TLS-450 Operator`s Quick Help - Veeder-Root

Manual No: 577013-969 ● Rev.: B
Operator's Quick Help
09-21-2007
11-31-30
ALL FUNCTIONS NORMAL
ALL TANKS
SYSTEM STATUS
ALL TANKS
INVENTORY
ALL SENSORS
USER DEFINED 1 USER DEFINED 2 USER DEFINED 3
FUEL MGMT
ENVIRONMENT
BIR
TLS-450
Notice
Veeder-Root makes no warranty of any kind with regard to
this publication, including, but not limited to, the implied
warranties of merchantability and fitness for a particular
purpose.
Veeder-Root shall not be liable for errors contained herein
or for incidental or consequential damages in connection
with the furnishing, performance, or use of this
publication.
Veeder-Root reserves the right to change system options or
features, or the information contained in this publication.
This publication contains proprietary information which is
protected by copyright. All rights reserved. No part of this
publication may be photocopied, reproduced, or translated to
another language without the prior written consent of Veeder-Root.
For complete product information, refer to your console’s Online
Help.
©Veeder-Root 2010. All rights reserved.
Table of Contents
Console Front Panel Features ..................................
Home Screen Controls ..............................................
Accessing Reports ....................................................
Understanding Alarms ..............................................
In-Tank Warning and Alarm Levels............................
BIR Status Warning ...................................................
Shift Close..................................................................
Add a Ticketed Delivery to a Tank .............................
Edit a Ticketed Delivery to a Tank .............................
To Start/Stop In-Tank Leak Test................................
To Start/Stop A Line Leak Test..................................
To Set System Date and Time...................................
Changing the Printer Paper ......................................
1
2
3
4
5
6
7
8
8
9
10
11
12
Page iii
CONSOLE FRONT PANEL FEATURES
09-21-2007
11-31-30
Page 1
ALL FUNCTIONS NORMAL
ALL TANKS
Touch
screen
ALL TANKS
SYSTEM STATUS
ALL SENSORS
USER DEFINED 1 USER DEFINED 2 USER DEFINED 3
Printer
INVENTORY
FUEL MGMT
ENVIRONMENT
BIR
969-2.eps
Status LEDs
NORMAL
WARNING
ALARM
HOME SCREEN CONTROLS
1
2
3
4
5
6
7
Page 2
Item
Button
1 Date /Time
2 Alarm
8
09-21-2007
11-31-30
ALL TANKS
SYSTEM STATUS
ALL TANKS
ALL SENSORS
9
USER DEFINED 1 USER DEFINED 2 USER DEFINED 3
10
20
11
DATA VIEW AREA
12
INVENTORY
DELIVERY
19
18
ENVIRONMENT
17
13
BIR
16
15
14
969-1.eps
3
4
5
6
7
8
9
10
11
12-15
16
17
18
19
20
System Status
Help
Print
Line Feed
Home
Back
Setup
Diagnostics
Shift Close
Scroll
BIR Reports
Environment Reports
Delivery Reports
Inventory Reports
Tab Screens
Action When Touched
Date/Time - Read only
Touch once to display Active Alarm Report, touch a
second time to silence the beeper.
System Status - multiple alarms will scroll
Opens online help for current screen
Prints out report viewed in screen
Advances paper several lines
Displays Home screen (shown)
Displays Previously viewed screen
Displays Main Setup screen
Displays Diagnostic Setup Screen
Allows you to close the current shift for one or all tanks.
Scroll up/down, right/left across data view area.
Accesses Reconciliation Report screens
Accesses Environmental Report screens
Accesses Delivery Report screens
Accesses Inventory Report screens
Accesses Related report, setup or diag screens
ACCESSING REPORTS
Page 3
INVENTORY REPORTS
BIR REPORTS
Current Inventory Shift
Inventory History Inventory
Reconciliation
DELIVERY REPORTS
ACTIVE ALARM REPORT
Last Delivery Adjusted
Manual
Delivery Delivery History Delivery
Ticketed
Delivery
DELIVERY
ENVIRONMENTAL REPORTS
Combined
Tank Test
ENVIRONMENT
Book
Variance
ENVIRONMENT
BIR
INVENTORY
Line
Leak
Sensor
Status
Sensor
History
T1: DELIVERY NEEDED
Reconciliation
Test Report
UNDERSTANDING ALARMS
How Do I Silence the Console Beeper and
Acknowledge the Alarm?
