PVI TempTrac Guide

Add to My manuals
30 Pages

advertisement

PVI TempTrac Guide | Manualzz

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

Installation and interface must be performed by a qualified controls technician.

IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND

CONFIGURATION OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL

OTHER PROVIDED INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING

THIS UNIT.

Contents

OVERVIEW OF INTERFACE METHODS: ................................................................................................. 2

TEMPTRAC PROTOCOL ........................................................................................................................... 4

ITEMS REQUIRED FOR GATEWAY INTERFACE: ................................................................................... 4

ITEMS REQUIRED FOR MODBUS DIRECT INTERACE: ......................................................................... 4

IDENTIFY EQUIPMENT: ............................................................................................................................. 5

WIRING BAS TO GATEWAY AND THEN GATEWAY TO TEMPTRAC: .................................................. 6

WIRING OF TEMPTRAC TO BAS (Direct, no Gateway): ........................................................................... 7

GATEWAY CONFIGURATION CONNECTION: ........................................................................................ 7

CONFIGURE GATEWAY DIP SWITCHES: ............................................................................................... 8

CONFIGURE THE GATEWAY USING THE HTML INTERFACE: ............................................................. 9

CONFIRM OPERATION: ........................................................................................................................... 10

TROUBLESHOOTING GATEWAY: .......................................................................................................... 10

HOOKUP OVERVIEW: .............................................................................................................................. 11

APPLICATION SPECIFICS: ...................................................................................................................... 12

POINTS LIST: ............................................................................................................................................ 16

TYPICAL POINTS: ..................................................................................................................................... 16

ALL POINTS INCLUDING ADVANCED: ................................................................................................... 18

ADVANCED MODBUS LIST: .................................................................................................................... 25

TO THE INSTALLER / CONTROLS INTEGRATOR: After installation and integration, these instructions must be given to the equipment user or left near the appliance.

SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain important integration information that will help you in maintaining and operating this appliance.

PVI INDUSTRIES, LLC - Fort Worth, Texas 76111 - Web www.pvi.com

- Phone 1-800-433-5654

Page 1 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

OVERVIEW OF INTERFACE METHODS:

This document is a quick reference for connecting the TempTrac water heater / boiler control to a Building

Automation System (BAS). Direct connection via MODBUS RTU or using a gateway to interface to protocols other than MODBUS RTU are the methods covered in this manual.

BAS to Heaters direct, using MODBUS RTU:

BAS

PVI WATER HEATERS

Other equipment

Building Automation System (BAS) connecting directly to water heaters using MODBUS RTU twisted pair wire. (Wiring is RS-485 physical layer.)

BAS to heaters using a Protocol Gateway:

BAS

PVI WATER HEATERS

GATEWAY

Other equipment

Building Automation System (BAS) connecting to a PVI gateway. This can provide interface to BACNET

MSTP, BACNET IP, LONWORKS, and MODBUS TCP.

(Wiring from gateway to heaters is RS-485 physical layer. Wiring from BAS to gateway will depend on

Protocol.)

BAS to heaters using discrete connections:

This is simply control of the heater using the external ENABLE/DISABLE contacts, remote equipment contacts and the alarm contacts. See wiring diagram of equipment for details.

Page 2 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

TempTrac Heater MODBUS fixed settings:

Most of the MODBUS RTU and Port settings are not adjustable

Baud Rate: 9600bps (Not adjustable)

Data Length: 8 bit (Not adjustable)

Parity: None (Not adjustable)

Stop Bits: 1 (Not adjustable)

Start/Stop: Silent interval of 3 characters minimum

Minimum Time Between Retry: 500 msec.

Maximum read command is 5 words

Steps to change the TempTrac MODBUS address:

Editing parameters should be done without any device trying to communicate through the MODBUS port.

To avoid interference from a gateway or BAS, you should unplug the MODBUS adapter port on the back of the TempTrac at the white header, while making changes to the TempTrac parameters.

The first step to interfacing with a TempTrac or group of TempTracs will be the assignment of the address number for each boiler. The default for TempTrac is Address #1. You can assign any number in the range of 1-247. This is the limitations of the MODBUS RTU standard.

The MODBUS address is the Adr parameter, and it is in the Pr2 menu.

Enter the Programming mode by pressing the SET and DOWN key for more than 3 seconds. (Lead with the SET key.)

Pressing the DOWN key, parameters will display in top, and value in bottom.

Select Pr2 / PAS (parameter / value), and press the SET key.

The lower display will show the value 0 - - with a flashing zero.

Use UP or DOWN keys to input the security code in the flashing digit; confirm each digit by pressing SET. The security code is 321.

After hitting SET on the last digit, you will be in the Pr2 menu.

Once you have entered the Pr2 menu press the DOWN key to move through the parameters until the Adr parameter appears on the top display.

Now press the SET key once and the value number will begin to blink. Use the arrow key to set the address and then hit the SET key.

After hitting the SET, it will automatically go to the next parameter. Let it time out, or cycle power to the TempTrac.

Each TempTrac on a RS-485 network must have a unique MODBUS address.

The TempTrac MODBUS adapter port:

The MODBUS adapter is an orange dongle with 2 green screw terminals attached to an 8 inch cable that plugs into the back of the TempTrac at a white header. This can be an option installed on heater, or it may be a separate line item part. When the option is available, it is MBUSC option code. As a standalone part, it is PN: 11807.

Page 3 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

TEMPTRAC PROTOCOL

The MODBUS RTU protocol is well established industry protocol and technical references for this are readily available on the Internet.

Data Types Used

The TempTrac only uses one data type

Holding Registers (40001

– 49999) Read/Write

Other data types such as Coils are not implemented in the TempTrac control.

Only the data points in the POINTS LIST should be accessed.

Physical Layer RS-485

MODBUS RTU uses the physical layer RS-485.

RS-485 (EIA-485): A 2 wire (twisted pair) multi drop network. Each device can send data by holding positive and negative voltage on the line and reversing polarity on the 2 wires. When no devices are transmitting, the line will be tristate. The recommended arrangement of the wires is as a connected series of point-topoint (multi-dropped) nodes, i.e. a line or bus, not a star, ring, or multiply connected network. The number of devices that can be connected to a single line is defined in the RS-485 standard by the input impedance of 32 UNIT LOADs. The wire and circuits interfacing on this 2 wire connection is considered the PHYSICAL

LAYER. (RS-485 is the same physical layer as used with BACNET MSTP.)

No provisions for biasing resistors or termination resistors are provided on the control. If required, this will need to be provided externally.

The PVI gateway does provide optional biasing (default) and can provide a termination resistor, if required.

ITEMS REQUIRED FOR GATEWAY INTERFACE:

One or more water heaters with a TempTrac control (red/orange LED display with 6 tactile buttons) including the RS-485 adapter.

Protonode Gateway with Power supply adapter (when ordering, please specify what protocol is required;

BACNET MSTP, BACNET IP, LONWORKS or MODBUS TCP).

Protonode Gateway Manual (Covers general information for the gateway).

PV7069-T.PDF Interface manual that covers specifics for interfacing with the TempTrac system. Also includes the points list for the TempTrac control system. (This document).

120VAC power outlet for the power supply.

Computer with web browser and Ethernet connection capability to configure gateway.

ITEMS REQUIRED FOR MODBUS DIRECT INTERACE:

One or more water heaters with a TempTrac control (red/orange LED display with 6 tactile buttons) including the RS-485 adapter.

PV7069-T.PDF Interface manual that covers specifics for interfacing with the TempTrac system. Also includes the points list for the TempTrac control system. (This document).

Page 4 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

IDENTIFY EQUIPMENT:

The equipment should have a TempTrac mounted on the control panel. The RS-485 adapter may be installed or may ship lose. The gateway and power supply ship lose. The gateway is a grey module that has a wall wart style power supply.

