MultilinD20MX - GE Grid Solutions

Multilin D20MX
Simple to Advanced Substation Automation Control
Economical Life Extension
Distribution and transmission industries are under pressure to ensure that their grids are reliable and to
prolong the usability of their assets. Data from these assets can be collected, aggregated and processed,
to provide visibility of system conditions. The MultilinTM D20MX Substation Controller is a specialized
computing platform designed to execute communications and energy management applications for the
monitoring and control of electrical substations. The D20MX is capable of amalgamating data from multiple
slave devices and D20 I/O modules connected via communication channels into a single database using
various protocols. The D20MX can execute local logic, compile data, process it through one of multiple
applications and report the results upstream to master stations through different server protocols.
• Backward compatible with earlier D20/D200
RTU chassis. simplifying upgrades and reducing
associated time and costs
The D20MX represents the next innovation in GE’s cyber secure RTU technology for NERC-CIP
environments. The D20MX is built upon the field-proven Multilin D20 technologies and continues the
tradition of reliable automation and control through high quality and long term product availability.
Key Benefits
• Reduces legacy D20/D200 RTU upgrade expenditures by over 50% through backwards compatibility
with existing D20/D200 installed accessories, such as chassis, modems and D20 I/O peripheral modules
• Minimizes operation and maintenance costs of existing D20-based SCADA infrastructure by leveraging
existing designs, processes and infrastructure
• Introduces a new and modern network security feature suite that enables effective compliance with
NERC® CIP requirements through the application of native cyber security features built into the D20MX
Substation Controller
Applications
Data Concentrator
Automatically consolidates collected information from intelligent electrical devices (IEDs), such as relays
and meters, and communicates to SCADA, EMS, DMS and Data Historian systems
Protocol Converter
Translates different data message formats between devices to support interoperability
Local Automation Platform
Implements popular distribution automation applications such as capacitor bank control, outage
prevention programs, feeder resource optimization and control interlocking, inhibition and subgrouping
• Modular hardware platform combines
functions onto a single board, eliminates addon expansion memory cards and cables, and
decreases service time and maintenance effort
• Employs super capacitors, extending
operation and availability, retaining system
clock and eliminating the need to plan for and
replace dead batteries
Cyber Security and
Risk Management
• Supports Cyber-Ark functionality for remote
access & open standard cyber security
features for NERC/CIP interoperability
• Syslog integration into enterprise system
assists with audit compliance
• SSH and SFTP provide secure firmware and
configuration file transfer
• Secure flash delete of customer information
- No need to return D20MX to factory for
re-imaging
Flexible and Reliable
• Configurable redundant and dual LAN options
with built-in dual Ethernet communication ports
• Alias IP address provides simultaneous
communications with both redundant and
dual LAN devices
• Multiple and simultaneous SCADA protocols
for communication to multiple masters
• Supports up to 35 serial ports all with full
modem control
• Supports up to 32 secondary IP addresses
D20MX Substation Controller
Advanced Controller
The Multilin D20MX Substation Controller collects, filters, and sorts data from a wide range of intelligent devices (RTUs, relays, meters) in the substation. The
D20MX preserves original data time stamps for accurate sequence of event (SOE) logs, allowing data from large diverse geographic regions and time zones to
be analyzed in extreme detail. Data can be presented simultaneously to multiple SCADA hosts. The D20MX comes with a built-in suite of protocols and security
applications to facilitate integration with various substation devices and SCADA hosts.
D20MX is the sixth generation of D20 CPUs designed to provide a smooth migration path for D20 users to extend the life of aging D20 systems. It introduces a
new and modern network security feature suite that enables effective compliance with NERC-CIP requirements, using open and trusted standards and protocols
that allow integration with modern cyber security systems and tools.
Advanced Substation Controller Connectivity
Sample Enterprise Protocols:
• DNP3 serial and Ethernet [TCP/UDP/IP]
• Tejas V
• HR6000/XA-21
SCADA
• Modbus serial (RTU or ASCII)
EMS
DMS
DATA HISTORIAN
• IEC 101/104
• LG-8979
• PG&E
D20MX Media Connectivity:
• 7 - 35 serial ports (RS232)
• Built-in dual Ethernet ports
Multilin D20MX
• (10/100/1000 Base TX or 100 Base FX)
Dual D.20 communication ports
Sample Device Protocols:
Ethernet Switch
• DNP3 serial and Ethernet[TCP/UDP/IP]
• Modbus serial (RTU or ASCII)
• IEC 101/104
• SEL
• IRIG-B support
Bay Controllers
Protection Relays
IEDs/Meters
D20MX Controller Main Connectivity Applications
GE P/N
B021-0
B021-0
A068
A033-5
A185-0
A009
A101-0
A003
A135-0
A023
SERVER PROTOCOLS [DPA]
DNP3 DPA
DNP3 DPA
Modbus DPA
Tejas V DPA
LG 8979 DPA
PG&E DPA
IEC 60870-5-101/104 DPA
Harris 6000/XA-21 DPA
Modbus TCP/IP DPA
CDC TYPE I DPA
GE P/N
B023-0
A059
A078-0
B060-0
A131-0
A018
A194-0
B080-0
A098
A074
CLIENT PROTOCOLS [DCA]
DNP3 DCA
Modbus DCA
SEL DCA
IEC 60870-5-101/104 DCA
Modbus TCP/IP DCA
Quantum Meter Scanner DCA
COOPER 2179 DCA
IEC 60870-5-103 DCA
COURIER DCA
PML DCA
2
V1.1
•
•
•
•
V1.2
V1.3
V1.4
•
•
•
•
•
•
V1.1
•
•
V1.2
V1.3
V1.4
V1.5
•
•
•
•
•
•
•
•
GE P/N
A030
A035
A118
A184-0
B009
A123-0
A113
DATA TRANSLATION APPLICATIONS [DTA]
Accummulator Freeze DTA
Analog Reference DTA
Failover DTA
General Alarm DTA
Mailbox DTA
NGC General DTA
Programmable Synchro Check Relay DTA
A036
A027
A088-0
A027-1
A083-0
A195
B099-0
B082-0
A041-1
Prologic Executor DTA
SOE Logger DTA
Substation Maintenance DTA
Communications Watchdog
Calculator DTA
Redundant I/O DTA
SNTP Client DTA
LogicLinx Executor DTA
Proportional Integrator Derivative Control DTA
B148
A017
A161-0
A121-0
A048
A104-0N
A193-0
A186-0
B119-1N
A065
A064
Time Zone and DST Setting DTA
DNP V1.00 DATA LINK DTA
Secondary Master Trip/Close DTA
Automatic Frequency Selection DTA
Status Combination DTA
Alarm Grouping DTA
Top of the Hour Analog Averaging DTA
Western Power Distribution (WPD) DTA
LAN Redundancy Manager DTA
CL&P DTA
TAP POSITION INDICATION DTA
GEDigitalEnergy.com
V1.1
•
•
•
•
•
•
•
V1.2
V1.3
V1.4
V1.5
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
D20MX Substation Controller
D20MX Classic and Advanced Automation Applications
APPLICATION ID
NAME
APPLICATION ID
D20MX CLASSIC APPLICATIONS
NAME
D20MX CLASSIC APPLICATIONS
A009
PG&E DPA
A041-1
Proportional Integrator Derivative Control DTA
A033-5
Tejas V DPA
A018
Quantum Meter Scanner DCA
A036
Prologic Executor DTA
A023
CDC Type I DPA
A113
Programmable Synchrocheck Relay DCA
A017
DNP V1.00 Data Link DTA
A185-0
8979 DPA
A194-0
COOPER 2179 DCA
D20MX ADVANCED AUTOMATION APPLICATIONS
A199-0
HR6000/XA-21 DPA
B082-0
Upgrade of Legacy D20/D200 RTUs
Logiclinx Executor DTA
D20MX Upgrade Process
The Multilin D20MX is more than an RTU. It’s a commitment to the ongoing
long term availability of GE’s automation products. Utilities have large
investments in hardwired automation systems.
Like everything else, this industrial equipment has a lifecycle that moves
from infancy to normal operation, and eventually to the wear out stages. As
a piece of equipment ages it fails more frequently, takes longer to repair, and
eventually reaches the end of its life. Re-design and forklift replacements
require utilities to re-engineer substation designs, replace field wiring, and
retrain staff to manage and maintain the system, which is a costly endeavor.
INSTALLATION COST
The Multilin D20MX provides a cost-effective alternative to upgrades of legacy
D20/D200 RTUs. This means that the investments made in GE’s automation
systems keep paying dividends beyond their originally projected end of life.
Simply replace the failed or end of life Multilin D20 processor module with a
Multilin D20MX and migrate the device configuration to extend the life of the
existing D20 Controller. Add cyber security features for integration into NERCCIP environments. As technology changes with market demands, GE continues
to invest in a partnership with their customers through advanced modular
design principals.
RTU UPGRADE SOLUTION
D20MX UPGRADE SOLUTION
Full replacement of existing
D20/D200 Unit and existing
I/O modules
Upgrade CPU to D20MX
•Retain existing I/O modules
•Retain I/O infrastructure
•Migrate to modern technologies
Modify field wiring
Yes
Not required
Modify engineering drawings
Yes
Not required
Building expansion
May be required
Not required
Marshaling panels
May be required
Not required
OutagesOUTAGES
Yes
Minimal
Modify operation processes
Yes
Not required
Retrain operations
personnelR
Yes
Minimal
Built-in cyber security
features
Unknown
Yes
Proprietary solutions
Unknown
Modern open industry
standards
MAINTENANCE
CYBER SECURITY
Integration of D20 Substation Controllers into NERC-CIP Environments
If one of the current users of your D20MX leaves your company, you can
lock down access to all the devices in your network from a central location.
That user instantly loses access to every D20MX, while other users remain
able to do their jobs without any adverse effects and costly password
change programs.
The Multilin D20MX supports a comprehensive set of security functions to
allow a seamless integration with existing IT department policies. Built-in
cyber security features, such as Remote Authentication Dial-In User Service
(RADIUS), Role Based Access Control (RBAC), and user activity logging, provide
a complete security toolkit required to enable effective compliance with
NERC-CIP requirements, using open and trusted standards and protocols,
that allow integration with modern cyber security systems and tools.
AAA Network Access
RADIUS
Radius servers use the AAA concept to manage network access by following
a few steps referred to as AAA transactions.
RADIUS is a client/server networking protocol that provides centralized
authentication, authorization, and accounting (AAA) management for
computers to connect and use a network service. With RADIUS each user in
your system has their own unique identification login, allowing you to control
who gets access to what devices from where. RADIUS provides centralized
AAA management for computers to connect to the D20MX.
Authentication
The user sends a request to gain access to a particular resource using access
credentials, typically, in the form of user name and password.The RADIUS
server verifies the user’s credentials and accepts or rejects access. The
D20MX supports primary and secondary RADIUS servers. If for any reason
the D20MX is not able to authenticate the user against the RADIUS servers,
the D20MX verifies the user’s credentials against a local password file.
GEDigitalEnergy.com
3
D20MX Substation Controller
Authorization
In a typical centralized user authentication system, access terms are defined
on a per user basis. For example, the following authorization attributes may
be associated for a specific user:
• Specific D20MX IP address to be accessed by the user
• Role ID assigned to the user, where role ID defines which commands and
displays the user is able to access on the D20MX
• Allowed time-of-day during which users can access the network
Accounting
When access is granted to the user, their activity can be registered for
security, system integrity monitoring and statistical purposes. For example,
the following user’s activity can be recorded:
DESCRPTION
ADMIN
ENGINEER
OPERATOR
OBSERVER
CAN CHANGE
PASSWORD
YES
NO
NO
NO
CAN CLEAR LOGIN
BUFFER
NO
NO
NO
NO
CAN CHANGE SCADA
YES
YES
NO
NO
CAN DOWNLOAD
FIRMWARE
YES
YES
NO
NO
CAN PERFORM
OPERATIONAL
CONTROL
(E.G.: BREAKER
OPERATIONS)
YES
YES
YES
NO
CAN VIEW
OPERATIONAL DATA
YES
YES
YES
YES
• User information
• Login time stamp
Advanced Automation
• Logout time stamp
The D20MX provides accounting information by logging the user’s activity to
a remote syslog server.
RBAC
RBAC is achieved using RADIUS or the D20MX’s internal database, ensuring
only authenticated and authorized users gain access to the system.
When you configure the D20MX to use RADIUS, each D20MX user is
identified by a role ID, which is an integer number provided by the RADIUS
server. The D20MX makes your life easier by including a pre-configured
default RBAC model.
When using RADIUS, revoking user privileges system-wide is as simple as
updating the centralized user database, saving you time and money.
Since releasing the first generation D20 back in 1988, GE’s automation
experts have learned a lot. Through challenging projects and installations
across the globe, the D20 has evolved into a leader in substation automation.
The culmination of that experience is the sixth generation, the Multilin
D20MX. The following are a sample of the advanced automation features
available today.
Substation Maintenance
If there is one thing operators hate, it’s false alarms. The D20MX can
suppress reporting of input points while they are unavailable during
maintenance. This allows users to disable groups of analog and digital input
points by ignoring their actual data and quality changes within selected
applications. While points are suppressed, a predefined suppression value
and the point suppression quality flag are provided instead. This is useful
during maintenance operations to prevent spurious OFFLINE alarms and
inaccurate readings while devices are powered off or disconnected during
the execution of maintenance activities.
Centralized Authentication and Authorization
USER
1. Login attempt
D20MX
NETWORK CONNECTION
2. D20MX RADIUS client sends user’s
credentials to RADIUS server
3. Valid user – RADIUS server accepts user
4. Invalid user – RADIUS server rejects user
4
GEDigitalEnergy.com
RADIUS SERVER
D20MX Substation Controller
Accumulator Freeze
Monitoring constantly incrementing and changing values, such as time of
use, and energy consumption across a system, makes accurate comparisons
of data a time-consuming effort. GE’s accumulator freeze application
simplifies this process automatically by capturing the instantaneous value
of accumulator records across the system at the same point in time, giving
engineers and operators a clear understanding of the state of their system.
A popular example of the use of accumulators is energy metering, where
pulse streams from meter pulse generators is proportional to energy flow.
This feature allows users to define groups of accumulator points whose
values are frozen periodically or on demand.
Alarm Management
The D20MX manages alarms based on real substation experience. This
application allows user-defined logical grouping of individual digital inputs
to generate general alarms based on the status of the signals monitored
within each group. Alarm groups are user-definable, with up to 32766
groups allowed. Status inputs may belong to as many groups as required.
The great flexibility of this application ensures that each group has its own
meaningful description and configurable latching or non-latching operation
modes. Latching alarms require operator acknowledgement for optimized
management of critical conditions in the system.
System Redundancy
Although the D20 family of RTUs is legendary for quality, GE has prepared
for those rare cases when a processor is unable to function. Through time
tested and utility accepted redundancy mechanisms, the D20MX is designed
for high availability requirements. In redundant processor mode, one device
stands waiting, ready to take over, should the other unit stop functioning.
Dual D20MX units can be deployed, creating a redundant system where
accumulators are automatically synchronized between the two systems and
configurations are synchronized on demand. Serial communication links are
automatically switched between the units based on system health.
The D20MX has redundant Ethernet , enabling automatic switchover
between two sets of Ethernet switches, ensuring there is no single point of
failure in the system.
Control Lockout
The control lockout feature ensures that only a single master station can
access a group of controls at one time, and can lock out groups of controls
to allow for safer local maintenance. Users can create custom control
groups. Any digital output can be included in any control group.
Analog Inputs Monitoring
GE’s analog reference provides enhanced and simplified monitoring of
analog input monitoring equipment. Operators define a reference value
used to compare against monitored signals. The application reports failures
in analog input hardware, allowing effective maintenance of the monitoring
devices, reduced downtime and increased reliability of the system.
SGConfig Setup Software
The Multilin SGConfig software integrates support for the complete portfolio
of GE’s Substation Controllers, including the D20MX series. The SGConfig
software introduces an updated graphical user interface while maintaining
configuration processes and workflows available in the ConfigPro
setup software.
Convenient access to product documentation and screencasts is provided
directly from the SGConfig software. (Screencasts are short instruction
videos on popular setup processes.)
Typical Architecture for Redundant D20 Substation Control System
SCADA Masters
WAN
RS232 Switch
D20MX
D20MX
RS232 Communications
WIRED I/O
Ethernet Switch A
LAN A
LAN B
Substation IED
Substation IED
Substation IED
Ethernet Switch B
GEDigitalEnergy.com
5
D20MX Substation Controller
Hardware Overview
Fully Equipped Out-of-the Box
Backwards Compatibility
Previous generations of D20/D200 RTUs required add-on system components
and software to support Ethernet communications and optional memory
expansion. The new D20MX is equipped by default with integrated memory,
10/100/1000BASE-TX or 100BASE-FX IEEE 802.3 compliant communications
and a core load firmware with a comprehensive set of key substation
automation applications.
The Multilin D20MX is an embedded single board computer powered by
a 667 Mhz PowerQUICC II Pro processor pin-for-pin compatible unit with
existing D20 processors and accessories, such as chassis, D20 remote I/O
peripherals, modems.
PCI mezzanine card site
for future expansion
Built-in 2 x 10/100/1000BaseTX or
2 x 100Base FX Ethernet ports
Compatible with classic D20
and D200 chassis
Super capacitor enables
maintenance-free, battery-less
operation
6
GEDigitalEnergy.com
Integrated CPU, memory, Ethernet
in a single D20MX processor
D20MX Substation Controller
Technical Specifications
SYSTEM
PROCESSOR:
ELECTRICAL
667 MHz embedded PowerQUICC II Pro
MEMORY
• 1024 MB of 266 MHz DDR2 RAM with ECC
• 16 MB NVRAM for persistent event storage
STORAGE
• 8 MB boot flash
• 256 MB firmware flash
OPERATING SYSTEM: VxWorks
LED INDICATORS
System status:
Power, Ready
Ethernet port status: Link and Activity status per port
Power supply:
Power
IRIG:
Flashes when active
COMMUNICATIONS
ENVIRONMENTAL
RATED POWER SUPPLIES
AC-DC: 100 to 240 V AC (±10%) 143 W
output maximum
Minimum/Maximum AC voltage:
90V AC / 265 V AC
100 to 300 V DC (±10%) 143 W output maximum
Minimum/Maximum DC voltage:
88 V DC / 330 V
DC
DC-DC: 20 to 55 V DC (±10%) 135 W maximum
Minimum/Maximum DC voltage:
18 V DC / 60 V DC
PEAK INRUSH CURRENT AT 25 °C ON COLD START
AC-DC :
50 A, max at 230 V AC
DC-DC: 50 A, max at 230 V AC
RATED FREQUENCY:50/60 Hz nominal (47 to 63 Hz)
(AC/DC)
NETWORK CONNECTIONS
• Dual redundant Ethernet interface
• Twisted Pair
• 10/100/1000BaseTX (Isolated RJ-45 connector)
• 100BaseFX (Fiber Optic: 1300 nm, 50/125 µm,
62.5/125 µm multi-mode duplex fiber cable, ST
connectors)
SERIAL COMMUNICATIONS
• D.20 Link, 2 channels
• Data rate: 250 kbps
• Surge protected to ±2000 V peak
RS-232, 7 CHANNELS
• 5-signal (TXD, RXD, RTS#, CTS#, DCD#) DTE ports
• Data rate: independently-selectable; refer to the
application configuration guides.
MAINTENANCE PORT
PHYSICAL
OVERALL HEIGHT:
40.34 mm (1.588 in.)
WIDTH:
261.87 mm (10.31 in.)
DEPTH:
160 mm (6.3 in.)
D20MX WEIGHT:
0.7 kg (1.65 lb.)
FIBER CARD WEIGHT:
0.2 kg (0.35 lb.)
OPERATING TEMPERATURE:0°C to +70°C
Note: Do not operate the D20MX above 60°C for extended
periods of time as this will shorten the life of the super
capacitor and reduce the backup time of the real time clock.
