advertisement
▼
Scroll to page 2
of 40
25Si / 28Si WALL MOUNTED COMBINATION BOILERS FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS 0 I This appliance is for use with Natural Gas or LPG (Cat II 2H3P). 25Si GC NUMBER 47 311 49 (N.G.) CG NUMBER 47 311 50 (L.P.G.) 28Si GC NUMBER 47 311 51 (N.G.) CG NUMBER 47 311 52 (L.P.G.) APPLIANCE OUTPUTS Minimum Maximum Domestic Hot Water 25 28 8.5 kW 8.5kw 25.0kW 28.0kw Central Heating 25 8.5 kW 25.0kW 28 8.5kw 28.0kw IMPORTANT: THESE INSTRUCTIONS APPLY IN THE UK ONLY AND MUST BE LEFT WITH THE USER OR AT THE GAS METER Read the instructions before starting work - they have been written to make the installation easier and prevent hold-ups. Contents 1. Installation Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 2. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 3. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4 4. Siting the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6 5. Flue Terminal Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 6. Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 7. Sealed System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 Open Vent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 8. Domestic Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 ......................................................... 9. Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 10. Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 11. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 12 12. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18 13. Handover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 20 14. Inspection and Servicing . . . . . . . . . . . . . . . . . . . . . . . . . Page 20 15. Replacement of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 22 16. Short Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 28 17. Operational Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . Page 30 18. Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 32 1. Installation Regulations 2. Introduction 1.1 Gas Safety (Installation & Use) Regulations 1998. It is the law that all gas appliances are installed by a competent person in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution. It is in your interest, and that of safety, to ensure compliance with the law. 1.2 The manufacturers notes must not be taken, in any way, as overriding statutory obligations. 1.3 The compliance with a British Standard or European Norm does not, in itself, confer immunity from legal obligations. 1.4 The installation of the appliance must be in accordance with the relevant requirements of the Gas Safety Regulations, current IEE Regulations, Building Regulations, Building Standards (Scotland) and local water bye-laws. 1.5 The installation should follow the recommendations of the following British Standards unless otherwise indicated and to any other relevant standards. BS5440:1 - Flues and ventilation for gas appliances: Flues BS5440:2 - Flues and ventilation for gas appliances: Air supply. BS5449 - Central heating for domestic premises. BS5482 - Domestic propane gas burning installations. BS5546:1 - Installation of gas hot water supplies. BS6700 - Domestic water supply (when relevant). BS6798 - Installation of gas fired hot water boilers. BS6891 - Low pressure gas pipework installations up to 28mm (R1). BS7593 - Water treatment. 1.6 The appliance and/or components must conform, where applicable, to all relevant Directives. 1.7 In accordance with COSSH the appliance does not contain any substances which are harmful to health. 1.8 Product Liability regulations indicate that, in certain circumstances, the installer can be held responsible, not only for mistakes on his part but also for damage resulting from the use of faulty materials. We advise that to avoid any risk, only quality approved branded fittings are used. 1.9 LPG Installation. The appliance shall not be installed in a room or internal space below ground level when it is intended for use with LPG. This does not preclude the installation into rooms which are basements with respect to one side of the building but open to the ground on the opposite side. 1.10 These instructions cover, as far as possible, the foreseeable situations which may arise. Contact Worcester Heat Systems Technical Department, Telephone: 0990 266241, for advice on specific installations. The Benchmark initiative is the new code of practice to encourage the correct installation, commissioning and servicing of domestic central heating boilers and system equipment. The 'Log-book' is a vital document that must be completed by the installer at the time of installation. It confirms that the boiler has been installed and commissioned according to the manufacturers instructions. Without the completion of the Log-book, manufacturers may refuse to respond to a call-out from a householder, who will be advised that he or she must call back the installer, who has not fulfilled his obligations to record the information required by the initiative. It is important that: The services and the system are properly flushed as specified. The User is clearly instructed on the correct operation of the appliance. The benefits of regular servicing are explained - to maintain the efficiency and extend the life of the appliance. 2.1 General Information The appliance is set to give the maximum output of 28 kW [28Si] or 25kW [25Si] to the domestic hot water and to the heating system. The hot water flow rate is limited to a nominal 10 l/min [28Si] or 9 l/min [25Si] at a maximum temperature rise of 40°C. The sanitary water section of the appliance is suitable for mains water pressure of upto 10bar. Kits are available to convert the appliance from Natural Gas to Propane operation and vice versa. 2.2 Electrical Supply 230V - 50Hz. Load 180 watts. External fuse 3A, Internal fuses F1 - 2A, F2 - 1.6A (20mm). 2.3 Gas Supply The appliances require a maximum of 3.38 m3/h of natural gas (G20) or 1.25 m 3/h of propane (G31) [28Si] or 2.98 m 3/h of natural gas (G20) or 1.12 m3/h of propane (G31) [25Si]. The installation and the connection of the gas supply to the appliance must be in accordance with BS6891. The meter or regulator should deliver a dynamic pressure of 20 mbar (G20) or 37mbar (G31) at the appliance, which is equivalent to about 18.5 mbar or 36 mbar at the gas valve inlet pressure test point. 2.4 Installation The appliance is suitable for indoor installation only and for use with a sealed system only. Do not place anything on top of the appliance. It is a room sealed appliance and a separate combustion air supply is not required in any room or compartment in which the appliance is fitted. If the appliance is fitted in a cupboard or a compartment is built around it after installation, then the structure must conform to the requirements of BS6798 and BS5440 Part 2. However, because of the low casing losses, there is not a need for the cooling ventilation openings in the compartment. The spaces specified in Section 6. Air Supply must be provided. There is space for the service pipes to pass at the back of the appliance. 2.5 Flue The flue can be to the right, left or rear. A vertical flue system is available. The flue terminal, on the outside wall, must not be obstructed or damaged. An internal flue fitting kit is available. Fitting instructions are given in Section 11.9. 2 Fig. 2. Water flow diagram. Fig. 1. Facia controls Central Heating Indicator Reset Light Button Power ON Indicator 11 Domestic Hot Burner Water Indicator Operation Light Light 10 ! 0 I 9 Mains ON/OFF Switch Central Heating Operation and Temperature Control Knob Domestic Hot Water Temperature Control Knob System Pressure Gauge 2.6 Controls Controls for switching the appliance On or Off and for adjusting the CH and DHW temperatures. The CH control knob also switches the CH off and on. A programmable room thermostat or a facia mounted programmer or clock is available. A room thermostat and/or an externally mounted programmer for mains voltage operation may be connected to the appliance. Only double insulated mains voltage controls not requiring an earth can be used. 2.7 System All dirt must be flushed from the system before connecting the appliance. The system can be pre-piped and flushed before the appliance is fitted. The connections in the system must withstand a pressure of upto 3 bar. Radiator valves must conform to BS2767: 10:1977. Table 3 gives the pump head available for the system and the required temperature differential. A drain cock must be fitted to the lowest point and an air vent to the highest point of the system. 2.8 Showers, Bidets, Taps and Mixing Valves All taps and mixing valves must be suitable for the available mains pressure and temperatures up to 65°C. It may be necessary to fit a pressure reducing valve. Hot and cold mains fed water can be supplied to overrim bidets but is subject to local water company requirements. The flow of water from individual outlets varies on all mains fed systems that are not fitted with flow balancing valves. If a pressure equalising valve is fitted then the domestic hot water temperature should be set to maximum. Thermostatically controlled shower valves give extra comfort and protection. 2.9 Safety The appliance must not be operated with the inner casing cover removed. The gas and electricity supplies must be turned off before working on the appliance. Temperature monitoring controls are fitted to prevent overheating. Automatic frost protection is provided together with automatic pump seizure protection. The gas valve solenoids are automatically checked for gas soundness. IMPORTANT: Where back-flow prevention devices, including water meters, are fitted the expansion of hot water into cold water main can be prevented. This can result in a pressure build-up that may cause damage to the boiler and household devices such as showers, washing machines etc. In these cases we recommend that a mini-expansion vessel be fitted adjacent to the boiler in the cold water pipe. 2.10 Operation Central Heating A demand for heat will ignite the burner. It will operate at minimum pressure for 2 minutes before increasing to the maximum 8 12 7 6 1 1. CH Flow. 2. Domestic Hot Water Supply. 