TempTrac back, showing adapter dongle.

TempTrac Front and side view

Protocol Gateway

TempTrac is mounted on the control panel of the equipment. On the back side of the TempTrac is a white header. The RS-485 adapter plugs into this with a 8 inch cable. The orange adapter has 2 green terminals labeled (+) & (-).

The Protocol Gateway, if supplied, comes with a power supply and ships as a loose item.

Page 5 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

WIRING BAS TO GATEWAY AND THEN GATEWAY TO TEMPTRAC:

Each gateway has 3 connection points.

The 6 position terminal block contains connection for power and MODBUS RTU (going to heaters).

The Ethernet port is for configuration, BACNET IP, or MODBUS TCP.

The 3 or 2 pin terminal is for the BAS interface: BACNET MSTP, or LONWORKS.

Power Connection:

Gateway power supply, 6 position terminal +PWR, -PWR.

Use supplied wall wart style power supply. 15VDC. Do not power other devices with same power supply.

If power adapter has not already been connected, cut and discard the connector on the end, strip and terminate the power adapter in the proper terminals. Verify polarity. If another supply is to be used, it must be isolated. Do not use 24VAC power from heater.

Gateway Connection to Heaters:

Wiring from Gateway to the heaters, use twisted pair wire.

Connector on the orange dongle adapter that is on the end of a 8” cable plugged into the back of the

TempTrac.

The wiring is standard 2 wire RS-485 wiring. You will connect all devices together in a daisy chain. We recommend the gateway to be at the start of this connection.

Gateway

6 Pos. terminal

TempTrac

Orange adapter

TempTrac #2

Orange adapter

Tx/+

Rx/-

GND

(+)

(-)

(+)

(-)

Building Automation Connection:

BAS protocol Connection Port on Gateway

BACNET MSTP 3 TERMINAL CONNECTOR

BACNET IP ETHERNET PORT

LONWORKS 2 TERMINAL CONNECTOR

MODBUS TCP ETHERNET PORT

Labeled

FIELD

ETHERNET

LonWorks

ETHERNET

Page 6 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

WIRING OF TEMPTRAC TO BAS (Direct, no Gateway):

The back side of the TempTrac has a white header with an 8 inch cable, connecting to an orange adapter module with 2 green terminals labeled (+) & (-). This is the RS-485 Modbus connection point.

Field connection for BAS

TempTrac

Orange adapter

TempTrac #2

Orange adapter

Testing

VDC

Results for proper hookup

RS 485 +

RS R85 -

GND

(+)

(-)

(+)

(-)

Positive lead

Negative lead

+ 0.100

To

+ 5.500

Ensure the proper polarity, check with a Digital Volt Meter set to Volts DC. Take a reading at the orange adapter from the (-) Terminal to the (+) Terminal. The (+) should be the positive lead when connected.

GATEWAY CONFIGURATION CONNECTION:

Both the LONWORKS and BACNET gateway have an Ethernet port. Connect the computer using a patch cable or cross-over cable to establish a direct connection to the gateway. Older units may require a crossover cable or two patch cables with an Ethernet switch. If using BACNET IP or MODBUS TCP interface, connect the BAS Ethernet cable to the gateway when configuration is complete.

At this point, each heater and the gateway should all be powered, and have all wiring finished. The RUN

LED will toggle every second to indicate the gateway is running.

Page 7 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

CONFIGURE GATEWAY DIP SWITCHES:

The ON position is toward the center of the module, and OFF is toward the edge of the module. Only the

BACNET gateway requires dip switch settings. The BACNET gateway is used for MODBUS TPC also.

DIP SWITCHES S0-3 PROTOCOL

Set Protocol (BACNET and MODBUS gateway only):

The gateway protocol is determined on power up by looking at the “S” dip switches.

If the protocol is changed, the configuration/profiles must be cleared and reconfigured. This is done with the HTML interface.

MODBUS RTU does not require a gateway.

LONWORKS: Configured in hardware, no need to adjust dip switches.

Protocol

BACNET IP

S0 S1 S2 S3

OFF OFF OFF OFF

BACNET MSTP ON OFF OFF OFF

MODBUS TCP OFF ON OFF OFF

MODBUS RTU ON ON OFF OFF

DIP SWITCHES B0-4 BAUD

3PIN CONNECTOR TO BAS, Configure BAUD:

Default is 38400.

Configures the Baud rate for the 3 position terminal block.

This is the connection that will connect to the Building Automation

System (BAS).

This is used only when the protocol is BACNET MSTP.

Baud

9600

B0 B1 B2 B3

ON ON ON OFF

19200 OFF OFF OFF ON

38400 * ON ON OFF ON

57600

76800

OFF OFF ON ON

ON OFF ON ON

A0-7 (BACNET MSTP) MAC ADDRESS:

Default is MAC address 3.

Configure the MAC address for the BACNET Gateway by summing the “A” dip switches that are ON.

MAC address range: 1

– 127

1 2 4 8 16 32 64 <-sum for address

A0 A1 A2 A3 A4 A5 A6 A7 Address

OFF OFF OFF OFF OFF OFF OFF OFF 0

ON OFF OFF OFF OFF OFF OFF OFF 1

Invalid

OFF ON OFF OFF OFF OFF OFF OFF 2

ON ON OFF OFF OFF OFF OFF OFF 3 *

OFF OFF ON OFF OFF OFF OFF OFF 4

ON OFF ON OFF OFF OFF OFF OFF 5

OFF ON ON OFF OFF OFF OFF OFF 6

ON ON ON OFF OFF OFF OFF OFF 7

Default

OFF OFF OFF ON OFF OFF OFF OFF 8

ON OFF OFF ON OFF OFF OFF OFF 9

OFF ON OFF ON OFF OFF OFF OFF 10

… … … … … … … … …

ON ON ON ON ON ON ON OFF 127

Page 8 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

CONFIGURE THE GATEWAY USING THE HTML INTERFACE:

This section will provide the parameters required for the TempTrac control. For more details of the gateway, consult the gateway manual.

Connect your computer’s Ethernet port to the Ethernet port of the gateway.

Using a web browser, browse to the gateway at IP address: 192.168.1.24 default (If you have changed the

IP address, go to the appropriate address.).

If the device IP address has been changed and is not known, a utility is available from Feildserver.com.

Contact Fieldserver for more information.

Menu options vary depending on if you are configuring a LONWORKS gateway, BACNET Gateway set for BACNET IP, a BACNET gateway set for BACNET MSTP, or a BACNET gateway set for MODBUS

TCP.

Using your browser, set the following and SUBMIT after each change.

MODBUS RTU Baud Rate: 9600

MODBUS RTU Parity: NONE

MODBUS RTU Data Bits: 8

MODBUS RTU Stop Bits: 1

(BACNET options)

BACNET Network Number: Must be unique network number on BACNET network

BACNET Node Offset: This will be used to create the DEVICE INSTANCE. Sum the device

MODBUS Address and this number. Example 50000 Node Offset + MODBUS address 1 = 50001

Device Instance. Each MODBUS device will have its own Device Instance number.

(BACNET MSTP option)

BACNET MSTP Max Master: 127

(BACNET IP option)

BACNET IP Port: 47808 (Default)

BACNET COV: COV Disable

(BACNET MSTP option)

BACNET BBMD: - (Default

“-“, enabling this is an advanced feature, not recommended)

BACNET Router: NO for 1 water heater, YES for multiple water heaters

SELECT THE DEVICE TYPE (BACNET & LONWORKS):

Press the ADD button, under Node ID enter the MODBUS address of the first heater. Typically you will have the nearest heater setup as MODBUS address 1, and the next heater MODBUS address 2. All heaters ship from factory with MODBUS Address set to 1. Each heater must have a unique MODBUS address. (See previous section Setup heater MODBUS address)

Under Current profile, select the proper interface for the TempTrac control.

