.71
0.83
0.86
0.89
0.93
0.93
MUZ-GE18NA-1
80
0.58
0.71
0.82
0.90
0.93
0.93
MUZ-GE15NA-1
80
0.67
0.81
0.86
0.87
0.93
0.93
MUZ-GE12NA
80
0.59
0.72
0.82
0.90
0.93
0.93
MUZ-GE09NA
80
0.60
0.74
0.85
0.93
0.93
0.93
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-33
3-8. Capacity correction curve by refrigerant piping length
DUE TO CONTINUING RESEARCH AND PRODUCT IMPROVEMENT,
SPECIFICATIONS AND DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-34
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-9. Capacity correction table by refrigerant piping length
(1) Cooling capacity correction
Refrigerant piping length (one way: ft.)
25 (std.)
40
65
100
MUZ-GE09NA
MUZ-GE12NA
MUZ-GE15NA-1
MUZ-GE18NA-1
1.0
0.954
0.878
-
MUZ-GE24NA
1.0
0.954
0.878
0.771
(2) Maximum refrigerant piping length & maximum height difference
Refrigerant piping: ft
Model
Additional
piping
Max. length
A
Additional
piping
Max. height
B
MUZ-GE09NA
65
MUZ-GE12NA
MUZ-GE15NA-1
Piping size: in.
Gas
Liquid
Outside
diameter
Minimum
Wall
thickness
Outside
diameter
Minimum
Wall
thickness
40
3/8
0.0315
1/4
0.0315
65
40
1/2
0.0315
1/4
0.0315
MUZ-GE18NA-1
100
50
1/2
0.0315
3/8
0.0315
MUZ-GE24NA
100
50
5/8
0.0315
3/8
0.0315
Indoor
unit
Max. Height
difference
B
Additional Piping
Max. length
A
Outdoor unit
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-35
3-9. Capacity correction table by refrigerant piping length
(3) M-SERIES PIPING CORRECTION COOLING
Refrigerant piping length (ft)
25(std)
40
65
100
1.000
0.954
0.878
0.771
(4) M-SERIES PIPING CORRECTION HEATING
Refrigerant piping length (ft)
25(std)
40
65
100
1.000
0.989
0.972
0.955
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-36
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-10. CHARGE CALCULATIONS
(1) ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calcualation.
Refrigerant piping length (one way): ft.
Model
MUZ-GE09NA
MUZ-GE12NA
MUZ-GE15NA-1
Outdoor unit
precharged
25ft
30ft
40ft
50ft
60ft
65ft
0
1.62
4.86
8.10
11.34
12.96
1 lb. 12 oz.
2 lb. 9 oz.
NOTE: Calculation: X oz. = 1.62/5 oz./ft
(Refrigerant piping length (ft) - 25)
Refrigerant piping length (one way): ft.
Model
MUZ-GE15NA-1
Outdoor unit
precharged
3 lb. 7 oz.
25
30
40
50
60
70
80
90
100
0
1.08
3.24
5.40
7.56
9.72
11.88
14.04
16.20
NOTE: Calculation: X oz. = 1.08/5 oz./ft (Refrigerant piping length (ft) - 25)
NOTE: Refrigerant piping exceeding 33 ft. requires additional refrigerant charge according to the calculation.
Model
MUZ-GE24NA
Refrigerant piping length (one way): ft.
Outdoor
unit
precharged
33
40
50
60
70
80
90
100
4 lb. 3 oz.
0
4.14
10.06
15.98
21.90
27.82
33.74
39.66
NOTE: Calculation: X oz. = 2.96/5 oz./ft
(Refrigerant piping length (ft) - 33)
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-37
3-11. AIR FLOW DATA
OUTLET AIR SPEED AND COVERAGE
Model name
MSZ-GE06NA-8
Mode
Function
Airflow
(CFM)
Air speed
(ft./s.)
Coverage (ft.)
HEAT
Dry
406
20.6
29.5
Dry
321
16.3
23.5
Wet
286
14.5
21.0
Dry
406
20.6
29.5
Dry
321
16.3
23.5
Wet
286
14.5
21.0
Dry
406
20.6
29.5
Dry
321
16.3
23.5
Wet
286
14.5
21.0
Dry
463
23.4
33.5
Dry
420
21.3
30.5
Wet
385
19.5
28.0
Dry
512
25.9
36.9
Dry
420
21.3
30.5
Wet
385
19.5
28.0
Dry
738
18.0
36.9
Dry
738
18.0
36.9
Wet
661
16.1
31.9
COOL
HEAT
MSZ-GE09NA-8
COOL
HEAT
MSZ-GE12NA-8
COOL
HEAT
MSZ-GE15NA-8
COOL
HEAT
MSZ-GE18NA-8
COOL
HEAT
MSZ-GE24NA
COOL
● The air coverage is the figure up to the position where the air speed is 1 ft./s., when air is blown out horizontally
from the unit properly at the High speed position.
The coverage should be used only as a general guideline since it varies according to the size of the room and
furniture arranged inside the room.
