PVI TempTrac Guide
Add to My manuals30 Pages
PVI TempTrac is an easy-to-use boiler and water heater control designed to provide reliable and efficient operation. It offers a wide range of features to meet the needs of various applications, including:
- Advanced control algorithms for precise temperature control
- Built-in diagnostics and alarms for proactive maintenance
- Multiple communication options for easy integration with Building Automation Systems (BAS)
- Remote monitoring and control capabilities for added convenience
advertisement
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Installation and interface must be performed by a qualified controls technician.
IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND
CONFIGURATION OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL
OTHER PROVIDED INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING
THIS UNIT.
Contents
TO THE INSTALLER / CONTROLS INTEGRATOR: After installation and integration, these instructions must be given to the equipment user or left near the appliance.
SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain important integration information that will help you in maintaining and operating this appliance.
PVI INDUSTRIES, LLC - Fort Worth, Texas 76111 - Web www.pvi.com
- Phone 1-800-433-5654
Page 1 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
OVERVIEW OF INTERFACE METHODS:
This document is a quick reference for connecting the TempTrac water heater / boiler control to a Building
Automation System (BAS). Direct connection via MODBUS RTU or using a gateway to interface to protocols other than MODBUS RTU are the methods covered in this manual.
BAS to Heaters direct, using MODBUS RTU:
BAS
PVI WATER HEATERS
Other equipment
Building Automation System (BAS) connecting directly to water heaters using MODBUS RTU twisted pair wire. (Wiring is RS-485 physical layer.)
BAS to heaters using a Protocol Gateway:
BAS
PVI WATER HEATERS
GATEWAY
Other equipment
Building Automation System (BAS) connecting to a PVI gateway. This can provide interface to BACNET
MSTP, BACNET IP, LONWORKS, and MODBUS TCP.
(Wiring from gateway to heaters is RS-485 physical layer. Wiring from BAS to gateway will depend on
Protocol.)
BAS to heaters using discrete connections:
This is simply control of the heater using the external ENABLE/DISABLE contacts, remote equipment contacts and the alarm contacts. See wiring diagram of equipment for details.
Page 2 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
TempTrac Heater MODBUS fixed settings:
Most of the MODBUS RTU and Port settings are not adjustable
Baud Rate: 9600bps (Not adjustable)
Data Length: 8 bit (Not adjustable)
Parity: None (Not adjustable)
Stop Bits: 1 (Not adjustable)
Start/Stop: Silent interval of 3 characters minimum
Minimum Time Between Retry: 500 msec.
Maximum read command is 5 words
Steps to change the TempTrac MODBUS address:
Editing parameters should be done without any device trying to communicate through the MODBUS port.
To avoid interference from a gateway or BAS, you should unplug the MODBUS adapter port on the back of the TempTrac at the white header, while making changes to the TempTrac parameters.
The first step to interfacing with a TempTrac or group of TempTracs will be the assignment of the address number for each boiler. The default for TempTrac is Address #1. You can assign any number in the range of 1-247. This is the limitations of the MODBUS RTU standard.
The MODBUS address is the Adr parameter, and it is in the Pr2 menu.
Enter the Programming mode by pressing the SET and DOWN key for more than 3 seconds. (Lead with the SET key.)
Pressing the DOWN key, parameters will display in top, and value in bottom.
Select Pr2 / PAS (parameter / value), and press the SET key.
The lower display will show the value 0 - - with a flashing zero.
Use UP or DOWN keys to input the security code in the flashing digit; confirm each digit by pressing SET. The security code is 321.
After hitting SET on the last digit, you will be in the Pr2 menu.
Once you have entered the Pr2 menu press the DOWN key to move through the parameters until the Adr parameter appears on the top display.
Now press the SET key once and the value number will begin to blink. Use the arrow key to set the address and then hit the SET key.
After hitting the SET, it will automatically go to the next parameter. Let it time out, or cycle power to the TempTrac.
Each TempTrac on a RS-485 network must have a unique MODBUS address.
The TempTrac MODBUS adapter port:
The MODBUS adapter is an orange dongle with 2 green screw terminals attached to an 8 inch cable that plugs into the back of the TempTrac at a white header. This can be an option installed on heater, or it may be a separate line item part. When the option is available, it is MBUSC option code. As a standalone part, it is PN: 11807.
Page 3 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
TEMPTRAC PROTOCOL
The MODBUS RTU protocol is well established industry protocol and technical references for this are readily available on the Internet.
Data Types Used
The TempTrac only uses one data type
Holding Registers (40001
– 49999) Read/Write
Other data types such as Coils are not implemented in the TempTrac control.
Only the data points in the POINTS LIST should be accessed.
Physical Layer RS-485
MODBUS RTU uses the physical layer RS-485.
RS-485 (EIA-485): A 2 wire (twisted pair) multi drop network. Each device can send data by holding positive and negative voltage on the line and reversing polarity on the 2 wires. When no devices are transmitting, the line will be tristate. The recommended arrangement of the wires is as a connected series of point-topoint (multi-dropped) nodes, i.e. a line or bus, not a star, ring, or multiply connected network. The number of devices that can be connected to a single line is defined in the RS-485 standard by the input impedance of 32 UNIT LOADs. The wire and circuits interfacing on this 2 wire connection is considered the PHYSICAL
LAYER. (RS-485 is the same physical layer as used with BACNET MSTP.)
No provisions for biasing resistors or termination resistors are provided on the control. If required, this will need to be provided externally.
The PVI gateway does provide optional biasing (default) and can provide a termination resistor, if required.
ITEMS REQUIRED FOR GATEWAY INTERFACE:
One or more water heaters with a TempTrac control (red/orange LED display with 6 tactile buttons) including the RS-485 adapter.
Protonode Gateway with Power supply adapter (when ordering, please specify what protocol is required;
BACNET MSTP, BACNET IP, LONWORKS or MODBUS TCP).
Protonode Gateway Manual (Covers general information for the gateway).
PV7069-T.PDF Interface manual that covers specifics for interfacing with the TempTrac system. Also includes the points list for the TempTrac control system. (This document).
120VAC power outlet for the power supply.
Computer with web browser and Ethernet connection capability to configure gateway.
ITEMS REQUIRED FOR MODBUS DIRECT INTERACE:
One or more water heaters with a TempTrac control (red/orange LED display with 6 tactile buttons) including the RS-485 adapter.
PV7069-T.PDF Interface manual that covers specifics for interfacing with the TempTrac system. Also includes the points list for the TempTrac control system. (This document).
Page 4 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
IDENTIFY EQUIPMENT:
The equipment should have a TempTrac mounted on the control panel. The RS-485 adapter may be installed or may ship lose. The gateway and power supply ship lose. The gateway is a grey module that has a wall wart style power supply.
TempTrac back, showing adapter dongle.
TempTrac Front and side view
Protocol Gateway
TempTrac is mounted on the control panel of the equipment. On the back side of the TempTrac is a white header. The RS-485 adapter plugs into this with a 8 inch cable. The orange adapter has 2 green terminals labeled (+) & (-).
The Protocol Gateway, if supplied, comes with a power supply and ships as a loose item.
Page 5 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
WIRING BAS TO GATEWAY AND THEN GATEWAY TO TEMPTRAC:
Each gateway has 3 connection points.
The 6 position terminal block contains connection for power and MODBUS RTU (going to heaters).
The Ethernet port is for configuration, BACNET IP, or MODBUS TCP.
The 3 or 2 pin terminal is for the BAS interface: BACNET MSTP, or LONWORKS.
Power Connection:
Gateway power supply, 6 position terminal +PWR, -PWR.