For BACNET Gateway: Select

BAC_IP Temptrac for BACNET IP

BAC_MSTP Temptrac for BACNET MSTP

For LONWORKS Gateway: Select LON TempTrac Water Heater

Press the Submit button.

Add additional devices as required.

After adding all devices, restart the gateway by clicking the SYSTEM RESTART button.

Page 9 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

CONFIRM OPERATION:

Heater Communication:

Communication between gateway and heaters is evident by rapid flashing of the TX and RX LEDs on the gateway. If only the TX is flashing (may be as slow as 30 seconds between flashes), that will indicate no response from the heaters.

Building Automation System Communication:

Using the HTML interface, you can confirm some operations and under USER MESSAGES, confirm there are no errors messages. At this point, the BAS will need to discover the gateway and implement the points into its integration.

TROUBLESHOOTING GATEWAY:

ï‚· ERR Red LED on o Gateway is reporting an error. o Connect to gateway with HTML interface to view error messages

ï‚· PWR LED not on o Confirm power on +PWR and

–PWR

ï‚· TX & RX not flashing o Confirm connections to heaters and MODBUS addressing o Confirm gateway has been configured

ï‚· TX flashing, RX not flashing o Gateway is talking to TempTrac, but not getting response from TempTrac. Confirm wiring, confirm TempTrac is configured to proper address, Baud, Parity, Stop bits.

Verify polarity of all connections:

Set a Digital Volt Meter to read DC Volts. (Capable of reading less than 1.0VDC)

Pos. (red) Neg. (black) Min Max Actual

Reading Probe Probe

Gateway 6 pin terminal block

+PWR

Tx/+

-PWR

Rx/-

+9.0VDC

+0.1VDC

Gateway 3 pin terminal block (BACNET MSTP only)

RS 485 + RS 485 -

TempTrac orange dongle (Each heater)

+0.1VDC

+30VDC

+5.5VDC

+5.5VDC

(+)

(+)

(+)

(+)

(-)

(-)

(-)

(-)

+0.1VDC

+0.1VDC

+0.1VDC

+0.1VDC

+5.5VDC

+5.5VDC

+5.5VDC

+5.5VDC

(+) (-) +0.1VDC +5.5VDC

For advance gateway troubleshooting, reference the gateway manual.

Page 10 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

HOOKUP OVERVIEW:

BACNET MSTP or LONWORKS

BACNET MSTP

OR

LONWORKS

BACNET IP or MODBUS TCP

BACNET IP

OR

MODBUS TCP

MODBUS RTU Direct Connect

MODBUS RTU

To heaters with

TempTrac

To heaters with

TempTrac

Power Adapter

To heaters with

TempTrac

Power Adapter

Page 11 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

APPLICATION SPECIFICS:

Each product that uses the TempTrac control may have subtle differences. The following products address the important information regarding each device.

Conquest 100 Gallon (199 – 299) & 130 gallon 399: (Smaller Conquest)

Model Numbers: 20 L 100A-GCL, 25 L 100A-GCL, 30 L 100A-GCL, 40 L 130A-GCL

Probe 1: Is in the top of the tank, and controls the burner

Probe 2: Is in the mid-section and controls the agitator pump using Relay3

Probe 3: Is in the flue

Alarm_AL2: Alarm on any failure

Burner_Relay1: Burner

Relay2: Alarm dry contact

Relay3: Agitator pump

Discrete connections:

External Enable: Terminals R1

– R2, Jumper to enable. Heater ships with jumper on this. An external enable/disable can be attached to this. This is a low current, low voltage contact. It is advised to use a contact with gold plating. If not available, use 2 contacts in parallel.

Alarm: A1 & A2 (Output from Heater) Closed = ALARM.

Remote Proving: C1 & C2. Ships with factory jumper. Open will prevent burner from operating. Keeping this open will create a lockout condition that will require user intervention.

Remote Equipment / Burner ON: Contact that will close P1

– P2 during a heating cycle. Open, the heater is not calling for heat.

No Setpoint Input: There is not a discreet method to send a setpoint signal to the Conquest.

Conquest 130 Gallon (500 – 800): (Larger Modulating Conquest)

Model Numbers: 50 L 130A-GCML, 60 L 130A-GCML, 70 L 130A-GCML, 80 L 130A-GCML

Same as the smaller Conquest with the addition of modulation.

Modulation Rate: Modulation rate, Low fire = 0, High Fire = 100

Discrete connections:

Same as the smaller Conquest with the following notes:

No Modulation Input: There is not discreet way for a building automation system to control the modulation (firing rate) of the Conquest.

Page 12 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

Centauri Boiler, Centauri Plus Boiler, VT3 Boiler:

Model Numbers: All Centauri, Centauri Plus and VT3 Boilers

Probe 1: This temperature is displayed in yellow in the lower section of the display.

With SSBCO option, this probe is located in the top of the boiler. Without this option, the probe is shipped uninstalled and should be installed in the BHWR piping to read the temperature of the water entering the boiler.

Probe 2: This temperature is displayed in red in the upper section of the display.

With SSBCO option, this probe is shipped uninstalled and is intended to be installed in the field in the boiler’s HWR piping. Without the SSBCO option, this probe is installed in the top of the boiler providing the outlet water temperature.

Probe 3: Is an Auxiliary probe that can be used for outdoor temperature or other temperature readings. This is optional and not standard.

Alarm_AL3: Alarm on any failure

Burner_Relay1: Burner

Relay2: Not used

Relay3: Isolation Valve control when the OnTrac boiler management system is controlling.

Modulation Rate: Modulation rate, Low fire = 0, High Fire = 100

Discrete connections:

Ext Enable: Terminals R1

– R2, Jumper to enable. Heater ships with jumper on this. An external enable/disable can be attached to this. (Recommend relay at boiler, min 10A at 24VAC.)

Remote Equipment: P1 & P2, this is a contact that is driven any time a call for heat is present. Note this is only provided if the Remote Equipment or Louver options are present.

Alarm: A1 & A2 provide a 3 min alarm signal that is present after a failure to ignite burner for 4 minutes.

This output will be active for 3 minute and then the communication alarm will become active dropping the call for heat and dropping this signal. It is possible to get this alarm and the alarm condition that caused this alarm can be corrected before the 3 minutes, removing the alarm and not having a lockout or alarm condition over communication. (3 min signal of alarm condition and potential lockout.)

Page 13 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

M3 Boiler

Probe 1: Is in the top of the tank, and controls the burner. Provides outlet temperature.

Probe 2: Is wired but lose and field installed in the boiler HWR piping.

Probe 3: Is in the flue.

Alarm_AL2: Alarm on any failure.

Burner_Relay1: Burner

Relay2: Alarm dry contact, goes to terminals A1 & A2.

Relay3: Isolation Valve control, used with OnTrac group control. Terminals labeled

CIRCULATOR 1 & 2.

Modulation Rate: Modulation rate, Low fire = 0, High Fire = 100.

Discrete connections:

External Enable: Terminals R1

– R2, Jumper to enable. Heater ships with jumper on this. An external enable/disable can be attached to this. This is a low current, low voltage contact. It is advised to use a contact with gold plating. If not available, use 2 contacts in parallel.

Alarm: A1 & A2 (Output from Heater) Closed = ALARM.

Remote Proving: C1 & C2. Ships with factory jumper. Open will prevent burner from operating. Keeping this open will create a lockout condition that will require user intervention.

Remote Equipment / Burner ON: Contact that will close P1

– P2 during a heating cycle. Open, the heater is not calling for heat.

