1-3 kVA UPS
INSTALLATION AND USER MANUAL
Green Point T
KEEP FOR FUTURE REFERENCE
for the entire life of the appliance
All rights reserved.
The information in this document is subject to change without notice.
Publish statement
Thank you for purchasing this series UPS.
This series UPS is an intelligent, single phase in single phase out, high frequency online
UPS designed by our R&D team who is with years of designing experiences on UPS.
With excellent electrical performance, perfect intelligent monitoring and network functions,
smart appearance, complying with EMC and safety standards, The UPS meets the
world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 1 of 22 + FR
Table of Contents
1.
2.
3.
Important Safety Warning ..................................................................................................................... 3
1-1
Transportation ............................................................................................................................. 3
1-2
Preparation ................................................................................................................................... 3
1-3
Installation .................................................................................................................................... 3
1-4
Operation ...................................................................................................................................... 4
1-5
Maintenance, service and faults ............................................................................................. 4
1-6
Symbols used in this guide ..................................................................................................... 5
Installationand setup .............................................................................................................................. 5
2-1
Unpack checking ........................................................................................................................ 5
2-2
Real panel view ........................................................................................................................... 5
2-3
LCD control panel....................................................................................................................... 7
2-4
Setup the UPS ............................................................................................................................. 8
Operations ................................................................................................................................................. 9
3-1
Button operation ......................................................................................................................... 9
3-2
LCD display ................................................................................................................................ 10
3-3
UPS setting................................................................................................................................. 13
3-4
Operating Mode Description.................................................................................................. 15
3-5
Operational Status and Mode(s) ........................................................................................... 16
3-6
Alarm or Fault reference code .............................................................................................. 16
4.
Troubleshooting..................................................................................................................................... 17
5.
Storage and Maintenance.................................................................................................................... 18
6.
Specification ........................................................................................................................................... 19
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 2 of 22 + FR
1. Important Safety Warning
Important safety instructions – Save these instructions
Please comply with all warnings and operating instructions in this manual strictly. Save
this manual properly and read carefully the following instructions before installing the unit.
Do not operate this unit before reading through all safety information and operating
instructions carefully
There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety instructions and
relative laws, otherwise it will result in personnel injury or equipment damage. Safety
instructions in this manual act as a supplementary for the local safety instructions. Our
company will not assume the liability that caused by disobeyingsafety instructions.
1-1 Transportation
l Please transport the UPS system only in the original package to protect against
shock and impact.
1-2 Preparation
l Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please
allow at least two hours for the UPS system to acclimate the environment.
l Do not install the UPS system near water or in moist environments.
l Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
l Do not block ventilation holes in the UPS housing.
1-3 Installation
l Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
l Place cables in such a way that no one can step on or trip over them.
l Do not connect domestic appliances such as hair dryers to UPS output sockets.
l The UPS can be operated by any individuals with no previous experience.
l Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
l Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
l Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
l When installing the equipment, it should ensure that the sum of the leakage current of
the UPS and the connected devices does not exceed 3.5mA.
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 3 of 22 + FR
1-4 Operation
l Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
l The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is
not connected to the building wiring outlet.
l In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
l Prevent no fluids or other foreign objects from inside of the UPS system.
1-5 Maintenance, service and faults
l The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
l Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the
battery and electrically live and dangerous.
l Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals
of high capability capacitor such as BUS-capacitors.
l Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
l Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, please verify that no voltage is present!
l Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary
when working with batteries:
᧩remove wristwatches, rings and other metal objects
᧩use only tools with insulated grips and handles.
l When changing batteries, install the same number and same type of batteries.
l Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
l Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic.
l Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
l Do not dismantle the UPS system.
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 4 of 22 + FR
1-6 Symbols used in this guide
WARNING!
Riskofelectricshock
CAUTION!
Readthisinformationtoavoidequipmentdamage
2. Installationand setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. Please keep the original package in a safe place for future use.