Use supplied wall wart style power supply. 15VDC. Do not power other devices with same power supply.
If power adapter has not already been connected, cut and discard the connector on the end, strip and terminate the power adapter in the proper terminals. Verify polarity. If another supply is to be used, it must be isolated. Do not use 24VAC power from heater.
Gateway Connection to Heaters:
Wiring from Gateway to the heaters, use twisted pair wire.
Connector on the orange dongle adapter that is on the end of a 8” cable plugged into the back of the
TempTrac.
The wiring is standard 2 wire RS-485 wiring. You will connect all devices together in a daisy chain. We recommend the gateway to be at the start of this connection.
Gateway
6 Pos. terminal
TempTrac
Orange adapter
TempTrac #2
Orange adapter
Tx/+
Rx/-
GND
(+)
(-)
(+)
(-)
Building Automation Connection:
BAS protocol Connection Port on Gateway
BACNET MSTP 3 TERMINAL CONNECTOR
BACNET IP ETHERNET PORT
LONWORKS 2 TERMINAL CONNECTOR
MODBUS TCP ETHERNET PORT
Labeled
FIELD
ETHERNET
LonWorks
ETHERNET
Page 6 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
WIRING OF TEMPTRAC TO BAS (Direct, no Gateway):
The back side of the TempTrac has a white header with an 8 inch cable, connecting to an orange adapter module with 2 green terminals labeled (+) & (-). This is the RS-485 Modbus connection point.
Field connection for BAS
TempTrac
Orange adapter
TempTrac #2
Orange adapter
Testing
VDC
Results for proper hookup
RS 485 +
RS R85 -
GND
(+)
(-)
(+)
(-)
Positive lead
Negative lead
+ 0.100
To
+ 5.500
Ensure the proper polarity, check with a Digital Volt Meter set to Volts DC. Take a reading at the orange adapter from the (-) Terminal to the (+) Terminal. The (+) should be the positive lead when connected.
GATEWAY CONFIGURATION CONNECTION:
Both the LONWORKS and BACNET gateway have an Ethernet port. Connect the computer using a patch cable or cross-over cable to establish a direct connection to the gateway. Older units may require a crossover cable or two patch cables with an Ethernet switch. If using BACNET IP or MODBUS TCP interface, connect the BAS Ethernet cable to the gateway when configuration is complete.
At this point, each heater and the gateway should all be powered, and have all wiring finished. The RUN
LED will toggle every second to indicate the gateway is running.
Page 7 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
CONFIGURE GATEWAY DIP SWITCHES:
The ON position is toward the center of the module, and OFF is toward the edge of the module. Only the
BACNET gateway requires dip switch settings. The BACNET gateway is used for MODBUS TPC also.
DIP SWITCHES S0-3 PROTOCOL
Set Protocol (BACNET and MODBUS gateway only):
The gateway protocol is determined on power up by looking at the “S” dip switches.
If the protocol is changed, the configuration/profiles must be cleared and reconfigured. This is done with the HTML interface.
MODBUS RTU does not require a gateway.
LONWORKS: Configured in hardware, no need to adjust dip switches.
Protocol
BACNET IP
S0 S1 S2 S3
OFF OFF OFF OFF
BACNET MSTP ON OFF OFF OFF
MODBUS TCP OFF ON OFF OFF
MODBUS RTU ON ON OFF OFF
DIP SWITCHES B0-4 BAUD
3PIN CONNECTOR TO BAS, Configure BAUD:
Default is 38400.
Configures the Baud rate for the 3 position terminal block.
This is the connection that will connect to the Building Automation
System (BAS).
This is used only when the protocol is BACNET MSTP.
Baud
9600
B0 B1 B2 B3
ON ON ON OFF
19200 OFF OFF OFF ON
38400 * ON ON OFF ON
57600
76800
OFF OFF ON ON
ON OFF ON ON
A0-7 (BACNET MSTP) MAC ADDRESS:
Default is MAC address 3.
Configure the MAC address for the BACNET Gateway by summing the “A” dip switches that are ON.
MAC address range: 1
– 127
1 2 4 8 16 32 64 <-sum for address
A0 A1 A2 A3 A4 A5 A6 A7 Address
OFF OFF OFF OFF OFF OFF OFF OFF 0
ON OFF OFF OFF OFF OFF OFF OFF 1
Invalid
OFF ON OFF OFF OFF OFF OFF OFF 2
ON ON OFF OFF OFF OFF OFF OFF 3 *
OFF OFF ON OFF OFF OFF OFF OFF 4
ON OFF ON OFF OFF OFF OFF OFF 5
OFF ON ON OFF OFF OFF OFF OFF 6
ON ON ON OFF OFF OFF OFF OFF 7
Default
OFF OFF OFF ON OFF OFF OFF OFF 8
ON OFF OFF ON OFF OFF OFF OFF 9
OFF ON OFF ON OFF OFF OFF OFF 10
… … … … … … … … …
ON ON ON ON ON ON ON OFF 127
Page 8 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
CONFIGURE THE GATEWAY USING THE HTML INTERFACE:
This section will provide the parameters required for the TempTrac control. For more details of the gateway, consult the gateway manual.
Connect your computer’s Ethernet port to the Ethernet port of the gateway.
Using a web browser, browse to the gateway at IP address: 192.168.1.24 default (If you have changed the
IP address, go to the appropriate address.).
If the device IP address has been changed and is not known, a utility is available from Feildserver.com.
Contact Fieldserver for more information.
Menu options vary depending on if you are configuring a LONWORKS gateway, BACNET Gateway set for BACNET IP, a BACNET gateway set for BACNET MSTP, or a BACNET gateway set for MODBUS
TCP.
Using your browser, set the following and SUBMIT after each change.
MODBUS RTU Baud Rate: 9600
MODBUS RTU Parity: NONE
MODBUS RTU Data Bits: 8
MODBUS RTU Stop Bits: 1
(BACNET options)
BACNET Network Number: Must be unique network number on BACNET network
BACNET Node Offset: This will be used to create the DEVICE INSTANCE. Sum the device
MODBUS Address and this number. Example 50000 Node Offset + MODBUS address 1 = 50001
Device Instance. Each MODBUS device will have its own Device Instance number.
(BACNET MSTP option)
BACNET MSTP Max Master: 127
(BACNET IP option)
BACNET IP Port: 47808 (Default)
BACNET COV: COV Disable
(BACNET MSTP option)
BACNET BBMD: - (Default
“-“, enabling this is an advanced feature, not recommended)
BACNET Router: NO for 1 water heater, YES for multiple water heaters
SELECT THE DEVICE TYPE (BACNET & LONWORKS):
Press the ADD button, under Node ID enter the MODBUS address of the first heater. Typically you will have the nearest heater setup as MODBUS address 1, and the next heater MODBUS address 2. All heaters ship from factory with MODBUS Address set to 1. Each heater must have a unique MODBUS address. (See previous section Setup heater MODBUS address)
Under Current profile, select the proper interface for the TempTrac control.
For BACNET Gateway: Select
BAC_IP Temptrac for BACNET IP
BAC_MSTP Temptrac for BACNET MSTP
For LONWORKS Gateway: Select LON TempTrac Water Heater
Press the Submit button.
Add additional devices as required.
After adding all devices, restart the gateway by clicking the SYSTEM RESTART button.
Page 9 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
CONFIRM OPERATION:
Heater Communication:
Communication between gateway and heaters is evident by rapid flashing of the TX and RX LEDs on the gateway. If only the TX is flashing (may be as slow as 30 seconds between flashes), that will indicate no response from the heaters.