No Setpoint Input: There is not a discreet method to send a setpoint signal to the M3 boiler.

No Modulation Input: There is not discreet way for a building automation system to control the modulation

(firing rate) of the Conquest.

Quickdraw Steam to Water Storage

Probe 1: Lower Sensor

Probe 2: Upper Sensor

Relay1: Control valve

Reference wiring diagram for more details. Options vary greatly on this product.

Discrete connections:

External Enable: Terminals

Remote Equipment / Heating: E1 & E2 terminals are closed when heating, and open when not. This is an option REMEQ.

Alarm: A1 & A2 terminals are closed when in Alarm. This is an option REMAL.

Quickdraw Steam to Water Instantaneous

Probe 1: Lower Sensor

Probe 2: Upper Sensor

Relay1: Control valve

Reference wiring diagram for more details. Options may vary on this product.

Discrete connections:

External Enable: Terminals

Remote Equipment / Heating: E1 & E2 terminals are closed when heating, and open when not. This is an option REMEQ.

Alarm: A1 & A2 terminals are closed when in Alarm. This is an option REMAL.

Page 14 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

Other Equipment and Equipment Custom features:

Reference supplied wiring diagram and the I & O Manual. Contact PVI for additional information.

Below is a list of other products that can use the TempTrac controller:

Quickdraw Water to water Storage

EZ PLATE STORAGE

TURBOPOWER 99

TURBOPOWER

POWER VT PLUS

TRICON

MAXIM 3

DURAWATT (With TTRAC option)

MAXIM (With TTRAC option)

COBREX STORAGE

Page 15 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

POINTS LIST:

The gateway will provide a full points list, including typical points and advanced points. Normal interface will only require the TYPICAL POINTS. Many points are provided as ADVANCED POINTS and not advised to be used in normal integration. The Advanced Points are present for the purpose of future development and custom applications. Please consult factory if any points not in the TYPICAL POINTS are required.

Key:

LONWORKS shows multiple devices connected with a device number suffix, (#) represent the device.

MODBUS address with “:” to designate single bit usage of register. Number following colon represents bit location, 0 is the least significant bit.

Point Name

MODBUS

BACNET

LONWORKS

NOTES

Read/Write

Register Type

BACNET Name

Lon Read name_#

Short Description

Address Offset

Object Instance

Lon Write name_#

MODBUS Address

BACNET Units

Lon Units

TYPICAL POINTS:

The points that are typically used to interface with the heater. Most integrations only require points from this list.

TYPICAL POINTS:

Control_CNT

MODBUS

BACNET

LONWORKS

Write

Holding Register

Enable nvoCtrl_CNT_#

Enable Heater 257=on 1 = off

1280

128100

41281

This can be used to prevent the heater from heating via communication. 257 or 0X0101 = on, 1 or 0x0000 = off

The resister cannot be read. The register should only be written to with the values 257 and 1, as it has other undocumented functions.

Setpoint_St1

MODBUS

BACNET

LONWORKS

Read/Write

Holding Register

Setpoint_St1 nvoSP_St1_#

This is the setpoint for the heater.

System Setpoint

768

76900 nviSP_St1_#

40769

Deg-F

Deg_F

Probe 1

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Probe1 nvoProbe1_#

Controlling Probe Degrees F

256 40257

25700 Deg-F

Deg_F

Probe that provides control of heating. Location can vary depending on equipment and application. See section that discussed the various equipment to determine actual location of probe. Connection on TempTrac is green screw terminals 14 and common 17.

Page 16 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

TYPICAL POINTS:

Probe 2

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Probe2 nvoProbe2_#

Probe 2 in degrees F

258

25900

40259

Deg-F

Deg_F

Optional probe on some devices, usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 15 and common 17.

Probe 3

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Probe3 nvoProbe3_#

Probe 3 in degrees F

260

26100

40261

Deg-F

Deg_F

Optional probe on some devices, not usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 16 and common 17.

Burner Runtime

MODBUS

BACNET

LONWORKS

Read/Write

Holding Register

Burner Runtime Hours 0-65535

848

BURNER_HOURS_ou1 84900 nvoBrnHr_ou1_ # nviBrnHr_ou1_#

40849

Hours

Hours

NOTE: Number of hours the burner has been enabled. Once it reaches 9999. This can be written to, as a way to reset it.

Modulation Rate

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Modulation_FR nvoMod_FR_#

Monitor the modulation signal

262 40263

26300

Modulation rate on the analog output 4-20ma is represented as 0-100. This feature was introduced in Firmware

0.5 (5) and is not available from older TempTrac modules already in the field.

Burner_Relay1

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Burner_Relay1 nvoBrn_Rel1_#

Status of burner, Relay1 (Output 1)

2049 42050:0

205050

This is Bit 0 of the Relay status word. It is the relay that controls the main heating output. Typically the Burner

Status. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0001, if result = 0, relay is off. If result = 1, relay is on.

Alarm_AL2

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_AL2 nvoAlarm_AL2_#

Status of digital input #2 Alarm

3328 43329:11

332961

Digital Input #2 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 11 of the ALARM STATUS ALL word.

Flashes ‘AL2’ or ‘LP’ on TempTrac display. In

BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x0800 = 0x0800 Alarm is active. = 0x0000 Alarm is not active.

Page 17 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

TYPICAL POINTS:

Alarm_AL3

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_AL3 nvoAlarm_AL3_#

Status of digital input #3 Alarm

3328

332962

43329:12

Digital Input #3 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 12 of the ALARM STATUS ALL word.

Flashes ‘AL3’ or ‘HP’ on TempTrac display. In

BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x1000 = 0x1000 Alarm is active. = 0x0000 Alarm is not active.

Com Status

MODBUS

BACNET

LONWORKS

Read Only

Input Register

Gateway_TT_Com_OK nvoGwyTTCmOK_#

Communication Status bit

NA

200

NA

NOTE: This point is not generated by the heater; it is generated internally by the gateway. It is a status of the communication connection between the gateway and the heater. If active (GOOD), the gateway is talking to the heater. If inactive (NOT_PRESENT) then the gateway does not have good communication with the heater. This point may take up to 3 minutes to register properly after communication is established or interrupted. If this value if reading NOT_PRESENT, then no all over values are suspect, as the device is not communicating.

Generally the Gateway will hold the last value received. The only way to ensure you have the current values from the heater is to verify this point is ACTIVE as well.

ALL POINTS INCLUDING ADVANCED:

Points listed below that are not in the TYPICAL POINTS are provided for advanced interface and for custom applications. Contact factory for additional information.

ALL POINTS INCLUDING ADVANCE:

Control_CNT

MODBUS

BACNET

LONWORKS

Write

Holding Register

Enable nvoCtrl_CNT_#

Enable Heater 257=on 1 = off

1280 41281

128100

This can be used to prevent the heater from heating via communication. 257 or 0X0101 = on, 1 or 0x0000 = off

The resister cannot be read. The register should only be written to with the values 257 and 1, as it has other undocumented functions.

Setpoint_St1

MODBUS

BACNET

LONWORKS

Read/Write

Holding Register

Setpoint_St1 nvoSP_St1_#

System Setpoint

768

76900 nviSP_St1_#

40769

Deg-F

Deg_F

This is the setpoint for the heater.

Setpoint_St1 C

MODBUS

BACNET

LONWORKS

Read/Write

Setpoint_St1_C

System Setpoint

76900 Deg-C

Special BACNET point that converts the Setpoint value to degrees C in the gateway. Not available in

LONWORKS or MODBUS.

