- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Power supply units
- iStarUSA
- IS-950R3KPD8
- Manual
advertisement
IS -950R3KPD8
Redundant Power Supply
( 3U- 950W 8 0 P L U S )
SPECIFICATION
Revision: 1.0
IS-950R3KPD8 http:// www.Xeal.com
TEL: 626-3038885 FAX: 626-3010588
1. Purpose
This specification defines the performance characteristics and functions of a 950 watts redundant power supply with Active PFC (Power Factor Correction) and hot swappable capabilities.
2. AC Input Requirements
Voltage (sinusoidal) : 100~240 VAC full range, with 10% tolerance. Input frequency ranges from
47hz~63hz
2.2 AC Input Current and Inrush Current
AC line inrush current shall not damage any component nor cause the AC line fuse to blow under any
DC conditions and with any specified AC line input voltage and frequency. Repetitive On/Off cycling of the AC input voltage shall not damage the power supply.
Table 1: AC Input Current and Inrush Current
Input
Voltage
100~240Vac 10%
Input Current Maximum
Inrush Current
15A~7.5A 80Apeak@115VAC
2.3 Input Power Factor Correction (Active PFC)
The power factor at 100% of rated load shall be ≥ 0.95 at nominal input voltage.
AC line transient conditions are characterized as “sag” and “surge” conditions. Sag conditions (also referred to as “brownout” conditions) will be defined as the AC line voltage dropping below nominal voltage. Surge conditions will be defined as the AC line voltage rising above nominal voltage. The power supply shall meet the regulation requirements under the following AC line sage and surge conditions.
Table 2: AC Line Sag Transient Performance
Voltage Line Criteria
Frequency
Continuous
0-1 AC cycle
10%
100%
Nominal AC Input ranges
Nominal AC Input ranges
50/60 Hz
50/60 Hz
100%
80%
No loss of function or performance
No loss of function or performance
> 1 AC cycle > 10% Nominal AC Input ranges 50/60 Hz 100% Loss of function Acceptable
Table 3: AC Line Surge Transient Performance
Duration
Continuous
Surge
10%
0 - ½ AC cycle 30%
Operating AC Voltage Line Frequency
Nominal AC Voltage
Mid-point of Nominal AC
Voltage
50/60 Hz
50/60 Hz
Performance Criteria
No loss of function or performance
No loss of function or performance
3. DC Output Specification
3.1 Output Power / Currents
Table 4: Load Range
V o l t a g e M i n i m u m L o a d
+ 3 .
3 V 1 A
+ 5 V
+ 1 2 V
1 2 V
1 A
2 A
0 A
+ 5 V S B 0 .
1
Notes:
Note 1: The +5 & +3.3 Volt total output shall not exceed 210W.
Note 2: The +5, +3.3 & +12Volt total output shall not exceed 930W.
M a x i m u m L o a d
3 0 A
4 0 A
6 8 A
0 .
5 A
3 A
3.2 Voltage Regulation, Ripple and Noise
Table 5: Regulation, ripple and noise
Output Voltage +3.3V +5V +12V -12V(Optional) +5VSB(Optional)
Load Reg.
Line Reg.
Ripple & Noise
±5%
±1%
60mV
±5%
±1%
60mV
±5%
±1%
120mV
±10%
±1%
120mV
±5%
±1%
60mV
Ripple and noise shall be measured using the following methods: a) Measurements made differentially to eliminate common-mode noise b) Ground lead length of oscilloscope probe shall be ≤ 0.25 inch. c) Measurements made where the cable connectors attach to the load. d) Outputs bypassed at the point of measurement with a parallel combination of
10uF tantalum capacitor in parallel with 0.1uF ceramic capacitors. e) Oscilloscope bandwidth of 0 Hz to 20MHz. f) Measurements measured at locations where remote sense wires are connected. g) Regulation tolerance shall include temperature change, warm up drift and dynamic load
The power supply shall be stable and meet all requirements in the following table, except dynamic loading
requirements.
Table 6: Capacitive Loading Conditions
+ 3 .