T1: DELIVERY NEEDED
Touch the Alarm button and the Active Alarm Report displays. Read the report, then:
Page 4
How Do I Learn More About an Alarm and What To Do
About It?
T1: DELIVERY NEEDED
The Active Alarm Report displays:
After touching this button, the
alarms separate in the report.
T1: DELIVERY NEEDED
Touch the alarm button a second time to silence the
beeper and acknowledges the alarm.
Touching anywhere in the desired alarm's row displays an Alarm Help screen in which its cause and
a suggested corrective action are shown.
IN-TANK WARNING AND ALARM LIMITS
Single-Wall
Tanks
Full Volume
Max (Label) Volume Limit
High Level Limit
Overfill Limit
Delivery Limit
Low Level Limit
High Water Limit
Water Warning Limit
Page 5
Double-Wall
Tanks
Full Volume
Max (Label) Volume Limit
High Level Limit
Overfill Limit
Delivery Limit
Low Level Limit
High Water Limit
Water Warning Limit
Annular (Interstitial) Area
BIR STATUS WARNING
When a condition that impacts reconciliation variance is identified by the console, it posts a BIR Status Warning. You can quickly
access the Reconciliation Status screen to learn more about this warning as follows:
BIR STATUS WARNING
Touch the Alarm button twice
Page 6
SHIFT CLOSE
1.
2.
Page 7
The minimum duration between shift closes is 2 hours (Manual Shift Close only).
A maximum of 8 shifts is allowed in a 24-hour period (midnight to midnight) (Manual and Timed Shift Close).
All Tanks
Close Shift 1 All Tanks
Allowable selections:
Tank 1
:
Tank X
All Tanks is the only option when Shift
Close Method selection is Timed.
OR
Tank X
If you select a single tank to close, all
the remaining tanks will automatically
be closed after the ‘Shift Close Timeout’
Period selected in Inventory Setup.
ADD A TICKETED DELIVERY TO A TANK
Add
Record
Ticketed
Delivery
DELIVERY
Page 8
Select tank
Enter delivery
info into the
Add Delivery
Ticket Dialog
fields.
EDIT A TICKETED DELIVERY TO A TANK
In the Data
View area,
Touch the
delivery you
want to edit.
Ticketed
Delivery
DELIVERY
Edit delivery
info in the Edit
Delivery Ticket
Dialog fields.
Select tank
Edit
Record
TO START/STOP AN IN-TANK LEAK TEST
Page 9
SLD
SLD
OR
Last Test
In Progress
Tank Test
OR
SLD
History
Manual
Test
Stop
Start
SELECT ONE OF THESE TAB SCREENS
Test Control Manual Stop
Timed Duration
2
Test Duration (Hours)
Stop
Allowable selections:
2 - 24 hours
Test Rate (gal/hr)
0.2 gph
Allowable selections:
0.1 gph (0.38 lph)
0.2 gph (0.76 lph)
Start
OR
Start
All Tanks
OR
Stop
All Tanks
• Do not start an in-tank leak test if there has been a
delivery to the tank within the previous 8 hours or an
invalid test will result.
• A delivery to a tank while a test is running invalidates
the test.
• Dispensing from a tank under test will cause a
Sudden Loss Alarm.
TO START/STOP A LINE LEAK TEST (PLLD OPTION)
Manual
Test
PLLD
Start
Test
3.0
Allowable selections:
3.0 gph (11.3 lph)
0.2 gph (0.76 lph)
0.1 gph (0.38 lph)
Start
Line X
Select Line
Stop
Page 10
Stop
TO SET SYSTEM DATE & TIME
Page 11
Date & Time
Set
Date and
Time
Hours
Minutes
01
55
YYYY
AM/PM
AM
MMM
DD
CHANGING THE PRINTER PAPER
Page 12
The paper roll should be changed when a red stripe appears on the
printouts.
TLS-450
A 4-roll pack of printer paper is available from your Service Contractor.
Swing down the printer cover (1) and push the paper feed release
lever (2) down. Remove the old roll of paper and discrard.
3
Unfasten the end of a fresh roll of paper and insert the roll into the
paper tray with the end of the paper tail facing you from the bottom of
the roll. Pull the tail out, up and over the new roll and push the tail
under the black paper feed roller until it exits above the feed roller (3).
Push the lever (2) down.
1
Touch the line feed button
to advance the paper a few lines
and verify the paper is feeding correctly. Close the printer cover.
2
For technical support, sales or
other assistance, please visit:
www.veeder.com