Page 18 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

ALL POINTS INCLUDING ADVANCE:

Hy1

MODBUS

BACNET

LONWORKS

Read

Holding Register

Hy1 nvoHy1_#

Setpoint Differential

772

77300

40773 delta-degrees-Fahrenheit

Differential. (if Hy1 is negative) The heater will begin heating when Probe #1 must fall this far below St1 setpoint, and stay on until the heater reaches St1 setpoint.

(If Hy1 is positive) The heater will come on when Probe #1 falls to or below St1 setpoint, and will not turn off until it has reached this far above St1 Setpoint. BACNET and LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this value.

St4

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

St4 nvoSt4_#

Modulation Start

792

79300

40793

No Units

Starting point of modulation. Related to the St1 setpoint. If Probe 1 is above St1 + St4, then Modulation signal will be low fire. If Probe 1 falls below (St1 + St4) then the analog output signal will modulate based on the setting in the SR register. This is set to No Units in BACNET because it can relative to St1 or is can be independent value. Typically it is configured as relative to St1. BACNET and LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this value.

SR

MODBUS

BACNET

LONWORKS

Read

Holding Register

SR nvoSR_#

Modulation bandwidth

793

79400

40794 delta-degrees-Fahrenheit

Normally this is a negative number. Number of degrees of change in Probe 1 that will modulate from 0 to 100%.

St1 + St4 = low fire, St1 + St4 + SR = High Fire. Temperatures above low fire will be low fire, temperatures below high fire will be high fire. In-between, the output will modulate from 4-20mA (0-100%) BACNET and

LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this value.

Probe 1

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Probe1 nvoProbe1_#

Controlling Probe Degrees F

256

25700

40257

Deg-F

Deg_F

Probe that provides control of heating. Location can vary depending on equipment and application. See section that discussed the various equipment to determine actual location of probe. Connection on TempTrac is green screw terminals 14 and common 17.

Probe 2

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Probe2 nvoProbe2_#

Probe 2 in degrees F

258

25900

40259

Deg-F

Deg_F

Optional probe on some devices, usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 15 and common 17.

Probe 3

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Probe3 nvoProbe3_#

Probe 3 in degrees F

260

26100

40261

Deg-F

Deg_F

Optional probe on some devices, not usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 16 and common 17.

Page 19 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

ALL POINTS INCLUDING ADVANCE:

Probe 1 C

MODBUS

BACNET

LONWORKS

Read Only

Probe1_C

Controlling Probe Degrees C

25790 Deg-C

Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in

LONWORKS or MODBUS.

Probe 2 C

MODBUS

BACNET

LONWORKS

Read Only

Probe2_C

Probe 2 in degrees C

25990 Deg-C

Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in

LONWORKS or MODBUS.

Probe 3 C

MODBUS

BACNET

LONWORKS

Read Only

Probe3_C

Probe 3 in degrees C

26190 Deg-C

Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in

LONWORKS or MODBUS.

Manual Modulation

MODBUS

BACNET

LONWORKS

Read/Write

Holding Register

PS4

NvoPS4_#

Force modulation to a level

797

79800

NviPS4_#

40798

Used to force a modulation rate. Typically used by service tech to make combustion adjustments at a particular firing rate. Normal setting is 101 = Auto. This allows the heater to modulate ad the load requires. If you put a value 0-100, it will force the heater to that firing rate when operating. 0=Low Fire, 100=High Fire

Use with caution. Advise allowing the heater do control its own modulation.

ALL

MODBUS

BACNET

LONWORKS

Read/Write

Holding Register

ALL nvoALL_#

Minimum Temperature Alarm

814 40815

81500 nviALL_#

Deg-F

Deg_F

Minimum temperature for Probe 1. Alarm will be activated if Probe 1 falls below this temperature. See Alarm points.

ALU

MODBUS

BACNET

LONWORKS

Read/Write

Holding Register

ALU nvoALU_#

Flame Current for proof of flame

815 40816

81600 nviALU_#

Deg-F

Deg_F

Maximum temperature for Probe 1. Alarm will be activated if Probe 1 rises above this temperature. See Alarm points.

Burner Runtime

MODBUS

BACNET

LONWORKS

Read/Write

Holding Register

Burner Runtime Hours 0-65535

848

BURNER_HOURS_ou1 84900 nvoBrnHr_ou1_ # nviBrnHr_ou1_#

40849

Hours

Hours

NOTE: Number of hours the burner has been enabled. Once it reaches 9999. This can be written to, as a way to reset it.

Page 20 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

ALL POINTS INCLUDING ADVANCE:

Maintenance Reminder

Read/Write

MODBUS

Holding Register

BACNET

LONWORKS oP1 nvooP1_#

Maintenance feature, set the value to 0.

Output #2 Mode

MODBUS

BACNET

LONWORKS

Read/Write

Holding Register

TT_2on nvoTT_2on_ #

Number of burner cycles 0-9999

851 40852

85200 nvioP1_#

Output #2 mode, ON, OFF, AUTO

855 40856

85600 nviTT_2on_#

TempTrac relay output spade 6 & 7. 0= Force relay off, 1=Force relay ON, 2= Auto (operates from thermostat functions).

Output #3 Mode

MODBUS

BACNET

LONWORKS

Read/Write

Holding Register

TT_3on nvoTT_3on_#

Output #2 mode, ON, OFF, AUTO

856

85700 nviTT_3on_#

40857

TempTrac relay output spade 8 & 9. 0= Force relay off, 1=Force relay ON, 2= Auto (operates from thermostat functions).

Software Version

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

VERSION_rEL nvoVer_rEL_#

Firmware revision

859

86000

40860

Software/Firmware revision number. At time of this manual, current version is 0.5 read as 5.

Modulation Rate

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Modulation_FR nvoMod_FR_#

Monitor the modulation signal

262

26300

40263

Modulation rate on the analog output 4-20ma is represented as 0-100. This feature was introduced in Firmware

0.5 (5) and is not available from older TempTrac modules already in the field.

RELAYS Status ALL

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

RELAYS nvoRELAYS_#

Shows the current state of the 3 output relays

2049 42050:0,1,2

205000

This register contains the relay status for all 3 relays. Bit 0 = relay 1 (4&5), Bit 1 = relay 2 (6&7), Bit 2 = relay 3

(8&9). See below breakout of each relay.

Burner_Relay1

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Burner_Relay1 nvoBrn_Rel1_#

Status of burner, Relay1 (Output 1)

2049

205050

42050:0

This is Bit 0 of the Relay status word. It is the relay that controls the main heating output. Typically the Burner

Status. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0001, if result = 0, relay is off. If result = 1, relay is on.

Page 21 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

ALL POINTS INCLUDING ADVANCE:

Relay2

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Relay2 nvoRelay2_#

Status of Relay2 (Output 3)

2049

205051

42050:1

This is Bit 1 of the Relay status word. It is the output #2 relay. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0002, if result = 0, relay is off. If result = 2, relay is on.

Relay3

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Relay3 nvoRelay3_#

Status of Relay3 (Output 3)

2049 42050:2

205052

This is Bit 2 of the Relay status word. It is the output #3 relay. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0004, if result = 0, relay is off. If result = 4, relay is on.

ALARM STATUS ALL

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

DIA nvoDIA_#

Alarm word, each bit represent separate alarms.

ALL ALARMS STATUS

3328

332900

43329

Alarm_LA

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_LA nvoAlarm_LA_#

Status of low temperature Alarm

3328

332950

43329:0

Low water temperature alarm. Probe 1 is lower than temperature in ALL point. This is Bit 0 of the ALARM

STATUS ALL word. In BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x0001 = 0x0001 Alarm is active. = 0x0000 Alarm is not active.

Alarm_HA

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_HA nvoAlarm_HA_#

Status of high temperature Alarm

3328 43329:1

332951

High water temperature alarm. Probe 1 is higher than temperature in ALU point. This is Bit 1 of the ALARM

STATUS ALL word. In BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x0002 = 0x0002 Alarm is active. = 0x0000 Alarm is not active.