HUMIDITY RATING:5% to 95% relative humidity,
non-condensing
ENVIRONMENTAL RATING
INGRESS PROTECTION: IP30 (IEC 60529)
INSTALLATION/OVERVOLTAGE CATEGORY: CAT II (2)
POLLUTION DEGREE:2
USE: Indoor use only
OPERATING ALTITUDE:Maximum altitude 3000 m [9480
feet] above sea level
MTBF (MIL-HDBK-217): D20MX Processor Board
• Non-VME with 10/100/1000BASE-TX copper:
449,616 hours at 40°C
• Non-VME with 100BASE-FX fiber optic: 265,657
hours at 40°C
SOFTWARE
CONFIGURATION: Performed using SGConfig 7 and
higher
BATTERY SHIPPING RESTRICTIONS
The D20MX does not contain a battery and is therefore not
affected by US DOT or ICAO shipping restrictions.
MATERIAL/FINISH:Galvannealed steel with black power
coat
KIT PACKAGE
LENGTH:
WIDTH:
49.5 cm (19.5 in.)
34.3 cm (13.5 in.)
HEIGHT:
15.2 cm (6 in.)
WEIGHT:
2.54 kg (5.6 lb.)
• RS-232, 1 channel/ 2 ports
• 2-signal (TXD, RXD)
• Data rate: 19200 (default)
GEDigitalEnergy.com
7
D20MX Substation Controller
Standards & Protection
EMISSION
EN55011 (CISPR 11)
ISM RF equipment – Electromagnetic disturbance characteristics
Radiated Emissions 30 MHz to 1 GHz
Conducted Emissions 150 kHz – 30 MHz
IMMUNITY
IEC 61000-4-2
Electrostatic discharge (ESD) immunity test
IEC 61000-4-3
Radiated, radio-frequency electromagnetic field immunity test
IEC 61000-4-4
Electrical fast transient/burst immunity test
IEC 61000-4-5
Surge immunity test
IEC 61000-4-6
IEC 60255-22-6
Immunity to conducted disturbances, induced by radio-frequency fields
IEC 60255-22-1
1 MHz burst immunity test
IEC 61000-4-8
Power frequency magnetic field immunity test
IEC 61000-4-9
Pulse magnetic field immunity test
IEC 60255-22-1
Damped Oscillatory and Ring wave
IEC 61000-4-11
Voltage dips, short interruptions and voltage variations immunity tests
IEC 61000-4-16
Test for immunity to conducted, common mode disturbances in the
frequency range 0 Hz to 150 kHz
IEC 61000-4-17
Ripple on DC input power port immunity test
IEC 61000-4-29+
Voltage dips, short interruptions and voltage variations on DC input power
port immunity test. This standard only applies when using high voltage DC
as the source (100 V DC to300 V DC).
SAFETY
EC 61010-1
Safety requirements for electrical equipment for measurement, control
and laboratory use - General requirements
IEC 60255-5
Insulation coordination for measuring relays and protection equipment –
Requirements and tests
Dielectric and Resistance measurements not applicable due to
design (TVS in circuit)
IEC 60068-2-1
Cold
2 hours non powered, soak at -40 °C, then warm to -20 °C and
leave powered for 16 hours
IEC 60068-2-22
Dry Heat
16 hours powered at +70 °C
IEC 60068-2-6
Vibration (sinusoidal)
A logarithmic sweep from 10 Hz to 150 Hz to 10 Hz at
1 oct/ min for 1 sweep cycle in the 3 orthogonal axes.