3 V
+ 5 V
+ 1 2 V
1 2 V
+ 5 V S B
1 0
1 0
1 0
1
1
1 2 0 0 0
1 2 0 0 0
1 1 0 0 0
3 5 0
3 5 0 uF uF u F u F u F
The output voltages shall remain within the limits specified in Table-Regulation, ripple and noise for the step loading and within the limits specified in Table-Transient Load Requirement for the capacitive loading.
The load transient repetition rate shall be tested between 50Hz and 5kHz at duty cycle ranging from
10%-90%. The load transient repetition rate is only a test specification. The step load may occur anywhere within the MIN load to the MAX load shown in Table-Load Range.
Output
+3.3V
Table 7: Transient Load Requirements
Step Load Size
30% of Max. Load
Load Slew Rate
0.5 A/uS
30% of Max. Load
0.5 A/uS
Capacitive Load
1000 uF
1000 uF +5V
+12V
+5VSB
65% of Max. Load
30% of Max. Load
0.5 A/uS
0.5 A/uS
2200 uF
1 uF
Any output overshoot at turn on shall be less than 10% of the nominal output value. Any overshoot shall recover to be within regulation requirements in less than 10ms.
Table 8: Output Voltage Timing
Item Description
Tvout_rise Output voltage rise time from each main output
Tvout_on
Tvout_off
Output voltage rise time for the 5Vsb out put
All main output must be within regulation of each other within
this time.
All main output must leave regulation within this time
Table 9: Turn On/Off Timing
Item Description
1
1
20
20
400
1500 mS mS mS mS
regulation. being within regulation.
17 mS of AC tested at 80% of maximum load.
16 mS
80% of maximum load.
Tpson_on_delay Delay from PSON# active to output voltage within regulation limits.
Tpson_pwok Delay from PSON# deactive to PWOK being deasserted.
Tpwok_on Delay from output voltage within regulation limits to
PWOK asserted at turn on.
Tpwok_off Delay from PWOK deasserted to output voltages dropping out of regulation limits.
100 1000 mS
Tpwok_low
Tsb_vout
Duration of PWOK being in the deasserted state during an off/on cycle using AC or the PSON# signal. .
Delay from +5VSB being in regulation to O/Ps being in regulation at AC turn on.
100 mS
50 1000 mS
Figure 1: Turn On/Off Timing
AC Input AC off AC On
T vout_holdup
Vout
T ac_on-delay
T pwok_low
Tsb_on-delay
T pwok_off
T pwok_off
PWOK T pwok_on
T pwok_holdup
T sb_on-delay
T pwok_on T pson_pwok
+5VSB T sb_vout
T sb_holdup
Min.>70mS
T pson_on_delay
PSON#
AC turn 0n/off cycle PSON turn on/off cycle
Command Code
EFRP-S3490 PMBUS Command Code Summary
Command Name
SMBus
Transaction Type
Number of
Data Bytes
78h STATUS_BYTE (Note 2)
79h STATUS_WORD (Note 2)
7Ah STATUS_VOUT (+12V)
7Bh STATUS_IOUT (+12V)
READ BYTE
READ WORD
READ BYTE
READ BYTE
1
2
1
1
1
READ 1
8 9 h R E A D _ I I N
8Bh READ_VOUT (+12V)
8Ch READ_IOUT (+12V)
8Dh READ_TEMPERATURE_1 (Note 1)
9 6 h R E A D _ P O U T
R E A D W O R D
READ WORD
READ WORD
READ WORD
READ WORD
2
2
2
2
2
9 9 h
9 A h M F R _ M O D E L
9Bh MFR_REVSION
9 E h
M F R _ I D
M F R _ S E R I A L
B1h
B 2 h
B 4 h
Over Limit Status (Note 2)
R e a d _ 5 V I O U T
R e a d _ 5 V V O U T
Note 1 : T1 was detected within the hotspot temperature of PSU.
Note 2 : The content is described below.
