SDM630 DC
Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems
USER MANUAL
2013 V1.1
Important Safety Information is contained in the Maintenance section. Familiarize yourself with this information before attempting installation or other procedures.
Symbols used in this document:
Risk of Danger: These instructions contain important safety information:
Read them before starting installation or servicing of the equipment
Caution: Risk of Electric Shock
1 Introduction
This document provides operating, maintenance and installation instructions . The unit measures and displays the characteristics of single phase two wires(1p2w) , three phase three wires(3p3w,) and three phase four wires(3p4w) supplies, including voltage, frequency, current, power ,active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh.
Maximum demand current can be measured over preset periods of up to 60 minutes. In order to measure energy,the unit requires voltage and current inputs in addition tot he supply required to power the product.
SDM630 DC supports max. 100A direct connection,saves the cost and avoid the trouble to connect external CTs,giving the unit a cost-effective and easy operation.Built-in interfaces provides pulse and Rs485 Modbus RTU outputs.Configuration is password protected.
1.1 Unit Characteristics
The Unit can measure and display:
Line voltage and THD% (total harmonic distortion) of all phases
Line Frequency
Currents, Current demands and current THD% of all phases
Power, maximum power demand and power factor
Active energy imported and exported
Reactive energy imported and exported
The unit has password-protected set-up screens for:
Changing password
Supply system selection 1p2w, 3p3w,3p4w
Demand Interval Time(DIT)
Reset for demand measurements
Pulse output duration
Two pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another display or a computer.
1.2 RS485 Serial – Modbus RTU
This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and controlling the Unit
Set-up screens are provided for setting up the RS485 port. Refers to section 4.8
1.3 Pulse output
This provides two pulse outputs that clock up measured active and reactive energy. The constant of SDM630 DC type for active energy is 1000imp/kWh. The pulse width for active energy can be set from the set-up menu.
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 1 -
2. Start-up Screens
The first screen lights up all display segments and can be used as a display check
The second screen indicates the firmware installed in the unit and its build number.
The interface performs a self-test and indicates the result if the test passes.
After a short delay, the screen will display active energy measurements.
3. Measurements
The buttons operate as follows:
Selects the Voltage and Current display screens
In Set-up Mode, this is the “Left” or “Back” button.
Select the Frequency and Power factor display screens
In Set-up Mode, this is the “Up” button
Select the Power display screens
In Set-up Mode, this is the “Down” button
Select the Energy display screens
In Set-up mode, this is the “Enter” or “Right” button
3.1 Voltage and Current
Each successive pressing of the button selects a new range:
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 2 -
Phase to neutral voltages
Current on each phase
Phase to neutral voltage THD%
Current THD% for each phase
3.2 Frequency and Power factor and Demand
Each successive pressing of the button selects a new range:
Frequency and Power Factor (total)
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 3 -
Power Factor of each phase
Maximum Power Demand
Maximum Current Demand
3.3 Power
Each successive pressing of the button select a new range:
Instantaneous Active Power in kW
Instantaneous Reactive Power in kVAr
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 4 -
Instantaneous Volt-amps in KVA
Total kW, kVArh, kVA
3.4 Energy Measurements
Each successive pressing of the button selects a new range:
Imported active energy in kWh
Exported active energy in kWh
Imported reactive energy in kVArh
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 5 -
Exported reactive energy in kVArh
Total active energy in kWh
Total reactive energy in kVAh
4. Set-up
To enter set-up mode, pressing the appears.
button for 3 seconds, until the password screen
Setting up is password-protected so you must enter the correct password (default ‘1000’) before processing. If an incorrect password is entered, the display will show: Err
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 6 -
To exit setting-up mode, press repeatedly until the measurement screen is restored.
4.1 Set-up Entry Methods
Some menu items, such as password,require a four-digit number entry while others, such as supply system, require selection from a number of menu options.
4.1.1 Menu Option Selection
① Use the and buttons to select the required item from the menu shown in section 4.1. selection does not roll over between bottom and top of list
②Press to confirm your selection
③If an item flashes, then it can be adjusted by the maybe a further layer.
and buttons. If not, there
④Having selected an option from the current layer, press
SET indicator will appear.
⑤Having completed a parameter setting, press to confirm your selection. The to return to a higher menu level. The SET indicator will be removed and you will be able to use the menu selection.
