APC ACRA100 hardware cooling accessory Installation Manual

Add to my manuals
68 Pages

advertisement

APC ACRA100 hardware cooling accessory Installation Manual | Manualzz
Operation and
Maintenance
Pumped Refrigerant System
Refrigeration Distribution Unit (RDU)
and Cooling Modules
ACDA901
ACOA500
ACOA501
ACRA100
ACRA101
This manual is available in English on the enclosed CD.
Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.
Deze handleiding staat in het Nederlands op de bijgevoegde cd.
Este manual está disponible en español en el CD-ROM adjunto.
Ce manuel est disponible en français sur le CD-ROM ci-inclus.
Questo manuale è disponibile in italiano nel CD-ROM allegato.
本マニュアルの日本語版は同梱の CD-ROM からご覧になれます。
Instrukcja Obsługi w jezyku polskim jest dostepna na CD.
O manual em Português está disponível no CD-ROM em anexo.
Данное руководство на русском языке имеется на прилагаемом компакт-диске.
您可以从包含的 CD 上获得本手册的中文版本。
동봉된 CD 안에 한국어 매뉴얼이 있습니다 .
동봉된 CD 안에 한국어 매뉴얼이 있습니다 .
American Power Conversion Legal Disclaimer
The information presented in this manual is not warranted by the American Power Conversion Corporation to be
authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site
specific development plan. Therefore, American Power Conversion Corporation assumes no liability for damages,
violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this
Publication.
The information contained in this Publication is provided as is and has been prepared solely for the purpose of evaluating
data center design and construction. This Publication has been compiled in good faith by American Power Conversion
Corporation. However, no representation is made or warranty given, either express or implied, as to the completeness or
accuracy of the information this Publication contains.
IN NO EVENT SHALL AMERICAN POWER CONVERSION CORPORATION, OR ANY PARENT,
AFFILIATE OR SUBSIDIARY COMPANY OF AMERICAN POWER CONVERSION CORPORATION OR
THEIR RESPECTIVE OFFICERS, DIRECTORS, OR EMPLOYEES BE LIABLE FOR ANY DIRECT,
INDIRECT, CONSEQUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL DAMAGES (INCLUDING,
WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT, REVENUE, DATA,
INFORMATION, OR BUSINESS INTERRUPTION) RESULTING FROM, ARISING OUT, OR IN
CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT,
EVEN IF AMERICAN POWER CONVERSION CORPORATION HAS BEEN EXPRESSLY ADVISED OF
THE POSSIBILITY OF SUCH DAMAGES. AMERICAN POWER CONVERSION CORPORATION
RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT
OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME WITHOUT NOTICE.
Copyright, intellectual, and all other proprietary rights in the content (including but not limited to software, audio, video,
text, and photographs) rests with American Power Conversion Corporation or its licensors. All rights in the content not
expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons
accessing this information.
This Publication shall not be for resale in whole or in part.
Contents
General Information ........................................................ 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Commissioning ............................................................... 3
Inspection Checklists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Initial Inspection Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Inspection Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical Inspection Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . .
User Interface Inspection Checklist . . . . . . . . . . . . . . . . . . . . . . . . .
Start-up Inspection Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Final Inspection Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
4
5
6
7
7
Operation ......................................................................... 8
The Pumped Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Refrigerant Circulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
System Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Pumped Refrigerant System Piping Diagram . . . . . . . . . . . . . . . . 11
OA Piping Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
RA Piping Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Display Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Using the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Scrolling status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main menu screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Navigating the screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sub-menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Path statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Password entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start the RDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stop the RDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start a CM Remotely . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stop a CM Remotely . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
15
16
16
17
17
18
18
18
18
General Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
RDU configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
CM Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Identify the cooling modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Pumped Refrigerant System Operation and Maintenance
i
Group Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Modify a Cooling Module (CM) ID . . . . . . . . . . . . . . . . . . . . . . . . . . .
View the groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unassign CMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
23
23
23
Control the Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Group PIDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Tune the PID loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
RDU (component) run hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Reset RDU run hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
CM (component) run hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Reset CM run hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Service intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Display Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Password and timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Identify the RDU by Name and Location . . . . . . . . . . . . . . . . . . . . . 30
Adjust display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Display units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Configure the network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
View Status Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Scrolling status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Cooling group status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
About the RDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
View event log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Clear event log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Respond to Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
View active alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clear active alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm messages and suggested actions . . . . . . . . . . . . . . . . . . . .
CM alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
37
37
38
41
Pumped Refrigerant System Operation and Maintenance
Network Management Card .......................................... 44
Quick Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
TCP/IP configuration methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
APC Device IP Configuration Wizard . . . . . . . . . . . . . . . . . . . . . . . . 45
.ini file utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
BOOTP and DHCP configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Remote access to the command line interface . . . . . . . . . . . . . . . . 46
Command line interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
How to Recover from a Lost Password. . . . . . . . . . . . . . . . . . . . . . .48
CM Display ..................................................................... 49
OA display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
RA display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Display Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Maintenance ................................................................... 51
Leak Detector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Monthly Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Cleanliness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Quarterly Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . .54
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Functional tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Semi-Annual Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . .54
Cleanliness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Troubleshooting ............................................................ 55
Pumped Refrigerant System Operation and Maintenance
iii
General Information
Overview
The pumped refrigerant system is composed of at least one 160 kW Refrigeration Distribution Units
(RDUs) circulating R-134a refrigerant to the Cooling Modules. Each RDU can support multiple
overhead or in row Cooling Modules.
Cooling Modules are identified as CMs on the display interface screens of the RDU and in this manual.
The exact type of Cooling Module is identified where specificity is required on both the display interface
and in this manual.
Note the definitions for the icons here and be observant for them throughout this manual. They are
intended to call attention to potential hazards and important information.
Save these instructions
This manual contains important instructions that must be followed during installation, operation, and
maintenance of the Rack PDU.
Pumped Refrigerant System Operation and Maintenance
1
Safety
Read and adhere to the following important safety considerations when working with this unit.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on the equipment. All electrical
work should be performed by licensed electricians. Practice lockout/tagout procedures.
Do not wear jewelry when working with electrical equipment.
Failure to follow these instructions can result in death or serious injury.
WARNING
HAZARD FROM MOVING PARTS
Keep hands, clothing, and jewelry away from moving parts. Check the equipment for
foreign objects before closing the doors and starting the equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
DAMAGE TO EQUIPMENT OR PERSONNEL
The equipment is heavy and can easily be tipped. For safety purposes, adequate
personnel must be present when moving this equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
HAZARD TO EQUIPMENT OR PERSONNEL
All work must be performed by American Power Conversion (APC®) by Schnieder Electric
authorized personnel.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
NOTICE
HAZARD TO EQUIPMENT
Circuit boards contained within this unit are sensitive to static electricity. Use one or more
electrostatic-discharge device while handling the boards.
Failure to follow these instructions can result in equipment damage.
2
Pumped Refrigerant System Operation and Maintenance
Commissioning
After installation, verify that all components are working properly and that the equipment is ready to
begin operation.
Inspection Checklists
Initial Inspection Checklist
The initial inspection ensures that the equipment has been properly installed, the location of the
equipment has been properly prepared and the equipment is free of damage.
Note: Although it is not necessary for the RDU to be installed in a room with a vapor barrier,
the computer room should have one as a vapor barrier minimizes moisture infiltration.
Without a vapor barrier, it will be difficult to maintain the humidity in the room. Do not
introduce unconditioned outside air into the computer room.
Note: A minimum of 900 mm (36 in) of clear floor space in front of the RDU is required for
service access.
5
Ensure the installation procedure is complete according to the installation manual.
5
If the RDU is installed in the computer room, ensure that the walls, floor, and ceiling of the room where the
equipment is located are sealed with a vapor barrier.
5
Ensure there is no evidence of damage to the equipment.
5
Ensure the equipment is level.
5
Ensure that the equipment is joined to the adjacent racks if it is installed at the end of a row.
5
Ensure the clearance around the equipment is in accordance with local and national codes and regulations as
well as the installation manual.
Pumped Refrigerant System Operation and Maintenance
3
Electrical Inspection Checklist
The electrical inspection verifies that all electrical connections are secure and correct and that the
equipment is properly grounded.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on the equipment. All electrical
work should be performed by licensed electricians. Practice lockout/tagout procedures.
Do not wear jewelry when working with electrical equipment.
Failure to follow these instructions can result in death or serious injury.
Ensure that the:
4
5
Incoming voltages match the phase and voltage listing on the nameplate.
5
Electrical wiring complies with local and national codes and regulations.
5
Equipment is properly grounded.
5
Access doors are properly grounded.
5
Electrical connections are tight, including contactors, terminal blocks, controllers, switches, relays, auxiliary
devices, and field connections.
5
Circuit breakers are properly connected and securely attached.
Pumped Refrigerant System Operation and Maintenance
Mechanical Inspection Checklist
The mechanical inspection verifies that all mechanical components and connections are secure and tight
and ready for start-up and system charging.
Note: Improperly installed piping may result in improper operation and possible damage to
the cooling unit or surrounding equipment.
Ensure that the:
5
Chilled water pipe fittings are tight, and have been leak checked. Leak check pressure can not exceed 300 psi
(2068 kpa).
5
Air is bled from the water system. If air remains in the system, bleed it out now.
5
Mechanical connections are tight.
5
Supply chilled water temperature is recorded.
5
Chilled water flow is correct based on the performance requirements of the RDU.
5
Field-installed traps and piping are in accordance with the installation manual. Strainers are in place in the
chilled water supply loop. Proper piping practices have been followed.
5
Piping is adequately supported and isolated when necessary.
5
Field-installed service valves are open.
5
Water outlet temperature sensor is positioned correctly. See the installation manual for correct positioning.
5
Piping in the building and on the roof is properly insulated.
5
Pumped refrigerant piping joints are tight, and have been leak checked. Leak check pressure can not exceed
150 psi (1034 kpa).
5
Pressure relief valve is installed in accordance with the installation manual as well as local and national codes
and regulations.
5
Refrigerant lines have been evacuated to ensure foreign particles have been removed from the system.
Evacuation level must be at a minimum 500 microns for 2 hours.
5
All piping (chilled water and refrigerant vapor) is properly insulated.
5
Covers and guards are in place.
of
Pumped Refrigerant System Operation and Maintenance
5
User Interface Inspection Checklist
The user interface inspection verifies that the sensors and internal communication links are installed
properly. Check that the outdoor heat exchanger is connected to the RDU(s).
