0.1to 0.4 5 0.1to 0.4 MPa Pressure Switch/Reed Switch Type

Pressure Switch/Reed Switch Type
Series IS10
ZSE30
ISE30
16% lighter 11% smaller
Weight: 62 g Overall height: 52 mm
∗Previous type 58.5 mm
Compared with IS1000
(Made by SMC)

100 V AC/DC specifications
52 mm

Compared with IS1000
(Made by SMC)
Set pressure range
to
MPa
 Service life:
million cycles
0.1 0.4
5
ZSP
ISA2
23
PSE
mm
Lubricator
0.7 MPa
0.1 to 0.4 MPa
Option: 0.1 to 0.6 MPa
Ambient and fluid temperature
Reed switch
1.0 MPa
Set pressure range
–5 to 60°C (No freezing)
Contacts
1a
Symbol
±0.05 MPa or less
Error of scale
Hysteresis
Fixed 0.08 MPa or less
Grommet, Lead wire length: 0.5 m
Option: 3 m, 5 m
Enclosure
Equivalent to IP40
Port size
1/8
Weight
62 g
0.2
0.1
50 mA
01
q
40 mA
20 mA
0.3
0.4
How to Order
IS10
AC 2 VA, DC 2 W
24 V or less
48 V
100 V
0.2
Set pressure scale (MPa)
q
Thread type
w
Seal
w
Description
Nil
R
NPT
N
Nil
S
+
a
q
e
e
Symbol
+
Semi-standard
Voltage AC/DC
0.3
0
0.1
Switch Characteristics
Max. operating current and range
OFF pressure
0.4
±0.05 MPa or less
Repeatability
Max. contact capacity
ON pressure
0.5
Air/Inert gas
Max. operating pressure
Wiring specifications
Up to 100 V AC/DC
IS10-01
ZSM1
Set Pressure Range
Electrical Circuit
Proof pressure
IS
ISG
Specifications
Fluid
Regulator
Air filter
Pressure switch
with piping adapter
Model
ZSE
ISE
PS
15 m
m
Pressure switch
with spacer
Can be connected ISE70
to Modular type
ZSE80
ISE80
F.R.L. units.
Pressure switch
Operating pressure (MPa)