Building Automation System Communication:
Using the HTML interface, you can confirm some operations and under USER MESSAGES, confirm there are no errors messages. At this point, the BAS will need to discover the gateway and implement the points into its integration.
TROUBLESHOOTING GATEWAY:
ï‚· ERR Red LED on o Gateway is reporting an error. o Connect to gateway with HTML interface to view error messages
ï‚· PWR LED not on o Confirm power on +PWR and
–PWR
ï‚· TX & RX not flashing o Confirm connections to heaters and MODBUS addressing o Confirm gateway has been configured
ï‚· TX flashing, RX not flashing o Gateway is talking to TempTrac, but not getting response from TempTrac. Confirm wiring, confirm TempTrac is configured to proper address, Baud, Parity, Stop bits.
Verify polarity of all connections:
Set a Digital Volt Meter to read DC Volts. (Capable of reading less than 1.0VDC)
Pos. (red) Neg. (black) Min Max Actual
Reading Probe Probe
Gateway 6 pin terminal block
+PWR
Tx/+
-PWR
Rx/-
+9.0VDC
+0.1VDC
Gateway 3 pin terminal block (BACNET MSTP only)
RS 485 + RS 485 -
TempTrac orange dongle (Each heater)
+0.1VDC
+30VDC
+5.5VDC
+5.5VDC
(+)
(+)
(+)
(+)
(-)
(-)
(-)
(-)
+0.1VDC
+0.1VDC
+0.1VDC
+0.1VDC
+5.5VDC
+5.5VDC
+5.5VDC
+5.5VDC
(+) (-) +0.1VDC +5.5VDC
For advance gateway troubleshooting, reference the gateway manual.
Page 10 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
HOOKUP OVERVIEW:
BACNET MSTP or LONWORKS
BACNET MSTP
OR
LONWORKS
BACNET IP or MODBUS TCP
BACNET IP
OR
MODBUS TCP
MODBUS RTU Direct Connect
MODBUS RTU
To heaters with
TempTrac
To heaters with
TempTrac
Power Adapter
To heaters with
TempTrac
Power Adapter
Page 11 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
APPLICATION SPECIFICS:
Each product that uses the TempTrac control may have subtle differences. The following products address the important information regarding each device.
Conquest 100 Gallon (199 – 299) & 130 gallon 399: (Smaller Conquest)
Model Numbers: 20 L 100A-GCL, 25 L 100A-GCL, 30 L 100A-GCL, 40 L 130A-GCL
Probe 1: Is in the top of the tank, and controls the burner
Probe 2: Is in the mid-section and controls the agitator pump using Relay3
Probe 3: Is in the flue
Alarm_AL2: Alarm on any failure
Burner_Relay1: Burner
Relay2: Alarm dry contact
Relay3: Agitator pump
Discrete connections:
External Enable: Terminals R1
– R2, Jumper to enable. Heater ships with jumper on this. An external enable/disable can be attached to this. This is a low current, low voltage contact. It is advised to use a contact with gold plating. If not available, use 2 contacts in parallel.
Alarm: A1 & A2 (Output from Heater) Closed = ALARM.
Remote Proving: C1 & C2. Ships with factory jumper. Open will prevent burner from operating. Keeping this open will create a lockout condition that will require user intervention.
Remote Equipment / Burner ON: Contact that will close P1
– P2 during a heating cycle. Open, the heater is not calling for heat.
No Setpoint Input: There is not a discreet method to send a setpoint signal to the Conquest.
Conquest 130 Gallon (500 – 800): (Larger Modulating Conquest)
Model Numbers: 50 L 130A-GCML, 60 L 130A-GCML, 70 L 130A-GCML, 80 L 130A-GCML
Same as the smaller Conquest with the addition of modulation.
Modulation Rate: Modulation rate, Low fire = 0, High Fire = 100
Discrete connections:
Same as the smaller Conquest with the following notes:
No Modulation Input: There is not discreet way for a building automation system to control the modulation (firing rate) of the Conquest.
Page 12 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Centauri Boiler, Centauri Plus Boiler, VT3 Boiler:
Model Numbers: All Centauri, Centauri Plus and VT3 Boilers
Probe 1: This temperature is displayed in yellow in the lower section of the display.
With SSBCO option, this probe is located in the top of the boiler. Without this option, the probe is shipped uninstalled and should be installed in the BHWR piping to read the temperature of the water entering the boiler.
Probe 2: This temperature is displayed in red in the upper section of the display.
With SSBCO option, this probe is shipped uninstalled and is intended to be installed in the field in the boiler’s HWR piping. Without the SSBCO option, this probe is installed in the top of the boiler providing the outlet water temperature.
Probe 3: Is an Auxiliary probe that can be used for outdoor temperature or other temperature readings. This is optional and not standard.
Alarm_AL3: Alarm on any failure
Burner_Relay1: Burner
Relay2: Not used
Relay3: Isolation Valve control when the OnTrac boiler management system is controlling.
Modulation Rate: Modulation rate, Low fire = 0, High Fire = 100
Discrete connections:
Ext Enable: Terminals R1
– R2, Jumper to enable. Heater ships with jumper on this. An external enable/disable can be attached to this. (Recommend relay at boiler, min 10A at 24VAC.)
Remote Equipment: P1 & P2, this is a contact that is driven any time a call for heat is present. Note this is only provided if the Remote Equipment or Louver options are present.
Alarm: A1 & A2 provide a 3 min alarm signal that is present after a failure to ignite burner for 4 minutes.
This output will be active for 3 minute and then the communication alarm will become active dropping the call for heat and dropping this signal. It is possible to get this alarm and the alarm condition that caused this alarm can be corrected before the 3 minutes, removing the alarm and not having a lockout or alarm condition over communication. (3 min signal of alarm condition and potential lockout.)
Page 13 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
M3 Boiler
Probe 1: Is in the top of the tank, and controls the burner. Provides outlet temperature.
Probe 2: Is wired but lose and field installed in the boiler HWR piping.
Probe 3: Is in the flue.
Alarm_AL2: Alarm on any failure.
Burner_Relay1: Burner
Relay2: Alarm dry contact, goes to terminals A1 & A2.
Relay3: Isolation Valve control, used with OnTrac group control. Terminals labeled
CIRCULATOR 1 & 2.
Modulation Rate: Modulation rate, Low fire = 0, High Fire = 100.
Discrete connections:
External Enable: Terminals R1
– R2, Jumper to enable. Heater ships with jumper on this. An external enable/disable can be attached to this. This is a low current, low voltage contact. It is advised to use a contact with gold plating. If not available, use 2 contacts in parallel.
Alarm: A1 & A2 (Output from Heater) Closed = ALARM.
Remote Proving: C1 & C2. Ships with factory jumper. Open will prevent burner from operating. Keeping this open will create a lockout condition that will require user intervention.
Remote Equipment / Burner ON: Contact that will close P1
– P2 during a heating cycle. Open, the heater is not calling for heat.
No Setpoint Input: There is not a discreet method to send a setpoint signal to the M3 boiler.
No Modulation Input: There is not discreet way for a building automation system to control the modulation
(firing rate) of the Conquest.
Quickdraw Steam to Water Storage
Probe 1: Lower Sensor
Probe 2: Upper Sensor
Relay1: Control valve
Reference wiring diagram for more details. Options vary greatly on this product.
Discrete connections:
External Enable: Terminals
Remote Equipment / Heating: E1 & E2 terminals are closed when heating, and open when not. This is an option REMEQ.
Alarm: A1 & A2 terminals are closed when in Alarm. This is an option REMAL.
Quickdraw Steam to Water Instantaneous
Probe 1: Lower Sensor
Probe 2: Upper Sensor
Relay1: Control valve
Reference wiring diagram for more details. Options may vary on this product.