READ BYTE
READ BYTE
R E A D W O R D
R E A D W O R D
1
1
2
2
3
2
1
0
7
6
5
4
Over Limit STATUS(B1h)
Reserved
Reserved
Reserved
Reserved
3V3_VOUT_OV
5V_VOUT_OV
3V3_IOUT_OC
5V_IOUT_OC
1
0
6
5
4
7
Power STATUS(B0h)
Reserved
Reserved
Reserved
3
2
Reserved
Power ON
Module Status
PS_ON
AC_OK
5
4
3
2
STATUS_FANS_1_2(81h)
7 Fan 1 Fault
6 Reserved
1
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
2
1
0
5
4
3
7
6
STATUS_WORD(79h)
(Upper byte)
VOUT
IOUT
Reserved
Reserved
Reserved
FAN
Reserved
Reserved
5
4
3
7
6
2
1
0
STATUS_BYTE(78h)
Also is the lower byte of
STATUS_WORD
Reserved
Reserved
VOUT_OV
IOUT_OC
Reserved
Reserved
Reserved
Temperature
PMBus Status Chart
5
4
3
2
1
0
STATUS_VOUT(7Ah)
7 VOUT_OV_Fault(12V)
6 Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
3
2
1
0
7
STATUS_IOUT(7Bh)
IOUT_OC_Fault(12V)
6
5
4
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
STATUS_TEMPERATURE(7Dh)
5
4
3
2
7
6
1
0
T1_OT
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Byte
STATUS_WORD
Status Registers Content
Bit Number Status Bit Name Meaning
0: Normal
79h
5
4
3
1
0
7
6
R
R
R e e e s s s e e e r v r v r v e e e d d d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
0: Normal
0: Normal
78h
3 R e s e r v e d
0: Normal
0: Normal
1
0
R e s e r v e d
R e s e r v e d
0: Normal
Power Status
B0h
Over Limit Status
B1h
7
6
5
4
7
6
5
4
R
R
R
R e e e e s s s s e e e e r v r v r v r v e e e e d d d d
1: Power OFF; 0: Power ON
1: Not inserted; 0: Inserted
1 PS_ON 1: PS_ON=High; 0: PS_ON=Low
0 AC_OK 1: AC Fail; 0: AC OK
R
R
R
R e e e e s s s s e e e e r v r v r v r v e e e e d d d d
2 5V_VOUT_OV 1: 5V has an over-voltage fault. 0: Normal
0 5V_IOUT_OC 1: 5V has an over-current fault. 0: Normal
STATUS_FANS_1_2
81h
2
1
0
7 Fan 1: Fan speed <300 rpm. 0: Normal
6 R e s e r v e d
5
4
3
R
R
R e s e s e s e r v e r v e r v e d e d e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
STATUS_VOUT
7Ah
STATUS_IOUT
7Bh
6
5
4
3
2
1
0
STATUS_TEMPERATURE
2
1
0
6
5
4
3
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
7Dh
6
5
4
3
2
1
0
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
R e s e r v e d
3.8 Efficiency
1 The power efficiency under below load conditions: a. 3.3V/25.09A, 5V/33.45A, 12V/56.87A ,-12V/0.42A, 5VSB/2.51A for 100% Load, shall be 80%. b. 3.3V/12.54A, 5V/16.73A, 12V/28.43A, -12V/0.21A, 5VSB/1.25A for 50% Load, shall be 80%. c. 3.3V/5.02A, 5V/6.69A, 12V/11.37A, -12V/0.08A, 5VSB/0.50A for 20% Load, shall be 80%.
Measuring at test backplane, Fan power consumption is not included.
2 The power efficiency shall be 78% at ATE test at full load@115Vac input.
4. Protection Circuits
Protection circuits inside the power supply shall cause only the power supply’s main outputs to shutdown. If the power supply latches off due to a protection circuit tripping, an AC cycle OFF for 15 sec and a PSON
# cycle HIGH for 1 sec must be able to restart the power supply.
4.1 Over Current Protection (OCP)
The power supply shall have current limit to prevent the +5V, +3.3V, and +12V outputs from exceeding the values shown in Table-Over Current Protection. The power supply shall latch off if the current exceeds the limit.