Ensure that:
6
5
An A-Link bus is connected to each RDU or cooling module (CM) and a terminator is plugged into all
unused A-Link connectors.
5
An A-Link bus is connected to the external temperature and humidity sensor (APC part number
AP9520TH).
5
The input contacts and output relays are connected correctly.
5
The building management system is connected correctly and a terminator is wired into the RDU between
Modbus D0 and Modbus D1.
5
The temperature sensors located on the equipment are connected correctly.
5
The rack temperature sensors are installed correctly.
5
The network port is connected correctly and an IP address has been assigned to the RDU(s).
5
The optional rope water detection device is installed properly.
Pumped Refrigerant System Operation and Maintenance
Start-up Inspection Checklist
The start-up inspection ensures that the equipment is operating properly after the initial start-up. This
inspection verifies that all modes of operation are working correctly and that the equipment is ready for
normal operation.
See “Start the RDU” on page 1 for startup information.
While the equipment is operating, ensure that:
5
The unit is free from malfunctions, including chilled water leaks, or other irregularities, in each mode of
operation.
5
Both the primary and secondary power inputs can supply power to all functions in the equipment.
5
A pump is operating.
5
Air filters in CMs (RA only) are clean and free of debris. Replace air filters with APC air filters only.
Final Inspection Checklist
The final inspection verifies that the system is clean, the installed options work properly, and the start-up
form is sent to APC.
Ensure that:
5
The system is clean and free from debris.
5
Packaging materials are disposed of properly.
5
The start-up form was completed and sent to APC.
Pumped Refrigerant System Operation and Maintenance
7
Operation
The Pumped Refrigerant System
System Operation
The primary function of the Pumped Refrigerant System is to capture the heat generated by IT
equipment and neutralize it before it mixes with the room air. The pumped refrigerant system uses two
circuits to remove heat. In the first circuit, water or a water/glycol mixture is pumped from the chiller
into a brazed plate heat exchanger located inside the RDU.
In the second circuit, R134a refrigerant circulates from the RDU to Cooling Modules located either over
the hot aisle or in the row. Cooling Module fans draw in hot air across their micro channel coil
completely evaporating the liquid refrigerant. The refrigerant vapor then returns to the RDU. There the
vapor is condensed back into a liquid in the brazed plate heat exchanger which rejects the heat to the
chilled water.
The system does only sensible cooling. No energy is wasted in latent energy removal. Less energy is
used to satisfy the IT load. A thermal containment system will further increase efficiency. A
conventional computer room air conditioner is used in conjunction with the pumped refrigerant system
to provide humidity control.
The pumped refrigerant system is flexible. Each system is configured to the user’s specific requirements.
As cooling needs increase, the system can be expanded. A system may have multiple RDUs. One RDU
can supply OA Cooling Modules and RA Cooling Modules.
Note: Only APC certified technicians should service the pumped refrigerant system.
Refrigerant Circulation
Each cooling module is connected to the RDU by overhead or under floor refrigerant distribution piping.
Note: Under floor refrigerant piping is not recommended.
Multiple electronic valves in each CM automatically regulate the refrigerant flow and coil temperature to
met the IT load at the desired supply air set point.
See the “OA Piping Diagram” on page 1 for the locations of the valves and sensors on the OA
Cooling Modules. See “RA Piping Diagram” on page 1 for the locations of the valves and
sensors on the RA Cooling Module
Refrigerant is circulated through the system by two fully redundant refrigerant pumps. The RDU display
interface allows you to program the number of run hours a pump will operate before switching to the
second pump. Pump redundancy ensures that the cooling modules continue to run uninterrupted.
The RDU is equipped with a subcooler to further cool the refrigerant leaving the brazed plate heat
exchanger. This additional subcooling allows the refrigerant pumps to operate correctly and efficiently
while responding to varying IT loads.
8
Pumped Refrigerant System Operation and Maintenance
In the absence of an IT load or when all the CMs are turned off, the RDU refrigerant pumps continue to
operate by bypassing the refrigerant through a pump head pressure control valve. This head pressure
control valve allows continuous operation of the pumps regardless of the load. While in bypass, the
refrigerant pumps reduce to a minimum speed allowing minimal power consumption and avoid the wear
of frequent starts and stops.
See the “Pumped Refrigerant System Piping Diagram” on page 1 for the locations of the RDU
components discussed above.
The RDU monitors room conditions to control the refrigerant condensing temperature relative to the
room dew point.
See the RDU Installation Manual, OA Installation Manual, and RA Installation Manual for
more information.
System Architecture
The pumped refrigerant system can be configured based on the customer requirements.
Examples below illustrate group usage with a single RDU.
Group 1
RDU
ID: 1
CM
Unit: 2
RDU: 1
Group: 1
CM
Unit: 1
RDU: 1
Group: 1
CM
Unit: 3
RDU: 1
Group: 1
One RDU, One Group
CAN Bus
Liquid Supply
Vapor Return
Group 1
RDU
ID: 1
CM
Unit: 1
RDU: 1
Group: 1
CM
Unit: 2
RDU: 1
Group: 1
CM
Unit: 3
RDU: 1
Group: 1
CM
Unit: 2
RDU: 1
Group: 2
CM
Unit: 3
RDU: 1
Group: 2
Group 2
CM
Unit: 1
RDU: 1
Group: 2
One RDU, Two Groups
Pumped Refrigerant System Operation and Maintenance
9
The example below shows two RDUs employed to control three groups of CMs.
Group 1
RDU
ID: 1
CM
Unit: 3
RDU: 1
Group: 1
CM
Unit: 2
RDU: 1
Group: 1
CM
Unit: 1
RDU: 1
Group: 1
Group 2
RDU
ID: 2
CM
Unit: 1
RDU: 2
Group: 2
CM
Unit: 1
RDU: 1
Group: 2
CM
Unit: 2
RDU: 2
Group: 2
CM
Unit: 2
RDU: 1
Group: 2
CM
Unit: 3
RDU: 2
Group: 2
Group 3
CM
Unit: 1
RDU: 2
Group: 3
CAN Bus
Liquid Supply
Vapor Return
10
CM
Unit: 2
RDU: 2
Group: 3
CM
Unit: 3
RDU: 2
Group: 3
Two RDUs, Three Groups
Pumped Refrigerant System Operation and Maintenance
CM
Unit: 3
RDU: 1
Group: 2
Pumped Refrigerant System Piping Diagram
Cooling
modules
Chilled water
supply
na3346a
RDU
Item Description
Item Description
Sight glass
Filter dryer
Refrigerant pump output temperature sensor
!
Liquid level sensor
Check valves
"
Refrigerant HXGR output temperature sensor
Refrigerant pump 2 output pressure sensor
#
Refrigerant HXGR output pressure sensor
Refrigerant pump 1 output pressure sensor
$
Condenser
Isolation valves
%
Refrigerant HXGR input temperature sensor
Pump 2
&
Two-way water ball valves
Pump 1
'
Leaving water temperature sensor
Refrigerant subcooler output temperature sensor
(
Entering water temperature sensor
Subcooler
ORD valve
Receiver
Pumped Refrigerant System Operation and Maintenance
11
OA Piping Diagram
Supply air
To RDU
na3386a
From RDU
Return air
Item
12
Description
Item
Description
Supply air temperature sensors
Solenoid valve
Micro-channel coil
Supply liquid temperature sensor
Fans
Refrigerant liquid pressure sensor
Return air temperature sensors
Evaporator pressure regulator (EPR)
Electronic expansion valve (EEV)
Refrigerant vapor pressure sensor
Remote rack inlet temperature sensor
Return vapor temperature sensor
Pumped Refrigerant System Operation and Maintenance
RA Piping Diagram
To RDU
From RDU
7/8'’
ACR
1 1/8'’
ACR
Supply Air
na3391a
Return Air
Item
Description
Item
Description
Fan
Return air temperature sensors
Micro-channel coil
Solenoid valve
Return vapor temperature sensor
Refrigerant liquid pressure sensor
Refrigerant vapor pressure sensor
Supply liquid temperature sensor
Evaporator pressure regulator (EPR)
Electronic expansion valve (EEV)
Service port
Rotalock adapter
Remote rack inlet temperature sensor
!
Supply air temperature sensors
Pumped Refrigerant System Operation and Maintenance
13
Display Interface
The display interface in the RDU also displays information pertinent to itself and to other system
components. OAs, RAs, and other Cooling Modules are identified as CMs on the display interface
screens.
Status
Check
Log
ESC
?
Warning
na3093a
Critical
14
Item
Description
Function
Critical Alarm LED (red)
When lit, a critical alarm condition exists and requires
your immediate attention.
Warning Alarm LED (yellow)
When lit, a warning alarm condition exists. Failure to
correct this condition could cause a critical alarm.
Check Log LED (yellow)
When lit, at least one new event has been logged
since the last time the log was checked. Only events
that pertain to the operation of the RDU or cooling
modules in the group will activate the LED.
Status LED (green)
When lit, the RDU is receiving electrical power.
When flashing green, the RDU is downloading
firmware for the controller. This may take several
minutes.
Liquid Crystal Display (LCD)
View alarms, status data, context-sensitive help, and
modify configurable items.
Up and down arrow keys
Select menu items and access information.
ESC key
Return to previous screen or cancel current operation.
Enter key
Open menu items and input changes to cooling group
level and cooling unit level settings.
Help key
Display context-sensitive help. Press the help key for
information about each option on the screen and for
instructions on performing tasks.
Pumped Refrigerant System Operation and Maintenance
Using the Display
Every time you apply power to the cooling unit, the display interface initializes, causing the LEDs to
cycle and the alarm-tone to activate.
Scrolling status screens
After start-up, the interface displays the firmware revision number of the display interface. The display
interface then scrolls automatically and continuously through screens of status information.
Status Screen Name
Status Information Displayed
System Status
• Alarms Present
• IP: xxx.xxx.xxx.xxx
• Date/Time
RDU
• On/Standby
• RDU ID (Unit identifier)
• Name
• Loc (RDU location)
CM ID
• CM ID
• Cool Out 15 kW
• Cool Setpt (Setpoint): 22°C (or 71.9°F)
• Rack Inlet: 23°C (or 73.7°F)
Press the up or down arrow key to interrupt the automatic scrolling and view a specific status screen. To
return to the scrolling status screens, press ESC from one of the main menu screens.
Main menu screens
On any top-level status screen, press the ENTER or ESC key to open the first
main menu screen.
For information on setting the time-out duration,
see.“Password and timeout” on page 30
All main menu choices are displayed on a series of main menu screens, as
shown.