Alarm_P1

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_P1 nvoAlarm_P1_#

Status of Probe 1 Alarm

3328

332952

43329:2

Probe 1 alarm. This can be a disconnected, open or shorted probe. This will shut down heating operation. This is Bit 2 of the ALARM STATUS ALL word. Flashes ‘P1’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x0004 = 0x0004 Alarm is active. = 0x0000 Alarm is not active.

Page 22 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

ALL POINTS INCLUDING ADVANCE:

Alarm_P2

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_P2 nvoAlarm_P2_#

Status of Probe 1 Alarm

3328

332958

43329:8

Probe 2 alarm. This can be a disconnected, open or shorted probe. This is Bit 8 of the ALARM STATUS ALL word. Flashes ‘P2’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x0100 = 0x0100 Alarm is active. = 0x0000 Alarm is not active.

Alarm_P3

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_P3 nvoAlarm_P3_#

Status of Probe 1 Alarm

3328

332959

43329:9

Probe 3 alarm. This can be a disconnected, open or shorted probe. This is Bit 9 of the ALARM STATUS ALL word. Flashes ‘P3’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x0200 = 0x0200 Alarm is active. = 0x0000 Alarm is not active.

Alarm_AL1

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_AL1 nvoAlarm_AL1_#

Status of digital input #1 Alarm

3328 43329:10

332960

Digital Input #1 alarm. This is typically not implemented. Refer to product specific details for information on this alarm. This is Bit 10 of the ALARM STATUS ALL word. Flashes ‘AL1’ on TempTrac display. In BACNET and

LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x0400 = 0x0400 Alarm is active. = 0x0000 Alarm is not active.

Alarm_AL2

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_AL2 nvoAlarm_AL2_#

Status of digital input #2 Alarm

3328 43329:11

332961

Digital Input #2 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 11 of the ALARM STATUS ALL word. Flashes ‘AL2’ or ‘LP’ on TempTrac display. In

BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x0800 = 0x0800 Alarm is active. = 0x0000 Alarm is not active.

Alarm_AL3

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_AL3 nvoAlarm_AL3_#

Status of digital input #3 Alarm

3328 43329:12

332962

Digital Input #3 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 12 of the ALARM STATUS ALL word. Flashes ‘AL3’ or ‘HP’ on TempTrac display. In

BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x1000 = 0x1000 Alarm is active. = 0x0000 Alarm is not active.

Page 23 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST

ALL POINTS INCLUDING ADVANCE:

Alarm_Nn1

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_Nn1 nvoAlarm_Nn1_#

Maintenance Alarm for output #1

3328

332963

43329:13

Maintenance Alarm. This is enabled when the time on ou1 is greater than the value in oP1. Flashes ‘Nn1’ on

TempTrac display. Bit #13 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x2000 = 0x2000 Alarm is active. = 0x0000 Alarm is not active.

Alarm_Nn2

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_Nn2 nvoAlarm_Nn2_#

Maintenance Alarm for output #2

3328

332963

43329:14

Maintenance Alarm. This is enabled when the time on ou2 is greater than the value in oP2. Flashes ‘Nn2’ on

TempTrac display. Bit #14 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x4000 = 0x4000 Alarm is active. = 0x0000 Alarm is not active.

Alarm_Nn3

MODBUS

BACNET

LONWORKS

Read Only

Holding Register

Alarm_Nn3 nvoAlarm_Nn3_#

Maintenance Alarm for output #3

3328

332963

43329:15

Maintenance Alarm. This is enabled when the time on ou3 is greater than the value in oP3. Flashes ‘Nn3’ on

TempTrac display. Bit #15 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point.

For MODBUS ALARMS && 0x8000 = 0x8000 Alarm is active. = 0x0000 Alarm is not active.

Com Status

MODBUS

BACNET

LONWORKS

Read Only

Input Register

Gateway_TT_Com_OK nvoGwyTTCmOK_#

Communication Status bit

NA

200

NA

NOTE: This point is not generated by the heater; it is generated internally by the gateway. It is a status of the communication connection between the gateway and the heater. If active (GOOD), the gateway is talking to the heater. If inactive (NOT_PRESENT) then the gateway does not have good communication with the heater. This point may take up to 3 minutes to register properly after communication is established or interrupted. If this value if reading NOT_PRESENT, then no all over values are suspect, as the device is not communicating.

Generally the Gateway will hold the last value received. The only way to ensure you have the current values from the heater is to verify this point is ACTIVE as well.

Page 24 of 30 PV7069-T 03/17

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST

ADVANCED MODBUS LIST:

The following is the direct MODBUS interface addresses. Descriptions of most to the MODBUS parameters are listed in the correlating TYPICAL POINTS defined previously. Many MODBUS parameters are not supported in the gateway interface. This is a complete reference list and contains advanced parameters. All MODBUS points normally required for interface are represented in the TYPICAL POINTS section. If there is a need for interfacing using other parameters, consult factory to confirm proper use.

Page 25 of 30 PV7069-T 01/05/16

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST

Label Firm

St1

Version

0.3 & 0.5

Set point1

St2

0.3 & 0.5

Set point2

St3

0.3 & 0.5

Set point3

St5

0.3 & 0.5

Description

Set point5 Set point 3 alternate

HY1

0.3 & 0.5

Differential for St1

LS1

0.3 & 0.5

Minimum set point1

US1

0.3 & 0.5

Maximum set point1

AC1

0.3 & 0.5

Anti-short cycle delay for output 1

S2c

0.3 & 0.5

HY2

0.3 & 0.5

Configuration of St2: dependent on St1 or independent

Differential for St2

LS2

0.3 & 0.5

Minimum set point2

uS2

0.3 & 0.5

Maximum set point2

AC2

0.3 & 0.5

Anti-short cycle delay for output 2

S3c

0.3 & 0.5

HY3

0.3 & 0.5

Configuration of St3: dependent on St1 or independent

Differential for set point 3 St3

LS3

0.3 & 0.5

Minimum set point 3 St3

uS3

0.3 & 0.5

Maximum set point 3 St3

AC3

0.3 & 0.5

Anti-short cycle delay for output 3

o3P

0.3 & 0.5

Probe selection for output 3

SSE

0.3 & 0.5

Set point shift for output 3 enable disable

HY5

0.3 & 0.5

Differential for set point 5

Ac5

0.3 & 0.5

Anti-short cycle delay for output 3 alternate set point

AcA

0.3 & 0.5

Time delay between the St3 to St5 set point shift diP; ind

-22÷22°F

-40°F÷St2

St2 ÷ 230°F

0÷30 min. diP; ind

-22÷22°F

-40°F÷St3

St3 ÷ 230°F

0÷30 min.

Pb1 / Pb2

No; Yes

-22÷22°F

0÷30 min.

0÷15 min.

Range

X÷Y

LS1÷US1

LS2÷US2

LS3÷US3

-20÷70°F

-22÷22°F

-40°F÷SET

SET ÷ 230°F

0÷30 min.

S4c

St4

SR

Th4

ANALOGUE OUTPUT 4÷20mA (output 4)

Configuration of St4: dependent on St1 or

0.3 & 0.5 independent

0.3 & 0.5

Analogue output set point

0.3 & 0.5

Analogue output band width

0.3 & 0.5

Outlet temperature threshold for forcing to 4ma the analog output

Differential for restart working of analog output

HY4

0.3 & 0.5

Ac4

0.3 & 0.5

PS4

0.3 & 0.5

Anti-short cycle delay for output 4

Analog output percentage (nu=101)

PP4

0.3 & 0.5

Analog output percentage with fault probe 1

(nu=101)

tt rr2

DYNAMIC RESET

0.3 & 0.5

Outdoor temperature threshold for dynamic reset of

St1

0.3 & 0.5

Outdoor temperature band width diP; ind

-100÷100°F

-100÷100°F

-40°F ÷ 230°F

-45 ÷ -1 °F

0÷30 min.