Voltage
Table 10: Over Current Protection
Minimum Maximum Shutdown Mode
+ 5 V 4 4 A 6 0 A L a t c h O f f
4.2 Over Voltage Protection (OVP)
The power supply shall shut down and latch off after an over voltage conditions occurs. 5Vsb will be auto-recovered after removing OVP limit.
Table 11: Over Voltage Protection
The power supply shall shut down in latch off mode when the output voltage is short circuit.
4.4 No Load Operation
No damage or hazardous condition should occur with all the DC output connectors disconnected from the load. The power supply may latch into the shutdown state
4.5 Over Temperature Protection (OTP)
The power supply will shut down i when an over temperature condition occurs; no damage shall be caused.
5. Environmental Requirements
5.1 Temperature
Operating Ambient, normal mode (inlet air): 0°C ~ 4 5°C (32°F~ 113°F)
Non-operating Ambient:: -40°C ~ 70°C (-40°F~ 158°F)
5.2 Humidity
Operating: 20% ~ 90%RH non-condensing
Non-Operating: 5% ~ 95%RH non-condensing
5.3 Altitude
Operating: Sea level to 10,000 ft
Non Operating: Sea level to 40,000 ft
Non-Operating: 50 G Trapezoidal Wave, 11mS half sin wave. The shock is to be applied in each of the orthogonal axes.
The power supply shall be subjected to a vibration test consisting of a 10 to 300 Hz sweep at a constant acceleration of 2.0g for duration of one (1) hour for each of the perpendicular axes X, Y and Z (0.1 octave/minute). The output voltages shall remain within specification.
Electromagn etic
Interference
Table 12 EMC Requirements
FCC CFR Title 47
Part 15
Sub Part B
EN55022/EN55024
Conducted B Class
Radiated B Class
Flicker IEC61000-3-3
ESD
Susceptibility
EN-61000-4-2
Radiated
Susceptibility
EFT/Burst
EN61000-4-3
EN61000-4-4
8KV by Air, 4KV by Contact
Performance Criteria B
80MHz~1000MHz
(3V/m(mns) Amplitude 80% AM 1KHz
Criteria A
5KHz, AC: 1KV, DC: 0,5 KV, Performance Criteria B
Surge
Voltage
Conducted
Susceptibility
RF
EN61000-4-5
EN61000-4-6
EN61000-4-8
Line-to-Line: 1KV
Line-to-Ground: 2KV
Performance Criteria B
0.15MHz~80MHz
3V/m Amplitude 80% AM 1KHz
Performance Criteria A
50 Hz/3A(ms)/m Performance Criteria A
Conducted
Voltage Dips and
Interruptions
Leakage
Current
EN61000-4-11
30%(Voltage Dips)
60%(Voltage Dips)
>95%(Voltage Dips)
10 ms
100ms
500ms
EN60950-1 3.5mA@240VAC
Criteria B
Criteria C
Criteria C
This power supply is designed to meet the following safety
Table 13: Product Safety
Product Safety: UL,cUL UL60950-1
CB IEC60950-1
TUV EN60950-1
CCC
FCC
BSMI CNS14366
6 Reliability
6.1 Mean Time Between Failures (MTBF)
The MTBF of the power supply shall be calculated utilizing the Part-Stress Analysis method of MIL217F.
The calculated MTBF of the power supply shall be greater than 100,000 hours under the following conditions:
Full rated load; 120V AC input; Ground Benign; 25°C
7.Mechanical Overview
Dimension: 86(W) x 126.9mm(H) x 290mm(D)
8. LED Indicators
There will be a LED on each power module to indicate power status
Table 14: LED Color and Power Status
Power Supply Status
PSU Works Normally
S t a n d b y ( O n l y + 5 V S B o u t p u t ) ( O p t i o n a l )
Power Fail
Fan Fail
Color
Green
A m b e r
Red
Red
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement