Eaton 5SC1000 uninterruptible power supply (UPS) User manual

Add to my manuals
12 Pages

advertisement

Eaton 5SC1000 uninterruptible power supply (UPS) User manual | Manualzz
ENGLISH
Installation
and user manual
5SC
5SC
5SC
5SC
Copyright © 2013 EATON
All rights reserved.
Service and support:
Call your local service representative
619-00470-01-i (en)
500i
750i
1000i
1500i
Certification Standards
UPS directives:
• Safety:
IEC 62040-1: 2008
• EMC:
IEC 62040-2: 2005
• Performance:
IEC 62040-3: 2010
CE mark (EN 62040-1: 2008 and EN 62040-2: 2006 (C1))
Class B emission level CISPR 22: 2005 + A2 2006 (EN 55022)
Harmonics emission: IEC 61000-3-2 edition 3.2: 2009
Flickers emission: IEC 61000-3-3 edition 2: 2008
The EC Declaration of Conformity is available upon request for products with a CE mark.
For copies of the EC Declaration of Conformity, contact Eaton Power Quality or check Eaton website:
www.powerquality.eaton.com
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
Do not discard the UPS or the UPS batteries in the trash.
This product contains sealed lead acid batteries and must be disposed as it's explain in this manual.
For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Information, advice, help.
Page 2
619-00470-01-i (en)
1. Introduction........................................................................................ 4
1.1 Environmental protection....................................................................................................4
2. Presentation....................................................................................... 5
2.1 Standard installation...........................................................................................................5
2.2 Rear panels.........................................................................................................................5
2.3 Control panel......................................................................................................................6
2.4 LCD description..................................................................................................................6
2.5 UPS setting through the LCD.............................................................................................6
3. Installation......................................................................................... 7
3.1 Unpacking and contents check...........................................................................................7
3.2 Communication ports.........................................................................................................8
4. Operation........................................................................................... 9
4.1 Start-up and Normal operation............................................................................................9
4.2 Starting the UPS on Battery...............................................................................................9
4.3 UPS Shutdown...................................................................................................................9
4.4 Operation on Battery Power...............................................................................................9
4.5 Return of AC Input Power...................................................................................................9
5. Maintenance.................................................................................... 10
5.1 Troubleshooting................................................................................................................. 10
5.2 Battery-module replacement............................................................................................ 11
6. Appendices....................................................................................... 12
6.1 Technical specifications..................................................................................................... 12
619-00470-01-i (en)
Page 3
ENGLISH
Contents
1. Introduction
Thank you for selecting an EATON product to protect your electrical equipment.
The 5SC range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features
of your UPS (Uninterruptible Power System).
Before installing 5SC, please read the booklet presenting the safety instructions.
Then follow the instructions in this manual.
To discover the entire range of EATON products and the options available for the 5SC range,
we invite you to visit our web site at www.eaton.com/powerquality or contact your EATON representative.
1.1 Environmental protection
EATON has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprises over 50 % of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packing materials are recyclable and bear the appropriate identification symbol
01
PET
Materials
Abbreviations
Number in
the symbols
Polyethylene terephthalat
PET
01
High-density polyethylene
HDPE
02
Polyvinyl chloride
PVC
03
Low-density polyethylene
LDPE
04
Polypropylene
PP
05
Polystyrene
PS
06
01
PET
Follow all local regulations for the disposal of packing materials.
End of life
EATON will process products at the end of their service life in compliance with local regulations.
EATON works with companies in charge of collecting and eliminating our products at the end of
their service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing centre for electrical and
electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations
concerning batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
Page 4
619-00470-01-i (en)
2.1 Standard installation
D
H
Description
Weights (kg/lb)
5SC
5SC
5SC
5SC
6.60 / 14.60
10.40 / 22.90
11.10 / 24.50
15.20 / 33.50
500i
750i
1000i
1500i
Dimensions (mm/inch)
DxWxH
240 x 150 x 210 / 9.4 x 5.9 x 8.3
340 x 150 x 210 / 13.4 x 5.9 x 8.3
340 x 150 x 210 / 13.4 x 5.9 x 8.3
410 x 150 x 210 / 16.1 x 5.9 x 8.3
W
2.2 Rear panels
5SC 500i
5SC 750i
2
RS232
5
OR
1
2
RS232
5
OR
1
3
OUTPUT
3
OUTPUT
INPUT
INPUT
4
4
Refer to the Bottom of
the unit for caution markings!