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-38
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-12. SOUND PRESSURE LEVELS
MSY-GE06/09NA-8
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-39
3-12. SOUND PRESSURE LEVELS
MSZ-GE12NA-8
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-40
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-12. SOUND PRESSURE LEVELS
MSZ-GE15NA-8
DUE TO CONTINUING RESEARCH AND PRODUCT IMPROVEMENT,
SPECIFICATIONS AND DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-41
3-12. SOUND PRESSURE LEVELS
MSZ-GE18NA-8
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-42
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-12. SOUND PRESSURE LEVELS
MSZ-GE24NA
Noise Criterion Curves
WALL
MSZ-GE24NA
MSZ-FE18NA
UNIT
1m
0.8m
NOTCH
SPL(dB (A))
COOL(Rated)
HEAT(Rated)
53
53
LINE
● ●
□ □
MICROPHONE
Test
conditions
are
based
on
JIS
Z8731
Ambient temperature Cooling DB:27℃ WB:19℃
Heating DB:20℃ WB:15℃
90
OCTAVE BAND SOUND PRESSURE LEVEL,dB re 0.002 MICRO BAR
80
NC-70
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES,Hz
MSZ63-1.XLS
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-43
3-12. SOUND PRESSURE LEVELS
MUZ-GE09NA
Noise Criterion Curves
MUZ-GE12NA
UNIT
1m
MICROPHONE
Test
NOTCH
SPL(dB(A))
COOL
HEAT
49
51
conditions
are
LINE
● ●
□ □
based
on
JIS
Z8731
Ambient temperature Cooling DB:35℃ WB:24℃
Heating DB: 7℃ WB: 6℃
90
80
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL,dB re 0.002 MICRO BAR
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES,Hz
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-44
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-12. SOUND PRESSURE LEVELS
MUZ-GE12NA
Noise Criterion Curves
MUZ-GE12NA
UNIT
1m
MICROPHONE
Test
NOTCH
SPL(dB(A))
COOL
HEAT
49
51
conditions
are
LINE
● ●
□ □
based
on
JIS
Z8731
Ambient temperature Cooling DB:35℃ WB:24℃
Heating DB: 7℃ WB: 6℃
90
80
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL,dB re 0.002 MICRO BAR
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES,Hz
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-45
3-12. SOUND PRESSURE LEVELS
MUZ-GE15NA-1
Noise Criterion Curves
MUZ-GE15NA
UNIT
1m
MICROPHONE
Test
NOTCH
SPL(dB(A))
COOL
HEAT
49
51
conditions
are
LINE
● ●
□ □
based
on
JIS
Z8731
Ambient temperature Cooling DB:35℃ WB:24℃
Heating DB: 7℃ WB: 6℃
90
80
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL,dB re 0.002 MICRO BAR
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES,Hz
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-46
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-12. SOUND PRESSURE LEVELS
MUZ-GE18NA-1
DUE TO CONTINUING RESEARCH AND PRODUCT IMPROVEMENT,
SPECIFICATIONS AND DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-47
3-12. SOUND PRESSURE LEVELS
MSZ-GE24NA
Noise Criterion Curves
WALL
MSZ-GE24NA
MSZ-FE18NA
UNIT
1m
0.8m
NOTCH
SPL(dB (A))
COOL(Rated)
HEAT(Rated)
53
53
LINE
● ●
□ □
MICROPHONE
Test
conditions
are
based
on
JIS
Z8731
Ambient temperature Cooling DB:27℃ WB:19℃
Heating DB:20℃ WB:15℃
90
OCTAVE BAND SOUND PRESSURE LEVEL,dB re 0.002 MICRO BAR
80
NC-70
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES,Hz
MSZ63-1.XLS
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-48
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-13. STANDARD OPERATION RANGE
Outdoor unit
Rating
Guaranteed Voltage
208/230V
60Hz
1 Phase
Min. 187V 208V 230V Max. 253V
Intake air
temperature
Function
DB (°F)
WB (°F)
DB (°F)
WB (°F)
Standard temperature
80
67
95
—
Maximum temperature
95
73
115
—
Minimum temperature
67
57
67
—
Condition
Cooling
—
78%
Maximum humidity
Heating
Outdoor
Indoor
Standard temperature
70
60
47
43
Maximum temperature
80
67
75
65
Minimum temperature
70
60
-13
-15
(1) OUTDOOR UNIT
MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA-1 MUZ-GE18NA-1 MUZ-GE24NA
OPERATING RANGE
(A) POWER SUPPLY
Rated voltage
Guaranteed Voltage (V)
208/230 V
1 phase
60 Hz
Outdoor unit
Min.187
208
230
Max.253
(B) OPERATION
Intake air temperature (°F)
Mode
Cooling
Condition
Indoor
DB
WB
DB
WB
Standard temperature
80
67
95
—
Maximum temperature
90
73
115
—
Minimum temperature
67
57
14
—
Maximum humidity
Heating
Outdoor
78%
—
Standard temperature