Discrete connections:
External Enable: Terminals
Remote Equipment / Heating: E1 & E2 terminals are closed when heating, and open when not. This is an option REMEQ.
Alarm: A1 & A2 terminals are closed when in Alarm. This is an option REMAL.
Page 14 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Other Equipment and Equipment Custom features:
Reference supplied wiring diagram and the I & O Manual. Contact PVI for additional information.
Below is a list of other products that can use the TempTrac controller:
Quickdraw Water to water Storage
EZ PLATE STORAGE
TURBOPOWER 99
TURBOPOWER
POWER VT PLUS
TRICON
MAXIM 3
DURAWATT (With TTRAC option)
MAXIM (With TTRAC option)
COBREX STORAGE
Page 15 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
POINTS LIST:
The gateway will provide a full points list, including typical points and advanced points. Normal interface will only require the TYPICAL POINTS. Many points are provided as ADVANCED POINTS and not advised to be used in normal integration. The Advanced Points are present for the purpose of future development and custom applications. Please consult factory if any points not in the TYPICAL POINTS are required.
Key:
LONWORKS shows multiple devices connected with a device number suffix, (#) represent the device.
MODBUS address with “:” to designate single bit usage of register. Number following colon represents bit location, 0 is the least significant bit.
Point Name
MODBUS
BACNET
LONWORKS
NOTES
Read/Write
Register Type
BACNET Name
Lon Read name_#
Short Description
Address Offset
Object Instance
Lon Write name_#
MODBUS Address
BACNET Units
Lon Units
TYPICAL POINTS:
The points that are typically used to interface with the heater. Most integrations only require points from this list.
TYPICAL POINTS:
Control_CNT
MODBUS
BACNET
LONWORKS
Write
Holding Register
Enable nvoCtrl_CNT_#
Enable Heater 257=on 1 = off
1280
128100
41281
This can be used to prevent the heater from heating via communication. 257 or 0X0101 = on, 1 or 0x0000 = off
The resister cannot be read. The register should only be written to with the values 257 and 1, as it has other undocumented functions.
Setpoint_St1
MODBUS
BACNET
LONWORKS
Read/Write
Holding Register
Setpoint_St1 nvoSP_St1_#
This is the setpoint for the heater.
System Setpoint
768
76900 nviSP_St1_#
40769
Deg-F
Deg_F
Probe 1
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Probe1 nvoProbe1_#
Controlling Probe Degrees F
256 40257
25700 Deg-F
Deg_F
Probe that provides control of heating. Location can vary depending on equipment and application. See section that discussed the various equipment to determine actual location of probe. Connection on TempTrac is green screw terminals 14 and common 17.
Page 16 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
TYPICAL POINTS:
Probe 2
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Probe2 nvoProbe2_#
Probe 2 in degrees F
258
25900
40259
Deg-F
Deg_F
Optional probe on some devices, usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 15 and common 17.
Probe 3
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Probe3 nvoProbe3_#
Probe 3 in degrees F
260
26100
40261
Deg-F
Deg_F
Optional probe on some devices, not usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 16 and common 17.
Burner Runtime
MODBUS
BACNET
LONWORKS
Read/Write
Holding Register
Burner Runtime Hours 0-65535
848
BURNER_HOURS_ou1 84900 nvoBrnHr_ou1_ # nviBrnHr_ou1_#
40849
Hours
Hours
NOTE: Number of hours the burner has been enabled. Once it reaches 9999. This can be written to, as a way to reset it.
Modulation Rate
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Modulation_FR nvoMod_FR_#
Monitor the modulation signal
262 40263
26300
Modulation rate on the analog output 4-20ma is represented as 0-100. This feature was introduced in Firmware
0.5 (5) and is not available from older TempTrac modules already in the field.
Burner_Relay1
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Burner_Relay1 nvoBrn_Rel1_#
Status of burner, Relay1 (Output 1)
2049 42050:0
205050
This is Bit 0 of the Relay status word. It is the relay that controls the main heating output. Typically the Burner
Status. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0001, if result = 0, relay is off. If result = 1, relay is on.
Alarm_AL2
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_AL2 nvoAlarm_AL2_#
Status of digital input #2 Alarm
3328 43329:11
332961
Digital Input #2 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 11 of the ALARM STATUS ALL word.
Flashes ‘AL2’ or ‘LP’ on TempTrac display. In
BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0800 = 0x0800 Alarm is active. = 0x0000 Alarm is not active.
Page 17 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
TYPICAL POINTS:
Alarm_AL3
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_AL3 nvoAlarm_AL3_#
Status of digital input #3 Alarm
3328
332962
43329:12
Digital Input #3 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 12 of the ALARM STATUS ALL word.
Flashes ‘AL3’ or ‘HP’ on TempTrac display. In
BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x1000 = 0x1000 Alarm is active. = 0x0000 Alarm is not active.
Com Status
MODBUS
BACNET
LONWORKS
Read Only
Input Register
Gateway_TT_Com_OK nvoGwyTTCmOK_#
Communication Status bit
NA
200
NA
NOTE: This point is not generated by the heater; it is generated internally by the gateway. It is a status of the communication connection between the gateway and the heater. If active (GOOD), the gateway is talking to the heater. If inactive (NOT_PRESENT) then the gateway does not have good communication with the heater. This point may take up to 3 minutes to register properly after communication is established or interrupted. If this value if reading NOT_PRESENT, then no all over values are suspect, as the device is not communicating.
Generally the Gateway will hold the last value received. The only way to ensure you have the current values from the heater is to verify this point is ACTIVE as well.
ALL POINTS INCLUDING ADVANCED:
Points listed below that are not in the TYPICAL POINTS are provided for advanced interface and for custom applications. Contact factory for additional information.
ALL POINTS INCLUDING ADVANCE:
Control_CNT
MODBUS
BACNET
LONWORKS
Write
Holding Register
Enable nvoCtrl_CNT_#
Enable Heater 257=on 1 = off
1280 41281
128100
This can be used to prevent the heater from heating via communication. 257 or 0X0101 = on, 1 or 0x0000 = off
The resister cannot be read. The register should only be written to with the values 257 and 1, as it has other undocumented functions.
Setpoint_St1
MODBUS
BACNET
LONWORKS
Read/Write
Holding Register
Setpoint_St1 nvoSP_St1_#
System Setpoint
768
76900 nviSP_St1_#
40769
Deg-F
Deg_F
This is the setpoint for the heater.
Setpoint_St1 C
MODBUS
BACNET
LONWORKS
Read/Write
Setpoint_St1_C
System Setpoint
76900 Deg-C
Special BACNET point that converts the Setpoint value to degrees C in the gateway. Not available in
LONWORKS or MODBUS.
Page 18 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Hy1
MODBUS
BACNET
LONWORKS
Read
Holding Register
Hy1 nvoHy1_#
Setpoint Differential
772
77300
40773 delta-degrees-Fahrenheit
Differential. (if Hy1 is negative) The heater will begin heating when Probe #1 must fall this far below St1 setpoint, and stay on until the heater reaches St1 setpoint.
(If Hy1 is positive) The heater will come on when Probe #1 falls to or below St1 setpoint, and will not turn off until it has reached this far above St1 Setpoint. BACNET and LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this value.
St4
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
St4 nvoSt4_#
Modulation Start
792
79300
40793
No Units
Starting point of modulation. Related to the St1 setpoint. If Probe 1 is above St1 + St4, then Modulation signal will be low fire. If Probe 1 falls below (St1 + St4) then the analog output signal will modulate based on the setting in the SR register. This is set to No Units in BACNET because it can relative to St1 or is can be independent value. Typically it is configured as relative to St1. BACNET and LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this value.