3. Domestic Cold Supply. 4. CH Return. 5. Relief Valve Discharge. 6. Relief Valve. 2 3 4 5 7. Domestic Water Flow Switch. 8. Pump. 9. Sealed System Expansion Vessel. 10. Bi-thermal Gas to Water Heat Exchanger. 11. Automatic Air Vent. 12. Fixed By-Pass. pressure over a period of 1 minute and then automatically match the system requirements. At the end of the demand the burner will go out, the pump will continue to run for up to 4 minutes or the fan for 35 seconds. There is an anti-cycle time of 3 minutes. Domestic Hot Water A demand for hot water will ignite the burner. The burner pressure will immediately rise to maximum. At the end of the demand the fan will continue to run for 35 seconds if there is no heating demand. The demand for hot water will override the CH function. In winter it may be necessary to reduce the flow at the taps to maintain the delivery temperature. 2.11 Conversion Instructions The appliance can be converted from LPG to NG and vice versa by replacing the burner and resetting the gas valve. To replace the burner and transfer the electrodes refer to Section 15.4.2,3 and 4. The burner part numbers are: NG (25Si and 28Si) 8 718 120 565 0 LPG (28Si) 8 718 120 566 0 LPG (25Si) 8 718 120 569 0 To reset the gas valve refer to Section 15.4.4, Section 12Commissioning and , for setting pressures, Table 1 in Section 3Technical Data. Always check for gas soundness after replacing components in the gas circuit. 3 3. Technical Data Table 1. The data plate is fixed to the inner casing cover. 25Si Table 1. NOMINAL BOILER RATINGS (10 Minutes After Lighting) BOILER ADJUSTED FOR G20 (Natural Gas) BURNER OUTPUT INPUT (Net) GAS RATE PRESSURE kW kW m bar. m3/h 8.5 10.5 0.7 1.12 25.0 27.8 11.5 2.98 8.5 25.0 28Si NOMINAL BOILER RATINGS (10 Minutes After Lighting) BOILER ADJUSTED FOR G20 (Natural Gas) BURNER OUTPUT INPUT (Net) GAS RATE PRESSURE kW kW m bar. m3/h 8.5 10.5 0.7 1.12 28.0 31.1 14.1 3.38 BOILER ADJUSTED FOR G31 (Propane) 10.5 4.2 0.42 27.8 35.7 1.12 8.5 28.0 Natural Gas: Net Input = Gross Input x 0.901 BOILER ADJUSTED FOR G31 (Propane) 10.5 2.3 31.1 35.5 LPG (Propane): Net Input = Gross Input x 0.922 Table 2. FLUE DETAILS HORIZONTAL FLUE mm WALL HOLE DIAMETER STANDARD FLUE EXTENDED FLUE EXTERNAL FIX 110 INTERNAL FIX 150 MINIMUM LENGTH 330/425 * MAXIMUM LENGTH 725 MAXIMUM LENGTH 2975 FLUE ASSEMBLY DIAMETER 100 * NOTE : Flue lengths between 330 and 425mm require the flue to be cut Table 3 MAXIMUM AVAILABLE PUMP HEAD BOILER OUTPUT kW HEAD Metres MIN. FLOW RATE L/min. FLOW/RETURN DIFFERENTIAL °C 8.5 5.9 11.0 11 25 2.0 30.5 12 28 2.0 30.5 13 Table 4 MECHANICAL SPECIFICATIONS CENTRAL HEATING FLOW - COMPRESSION 22mm RETURN - COMPRESSION 22mm COLD WATER INLET - COMPRESSION 15mm DOMESTIC WATER FLOW - COMPRESSION 15mm 3 GAS INLET Rp ⁄4 RELIEF VALVE DISCHARGE (PUSH FIT) 15mm CASING HEIGHT 800mm CASING WIDTH 440mm CASING DEPTH 360mm WEIGHT - LIFT 42.3kg WEIGHT - UNPACKED 45.8kg WEIGHT - PACKAGED 52kg 4 0.42 1.25 Table 5 PERFORMANCE SPECIFICATIONS PRIMARY WATER CAPACITY litres 25Si 2.0 28Si 2.0 MAXIMUM MAINS INLET PRESSURE bar 10 10 MINIMUM MAINS INLET PRESSURE (WORKING) FOR MAXIMUM FLOW bar 1.1 1.3 MINIMUM MAINS INLET PRESSURE (WORKING) FOR OPERATION bar 0.5 0.5 DOMESTIC HOT WATER TEMPERATURE RANGE °C 40 - 62 40 - 62 MAXIMUM CENTRAL HEATING FLOW TEMPERATURE °C 82 (nom) 82 (nom) MAXIMUM CENTRAL HEATING SYSTEM SET PRESSURE bar 2.5 2.5 MINIMUM CENTRAL HEATING SYSTEM PRESSURE bar 1 1 NATURAL GAS (G20) 8.5 - 25 8.5 - 28.0 LPG - PROPANE (G31) 8.5 - 25 8.5 - 28.0 NATURAL GAS (G20) 8.5 - 25 8.5 - 28.0 LPG - PROPANE (G31) 8.5 - 25 8.5 - 28.0 DOMESTIC HOT WATER SPECIFIC RATE - 30°C RISE l/min 12.0 13.4 MAXIMUM DOMESTIC HOT WATER FLOW RATE - 40°C RISE l/min 9.0 OUTPUT TO DOMESTIC HOT WATER kw OUTPUT TO CENTRAL HEATING kw 10.0 NOx CLASSIFICATION FOR BOTH 25 & 28Si Class 2 SEDBUK NUMBER SEDBUK BAND 78.0 78.2 D D Table 6 DISCHARGE RATE l/min TEMPERATURE RISE °C TEMPERATURE RISE °C DOMESTIC HOT WATER TEMPERATURE RISE 7 8 25Si 51 45 28Si 57 50 Table 7 GAS SUPPLY SYSTEM - BASED ON NG (G20) TOTAL LENGTH OF GAS SUPPLY PIPE (COPPER) metres 3 6 9 12 GAS DISCHARGE RATE - PRESSURE DROP 1mbar. m3/h PIPE DIAMETER mm 8.7 5.8 4.6 3.9 22 18.0 12.0 9.4 8.0 28 Table 8 CLEARANCES (mm) INSTALLATION ABOVE APPLIANCE AND/OR FLUE ELBOW 30 IN FRONT OF APPLIANCE 600 BENEATH APPLIANCE 200 RIGHT AND LEFT HAND SIDE 10 SERVICE 30 600 200 10 Refer to Section 6. Table 9 INITIAL PRESSURE bar 1.0 1.5 SYSTEM CAPACITY TOTAL SYSTEM VOLUME litres INITIAL CHARGE PRESSURE bar 0.5 1.0 1.5 57 75 N/A 31 42 52 5 9 40 45 10 36 40 4. Siting The Appliance Fig. 3. Appliance casing dimensions and required clearances (front view). The appliance may be installed in any room but refer to the requirements of the current IEE Regulations and, in Scotland, the relevant electrical provisions of the Building Regulations with respect to the installation of appliances in rooms containing baths or showers. Where a room sealed appliance is installed in a room containing a bath or shower, any switch or appliance control using mains electricity must NOT be able to be touched by a person using the bath or shower. The appliance is NOT suitable for external installation. No special wall protection is required. The wall must be able to support the weight of the appliance. Refer to Table 4. The specified clearances must be available for installation and servicing. Refer to Table 8, Fig.3, 4 and Section 6. Air Supply. The appliance can be installed in a cupboard/compartment to be used for airing clothes providing that the requirements of BS6798 and BS5440 Part 2 are followed. Refer to Section 2.4. The airing space must be separated from the boiler space by a perforated non-combustible partition. Expanded metal or rigid wire mesh is acceptable provided that the major dimension is less than 13mm. The clearance between the front of the appliance and the cupboard/compartment door should be not less than 75mm. LPG Installation. Refer to Section 1.9. 30 170 440 10 10 200 All dimensions in mm Fig.4. Appliance casing dimensions and required clearances (side view). 200 106 Fig. 6. Pipework connections Valves shown closed. 230 600 800 NOTE: Casing is 3mm above the top of the wall mounting frame. Refer to Fig.15. 360 A B C D E F View on underside of appliance showing connections 200 All dimensions in mm Fig. 5. Side flue opening 20 106 A B 190 C 230 D E (A, B, C, D,) F A B C D E F CH Flow DHW Flow Gas Cold Water Inlet CH Return Relief Valve Discharge = = = = = = 55 120 185 250 315 375 All dimensions in mm All dimensions in mm 6 5. Flue terminal positions 6. Air Supply The flue system must be installed following the requirements of BS5440: 1. Standard flue kit length is 330 - 725mm (as measured from the centre of the flue turret) with extension kits for flues up to 2975mm measured from the centre line of the flue turret. The terminal must not cause an obstruction or the combustion products a nuisance. Under some conditions the terminal might steam and positions where this might be a nuisance should be avoided. Refer to Fig 7 If the terminal is less than 2m above a surface to which people have access then a guard must be fitted. The guard must be evenly spaced about the terminal and fixed with plated screws. A Type K2 guard is available from Tower Flue Components, Vale Rise, Tonbridge, TN9 1TB. 6.1 The appliance does not require a separate vent for combustion air. 6.2 The appliance can be fitted in a cupboard with no vents for cooling but the minimum clearances must be increased to those given below (note the clearances at the front are for a removable panel e.g. a door). NG LPG Above the Turret 30mm 30mm In front 75mm 250mm Below 200mm 200mm Right-hand side 10mm 75mm Left-hand side 10mm 75mm 6.3 If the appliance is to be fitted in a cupboard or compartments with less clearance than those above (minimum clearances given in Section 4. Siting The Appliance) then permanent vents for cooling are required. One at high level and one at low level, either direct to outside air or to a room. Both vents must pass to the same room or be on the same wall to the outside air. 6.4 The minimum free areas required are: Fig. 7. Siting of the flue terminal. TERMINAL POSITION MIN. DISTANCE A– Directly below an openable window or other opening e.g. air brick. B– Below gutters, soil pipes or drain pipes. C– Below eaves. D– Below balconies or car port roof. E– From vertical drain pipes and soil pipes. F– From internal or external corners. G– Above ground, roof or balcony level. H– From a surface facing a terminal. I– From a terminal facing a terminal J– From an opening in a car port (e.g. door window) into dwelling. K– Vertically from a terminal on the same wall. L– Horizontally from a terminal on the same wall. M– From door, window or air vent (achieve where possible). 300 mm 75 mm 200 mm 200 mm 75 mm 300 mm 300 mm 600 mm 1200 mm POSITION OF AIR VENTS AIR FROM THE ROOM HIGH LEVEL 315cm LOW LEVEL 315cm AIR DIRECT FROM OUTSIDE 2 2 158cm 2 2 158cm 1200 mm 1500 mm 300 mm 300 mm A L G B,C K L D K F F HI A F J E G M 7 The system and the appliance must be properly vented. Repeated venting loses water from the system, which must be replaced. The make-up connection must be close to the appliance in the heating return pipe through an approved nonreturn valve. Refer to Fig 10. The connection to the mains water supply must have the approval of the local Water Company. The integral by-pass is not adjustable. The pump is set at maximum and should not be adjusted. All connections in the system must withstand a pressure of up to 3 bar. The radiator valves must confirm to BS 2767:10 and other valves to BS1010. 