Operate
Groups
RDU
Cooling Modules
CMs in Network
View Alarms
Clear Alarms
View Event Log
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
Set Display Unit
Configure Display
Configure Network
Set Identification
Pumped Refrigerant System Operation and Maintenance
na3119a
Note: Once a period of inactivity (at the keys of the display
interface) exceeds the Password Timeout setting, the display
interface returns to the scrolling status screens.
15
Navigating the screens
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
na1623d
Selector arrow. Press the up or down arrow key to move the selector arrow to a menu option. Press
the ENTER key to view the selected sub-menu screen. In the example shown below, the selector arrow
points to the Set Date and Time setting. To select that item, press the ENTER key.
Note: If the selector arrow is on the top line of a main menu screen, press the up arrow key to
move the selector arrow to the top line of the previous screen.
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
na1623b
Continue arrows. Continue arrows indicate that additional options or settings are available on a
menu or status screen. Press the up or down arrow key to view the additional items.
Sub-menus
Time: 13:15:23
Date: 18-Nov-2010
Format: dd/mm/yyyy
na1623c
Selecting a main menu option displays the sub-menu screen for that option. In this example, the selector
arrow is on the top line of the Set Date and Time sub-menu screen.
Use the up or down arrow key to move the selector arrow to an option, and press the ENTER key.
• List of choices. If the setting is a list of choices, an input arrow displays next to the setting.
Press the up or down arrow key to select the menu option to change. Then press the ENTER key to
exit the input mode and save the setting. Press the ESC key to exit without saving.
• Numbers or text fields. If the setting is a number or text field, use the arrow keys to select the
value of the first character, and press the ENTER key to move to the next character. Press the ENTER
key after the last character is set to exit the input mode and save the setting. Press the ESC key to
exit without saving. If an invalid value is entered, the display interface beeps and restores the
previous valid value to the field.
Time: 13:15:23
Date: 18-Nov-2010
Format: dd/mm/yyyy
16
na1622a
Input arrows. Input arrows next to a selected setting indicate that the setting can be modified by
pressing the up or down arrow key. Press the ENTER key to save the change or the ESC key to cancel the
change.
Pumped Refrigerant System Operation and Maintenance
Using the Path statement
Select the main- and sub-menu options specified in the path statement to view or configure a setting. The
path statement lists the main- and sub-menu items you select to navigate to the item to view or modify.
The parts of the path statement are defined below:
Path: Main > Set Password > Change Passwords
Main >Your starting point is the main menu.
Set Password > Scroll to and select this option from the main menu.
Change Passwords > Scroll to and select this option from the sub-menu.
Subsequent options are listed and defined under the path statement.
Password entry
The cooling unit has two levels of password protection:
Device password. Allows Device Users to change basic and environmental settings.
Admin password. Allows all privileges granted for Device Users, and also allows the Administrator to
modify settings that control the components in the RDU or CMs in the group or change advanced
options.
When you try to change a setting, the display interface prompts you to enter your Admin password. The
default value for both the Device and Admin password is apc (lowercase). To enter your password, use
the up or down arrow key to scroll through the available character set. Press the ENTER key to select the
current character and move the cursor to the next character position. After selecting the last character of
your password, press the ENTER key once more to submit your password.
Once the password is entered, it remains in effect until the period of inactivity exceeds the Password
Timeout setting.
See “Password and timeout” on page 1.
Note: Passwords are case-sensitive.
Invalidate NOW. Selecting this option will cause a logout immediately from either Admin or Device
and the user must login again with the appropriate password to gain access.
Pumped Refrigerant System Operation and Maintenance
17
Start the RDU
Path: Main > Operate > Operate
To start the RDU, Select On. The pumps will start when the pump starting conditions are met. There
must be a refrigerant reserve of at least 20% in the receiver. The Subcooler Outlet Temperature must be
less than or equal to 55°F and the Subcooler Outlet Temperature must be at least 0.3°F cooler than the
Condensing Temperature.
The RDU will run according to the configured settings.
Note: Operate only affects the local RDU. You must set the Operate option for each RDU in
the group.
Stop the RDU
Path: Main > Operate > Operate
Select Standby. The RDU will enter the standby mode and the CMs associated with the RDU will shut
down. This is not an alarm condition.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The Standby option does not remove power from the RDU. You must
disconnect power at the mains to remove power from the RDU.
Failure to follow these instructions can result in death or serious injury.
Start a CM Remotely
Path: Main > Cooling Modules > Select CM > Operate
To start the CM, select On.
Note: The CMs Local On/Off setting must be set to On for the CM to operate. Additionally,
the CM will not operate until the RDU has started the pump.
Stop a CM Remotely
Path: Main > Cooling Modules > Select CM > Operate
To stop the CM, select Standby.
18
Pumped Refrigerant System Operation and Maintenance
General Configuration
The configuration options are set during the commissioning of the RDU(s) and cooling modules (CMs)
in the group.
CAUTION
HAZARD TO EQUIPMENT OR PERSONNEL
All work must be performed by American Power Conversion (APC®) by Schnieder Electric
authorized personnel.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Note: The Admin Password is required before configuration changes can be entered.
RDU configuration
Path: Main > RDU > Configuration
RDU ID. Enter an identifier number for the RDU.
Start-up Dly. Enter a value for the delay. The start-up delay begins when the unit is started and
initialized. The RDU cannot begin operation until this delay expires. Use the start-up delay to restart
equipment sequentially after a scheduled downtime or a power outage.
Pump Changeover. The accumulated runtime before the pump is switched over to the lag pump. Enter
a value for the Pump Rotation Time in Days. If set to zero, the function is disabled.
Stop On Leak. When set to Yes, the RDU will stop if a Water Detection Fault activates. Set to No to
disable the RDU from stopping if a leak is detected.
Note: The leak sensor (APC part number AP9325) is optional.
Note: There are several alarms that will cause the cooling unit to enter Stop mode:
• Water Detection Fault (when Stop On Leak is set to Yes)
• Persistent Receiver Pumped Dry
• Pump 1 Fault (must occur with Pump 2 fault to initiate Stop mode.)
• Pump 2 Fault (must occur with Pump 1 fault to initiate Stop mode.)
• Persistent Pumps Vapor Locked
See “Alarm messages and suggested actions” on page 1 for more information on alarms.
Pumped Refrigerant System Operation and Maintenance
19
Power Source. The RDU has two AC inputs. One input is redundant. When Dual Feed is selected, an
alarm will initiate if either of the AC inputs fails. If only one feed is used, select Single Feed.
Fluid Temp High Thres. Fluid Temperature High Threshold: configure the entering fluid temperature
high threshold. An alarm will initiate when the inlet water temperature exceeds the threshold.
Bypass Mode. Enable/Disable. Select Enable to operate the Bypass Valve.
Reset Options. Run Hours: resets the run hours for the two pumps or the two DC power supplies.
Pump Fault: clears a pump fault. Pump Fault must be selected to remove a Pump Fault Alarm.
Unassign RDU. Removes the RDU from the group. Any CMs associated to the unassigned RDU will
also become unassigned.
RefrigLeak Enable. Enable or disable refrigerant leak detection. When enabled, a Critical alarm will
alert you if a loss is detected. A Warning alarm will alert you if leak detection is suspended. Leak
monitoring will continue as long as the RDU is ON, the configuration of the system has not changed, and
the total system load exceeds 3 kW.
Refrigerant Cal. Calibrates the refrigerant leak detector. The refrigerant leak detector must be
calibrated before use. Additionally, the refrigerant leak detector function must be Enabled before it can
be calibrated. See “RefLeak” on page 1 for information on Calibration Status settings. The RDU and
CMs must be ON with a minimum system load of 5kW. When calibration is complete the leak detector
will automatically start leak monitoring.
Calibrate:
• following the addition or removal of CMs.
• anytime refrigerant is added to the system.
Lead Pump. Assigns the lead pump of the two refrigerant pumps in the RDU. When the pump rotation
time is reached, the RDU will change the assignment of Lead Pump to the lag pump. See “Pump
Changeover” on page 1 to set up pump rotation time.
View and edit the state of input and output contacts:
Input Normal State. Set the normal state of the contact (open or closed). The RDU changes its
operating mode to Standby when the actual state differs from the normal state.
Output Source. Define the type of output source (alarm), either Any Alarm or Critical, that causes the
output to change from its normal state.
Output Normal State. Set the normal state of the contact (open or closed). If the state of an alarm or
event mapped to this contact changes from the normal state, the contact also changes state.
Reboot the Network Management Card.
Path: Main > RDU > Configuration > ResetOptions
Reset NMC. The NMC is rebooted. This is done without interrupting the operation of the pumped
refrigerant system. You will be prompted for a confirmation (Yes/No).
20
Pumped Refrigerant System Operation and Maintenance
CM Configuration
Path: Main > Cooling Modules > Select CM > Configuration > Parameters
Startup Dly. Enter a value for the delay. The startup delay begins when the unit is started and initialized.
The CM cannot begin operation until this delay expires. Use the startup delay to restart equipment
sequentially after a scheduled downtime or a power outage.
Power Source. The CM has two AC inputs. One input is redundant. When Dual Feed is selected, an
alarm will initiate if either of the AC inputs fails. If only one feed is used, select Single Feed.
Disp On Off. Enables/Disables the On/Off control on the local display of the CM.
Stop Cool Fail. If enabled, the unit will shut down if a Cool Fail condition is detected. Cool Fail is a
condition where the difference between the supply air temperature of the CMs and 90°F integrated over
time exceeds 300 seconds, given that the difference is positive and the power output of the CMs is less
than 4 kW.
Pumped Refrigerant System Operation and Maintenance
21
Identify the cooling modules
Path: Main > CMs In Network > Unconfigured CMs
To add an unconfigured CM to the group: Physically note on paper the temporary ID number as it
appears on the display of the CM once power is applied.
Bring the note with the number back to the RDU and proceed to configure the CM using the temporary
ID number to identify the CM from the list that appears on the RDU display interface.
Note: Be careful to add only CMs that are physically piped to the RDU. Do not add CMs that
are piped to other RDUs.
Note: Name the CM according to the three digit protocol:
• First digit is the RDU #
• Second digit is the Group #
• Third digit is the CM #
If there are unassigned CMs, the screen will show a list of the CMs by identification number. To assign a
CM to the group, select the CM. You must enter the Admin Password to continue to the next screen.
RDU ID. The unique identification number of the RDU. Range: 1 through 4. This value is used to
identify the RDU from which CMs will receive refrigerant from the RDU.
Group #. Use the up and down arrow buttons to scroll to the group number you want.
