- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- APC
- SUVTP20KH2B2
- Data Sheet
advertisement
▼
Scroll to page 2
of 6
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Warning: ALL safety instructions in the Safety Sheet (990-2822) must be read, understood, and followed when installing the UPS system. Failure to do so could result in equipment damage, serious injury, or death. Installation Smart-UPS® VT 10-40 kVA 380/400/415 V with batteries Warning: After the UPS has been electrically wired, do not start it up. Start-up is commissioned to APCauthorized personnel only. Caution: All electrical power and power control wiring must be installed by a qualified electrician, and must comply with local and national regulations for maximum power rating. Note: Ensure that the unit is in its final location prior to installation. Note: Battery and utility/mains power must not be connected until all other wiring has been completed. 10-40 kVA 20-40 kVA without front panel 10-15 kVA without front panel Level the Enclosure 10-40 kVA from the rear 10-20 kVA Warning: The system must be installed on a level floor. The leveling feet will stabilize the enclosure, but will not account for a badly sloped floor. 10-20 kVA without front panel 10-20 kVA from the rear Use a 13/14 mm wrench to adjust the four leveling feet. Ensure that the system is level. Caution: Do not move the enclosure after the leveling feet have been lowered. 990-1986B-001 *990-1986B- 10/2008 Floor Anchoring (if applicable) Anchor the UPS enclosure to the floor Note: Floor-anchoring bolts are not provided with the UPS. Purchase the bolts locally (minimum size: M8). Follow the specifications given by the manufacturer of the floor anchoring system when bolting the UPS system to the floor. Reuse the two transport brackets (one on each side) that were used to secure the UPS to the pallet during transport. Drill two to six holes in the floor for each bracket. Attach with bolts. Prepare for Cables Connect the AC Input and AC Output Cables Bottom cable entry Dual mains Remove the three busbars A, Warning: Use compression type lugs ONLY. Do not loosen or add cables to any factory preinstalled cables on busbars. Use the front part of busbar for connection only. From the rear of the UPS, loosen the six M4 screws from the upper cover (the cable landing area) on the back and remove. B, and C by removing two M6 screws from each busbar. Connect the AC input cables and Single mains the neutral to the input cable landings. Connect the AC input cables and the neutral to the input cable landings. Connect the AC output cables and the neutral to the the neutral to the bypass cable landings. output cable landings. Route the cables from the slanted back plate, up through the punched bracket, and into the cable landing area. Connect the ground cables to the studs (earth symbol beneath) using a screw. Connect the output cables and Fasten the cables with cable ties Connect the bypass cables and the neutral to the output cable landings. Connect the ground cables to the studs (earth symbol beneath) using a screw. Note: A conduit box (part no. SUVTOPT001) is available as an option. 2 Connect the DC Battery Cables (if applicable) Connect battery cables BAT+, BAT÷, and N to the battery cable Connect the Communication Cables 1 EPO circuit 2 3 J106 and J108 pin connections 4 EPO is activated when an isolated SELV 24 VDC voltage is supplied on pin 1 with reference to pin 2. Connections: 3-5 and 4-6. 5 Note: The UPS must be connected to either a dry contact or a 24 VDC EPO (Emergency Power Off) switch. landings. 2: +24 V Normally Open J108 6 Note: The external EPO +24 VDC, 1500 mA circuit can be supplied through other vendors. J108 3: Dry Contacts Normally Closed 1 EPO is activated when a connection from pin 3 to pin 5 is opened. Connections: 4-6. 2 3 EPO circuit 4 5 6 Note: Always follow the pin connection procedures from the top and work down: J106 (8-1), J108 (1-6). 