Acceleration level 1 g
IEC 60068-2-27
Shock - Operating Response Test Shock - Non-Operating With - Stand Test
Pulse shape: Half sine Pulse duration: 11 ms
• Operating Response Test: Acceleration level: 5 g’s
ENVIRONMENTAL
• Non-Operating Withstand Test: Acceleration level:15 g’s
• 3 pulses per polarity per axis for a total of 18 pulses
IEC 60068-2-29
Bump – Non operating test
Pulse shape: Half sine Pulse duration: 11 ms
Acceleration level: 10 g’s 1000 pulses per polarity per
axis for a total of 6000 pulses
IEC 60068-2-30
Damp heat, cyclic (12 h + 12 h cycle)
Dropping on each face Dropping on each corner
IEC 60068-2-31
Drop and topple
Toppling (or pushover) For a total of 12 drops
IEC 60068-2-78
Humidity Testing
96 hours steady state humidity at 40 °C and 93% RH
8
GEDigitalEnergy.com
D20MX Substation Controller
Ordering Codes
Multilin D20MX Substation Controller
D20MX
-*
D20 MX CPU Options
A
(A) - D20MX dual 10/100/1000BASE-TX Ethernet Ports (front access)
C
(C) - D20MX dual 100BASE-FX ST Ethernet Ports (front access)
*
*
*
*
*
*
*
*
*
U
U
G
D20MX Power Supply
(G) - D20MX dual 100BASE-FX Ethernet Ports (rear access)
A
(A) - D20 Power Supply, 20-60VDC Input, 24V ISO Output
B
(B) - D20 Power Supply, 20-60VDC Input, 48V ISO Output
C
(C) - D20 Power Supply, 100-300VDC/85-264VAC Input, 24V ISO Output
D
D20MX Modem Slots
(D) - D20 Power Supply, 100-300VDC/85-264VAC Input, 48V ISO Output
U
U
U
(U) - Empty slot with cover plate
A
A
A
(A) - Wesdac D20 202 bin modem
C
C
C
(C) - Telenetics 14400 baud modem 2-wire dial up
D
D
D
(D) - Telenetics 14400 baud modem 4-wire leased line
E
(E) - D20MX dual 100BASE-FX ST Media Interface Card
F
D20MX
Serial Termination Panel
(F) - D20MX dual 100 BASE-FX LC Media Interface Card
A
(A) - 19" Rack Mount Serial IO Westerm Panel
B
0
H
(B) - D20 Chassis Rear Mounted Serial IO Westerm Panel
(C) - D20 Chassis Rear Mounted Serial IO Westerm Panel w/Extended
Bracket
(0H) -D20MX firmware v1.40 (9600 baud)
0
J
(0J) -D20MX firmware v1.40 (19200 baud)
0
K
(0K) -D20MX firmware v1.50 (9600 baud)
0
L
(0L) -D20MX firmware v1.50 (19200 baud)
0
U
(0U) -D20MX firmware Latest Release (19200 baud)
0
V
(0V) -D20MX firmware Latest Release (9600 baud)
C
D20MX Firmware Options
D20MX Classic Applications
License
D20MX Advanced Automation
Applications License
Future Feature
Future Feature
Serial Expansion
* Description
U
(U) - Not required
A
(A) - D2X CLASSIC APPLICATIONS
U
(U) - Not required
B
(B) - ADVANCED AUTOMATION APPLICATIONS
U
(U) - Not required
U
(U) - Not required
U (U) - Not required
(A) - 7 additional ports (14 ports total. 1x 19" Rack Mount Serial IO
A
Westerm Panel)
(B) - 14 additional ports (21 ports total. 2x 19" Rack Mount Serial IO
B
Westerm Panel)
(C) - 21 additional ports (28 ports total. 3x 19" Rack Mount Serial IO
C
Westerm Panel)
Note: The 19” Rack Mounted Serial IO Westerm Panel included with the Serial Expansion options must be installed directly below the D20 chassis
GEDigitalEnergy.com
9
D20MX Substation Controller
Ordering Codes
D200 D20MX Processor Gateway
D200MX
D20MX CPU Options
D20MX Power Supply
-*
*
*
*
*
*
*
*
*
*
*
*
*
*
U
U
C
* Description
(A) - D20MX dual 10/100/1000BASE-TX Ethernet Ports (front
access)
(C) - D20MX dual 100BASE-FX ST Ethernet Ports (front access)
G
(G) - D20MX dual 100BASE-FX Ethernet Ports (rear access)
A
A
(A) - D20 Power Supply, 20-60VDC Input, 24V ISO Output
B
U