70
60
47
43
Maximum temperature
80
67
75
65
Minimum temperature
70
60
5
4
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-49
3-14. ACCESSORIES
(1) INDOOR UNIT
Part Number
Descriptions
Applicable model
C13-103
Blue Diamond Sensor Extension Cable - 15 Ft. DPLS1
Drain Pan Level Sensor/Control for indoor unit shut off to
prevent Drain Pan Overflow
MAC-2310FT-E
Anti-Allergy Enzyme Filter (qty of 2)
GE24
MAC-308FT-E
Platinum Catalyst Deodorizing Filter
GE06,09,12,15,18
All Models
System Control Interface - MA, Contact terminal, and
MAC-333IF-E
M-NET Control Adapter, Supplemental heat and humidifier
All Models
adaptor
MAC-408FT-E
Anti-Allergy Enzyme Filter (qty of 2)
MCCH1
Portable Central Controller (PCC) - controls up to 16
RedLINK Zones - requires an MHK1 on each indoor unit
MHK1
Wireless wall-mounted remote controller (MRCH1) with a
signal receiver (MIFH1) and cable (MRC1) all in one kit
MOS1
Outdoor Air Sensor - reads both outside temperature and
humidity displayed on MRCH1 and MCCH1 if installed
PAC-YT53CRAU
Simple MA Remote Controller (requires MAC-333IF-E
interface for MSY/Z and MFZ indoor units)
GE06,09,12,15,18
All Models
Wall mounted, hard wired, multi-functional controller: used
specifically for grouping (up to 16 units), twinning, lead/lag,
PAR-31MAA
and 7 day programmable applications
(requires MAC-333IF-E interface for MSY/Z and MFZ indoor
units)
RCMKP1CB
Lockdown Bracket for wireless, hand-held, remote
controllers
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-50
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES
(1) INDOOR UNIT cont.
Part Number
Descriptions
Applicable model
SI30-115
Mini-Condensation pump - 115 volt application
SI30-230
Mini-Condensation pump - 230 volt application
3-Pole Disconnect Switch 30 Amps 600 volts rated for
TAZ-MS303
All Models
interupting power supply at/near indoor unit - fits 2 X 4 utility
box
X87-721
Advanced Blue Diamond Mini-Condensation pump w/
Resevoir & Sensor - 208/230 volt application
MLS143812T-15
1/4 x 3/8 x 15' / 1/2" Twin-Tube Insulation
MLS143812T-30
1/4 x 3/8 x 30' / 1/2" Twin-Tube Insulation
GE09,12
MLS143812T-50
1/4 x 3/8 x 50' / 1/2" Twin-Tube Insulation
MLS143812T-65
1/4 x 3/8 x 65' / 1/2" Twin-Tube Insulation
MLS141212T-15
Diamondback
Linesets
1/4 x 1/2 x 15' / 1/2" Twin-Tube Insulation
MLS141212T-30
1/4 x 1/2 x 30' / 1/2" Twin-Tube Insulation
MLS141212T-50
1/4 x 1/2 x 50' / 1/2" Twin-Tube Insulation
MLS141212T-65
1/4 x 1/2 x 65' / 1/2" Twin-Tube Insulation
MLS141212T-100
1/4 x 1/2 x 100' / 1/2" Twin-Tube Insulation
GE15,18
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-51
3-14. ACCESSORIES
(1) INDOOR UNIT cont.
Part Number
Descriptions
Applicable model
MPLS385812T-10
3/8 x 5/8 x 10' / 1/2" Twin-Tube Insulation
MPLS385812T-15
3/8 x 5/8 x 15' / 1/2" Twin-Tube Insulation
MPLS385812T-30
MPLS385812T-50
Diamondback
Linesets
3/8 x 5/8 x 30' / 1/2" Twin-Tube Insulation
GE24
3/8 x 5/8 x 50' / 1/2" Twin-Tube Insulation
MPLS385812T-65
3/8 x 5/8 x 65' / 1/2" Twin-Tube Insulation
MPLS385812T-100
3/8 x 5/8 x 100' / 1/2" Twin-Tube Insulation
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-52
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES
(2) OUTDOOR UNIT
Part Number
Descriptions
Applicable model
CWMB1
4 piece ( 1 pair) condensing unit wall mounting brackets painted steel
All Models
DSD-400P
Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic
MAC-640BH-U
Outdoor Unit Drain Pan Heater used during defrost cycle
GE09,12,15
MAC-641BH-U
Outdoor Unit Drain Pan Heater used during defrost cycle
GE18
MAC-642BH-U
Outdoor Unit Drain Pan Heater used during defrost cycle
MAC-860DS
MAC-886SG-E
MAC-889SG
ULTRILITE1
Outdoor drain pan socket - Provides pipe connection to route
condensate out of drain pan
GE24
Outdoor air outlet guide for directing discharge air away from
other outdoor unit
Outdoor air outlet guide for directing discharge air away from
other outdoor unit
Condensing Unit Mounting Pad 16" x 36" x 3"
GE09,12,15,18,24
All Models
Due to continuing improvement, above specification may be subject to change without notice.
2013 M-Series - MSZ-GE Heat Pump Systems (October 2013)
© 2013 Mitsubishi Electric US, Inc.
MSZ-GE-53