7. Sealed System The system must comply with requirements of BS6798 and BS5449 and must not be operated without being full of water and correctly pressurised. Refer to Fig 8. The pressure relief valve will operate at 3 bar. The discharge pipe must be directed away from any electrics or from where it might be a hazard. The expansion vessel, to BS4814, has a capacity of 8 litres charged to 0.5 bar, which is suitable for a static head of 5 metres. A schraider type valve allows the pressure to be increased if the static head is greater than 5 metres. If the expansion vessel fails then it must be replaced with the designated spare part. Refer to BS 7074:1, BS5449 and Table 9 for a guide to the available system capacity. The maximum system design pressure is 1.5 bar. If the pressure is above 2.65 bar when the appliance is at maximum temperature then another expansion vessel must be fitted as near to the appliance as possible in the return pipe. The pressure gauge shows the system pressure. Fill and pressurise the system through a WRc approved filling kit. Refer to Fig 9. Open Vent System This appliance is NOT suitable for connection to an open vent system. Fig. 8. Sealed primary water system. APPLIANCE Mains cold water Refer to 'Water Flow Diagram' Fig.2. Radiator valve Lockshield valve Hot water out Heating return British Standard stop valve. Fixed spindle type Heating flow NOTE: A drain cock should be installed at the lowest point of the heating circuit and beneath the appliance. Water main Fig 9 - System Fill Fig 10 - System make up 4 2 1 300mm Above the highest point of the system 3 5 6 1.Central Heating Return 2.Auto Air vent 3.Non-return Valve 4.Make-up Vessel 5.Stop Cock 6.Fill Point 8 8. Domestic Hot Water 9. Gas Supply It may be necessary to contact the local Water Company before connecting the appliance. Devices, which would prevent the flow of expansion water, must not be fitted unless separate arrangements have been made. A mini-expansion vessel kit is available as an optional extra. The last 600mm of mains water pipe before the appliance must be in copper. The domestic hot water circuit of the appliance is suitable for a mains pressure of up to 10 bar. A pressure reducing valve must be fitted if necessary. A mains water supply isolating valve is fitted. The maximum hot water flow rate is set at the factory to 10 l/min [28Si] or 9 l/min [25Si] giving a nominal temperature rise of 40°C with the temperature control at maximum. Refer to Table 6. The temperature rise, up to the maximum set by the user is automatically maintained by the modulation of the heat input. In winter it may be necessary to reduce the water flow at the tap or shower to maintain the required delivery temperature. It is recommended that long pipe runs to taps or showers are insulated to prevent the rapid cooling of the water. Hot and cold taps and mixing valves must be suitable for the available mains pressure. If necessary, a pressure reducing valve should be fitted. No anti-syphonage arrangements are necessary for fixed head showers. The hose of a loose-head shower must be fixed so that the shower head cannot get closer than 25mm to the top edge of the bath to prevent its immersion in the water. Alternatively the shower can be fitted with an anti-syphonage device at the flexible hose connection. Thermostatically controlled or pressure balancing shower valves should be used where possible to give extra comfort and guard against extreme temperature. Hot and cold mains water direct to a bidet is, subject to the approval of the local water company, permissible provided that the bidet is of the overrim flushing type. The outlets must be shrouded and unable to be fitted with a hand-held spray. No antisyphon arrangements are needed. LIME SCALE: In areas of temporary hardness [ greater than 200ppm of calcium bicarbonate] it is suggested that a proprietary scale reducer is fitted in the mains cold water connection to the appliance. Installation of a scale inhibitor assembly should be in accordance with the requirements of the local Water Company. An isolating valve should be fitted to allow servicing. The water hardness can be determined by reference to the local Water Company. The appliance requires a maximum of 3.38 m3/h of natural gas (G20) or 1.2 m3/h of propane (G31) [28Si] or 2.98 m3/h of natural gas (G20) or 1.25 m3/h of propane (G31) [25Si]. Refer to Table 7. A natural gas appliance must be connected to a governed meter. The installation and connection of the gas supply to the appliance must be in accordance with BS6891. The meter (NG) and the pipework to the appliance must be checked, preferably by the gas supplier, to ensure that a dynamic pressure of 20mbar for natural gas and 37mbar for propane is available at the appliance [equivalent to about 18mbar or 35mbar at the gas valve inlet pressure connection] and that the gas flow is adequate for all the installed gas appliances operating together. 10. Electrical Mains supply: 230V ~ 50 Hz 180watts. External fuse 3A. Internal fuses F1-2A, F2-1.6A (20mm). Spare internal fuses are supplied with the appliance. Refer to Fig 13. The appliance must be earthed and it must be possible to completely isolate the appliance. The mains cable must be 0.75mm2 (24x0.20 mm) to BS6500 Table 15 or 16. The mains cable must be connected to the terminal ST12 marked L (red or brown lead), N (black or blue lead) and the Earth stud (green or green/yellow lead) and secured with the cable clamp. The Earth lead must be still be slack when the other leads are taut. Refer to Fig 14. The connection to the mains must be either : A 3A fused threepin plug and unswitched socket outlet (both complying with BS1363) or a double pole isolator with a contact separation of 3mm in all poles and supplying the appliance and controls only. A room thermostat or an externally mounted programmer must be suitable for mains voltage operation, the leads must be securely fixed in the cable clamps. Only double insulated mains voltage controls not requiring an earth lead may be used. The control board is accessed by removing the controls connections cover. Refer to Fig 29. A programmer or clock is available to fit into the facia. Full instructions are sent with the control. On very rare occasions an external frost thermostat might be considered where parts of the system are remote from the appliance. Refer to WHS Technical Department for more information, Tel: 08705 266241. Safety Check: If there is an electrical fault after installation check for fuse failure, short circuits, incorrect polarity of connections, earth continuity or resistance to earth. 9 Fig. 11. Wiring diagram. Fan Overheat cut-off device CH sensor (front of heat exchanger) Flame sense electrode Spark electrode Air pressure switch Gas valve Reg Flow switch Pump Main Main Spark transformer DHW sensor Link ST16 ST15 ST1 yellow brown ST8 blue brown blue brown Control Board ST12 Mains in 2 pink 2 yellow 2 green 2 red 2 orange 10 2 blue 2 brown 2 violet white LIVE IN ST12 Pin N ST12 Pin L Fuse F1 (2A Slow) On/Off switch 11 ST1 Centre Pin ST15 Pin L ST8 (LR) Spark Red Indicators Red Settings Electronics/ microprocessor (Safety Low Voltage) REL 3 Optional link Room thermostat ST8 (NS) Transformer Fuse F2 (1.6A Slow) Spark electrodes DHW demand indicator Red Flame detect indicator Outputs REL 1 ST8 (LS) Electronics green Mains indicator CH demand indicator N N 24V programmer Overheat cut-off Flame sense Air pressure switch DHW sensor CH sensor Flow switch Main valve Main valve Regulator valve Fig. 12. Functional flow diagram. Inputs DHW control knob CH Control knob CH pressure adjust pot Gas valve mode switch Reset button Convert AC to low voltage electronics Electronics Fan Pump Electronics Fig 13 - Replacement internal fuses Fig.14 . Mains electricity connections. NOTE: Check the size of the fuse before fitting 1 Bottom Left Hand Side - Facia ST12 230V Live Brown N LS LR 2 L N E Blue Neutral Blue Mains lead Strain relief clamp 5. Clip on Facia cover Note: When the mains ON/OFF switch on the facia is turned OFF the 2amp fuse is still live. Refer to Fig.12. appliance then they must be arranged to pass behind the expansion vessel. Refer to Fig 3. Pipework must not run horizontally within the limits of the casing. Support the valves when tightening the connections to prevent distortion of the manifold assembly It is important that the pipes are not fixed near the appliance using clips that put a strain on the connections. Before the appliance is fitted to the wall thoroughly flush the system and mains water supply. 11. Installing The Appliance Note: READ THIS SECTION FULLY BEFORE COMMENCING THE INSTALLATION 11.1 General The appliance is only suitable for fitting to a sealed system. The flue must be installed as specified in BS5440:1. 11.2 Unpacking Remove the appliance from its packaging and check the contents against the packing list. Lie the appliance on its back and undo the union connections on the manifold assembly. Refer to Fig 16. Slide the appliance off the wall mounting assembly. 11.3 Site Preparation Check that the correct position for the appliance has been chosen. Refer to Section 4 and Table 8. Check that the wall is flat and will support the weight of the appliance. Refer to Table 4. 11.4 Fixing Holes and Flue Opening Hold the wall mounting assembly against the wall. Check that the assembly is level. The diamond cut-out on the assembly indicates the centre-line of the appliance. Mark the position of the fixing holes and the flue opening. Refer to Fig. 5 and 15. Mark the centrelines of the pipe connections to aid the preplumbing of the system pipework. Check the position of the fixing points and flue opening before drilling the fixing holes 60mm deep for the No. 12 size plugs and cutting the flue duct hole at 110mm diameter [150mm diameter for internally fitted flues]. 11.5 Wall Mounting Plate and Manifold Fit the plugs and insert the bottom screws. Offer the assembly to the wall utilising the keyhole slots on the manifold assembly and fix to the wall. Refer to Fig 15 and 16. Check that the assembly is properly aligned before tightening the screws. 