Range: 1 through 15. This value is used to identify which CMs are to operate as a group.
CM #. Use the up and down arrow buttons to scroll to the number you want to associate to the CM you
are adding. Range: 1 through 15. The value selected uniquely identifies a CM within a set of CMs having
the same RDU ID and Group # parameters.
Assign CM. Selecting Assign CM opens the next screen. Select Yes to add the CM to the group.
Pool Empty. If this screen appears when you select Unconfigured CM, there are no unassigned CMs.
22
Pumped Refrigerant System Operation and Maintenance
Group Configuration
Group settings determine which modules are available in each group and how the groups should operate.
CAUTION
HAZARD TO EQUIPMENT OR PERSONNEL
All work must be performed by American Power Conversion (APC®) by Schnieder Electric
authorized personnel.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Modify a Cooling Module (CM) ID
Path: Main > Cooling Modules > Select CM > Configuration > Modify CM ID
RDU ID. The unique identification number of the RDU.
Group #. Select a new Group number.
CM #. Select a new CM number.
Assign CM. Select to apply the changes to the selected CM. Once selected, the confirmation screen
comes up. Select Yes or No.
View the groups
Path: Main > Groups
Select Group. Select the group you want to view.
CM List. From the group number you selected, you can view the CMs by ID number.
Number of Units. Select the number of CMs you expect to be in the group. The Group
Communications Loss alarm is initiated if the CMs detect less or more CMs than this value.
Unassign CMs
Two menu paths are available to unassign cooling modules.
1. From this menu, select the CM ID to unassign. Press the ENTER key and Select Yes.
Path: Main > CMs in Network > All Assigned CMs
2. From this menu, press the ENTER key and select.
Path: Main > Cooling Modules > Select CM > Configuration > Unassign CM
Configure Modbus
Path: Main > Configure Modbus
Modbus. Enable or Disable the Modbus communication protocol.
Target Id. Each Modbus device must have a unique target identification number. Enter a unique number
from 1 to 247 for the RDU.
Baud Rate. 9600 bps.
Pumped Refrigerant System Operation and Maintenance
23
Control the Environment
The primary function of the Pumped Refrigerant System is to capture the heat generated by IT
equipment and neutralize it before it mixes with the room air.
Controls in the RDU monitor room conditions to ensure the leaving refrigerant temperature to the CMs is
always above the room dew point.
In a HACS or RACS environment, the CMs neutralize the heat accumulated in the common hot aisle and
expel it into the surrounding environmental space at the desired temperature.
Path: Main > Groups > Select Group > Setpoints
A setpoint is the target value that a cooling group tries to maintain. The default setpoints are appropriate
for most cooling applications.
The setpoints for each mode must be within the following ranges:
Cool Stpt. 22.2°C (66 - 90°F) This setting is only available in InRow mode.
Supply Stpt. 17.8–29.4°C (64.0–84.9°F)
Note: The Supply Stpt setting is defined by APC authorized personnel only when the group is
commissioned.
Note: The Supply Stpt setting must never be set higher than the Cool setpoint.
Fan Speed. When the CM is programmed for HACS or RACS mode and Air Flow is set to Auto, the
Air Flow property specifies the desired temperature difference (dT) across the IT equipment.
When the CM is programmed for InRow, HACS or RACS with Air Flow set to Manual, select the Fan
Speed from the following options.
• Low: 16.7°C (30°F) DT (60% of maximum fan speed)
• Med-Low: 13.9°C (25°F) DT (70% of maximum fan speed)
• Med: 11.1°C (20°F) DT (80% of maximum fan speed)
• Med-High: 6.3°C (15°F) DT (90% of maximum fan speed)
• High: 5.6°C (10°F) DT (100% of maximum fan speed)
The Fan Speed setting is ignored when the CM is set to the InRow mode and Air Flow is set to Auto.
24
Pumped Refrigerant System Operation and Maintenance
Air Flow. Manual/Auto (RA only)
Cfg Type. Select the cooling configuration from the following options:
• In-Row: The air flow is not ducted. The hot-aisle air is cooled and the cooled-air supply is shared
by all loads in the row.
• RACS (Rack Air Containment System): Air flow in the enclosure is controlled by a ducting
system fitted to the enclosure.
• HACS (Hot Aisle Containment System): Air flow in the room is controlled by enclosing the hot
air aisle. The loads share an enclosed common hot aisle.
Light On Time. The number of minutes the task lights will remain on after movement is
detected. (OA only)
Dsp Units. US/Metric
Measurements
Path: Main > Groups > Select Group > Measurements
View sensor readings from the CMs as a combined average from the display interface of the RDU.
Cool Output. Capacity output in kW.
Avg Sply Air. The combined average supply air temperature of all CMs in the group in °C (°F).
Avg Ret Air. The combined average return air temperature of all the CMs in the group displayed
in °C (°F).
Avg Fan. The combined average fan speed of all the CMs in the group displayed in percent of full scale
(0 - 100%).
Airflow - Avg CFM. The combined average cubic feet per minute (CFM) of air flow that the CMs are
creating.
Total CFM. The combined total CFM of all CMs in the group.
Pumped Refrigerant System Operation and Maintenance
25
Group PIDs
Path: Main > Groups > Select Group
Set Cool PID. Tune the Rack Inlet Temperature Controller. (InRow mode only)
Reset to Defaults. Resets to the default settings.
The Proportional plus Integral plus Derivative (PID) loop controls the output of the fans.
NOTICE
HAZARD TO EQUIPMENT
This procedure is to be performed by APC authorized personnel only. Improperly set PID
controls could result in equipment damage.
Failure to follow these instructions can result in equipment damage.
Gain (P). The proportional multiplier (gain) for this mode or actuator. The proportional multiplier
adjusts for the difference (error) between the measured value and the setpoint.
Rate (I). The integral multiplier (reset rate) for this mode or actuator. The integral multiplier adjusts for
error measurement and the amount of time that the error has existed. The integral multiplier adds to or
subtracts from the output in small increments to correct for the offset error caused by the proportional
contribution.
Deriv (D). The derivative multiplier (derivative) for this mode or actuator. The derivative multiplier
adjusts the output for rapid changes in the error, correcting for the rate of change of the error.
26
Pumped Refrigerant System Operation and Maintenance
Tune the PID loop
Tune the PID loop to optimize the performance of the cooling group.
NOTICE
HAZARD TO EQUIPMENT
This procedure is to be performed by APC authorized personnel only. The PID loop must
be tuned after the equipment in the room is installed and running.
Failure to follow these instructions can result in equipment damage.
Note: The PID loop should be tuned periodically to account for changes in the room load.
1. Adjust the integral and derivative constants to zero and the proportional constant to 1.0.
2. Set the temperature setpoint value and start the cooling group.
3. When the temperature reaches a stable value, increase the proportional constant by 0.5. If the
temperature does not respond to this change, adjust the setpoint.
4. Repeat step 3 until the temperature value starts to oscillate and the peak amplitude of the
oscillations is constant.
5. Note the time, in minutes, between the peaks of the oscillations. This is the Ultimate Period, PU.
6. Note the value of the proportional constant. This is the Ultimate Gain, GU.
7. Compute the PID constants using the table below. Use the equations for that control method in
the row to compute the values for each constant.
Control Method
Proportional
Integral
Derivative
P
0.5*GU
–
–
P+I
0.45*GU
0.54*GU /PU
–
P+I+D
0.6*GU
1.2*GU/PU
0.075*GU *PU
8. Set each constant according to these calculations.
Pumped Refrigerant System Operation and Maintenance
27
Further tune the PID loop in the following ways to account for changes in the room load:
Loop Behavior
PID Tuning Correction
Slow response to temperature changes
Increase the proportional multiplier or increase the derivative
multiplier.
Increase the derivative or the proportional multiplier.
Overcooling/undercooling after changes in the
room load or changes in setpoint
Environmental temperature never reaches the
setpoint
Overcooling/undercooling on constant room load
Increase the integral multiplier.
Decrease the integral multiplier.
RDU (component) run hours
The RDU records the number of hours each of its components has operated. When a component is
replaced, use the Reset Run Hours option to reset the run hours for the displayed component to zero.
Path: Main > RDU > Status > Run Hours
Run Hours. View the run hours for the Refrigerations Pumps (1 and 2) and for the DC Power Supplies
(1 and 2).
Reset RDU run hours
Path: Main > RDU > Configuration > Reset Options > Run Hours
Reset Run Hrs. Reset the run hours for the Refrigerations Pumps (1 and 2) and for the DC Power
Supplies (1 and 2) when one of these components is replaced.
CM (component) run hours
Path: Main > Cooling Modules > Select CM > Status > Run Hours
Run Hrs. View the run hours for the fans and fan air filters (RA only of the selected CM).
Reset CM run hours
Path: Main > Cooling Modules > Select CM > Configuration > Reset Run Hours
Reset Run Hrs. Reset the run hours for the fans and fan air filters (RA only) of the selected CM after
they are replaced.
Thresholds
Set alarms to alert you to threshold violations.
Path: Main > Cooling Modules > Select CM > Configuration > Alarm Threshlds
When the monitored input violates the set temperature threshold of the CM, an alarm will occur. Set
thresholds for the following sensors:
Rack Inlet. The temperature of the air entering the rack at the rack inlet sensor.
Supply Air. The average temperature of the air output from the CM, measured by the supply air
temperature sensors.
Return Air. The temperature of the air entering the CM at the return temperature sensors.
28
Pumped Refrigerant System Operation and Maintenance
Service intervals
Path: Main >Cooling Modules > Select CM > Configuration > Service Intervals
The service interval depends on environmental cleanliness. Each component interval setting has an
alarm. If enabled, the alarm will sound when the interval has elapsed. The alarm is cleared by selecting
Clear Alarms in the main menu. Set the number of weeks to service the following:
Air Filter Maintenance Interval. (Only displays for CMs with air filters.) The default is 18 weeks.
Alarm > Select > Enabled/Disabled
Note: The CM Air Filter interval alarm is enabled by default.
Pumped Refrigerant System Operation and Maintenance
29
Display Settings
Set display interface settings, including time and date, units of measure, passwords, and time-out
settings. You can also adjust the contrast, key click, beeper volume, and beep on alarm settings.
Password and timeout
Path: Main > Set Password
Note: The default user password is apc (lowercase). See “Password entry” on page 1 for more
information on how to enter the password.
Change passwords. Set the Admin and Device passwords.