4: +24 V Normally Closed J108 Note: ONLY APC Smart-UPS VT XR Battery Enclosure (SUVTRBXRB6) must be connected to the UPS. EPO is activated when a SELV 24 VDC voltage is removed from pin 3 with reference to pin 4. 1 2 3 J108 pin connections: 1 2 3 4 5 6 Normally open EPO Normally open EPO return Normally closed EPO Normally closed EPO return +24 V SELV supply SELV ground J106 pin connections: 8 7 6 5 4 3 2 1 Ext. charging control return External control of charging Q3 active return Q3 active Battery measurement supply* Battery unit quantity* Max. battery temperature* Battery measurement return* * Should be used with APC XR Enclosures EPO wiring – pin connections J108. Connect the EPO cable, using one of the following four wiring configurations. 5 6 Pin connections J106 (UPS). Pins 1 to 4 are for battery measurement (only applicable to APC XR Battery Enclosures). J106 8 7 6 5 Charging control switch Q3 switch 4 4 3 3 2 2 1 1 J200 (XR Batteries) Pins 5 and 6 are for external maintenance bypass Q3 (auxiliary switch N/C type). When Q3 is closed, signals are fed back to the UPS controller. Pins 7 and 8 are for external charge control. When 7 and 8 are closed, the UPS charges batteries with a pre-defined percentage (0-2550-75-100%) of the maximum charging power. To be used in generator applications, or if special codes require control of charging. When Q3 is closed, signals are fed back to the UPS controller. Note: When connecting the Q3 auxiliary signal, use goldplated N/C auxiliary switch. 1: Dry Contracts Normally Open J108 1 2 3 4 5 6 EPO circuit 4 EPO circuit EPO is activated when pin 1 is connected to pins 3 and 5. Connections: 2-4-6, 3-5 and 1 => 3 Note: Reinstall the cable landing cover. Connect APC communication options Note: The cable routing of the power chute software and the temperature sensor is identical. Specifications Warning: The UPS must be supplied from a 380/220 V, 400/230 V or 415/240 V L1, L2, L3, N, PE, 50 Hz. Note: The temperature sensor is provided in a plastic bag attached to the front of the UPS behind the front panel. AC input Turn the screw below the user interface display to the 10 kVA UPS ratings 380 V 400 V 415 V right to the unlocked position. Lift the front panel to free the two tabs at the bottom of 40-70 40-70 40-70 Nominal input current (A)1 13.0 12.3 11.9 the enclosure. Max. input current (A)2 14.3 13.5 13.1 Input current limit (A)3 16.8 16.8 16.8 front and remove the cableinlet plate. Guide the cable through the side panel hole and run the cable upwards inside the panel. Pull the cable out of the side panel through the hole closest to the Network Management Card area. 380 V 400 V 415 V 380 V 400 V 415 V Input frequency (Hz) 40-70 40-70 40-70 40-70 40-70 40-70 Nominal input current (A)1 38.6 36.7 35.3 51.7 49.1 47.3 Max. input current (A)2 42.5 40.3 38.9 56.8 54.0 52.1 Input current limit (A)3 50.1 50.1 50.1 66.9 66.9 66.9 Input current based on rated load and batteries fully charged. Input current based on fully battery recharge, nominal voltage and rated load. 3 Current limitation through electronic current limiting is based on full battery recharge and -15% input voltage. 2 AC output Input current based on rated load and batteries fully charged. Input current based on fully battery recharge, nominal voltage and rated load. 3 Current limitation through electronic current limiting is based on full battery recharge and -15% input voltage. 2 15 kVA UPS ratings 10 kVA UPS ratings 380 V 400 V 415 V Nominal output current (A) 15.2 15 kVA 380 V 400 V 415 V UPS ratings Input frequency (Hz) 40-70 40-70 40-70 40-70 40-70 40-70 Nominal input current (A)1 19.4 18.5 17.8 26.0 24.7 23.8 Max. input current (A)2 21.4 20.3 19.6 28.6 27.2 26.2 Input current limit (A)3 25.2 25.2 25.2 33.8 33.8 33.8 1 14.4 13.9 20 kVA 380 V 400 V 415 V Input current based on rated load and batteries fully charged. Input current based on fully battery recharge, nominal voltage and rated load. 3 Current limitation through electronic current limiting is based on full battery recharge and -15% input voltage. 