KSTAR
Memopower Plus II
Double conversion true-online UPS
1500 – 3000 VA
Power protection suitable for:
- IT and networking environments
- Servers
- Telecommunications and VoIP
- Security systems
- Automatic control systems
- Manufacturing systems
- Various other critical systems
Features
- Rack/Tower convertible design
- Efficiency up to 90%
- Patented rotated mimic LCD display
- Estimated remaining time displayed on the LCD
- True Online Double Conversion
- Support Economic (ECO) Operation Mode
- High output power factor - Matching battery pack
- Charger/Fan status on the LCD display
- Optional powerful charger
- Green concept design for energy saving
- Emergency power-off
- Hot-swappable battery
- 3-level intelligent charging method
High performance
- Double conversion topology. The Memopower Plus II series
constantly monitors the condition of ingoing power and
regulates voltage and frequency for a stable output.
- The UPS’s output remains within 2% of the nominal voltage,
even when experiencing severe power problems.
- High efficiency (>90%) and power factor (0,9).
The Memopower Plus II convertible double
conversion online UPS series, featured with
3-level charging method, high input & output
power factors, up to 90% conversion efficiency,
superior input voltage window for energy saving,
estimated remaining time and ECO mode, is an
ideal solution to your computer center, network
center, communication system, automatic control
system or other critical systems, which is
demanding a thorough protection.
www.Elinex.com/Kstar
Reliable and eco-friendly
- Standard equipped with an internal bypass allowing
continued service in case of an internal fault. Optional
external bypass for easy maintenance without having to
power down critical systems.
- Hot-swappable batteries, intelligent charging method and
optional powerful charger.
- Possibility of adding extra runtime with external battery
modules.
- Efficiency up to 94% in eco-mode.
Versatile and space-saving
- Low profile formfactor.
- Easily convert from tower to rackmount model, complete
with rotating LCD display.
- Low weight and low noise.
Technical specifications KSTAR Memopower Plus II
Double conversion true-online UPS / 1500 – 3000 VA
GENERAL
User interface
LCD display in English language
LEDs
Four status-indicating LEDs: load/battery/input/output
Topology
True online, double conversion
Diagnostics
Upon power on and software controlled
UPS bypass
Automatic bypass
ELECTRICAL INPUT
Nominal voltage
200-240V
Voltage range
200-240Vac
Frequency range
45Hz – 65Hz
ELECTRICAL OUTPUT
Power factor
0,9
Voltage
±2% of nominal regulation
Frequency
50Hz or 60Hz (Synchronized to mains)
Frequency regulation
±0,02Hz online
Load crest factor
3:1
COMMUNICATIONS
Ports
RS232 and USB
Optional
communication cards
SNMP card for monitoring through web browser interface
Relay interface card for communication and control
software
ENVIRONMENTAL
Safety markings
CE, IEC 62040-2, IEC 62040 1-1
Audible noise
<50 dB (at 1 meter)
Ambient operating
0°C to +40°C
Storage temperature
With batteries: -25°C to +40°C
Without batteries: -25°C to +55°C
Humidity
0 to 90% non-condensing
PROTECTION
Overload AC Mode
Load<100%~150%:30S; Load>150% 300ms then shut
down UPS completely
Overload Battery Mode
Load<100%~150%:30S; Load>150% 300ms then shut
down UPS completely
Overload Bypass Mode
Load>130%: 60S then shut down output
Short Circuit
Hold whole system
Overheat
Line Mode: Switch to bypass; Battery Mode: shut down
UPS immediately
Self-diagnostics
Upon power-on and software control
EPO
Shut down UPS immediately
DESCRIPTION
INTERNAL
BATTERIES
MAX. AMOUNT
OF EBM’S
INPUT
CONNECTION
OUTPUT
CONNECTION
BATTERY
TYPE
MAX. CHARGE
CURRENT
DIMENSIONS,
MM (W X D X H)
WEIGHT,
KG
RTII BR06009 1,5kVA
6
4
C14
6 x C13
12V 9AH
2A
440 x 430 x 86,5 (2u)
15
RTII BR12009 3kVA
12
4
C20
6 x C13, 1 x C19
12V 9AH
2A
440 x 572 x 86,5 (2u)
32
Kstar Memopower RTII 1,5 kVA
Kstar Memopower RTII 3 kVA
(1 STRINGS)
(3 STRINGS)
+1 EBM
+2 EBM'S
+3 EBM'S
100%
4
16
34
50
65
100%
3
15
35
45
65
75%
5
21
70
90
120
75%
4
19
65
90
110
LOAD
UPS
(5 STRINGS)
(7 STRINGS)
+4 EBM'S
(9 STRINGS)
LOAD
UPS
(1 STRINGS)
+1 EBM
(3 STRINGS)
+2 EBM'S
(5 STRINGS)
+3 EBM'S
(7 STRINGS)
+4 EBM'S
(9 STRINGS)
50%
11
47
80
150
180
50%
10
45
80
140
160
25%
30
110
210
350
420
25%
30
120
210
340
420
*The backup time is expressed in minutes, calculated with power factor 0.9
*The backup time is expressed in minutes, calculated with power factor 0.9
Elinex Power Solutions
Wolweverstraat 15, 2984 CE Ridderkerk, The Netherlands
W : www.Elinex.com/Kstar, E : Sales@Elinex.com, T : +31 (0)180 - 721 359