SR
MODBUS
BACNET
LONWORKS
Read
Holding Register
SR nvoSR_#
Modulation bandwidth
793
79400
40794 delta-degrees-Fahrenheit
Normally this is a negative number. Number of degrees of change in Probe 1 that will modulate from 0 to 100%.
St1 + St4 = low fire, St1 + St4 + SR = High Fire. Temperatures above low fire will be low fire, temperatures below high fire will be high fire. In-between, the output will modulate from 4-20mA (0-100%) BACNET and
LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this value.
Probe 1
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Probe1 nvoProbe1_#
Controlling Probe Degrees F
256
25700
40257
Deg-F
Deg_F
Probe that provides control of heating. Location can vary depending on equipment and application. See section that discussed the various equipment to determine actual location of probe. Connection on TempTrac is green screw terminals 14 and common 17.
Probe 2
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Probe2 nvoProbe2_#
Probe 2 in degrees F
258
25900
40259
Deg-F
Deg_F
Optional probe on some devices, usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 15 and common 17.
Probe 3
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Probe3 nvoProbe3_#
Probe 3 in degrees F
260
26100
40261
Deg-F
Deg_F
Optional probe on some devices, not usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 16 and common 17.
Page 19 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Probe 1 C
MODBUS
BACNET
LONWORKS
Read Only
Probe1_C
Controlling Probe Degrees C
25790 Deg-C
Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in
LONWORKS or MODBUS.
Probe 2 C
MODBUS
BACNET
LONWORKS
Read Only
Probe2_C
Probe 2 in degrees C
25990 Deg-C
Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in
LONWORKS or MODBUS.
Probe 3 C
MODBUS
BACNET
LONWORKS
Read Only
Probe3_C
Probe 3 in degrees C
26190 Deg-C
Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in
LONWORKS or MODBUS.
Manual Modulation
MODBUS
BACNET
LONWORKS
Read/Write
Holding Register
PS4
NvoPS4_#
Force modulation to a level
797
79800
NviPS4_#
40798
Used to force a modulation rate. Typically used by service tech to make combustion adjustments at a particular firing rate. Normal setting is 101 = Auto. This allows the heater to modulate ad the load requires. If you put a value 0-100, it will force the heater to that firing rate when operating. 0=Low Fire, 100=High Fire
Use with caution. Advise allowing the heater do control its own modulation.
ALL
MODBUS
BACNET
LONWORKS
Read/Write
Holding Register
ALL nvoALL_#
Minimum Temperature Alarm
814 40815
81500 nviALL_#
Deg-F
Deg_F
Minimum temperature for Probe 1. Alarm will be activated if Probe 1 falls below this temperature. See Alarm points.
ALU
MODBUS
BACNET
LONWORKS
Read/Write
Holding Register
ALU nvoALU_#
Flame Current for proof of flame
815 40816
81600 nviALU_#
Deg-F
Deg_F
Maximum temperature for Probe 1. Alarm will be activated if Probe 1 rises above this temperature. See Alarm points.
Burner Runtime
MODBUS
BACNET
LONWORKS
Read/Write
Holding Register
Burner Runtime Hours 0-65535
848
BURNER_HOURS_ou1 84900 nvoBrnHr_ou1_ # nviBrnHr_ou1_#
40849
Hours
Hours
NOTE: Number of hours the burner has been enabled. Once it reaches 9999. This can be written to, as a way to reset it.
Page 20 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Maintenance Reminder
Read/Write
MODBUS
Holding Register
BACNET
LONWORKS oP1 nvooP1_#
Maintenance feature, set the value to 0.
Output #2 Mode
MODBUS
BACNET
LONWORKS
Read/Write
Holding Register
TT_2on nvoTT_2on_ #
Number of burner cycles 0-9999
851 40852
85200 nvioP1_#
Output #2 mode, ON, OFF, AUTO
855 40856
85600 nviTT_2on_#
TempTrac relay output spade 6 & 7. 0= Force relay off, 1=Force relay ON, 2= Auto (operates from thermostat functions).
Output #3 Mode
MODBUS
BACNET
LONWORKS
Read/Write
Holding Register
TT_3on nvoTT_3on_#
Output #2 mode, ON, OFF, AUTO
856
85700 nviTT_3on_#
40857
TempTrac relay output spade 8 & 9. 0= Force relay off, 1=Force relay ON, 2= Auto (operates from thermostat functions).
Software Version
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
VERSION_rEL nvoVer_rEL_#
Firmware revision
859
86000
40860
Software/Firmware revision number. At time of this manual, current version is 0.5 read as 5.
Modulation Rate
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Modulation_FR nvoMod_FR_#
Monitor the modulation signal
262
26300
40263
Modulation rate on the analog output 4-20ma is represented as 0-100. This feature was introduced in Firmware
0.5 (5) and is not available from older TempTrac modules already in the field.
RELAYS Status ALL
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
RELAYS nvoRELAYS_#
Shows the current state of the 3 output relays
2049 42050:0,1,2
205000
This register contains the relay status for all 3 relays. Bit 0 = relay 1 (4&5), Bit 1 = relay 2 (6&7), Bit 2 = relay 3
(8&9). See below breakout of each relay.
Burner_Relay1
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Burner_Relay1 nvoBrn_Rel1_#
Status of burner, Relay1 (Output 1)
2049
205050
42050:0
This is Bit 0 of the Relay status word. It is the relay that controls the main heating output. Typically the Burner
Status. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0001, if result = 0, relay is off. If result = 1, relay is on.
Page 21 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Relay2
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Relay2 nvoRelay2_#
Status of Relay2 (Output 3)
2049
205051
42050:1
This is Bit 1 of the Relay status word. It is the output #2 relay. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0002, if result = 0, relay is off. If result = 2, relay is on.
Relay3
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Relay3 nvoRelay3_#
Status of Relay3 (Output 3)
2049 42050:2
205052
This is Bit 2 of the Relay status word. It is the output #3 relay. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0004, if result = 0, relay is off. If result = 4, relay is on.
ALARM STATUS ALL
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
DIA nvoDIA_#
Alarm word, each bit represent separate alarms.
ALL ALARMS STATUS
3328
332900
43329
Alarm_LA
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_LA nvoAlarm_LA_#
Status of low temperature Alarm
3328
332950
43329:0
Low water temperature alarm. Probe 1 is lower than temperature in ALL point. This is Bit 0 of the ALARM
STATUS ALL word. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0001 = 0x0001 Alarm is active. = 0x0000 Alarm is not active.
Alarm_HA
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_HA nvoAlarm_HA_#
Status of high temperature Alarm
3328 43329:1
332951
High water temperature alarm. Probe 1 is higher than temperature in ALU point. This is Bit 1 of the ALARM
STATUS ALL word. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0002 = 0x0002 Alarm is active. = 0x0000 Alarm is not active.
Alarm_P1
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_P1 nvoAlarm_P1_#
Status of Probe 1 Alarm
3328
332952
43329:2
Probe 1 alarm. This can be a disconnected, open or shorted probe. This will shut down heating operation. This is Bit 2 of the ALARM STATUS ALL word. Flashes ‘P1’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0004 = 0x0004 Alarm is active. = 0x0000 Alarm is not active.
Page 22 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Alarm_P2
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_P2 nvoAlarm_P2_#
Status of Probe 1 Alarm
3328
332958
43329:8
Probe 2 alarm. This can be a disconnected, open or shorted probe. This is Bit 8 of the ALARM STATUS ALL word. Flashes ‘P2’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0100 = 0x0100 Alarm is active. = 0x0000 Alarm is not active.
