PME 71.402 () - Siemens Combustion Controls

Presentation example PME7...
Presentation example LME7...
PME71.402...
Program module for burner control LME71.000
User Documentation
Application:
- 1-stage, direct or pilot ignited forced draft burners
- E.g. for burners to EN 676
The PME7… and this User Documentation are intended for use by OEMs which
integrate the LME7... with PME7... in their products.

Software Version V02.00
CC1A7105.4en
26.09.2014
Note!
This documentation is only valid together with LME7... Basic Documentation
(P7105)!
Building Technologies Division
Infrastructure & Cities Sector
Contents
1
Supplementary documentation ....................................................................3
2
Warning notes ................................................................................................4
3
Typographical conventions ..........................................................................4
4
Program sequence PME71.402... ..................................................................5
5
List of phase display .....................................................................................6
6
Fuel trains (examples) ....................................................................................7
6.1
Gas direct ignition (G), 1-stage ........................................................................7
6.2
Gas pilot ignition 1 (Gp1/1), 1-stage ................................................................7
7
Input gas pressure switch-min .....................................................................7
8
Time table and settings .................................................................................8
9
Inputs and outputs / internal connection diagram .....................................9
10
Parameter list (AZL2...) ................................................................................10
11
Error code list...............................................................................................13
12
Legend ..........................................................................................................14
13
List of figures ...............................................................................................15
2/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME41.402...
Contents
CC1A7105.4en
26.09.2014
1
Supplementary documentation
Product type
Type of documentation
Documentation number
LME…
Environmental Product Declaration
E7105
PME…
Environmental Product Declaration
E7105.1
LME7...
Data Sheet
N7105
LME...
Product Range Overview
Q7010
LME7
Basic Documentation
P7105
3/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
1 Supplementary documentation
CC1A7105.4en
26.09.2014
2
Warning notes
Warning!
The safety, warning and technical notes given in the Basic Documentation
on the LME7... (P7105) apply fully to the present document also!
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!
The LME7... are safety devices! Do not open, interfere with or modify the unit.
Siemens does not assume responsibility for damage resulting from unauthorized
interference!
3
Typographical conventions
Safety notes
This User Documentation contains notes which must be observed to ensure your
personal safety and to protect the product and the connected equipment.
The instructions and notes are highlighted by warning triangles or a hand symbol and
are presented as follows, depending on the hazard level:

Warning
means that death, severe personal injury or substantial
damage to property can occur if adequate precautionary
measures are not taken
Note
draws your attention to important information on the
product, on product handling, or to a special part of the
documentation
Qualified personnel
Only qualified staff are allowed to install and operate the equipment. Qualified staff in
the context of the safety-related notes contained in this document are persons who are
authorized to commission, ground and tag devices, systems and electrical circuits in
compliance with established safety practices and standards.
Correct use
Note the following:
The device may only be used on the applications described in the technical
documentation and only in connection with devices or components from other suppliers
that have been approved or recommended by Siemens.
The product can only function correctly and safely if shipped, stored, set up and
installed correctly, and operated and maintained as specified.
4/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME41.402...
2 Warning notes
CC1A7105.4en
26.09.2014
4
Program sequence PME71.402...
 For fuel trains G and Gp1/1
Figure 1: Program sequence
5/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
4 Program sequence PME71.402...
CC1A7105.4en
26.09.2014
5
Phase number of display
List of phase display
LED
Function
LOC
OFF
Lockout phase
OFF
OFF
OFF
Standby, waiting for heat request
P08
Ph08
OFF
Power ON/test phase (e.g. detector test)
P21
Ph21
Yellow
Safety valve ON, air pressure switch in no-load position
Test if POC closed
(timeout/lockout after 5 seconds)
P22
Ph22
Yellow
Part 1: Fan motor ON
Part 2: Specified time air pressure switch
Message (timeout), stabilization air pressure switch
P30
Ph30
Yellow
Part 1: Prepurge time without extraneous light test
Part 2: Prepurging with extraneous light test (2.1 seconds)
P38
Ph38
Yellow flashing
Preignition time
P40
Ph40
Yellow flashing
Postignition time
P42
Ph42
Green
Flame detection
P44
Ph44
Green
Interval: End of safety time and fuel valve 1 ON
P50
Ph50
Green
Part 1: Interval: Fuel valve 1 ON and pilot valve OFF
Part 2: Flame-out response time
oP:P1
Green
Operation
P10
Ph10
OFF
Home run
P74
Ph74
Yellow
Postpurge time
7-segment
LOC
AZL2...