2-1 Unpack checking
l Don’t lean the UPS when moving it out from the packaging
l Check the appearance to see if the UPS is damaged or not during the transportation,
do not switch on the UPS if any damage found. Please contact the dealer right away.
l Check the accessories according to the packing list and contact the dealer in case of
missing parts.
2-2 Real panel view
1KVA(S):
1KVA(H):
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 5 of 22 + FR
2KVA(S):
2KVA(H)/3KVA(H)
3KVA(S):
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 6 of 22 + FR
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
AC input
Network /Fax/Modem Surge Protection(option)
Input circuit breaker
EPO(option)
USB communication port(option)
RS-232 communication port
SNMP intelligent slot (option)
Output receptacles
Battery Terminal
Output Terminal
2-3 LCD control panel
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 7 of 22 + FR
LCD control panel introduction
᧤1᧥LED᧤from top to bottom: “alarm”, “bypass”, “battery”, “inverter”᧥ ᧤2᧥LCD display᧤3᧥
Selectbutton:enter to next item᧤4᧥Off button ᧤5᧥On button
2-4 Setup the UPS
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension
cords.
l For 200/208/220/230/240VAC models: The power cord is supplied in the UPS
package.
Step 2: UPS output connection
l For socket-type outputs, simply connect devices to the outlets.
l For terminal-type input or outputs, please follow below steps for the wiring
configuration:
a) Remove the small cover of the terminal block
b) Suggest
using
AWG14
or
(200/208/220/230/240VAC models).
2.1mm2
power
cords
for
3KVA
c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 3 Communication connection
Communication port:
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 8 of 22 + FR
The UPS is equipped with intelligent slot perfect for either SNMP or Relay card. When
installing either SNMP or Relay card in the UPS, it will provide advanced
communication and monitoring options.
NOTE: USB port and RS-232 port can’t work at the same time.
Step 4: Turn on the UPS
Press the ON button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not
expect full battery run capability during this initial charge period.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully
configure UPS shutdown. You may insert provided CD into CD-ROM to install the
monitoring software.
Step 6: External battery connection
If your UPS is not including batteries. Please connect external batteries as below
chart.
3. Operations
3-1 Button operation
Button
Ø
Ø
ON Button
Ø
IV390E Rev. 00
Date of issue: 2015-10-29
Function
Turn on the UPS: Press and hold ON button for at least 2
seconds to turn on the UPS.
Down key: Press this button to display next selection in
UPS setting mode.
Exit setting mode:Press this button to confirm seletion
and exit setting mode when LCD display the last selection
in UPS setting mode.
Installation and user manual
Pag. 9 of 22 + FR
Ø
Ø
OFF Button
Ø
Ø
Ø
Select/Mute
Button
Ø
OFF + Select
Button
Ø
Turn off the UPS: Press and hold this button at least 2
seconds to turn off the UPS in battery mode. UPS will be
in standby mode under power normal or transfer to
Bypass mode if the Bypass enable setting by pressing this
button.
Switch to bypass mode: When the main power is
normal, press and hold this button for 2 seconds. Then
UPS will enter to bypass mode. This action will be
ineffective when the input voltage is out of acceptable
range.
Up key: Press this button to display previous selection in
UPS setting mode.
Switch LCD message: Press this button to change the
LCD message for input voltage, input frequency, battery
voltage, output voltage and output frequency etc.
Mute the alarm: When the UPS is on battery mode, press
and hold this button for at least 2 seconds to disable or
enable the alarm system. But it’s not applied to the
situations when warnings or errors occur.
Switch to UPS self-test mode: Press and hold this
button for 2 seconds to enter UPS self-testing while in AC
mode.
Setting mode: Press and hold this button for 5 seconds to
enter UPS setting mode.
3-2 LCD display
There are 8 interfaces available in the LCD display
Item
01
Interface Description
Input voltage
IV390E Rev. 00
Date of issue: 2015-10-29
Content Displayed
Installation and user manual
Pag. 10 of 22 + FR
02
Battery voltage
03
Output voltage
04
Load
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 11 of 22 + FR
05
Temperature
(Heatsink Temperature &
Environment Temperature)
Note᧶1KVA(S) only has
Heatsink Tem perature.