Alarm_P3
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_P3 nvoAlarm_P3_#
Status of Probe 1 Alarm
3328
332959
43329:9
Probe 3 alarm. This can be a disconnected, open or shorted probe. This is Bit 9 of the ALARM STATUS ALL word. Flashes ‘P3’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0200 = 0x0200 Alarm is active. = 0x0000 Alarm is not active.
Alarm_AL1
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_AL1 nvoAlarm_AL1_#
Status of digital input #1 Alarm
3328 43329:10
332960
Digital Input #1 alarm. This is typically not implemented. Refer to product specific details for information on this alarm. This is Bit 10 of the ALARM STATUS ALL word. Flashes ‘AL1’ on TempTrac display. In BACNET and
LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0400 = 0x0400 Alarm is active. = 0x0000 Alarm is not active.
Alarm_AL2
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_AL2 nvoAlarm_AL2_#
Status of digital input #2 Alarm
3328 43329:11
332961
Digital Input #2 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 11 of the ALARM STATUS ALL word. Flashes ‘AL2’ or ‘LP’ on TempTrac display. In
BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0800 = 0x0800 Alarm is active. = 0x0000 Alarm is not active.
Alarm_AL3
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_AL3 nvoAlarm_AL3_#
Status of digital input #3 Alarm
3328 43329:12
332962
Digital Input #3 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 12 of the ALARM STATUS ALL word. Flashes ‘AL3’ or ‘HP’ on TempTrac display. In
BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x1000 = 0x1000 Alarm is active. = 0x0000 Alarm is not active.
Page 23 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Alarm_Nn1
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_Nn1 nvoAlarm_Nn1_#
Maintenance Alarm for output #1
3328
332963
43329:13
Maintenance Alarm. This is enabled when the time on ou1 is greater than the value in oP1. Flashes ‘Nn1’ on
TempTrac display. Bit #13 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x2000 = 0x2000 Alarm is active. = 0x0000 Alarm is not active.
Alarm_Nn2
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_Nn2 nvoAlarm_Nn2_#
Maintenance Alarm for output #2
3328
332963
43329:14
Maintenance Alarm. This is enabled when the time on ou2 is greater than the value in oP2. Flashes ‘Nn2’ on
TempTrac display. Bit #14 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x4000 = 0x4000 Alarm is active. = 0x0000 Alarm is not active.
Alarm_Nn3
MODBUS
BACNET
LONWORKS
Read Only
Holding Register
Alarm_Nn3 nvoAlarm_Nn3_#
Maintenance Alarm for output #3
3328
332963
43329:15
Maintenance Alarm. This is enabled when the time on ou3 is greater than the value in oP3. Flashes ‘Nn3’ on
TempTrac display. Bit #15 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x8000 = 0x8000 Alarm is active. = 0x0000 Alarm is not active.
Com Status
MODBUS
BACNET
LONWORKS
Read Only
Input Register
Gateway_TT_Com_OK nvoGwyTTCmOK_#
Communication Status bit
NA
200
NA
NOTE: This point is not generated by the heater; it is generated internally by the gateway. It is a status of the communication connection between the gateway and the heater. If active (GOOD), the gateway is talking to the heater. If inactive (NOT_PRESENT) then the gateway does not have good communication with the heater. This point may take up to 3 minutes to register properly after communication is established or interrupted. If this value if reading NOT_PRESENT, then no all over values are suspect, as the device is not communicating.
Generally the Gateway will hold the last value received. The only way to ensure you have the current values from the heater is to verify this point is ACTIVE as well.
Page 24 of 30 PV7069-T 03/17
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
ADVANCED MODBUS LIST:
The following is the direct MODBUS interface addresses. Descriptions of most to the MODBUS parameters are listed in the correlating TYPICAL POINTS defined previously. Many MODBUS parameters are not supported in the gateway interface. This is a complete reference list and contains advanced parameters. All MODBUS points normally required for interface are represented in the TYPICAL POINTS section. If there is a need for interfacing using other parameters, consult factory to confirm proper use.
Page 25 of 30 PV7069-T 01/05/16
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
Label Firm
St1
Version
0.3 & 0.5
Set point1
St2
0.3 & 0.5
Set point2
St3
0.3 & 0.5
Set point3
St5
0.3 & 0.5
Description
Set point5 Set point 3 alternate
HY1
0.3 & 0.5
Differential for St1
LS1
0.3 & 0.5
Minimum set point1
US1
0.3 & 0.5
Maximum set point1
AC1
0.3 & 0.5
Anti-short cycle delay for output 1
S2c
0.3 & 0.5
HY2
0.3 & 0.5
Configuration of St2: dependent on St1 or independent
Differential for St2
LS2
0.3 & 0.5
Minimum set point2
uS2
0.3 & 0.5
Maximum set point2
AC2
0.3 & 0.5
Anti-short cycle delay for output 2
S3c
0.3 & 0.5
HY3
0.3 & 0.5
Configuration of St3: dependent on St1 or independent
Differential for set point 3 St3
LS3
0.3 & 0.5
Minimum set point 3 St3
uS3
0.3 & 0.5
Maximum set point 3 St3
AC3
0.3 & 0.5
Anti-short cycle delay for output 3
o3P
0.3 & 0.5
Probe selection for output 3
SSE
0.3 & 0.5
Set point shift for output 3 enable disable
HY5
0.3 & 0.5
Differential for set point 5
Ac5
0.3 & 0.5
Anti-short cycle delay for output 3 alternate set point
AcA
0.3 & 0.5
Time delay between the St3 to St5 set point shift diP; ind
-22÷22°F
-40°F÷St2
St2 ÷ 230°F
0÷30 min. diP; ind
-22÷22°F
-40°F÷St3
St3 ÷ 230°F
0÷30 min.
Pb1 / Pb2
No; Yes
-22÷22°F
0÷30 min.
0÷15 min.
Range
X÷Y
LS1÷US1
LS2÷US2
LS3÷US3
-20÷70°F
-22÷22°F
-40°F÷SET
SET ÷ 230°F
0÷30 min.
S4c
St4
SR
Th4
ANALOGUE OUTPUT 4÷20mA (output 4)
Configuration of St4: dependent on St1 or
0.3 & 0.5 independent
0.3 & 0.5
Analogue output set point
0.3 & 0.5
Analogue output band width
0.3 & 0.5
Outlet temperature threshold for forcing to 4ma the analog output
Differential for restart working of analog output
HY4
0.3 & 0.5
Ac4
0.3 & 0.5
PS4
0.3 & 0.5
Anti-short cycle delay for output 4
Analog output percentage (nu=101)
PP4
0.3 & 0.5
Analog output percentage with fault probe 1
(nu=101)
tt rr2
DYNAMIC RESET
0.3 & 0.5
Outdoor temperature threshold for dynamic reset of
St1
0.3 & 0.5
Outdoor temperature band width diP; ind
-100÷100°F
-100÷100°F
-40°F ÷ 230°F
-45 ÷ -1 °F
0÷30 min.