11.6 Gas and Water Pipes Remove the gas cock and fix the appropriate fitting to connect the inlet pipe and refit. Refer Fig 16. Pre-plumbing is not recommended if no movement in the pipes is available. If it is necessary for any of the pipes to run up the back of the Fig.15 . Wall mounting assembly 338 65 60 60 367 540 797 Cabinet Height 800 75 218 20 12 1. Fuse -F1 T2A 2. Fuse -F2 T1.6A 3. Connections Cover 4. Connections Cover Fixing Screw 3 External control 4 5 Earth Green/Yellow All dimensions in mm Fig.18. Inner case and facia fixing Fig.16 . Manifold assembly Fixing screws (4) Position of the cabinet fixing screw Wall Frame Wall Frame Fibre Washer Inner case cover 65 65 65 65 Facia panel fixing screws (2) CH Flow DHW Flow Gas DHW Cold Inlet 0 I CH Return Facia All dimensions in mm 11.7 Install the Boiler Remove the cabinet by unscrewing the screw at the top front and releasing the sides. Lift from the top location. Refer to Fig. 18. Check that the gas and water valves are closed. Refer to Fig.16. Fit the new seals, in the hardware pack, to the service valves on the manifold. Lift the appliance to the wall, engage in the top support and lower onto the manifold assembly. Tighten the gas and water connections. Fit a discharge pipe to the relief valve leading it away from any electrics or where it might be a hazard. Lower the facia to gain access. The pipe must not be less than 15mm in diameter and must run continuously downward outside the appliance. Refer to Fig 17. 11.8 Air and Flue Duct Preparation The method of installation of the flue system may be varied to suit the actual site conditions. The instructions for connecting and fixing the ducts must, however, be strictly followed. Remove all packing material from the flue components. Fit the flue restrictor ring by unscrewing and removing the flue spigot from the boiler. Refer to Fig.19. Restrictor Size 79mm to all Horizontal and Vertical flues upto 725mm long. The standard telescopic flue assembly is suitable (without cutting) for flues from 425mm up to 725mm measured from the centre-line of the boiler flue outlet to the outer face of the wall. Refer to Fig.20. The minimum length of the standard flue, after cutting is 330mm. Fig.17 . Relief valve drain connection Relief Valve Drain Connection (push fit) Pump Fig.19. Flue spigot and restrictor 1 2 Boiler Drain 3 4 1. 2. 3. 4. Pressure Gauge Capillary Relief Valve 13 Flue spigot fixing screws Flue spigot Restrictor ring Flue spigot fixing holes 11.9 Measure and Cut the Ducts. General: Cut the ducts as necessary, ensuring that the ducts are square and free from burrs. Always check the dimensions before cutting. Measure the distance L. Refer to Fig. 22 and 23. Fig.20. Standard flue assembly Flue turret assembly The standard flue can be telescopically adjusted to any length between 425mm and 725mm measured from the centre of the turret. Fix the flue assembly together using the self-tapping screws provided. Refer to Fig. 20. Terminal assembly L Fixing screw It will only be necessary to cut the standard assembly if L is less than 425mm. Cut the flue turret assembly and the terminal assembly by the same amount i.e L=350 - remove 75mm from each assembly. Telescopic adjustment Appliance casing Minimum side flue length = 330mm (accommodating a 10mm Service clearance and a 100mm wall) Minimum rear flue length = 330mm 100mm wall) If L is greater than 725mm then extension duct kit/s will be required - each kit extends the flue by 750mm up to a maximum of 2975mm. See table below. EXTENSION 1 2 3 If L is between MAXIMUM FLUE LENGTH mm 1475 2225 2975 (accommodating a 1175 - 1475mm 1925 - 2225mm 2675 - 2975mm it is not necessary to cut the ducts. (1 extension) (2 extension) (3 extension) If L is between (1 extension) (2 extension) (3 extension) 725 - 1175mm 1475 - 1925mm 2225 - 2675mm It is necessary to shorten the assembly by cutting the first extension duct assembly i.e. L = 1000mm - remove 175mm from the air and flue ducts. Fig.21. Extension duct Terminal assembly L Flue turret assembly Appliance Fixing screw Fixing screw casing Ducts of equal length Fig.22. Flue duct length - side Flue turret assembly Terminal assembly L 14 Fig.24 . Flue Turret Fixing Fig.23. Flue duct length - rear Flue turret assembly L Terminal assembly 1 2 3 1. 2. 3. 4. NOTE: Extension duct measurements do not include the socketed end. Unless specifically instructed the socketed end must not be removed. Flue turret assembly Clamp Appliance Fixing Screw 4 Fig.25 . Terminal assembly for internal fitting of the flue. Fix the flue ducts together before fixing the surrounding air duct, the cut ducts fit into the flue assembly. Fixing clamp Flue centering ring 11.10 Fitting the Flue Assembly with Access to the Terminal. Prepare the flue duct assembly as described in Section 11.8. Apply the plastic tape to the air duct in contact with the external brickwork. From inside push the assembly through the wall. Align the flue turret and push fully onto the spigot on the appliance. Tighten the clamping ring and fix with the screw provided. Refer to Fig.24. Air duct Flue Terminal Rubber sealing gasket Flue duct Make good the internal wall face and the external brickwork or rendering. 11.11 Fitting of the Flue Assembly without access to the Terminal. A rubber gasket kit is available from Worcester Heat Systems. NOTE: A larger diameter opening in the wall is required. Refer to Table 2. Rubber sealing gasket Prepare the flue assembly as described in Section 11.8. Flue terminal Fit the rubber sealing gasket centrally onto the terminal assembly and tighten the clamp. Refer to Fig. 25. Apply the plastic tape to the air duct in contact with the external brickwork. Clamping ring From inside push the assembly through the wall so that the gasket flange is against the outer face. Refer to Fig. 25. It may be necessary to adjust the legs of the flue centering ring. Align the flue turret and push fully onto the socket on the appliance. Tighten the clamping ring and fix with the screw provided. Refer to Fig. 24. Seal the gap around the duct at the inner wall face with the flexible seal provided and make good. NOTE: The flue system ducts between the elbows, dimension Y, requires the socketed ends (of the first extension if two or more are used) to be removed and the air and flue tubes to be cut to the same length. Cut the ducts to a length Y - 162mm. Refer to Fig.26. The final section, dimension Z, of the flue system must include a section of plain duct assembly i.e . an extension assembly with the sockets removed. Reduce the final section, including the terminal assembly, by the appropriate amount i.e. Air duct Z 81mm and the flue duct Z - 51mm. Refer to Fig.26. 11.12 Flue Bends. 90° and 45° bends are available. A maximum of two bends may be used in addition to the first bend on the flue turret. A 90° bend is equivalent to 1m of straight duct. A 45° bend is equivalent to 0.5m of straight duct. If Z is less than 425mm it will be necessary to cut the air and flue ducts of the extension to a plain length of 100mm and reduce the length of the terminal assembly i.e Z=350mm - remove 75mm from the terminal assembly. A maximum flue assembly of 2m is possible with 1 X 90° bend and 1m with 2 X 90° bends. Measure the lengths X,Y and Z. Refer to Fig.26. The maximum value of X using the turret assembly only is 506mm. Reduce the ducts to the appropriate length i.e. X = 406mm, cut 100mm from the air duct and 120mm (to cover the entry into the 45° or 90° elbow) from the flue duct. Refer to Fig.27. If Z is 425 - 725mm it is not necessary to cut the terminal assembly or use a second extension duct as the length can be set telescopically. If Z is greater than 725mm then two extension duct assemblies will be required, the first assembly being cut to length as plain tubes. 15 Z Fig.26. Flue bends Y-162 Plain tube Y X If more than two extension ducts are needed in any section to achieve the required length then the final section of the assembly must not be less than 325mm without cutting the terminal assembly. NOTE: The flue duct of the final extension must be 30mm longer than the air duct. Fig.27 - Elbow to Flue Turret Assembly. Each section must be connected to the previous section of the flue bend by fixing the flue ducts together and then similarly fixing the air ducts which engage the elbows. 120mm 100mm Flue Turret Fit the assembly as described in Section 11.9, 11.10 as appropriate. Make good the internal and external brickwork or rendering. 11.13 Vertical Adapter for Horizontal Flues. An adapter is available for an initial short section of vertical flue. Refer to Fig. 28. Measure and cut the flue as described in Section 11.11. The first, vertical, section (equivalent to dimension X) is measured from the top of the boiler casing. Cut the vertical section of the extension duct to 167mm less than the measured distance. Do not remove the socketed ends. The minimum measured distance is 167mm. Seal the air duct to the spigot using silicone sealant. Fix the adaptor with the clamp and screw provided. Bend Fig.28 Vertical Adapter. Flue Duct 11.14 Completion of the Installation. Check that all the connections on the manifold have been tightened. Refer to Fig.6. Air Duct Remove the facia bottom panel. Refer to Fig.29. Connect the mains electricity supply lead to the appliance and secure the cable clamp. Refer to Fig.14. Check there is sufficient loose lead to allow the release of the facia panel assembly and that the earth lead of the mains supply cable is longer than the live and neutral leads. Adapter Fit the facia mounted programmer if applicable. Refer to Fig.31. Clamp Connect any external controls ensuring that the leads pass through the appropriate clamps. refer to Fig.32. Flue Spigot Test for gas soundness as described in BS6891. If the appliance is not commissioned immediately, replace the cabinet and facia bottom panel. Check that the gas and electricity services have been turned off. 16 Fig.29. Facia connections cover Cover panel Fig.30. Programmer cover Facia Controls connections cover Programmer connections Facia Fixing screw Facia bottom panel (clip-on) Fig 32 - Mains Voltage External Controls Connections NOTE: Only double insulated controls not requiring an earth can be used Ns Ls LR Ns Ls LR Control board ST8 Programmer connector Live Switched Live Remove Link Neutral Neutral Facia Switched Live ST8 Live Fig.31. Programmer connection Remove Link Motor 230 V Room Thermostat Connections 230 V Programmer Connections 230 V room thermostat and Programmer Connections Ns Ls LR ST8 Fig.33. Facia connections 1 2 11 3 4 5 10 7 6 9 8 6. Controls 24V - ST13 7. Mains harness ST16 8. Fan ST1 9. Pump ST5 10. Earth tag 11. Cable clamps (threaded) 1. Earth screw 2. Mains connection (L N) 3. Fuse F1 4. Mains voltage room thermostat/external control-mains voltage ST8 5. Fuse F2 17 Live Series connection to be made safe Live Motor Ne ut ral e Liv Pressure gauge d he itc Sw Programmer Neutral Clip Swit che d Liv e Programmer connections Fig. 35. Pump venting. 