ZSE40
ISE40
ZSE10
ISE10
Hysteresis
∗Previous type 74 g
RoHS
None
With seal
Set pressure
Nil
0.1 to 0.4 MPa
range
6 Note1) 0.1 to 0.6 MPa
+
b
Lead wire
length
Nil
L
Z
+
c
0.5 m
3m
5m
Semi-standard: Select one
option each in a through c.
Place them in alphanumerical
order.
Example) IS10-N01-6PZ
Note 1) Set pressure range of
6P(L, Z) is 0.2 to 0.6
MPa (30 to 90 psi).
Note 2) This product is for overseas use only according
to the new Measurement Law. (The SI unit
type is provided for use
in Japan.)
Scale plate
MPa
Nil
pressure unit P Note2) Both MPa and psi
917
Series IS10
(13)
(23)
(5000)
(3000)
(500)
Dimensions/Construction
t
r
y
e
Component Parts
u
i
w
52
44
o
No.
0.1
0.3
0.2
0.4
MPa
!0
!1
!2
q
1/8
23
Wiring
Mounting
Warning
Warning
1. Connect load before connecting with power
source.
The switch will break instantly if no load is
connected.
2. Make the wiring length as short as possible. When the load which is operated by
the pressure switch is an inductive load,
or the lead wire is 5 m or longer, use the
contact protection box shown in the table
below.
Otherwise, damage to the switch can result.
Part no.
CD-P11
CD-P12
Voltage
15
Lead wire length
100 VAC Switch side: 0.5 m
24 VDC Load side: 0.5 m
• Internal circuit of contact protection box
1. When handling the product, hold the body and do
not apply tensile stress to the power supply cable.
Otherwise, damage may occur to the product.
2. Avoid repeatedly bending or stretching the lead wire.
Wiring which applies repeated bending and tensile
stress to the lead wire can break the circuit. If the
lead wire is damaged, causing operation failure,
replace the product with a new one.
3. Do not drop or bump the product when
handling the product.
4. Apply a wrench to the bottom of the product when screwing.
Turning it by applying a wrench on the top of the
main body may cause damage to the product.
Recommended tightening torque: 7 to 9 N·m
CD-P11
Brown
Blue
Choke coil
Brown (+)
Zener diode Load side
Blue
Blue (–)
• How to connect contact protection box
Connect the lead wires from the body and
the contact protective box side indicated
“SWITCH.” Make the lead wire as short as
possible, within 1 m.
3. Dimensions of lead wire
Enclosure: ø 3.4
Insulator: ø 1.1
Conductor: ø 0.64
For details, refer to the operation manual.
918
Material
Body
2
Switch assembly
3
Shield plate
Steel sheet
4
Cover
Steel sheet
5
Adjusting screw
Brass
6
Hexagon nut
Brass
7
Indicator
8
Spring
ZDC
—
PBT
Stainless steel
9
Magnet
—
10
Piston
POM
11
Seal piston
NBR
12
Scale plate
PC
Pressure Source
Warning
1. Operating fluids are either air or inert gas
exclusively.
Never use other fluids. Never use in an environment where flammable fluid or gas is
used. Since this is not an explosion-proof
construction, it may lead to an explosive
disaster.
2. Not applicable to corrosive gas and liquid.
Otherwise, damage to the body or liquid
leakage can result.
3. Avoid use in vacuum applications.
Switch may be imploded.
4. This product (Series IS10) uses a reed
switch. If the chattering of the output signal is a problem, choose a solid state
type pressure switch or adjust by PLC.
Pressure Setting
Brown ( )
Choke coil
Load side
Surge
absorber
Blue ( )
CD-P12
Brown
Description
1
Warning
5. Mounting direction is available in either
horizontal or perpendicular.
Operating Environment
Warning
1. Avoid using a switch in a magnetic environment.
It may cause a malfunction.
2. Do not use in such an environment, where water
or oil is splashed.
Since it is the open type construction, if
water or oil make an ingress into the internal
parts, the electric circuit will be corroded and
may result in a malfunction or damage.
3. Avoid vibration.
Vibration may cause a malfunction or may
cause setting to be incorrect.
1. Set within the display pressure range of
the scale plate.
Caution
1. The pressure can be adjusted by rotating the
adjustment screw. The red indicator goes up
and down according to the adjustment.
Rotate the screw clockwise for high pressure.
2. Use a screwdriver of a size suitable for
the groove of the adjustment screw.
3. Scale of switching set display is the set
value at the pressure drop.
4. The ON signal is output through the pressure set
on the scale plate, to which the hysteresis is
added for detecting the ON-pressure signal.
5. The pressure displayed on the scale plate
is a guideline only.
Measure the accurate pressure with the pressure gauge.
Pressure Switch
Reed Switch Type
Series IS10
Pressure Switch for Connecting to Modular/F.R.L. Units
Pressure Switch with Spacer
23
Symbol
ZSE30
ISE30
(5000)
(3000)
(500)
(23)
(13)
15
IS10M 30
ZSE40
ISE40
Pressure switch
Semi-standard: Select one option each in a through c.
Place them in alphanumerical order.
Example) IS10M-6LP
ZSE10
ISE10
0.1
0.3
0.2
0.4
ISE70
C
MPa
ZSE80
ISE80
B
Symbol Description
Body size
20 30 40 50 60
Semi-standard
a
ZSE
ISE
Set pressure
Nil 0.1 to 0.4 MPa
range
6 Note 1) 0.1 to 0.6 MPa
+
b
Lead wire
length
Nil
L
Z
Lubricator
0.5 m
3m
5m
A
D
Air filter
Regulator
PS
+
MPa
Nil
Scale plate
pressure unit P Note 2) Both MPa and psi
Note 1) Set pressure range of 6P(L, Z) is 0.2 to 0.6 MPa (30 to 90 psi).
Note 2) This product is for overseas use only according to the new
Measurement Law. (The SI unit type is provided for use in Japan.)
A
B
C
D
Applicable model
IS10M-20
11
74
64
28 AC20
IS10M-30
13
85
71
30 AC25, AC30
IS10M-40
15
93
75
36 AC40
IS10M-50
17
97
77
44 AC40-06
IS10M-60
22
91
67
53 AC50, AC55, AC60
Note) Prepare a spacer separately for modular connection.
Model
c
(23)
Semi-standard: Select one option each in a through d.
Place them in alphanumerical order.
Example) IS10E-30N03-6PRZ
Pressure switch with piping adapter
0.1
0.3
0.2
0.4
C
MPa
Body size
20
Nil
Thread type
N
F
30
40
Port size
1/8
1/4
3/8
1/2
3/4
+
a
Set pressure
Nil 0.1 to 0.4 MPa
range
6 Note 1) 0.1 to 0.6 MPa
Semi-standard
+
b
Lead wire
length
Nil
L
Z
0.5 m
3m
5m
+
c
Scale plate
MPa
Nil
pressure unit P Note 2) Both MPa and psi
+
Mounting
Nil
Right
position
R
Left
Note 1) Set pressure range of 6P(L, R, Z) is 0.2 to 0.6 MPa (30 to 90 psi).
Note 2) For thread type: NPT only.
This product is for overseas use only according to the new
Measurement Law. (The SI unit type is provided for use in Japan.)
d
Left
Right
Rc
NPT
G
+
01
02
03
04
06
B
Symbol Description
PSE
IS
ZSM1
Symbol
(5000)
(3000)
(500)
23
(13)
E
03
ISA2
ISG
Pressure Switch with Piping Adapter
IS10E 30
ZSP
A
D
Port size
Filter regulator
Applicable model
Port size
A
B
C
D
E
IS10E-2001
1/8
AC20
IS10E-2002
1/4
30
66
55
28
16 AR20, AW20
AWM20, AWD20
IS10E-2003
3/8
IS10E-3002
1/4
AC25, AC30
IS10E-3003
3/8
32
73
59
30
13 AR25, AR30, AW30
AWM30, AWD30
IS10E-3004
1/2
IS10E-4002
1/4
Note 2)
AC40
IS10E-4003
3/8
32
79
61
37
13 AR40, AW40
IS10E-4004
1/2
AWM40, AWD40
IS10E-4006
3/4
Note 1)  in the model numbers indicates a thread type. No indication is necessary for Rc;
however, indicate N for NPT, and F for G.
Note 2) Cannot be mounted to the AC40-06 and AW40-06.
Note 3) Prepare a spacer separately for modular connection.
∗ The pressure switch can be mounted on the AC40-06 and above and the AW40-06 by screwing the IS10-01
into the piping adapter E500-06-X051 or E600-06-X501 to E600-10-X501 (Rc1/8 threaded on top surface).
Products with a premounted switch are available as a special order. Please contact SMC beforehand.
Model Note 1)
For details, refer to “Modular/F.R.L. Units, Series AC” in Best Pneumatics No.5.
919
Open as PDF