06
Firmware Version & UPS
model.
07
CODE
(Operational status and
mode)
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 12 of 22 + FR
08
Alarm Code(Warming
Message)
All alarm codes are
present when abnormal
behavior(s) occur(s)
09
The charging status can
also be shown on the
screen as below while
the charger is on.
3-3 UPS setting
The setting fuction is controled by 3 buttons (Enter/SelectP,Off/up ▲, On/down▼): Enter
P+Off/up ▲---goes into the setting page,Enter P--- value adjustment; Off ▲ & On ▼---for choosing
different pages.
After the UPS turn ON, press buttons P& ▲ for 5seconds and then goes into the setting interface
page.
Note: Figure at left corner is the page number of the setting pages.
Item
IV390E Rev. 00
Date of issue: 2015-10-29
Settings
Content Displayed
Installation and user manual
Pag. 13 of 22 + FR
01
Mode setting
Press select button P to change the
setting (ECO or NOR).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼ button to select the
next setting.
02
Output voltage setting
Press select button P to change the
setting
(100,110,115,120,127
or
200,208᧨220, 230, 240).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼ button to select the
next setting.
03
Frequency setting
Press select button P to change the
setting (50 or 60Hz).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼ button to select the
next setting.
04
Battery capacity setting
Press select button P to change the
setting (Battery capacity range is
1-200Ah).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼ button to select the
next setting.
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 14 of 22 + FR
05
Bypass voltage upper limit
setting
Press select button P to change the
setting(The bypass voltage upper limit
range is 230-264Vac ).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼ button to select the
next setting.
06
Bypass
setting
voltage
lower
limit
Press select button P to change the
setting(The bypass voltage lower limit
range is 170-220Vac).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼ button to select the
next setting.
07
Mute setting
Press select buttonP
thesetting(ON or OFF).
to
change
Press UP button ▲ to select the
previous setting.
Press DOWN ▼ button to save and
exit the setup.
3-4 Operating Mode Description
Operating mode
Online mode
ECO mode
Description
When the input voltage is
within acceptable range,
UPS will provide pure and
stable AC power to output.
The UPS will also charge
the battery at online mode.
Energy saving mode:
Display
Inverter led light
Bypass led light
When the input voltage is
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 15 of 22 + FR
within voltage regulation
range, UPS will bypass
voltage to output for
energy saving.
When the input voltage is
beyond the acceptable
range or power failure and
alarm is sounding every 4
second, UPS will backup
power from battery.
UPS is powered off and no
output supply power, but
still can charge batteries.
Battery mode
Standby mode
Bypass mode
Battery led light
All LEDs turn off
Bypass led light
When input voltage is
within acceptable range
but UPS is overload, UPS
will enter bypass mode or
bypass mode can be set
by front panel. Alarm is
sounding every 10 second.
3-5 Operational Status and Mode(s)
item
Content Displayed
1
2
3
4
5
6
7
8
9
10
11
12
Initialized
Standby Mode
No Output
Bypass Mode
Utility Mode
Battery Mode
Battery Self-diagnostics
Inverter is starting up
ECO Mode
EPO Mode
Maintenance Bypass Mode
Fault Mode
3-6 Alarm or Fault reference code
Event log
UPS Alarm Warning
1
Rectifier Fault
2
Inverter fault(Including
bridge is shorted)
9
Fan fault
IV390E Rev. 00
Date of issue: 2015-10-29
Buzzer
Inverter
LED
Beep continuously
Fault LED lit
Beep continuously
Fault LED lit
Beep continuously
Fault LED lit
Installation and user manual
Pag. 16 of 22 + FR
13
Battery Charger fault
Beep continuously
Fault LED lit
15
DC Bus over voltage
Beep continuously
Fault LED lit
16
DC Bus below voltage
Beep continuously
Fault LED lit
17
DC bus unbalance
Beep continuously
Fault LED lit
18
Soft start failed
Beep continuously
Fault LED lit
19
Over Temperature
Twice per second
Fault LED lit
26
Battery over voltage
Once per second
Fault LED blinking
29
Output Short-circuit
Once per second
Fault LED blinking
30
Input current limit
Once per second
Fault LED blinking
31
Bypass over current
Once per second
BPS LED blinking
32
Overload
Once per second
INV or
blinking
33
No battery
Once per second
Battery LED blinking
34
Battery under voltage
Once per second
Battery LED blinking
35
Battery low pre-warning
Once per second
Battery LED blinking
36
Over load time out
Once per 2 seconds
Fault LED blinking
37
DC component over limit.
Once per 2 seconds
INV LED blinking
39
Mains volt. Abnormal
40
Mains freq. abnormal
41
Bypass Not Available
BPS LED blinking
42
Bypass unable to trace
BPS LED blinking
43
Inverter on invalid
44
Once per 2 seconds
Once per 2 seconds
BPS
LED
Battery LED lit
Battery LED lit
Not at Inverter side
4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table
below.
Symptom
Possible cause
No indication and alarm even The AC input power is not
though the mains is normal.
connected well.
IV390E Rev. 00
Date of issue: 2015-10-29
Remedy
Check if input power cord
firmly connected to the
mains.
Installation and user manual
Pag. 17 of 22 + FR
The AC input is connected to
the UPS output.
Alarm code is shown as“33” and The external or internal
battery is incorrectly
battery led blinking.
connected.
Plug AC input power cord to
AC input correctly.
Check if all batteries are
connected well.
Alarm code is shown as “26”
and battery led blinking.
Battery voltage is too high or
the charger is fault.
Contact your dealer.
Alarm code is shown as “34”
and battery led blinking
Battery voltage is too low or
the charger is fault.
Contact your dealer.
Alarm code is shown as “32”
and INV or BYPASS led
blinking.
UPS is overload
Remove excess loads from
UPS output.
Alarm code is shown as “29”
and FAULT led light.
The UPS shut down
automatically because short
circuit occurs on the UPS
output.
Check output wiring and if
connected devices are in
short circuit status.
Alarm code is shown as “9” and
FAULT led light.
Fan fault.
Contact your dealer.
Alarm code is shown as “01,02,
15,16,17,18”
A UPS internal fault has
occurred.
Contact your dealer.
Battery backup time is
shorter than nominal value
Batteries are not fully
charged
Batteries defect
Charge the batteries for at
least 5 hours and then check
capacity. If the problem still
persists, consult your dealer.
Contact your dealer to
replace the battery.
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at
25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case,
please contact your dealer.
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 18 of 22 + FR
Be sure to deliver the spent battery to a recycling facility or ship it
to your dealer in the replacement battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
-25°C - 40°C
40°C - 45°C
Recharge Frequency
Every 3 months
Every 2 months
Charging Duration
1-2 hours
1-2 hours
6. Specification
MODEL
1KVA(S)
PHASE
Capacity (VA/Watts)
INPUT
Nominal voltage
1000VA / 900W
Low
line
come
back
High
line
transf
er
High
line
come
back
Operating frequency
range
Power factor
Bypass voltage range
2KVA(S)
2KVA(H)2KVA(H)
B
Single phase with ground
2000VA / 1800W
3KVA(S)
3KVA(H)B
3KVA(H)
3000VA / 2700W
100/110/115/120/127VAC or 200/208/220/230/240VAC
85 or 160Vac±5% @100%-80% load;
75 or 140Vac±5% @80%-70% load;
65 or 120Vac±5% @70%-60% load;
55 or 110Vac±5% @60%-0% load;
(Ambient Temp. <35Ԩ)
95 or 175Vac±5% @100%-80% load;
85 or 155Vac±5% @80%-70% load;
75 or 135Vac±5% @70%-60% load;
65 or 125Vac±5% @60%-0% load;
(Ambient Temp. <35Ԩ)
Low
line
transf
er
Operating
voltage range
1KVA(H)1KVA(H)
B
145 or 300Vac ±5%
140 or 290Vac ±5%
40-70Hz
0.990 @100% load(Nominal Input Voltage)
Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in LCD from 230Vac to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
115-132: setting the high voltage point in LCD from 115Vac to 132Vac(Default: 132Vac)
Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in LCD from 170Vac to 220Vac. (Default: 170Vac)
For 100/110/115/120/127 VAC models:
95-110: setting the high voltage point in LCD from 95Vac to 110Vac. (Default: 95Vac)
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 19 of 22 + FR
ECO range
Generator input
OUTPUT
Output voltage
Power factor
Voltage regulation
Line
Mode
(synchro
Frequency
nized
range)
Bat. Mode
Crest factor
Harmonic distortion
(THDv)
Waveform
AC
mode
<->Batt.