Standby
Startup
Operation
oP1
Shutdown
Safety shutdown phases
P01
Ph01
Yellow / red
Under voltage / over voltage
P02
Ph02
Yellow
Safety shutdown (e.g. open safety loop)
 Lockout
P04
Ph04
Green / red
Extraneous light in standby
P90
Ph90
Yellow
Gas pressure switch-min open
 safety shutdown and start prevention
6/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME41.402...
5 List of phase display
CC1A7105.4en
26.09.2014
6
Fuel trains (examples)
6.1 Gas direct ignition (G), 1-stage
Program
G
LME71.000...
X7-01
Gas direct 1-stage
V1
X7-04
SV
Dbr2
Figure 2: Fuel train gas direct ignition (G), 1-stage
6.2 Gas pilot ignition 1 (Gp1/1), 1-stage
Program
Gp1/1
LME71.000...
X7-01
X7-04
Gas pilot 1-stage
V1
SV
PV
Figure 3: Fuel train gas pilot ignition 1 (Gp1/1), 1-stage
7
Behavior in the event gas
pressure switch-min fails
(terminal X5-01 pin 2 and 3)
Input gas pressure switch-min
If gas pressure switch-min fails, safety shutdown is triggered and startup prevented
until gas pressure switch-min closes again. During start prevention, the yellow LED is lit
and the safety circuit is active. Burner control operates in phase 90.
7/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
6 Fuel trains (examples)
CC1A7105.4en
26.09.2014
8
Time table and settings
Type
PME71.402...
tw
TSA
max.
Requirements
Factory setting
Max.
Min.
Step size
2.5
--2.5
-----
3
t3n+0.45
14
-----
t1
P225
min.
30
29.106+2.1
1237+2.1
0+2.1
4.851
t3
P226
min.
3
3.087
37.485
1.029
0.147
Function parameter
Repetition in the event of loss of flame during operation
0 = none
1 = none
2 = 1 x repetition
Continuous pilot (during operation)
0: OFF
1: ON
Times in seconds
t8
t4
t3n
P234
P230
P257
min.
min.
approx.
2.5
3
15
2.205+0.3 3.234 19.404
13.23+0.3 74.97
1237
0+0.3
3.234
0
0.147
0.294 4.851
Parameter number
240
247
t9
P231
approx.
3
2.646
74.97
0
0.294
t10
P224
approx.
15
13.818
13.818
0
0.294
t22
approx.
1)
2)
3)
--t9+1
-------
----1
0.3
---
----0.45
0.3
---
----0.45
-----
Factory setting
0
0
Legend
tw
TSA
t1
t3
t3n
t4
t8
t9
t10
t22
Waiting time
Safety time
Prepurge time
Preignition time
Postignition time parameter 257 +0.3 seconds
Interval: End of safety time - fuel valve 1 ON
Postpurge time
Interval: Fuel valve 1 ON and pilot valve OFF
Specified time air pressure switch message (timeout)
2nd safety time
1)
2)
3)
Reaction time to a change of signal by the air pressure switch contact (opens) and flame-out response time in the event of loss of flame
Reaction time to a change of signal by the inputs (e.g. pressure switch-min)
Flame detection time
8/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
8 Time table and settings
CC1A7105.4en
26.09.2014
9
Inputs and outputs / internal connection diagram
BCI
X76
X56

Note!
*) If POC not used,
wire link Dbr1 must be connected!
GND
Not used
X66
Not used
Not used
X65
BCI
K2/1
K1
7105d41e/0914
K7
K5
X2-03
X2-01
03K105
K4
04K01
X7-04
04K77
X4-02
µC
X2-02
04K22
A
X5-03
X7-01
Feedback input POC
K2/2
Output pilot valve PV
03K66
Dbr2 for
direct ignition
03K34
+
X6-03
03K57
LME71.000...