Refer to the Bottom of
the unit for caution markings!
5SC 1000i
5SC 1500i
2
RS232
5
OR
1
OUTPUT
2
RS232
5
OR
1
OUTPUT
OUTPUT
3
3
INPUT
4
Refer to the Bottom of
the unit for caution markings!
4
Refer to the Bottom of
the unit for caution markings!
INPUT
(1) USB communication port
(2) RS232 communication port
(3)Outlets for connection of critical equipment
(4)Socket for connection to AC-power source
(5)Ground screw
619-00470-01-i (en)
Page 5
ENGLISH
2. Presentation
2. Presentation
2.3 Control panel
The UPS has a three-button LCD. It provides useful information about the UPS itself, load status, events,
measurements and settings.
6
AVR
7
%
Min
Hz
kVA
kW
6
ON/OFF button
7
Scroll down
8
Mute alarm
9
UPS ON
10
AVR mode
11
Battery mode
12
Internal fault
13
Output load level
14
Battery level
15
Input measurements
16
Output measurements
17
Measuring unit
8
2.4 LCD description
10
11
9
12
13
14
15
17
16
2.5 UPS setting through the LCD
Release scroll down button to select menu
5s
2s
2s
Output voltage
Alarm
2s
Sensitivity (1)
Example of setting
10s
5s
5s
Save the new value
• LCD will shut off if there is no activity for 3 minutes.
(1) In low sensitivity mode (Lo) UPS will tolerate more fluctuations in power and will go on battery power less
often. If the connected load is sensitive to power disturbances, keep the sensitivity as Standard (Std).
Page 6
619-00470-01-i (en)
3.1 Unpacking and contents check
1
4
5
2
3
6
(1) 5SC UPS
(2) Quick start and safety instructions
(3) User manual and IPSS (Intelligent Power Software Suite) CDROM
(4) 2 connection cables for the protected equipment
(5) RS232 communication cable
(6) USB communication cable
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.
619-00470-01-i (en)
Page 7
ENGLISH
3. Installation
3. Installation
3.2 Communication ports
Connection of RS232 or USB communication port
The RS232 and USB communication ports cannot operate simultaneously.
1
1. C
onnect the RS232 (5) or USB
(6) communication cable to
the serial or USB port on the
computer equipment.
2
5
6
2. C
onnect the other end of the
communication cable (5) or
(6) to the USB (1) or RS232 (2)
communication port on
the UPS.
The UPS can now communicate
with EATON power management
software.
Characteristics of the optocoupler RS232 communications port
• Pins 1, 3, 4, 5, 6, 10: not used
• Pin 2: common (user)
• Pin 7: low battery
• P
in 8: operation on battery
power
• P
in 9: UPS ON, equipment
supplied
n.o.: normally open contact
When a signal is activated, the contact is closed between the common (pin 2) and the pin
for the corresponding signal.
Contact characteristics (optocoupler)
• Voltage: 48 V DC max
• Current: 25 mA max
• Power: 1.2 W
Page 8
619-00470-01-i (en)
4.1 Start-up and Normal operation
To start the UPS:
1. Verify that the UPS power cord is plugged in.
2. Press the
button on the UPS front panel for at least 2 seconds.
3.Check the UPS front panel display for active alarms.
If the
indicator is on, do not proceed until all alarms are cleared.
Correct the alarms and restart if necessary.
4.Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and any loads
are powered and protected.
4.2 Starting the UPS on Battery
Before using this feature, the UPS must have been powered by utility power with output enabled at
least once.
To start the UPS on battery:
1.Press the
button on the UPS front panel until the UPS front panel display illuminates.
The UPS cycles through Standby mode to Battery mode. The
indicator illuminates solid.
The UPS supplies power to your equipment.
2.Check the UPS front panel display for active alarms. Resolve any active alarms before continuing.
See "Troubleshooting" on page 10.
4.3 UPS Shutdown
To shut down the UPS:
1. Press the
button on the front panel for three seconds.
