EYZ 292 - Sauter Controls

96.692/1
EYZ 292: novaNet292, Ethernet interface
The novaNet292 is a novaNet Ethernet interface for connecting the CASE Suite/CASE Engine programming tools and the various novaPro software on the management level to the EY3600 system
with Ethernet in a local area network (LAN).
It is possible to create a link from the PC Ethernet interface via novaNet292 to the EY3600 novaNet
system bus. Up to five possible CASE Engine Clients can access the novaNet at the same time. One
application for the exchange of data (e.g. novaPro32, novaPro Open, novaPro or novaNet OPC
Server) with the EY3600 is supported by a Windows driver (novaVPort). It is easy to configure the
interface using the novaNet292 Configurator.
Type
Description
novaNet Ethernet interface
EYZ 292 F001
EYZ 292 F002
Technical data
Power supply
Panel-mounted
Desktop model
Power consumption
230 V~/+10% to –15%,
115 V~/+10% to –15%,
50/60 Hz
6 VA/< 7 W
Ports / Communication
novaNet F001
F002
Ethernet
10Base-T
Serial Port
RS-232
1× a/b terminals
1× RJ-11 socket
1× RJ-45 socket
10 MBit/s
1× DB-9 (male)
acc. DTE (57k6, 8n1)
Standard settings
TCP/IP Address
Subnet Mask
TCP Port (App 1)
TCP Port (App 2)
192.168.10.20
255.255.255.0
51806 (nova292-Server)
51807 (nova291-Emulation)
Dimensions W×H×T
F001
F002
193 × 131 × 41 mm
228 × 131 × 41 mm
Power
230 V~/115 V~
230 V~/115 V~
Storage and transport temp.
Ambient conditions:Ambient temperature
Humidity
Degree of protection
Protection class
Wiring diagram
Dimension drawing
F001
F002
F001
F002
Fitting instructions
Declaration on materials
Product documentation
CE-Conformity
Directive 2006/95/EC
EMC directive 2004/108/EC
Weight
kg (lb)
0,650 (1,4)
0,700 (1,5)
-25...70 °C (-13...158°F)
0...45 °C (32...113°F)
10...80 %rh
without condensation
IP 20
I
A10400
A10401
M10445
M10448
MV 505997
MD 96.692
SH 7013505
EN 60950-1
EN 61000-6-1
EN 61000-6-2
EN 61000-6-4
EN 55024
Accessories
YYD 292 F010
0367862 001
0367862 002
0367862 003
0367842 002
0367842 003
0367842 004
0374509 001
0374677 001
0386301 001
0386507 001
1)
1)
novaNet292 driver software, current version on CD
Connection lead: novaNet292 – AS 1,5 m (4,9 ft)
Connection lead: novaNet292 – AS 2,9 m (9,5 ft)
Connection lead: novaNet292 – AS 6 m (19,7 ft)
Ethernet cable 1,5 m
Ethernet cable 2,9 m
Ethernet cable 6 m
Plug-in piece, 3-pin, (supplied with F001)
Kit for fitting to 2-DIN rail
Serial cable for firmware update and software reset (DB 9)
Ethernet crossover cable, 3 m
CD should be ordered separately or downloaded from intranet.
Sauter Systems
7196692003 03
96.692/2 EYZ 292
Operation
The novaNet292 can be used for various tasks and applications, such as:1. Access unit for CASE Engine including CASE Monitor (for time programmes)
The novaNet292 is an access unit for CASE Engine for parameterising and programming EY3600
automation stations (nova), compact controllers (novaFlex) and room controllers (ecos). The novaNet292 runs as a nova292 server. Up to five CASE Engines can use a novaNet292 at the same
time.
2.
Interface for novaPro32, novaPro Open, novaPro and novaNet OPC Server
The novaNet292 can be used together with the additional Windows novaVPort driver as a novaNet291 router. For novaPro… visualisation, the EY3600 driver is configured for the novaVPort
virtual COM-port driver. The novaNet292 runs as a nova291 emulation. Up to six novaVPort drivers can be set up on one computer. However, only one EY3600 driver can communicate from novaPro… via novaVPort with a novaNet292.
3.
Interface for novaMit29x for monitoring and inspecting the EY3600 novaNet system bus
Notes to operation:ƒ The nova291 emulation of the novaNet292 cannot emulate a novaNet291 router in dial-up mode (no
remote operation [router] and no remote monitoring [routel] via analogue/ISDN modem).
ƒ The novaNet292 is ideal for laptops and PCs that do not have a serial interface or an ISA slot. An
Ethernet interface is needed on the computer.
ƒ The applications can also be run in parallel (from Version 1.1). A switch located in the motor control
centre enables the technician to connect into the system with CASE and, for example, make FBD
modifications or check novaNet bus loads without having to disconnect the higher-level management system (such as novaPro…). (Topology c)
Applications
The following Ethernet network topologies are supported by the novaNet292:a Directly at PC with Ethernet
cross-over cable ('PTP')
CASE Engine
novaPro...
b With novaNet supply line
and one switch/hub
CASE Engine
novaPro...
c With Ethernet supply line
and two switches/hubs
CASE Engine
novaPro...
novaMit29x
Ethernet
Ethernet
switch
switch
switch
Crossover
novaNet292
novaNet292
novaNet
Sauter Systems
novaNet292
novaNet
novaNet
7196692003 03
EYZ 292
96.692/3
Notes to applications:ƒ The more switches or hubs there are fitted in the Ethernet network, the longer are the times
needed to transmit the telegrams on the Ethernet network. Experience shows that the
PC-novaNet292 network still works well with 'ping times' of about 30 ms. There should be no
telegram time-outs on the network.