0÷100, nu

0÷100, nu

-40÷230°F

-100÷100°F

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr3

Pr2

Pr2

Pr2

Pr2

Rev

0.3

Rev

0.5

Level Level

Pr1

Pr1

Pr1

Pr1

Pr2

Pr2

Pr2

Pr2

Pr1

Pr1

Pr1

Pr1

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

782

783

784

785

786

787

788

789

790

791

777

778

779

780

781

Register

40000+

769

770

771

772

773

774

775

776

0x308

0x309

0x30A

0x30B

0x30C

0x30D

0x30E

0x30F

0x310

0x311

0x312

0x313

0x314

0x315

0x316

Hex Add

Modbus

base 0

0x300

0x301

0x302

0x303

0x304

0x305

0x306

0x307

Pr3

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr3

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

0x317

0x318

0x319

0x31A

0x31B

0x31C

0x31D

0x31E

Pr2

Pr2

Pr2

Pr2

0x31F

0x320

792

793

794

795

796

797

798

799

800

801

Page 26 of 30 PV7069-T 01/05/16

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST rr1 tt2

Ht2 i1P i2P i2d i3P i3d cF rES dS2 dS2 dS1 dS1

Alc

ALL

ALL

Alu

Alu

AFH

ALd dAo

0.3 & 0.5

Maximum shift of St1

0.3 & 0.5

0.3 & 0.5

Outdoor temperature threshold to open all the loads

0.3 & 0.5

0.3 & 0.5

Differential for restart working of controller

DIGITAL INPUTS

0.3 & 0.5

Digital input 1 polarity

Digital input 2 polarity

Digital input 2 alarm delay

0.3 & 0.5

0.3 & 0.5

Digital input 3 polarity

Digital input 3 alarm delay

-100÷100°F

-40÷230°F

-45 ÷ -1 °F

CL÷OP

CL÷OP

0÷255 min.

CL÷OP

0÷255 min.

DISPLAY

0.3 & 0.5

Temperature measurement unit

0.3 & 0.5

Resolution (integer/decimal point) only for °C

0.3

Default showing for display #2 Top (red)

0.5

Default showing for display #2 Top (red) Pb3 will display yellow EXT, Ani will display yellow Valve/M

0.3

0.5

°C ÷ °F in ÷ de

Pb2, Pb3

Default showing for display #1 Bottom (Yellow)

Default showing for display #1 Bottom (Yellow) Pb3 will display yellow EXT, Ani will display yellow Valve/M

Pb1,Pb2,Pb3,AnI

Pb1; tiM

Pb1,Pb2,Pb3,AnI, TiM

ALARMS

0.3 & 0.5

Temperature alarms configuration: dependent on St1 or independent rE÷Ab

0.3

0.5 minimum temperature alarm for Pb1 (Alarm LA flash only) minimum temperature alarm for Pb1 (Alarm LA flash and signal on 3329)

-40÷230°F

-40÷230°F

0.3

0.5

MAXIMUM temperature alarm for Pb1 (Alarm HA flash only)

MAXIMUM temperature alarm for Pb1 (Alarm HA flash and signal on 3329)

-40÷230°F

0.3 & 0.5

0.3 & 0.5

0.3 & 0.5

Differential for temperature alarm recovery

Temperature alarm delay

Delay of temperature alarm at start up 1 = 10 min disp 0.1

-40÷230°F

1÷45°F

0÷255 min.

0 ÷ 23h 50 min.

oF1

ANALOGUE INPUTS

0.3 & 0.5

First probe calibration

Second probe presence

P2P

0.3 & 0.5

oF2

0.3 & 0.5

Second probe calibration

Third probe presence

P3P

0.3 & 0.5

oF3

0.3 & 0.5

Third probe calibration

-21÷21°F

No; Yes

-21÷21°F

No; Yes

-21÷21°F

TIME AND DATE

Pr2

Pr2

Pr2

Pr3

Pr3

Pr2

Pr2

Pr3

Pr2

Pr3

Pr2

Pr3

Pr3

Pr2

Pr2

Pr3

Pr3

Pr2

Pr2

Pr2

Pr3

Pr2

Pr3

Pr2

Pr3

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

0x321

0x322

0x323

0x324

0x325

0x326

0x327

0x328

0x32D

0x32E

0x32E

0x32F

0x32F

0x330

0x331

0x332

0x329

0x32A

0x32B

0x32B

0x32C

0x32C

0x333

0x334

0x335

0x336

0x337

802

803

804

805

806

807

808

809

820

821

822

823

824

810

811

812

812

813

813

814

815

815

816

816

817

818

819

Page 27 of 30 PV7069-T 01/05/16

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST

Hur

Min

0.3 & 0.5

0.3 & 0.5

dAY

0.3 & 0.5

Current hour

Current minute

Current day

E1

S1

ENERGY SAVING TIMES

0.3 & 0.5

0.3 & 0.5

Sb1

0.3 & 0.5

Energy saving start on Sunday

Energy saving stop on Sunday

Set back temperature on Sunday

E2

S2

0.3 & 0.5

0.3 & 0.5

Energy saving start on Monday

Energy saving stop on Monday

Set back temperature on Monday

Sb2

0.3 & 0.5

E3

0.3 & 0.5

Energy saving start on Tuesday

S3

0.3 & 0.5

Energy saving stop on Tuesday

Set back temperature on Tuesday

Sb3

0.3 & 0.5

E4

0.3 & 0.5

Energy saving start on Wednesday

S4

0.3 & 0.5

Energy saving stop on Wednesday

Set back temperature on Wednesday

Sb4

0.3 & 0.5

E5

0.3 & 0.5

Energy saving start on Thursday

Energy saving stop on Thursday

S5

0.3 & 0.5

Sb5

0.3 & 0.5

Set back temperature on Thursday

E6

S6

0.3 & 0.5

0.3 & 0.5

Energy saving start on Friday

Energy saving stop on Friday

Set back temperature on Friday

Sb6

0.3 & 0.5

E7

0.3 & 0.5

Energy saving start on Saturday

S7

0.3 & 0.5

Energy saving stop on Saturday

Sb7

0.3 & 0.5

Set back temperature on Saturday

ou1 ou2 ou3 oP1 oP2 oP3

WORKING HOURS

0.3 & 0.5 working hours actual of relay 1

0.3 & 0.5 working hours actual of relay 2

0.3 & 0.5 working hours actual of relay 3

0.3 & 0.5

0.3 & 0.5

0.3 & 0.5 working hours limit of relay 1, Nn1 Alarm when reached working hours limit of relay 2, Nn2 Alarm when reached working hours limit of relay 3, Nn3 Alarm when reached