⑥ On completion of all set-up, press restored.
and buttons for further repeatedly until the measurement screen is
4.1.2 Number Entry Procedure
When setting up the unit , some screens require the entering of a number. In particular, on entry to the setting up section, a password must be entered. Digits are set individually, from left to right. The procedure is as follows:
①the current digit to be set flashes and is set using the
②Press been set.
and buttons to confirm each digit setting. The SET indicator appears after the last digit has
③After setting the last digit, press will be removed.
to exit the number setting routine. The SET indicator
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 7 -
4.2 Change password
1
2
3
4
Use the password option and to choose the change
Press the to enter the change password routine. The new password screen will appear with the first digit flashing
Use and to set the first digit and press digit will flash.
to confirm your selection. The next
Repeat the procedure for the remaining three digits
5 After setting the last digit, SET will show.
6
Press removed to exit the number setting routine and return to the Set-up menu. SET will be
4.3 DIT Demand Integration Time
This sets the period in minutes over which the current and power readings are integrated for
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 8 -
maximum demand measurement. The options are: off, 5, 10,15 30,60 minutes
1
From the set-up menu, use and buttons to select the DIT option. The screen will show the currently selected integration time.
2
Press to enter the selection routine. The current time interval will flash
3
Use required.
and buttons to select the time
4
Press to confirm the selection. SET indicator will appear.
5
Press to exit the DIT selection routine and return to the menu.
4.4 Supply System
Use this section to set the type of power supply being monitored.
1
From the Set-up menu, use and buttons to select the System option. The screen will show the currently selected power supply .
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 9 -
2
Press to enter the selection routine. The current selection will flash
3
Use and buttons to select the required system option: 1P2(W),3P3(W) ,3P4(W)
4
Press to confirm the selection. SET indicator will appear.
5
Press to exit the system selection routine and return to the menu. SET will disappear and you will be returned to the main Set-up Menu
4.5 Pulse output
This option allows you to configure the pulse output. The output can be set to provide a pulse for a defined amount of energy active or reactive.
Use this section to set up the relay pulse output—Units: kWh , kVArh
1
From the Set-up menu, use and buttons to select the Pulse output option.
2
Press to enter the selection routine. The unit symbol will flash.
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 10 -
3
Use kVArh.
and buttons to choose kWh or
4
On Completion of the entry procedure, press to return to the main set up menu.
to confirm the setting and press
4.5.1 Pulse rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
0.01kWh/0.1kWh/1kWh/10kWh/100kWh.
1
(It shows 1 impulse = 10kWh/kVArh)
From the Set-up menu, use buttons to select the Pulse Rate option.
and
2
Press to enter the selection routine. The current setting will flash.
0.01/0.1/1/10/100kWh/kVarh per pulse
3
Use and procedure, press set up menu.
buttons to choose pulse rate.On Completion of the entry to confirm the setting and press to return to the main
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 11 -
4.5.2 Pulse Duration
The energy monitored can be active or reactive and the pulse width can be selected as 200, 100 or 60ms.
1
(It shows pulse width of 200ms)
From the Set-up menu, use and buttons to select the Pulse width option.
2
Press to enter the selection routine. The current setting will flash.
3
Use and procedure, press set up menu.
buttons to choose pulse width.On Completion of the entry to confirm the setting and press to return to the main
4.6 Communication
There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus
RTU, parameters are selected from Front panel.
4.6.1 RS485 Address
(The range is from 0 to 247)
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 12 -
4.6.2 Baud Rate
1
From the Set-up menu, use buttons to select the Baud Rate option.
and
2
Press to enter the selection routine. The current setting will flash.
3
Use and buttons to choose Baud rate 2.4k. 4.8k, 9.6k, 19.2k, 38.4k
4
On Completion of the entry procedure, press to confirm the setting and press
4.6.3 Parity
1 to return to the main set up menu.
From the Set-up menu, use buttons to select the Parity option.
and
2
Press to enter the selection routine. The current setting will flash.
3
Use and
(EVEN / ODD / NONE) buttons to choose Parity
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 13 -
4
On Completion of the entry procedure, press to confirm the setting and press to return to the main set up menu.
4.6.4 Stop bits
1
From the Set-up menu, use buttons to select the Stop Bit option.
and
2
Press to enter the selection routine. The current setting will flash.
3
Use
(2 or 1) and buttons to choose Stop Bit
4
On completion of the entry procedure, press to confirm the setting and press to return to the main set up menu.
4.7 CLR
The meter provides a function to reset the maximum demand value of current and power.
1
From the Set-up menu, use buttons to select the reset option.
and
2
Press will flash.
to enter the selection routine. The dIt
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 14 -
3
Press to confirm the setting and press to return to the main set up menu.