1. Move the selector arrow next to the Change Passwords option and press the ENTER key.
2. Select the password to change (either Admin or Device).
3. Enter a new password (up to 8 characters).
4. Press the ENTER key to confirm.
Timeout. Set the length of time which can elapse when no keys are pressed before the display interface
returns to the scrolling screen status. The password must then be entered to regain access.
Invalidate. Override the password timeout and require password entry immediately.
Date and time
Path: Main > Set Date & Time
Set the time. Enter the correct time, and press the ENTER key. The Time is displayed on some status
screens and is also used in the alarm and event logs to time-stamp events
Set the date. Enter the day, month, and year, and press the ENTER key. The Date is displayed on some
status screens and is also used in the alarm and event logs to date-stamp events.
Set the format. Use the up or down arrow key to select the date Format setting.
• mm/dd/yyyy (11/16/2009) (Default)
• yyyy-mm-dd (2009-11-16)
• dd-mmm-yy (16-Nov-09)
• mmm-dd-yy (Nov-16-09)
• dd.mm.yyyy (16.11.2009)
Identify the RDU by Name and Location
Path: Main > Set Identification
User Defined Name. Use this to identify the unit by giving the unit a name.
User Defined Loc. Use this to identify the unit by its location.
30
Pumped Refrigerant System Operation and Maintenance
Adjust display
Path: Main Menu > Configure Display
Contrast. Adjust the visibility of the screen text. Lower numbered settings provide darker text; higher
numbers provide lighter text. Settings range from 0–7.
Key Click. Enable or disable an audible tone that will sound every time a key is pressed on the display
interface.
Beeper Volume. Set the volume of the display interface alarm tone, and for the audible tone that sounds
every time a key is pressed on the display interface.
Beep On Alarm. Set the cooling unit to sound an audible tone every 30 seconds when a new alarm
occurs. Silence the audible tone by pressing any key on the display interface. When the alarm clears
itself, the tone will stop on its own.
Display units
Path: Main Menu > Set Display Units
Set the units of measure for the cooling unit to either US or Metric.
Pumped Refrigerant System Operation and Maintenance
31
Network Configuration
The RDU is shipped with a Network Management Card that enables you to manage the RDU and
attached CMs over your network. Configure the network settings for the Rack PDU Network
Management Card from the display interface. The management card allows remote control and
configuration of the equipment.
Configure the network
Path: Main > Configure Network
MAC Address. Displays the unique network identifier assigned to the Network Management Card of
the RDU at the factory.
IP Address. You will be prompted to enter an Admin password. Enter the password and press ENTER to
return to the IP screen. Press ENTER again to change the following settings for Manual boot mode only.
• IP: Enter the IP address assigned to the Network Management Card of the cooling unit.
• SM: Enter the subnet mask for the Network Management Card of the cooling unit.
• GW: Enter the default gateway for the Network Management Card of the cooling unit.
Boot Mode. Set the method by which the Network Management Card of the RDU will acquire its
network settings.
• Manual: Enter the IP Address, subnet mask, and default gateway using the IP Address menu.
• BOOTP: Set the Network Management Card of the unit to obtain its network settings from a
BOOTP server.
• DHCP: Set the Network Management Card of the unit to obtain its network settings from a
DHCP server.
By default, DHCP requires an APC cookie before it will accept an IP address. See
“DHCP” on page 1 for more information.
• BOOTPDHCP: Set the Network Management Card of the unit to search for its network settings
from either a BOOTP or a DHCP server.
32
Pumped Refrigerant System Operation and Maintenance
View Status Readings
The display interface has several options for viewing the status of the RDU, the CMs in the cooling
group either individually or as a group, and the environment being controlled. The status readings for the
cooling unit are available under the View Unit Status option in the main menu, and status readings for
the cooling group are available under the View Group Status option on the main menu or on the
scrolling status screens.
Scrolling status screens
When the display interface is idle, it scrolls through screens of status information. Press the up or down
arrow key to interrupt the automatic scrolling and view a specific status screen.
• Alarms Present: If any alarms are present they will display.
• IP: The IP address of the RDU.
• RDU: Displays the current operating status of the RDU.
• RDU ID: Display the unique ID for this RDU.
• User Defined Name: The selected name is displayed.
• User Defined Location: The selected location is displayed.
• CMID: Cooling Module ID.
• Cool Out: Output displayed in kW.
• Cool Stpt: Displayed in F or C.
• Rack Inlet: Displayed in F or C.
Status
Path: Main > RDU > Status > Overview
View information specific to this RDU.
Op Mode. The RDU is in one of the following modes:
• On: The RDU is pumping refrigerant to the CMs at the proper condensing temperature.
• Standby: The RDU is receiving power but not enabled for pumping.
• Stop: The RDU has stopped due to an unrecoverable condition.
For more information, see “Stop On Leak” on page 1.
Lead Pump. Specifies which refrigerant pump is operating presently, either Pump 1 or Pump 2.
RefLeak. Specifies Calibration Status as: Suspended, Calibrating, Operating, or Disable.
Path: Main > RDU > Status > Active TH Sensors
Displays a list of Temperature Humidity sensors by address, present in the system.
Pumped Refrigerant System Operation and Maintenance
33
Path: Main > RDU > Status > Measurements
Temperatures. The temperature at each of the sensors in the RDU.
• Water In: The temperature of the chilled water entering the RDU.
• Water Out: The temperature of the chilled water leaving the RDU.
• Condenser: The temperature of the refrigerant leaving the condenser.
• Dew Point: The temperature at which condensation will occur in the conditioned environment.
• Pump Outlet: The temperature of the refrigerant leaving the pump.
• SubCool Out: The temperature of the refrigerant leaving the sub-cooler (heat exchanger).
• Cond Outlet: The temperature of refrigerant leaving the heat exchanger.
• Cond Inlet: The temperature of refrigerant entering the heat exchanger.
Pressures. The pressure sensor readings.
• Cond Out: The pressure of refrigerant leaving the heat exchanger.
• Pump 1 Head: The difference between the outlet pressure and the inlet pressure of Pump 1.
• Pump 2 Head: The difference between the outlet pressure and the inlet pressure of Pump 2.
Speed and Volume. The sensor readings displayed as RPMs or percentage of total capacity.
• Pump 1: The speed of Pump 1 as a percentage of the total capacity.
• Pump 2: The speed of Pump 2 as a percentage of the total capacity.
• CW VLV: The volume of chilled water passing through the valve, expressed in percentage of
total capacity.
• BypassVlv Pos: The volume of chilled water passing through the bypass valve, expressed in the
percentage of the total capacity.
Power. View power usage expressed in Amps.
• DC Supply 1: The amount of current used by DC power supply 1.
• DC Supply 2: The amount of current used by DC power supply 2.
• Total DC PS: The amount of current used by both DC power supplies.
Contacts. View the state of input and output contacts.
• Input State: Open or Closed
• Output State: Open or Closed
34
Pumped Refrigerant System Operation and Maintenance
Path: Main > Cooling Modules > Select CM > Status > Overview
Temperature. The temperature at each of the sensors in the selected CM.
• Rack Inlet: The temperature of the air entering the rack at the remote temperature sensor.
• Supply Air: The average temperature of the air entering the CM as measured by the supply air
temperature sensors.
• Return Air: The average temperature of the air leaving the CM as measured by the return air
temperature sensors.
• Liquid In: The temperature of the pumped refrigerant entering the CM as measured by the liquid
refrigerant temperature sensor.
• Vapor Out: The temperature of the pumped refrigerant leaving the CM as measured by the vapor
refrigerant temperature sensor.
• Evaporator: The evaporation temperature of the refrigerant as it leaves the evaporator.
Pressures. The pressure sensor readings:
• Liquid In: The pressure of the pumped refrigerant entering the CM as measured by the liquid
refrigerant pressure transducer.
• Vapor Out: The pressure of the pumped refrigerant leaving the CM as measured by the vapor
refrigerant pressure transducer.
Valve Positions. The positions of the EEV and EPRV as expressed in a percentage of a full open
condition.
• EEV Pos: The current position of the Electronic Expansion Valve.
• EPRV Pos: The current position of the Electronic Pressure Regulator Valve.
Pumped Refrigerant System Operation and Maintenance
35
Cooling group status
Path: Main > View Group Status
View information about the group.
Max Rack. The highest rack temperature reported by any sensor.
Min Rack. The lowest rack temperature reported by any sensor.
Air Flow. The combined airflow output of the modules in the group.
Cool Output. The combined output of the group.
Cool Demand. The cooling output required to meet the current heat load of the conditioned space.
Cool Setpt. The temperature you set to maintain the room environment.
About the RDU
Path: Main > RDU > About
View identifying information that is helpful when obtaining service:
• RDU ID: Identifier of the RDU
• S/N: Serial number
• F/W: Controller firmware revision
• H/W: Hardware revision
• RDU APP: Application firmware version
• AOS Ver: APC OS firmware version
36
Pumped Refrigerant System Operation and Maintenance
Event Log
The event log saves status information and a message each time a change in the group is detected.
Alarms and events are recorded in the log and displayed on the active alarms screen. Status events
(informational) and system configuration changes are only displayed in the event log.
View event log
Path: Main > View Event Log
The event log keeps a record of all alarms and events. The screen displays the following:
• The name of the event.
• The time and date the event occurred.
Use the arrow keys to scroll through the list of events and display the date and time for each event.
Clear event log
Path: Main > Clear Event Log
A confirmation screen is displayed when you select this option. Enter the Admin password to erase the
log. Select YES to erase all of the events in the log. Select NO to return to the main screen.
Respond to Alarms
When an alarm is triggered, the unit alerts you through the display by the following methods:
• Active alarm screen entry on scrolling status screens
• LEDs on the front panel display
• An optional audible alarm every 30 seconds, if enabled
View active alarms
Path: Main > View Alarms
The View Alarms screen provides the number of alarms, the severity, and a brief description of the
alarm. Press the arrow keys to view the rest of the list.
Clear active alarms
Path: Main > Clear Alarms
A confirmation screen is displayed when you select this option. Enter the Admin password to clear the
alarm list. Select YES to clear all of the alarms in the list. Select NO to return to the main screen. If the
conditions that caused the alarm still exist, those conditions cause the alarm to be regenerated.