1on

2on

3on

OUTPUTS SETTING

The output 1 force ON / OFF or Temperature

0.3 & 0.5 regulation

0.3 & 0.5

0.3 & 0.5

The output 2 force ON / OFF or Temperature regulation

The output 3 force ON / OFF or Temperature regulation

OTHER

0 ÷ 23

0 ÷ 59

Sun ÷ SAt

0 ÷ 23h 50 min. - nu

0 ÷ 23h 50 min. - nu

-40÷40°F

0 ÷ 23h 50 min. - nu

0 ÷ 23h 50 min. - nu

-40÷40°F

0 ÷ 23h 50 min. - nu

0 ÷ 23h 50 min. - nu

-40÷40°F

0 ÷ 23h 50 min. - nu

0 ÷ 23h 50 min. - nu

-40÷40°F

0 ÷ 23h 50 min. - nu

0 ÷ 23h 50 min. - nu

-40÷40°F

0 ÷ 23h 50 min. - nu

0 ÷ 23h 50 min. - nu

-40÷40°F

0 ÷ 23h 50 min. - nu

0 ÷ 23h 50 min. - nu

-40÷40°F

0÷9999 Hours

0÷9999 Hours

0÷9999 Hours

0÷9999, 0=disabled

0÷9999, 0=disabled

0÷9999, 0=disabled rEG=2; on=1; oFF=0 rEG=2; on=1; oFF=0 rEG=2; on=1; oFF=0

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr1

Pr1

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

0x338

0x339

0x33A

0x350

0x351

0x352

0x353

0x354

0x355

0x33B

0x33C

0x33D

0x33E

0x33F

0x340

0x341

0x342

0x343

0x344

0x345

0x346

0x347

0x348

0x349

0x34A

0x34B

0x34C

0x34D

0x34E

0x34F

0x356

0x357

0x358

825

826

827

834

835

836

837

838

839

840

828

829

830

831

832

833

841

842

843

844

845

846

847

848

849

850

851

852

853

854

855

856

857

Page 28 of 30 PV7069-T 01/05/16

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST

Adr

Ptb rEL i1S i1t i1d i1F i2F i3F

0.3 & 0.5

0.3 & 0.5

0.3 & 0.5

0.5

0.5

0.5

0.5

0.5

0.5

oS2

0.5

(TP1)

0.3 & 0.5

0.3

(TP2)

0.3 & 0.5

0.3

(TP3)

0.3 & 0.5

0.3

0.5

0.3 & 0.5

0.3

0.3

0.3

0.5

0.5

0.5

0.5

0.5

0.5

Serial address

Parameter map code always = 1

Software release 5 = V0.5, 3 = V0.3

Analog output when Digital Input 1 is activated

Analog output at i1S extra time if Digital Input 1 is not activated

0÷247 readable only readable only

4-20mA

Digital Input 1 Alarm Delay

If Yes, Digital Input 1 will function as Alarm. Operating only when trying to call for output 1 and Input 1 is active, subject to i1d timer

0÷30 sec.

0÷255 min.

No; Yes

Digital Input 2 will function only when Output 1 is energized

Digital Input 3 will function only when Output 1 is energized, When Edi is selected, Output 1 will open when digital input 3 is activated

No; Yes

Output 2 function: either temp relay or alarm relay

Probe 1 temperature

Probe 1 Information/Status Normal=512 or 0x0200,

Fault=515 or 0x0203. Fault will, drop call for heat, buz,

Flash Yellow P1, light yellow valve/M

No; Yes; Edi

Std; AL

Degrees F/C

Probe 2 temperature

Probe 2 Information/Status Normal=512 or 0x0200,

Fault=515 or 0x0203. Fault will buz, Flash Red P2 bit (0,1 on) probe failure

Degrees F/C

Probe 3 temperature

Probe 3 Information/Status Normal=512 or 0x0200,

Fault=515 or 0x0203. Fault will buz, Flash Red P3 bit (0,1 on) probe failure

Degrees F/C

Modulation rate output (4 to 20mA)

Statas of Relay 1,2&3

Input 3 Alarm, buz, ALMMB, Flashes HP= 4096 or

0x0800

Input 2 Alarm, buz, Flashes LP= 4096 or 0x0800

Input 2 & 3, buz, Flashed HP & LP= 4096 or 0X0800

Low Temperature Alarm, beep, Flash Yellow LA= 1 or

0x0001

High Temperature Alarm, beep, Flash yellow HA= 2 or

0x0002

Probe 1 error, open or shorted, Drops call for heat, yel valve/M on, Flash Yellow P1=4 or 0x0004 bit (0,1 on) probe failure

0÷100% bit 0,1,2 bit # 12 or 13th bit bit # 12 or 13th bit bit # 12 or 13th bit bit # 0 or 1st bit bit # 1 or 2nd bit bit # 2 or 3rd bit

Probe 2 error, open or shorted, Flashing red P2=256 or 0x0100

Probe 3 error, open or shorted, Flashing red P3=512 or 0x0200

ALARM 1 (stops heating) Input 1, beep, Flash AL1 =

1024 or 0x0400. Will recover if Input 1 goes away, or need for call for heat goes away bit # 8 or 9th bit bit # 9 or 10th bit bit # 10 or 11th bit

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

Pr2

0x359

0x35A

0x35B

0x35C

0x35D

0x35E

0x35F

0x360

864

865

0x361

0x362

0x100

866

867

257

0xD00 3329

0x101

0x102

0x103

0x104

0x105

0x106

0x801

0xD00

0xD00

0xD00

0xD00

0xD00

0xD00

0xD00

0xD00

858

859

860

861

862

863

262

263

2050

3329

3329

3329

3329

3329

3329

3329

3329

258

259

260

261

Page 29 of 30 PV7069-T 01/05/16

Part number 129209

TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST

0.5

0.5

0.5

0.5

0.5

0.3 & 0.5

0.3 & 0.5

0.3 & 0.5

ALARM 2 (Lockout, stops heating) Input 2, Flash AL2 &

Lguage & valve= 2048 or 0x1000 bit # 11 or 12th bit

ALARM 3 (Lockout, stops heating) Input

3/ALMMB/ALOAF, beep, Flash AL3 & Hguage & valve

(This is ALARM ON ANY FAILURE)= 4096 or 0x0800 bit # 12 or 13th bit

Maintenance Relay1, beep, Flash Nn1 & wrench=8192 or 0x2000 You must reset hours ou1 or set oP1=0

Maintenance Relay2, beep, Flash Nn2 & wrench=16384 or 0x4000 You must reset hours ou2 or set oP2=0

Maintenance Relay3, beep, Flash Nn3 & wrench=32768 or 0x8000 You must reset hours ou3 or set oP3=0

On/Off On=257 or 0x0101, Off=1 or 0x0001 Can be used to reset ALMMB alarm by cycling OFF, wait 30 sec , ON

Keyboard Lock Lock=2056 or 0x0808, Unlock=8 or

0x0008. If locked PoF is displayed when keypad edit is attempted

Reset audible alarm when condition is corrected,

4112 or 0x1010 does not reset alarm, just stops the beeping

Energy Savings Registers are enumerated 0 to 145 w/145=n/u

10 min each with 145=nu

All other enumerations start at 0 and count up bit # 13 or 14th bit bit # 14 or 15th bit bit # 15 or 16th bit

Low byte is mask, Hi byte is command. Bit # 0 & #8

Low byte is mask, Hi byte is command. Bit # 3 &

#11

Low byte is mask, Hi byte is command. Bit # 3 &

#12

Pr2

0xD00 3329

Pr2

Pr2

Pr2

0xD00

0xD00

0xD00

0xD00

Pr2

Pr2

0x500

0x500

1281

1281

Pr2

Pr2

0x500 1281

3329

3329

3329

3329

Page 30 of 30 PV7069-T 01/05/16

Part number 129209

advertisement

Key Features

  • Simple and intuitive user interface for easy setup and operation
  • Built-in diagnostics and alarms for proactive maintenance
  • Flexible communication options for easy integration with Building Automation Systems (BAS)

Related manuals

Frequently Answers and Questions

What types of communication options does the TempTrac support?
The TempTrac supports MODBUS RTU and BACnet MSTP/IP.
Can I monitor and control the TempTrac remotely?
Yes, the TempTrac can be monitored and controlled remotely using a web browser or mobile app.
What is the default MODBUS address for the TempTrac?
The default MODBUS address for the TempTrac is 1.