0÷100, nu
0÷100, nu
-40÷230°F
-100÷100°F
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr3
Pr2
Pr2
Pr2
Pr2
Rev
0.3
Rev
0.5
Level Level
Pr1
Pr1
Pr1
Pr1
Pr2
Pr2
Pr2
Pr2
Pr1
Pr1
Pr1
Pr1
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
782
783
784
785
786
787
788
789
790
791
777
778
779
780
781
Register
40000+
769
770
771
772
773
774
775
776
0x308
0x309
0x30A
0x30B
0x30C
0x30D
0x30E
0x30F
0x310
0x311
0x312
0x313
0x314
0x315
0x316
Hex Add
Modbus
base 0
0x300
0x301
0x302
0x303
0x304
0x305
0x306
0x307
Pr3
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr3
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
0x317
0x318
0x319
0x31A
0x31B
0x31C
0x31D
0x31E
Pr2
Pr2
Pr2
Pr2
0x31F
0x320
792
793
794
795
796
797
798
799
800
801
Page 26 of 30 PV7069-T 01/05/16
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST rr1 tt2
Ht2 i1P i2P i2d i3P i3d cF rES dS2 dS2 dS1 dS1
Alc
ALL
ALL
Alu
Alu
AFH
ALd dAo
0.3 & 0.5
Maximum shift of St1
0.3 & 0.5
0.3 & 0.5
Outdoor temperature threshold to open all the loads
0.3 & 0.5
0.3 & 0.5
Differential for restart working of controller
DIGITAL INPUTS
0.3 & 0.5
Digital input 1 polarity
Digital input 2 polarity
Digital input 2 alarm delay
0.3 & 0.5
0.3 & 0.5
Digital input 3 polarity
Digital input 3 alarm delay
-100÷100°F
-40÷230°F
-45 ÷ -1 °F
CL÷OP
CL÷OP
0÷255 min.
CL÷OP
0÷255 min.
DISPLAY
0.3 & 0.5
Temperature measurement unit
0.3 & 0.5
Resolution (integer/decimal point) only for °C
0.3
Default showing for display #2 Top (red)
0.5
Default showing for display #2 Top (red) Pb3 will display yellow EXT, Ani will display yellow Valve/M
0.3
0.5
°C ÷ °F in ÷ de
Pb2, Pb3
Default showing for display #1 Bottom (Yellow)
Default showing for display #1 Bottom (Yellow) Pb3 will display yellow EXT, Ani will display yellow Valve/M
Pb1,Pb2,Pb3,AnI
Pb1; tiM
Pb1,Pb2,Pb3,AnI, TiM
ALARMS
0.3 & 0.5
Temperature alarms configuration: dependent on St1 or independent rE÷Ab
0.3
0.5 minimum temperature alarm for Pb1 (Alarm LA flash only) minimum temperature alarm for Pb1 (Alarm LA flash and signal on 3329)
-40÷230°F
-40÷230°F
0.3
0.5
MAXIMUM temperature alarm for Pb1 (Alarm HA flash only)
MAXIMUM temperature alarm for Pb1 (Alarm HA flash and signal on 3329)
-40÷230°F
0.3 & 0.5
0.3 & 0.5
0.3 & 0.5
Differential for temperature alarm recovery
Temperature alarm delay
Delay of temperature alarm at start up 1 = 10 min disp 0.1
-40÷230°F
1÷45°F
0÷255 min.
0 ÷ 23h 50 min.
oF1
ANALOGUE INPUTS
0.3 & 0.5
First probe calibration
Second probe presence
P2P
0.3 & 0.5
oF2
0.3 & 0.5
Second probe calibration
Third probe presence
P3P
0.3 & 0.5
oF3
0.3 & 0.5
Third probe calibration
-21÷21°F
No; Yes
-21÷21°F
No; Yes
-21÷21°F
TIME AND DATE
Pr2
Pr2
Pr2
Pr3
Pr3
Pr2
Pr2
Pr3
Pr2
Pr3
Pr2
Pr3
Pr3
Pr2
Pr2
Pr3
Pr3
Pr2
Pr2
Pr2
Pr3
Pr2
Pr3
Pr2
Pr3
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
0x321
0x322
0x323
0x324
0x325
0x326
0x327
0x328
0x32D
0x32E
0x32E
0x32F
0x32F
0x330
0x331
0x332
0x329
0x32A
0x32B
0x32B
0x32C
0x32C
0x333
0x334
0x335
0x336
0x337
802
803
804
805
806
807
808
809
820
821
822
823
824
810
811
812
812
813
813
814
815
815
816
816
817
818
819
Page 27 of 30 PV7069-T 01/05/16
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
Hur
Min
0.3 & 0.5
0.3 & 0.5
dAY
0.3 & 0.5
Current hour
Current minute
Current day
E1
S1
ENERGY SAVING TIMES
0.3 & 0.5
0.3 & 0.5
Sb1
0.3 & 0.5
Energy saving start on Sunday
Energy saving stop on Sunday
Set back temperature on Sunday
E2
S2
0.3 & 0.5
0.3 & 0.5
Energy saving start on Monday
Energy saving stop on Monday
Set back temperature on Monday
Sb2
0.3 & 0.5
E3
0.3 & 0.5
Energy saving start on Tuesday
S3
0.3 & 0.5
Energy saving stop on Tuesday
Set back temperature on Tuesday
Sb3
0.3 & 0.5
E4
0.3 & 0.5
Energy saving start on Wednesday
S4
0.3 & 0.5
Energy saving stop on Wednesday
Set back temperature on Wednesday
Sb4
0.3 & 0.5
E5
0.3 & 0.5
Energy saving start on Thursday
Energy saving stop on Thursday
S5
0.3 & 0.5
Sb5
0.3 & 0.5
Set back temperature on Thursday
E6
S6
0.3 & 0.5
0.3 & 0.5
Energy saving start on Friday
Energy saving stop on Friday
Set back temperature on Friday
Sb6
0.3 & 0.5
E7
0.3 & 0.5
Energy saving start on Saturday
S7
0.3 & 0.5
Energy saving stop on Saturday
Sb7
0.3 & 0.5
Set back temperature on Saturday
ou1 ou2 ou3 oP1 oP2 oP3
WORKING HOURS
0.3 & 0.5 working hours actual of relay 1
0.3 & 0.5 working hours actual of relay 2
0.3 & 0.5 working hours actual of relay 3
0.3 & 0.5
0.3 & 0.5
0.3 & 0.5 working hours limit of relay 1, Nn1 Alarm when reached working hours limit of relay 2, Nn2 Alarm when reached working hours limit of relay 3, Nn3 Alarm when reached
1on
2on
3on
OUTPUTS SETTING
The output 1 force ON / OFF or Temperature
0.3 & 0.5 regulation
0.3 & 0.5
0.3 & 0.5
The output 2 force ON / OFF or Temperature regulation
The output 3 force ON / OFF or Temperature regulation
OTHER
0 ÷ 23
0 ÷ 59
Sun ÷ SAt
0 ÷ 23h 50 min. - nu
0 ÷ 23h 50 min. - nu
-40÷40°F
0 ÷ 23h 50 min. - nu
0 ÷ 23h 50 min. - nu
-40÷40°F
0 ÷ 23h 50 min. - nu
0 ÷ 23h 50 min. - nu
-40÷40°F
0 ÷ 23h 50 min. - nu
0 ÷ 23h 50 min. - nu
-40÷40°F
0 ÷ 23h 50 min. - nu
0 ÷ 23h 50 min. - nu
-40÷40°F
0 ÷ 23h 50 min. - nu
0 ÷ 23h 50 min. - nu
-40÷40°F
0 ÷ 23h 50 min. - nu
0 ÷ 23h 50 min. - nu
-40÷40°F
0÷9999 Hours
0÷9999 Hours
0÷9999 Hours
0÷9999, 0=disabled
0÷9999, 0=disabled
0÷9999, 0=disabled rEG=2; on=1; oFF=0 rEG=2; on=1; oFF=0 rEG=2; on=1; oFF=0
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr1
Pr1
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
0x338
0x339
0x33A
0x350
0x351
0x352
0x353
0x354
0x355
0x33B
0x33C
0x33D
0x33E
0x33F
0x340
0x341
0x342
0x343
0x344
0x345
0x346
0x347
0x348
0x349
0x34A
0x34B
0x34C
0x34D
0x34E
0x34F
0x356
0x357
0x358
825
826
827
834
835
836
837
838
839
840
828
829
830
831
832
833
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
Page 28 of 30 PV7069-T 01/05/16
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
Adr
Ptb rEL i1S i1t i1d i1F i2F i3F
0.3 & 0.5
0.3 & 0.5
0.3 & 0.5
0.5
0.5
0.5
0.5
0.5
0.5
oS2
0.5
(TP1)
0.3 & 0.5
0.3
(TP2)
0.3 & 0.5
0.3
(TP3)
0.3 & 0.5
0.3
0.5
0.3 & 0.5
0.3
0.3
0.3
0.5
0.5
0.5
0.5
0.5
0.5
Serial address
Parameter map code always = 1
Software release 5 = V0.5, 3 = V0.3
Analog output when Digital Input 1 is activated
Analog output at i1S extra time if Digital Input 1 is not activated
0÷247 readable only readable only
4-20mA
Digital Input 1 Alarm Delay
If Yes, Digital Input 1 will function as Alarm. Operating only when trying to call for output 1 and Input 1 is active, subject to i1d timer
0÷30 sec.
0÷255 min.
No; Yes
Digital Input 2 will function only when Output 1 is energized
Digital Input 3 will function only when Output 1 is energized, When Edi is selected, Output 1 will open when digital input 3 is activated
No; Yes
Output 2 function: either temp relay or alarm relay
Probe 1 temperature
Probe 1 Information/Status Normal=512 or 0x0200,
Fault=515 or 0x0203. Fault will, drop call for heat, buz,
Flash Yellow P1, light yellow valve/M
No; Yes; Edi
Std; AL
Degrees F/C
Probe 2 temperature
Probe 2 Information/Status Normal=512 or 0x0200,
Fault=515 or 0x0203. Fault will buz, Flash Red P2 bit (0,1 on) probe failure
Degrees F/C
Probe 3 temperature
Probe 3 Information/Status Normal=512 or 0x0200,
Fault=515 or 0x0203. Fault will buz, Flash Red P3 bit (0,1 on) probe failure
Degrees F/C
Modulation rate output (4 to 20mA)
Statas of Relay 1,2&3
Input 3 Alarm, buz, ALMMB, Flashes HP= 4096 or
0x0800
Input 2 Alarm, buz, Flashes LP= 4096 or 0x0800
Input 2 & 3, buz, Flashed HP & LP= 4096 or 0X0800
Low Temperature Alarm, beep, Flash Yellow LA= 1 or
0x0001
High Temperature Alarm, beep, Flash yellow HA= 2 or
0x0002
Probe 1 error, open or shorted, Drops call for heat, yel valve/M on, Flash Yellow P1=4 or 0x0004 bit (0,1 on) probe failure
0÷100% bit 0,1,2 bit # 12 or 13th bit bit # 12 or 13th bit bit # 12 or 13th bit bit # 0 or 1st bit bit # 1 or 2nd bit bit # 2 or 3rd bit
Probe 2 error, open or shorted, Flashing red P2=256 or 0x0100
Probe 3 error, open or shorted, Flashing red P3=512 or 0x0200
ALARM 1 (stops heating) Input 1, beep, Flash AL1 =
1024 or 0x0400. Will recover if Input 1 goes away, or need for call for heat goes away bit # 8 or 9th bit bit # 9 or 10th bit bit # 10 or 11th bit
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
0x359
0x35A
0x35B
0x35C
0x35D
0x35E
0x35F
0x360
864
865
0x361
0x362
0x100
866
867
257
0xD00 3329
0x101
0x102
0x103
0x104
0x105
0x106
0x801
0xD00
0xD00
0xD00
0xD00
0xD00
0xD00
0xD00
0xD00
858
859
860
861
862
863
262
263
2050
3329
3329
3329
3329
3329
3329
3329
3329
258
259
260
261
Page 29 of 30 PV7069-T 01/05/16
Part number 129209
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
0.5
0.5
0.5
0.5
0.5
0.3 & 0.5
0.3 & 0.5
0.3 & 0.5
ALARM 2 (Lockout, stops heating) Input 2, Flash AL2 &
Lguage & valve= 2048 or 0x1000 bit # 11 or 12th bit
ALARM 3 (Lockout, stops heating) Input
3/ALMMB/ALOAF, beep, Flash AL3 & Hguage & valve
(This is ALARM ON ANY FAILURE)= 4096 or 0x0800 bit # 12 or 13th bit
Maintenance Relay1, beep, Flash Nn1 & wrench=8192 or 0x2000 You must reset hours ou1 or set oP1=0
Maintenance Relay2, beep, Flash Nn2 & wrench=16384 or 0x4000 You must reset hours ou2 or set oP2=0
Maintenance Relay3, beep, Flash Nn3 & wrench=32768 or 0x8000 You must reset hours ou3 or set oP3=0
On/Off On=257 or 0x0101, Off=1 or 0x0001 Can be used to reset ALMMB alarm by cycling OFF, wait 30 sec , ON
Keyboard Lock Lock=2056 or 0x0808, Unlock=8 or
0x0008. If locked PoF is displayed when keypad edit is attempted
Reset audible alarm when condition is corrected,
4112 or 0x1010 does not reset alarm, just stops the beeping
Energy Savings Registers are enumerated 0 to 145 w/145=n/u
10 min each with 145=nu
All other enumerations start at 0 and count up bit # 13 or 14th bit bit # 14 or 15th bit bit # 15 or 16th bit
Low byte is mask, Hi byte is command. Bit # 0 & #8
Low byte is mask, Hi byte is command. Bit # 3 &
#11
Low byte is mask, Hi byte is command. Bit # 3 &
#12
Pr2
0xD00 3329
Pr2
Pr2
Pr2
0xD00
0xD00
0xD00
0xD00
Pr2
Pr2
0x500
0x500
1281
1281
Pr2
Pr2
0x500 1281
3329
3329
3329
3329
Page 30 of 30 PV7069-T 01/05/16
Part number 129209
advertisement
Key Features
- Simple and intuitive user interface for easy setup and operation
- Built-in diagnostics and alarms for proactive maintenance
- Flexible communication options for easy integration with Building Automation Systems (BAS)
Related manuals
Frequently Answers and Questions
What types of communication options does the TempTrac support?
Can I monitor and control the TempTrac remotely?
What is the default MODBUS address for the TempTrac?
advertisement
Table of contents
- 2 OVERVIEW OF INTERFACE METHODS
- 4 TEMPTRAC PROTOCOL
- 4 ITEMS REQUIRED FOR GATEWAY INTERFACE
- 4 ITEMS REQUIRED FOR MODBUS DIRECT INTERACE
- 5 IDENTIFY EQUIPMENT
- 6 WIRING BAS TO GATEWAY AND THEN GATEWAY TO TEMPTRAC
- 7 WIRING OF TEMPTRAC TO BAS (Direct, no Gateway)
- 7 GATEWAY CONFIGURATION CONNECTION
- 8 CONFIGURE GATEWAY DIP SWITCHES
- 9 CONFIGURE THE GATEWAY USING THE HTML INTERFACE
- 10 CONFIRM OPERATION
- 10 TROUBLESHOOTING GATEWAY
- 11 HOOKUP OVERVIEW
- 12 APPLICATION SPECIFICS
- 16 POINTS LIST
- 16 TYPICAL POINTS
- 18 ALL POINTS INCLUDING ADVANCED
- 25 ADVANCED MODBUS LIST