20 kVA 380 V 400 V 415 V Nominal output current (A) 22.8 21.7 20.9 380 V 400 V 415 V 30.4 30 kVA UPS ratings 28.9 27.8 40 kVA 380 V 400 V 415 V 380 V 400 V 415 V 2 Plug the cable into the probe socket / PowerChute inlet. UPS ratings 1 Network Management Guide the cable through card the hole in the bottom plate and up through the cableinlet. 40 kVA 1 Input frequency (Hz) Remove the two screws from the cable-inlet at the 30 kVA Reattach the cable-inlet plate (). 4 Nominal output current (A) 45.6 43.3 41.7 60.8 57.7 55.6 Battery input UPS ratings Recommended current protection 15 kVA 15 kVA 20 kVA 30 kVA ± 192 ± 192 ± 192 ± 192 ± 192 External battery fuse (A) 125 125 125 125 125 125 1.6-1.75 V/cell (automatic, depending on load) Bypass input 10 kVA UPS ratings Note: AC input/output over-current protection and AC input/output disconnect must be provided by the customer 40 kVA Nominal voltage (V) 380 V 400 V 415 V 50-60 50-60 50-60 Nominal input current (A)1 13.0 12.3 11.9 1 Input current based on rated load and batteries fully charged. 15 kVA UPS ratings Input frequency (Hz) 50-60 10 kVA 16 16 16 16 10 kVA 15 kVA 25 25 25 25 Mains input 2 kA – – – 16.4 A 20 kVA 35 35 35 35 Bypass input 1.7 kA 121.5 A – – 16.7 A Output 9 kA 121.5 A 22.8 A 19 A 16.7 A 30 kVA 50 50 50 50 Duration <10 ms 500 ms 10 s 10 min. ∞ 40 kVA 63 63 63 63 15 kVA Mains input 2.1 kA – – – 24.6 A Bypass input 1.8 kA 182 A – – 25.1 A Output 9 kA 182 A 34.2 A 25.4 A 25.1 A Duration <10 ms 500 ms 60 s 10 min. ∞ Mains input 2.5 kA – – – 32.5 A Bypass input 2.3 kA 244 A – – 33.4 A Output 9 kA 244 A 68.4 A 57 A 33.4 A Duration <10 ms 500 ms 60 s 10 min. ∞ Nominal input current (A)1 19.4 1 Mains input 2.5 kA – – – 32.5 A 50-60 50-60 18.5 17.8 26.0 24.7 23.8 Input current based on rated load and batteries fully charged. 30 kVA UPS ratings Nominal voltage (V) Nominal input current (A)1 38.6 1 40 kVA 380 V 400 V 415 V 50-60 2 Required upstream current protection, mains input: gL type fuse. Required upstream current protection, bypass input: gL type fuse. 20 kVA 380 V 400 V 415 V 50-60 380 V 400 V 415 V 50-60 50-60 50-60 50-60 50-60 36.7 35.3 51.7 49.1 47.3 Input current based on rated load and batteries fully charged. Continuously Q2 Note: The recommended cable sizes are based on an environment with an ambient temperature of 30°C. 50-60 125% overload normal/ battery operation Q3 Recommended cable sizes 50-60 150% overload normal/ battery operation Q52 20 kVA 380 V 400 V 415 V Internal fault1 800% overload bypass operation Q11 1 Input frequency (Hz) Minimum breaker settings Mains input [mm2] AC output [mm2] Battery input Bypass input [mm2] 70ºC [mm2] Wire 30 kVA 10 kVA 2.5 2.5 6 2.5 Bypass input 2.3 kA 244 A – – 33.4 A 15 kVA 6 6 10 6 Output 9 kA 244 A 68.4 A 57 A 33.4 A 20 kVA 10 10 16 10 Duration <10 ms 500 ms 60 s 10 min. ∞ 30 kVA 16 16 35 16 40 kVA Mains input 3 kA – – – 65.6 A 25 25 50 25 Bypass input 2.3 kA 487 A – – 66.9 A Output 14 kA 487 A 91.2 A 76 A 66.9 A Duration <10 ms 500 ms 60 s 10 min. ∞ Note: Use Molex lug type or equivalent, and crimp to manufacturer’s specifications. Warning: At 100% switch mode load, the neutral must be rated for 200% phase current. 5 40 kVA 1 For the output value, the short-circuit level is indicated. Recommended lug size and torque value Note: Power terminal lug diameter: 6 mm. Torque value: 7 Nm. Checklist Check that the power wiring is torqued to 7 Nm. Verify phase-rotation to the right (L1, L2, L3) and make sure a neutral connection is present. Leave a wiring diagram on site for service personnel. Re-install the cable landing cover. Re-mount the front panel If XR Battery Enclosures are installed, make sure that all DC breakers (if applicable) are in the OFF position and that both 125 A fuses are removed from the XR Battery Enclosures. For any optional equipment, refer to the product-specific manuals. Contact Information For local, country-specific centers: go to www.apc.com/support/ contact. Appendix Wiring diagrams Diagram with Maintenance Bypass Panel Diagram without Maintenance Bypass Panel 6
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project