X3-04
05K30
NT
N L
03K15
Output alarm
X3-02
03K54
X5-01
X9-04
02K43
X10-06
FSV1
LED
05K37
X10-05
FSV2
03K30
02K02
/reset
Coding
Plug marking
Figure 4: Inputs and outputs / internal connection diagram
9/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
9 Inputs and outputs / internal connection diagram
CC1A7105.4en
26.09.2014
10 Parameter list (AZL2...)
Parameter-
Parameter
Edit
Value range
number
Min.
Password level
Max.
Resolution
Factory setting
reading from
level
000
Password level
writing from level
Internal parameter
41
Heating engineer's password (4 characters)
Edit
xxxx
xxxx
---
---
---
OEM
42
OEM's password (5 characters)
Edit
xxxxx
xxxxx
---
---
---
OEM
60
Backup/restore
Edit
---
---
---
---
---
SO
100
General
102
Identification date
Read only
---
---
---
---
Info
---
103
Identification number
Read only
0
9999
1
0
Info
---
113
Burner identification
Edit
x
xxxxxxxx
1
---
Info
SO
140
Mode display of display and operating unit AZL2...
1
4
1
1
SO
SO
1 = standard (program phase)
2 = flame 1 (QRA.../ION)
Edit
3 = flame 2 (QRB.../QRC...)  not used
4 = active power (power value)
164
Number of startups resettable
Resettable
0
999999
1
0
Info
Info
166
Total number of startups
Read only
0
999999
1
0
Info
---
170.00
Switching cycles relay contact K12
Read only
0
999999
1
0
Info
---
170.01
Switching cycles relay contact K11
Read only
0
999999
1
0
Info
---
170.02
Switching cycles relay contact K2
Read only
0
999999
1
0
Info
---
170.03
Switching cycles relay contact K1
Read only
0
999999
1
0
Info
---
171
Max. switching cycles relay
Read only
0
999999
1
0
Info
---
10/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
10 Parameter list (AZL2...)
CC1A7105.4en
26.09.2014
Parameter
Parameter
Edit
Value range
number
Min.
Password level
Max.
Resolution
Factory setting
reading from
level
200
Password level
writing from level
Burner control
224
Specified time air pressure switch
Edit
0s
13.818 s
0.294 s
13.818 s
SO
OEM
225
Prepurge time -2.1 seconds
Edit
0s
1237 s
4.851 s
29.106 s
SO
OEM
226
Preignition time
Edit
1.029 s
37.485 s
0.147 s
3.087 s
SO
OEM
230
Interval: End of safety time - fuel valve 1 ON
Edit
3.234 s
74.97 s
0.294 s
3.234 s
SO
OEM
231
Interval: Fuel valve 1 ON - pilot valve OFF
Edit
0s
74.97 s
0.294 s
2.646 s
SO
OEM
234
Postpurge time
Edit
0s
1237 s
4.851 s
19.404 s
SO
OEM
240
Repetition in the event of loss of flame during
Edit
0
2
1
0
SO
OEM
Edit
0
1
1
0
SO
OEM
Edit
0s
13.23 s
0.147 s
2.205 s
SO
OEM
operation
0: None
1: None
2: 1 x repetition
247
Continuous pilot (during operation)
0: OFF
1: ON
257
Postignition time -0.3 seconds
11/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
10 Parameter list (AZL2...)
CC1A7105.4en
26.09.2014
Parameter
Parameter
Edit
Value range
number
Min.
Password level
Max.
Resolution
Factory setting
reading from
level
700
Error history
701
Current error:
702
Read only
00: Error code
2
255
1
01: Startup meter reading
0
999999
1
02: HMI phase
---
---
---
03: Power value
0%
100%
1
00: Error code
2
255
1
01: Startup meter reading
0
999999
1
02: HMI phase
---
---
---
03: Power value
0%
100%
1
2
255
1
Error history former 1:
Read only
Password level
writing from level
---
Service
---
---
Service
---
---
Service
---
•
•
•
711
Error history former 10:
00: Error code
01: Startup meter reading
Read only
0
999999
1
02: HMI phase
---
---
---
03: Power value
0%
100%
1
900
Process data
936
Normalized speed
Read only
0%
100%
0.01%
---
Service
---
951
Mains voltage
Read only
0V
LME71.000A1: 175 V
1V
---
Service
---
1%
---
Service
---
LME71.000A2: 350 V
954
Flame intensity
Read only
0%
100%
12/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
10 Parameter list (AZL2...)
CC1A7105.4en
26.09.2014
11 Error code list
Error code
Clear text
Possible cause
Loc 2
No establishment of flame at the end
of safety time
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- Faulty ignition equipment
Loc: 3
Loc 3
Air pressure faulty (air pressure switch
welded in no-load position, decrease
to specified time (air pressure switch
flame-on response time)
Air pressure switch faulty
- Loss of air pressure signal after specified time
- Air pressure switch has welded in no-load
position
Loc: 4
Loc 4
Extraneous light
Extraneous light during burner startup
Loc: 5
Loc 5
Air pressure faulty, air pressure switch
welded in working position
Loc: 7
Loc 7
Loss of flame
Loc: 10
Loc 10
Error not relatable (application),
internal error
Wiring error or internal error, output contacts,
other faults
Loc: 14
Loc 14
POC error
Error valve closure control POC
Loc: 22
Loc 22
Safety loop open
- Gas pressure switch-max open
- Safety limit thermostat cut out
Loc: 138
Loc 138
Restore process successful
Restore process successful
Loc: 139
Loc 139
No program module detected
No program module plugged in
Loc: 167
Loc 167
Manual locking
Manual locking
Loc: 206
Loc 206
AZL2... incompatible
Use the latest version
rSt Er1
rSt Er1
Error in compatibility program module
to basic unit during restore process
- Program sequence of program module does not
match the basic unit
rSt Er2
rSt Er2
Error in compatibility program module
to basic unit during restore process
- Hardware of basic unit does not match the
program module
rSt Er3
rSt Er3
Error during restore process
- Program module faulty
- Program module removed during restore
process
bAC Er3
bAC Er3
Fault of compatibility program module
to basic unit during backup process
Program sequence of program module does not
match the basic unit
Err PrC
Err PrC
Fault of program module
- Error in data content of program module
- No program module fitted
AZL2...
Loc: 2
7-segment
Time supervision air pressure switch
- Air pressure switch has welded in working
position
Too many losses of flame during operation
(limitation of repetitions)
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner
13/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
11 Error code list
CC1A7105.4en
26.09.2014
12 Legend
AL
Dbr...
Alarm device
Wire link
Lockout reset button (info button)
/reset
(EK1)
EK2
FSV
ION
K...
LED
LP
LR
LR-OPEN
LR-CLOSED
M
NT
Pmax
Pmin
POC
PV
QRA...
R
SK
SV
V1
Z
Remote lockout reset button
Flame signal amplifier
Ionization probe
Relay contact
3-color signal lamp
Air pressure switch
Load controller
Load controller OPEN position
Load controller CLOSED position
Fan motor
Power supply unit
Pressure switch-max
Pressure switch-min
Valve closure control (proof of closure)
Pilot valve
Flame sensor
Control thermostat or pressurestat
Safety Loop
Safety valve
Fuel valve
Ignition transformer
Input/output signal 1 (ON)
Input/output signal 2 (OFF)
Permissible input signal 1 (ON) or 0 (OFF)
14/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...
12 Legend
CC1A7105.4en
26.09.2014
13 List of figures
Figure 1: Program sequence ........................................................................................... 5
Figure 2: Fuel train gas direct ignition (G), 1-stage ......................................................... 7
Figure 3: Fuel train gas pilot ignition 1 (Gp1/1), 1-stage ................................................. 7
Figure 4: Inputs and outputs / internal connection diagram ............................................. 9
Siemens AG Infrastructure & Cities Sector Building Technologies Division
Berliner Ring 23
D-76437 Rastatt
Tel. +49 7222 598 279
Fax +49 7222 598 269
www.siemens.com
© 2014 Siemens AG Infrastructure & Cities Sector
Building Technologies Division
Subject to change!
15/15
Building Technologies Division
Infrastructure & Cities Sector
User Documentation PME71.402...