12. Commissioning The Appliance Pump Benchmark Water Treatment: For optimum performance after installation, this boiler and its associated central heating system should be flushed in accordance with the guidelines given in BS7593:1992 - Treatment of water in domestic hot water systems. Full instructions are supplied with proprietary cleansers sold for this purpose. If an inhibitor is to be used after flushing, it should be used in accordance with the inhibitor manufacturers instructions. Suitable flushing agents and inhibitors are available from Betz Dearborn Tel: 0151 4209563 and Fernox Tel: 01799 550811. Instructions for use are supplied with these products. Pump cap Electrical connections cover Fig.34. Automatic air vent and combustion test point 12.3 Set the System Pressure Fill the system until the pressure gauge is at 2.5bar and check for leaks. Release water from the system using the relief valve test knob until the required system pressure is obtained, upto a maximum of 1.5bar. Set the pointer on the pressure gauge to record the set system pressure. If the pressure indicated on the gauge is greater than 2.65bar when operating at the maximum central heating temperature, an extra expansion vessel must be fitted to the system as close as possible to the appliance central heating return connection. The appliance [as despatched] can accommodate a system volume of 100 litres with a system pressure of 0.5bar. Refer to BS7074 Part 1, BS5449 and Table 8. If the system volume is greater then an extra vessel must be fitted as close as possible to the appliance central heating return connection and pressurised to the same figure as the integral vessel. 12.4 Clock/Programmer: The controls fitted to the appliance should be set up at this stage. 12.5 Check that the gas and electricity supplies are turned off. Connect a pressure gauge to the gas valve burner pressure test point. Refer to Fig 36. Flue connections Automatic air vent Expansion vessel charging point Expansion vessel Combustion products test point (front cap) Wall mounting frame 12.1 Remove the appliance cabinet by removing the screw at the top centre of the cabinet. Check that the electrical supply and the gas supply to the appliance are turned off and that all the water connections throughout the system are tight. Open the system valves at the appliance. Refer to Fig.6. Open all the radiator valves. Remove the automatic air vent cap. Refer to Fig. 34. Fill the system through the external filling loop. Refer to Section 7, Sealed System. Vent each radiator in turn. The automatic air vent will vent the appliance. Refer to Fig 34. Remove the cap from the pump and turn the shaft about half a turn. Replace the cap. Refer to Fig 35. Check that the pressure relief valve operates by turning the knob anti-clockwise until it releases. Lower the facia to gain access to the relief valve. Refer to Fig 17. Water should be expelled from the discharge pipe. 12.2 Set the Expansion Vessel Pressure The charge pressure of the expansion vessel as dispatched is 0.5bar, which is equivalent to a static head of 5m [17ft]. The charge pressure must not be less than the static head at the point of connection. A Schraeder type valve is fitted to the expansion vessel to allow the charge pressure to be increased if necessary. Refer to Fig 34. The expansion vessel must be charged to 0.35bar less than the initial system design pressure. Note: 1bar = 10.2m = 33.5ft of water. Fig. 36. Gas valve. Modulating solenoid valve Burner connection Burner pressure test point Minimum pressure adjustment screw Maximum pressure adjustment screw Safety solenoid valves Inlet pressure test point Gas 18 Remove the clip-on facia bottom cover and controls connections cover. Refer to Fig 29. Slide down the access panel to display the mode switch and the adjusting tool. Refer to Fig 37. 12.6 Checking the Burner Pressure Check that all the radiator valves are open. Check that the system is pressurised and set to the required pressure as indicated on the gauge. Set the temperature control knobs to maximum and the clock/programmer to operate continuously. Turn on the gas and electricity supplies. Set the mode switch to MAX using the mode adjuster tool. Refer to Fig 37 and 38. NOTE: Two red lights will flash rapidly on the facia. necessary for the central heating potentiometer to be adjusted to change the burner pressure. If adjustment is required then the adjusting tool is used to alter the setting of the potentiometer. Refer to Fig 38. Set the mode switch to MIN. NOTE: Two red lights will flash rapidly on the facia. The burner pressure will drop to the minimum pressure appropriate to the appliance and the gas for both the central heating and domestic hot water modes. Refer to Table 1. It should not be necessary for the central heating potentiometer to be adjusted. Test for gas soundness at the joint between the burner and the gas valve with leak detection fluid. Set the mode switch back to Normal. Turn the electricity supply off and then back on to reset the controls. Replace the facia cover panels. 12.7 Domestic Hot Water Turn the central heating temperature control knob fully anticlockwise. Refer to Fig. 39. Open a hot tap near the appliance. The burner will light and go to the maximum burner pressure appropriate to the appliance and the gas . Refer to Table 1. Gradually close the tap and check that the burner pressure falls. Fully open the tap and check that the pressure rises. Close the tap and check that the burner goes out. The fan may continue running until the appliance has cooled to a pre-set temperature. 12.8 Central Heating Check that all the radiator valves are open. Check that the system is pressurised and set to the required pressure as indicated on the gauge. Check that the clock/programmer is set to operate continuously. Set the room thermostat and the central heating temperature control to maximum. The burner will light and the appliance will modulate its output from minimum to maximum over a period of about two minutes. Check that all the radiators are heating up evenly. Shut down all but one of the radiators and observe the burner pressure fall. Open all the radiators and check that the burner pressure rises. 12.9 Balance the system to give a temperature differential of 11°C. A non-adjustable by-pass is fitted to the appliance. 12.10 Set the room thermostat to minimum and check that the burner goes out. Reset the room thermostat to maximum and the burner will re-light and follow the normal operating procedure. Turn off the gas service cock. The burner will go out but sparking from the electrode will continue for 10 seconds when the appliance will ‘lock-out’. After 60 seconds carefully open the gas service cock, press the reset button and observe the burner relight and follow the normal sequence of operation. Refer to Fig 6 and 39. Turn off the gas service cock and the electricity supply to the appliance. Drain the system while the appliance is hot. Refill, vent and re-pressurise the system as described in Section 12.1 preceding, adding, if necessary, a suitable proprietary inhibitor. Further information is available from Betz Dearborn 0151 420 9563 or Fernox 01799 550811. 12.11 Domestic Hot Water and Central Heating Set all controls to maximum. Turn on the electricity supply to the appliance and open the gas service cock at the appliance. The burner will light and heat will pass into the system. Turn on a hot tap and check that hot water is soon discharged from the tap. Close the tap. The appliance will then return to the central heating mode and automatically balance with the system requirements. Turn off the appliance. 12.12 Completion of Commissioning Disconnect the pressure gauge and tighten the test point screw. Restart the appliance and check for gas soundness around the test point screw. Refit the cabinet. Fig.37. Mode control cover Mode adjuster Facia Mode adjustment cover Fig.38. Mode adjustment Central heating limit potentiometer Max/Min switch Not operational A continuous spark will occur until the burner is alight and sensed by the control circuit. The burner will remain at its maximum domestic hot water pressure for one minute. Refer to Table 1. It should not be necessary for the gas valve to be adjusted. Note: The burner pressure is factory set and if, after checking that the dynamic (working) supply pressure is sufficient i.e. 18.0mb (NG) approx, or 36mb (LPG) at the gas valve inlet pressure test point, the correct pressure cannot be obtained then Worcester Heat Systems Service Department should be contacted. If the appliance does not light then check that it is not in the ‘lock-out’ state by pressing the reset button. Refer to Fig 39. Set the mode switch to Normal. The burner pressure will drop to the minimum setting and will ramp up to the maximum central heating pressure appropriate to the appliance and the gas. Refer to Table 1. It should not be 19 If the appliance is to be passed over to the user immediately then set the controls to the users requirements. If the appliance is to be left inoperative in frosty conditions then set the programmer, if fitted, to off. Do not turn the electricity or gas supplies off. The appliance will operate under the control of the integral frost protection facility. If there is any possibility of the appliance being left totally unused in freezing conditions then switch off the gas and electricity and drain the appliance and the system. starting any service procedures. Always test for gas soundness after the service has been completed. 