Pumped Refrigerant System Operation and Maintenance
37
Alarm messages and suggested actions
Alarm Message
Severity
Bypass Valve Actuator Fault Warning
CM Communication Fault
Critical
Condenser Inlet
Temperature Sensor Fault
Warning
Condenser Outlet Pressure Critical
Sensor Fault
Condenser Outlet
Temperature Sensor Fault
Critical
Condensing Temperature
High Violation
Warning
Condensing Temperature
Low Violation
Warning
CW Valve Actuator Fault
Critical
DC Power Supply 1 Fault
DC Power Supply 2 Fault
Discrete Input Abnormal
Entering Fluid Temperature
High Violation
Critical
Critical
Warning
Warning
Inlet Water Temperature
Sensor Fault
Low Refrigerant Level
Warning
Warning
No Redundant Pump
Warning
No Temperature/Humidity
Sensors Available
Critical
Outlet Water Temperature
Sensor Fault
Warning
Persistent Pumps Vapor
Locked
Critical
38
Action Required
• Verify the actuator is connected properly.
• Tighten the linkage screw on the actuator shaft.
• Confirm that the rotary switch is pointing toward the top of the cooling
unit when the valve in the fully closed position.
• For assistance, contact Technical Support.
• Verify that the power is ON to the Cooling Module.
• Contact Technical Support.
• Make sure the temperature sensor entering the heat exchanger is
connected and placed properly.
• Make sure the Condenser Inlet temperature threshold is set correctly in
the Sensor Measurements screen.
• If the problem persists, contact Technical Support.
• Make sure the pressure sensor leaving the heat exchanger is connected
and placed properly.
• If the problem persists, contact Technical Support.
• Make sure the temperature sensor leaving the heat exchanger is
connected and placed properly.
• If the problem persists, contact Technical Support.
• Verify that the chilled water temperature and flow is within
specifications.
• If the problem persists, contact Technical Support.
• Verify that the chilled water temperature and flow is within
specifications.
• If the problem persists, contact Technical Support.
• Verify the actuator is connected properly.
• Tighten the linkage screw on the actuator shaft.
• Confirm that the rotary switch is pointing toward the top of the cooling
unit when the valve is in the fully closed position.
• For assistance, contact Technical Support.
• Contact Technical Support.
• Contact Technical Support.
• Contact Technical Support.
• Verify that the temperature sensor is properly installed.
• Make sure the chiller is operating properly.
• If the problem persists, contact Technical Support.
• Make sure the temperature sensor is connected and placed properly.
• If the problem persists, contact Technical Support.
• Add necessary amount of refrigerant to maintain the minimum
refrigerant level in the receiver.
• There are other Pump Faults that must be resolved.
• If the problem persists, contact Technical Support.
• Make sure the sensors are connected and configured properly.
• Make sure the CAN terminators are installed
• Contact Technical Support.
• Make sure the sensor is connected properly.
• Make sure the Water Out temperature threshold is set correctly in the
Sensor Measurements screen.
• If the problem persists, contact Technical Support.
• Contact Technical Support
Pumped Refrigerant System Operation and Maintenance
Alarm Message
Severity
Persistent Receiver Pumped Critical
Dry
Primary Power Source
Failure
Warning
Secondary Power Source
Failure
Warning
Pump 1 Discharge Pressure
Sensor Fault
Pump 1 Fault
Pump 1 High Head Pressure
Pump 2 Discharge Pressure
Sensor Fault
Pump 2 Fault
Pump 2 High Head Pressure
Pumps Vapor Locked
Pump Outlet Temperature
Sensor Fault
RDU Communication Fault
Receiver Pumped Dry
Critical
Refrigerant Loss Detected
Critical
Refrigerant Loss Detection
Disabled
Warning
Starting Conditions Not
Satisfied
System Stop
Warning
Subcooler Outlet
Temperature Sensor Fault
Temperature/Humidity
Sensor Duplicate CAN
Address
Temperature/Humidity
Sensor N Added
Temperature/Humidity
Sensor N Removed
Warning
Warning
Warning
Critical
Warning
Warning
Warning
Warning
Critical
Warning
Critical
Warning
Action Required
• Verify that there is adequate refrigerant in the system.
• Verify that the Cooling Modules are functioning properly.
• If the problem persists, contact Technical Support.
• Ensure that the power source is connected properly and within
specifications.
• If the problem persists, contact Technical Support.
• Ensure that the power source is connected properly and within
specifications.
• If the problem persists, contact Technical Support.
• Make sure the pressure sensor is connected properly.
• If the problem persists, contact Technical Support.
• Contact Technical Support.
• Contact Technical Support.
• Make sure the pressure sensor is connected properly.
• If the problem persists, contact Technical Support.
• Contact Technical Support.
• Contact Technical Support.
• Contact Technical Support.
• Make sure the temperature sensor is connected properly.
• If the problem persists, contact Technical Support.
• Contact Technical Support.
• Verify that there is adequate refrigerant in the system. Add refrigerant if
necessary.
• If the problem persists, contact Technical Support.
• A refrigerant leak has been detected.
• Identify the source of the leak.
• Have the leak repaired and the refrigerant replaced.
• For assistance, contact Technical Support.
• At least one of the following conditions has occurred:
- Refrigerant was added to the system
- One or more CMs have been added or removed from the system.
- One or more CMs have been placed into Standby, Stop or Maint mode.
• If the change is permanent, the refrigerant leak detector must be
recalibrated.
• For assistance, contact Technical Support.
• Ensure the chilled water temperature is within specifications.
• If the problem persists, contact Technical Support.
• Check for other alarms (Water Leak Detected, Persistent Receiver
Pumped Dry, Pump Fault, Pumps Vapor Locked).
• If the problem persists, contact Technical Support.
• Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
• Inspect the DIP switches on the temperature/humidity sensors and
ensure that all the settings are unique.
Informational • Notification that the addition of the new sensor has been recognized by
the RDU.
Informational • Notification that the removal of the sensor has been recognized by the
RDU.
Pumped Refrigerant System Operation and Maintenance
39
Alarm Message
Severity
Action Required
Unit is in Maintenance
Mode
Water Leak Detected
Critical
• Service Technician may be troubleshooting the unit. To return the unit to
normal operation, reset the unit.
• Identify and isolate the source of the leak.
• For assistance, contact Technical Support.
• Identify and isolate the source of the leak.
• For assistance, contact Technical Support.
Water Leak Detected
Warning
40
Critical
Warning
Pumped Refrigerant System Operation and Maintenance
CM alarm messages
Alarm
Number
28
29
22
17
Alarm Message
Severity Action Required
Air Filter Service
Interval Expired (RA
only)
Evaporative Temperature
Below Dewpoint
Fan 1 Door Open (OA
only)
Fan 1 Fault
Warning • Clean or replace the air filter
• Reset the alarm.
Critical
• Contact Technical Support.
Critical
• Make sure the door is closed.
• Make sure the door interlock switch is connected properly.
• Make sure the fan door is fully closed.
• Make sure all intakes are clear of blockage.
• Make sure the fan housing is full installed in the locked position.
• If the problem persists, contact Technical Support.
• Make sure the fan housing is fully installed and in the locked
position.
• Make sure the fan is set to the correct voltage.
• If the problem persists, contact Technical Support.
• Make sure the door is closed.
• Make sure the door interlock switch is connected properly.
• Make sure the fan door is fully closed.
• Make sure all intakes are clear of blockage.
• Make sure the fan housing is full installed in the locked position.
• If the problem persists, contact Technical Support.
• Make sure the fan housing is fully installed and in the locked
position.
• Make sure the fan is set to the correct voltage.
• If the problem persists, contact Technical Support.
• Make sure all intakes are clear of blockage.
• Make sure the fan housing is full installed in the locked position.
• If the problem persists, contact Technical Support.
• Make sure all intakes are clear of blockage.
• Make sure the fan housing is full installed in the locked position.
• If the problem persists, contact Technical Support.
• Make sure all intakes are clear of blockage.
• Make sure the fan housing is full installed in the locked position.
• If the problem persists, contact Technical Support.
• Contact Technical Support.
• Confirm that the A-Link cables are connected properly to the ALink ports.
• Confirm that the A-Link network has terminators on the first and
the last units in the chain.
• Verify the number of cooling units in the group is correct.
• If the problem persists, contact Technical Support.
• Make sure the refrigerant supply pressure sensor is connected
properly.
• If the problem persists, contact Technical Support.
• Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
• Make sure the power source is connected properly and is within
specifications.
Warning
24
Fan 1 Missing or Wrong Critical
Type (OA only)
23
Fan 2 Door Open (OA
only)
Fan 2 Fault
18
Critical
Warning
25
Fan 2 Missing or Wrong Critical
Type (OA only)
19
Fan 3 Fault (RA Only)
Warning
20
Fan 4 Fault (RA Only)
Warning
21
Fan 5 Fault (RA Only)
Warning
27
13
Fan Type Not Configured Critical
Group Communication Warning
Fault
8
Liquid Inlet Pressure
Sensor Fault
Critical
5
Liquid Temperature
Sensor Fault
Primary Power Source
Failure
Critical
15
Warning
Pumped Refrigerant System Operation and Maintenance
41
Alarm
Number
31
16
32
7
10
30
11
0
1
2
12
3
4
33
35
36
37
38
42
Alarm Message
Severity Action Required
Primary Power Source
Overvoltage
Secondary Power Source
Failure
Secondary Power Source
Overvoltage
Rack Temperature
Sensor Fault
Rack Temperature High
Violation
Critical
• The input voltage is higher than the unit’s rated value. Connect the
unit to a properly rated voltage input.
Warning • Make sure the power source is connected properly and is within
specifications.
Critical • The input voltage is higher than the unit’s rated value. Connect the
unit to a properly rated voltage input.
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
Critical • Make sure the temperature sensor is connected properly.
• Make sure the Rack Inlet High Temperature threshold is set
correctly in the Thresholds screen.
• If the problem persists, contact Technical Support.
Critical • Confirm that the A-Link network has terminators on the first and
RDU Communications
Fault
the last units in the chain.
• Confirm that the A-Link cables are connected properly to the ALink ports.
• If the problem persists, contact Technical Support.
Return Air High
Warning • Make sure the sensor is connected properly.
Temperature Violation
• Make sure the Return Air High Temperature threshold is set
correctly in the Thresholds screen.
• If the problem persists, contact Technical Support.
Return Air Temperature Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
Sensor Fault
(Front - OA, Top - RA)
Return Air Temperature Critical • Make sure the sensor is connected properly.
Sensor Fault
• If the problem persists, contact Technical Support.
(Middle)
Return Air Temperature Critical • Make sure the sensor is connected properly.
Sensor Fault
• If the problem persists, contact Technical Support.
(Rear - OA, Bottom - RA)
Supply Air High
Warning • Make sure the sensor is connected properly.
Temperature Violation
• Make sure the Supply Air High Temperature threshold is set
correctly in the Thresholds screen.
• If the problem persists, contact Technical Support.
Supply Air Temperature Critical • Make sure the sensor is connected properly.
Sensor Fault
• If the problem persists, contact Technical Support.
(Front) OA only
Supply Air Temperature Critical • Make sure the sensor is connected properly.
Sensor Fault
• If the problem persists, contact Technical Support.
(Rear) OA only
Unit in Maintenance
Critical • Service Technician may be troubleshooting the unit. To return the
Mode
unit to normal operation, reset the unit.
Upper Supply
Critical • Make sure the sensor is connected properly.
Temperature 1 Fault
• If the problem persists, contact Technical Support.
Upper Supply
Critical • Make sure the sensor is connected properly.
Temperature 2 Fault
• If the problem persists, contact Technical Support.
Upper Supply
Critical • Make sure the sensor is connected properly.
Temperature 3 Fault
• If the problem persists, contact Technical Support.
Upper Supply
Critical • Make sure the sensor is connected properly.
Temperature 4 Fault
• If the problem persists, contact Technical Support.
Pumped Refrigerant System Operation and Maintenance
Alarm
Number
39
40
41
42
14
26
9
6
Alarm Message
Severity Action Required
Lower Supply
Temperature 1 Fault
Lower Supply
Temperature 2 Fault
Lower Supply
Temperature 3 Fault
Lower Supply
Temperature 4 Fault
Unit ID Needs
Configuration
Unit Personality Not
Configured
Vapor Outlet Pressure
Sensor Failure
Critical
Vapor Temperature
Sensor Fault
Critical
• Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
• Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
• Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
• Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
• Configure the unit through the display interface.
Critical
• Contact Technical Support.
Critical
Critical
Critical
Critical
• Make sure the refrigerant HXGR pressure sensor is connected
properly.
• If the problem persists, contact Technical Support.
Warning • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
Pumped Refrigerant System Operation and Maintenance
43
Network Management Card
Quick Configuration
Overview
Note: Disregard the procedures described in this chapter if you have APC InfraStruxure®
Central as part of your system. See the documentation for your device for more information.
You must configure the following TCP/IP settings before the RDU can operate on a network:
• IP address of the RDU
• Subnet mask
• Default gateway
Note: If a default gateway is unavailable, use the IP address of a computer that is located on
the same subnet as the RDU and that is usually running. The RDU uses the default gateway to
test the network when traffic is very light.
Note: Do not use the loopback address (127.0.0.1) as the default gateway address for the
RDU. It disables the card and requires you to reset the TCP/IP settings to their defaults using a
local serial login.
See “Watchdog Features” in the “Introduction” of the Rack PDU User’s Guide for more
information about the watchdog role of the default gateway.
TCP/IP configuration methods
Use one of the following methods to define the TCP/IP settings needed by the RDU:
• APC Device IP Configuration Wizard (See “APC Device IP Configuration Wizard” on page 1.)
• BOOTP or DHCP server (See “BOOTP and DHCP configuration” on page 1.)
• Networked computer (See “Local access to the command line interface” on page 1 or “Remote
access to the command line interface” on page 1.)
44
Pumped Refrigerant System Operation and Maintenance
APC Device IP Configuration Wizard
You can use the APC Device IP Configuration Wizard at a computer running Microsoft® Windows®
2000, Windows Server® 2003, or Windows XP to discover unconfigured RDUs and configure their basic
TCP/IP settings, one card at a time, over the network.
Note: Most software firewalls must be temporarily disabled for the Wizard to discover
unconfigured RDUs.
1. If autorun is enabled, the user interface of the CD starts when you insert the Utility CD into a
computer on your network. Otherwise, open the file contents.htm on the CD.
2. Select the Device IP Configuration Wizard from the main menu.
3. When the Wizard discovers the unconfigured RDU, follow the on-screen instructions.
Note: If you leave the option Start a Web browser when finished enabled, you can access
the RDU through your browser by using apc (the default) for both the user name and
password.
.ini file utility
You can use the .ini file export utility to export .ini file settings from configured RDUs to one or more
unconfigured RDUs. The utility and documentation are included on the Utility CD.
BOOTP and DHCP configuration
The default TCP/IP configuration setting, BOOTP & DHCP, assumes that a properly configured
BOOTP or DHCP server is available to provide TCP/IP settings to RDUs. The RDU first attempts to
discover a properly configured BOOTP server, and then a DHCP server. It repeats this pattern until it
discovers a BOOTP or DHCP server.
A user configuration (.ini) file can function as a BOOTP or DHCP boot file. For more
information, see the TCP/IP configuration section of the InRow RD User’s Guide, available
from the Utility CD or the APC Web site, www.apc.com.
If neither of these servers is available, see “APC Device IP Configuration Wizard” on page 1,
“Local access to the command line interface” on page 1, or “Remote access to the command
line interface” on page 1 to configure the needed TCP/IP settings.
BOOTP. For the Rack PDU to use a BOOTP server to configure its TCP/IP settings, it must find a
properly configured RFC951-compliant BOOTP server.
In the BOOTPTAB file of the BOOTP server, enter the RDU’s MAC address, IP address, subnet mask,
and default gateway, and, optionally, a bootup file name. Look for the MAC address on the bottom of the
RDU or on the Quality Assurance slip included in the package.
When the RDU reboots, the BOOTP server provides it with the TCP/IP settings.
• If you specified a bootup file name, the RDU attempts to transfer that file from the BOOTP server
using TFTP or FTP. The RDU assumes all settings specified in the bootup file.
• If you did not specify a bootup file name, you can configure the other settings of the RDU
remotely through its Web interface or command line interface; the user name and password are
both apc, by default.
To create a bootup file, see your BOOTP server documentation.
Pumped Refrigerant System Operation and Maintenance
45
DHCP. You can use an RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for
the RDU.
This section summarizes the RDU’s communication with a DHCP server. For more detail
about how a DHCP server can configure the network settings for a RDU, see “DHCP
Configuration” in the RDU User’s Guide on the Utility CD.
1. The RDU sends out a DHCP request that uses the following to identify itself:
– A Vendor Class Identifier (APC by default)
– A Client Identifier (by default, the MAC address of the RDU)
– A User Class Identifier (by default, the identification of the application firmware installed on
the RDU)
2. A properly configured DHCP server responds with a DHCP offer that includes all the settings
that the RDU needs for network communication. The DHCP offer also includes the Vendor
Specific Information option (DHCP option 43). By default, the RDU ignores DHCP offers that
do not encapsulate the APC cookie in DHCP option 43 using the following hexadecimal format:
Option 43 = 01 04 31 41 50 43
where:
– the first byte (01) is the code
– the second byte (04) is the length
– the remaining bytes (31 41 50 43) are the APC cookie.
See your DHCP server documentation to add code to the Vendor Specific Information option.
Note: To disable the requirement that a DHCP offer include the APC cookie, clear the check
box Require vendor specific cookie to accept DHCP Address in the Web interface:
Administration > Network>TCP/IP>DHCP. Alternately, at the command line interface, use
this command to disable the DHCP cookie requirement: boot -c disable
Local access to the command line interface. You can use a computer connected to the serial port
on the front of the RDU to access the command line interface.
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Use the provided serial cable (APC part number 940-0299) to connect the selected port to the
serial port on the front panel of the InRow RD.
3. Run a terminal program (such as HyperTerminal) and configure the selected port for 9600 bps, 8
data bits, no parity, 1 stop bit, and no flow control. Save the changes.
4. Press ENTER, repeatedly if necessary, to display the User Name prompt.
5. Use apc for the user name and password.
See “Command line interface” on page 1 to finish the configuration.
Remote access to the command line interface
From any computer on the same network as the RDU, you can use ARP and Ping to assign an IP address
to the RDU, and then use Telnet to access its command line interface and configure the other TCP/IP
settings.
46
Pumped Refrigerant System Operation and Maintenance
Note: After the RDU has its IP address configured, you can use Telnet, without first using
ARP and Ping, to access that RDU.
1. Use the MAC address of the RDU in the ARP command to define the IP address.
Note: Look for the MAC address on the back of the Network Management Card or on
the Quality Assurance slip included in the package (with the replacement Network
Management Card).
For example, to define 156.205.14.141 as the IP address of a RDU with 00 c0 b7 63 9f 67 as its
MAC address, use one of the following commands:
– Windows command format:
arp -s 156.205.14.141 00-c0-b7-63-9f-67
– LINUX command format:
arp -s 156.205.14.141 00:c0:b7:63:9f:67
2. Use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. For the
IP address defined in step 1, use one of the following commands:
– Windows command format:
ping 156.205.14.141 -l 113
– LINUX command format:
ping 156.205.14.141 -s 113
3. Use Telnet to access the RDU at its newly assigned IP address. For example:
telnet 156.205.14.141
4. Use apc for both user name and password.
See “Command line interface” on page 1 to finish the configuration.
Command line interface
After you log on at the command line interface, as described in “Local access to the command line
interface” on page 1 or “Remote access to the command line interface” on page 1, you can manually
configure network settings.
1. Contact your network administrator to obtain the IP address, subnet mask, and default gateway
for the RDU.
2. Use these three commands to configure network settings. (Text in italics indicates a variable.)
a. tcpip -i yourIPaddress
b. tcpip -s yourSubnetMask
c. tcpip -g yourDefaultGateway
For each variable, type a numeric value that has the format xxx.xxx.xxx.xxx.
For example, to set a system IP address of 156.205.14.141, type the following command and
press ENTER:
tcpip -i 156.205.14.141
3. Type exit. The RDU restarts to apply the changes.
Pumped Refrigerant System Operation and Maintenance
47
How to Recover from a Lost Password
You can use a local computer that connects to the RDU through the serial port to access the command
line interface.
1. Select a serial port at the local computer, and disable any service that uses that port.
2. The APC serial cable (not provided) is used to connect the console port at the RDU and to your
computer. (This cable is available to order from APC.)
3. Run a terminal program (such as HyperTerminal®) and configure the selected port for 9600 bps,
8 data bits, no parity, 1 stop bit, and no flow control.
4. Press ENTER, repeatedly if necessary, to display the User Name prompt. If you are unable to
display the User Name prompt, verify the following:
– The serial port is not in use by another application.
– The terminal settings are correct as specified in step 3.
– The correct cable is being used as specified in step 2.
5. Press the Reset button. The Status LED will flash alternately orange and green. Press the Reset
button a second time immediately while the LED is flashing to reset the user name and password
to their defaults temporarily.
Note: Pressing the Reset button will reboot the controller, causing a temporary loss of
cooling.
6. Press ENTER, repeatedly if necessary, to display the User Name prompt again, then use the
default, apc, for the user name and password. (If you take longer than 30 seconds to log on after
the User Name prompt is redisplayed, you must repeat step 5 and log on again.)
7. At the command line interface, use the following commands to change the User Name and
Password settings, both of which are now apc:
user -an yourAdministratorName
user -ap yourAdministratorPassword
For example, to change the Administrator user name to Admin, type:
user -an Admin
8. Type quit or exit to log off, reconnect any serial cable you disconnected, and restart any
service you disabled.
48
Pumped Refrigerant System Operation and Maintenance
CM Display
InRow
OA
STATUS
UNIT ID
LIGHTS
SUPPLY AIR
TEMP
WARNING
RACK INLET
TEMP
CRITICAL
ALARM
CODE
Cooling
System
na3132a
OA display
Item
Description
Infrared remote control receiver
Status LED
Lights LED
Warning LED
Critical alarm LED
Menu selection scroll up key
Enter key
Menu selection scroll down key
Alarm code LED
Rack inlet temperature LED
Supply air temperature LED
Unit ID LED
Motion sensor for lights
! Infrared remote control
RA display
Item Description
InRow RA
Warning LED
UNIT ID
SUPPLY AIR
TEMP
WARNING
RACK INLET
TEMP
CRITICAL
ALARM
CODE
Cooling System
na3392a
STATUS
Status LED
Critical alarm LED
Menu selection scroll up key
Enter key
Menu selection scroll down key
Alarm code LED
Rack inlet temperature LED
Pumped Refrigerant System Operation and Maintenance
49
Display Operation
The display scrolls automatically through the sensor readings and alarms from the items listed to the
right side of the display screen. To view information from the items listed to the left of the display
screen, press the ENTER key and use the up or down keys to move through the display.
All CMs have a three digit LED display. The capability of the display is limited to relaying sensor
readings, the identification number of the CM, and alarms by number only.
Alarm levels are indicated by the LEDs. See the display interface on the RDU for alarm descriptions or
for interactive ability.
The RDU comes with an infrared remote control which is used to operate the OAs. The remote has a
menu selection scroll up, scroll down, and enter key.
OAs (only) have a motion sensor to activate the lights.
Cooling Modules are powered on or off from the individual CM, not from the RDU.
Cooling On/Off. press the ENTER key on the display interface. The Status LED will illuminate. The
display interface will read On. Press the Enter key once more to turn cooling to Standby.
Disable On/Off lights. OA only. Press the ENTER key on the display interface. Press the Menu selection
Scroll Down key once. The Lights LED will illuminate. The display interface screen will read On. Press
the Enter key once more to turn the lights Off. The lights on that OA will remain off until the value is set
to On.
Warning LED. A Yellow LED will illuminate when Warning level alarms are initiated.
Critical LED. A Red LED will illuminate when Critical level alarms are initiated.
Note: 60 seconds following access of the features located from the left side of the display
screen (as facing the display) will elapse before the display will revert to scrolling through the
features located to the right of the display screen.
Unit ID. The Unit ID is the identifier given to the CM after it is installed in the system. The RDU uses
the unique number to identify and control the CM.
Supply Air Temp. The supply air temperature sensor reading. Centigrade or Fahrenheit display is
selected at the RDU.
Rack Inlet Air Temp. Rack inlet air temperature sensor reading. Centigrade or Fahrenheit display is
selected at the RDU.
Alarm Code. The Alarm Code number corresponds to the alarm codes listed in “CM alarm messages”
on page 1. Refer to the list to identify the alarm.
50
Pumped Refrigerant System Operation and Maintenance
Maintenance
Leak Detector
Calibration
The leak detection feature must be calibrated before it can be used.
Note: In order for calibration to successfully complete, the RDU and CMs must be on with a
minimum system load of 5 kW.
Path: Main > RDU > Status > Measurements
From the display interface, or BMS, start calibration from the above path.
Choose Calibrating to initiate the feature.
When Calibration is complete, the leak detector will automatically start leak monitoring.
Leak monitoring will continue as long as the RDU is on, the configuration of the system has not
changed, and the total system load exceeds 3 kW.
Note: Leak detection is Suspended and a Warning alarm will come on when:
1. Refrigerant is added to the system
2. CMs are added or removed from the system
3. CMs are placed into Standby, Evacuation, Stop, or Maintenance modes
Pumped Refrigerant System Operation and Maintenance
51
Monthly Preventive Maintenance
Photocopy the following pages and use them during the maintenance procedures. After they have been
completed, save them for future reference.
Prepared By: ________________________________
Model Number: ______________________________
Serial Number: _______________________________
Date: ______________________________________
Environment
q In what type of room is the equipment located?
__________________________________________________
q Is the equipment maintaining the temperature setpoint?
___________________________________________________
Temperature setpoint _________________________________
q Is there visible damage to the equipment (dents, scratches)?
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________
q Check for environmental damage (dirt, dust, debris, liquid stains) around the installation area.
____________________________________________________________________________________
____________________________________________________________________
q Record the room temperature near the returns of the cooling modules.
Temperature ________________
q Record the alarm history for the last month.
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________
Cleanliness
q Check the condition of the area around the unit. Clean if necessary.
q Check for accumulation of debris. Clean as required.
52
Pumped Refrigerant System Operation and Maintenance
Mechanical
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on the equipment. All electrical
work should be performed by licensed electricians. Practice lockout/tagout procedures.
Do not wear jewelry when working with electrical equipment.
Failure to follow these instructions can result in death or serious injury.
q Which refrigerant pump is operating? __________________________
– Pump 1 run hours: _______________________________
– Pump 2 run hours: _______________________________
q Record the refrigerant pump operating information.
– Pressure: _______________________________
– Speed: _________________________________
q Record the inlet and outlet temperatures for the heat exchanger.
– Inlet temperature: ________________________
– Outlet temperature: _______________________
Electrical
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on the equipment. All electrical
work should be performed by licensed electricians. Practice lockout/tagout procedures.
Do not wear jewelry when working with electrical equipment.
Failure to follow these instructions can result in death or serious injury.
q Inspect the electrical panel for tight connections and for overheated connections from loose contact
terminals.
q Confirm the incoming main voltage matches the equipment nameplate. The measurement should be within
10% of the nameplate listing.
Pumped Refrigerant System Operation and Maintenance
53
Quarterly Preventive Maintenance
* Perform all the Monthly Preventive Maintenance items and the items below.
Prepared By: _________________________________
Model Number: _______________________________
Serial Number: _______________________________
Date: ______________________________________
Mechanical
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on the equipment. All electrical
work should be performed by licensed electricians. Practice lockout/tagout procedures.
Do not wear jewelry when working with electrical equipment.
Failure to follow these instructions can result in death or serious injury.
q Clean the dust from door perforations.
Functional tests
q Verify the cooling operation mode is functioning properly.
Semi-Annual Preventive Maintenance
* Perform all the Monthly/Quarterly Preventive Maintenance items and the items below.
Prepared By: _________________________________
Model Number: _______________________________
Serial Number: _______________________________
Date: ______________________________________
Cleanliness
q Check the cleanliness of the unit. Clean if required.
54
Pumped Refrigerant System Operation and Maintenance
Troubleshooting
Problem
Possible Cause
Display interface not
• Display interface
operational, but
not connected
equipment operates
properly
Alarms do not show up • External
on monitoring equipment monitoring
equipment is not
(Customer Output
receiving power or
Contact)
is not functioning
properly
Equipment does not shut • Drive voltage
down on command
No communication with • Improper
building management
connection
system (BMS) port
Cooling modules are not • A-Link failure
communicating with the
RDU
Equipment does not shut • Drive voltage
down on command
No communication with • Improper
building management
connection
system (BMS) port
CMs are not
communicating with
each other
• A-Link failure
• Upper or lower
Output air is 17° C
(62° F) and CM fans are supply air sensor
running at a very high
rate of speed.
Corrective Action
• Verify that the display interface cable is connected properly.
• Confirm that power, if required, is being supplied to the external
equipment.
• If the RDU is providing power to the external equipment, verify that the
external equipment is <50 mA.
• Test the external equipment by bypassing the customer output contact.
• Verify that there is a drive voltage entering the input of the RDU. You
may use the +12 V or +24 V. You must also use the ground.
• Confirm that the RDU is connected to the BMS port and not to the
Control port.
• Make sure that the wire polarity is correct. Using a DC voltmeter, test the
signal with no transmissions in progress. Expect the voltage at pin 2 to
be greater than at pin 1 by at least 200 mV. Measure the RDU with the
cable disconnected, and then measure it again with the cable connected.
If the signal is less than 200 mV, the RDU may be reverse-wired.
• Make sure every CM has either two sets of wires on the connector or one
set of wires and a terminating resistor of 100 to 120 ohms.
• Verify that the first and last cooling modules have one cable and a
terminator.
• Verify that every other cooling module has two cables.
• Confirm that the A-Link cables are connected to the A-Link ports and
that a network cable is connected to the network port.
• Verify that the number of cooling modules in the cooling group matches
the group number setting.
• Verify that there is a drive voltage entering the input of the cooling unit.
You may use the available +12 V or +24 V. You must also use the
ground.
• Confirm that the RDU is connected to the BMS port and not to the
Control port.
• Make sure that the wire polarity is correct. Using a DC voltmeter, test the
signal with no transmissions in progress. Expect the voltage at pin 2 to
be greater than at pin 1 by at least 200 mV. Measure the RDU with the
cable disconnected, and then measure it again with the cable connected.
If the signal is less than 200 mV, the RDU may be reverse-wired.
• Make sure that every CM has either two sets of wires on the connector or
one set of wires and a terminating resistor of 100 to 120 ohms.
• Verify that the first and last CMs have one cable and a terminator.
• Verify that every other cooling module has two cables.
• Confirm that the A-Link cables are connected to the A-Link ports and
that a network cable is connected to the network port.
• Verify that the number of CMs in the cooling group matches the group
number setting.
• Either the upper or lower supply air temperature sensor has a fault.
Verify that both supply air temperature sensors are installed and working
properly.
Pumped Refrigerant System Operation and Maintenance
55
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer
support requests.
– www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer support
information.
– www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact the APC Customer Support Center by telephone or e-mail.
– Local, country-specific centers: go to www.apc.com/support/contact for contact information.
For information on how to obtain local customer support, contact the APC representative or other distributors
from whom you purchased your APC product.
© 2012 APC by Schneider Electric. APC, the APC logo, and InRow are owned by Schneider Electric
Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other
trademarks are property of their respective owners.
990-3421B-001
1/2012