(B) - D20 Power Supply, 20-60VDC Input, 48V ISO Output
(C) - D20 Power Supply, 100-300VDC/85-264VAC Input, 24V ISO
Output
(D) - D20 Power Supply, 100-300VDC/85-264VAC Input, 48V ISO
Output
(U) - Empty slot with cover plate
C
D
D20MX Modem slots
1, 2, 3, 4, 5, 6, 7, & 8
U
U
U
U
U
U
U
A
A
A
A
A
A
A
A
(A) - Wesdac D20 202 bin modem
C
C
C
C
C
C
C
C
(C) - Telenetics 14400 baud modem 2-wire dial up
D
D
D
D
D
D
D
D
(D) - Telenetics 14400 baud modem 4-wire leased line
E
(E) - D20MX dual 100BASE-FX ST Media Interface Card
F
D20MX Firmware
Options
D20MX Classic
Applications License
D20MX Advanced
Automation
Applications License
Future Feature
Future Feature
Serial Expansion
(F) - D20MX dual 100 BASE-FX LC Media Interface Card
0
H
(0H) -D20MX firmware v1.40 (9600 baud)
0
J
(0J) -D20MX firmware v1.40 (19200 baud)
0
K
(0K) -D20MX firmware v1.50 (9600 baud)
0
L
(0L) -D20MX firmware v1.50 (19200 baud)
0
U
(0U) -D20MX firmware Latest Release (19200 baud)
0
V
(0V) -D20MX firmware Latest Release (9600 baud)
U
(U) - Not required
A
(A) - D2X CLASSIC APPLICATIONS
U
(U) - Not required
B
(B) - ADVANCED AUTOMATION APPLICATIONS
U
(U) - Not required
U
(U) - Not required
U (U) - Not required
A (A) - 7 additional ports (14 ports total)
B (B) - 14 additional ports (21 ports total)
C (C) - 21 additional ports (28 ports total)
(D) - 28 additional ports (35 ports total, additional Serial IO panel
D
included)
10
GEDigitalEnergy.com
D20MX Substation Controller
Ordering Codes
Upgrade Kits Order Codes
D20MXK
D20 MX CPU Options
D20MX CPU Options
-*
*
*
*
*
*
*
U
U
A
(A) - Upgrade Kit for D20 Horizontal chassis - Multi Slot
D
(D) - Upgrade Kit for D20 Horizontal chassis - Single Slot
B
(B) - Upgrade Kit for D200 Vertical chassis
C
(C) - D20MX CPU only
E
(E) - Serial Expansion only for D20 Horizontal chassis
F
(F) - Serial Expansion only for D200 Vertical chassis
A
(A) - D20MX dual 10/100/1000BASE-TX Ethernet Ports (front access)
C
(C) - D20MX dual 100BASE-FX ST Ethernet Ports (front access)
G
(G) - D20MX dual 100BASE-FX Ethernet Ports (rear access)
U
D20MX Media Interface Card
Options
D20MX Firmware Options
D20MX D2X CLASSIC Applications
License
D20MX ADVANCED AUTOMATION
Applications License
FUTURE Feature
FUTURE Feature
Serial Expansion
* Description
(U) - Not required
U
(U) - Not required
E
(E) - D20MX dual 100BASE-FX ST Media Interface Card
F
(F) - D20MX dual 100 BASE-FX LC Media Interface Card
0
H
(0H) -D20MX firmware v1.40 (9600 baud)
0
J
(0J) -D20MX firmware v1.40 (19200 baud)
0
K
(0K) -D20MX firmware v1.50 (9600 baud)
0
L
(0L) -D20MX firmware v1.50 (19200 baud)
0
U
(0U) -D20MX firmware Latest Release (19200 baud)
0
V
(0V) -D20MX firmware Latest Release (9600 baud)
U
U
(UU) -Not required
U
(U) - Not required
A
(A) - D2X CLASSIC APPLICATIONS
U
(U) - Not required
B
(B) - ADVANCED AUTOMATION APPLICATIONS
U
(U) - Not required
U
(U) - Not required
U (U) - Not required
A (A) - 7 additional ports (14 ports total)
B (B) - 14 additional ports (21 ports total)
C (C) - 21 additional ports (28 ports total)
D (D) - 28 additioanl ports (35 ports total)
Note: Serial IO Westerm panel not included with SE in kits. This is a D20MX upgrade kit, RTU already has SIO panel.
GEDigitalEnergy.com
11
GEDigitalEnergy.com
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
Company.
GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.
Copyright 2015, General Electric Company. All Rights Reserved.
GEA-12711F(E)
English
150629