5 Specifications
5.1 Measured Parameters
The unit can monitor and display the following parameters of a single phase two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) supply.
5.1.1 Voltage and Current
Phase to neutral voltages 100 to 289V a.c. (not for 3p3w supplies)
Voltages between phases 173 to 500V a.c. (3p supplies only)
Percentage total voltage harmonic distortion (THD%) for each phase to N ( not for 3p3w supplies)
Percentage voltage THD% between phases (three phase supplies only)
Current THD% for each phase
5.1.2 Power factor and Frequency and Max. Demand
Frequency in Hz
Instantaneous power:
Power 0 to 3600 MW
Reactive Power 0 to 3600 MVAr
Volt-amps 0 to 3600 MVA
Maximum demanded power since last Demand reset Power factor
Maximum neutral demand current, since the last Demand reset (for three phase supplies only)
5.1.3 Energy Measurements
Imported active energy 0 to 9999999.9 kWh
Exported active energy 0 to 9999999.9 kWh
Imported reactive energy 0 to 9999999.9 kVArh
Exported reactive energy 0 to 9999999.9 kVArh
Total active energy
Total reactive energy
0 to 9999999.9 kWh
0 to 9999999.9 kVArh
5.2 Measured Inputs
Voltage inputs through 4-way fixed connector with 2.5mm² stranded wire capacity. single phase two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) unbalanced. Line frequency measured from L1 voltage or L3 voltage.
Three current inputs (six physical terminals) with 2.5mm² stranded wire capacity for connection of external CTs. Nominal rated input current 5A or 1A a.c. Rms.
5.3 Accuracy
Voltage
Current
0·5% of range maximum
0·5% of nominal
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 15 -
Frequency
Power factor
Active power (W)
Reactive power (VAr)
Apparent power (VA)
Active energy (Wh)
Reactive energy (VARh)
Total harmonic distortion
Temperature co-efficient
Response time to step input
0·2% of mid-frequency
1% of unity (0.01)
±1% of range maximum
±2% of range maximum
±1% of range maximum
Class 1 IEC 62053-21
±2% of range maximum
1% up to 31st harmonic
Voltage and current = 0.013%/°C typical
Active energy = 0·018%/°C, typical
1s, typical, to >99% of final reading, at 50 Hz.
5.4 Interfaces for External Monitoring
Three interfaces are provided:
an RS-485 communication channel that can be programmed for Modbus RTU protocol
an relay output indicating real-time measured energy.(configurable)
An pulse output 1000Imp/kWh
The Modbus configuration (Baud rate etc.) and the pulse relay output assignments (kW/kVArh, import/export etc.) are configured through the Set-up screens.
5.4.1 Pulse Relay Output
The pulse relay output can be set to generate pulses to represent kWh or kVArh.
Rate can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
Pulse width 200/100/60 ms.
Relay Rating 240V ac 50mA
5.4.2 RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be configured from the
Set-up menu:
Baud rate 2400, 4800, ,9600, ,19200, 38400
Parity none/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 1 to 247
Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be configured from the set-up menu.
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 16 -
5.5 Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is verified under nominal value (within the specified tolerance) of these conditions.
Ambient temperature 23°C ±1°C
Input waveform 50 or 60Hz ±2%
Input waveform
Auxiliary supply voltage
Sinusoidal (distortion factor < 0·005)
Nominal ±1%
Auxiliary supply frequency
Auxiliary supply waveform (if AC)
Magnetic field of external origin
Nominal ±1%
Sinusoidal (distortion factor < 0·05)
Terrestrial flux
5.6 Environment
Operating temperature
Storage temperature
Relative humidity
Altitude
Warm up time
-25°C to +55°C*
-40°C to +70°C*
0 to 90%, non-condensing
Up to 2000m
1 minute
Vibration
Shock
10Hz to 50Hz, IEC 60068-2-6, 2g
30g in 3 planes
*Maximum operating and storage temperatures are in the context of typical daily and seasonal variation.
5.7 Mechanics
DIN rail dimensions
Mounting
Sealing
Material
6 Dimensions
72 x 94.5 mm (WxH) per DIN 43880 ( SDM630CT)
76 x 100 mm (WxH) per DIN 43880 ( SDM630DC)
DIN rail (DIN 43880)
IP20 (minimum)
Self-extinguishing UL 94 V-0
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 17 -
7.
Installation
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com
Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001.
- 18 -