The UPS starts to beep. The UPS then transfers to Standby mode, and the
indicator turns off.
4.4 Operation on Battery Power
Transfer to battery power
• The connected devices continue to be supplied by the UPS when AC input power is no longer available.
The necessary energy is provided by the battery.
• The
indicator illuminates solid.
• The audio alarm beeps every ten seconds.
The connected devices are supplied by the battery.
Low-battery warning
• The
indicator illuminates solid.
• The audio alarm beeps every three seconds.
The remaining battery power is low. Shut down all applications on the connected equipment because
automatic UPS shutdown is imminent.
End of battery backup time
• All the LEDs go OFF.
• The audio alarms stops.
4.5 Return of AC Input Power
Following an outage, the UPS restarts automatically when AC input power returns (unless the restart
function has been disabled) and the load is supplied again.
619-00470-01-i (en)
Page 9
ENGLISH
4. Operation
5. Maintenance
5.1 Troubleshooting
Operation status
Overload
Short-circuit fault
Battery fault
Possible cause
Action
Power requirement exceeds the
Remove some of the equipment
UPS capacity (greater than 105 % of from the UPS.The UPS continues
nominal).
to operate, but may shutdown
if the load increases.The alarm
resets when the condition becomes
inactive.
A short-circuit occurred.
Check device connection or
integrity.
The batteries in the UPS are
disconnected.
The end of battery life is reached.
Fan fault
Charger fault
The UPS has a fan fault.
The UPS has a charger fault.
If error persists, note the alarm
message and the UPS serial
number, and then contact your
service representative.
Verify that all batteries are properly
connected.
If error persists, note the alarm
message and the UPS serial
number, and then contact your
service representative.
Contact your service representative
for battery replacement.
Check that no object is blocking the
fan.
If error persists, note the alarm
message and the UPS serial
number, and then contact your
service representative.
The UPS does not charge the
battery anymore.
Note the alarm message and
the UPS serial number, and then
contact your service representative.
Page 10
619-00470-01-i (en)
5.2 Battery-module replacement
Safety recommendations
The battery can cause electrocution and high short-circuit currents. The following safety precautions
are required before servicing the battery components:
• remove watches, rings, bracelets and all other metal objects from the hands and arms,
• use tools with an insulated handle.
Battery tray removal on tower models
This operation must be performed when the UPS is switched OFF, and unplugged from AC source.
A-R
emove the front panel.
A
B-D
isconnect the battery block by
separating the two connectors
(never pull on the wires).
B
C-R
emove the plastic protection cover
in front of the battery (one screw).
C
D
D-P
ull the plastic tab to remove
the battery block and replace it.
Mounting the new battery module
Carry out the above instructions in reverse order.
● To ensure safety and high performance, use only batteries supplied by EATON.
● Take care to firmly press together the two parts of the connector during remounting.
619-00470-01-i (en)
Page 11
ENGLISH
5. Maintenance
6. Appendices
6.1 Technical specifications
Filter
Transformer
"AVR"
Charger
Inverter
Battery
Output Power
@ 230 V
•Rated input voltage
•Input voltage range
•Input frequency
range
•Voltage
•Frequency
•Standard
•Operating
temperature range
•Storage
temperature range
•Relative humidity
•Noise level
5SC 500i
500 VA
350 W
5SC 750i
5SC 1000i
5SC 1500i
750 VA
1000 VA
1500 VA
525 W
700 W
1050 W
AC Input power
Single phase 220-240 V
184 to 276 V
45 to 55 Hz (50 Hz system), 55 to 65 Hz (60 Hz system)
Output on battery power
220/230/240 V (-10/+6 %) (1)
50/60 Hz ±0.1 Hz
Battery (sealed lead acid, maintenance free)
1 x 12 V
2 x 12 V
2 x 12 V
9 Ah
7 Ah
9 Ah
Environment
0 to 35 °C / 32 to 95 °F
3 x 12 V
9 Ah
-15 to +40 °C / 5 to 104 °F
0 to 90 % (without condensation)
< 40 dBA in normal mode
(1) Adjustable to 220/230/240 V, must be set to the identical AC power source value.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,
250 V which is IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A,
250 V.
This product is designed for IT power distribution system.
Page 12
619-00470-01-i (en)