Transfer
mode
time
Inverter
<->
bypass
Same as bypass
Support
100/110/115/120/127VAC or 200/208/220/230/240Vac
0.9
±1%(Batt. Mode)
47-53Hz or 57-63Hz
(50/60±0.1)Hz
3:1
≤3% THDwith linear load
≤6% THD with non linear load
Pure Sinewave
Zero
4ms(Typical)
>88%(AC mode)
>83%(DC mode)
Efficiency
>89%(AC mode)
>87%(DC mode)
>90%(AC mode)
>88%(DC mode)
BATTERY
12V9A
H
Battery Type
Numbers
2
Backup time
depends on the
capacity of
external
batteries
2
3
4
depends on the
capacity of external
batteries
4
6
12V9AH
depends on the
capacity of
external batteries
6
6
8
82.1
VDC
±1%
109.4
VDC
±1%
Long run unit depends on the capacity of external batteries
Typical recharge
time(standard modle)
Charging voltage
Charge current
SYSTEM FEATURES
Overload
@35Ԩ
12V9A
H
Line
Mode
Battery
Mode
Bypass
Mode
4 hours recover to 90% capacity (Typical)
27.4
VDC
±1%
1A
27.4
VDC
±1%
41.0
VDC
±1%
12A
54.7
VDC
±1%
1A
54.7
VDC
±1%
82.1
VDC
±1%
12A
82.1
VDC
±1%
1A
12A
Ambient Temp.<35Ԩ
105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass
when the utility is normal
110%~130%: UPS shuts down after 1minute at battery mode or transfer to bypass when
the utility is normal
>130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the
utility is normal
35Ԩ<Ambient Temp.<40Ԩ
105%~110%: UPS shuts down after 1 minutes at battery mode or transfer to bypass when
the utility is normal
>110%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the
utility is normal
8A(Input breaker)
Short Circuit
IV390E Rev. 00
Date of issue: 2015-10-29
16A(Input breaker)
25A(Input breaker)
Hold Whole System
Installation and user manual
Pag. 20 of 22 + FR
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Alarm and Switch off
Shut down UPS immediately
Line Failure, Battery Low, Overload, System Fault
USB(or RS232), SNMPcard(optional), Relay card (optional)
Low battery voltage
EPO (optional)
Audible & Visual alarms
Comunication interface
ENVIRONMENTAL
0ഒᨺ40ഒ
Operating temperature
-25ഒᨺ55ഒ
Storage temperature
Humidity range
20-90 % RH @ 0- 40°C (non-condensing)
Altitude
Noise level
PHYSICAL
Dimension W×H×D
(mm)
Net Weight (kg)
STANDARDS
Safety
< 1500m
Less than 50dBA at 1 Meter
144*209*
293
144*209*293
144*209*
399
144*209*399
191*337*46
0
144*209*399
8.9
4.2
16.2
6.3
24.8
6.5
EMC
IEC/EN62040-1,IEC/EN60950-1
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
* Derate to 80% of capacity when the output voltage is adjusted to100/200/208VAC
** Product specifications are subject to change without further notice.
IV390E Rev. 00
Date of issue: 2015-10-29
Installation and user manual
Pag. 21 of 22 + FR