14.3 Component Access To service the appliance it may be necessary to remove some or all of the following parts to gain access to components which may need to be checked or replaced. Cabinet Unscrew the screw at the top of the cabinet, release the sides. Lift up and away from the top locating pegs. Facia Panel Unscrew the two screws and lower. Refer to Fig 40. Inner Case Cover Unscrew the four fixing screws and remove the cover. Refer to Fig 40. 13. Handover Fig. 39. Facia controls Central Heating Reset Indicator Button Light Power ON Indicator Domestic Hot Burner Water Indicator Operation Light Light Fig.40. Inner case and facia fixing Fixing screws (4) ! 0 I Inner case cover Mains ON/OFF Switch Central Heating Operation and Temperature Control Knob Domestic Hot Water Temperature Control Knob System Pressure Gauge Facia panel fixing screws (2) 13.1 Hand over the User Booklet. 13.2 Explain how to operate the appliance safely and efficiently. 13.3 Tell the user what to do if the appliance is not to be used in very cold conditions. 13.4 Tell the user what to do if the system pressure falls. 13.5 Explain that regular servicing will maintain the safe and efficient operation and extend the life of the appliance. WHS can offer a comprehensive maintenance contract. 13.6 Tell the user that any work on the appliance must only be carried out by a competent, CORGI registered, person. 13.7 Complete and hand over to the user the Benchmark Log-Book. 0 I Facia Combustion Chamber Unscrew the two screws at the top and the two wing nut extended screws at the sides, pull forward and remove. Refer to Fig 41. Fan Carefully pull off the electrical connections and the tubes from the airflow-sensing device. Unscrew the four screws and remove the fan assembly. Refer to Fig 42. Flue Hood Remove the fan. Unscrew the four screws and remove the hood. Refer to Fig 43. Burner Remove the combustion chamber. Carefully pull off the connections to the spark and flame sensing electrodes. Release the union nut beneath the burner and remove. Refer to Fig 44. 14.4 Component Cleaning Only use a non-metallic brush to clean components. Clean the fan taking care not to block air flow detector. Clean the burner to ensure that the blades and injectors are clear. Do not us a metal probe to clean the injectors. Clean the electrodes, replace if there is any sign of deterioration. Clean the heat exchanger. Cover the gas inlet tube and remove any deposits from the heat exchanger from the top and bottom. Carefully straighten any distorted fins on the heat exchanger. Check the combustion chamber insulation and replace if there is any sign of damage or deterioration. Refer to Section 15.4.5. Clean the controls in situ using a non-metallic brush. Carefully refit any components removed in the reverse order. Check that all screws are tight and the connections properly remade with the appropriate gaskets/O-rings. Re-commission, as necessary, for correct operation to the users requirements. Refer to Section 12 Commissioning. 14. Inspection And Service 14.1 The extent of the service is determined by the operating condition of the appliance when tested by a competent person. It is the law that any service work is carried out by a competent CORGI registered person. 14.2 Inspection Check that the terminal and the terminal guard, if fitted, are clear and undamaged. If the appliance is in a compartment or cupboard check that the specified service space around the appliance is clear. Refer to Table 8. Check all the joints and connections in the system and remake any that show signs of leakage. Refill and re-pressurise as described in Section 12-Commissioning. Operate the appliance and take note of any irregularities. Refer to Section 18-Fault Finding for rectification procedures. Check the combustion performance Remove the cap from the sample point on the top of the appliance. Refer to Fig 34. Connect the sampling meter. With the appliance at maximum rate and stable in the DHW mode expect readings of NG 5.5 - 8.5% CO2, 0.002 - 0.015% CO. These figures cover all flue conditions. Refit the cap after the test. Disconnect the electrical supply at the mains and turn off the gas supply at the gas service cock on the appliance before 20 Fig.41. Inner case components Flue spigot Inner casing Combustion products test point (front cap) Fan assembly Flue hood Overheat thermostat (at rear) Combustion chamber/flue hood fixing screws Primary sensor Heat exchanger Combustion chamber fixing screw Combustion chamber fixing screw Combustion chamber Burner Burner connection 21 Fig.43. Flue hood Fig.42. Fan assembly Fan assembly Flue hood fixing screws Fan assembly fixing screws Air flow sensing tube Flue hood Air flow sensing tube (red) Flue hood Flue hood/Heat exchanger guide Fig.44. Burner assembly Burner blade assembly Spark electrode assembly Flame sense electrode Burner manifold Fixing screw Fixing screw NOTE: Front and rear crosslighting strips are not shown Spark electrode leads Burner connection union Flame sense electrode lead Important: A small quantity of water will remain in some components even after the appliance has been drained. Protect any electrical components when removing items from the water circuits. 15.4 Component Replacement Refer to Fig 41 and 45 for an indication of the location of the various components. Replace any components removed from the appliance in the reverse order using new gaskets/O-rings/sealant/heat transfer paste where necessary. Always check that any electrical connections are correctly made and that all screws are tight. Remove casing and cover panels and lower the facia, as necessary, to gain access to the components. Refer to Section 14, Inspection and Servicing. 15.4.1 Gas Valve Do not remove the inner casing. Unscrew the union connections above and below the gas valve and remove the assembly. Disconnect/unplug the electrical connections from the valve. Use new gaskets when replacing the valve. Refer to Fig 45. Set the Gas Valve: Connect a pressure gauge to the burner pressure test point on the valve. Refer to Fig 36. 15. Replacement Of Parts Important: Turn off the gas and electricity supplies before replacing any components. 15.1 After the replacement of any components always check for gas soundness where relevant and carryout functional checks as described in Section 12-Commissioning. Any O-ring or gasket that appears damaged must be replaced. Complete gasket and O-ring packs are available for gas and water connections on the appliance. 15.2 Component Access Refer to Section 14, Inspection and Servicing for access to components. 15.3 Draining the Appliance Primary System: Turn off the heating flow and return valves at the appliance. Refer to Fig 16. Open the drain tap. Refer to Fig 17. Close the drain tap when the flow from the appliance has stopped. DHW Circuit: Turn off the mains cold water supply at the appliance. Refer to Fig 16. Open a hot tap below the level of the appliance to drain the domestic hot water from the appliance. 22 Fig.45 . Lower casing - gas and water controls. Gas Valve Pump connection Air flow switch Expansion vessel connection Water flow switch Pump Red tube (+ve) Pump connection Clear tube (-ve) Pressure gauge Relief valve Earth connection Boiler drain connection 1 Transformer Facia assembly Spark electrode lead Switch on the gas and electricity supplies. Check for gas tightness at the gas valve inlet. Refer to Section12-Commissioning for the method of checking the pressures. Check for gas soundness at the gas valve outlet. Adjust the maximum and start pressure [minimum], as necessary, to obtain the required pressures. Switch off the appliance and disconnect the pressure gauge. 15.4.2 Spark Electrode Remove the inner casing and the combustion chamber. Carefully pull off the leads from the electrodes. Loosen the screw and remove the spark electrode assembly. Refer to Fig 46. Fig.47. Flame sense electrode Notched to aid location in the fixing bracket Flame sense electrode Burner blade assembly NOTE: Cross- lighting strips are not shown Fixing bracket Fig.46. Spark electrode assembly Fixing screw Notched to aid location in the fixing bracket Flame sense electrode assembly Spark electrode Burner blade assembly and remove the flame sensing electrode assembly. Refer to Fig 47. Ensure that the electrode is at the correct height above the burner blade. 15.4.4 Burner Remove the inner casing and the combustion chamber. Remove the electrode connections. Release the union connection beneath the burner and remove the burner from the appliance. Refer to Fig 44. Do not omit the gasket when fitting the new burner. 15.4.5 Combustion Chamber Insulation Remove the burner as described in 15.3.4 preceding. Remove the primary heat exchanger as described in 15.4.21 following. Replace the side and front pads in the combustion chamber assembly. Refer to Fig 48. Replace the rear insulation pad. NOTE: Cross- lighting strips are not shown Fixing bracket Fixing screw Spark electrode assembly 15.4.3 Flame Sense Electrode Remove the inner casing and the combustion chamber. Carefully pull off the lead from the electrode. Loosen the screw 23 Fig.48. Combustion Chamber Insulation. Fig.50. Pressure Gauge capillary fixing Pressure gauge capillary fixing clip Insulation panel-front Boiler drain ON/OFF Combustion chamber assembly Boiler drain tube connection (tube attached) Fixing screws Relief valve Pressure gauge capillary Insulation panel-side Relief valve fixing clip Do not omit the O-ring from the pressure capillary when fitting the replacement gauge. 15.4.7 Relief Valve Remove the cabinet and lower the facia. Check that the appliance has been fully drained. Disconnect the relief valve drainpipe. Unclip and pull-out the valve. Refer to Fig 51. 15.4.6 Pressure Gauge Remove the cabinet and lower the facia panel. Refer to Fig 40. Check that the appliance has been fully drained. Withdraw the clip and remove the pressure-sensing head. Refer to Fig 50. Unclip the gauge head from its mounting bracket and remove.Refer to Fig 49 Fig.51 . Relief valve drain connection Relief Valve Drain Connection (push fit) Pump Fig.49. Pressure Gauge head Pump Boiler Drain Casing side panel Pressure gauge capillary Mounting bracket Pressure Gauge Capillary Pressure gauge head Facia panel 24 Relief Valve 15.4.8 Flow Switch Drain the DHW circuit as described in 15.3 preceding. Remove the cabinet and lower the facia panel. Carefully pull off the connections from the micro-switch. Undo the two union connections on the valve and remove the valve. Refer to Fig 52. Do not omit the gaskets when fitting the replacement switch. The new flow-switch must be set to deliver the correct flow rate to give a temperature rise of 40°C ie 10 l/min (28Si) or 9 l/min (25Si). The adjustment is made by turning the red adjuster clockwise to reduce the flow rate and anti-clockwise to increase the flow rate. Make the adustment with the gas turned off. 15.4.10 Control Board Remove the facia bottom panel and carefully disconnect all the electrical connections. Refer to Fig 33. Remove the cabinet and lower the facia panel as described in Section 14.3, Inspection and Servicing. Disconnect the earth connection at the appliance. Refer to Fig 45. Unscrew the four screws and remove the metal cover. Refer to Fig 54. Lift out the control board. Refer to Fig 55 Pull out and transfer the transformer to the new board together with the plastic locating frame. Re-commission the appliance to check and set the burner pressures. Refer to Section 12, Commissioning. Fig. 52. Water Flow switch. Micro Switch Fig.54. Control board cover Seal Flow Switch RED KNOB NOT SHOWN Main earth connection Outlet Union Cover panel Control board fixing screws Facia assembly pivot point Inlet Union (with seal) Control board Cold Water Inlet Transformer Facia assembly 15.4.9 Inlet Water Filter Remove the flow switch as described in 15.4.8 preceding. Unscrew the two screws and remove the securing plate. Firmly withdraw the union connection assembly and pull out the filter. Refer to Fig 53. Carefully clean or replace the filter. Fig.55. Control board Fig. 53. Inlet water filter Control board locating frame Flow Switch Filter O-Ring Securing Plate and Screws Control board Seal Inlet Union Facia assembly 25 15.4.11 Transformer Remove the cabinet and lower the facia panel as described in Section 14, Inspection and Servicing. Unscrew the four screws and remove the metal cover. Refer to Fig 54. Pull out the transformer. Refer to Fig 56. Do not omit the heat transfer paste when fitting the replacement sensor. 15.4.16 Overheat Thermostat Remove the cabinet and the inner casing. Carefully pull-off the connections. Unscrew the two screws and remove the sensor. Refer to Fig 58. Fig.56. Transformer Fig.58. Primary sensor and overheat thermostat Control board Primary sensor leads (red) Flue hood Mounting plate Overheat thermostat leads (orange) Primary sensor Fixing screws Overheat thermostat Transformer Fixing clip Mounting plate Facia 15.4.12 Clock/Programmer Remove the clock/programmer assembly by carefully pulling it from the facia to release the clips. Unplug the connector at the control board. Comprehensive instructions are sent with the new control. Refer to Fig 57. Fig.57. Programmer connection Apply a small quantity of heat transfer paste to the face of the replacement sensor. Carefully reposition the sensor so that the connections are away from the flue hood. Reconnect the sensor. 15.4.17 DHW Sensor Remove the cabinet and lower the facia. Carefully pull off the connections. Unscrew the clip and remove the sensor. Apply a small quantity of heat transfer paste to the face of the replacement sensor. Refer to Fig 59. Control board Facia Programmer connector Programmer connections Fig.59. Domestic hot water sensor Clip Programmer Cenral heating flow pipe Pressure gauge Domestic hot water flow pipe Domestic hot water temperature sensor 15.4.13 Fan Remove the inner casing. Remove the fan as described in Section 14.3, Inspection and Servicing. Ensure that all the connections are correctly made to the new fan. 15.4.14 Air Flow Detector Remove the fan as described in 15.3.13 preceding. Unscrew and , through the fan outlet, withdraw the airflow detector. Refer to Fig 42. 15.4.15 Primary [CH] Sensor Remove the cabinet and inner casing. Carefully pull-off the connections. Withdraw the clip and lift off the sensor. Refer to Fig 58. Fixing clip Air flow switch Sensor leads (yellow) Fixing screws 26 15.4.18 Pump Check that the primary circuit has been fully drained as described in 15.3 preceding. Release the water connections and remove the pump. Refer to Fig 45. Disconnect and transfer the electrical connections to the new pump. Set the pump speed to maximum. Do not forget the gaskets at the connections. Alternatively the pump head only [Grundfos 15-60] may be replaced by unscrewing the four securing screws. Take care not to scratch the mating surfaces . 15.4.19 Expansion Vessel The specified replacement can be fitted into the system return as close to the appliance as possible. Re-fill and pressurise the system as described in Section 12 Commissioning. 15.4.20 Auto Air Vent Drain the primary circuit as described in 15.3 preceding. Unscrew and remove the auto air vent. Do not omit the sealant (Loctite 575) when fitting the replacement air vent. Remove the cap. Refer to Fig 34. 15.4.21 Primary Heat Exchanger Check that the appliance has been fully drained as described in 15.3 preceding. Remove the combustion chamber as described in Section 14.3, Inspection and Servicing. Remove the temperature sensors as described in 15.4. 15, 16 and 17 preceding. Undo the four union connections and remove the heat exchanger. Do not omit the sealing washers when fitting the replacement heat exchanger. Refer to Fig 60. 15.4.22 Air Flow Switch Carefully pull-off the connections from the switch. Unclip and remove the switch. Refer to Fig 61. Ensure that the connections are correctly made on the replacement switch. Fig.60. Primary heat exchanger Heat Exchanger Central heating flow Central heating return Domestic water inlet Domestic hot water flow Fibre washer Union connections Union connections Fibre washer Fig.61. Air flow switch Air flow switch Air flow switch leads (green) Red tube Clear tube 27 16. Short Parts List Key No. G.C. No. 10 15 17 18 25 26 28 30 34 34 34 35 39 49 52 55 57 59 63 63 66 69 70 77 84 85 96 E27-572 E27-578 E27-580 E27-582 E27-586 E27-587 E01-601 E27-592 E27-596 E27-597 E27-598 E27-600 E27-605 E27-616 299-363 E27-618 E27-620 E27-623 375-696 375-696 299-495 E25-322 E25-323 E27-636 E27-643 E27-644 E27-648 Part Flow Switch Water Filter Pressure Relief Valve Pump Pressure Gauge Expansion Vessel Automatic Air Vent Gas Valve Burner (NG) Burner (LPG) 28Si Burner (LPG) 25Si Primary Heat Exchanger Combustion Chamber Insulation Fan Assembly Air Flow Detector Inner Case Seal Air Flow Switch Control Board Primary (CH) Sensor DHW Sensor Overheat Thermostat Spark Electrode Assembly Flame Sense Electrode Transformer Fibre Washer Pack O-Ring Pack Digital Timer Fuse Pack Manufacturer Prettl Prettl Altechnic Grundfos 59896603 Inter Albion x 32556 Winkleman & Panhof 15KCaleffi 502632CST Junkers Vulcano Vulcano Vulcano ELM Avon WHS WHS Huba 605. 99486 Junkers Heatronic Elmwood Elmwood Elmwood Vulcano Vulcano Junkers Qty WHS Part No. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 717 002 122 0 8 716 148 410 0 8 716 156 764 0 8 716 143 114 0 8 716 142 388 0 8 715 407 154 0 8 716 140 504 0 8 747 003 381 0 8 718 120 565 0 8 718 120 566 0 8 718 120 569 0 8 716 759 081 0 8 716 121 601 0 8 716 121 546 0 8 716 141 000 0 8 716 121 602 0 8 716 142 387 0 8 748 300 336 0 8 716 142 302 0 8 716 142 302 0 8 716 142 389 0 8 708 107 008 0 8 708 107 009 0 8 747 201 274 0 8 716 121 603 0 8 716 121 604 0 7 716 192 019 8 716 156 013 0 FLUE OPTIONS E01-943 E01-944 E01-945 E01-946 E01-058 E01-059 Telescopic Horizontal Flue Kit Extension Flue Kit Vertical Flue Kit Vertical Flue Adaptor Internal Fixing Kit Flue Elbow Kit Flue Elbow Kit 425 - 725mm 750mm Telescopic Flue 90 deg. 45 deg. 28 7 716 191 068 7 716 191 006 7 716 191 069 7 716 191 016 7 716 191 019 7 716 191 013 7 716 191 014 29 17. Operational Flow Diagrams Room thermostat and/or mains programmer (or link) On AND AND Electronic facia programmer (if fitted) On AND ST13 link in AND CH control knob On CENTRAL HEATING FUNCTION MAIN SWITCH ON CENTRAL HEATING DEMAND CH light On. Pump On. Fan ON/ ignition Sequence. Burner Light On. Three minute wait Green Light On Two minute minimum burner pressure then ramp up pressure over next one minute Modulate gas to maintain flow temperature set by control knob DEMAND END Overrun function (see overleaf) Over temperature shutdown if flow temperature 5°C above set value Gas valve Off. (CH light still on. Pump still On) DOMESTIC HOT WATER FUNCTION MAIN SWITCH ON DOMESTIC HOT WATER DEMAND (Priority over CH demand) YES Is CH interrupted? NO Flow switch On (Tap open) Green Light On Pump continue 4 seconds if primary temp above DHW setting. Burner to MAX for 4 seconds Modulate gas to maintain delivered water temperature set by control knob Ignition sequence and burner to MAX for 4 seconds DHW temp drops to user set point Primary 75° Over temperature shut-down if water temperature above 85°C Gas valve off. Fan on 35 seconds. Pump on until temp drops to 60°C Primary temperature 115°C Gas valve off. Fan on. Pump on 30 DEMAND END Overrun function (see overleaf) OVERRUN FUNCTION END DHW DEMAND If primary temp above 80° fan runs until temp below 80°C (35 seconds minimum) Fan overrun function active for 3 minutes If primary temp below 80° run fan for 35 seconds If primary temp over 85° pump cycles for 2 seconds every 10 seconds until temp below 85° END CH DEMAND If primary rises above 85° fan runs until temp falls below 80° After 3 minutes the pump runs if: primary temp over 95° until below 77° hot water temp over 98° until below 63° Pump runs for 3 minutes AUTOFROSTAT FUNCTION No demand and primary temperature below 8°C Internal “Autofrostat” demand Wait in normal off state for 30 minutes Run Runpump pumpfor four minutes Monitor central heating sensor Below 5°C 5°C to 9°C Above 9°C Commence normal central heating mode until temperature reaches 20°C 30°C 31 Return to normal off state 18. Fault Finding Note: This fault-finding information is for guidance only. Worcester Heat Systems cannot be held responsible for costs incurred by persons not deemed to be competent. The electronic control system for this boiler incorporates four lights on the facia. These are used to show normal operating status. But as a secondary function, by flashing, they can also be used to help provide fault diagnostics. Therefore, with individual or groups of lights being permanently off, on or flashing, every normal fault can be identified. To use the fault finding system, select a box below which represents the light situation during your fault. Then refer to the appropriate following section. This fault-finding system assumes that the appliance has been operating correctly until the time of failure. PRELIMINARY CHECKS Preliminary electrical system checks are the first electrical checks to be carried out during a fault-finding procedure. On completion of the Service/Fault-Finding task which has required the breaking and remaking of electrical connections, check (a) EARTH CONTINUITY, (b) SHORT CIRCUIT CHECK, (c) POLARITY and (d) RESISTANCE TO EARTH. 