ƒ For the novaNet292, which is always used together with an application on the PC, it is advisable
to structure the network in such a way that the integration of process data, i.e. the communication between PC and novaNet292, is carried out in 'isolation'.
ƒ When the EYZ 292 F001 is fitted in a panel, it is advisable to fit a small switch so that a service
technician has access on site.
ƒ More information on these notes and the supported topologies can be found in the help file that is
installed with the novaNet292 software.
Wiring
a) novaNet
With the novaNet link from the novaNet292 to an automation station, the maximum novaNet network
time constant should not exceed 120 µs. This means that a segment of a novaNet cable can have a
maximum time constant of 30 µs (max. 300 Ohm/200 nF).
N.B.: When using a novaNet292 a resistor of 1000 Ω (¼ Watt, 10 %) is required in the novaNet. If it
does not exist, it should be fitted at the position between a and b in the novaNet in order to reduce the
interference from incorrectly-fitted novaNet communication subscribers (e.g. due to inadequate
earthing) or from wiring that is susceptible to interference.
b) Ethernet
The Ethernet connection of the novaNet292 is a 10Base-T connection and can be used with standard
Ethernet cables, preferably CAT-5.
10Base-T (IEEE 802.3i) runs via four cores (two twisted pairs) of a CAT-3 or CAT-5 cable. A hub or
switch is in the middle and has one port for each subscriber. The transmission speed is 10 Mbit/s and
the maximum length of any segment is 100 metres.
c) Serial interface
The serial interface on the novaNet292, as an item of data terminal equipment (DTE), is laid out as
follows:Pin 2:
RD (receive data)
Pin 3:
TD (transmit data)
Pin 5:
GND (ground: reference potential to 0 V)
Pin 7:
RTS (request to send)
Pin 8:
CTS (clear to send)
Pins 1, 4, 6, 9:
NC (not connected)
The connection with a PC COM interface can be made using a serial null-modem cable (accessory
no.: 0386301 001).
Further details can be found in the Fitting Instructions (MV 505997).
Sauter Systems
7196692003 03
96.692/4 EYZ 292
Hardware
The novaNet292 novaNet Ethernet interface is available in two different versions. Type EYZ 292 F001
is designed for fitting to a top-hat rail (EN 50022) in a panel. Type EYZ 292 F002 is a desktop variant
of the novaNet292. Possible usage in training centres, by commissioning engineers or service technicians etc.
The unit has an Ethernet interface (RJ-45, 10Base-T) and a novaNet interface (a/b plug as screw-type
terminals on the EYZ 292 F001, RJ-11 plug on the EYZ 292 F002). There is a serial interface (DB-9,
male) available for firmware updates, support purposes and for carrying out an IP reset of the novaNet292 configuration.
The unit can run on either 230 Volt~ (50 Hz) or 110 Volt~ (60 Hz). On the EYZ 292 F001, the power
supply is via a screw-on plug, while the EYZ 292 F002 has a socket for an IEC-320 AC power cable
and an ON/OFF switch. In operation, the unit has a power consumption of max. 7 Watt.
The novaNet292 is an embedded Linux platform based on a Samsung ARM7 processor (S3C44B0;
66MHz) and has 16 Mbyte flash PROM and 16 Mbyte DRAM.
Various LEDs indicate the status of the unit.
LED display and diagnostics
Inscription
Error
Colour
Status (speed)
Denotes
Inactive
In the correct enterprise
Flashing
In the starting phase
Ready for use after approximately 30 seconds
Flashing:
every 1 sec.
Indicate a failure:Missing one novaVPort communication
(Flashes after approximately 30 s Ethernet interruption)
None novaNet telegrams (novaNet Receive - Rx)
Red
every ¼ sec.
novaNet
Yellow
Active
Sending a novaNet telegram (novaNet Send - Tx)
Power
Green
Flashing
Device switched on (power supply present)
Activity
Green
Active
Receiving (Rx-Receive) and sending (Tx-Transmit) an
Ethernet telegram
Link
Yellow
Active
Ethernet connection established (physically) and connection
to network or network card of the PC.
novaNet292 software
The novaNet292 software is supplied with CASE Suite or novaPro32 for CASE Suite. However, the
latest novaNet292 software can be downloaded as a single installation from the Sauter intranet. Furthermore, a driver CD containing the novaNet292 software is available to order (accessory no.:
YYD 292 F010).
Minimum PC requirements:CPU clock speed: 800 MHz (more recommended)
RAM: 256 MB (more recommended)
Hard disk: 1 GB (more recommended)
Installation of novaNet292 software requires approx. 9,5 MB
Ethernet interface with Ethernet cross-over cable
Serial interface (or standard USB-COM converter) for firmware updates
Operating system requirements:Windows 2000, XP, Server 2000, Server 2003 (recommended with Service Packs)
.NET-Framework 1.1
Further details on the installation of the novaNet292 software, on the novaNet292 Configurator and
on the novaVPort virtual COM-Port driver can be found in the help file (eGuide: novaNet292.chm).
The latest help files (in German, French and English) are also installed and can also be downloaded
from the intranet.
Sauter Systems
7196692003 03
EYZ 292
96.692/5
Wiring diagram
EYZ 292 F001
RJ 45
Ethernet
L
b
DB 9
RS232
a
A10400
EYZ 292 F002
RJ 45
Ethernet
ON/ OFF
DB 9
RS232
I
O
b
a
54321
A10401
Dimension drawings
EYZ 292 F001
131
EYZ 292 F002
M10445
M10448
Sauter Systems
Printed in Switzerland
Right of amendment reserved
N.B.: A comma between cardinal
numbers denotes a decimal point
© Fr. Sauter AG, CH-4016 Basle
7196692003 03