2 lights flashing fast FAIL POINT K L Note: Slow flash is once per second, fast flash is five times per second. Slow flash can only be cleared by using the facia reset button (press for at least one second). Fast flash is cleared by removing fault and/or main switch off/on. 32 Is the facia on/off switch turned on? `(Clockwise) No Turn switch on. FAIL POINT A Yes Is there a 230V AC live supply across Terminal ST12 pins L and N No Check electrical supply to boiler. Yes Has fuse F1 blown? No Replace control board (Section 15.4.10) Yes Replace fuse and investigate cause. Suggestions: Cable damage, connections to (or faults within) pump, fan, external 230V controls, transformer or board. FAIL POINT B Has fuse F2 blown? No Yes Replace fuse. This will be caused by fuse fatigue or by the board. Remove control board from facia (See Section 15.4.10) and separate transformer from board. Measure resistance across the two pairs of adjacent pins on the transformer. Are any pair above 100 ohms? Yes FAIL POINT C Replace transformer. Green diode is damaged. Replace control board. (Section 15.4.10) 33 No Replace control board (Section 15.4.10). With CH control knob fully clockwise, does the boiler ignite and appear to run normally in central heating mode? No Is there 230V AC across terminal ST8 pins LR and N? No There is no heat demand. Check room thermostat or mains programmer (or link). Yes Yes Red diode is damaged. Replace control board. (Section 15.4.10) FAIL POINT D Is there a link at terminal ST13 pins 1 and 2? No Insert a link Yes Is there an electronic programmer at position ST5 at righthand end of board? No Replace control board. (Section 15.4.10). Yes Remove programmer connector from board edge. Does CH lamp now light? No Yes FAIL POINT E Correctly set or replace electronic programmer. With a hot water tap fully open, does the boiler ignite and appear to run normally in hot water mode? Yes Red diode is damaged. Replace control board. (Section 15.4.10) No Remove multiway connector from board position ST16. With tap still open is there continuity across contacts 19 and 20 (2 pink wires)? No Locate and observe the flowswitch assembly (behind the air pressure switch). Does the lever above the microswitch move up and down with the demands, thus activating and de-activating the microswitch? Yes Yes Replace control board. (Section 15.4.10). Check or replace wiring or microswitch 34 No Replace flowswitch assembly FAIL POINT F Is the boiler in a very cold environment (less than 5°C)? No Replace control board. (Section 15.4.10). Note: A damp board could cause this fault. Yes Boiler is running in “Autofrost stat” mode. See Section 17. Is the boiler fully water pressurised and is all air vented? No Rectify fault. FAIL POINT G “Primary Overheat” Yes Reset the controls and restart the boiler. Does the pump run? No Repair or replace pump. (Section 15.4.18). Yes Remove inner casing cover and inspect the primary sensor (left of heat exchanger). Is it correctly fixed to pipe? No Re-fix sensor to pipe. Yes Remove the multiway connector from board position ST16. Is there a short circuit across contacts 5 & 6? No Replace overheat thermostat or check wiring to it Yes Fault caused by control board or heat exchanger 35 Is the gas supply connected and at the correct pressure? No Rectify gas supply problem. Yes Remove front panel. Reset and restart the boiler. Can a flame be seen through the spy glass? No Remove inner cover. Reset and restart the boiler. Does a spark occur across the electrodes? No Are the electrodes and gap and connections in good order? No Repair or replace spark electrode (Section 15.4.2) or HT leads Yes Replace control board. (Section 15.4.10). Yes Turn off boiler. Remove the multiway connector from board position ST16. Test resistance across contacts 7 and 8 (brown wires) and 9 and 10 (violet wires). Are both reading below 200 ohms? FAIL POINT H “Burner Lockout” Yes No Yes Turn off boiler. Remove inner cover and combustion chamber cover. Are the sense electrode and lead in good condition and is gap correct? Yes Replace gas valve. (Section 15.4.1). Replace control board. (Section 15.4.10). If problem not solved replace gas valve. (Section 15.4.1) No Repair or replace flame sensor (Section 15.4.3) or wiring. Yes Remove multiway connector from board position ST16. Is there continuity from contact 11 (white wire) to flame sensor? No Yes Does the flashing fault signal occur at the start of a demand? No Remove both brown connectors from gas valve. Is there continuity from brown and violet wires to multiway connector? Flashing occurs at end of demand. Replace gas valve. (Section 15.4.1). Yes Replace control board (Section 15.4.10). Note: It is not possible to reliably check the cross-light performance of the burner. In the unlikely event of such a fault, investigate flue problems or replace burner or injector. (Section 15.4.4). 36 No Repair or replace harness. Is the multiway connector at board position ST16 pushed fully home on to the board? No Push fully home Yes Check the DHW sensor. Is it correctly fitted onto the pipe with heat conductive paste between the pipe and sensor? No Re-fix sensor onto pipe Yes FAIL POINT I “Sensor Fault” Remove multiway connector from board position ST16. Test resistance across contacts 17 and 18 (yellow wires). Is it between 1 kohm and 30 kohm? No No Repair or replace harness. Yes Check or replace DHW sensor. (Section 15.4.17). Yes Test resistance across contacts 12 and 13 (red wires). Is it between 1 kohm and 30 kohm? Is there continuity from contacts 17 and 18 to DHW sensor? No Is there continuity from contacts 12 and 13 to CH sensor? No Repair or replace harness. Yes Check or replace CH sensor. (Section 15.4.15). Yes Test resistance across contacts 7 and 8 (brown wires) and 9 and 10 (violet wires). Are both readings below 200 ohms? Yes Replace control board. (Section 15.4.10). No Remove both brown connectors from gas valve. Is there continuity from brown and violet wires to the multiway connector? No Yes Replace gas valve. (Section 15.4.1). 37 Repair or replace harness. Does the fan run before the fault occurs? No Turn off boiler. Is there continuity across the C and NO terminals of the air pressure switch (where green wires are fitted)? No Remove the fan connector from board position ST1 and restart the boiler. Is there mains 230V across the centre (L) and left (N) tracks at ST1? Note: Take care not to short L to N. No Replace control board. (Section 15.4.10). Yes Yes Yes Air pressure switch is shorting. Replace switch. (Section 15.4.22) FAIL POINT J “Air Pressure Fault” Does the burner ignite (burner light on) before fault occurs? No Remove electrical connectors from pressure switch and restart boiler. Is there continuity between C and NO terminal (where green wires were fitted) when the fan runs? Repair or replace fan (Section 15.4.13) or cable. No Pressure switch has not closed. Are the silicon tubes in good condition and free of condensation. Replace tubes. If condensation has occurred, also replace pressure switch and check condition of Venturi in the fan. Yes Inspect the flue. Is it free of any restrictions? Yes Replace air pressure switch (Section 15.4.22). Note: In the unlikely event of this not solving the problem inspect the pressure pick-up (Venturi) in the fan. Yes Yes Remove multiway connector from board position ST16. Is there continuity of the green wires? No No Yes Replace control board. (Section (15.4.10). Pressure switch has opened during operation. Check flue for blockage. Also investigate sense tubes and pressure switch. 38 Repair wires or replace harness. No Rectify flue problem. FAIL POINT K The gas valve mode switch (concealed by the facia side panel) is not set correctly FAIL POINT L Light indication during fault not covered by above details. Turn to 'NORM' position Control board is likely to be wet or damaged or malfunctioning. Check for wet board or connections. Dry and re-use or replace control board. (Section 15.4.10). Hot water temperature always too hot during a demand (not regulating). Hot water sensor could be off or poorly fixed to pipe. Repair or replace sensor. (Section 15.4.15). Water temperature very low/low gas pressure (with all knobs set to maximum)? Is the gas set to correct pressure? No Set pressure. Yes Remove multiway connector from board position ST16. Is the resistance across contacts 1 and 2 (blue wires) below 60 ohms. No Yes Remove blue (top) connector from gas valve. Is there continuity along blue wires to multiway connector? Yes Replace control board. (Section 15.4.10). Replace gas valve. (Section 15.4.1). 39 No Repair wires or replace harness. This manual is to be used in conjunction with the variant part number of the bar code below: Bosch Group Worcester Heat Systems Limited (Bosch Group), Cotswold Way, Warndon, Worcester WR4 9SW. Telephone: (01905) 754624. Fax: (01905) 754619. Technical Helpline (08705) 266241. www.worcester-bosch.co.uk This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued improvement. All goods sold are subject to our official Conditions of Sale, a copy of which may be obtained on application. PUBLICATION 8 716 115 067a (05/08)
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project