cisco two-way capacitor bank controller/monitor specifications model

CISCO TWO-WAY CAPACITOR BANK
CONTROLLER/MONITOR SPECIFICATIONS
MODEL KFZ00-RCR1109
Overview
Hardware Features
The CSE multifunction all season Capacitor Bank
Controllers (CapBank) are two-way terminals for
remote control and monitoring of power factor
correction for line capacitors and other similar control
capabilities. CSE CapBank controls are based upon
one or more of the following functions:
Ability to Integrate with:
 Dispatch at energy control center
 Retail energy desk (Energy Supply and Marketing)
 Supervisory control (SCADA)
 Customer Information System (CIS, CICS, or
other)
Communication Options:
 Cisco Mesh Networks
 Other Communication Paths available
Capacitor Bank Control Features:
 Cost effective remote controllable & programmable
 Historical event counters
 Over four million individual addresses with remote
programmability
 Data recall parameters
 Visual indicators
 Remote test functions
 Standard 4-jaw or 6-jaw meter socket Mount:
NEMA 250 enclosure with seal & latch
 Field Safety - local out of service
 Power Factor
 Load Current
 Voltage
 Temperature
 VAR Management  Time of day and day of
week
The functions listed above can be factory programmed
as defined by the Utility; however, these functions can
be overridden by the Control Platform. The Control
Platform is flexible and can be an interface with an
existing software application, such as SCADA/EMS,
or a part of the CSE Demand Response Control
Platform. The Control Platform is configurable to
operate by SCADA control or as an independent
Control Platform with SCADA override. CSE
applications are windows based, menu driven and can
be used on any PC.
The two-way communications is achieved via Cisco
Mesh Network. This two-way communication is
managed utilizing a high speed processor and flash
memory. With two-way communication, users can
monitor real-time line conditions, retrieve load data
and program the CapBank. Data from the CapBank
can be retrieved during off-peak hours conserving
airtime and communication costs or in near real-time.
1215 Brookville Way, Indianapolis, Indiana 46239
P: 317-375-3600 ♦ F: 317-375-3610 ♦ www.corporatesystems.com
CISCO TWO-WAY CAPACITOR BANK
CONTROLLER/MONITOR
MODEL KFZ00-RCR1109
ADDRESS CODES
Individual Address:
Common Individual Address:
Group:
4,194,304 (222) Possibilities.
Addresses all units.
16,384 (214) Possible groups
Group Address:
127 (27-1) Possible groups with subgroups
Subgroup Address:
128 (27) Possible subgroups each
Address Assignment (Remote):
Address Function:
COMMUNICATION OPTIONS
Type:
Regulatory Compliance:
DATA RECALL PARAMATERS
Last Message Received
CapBank Switch Position
Trip/Close Operation Counter
VAR Recordings
VISUAL INDICATORS
LED 1 Trip:
LED 2 Close:
LED 3 Test:
LED 4 Local Control Status:
TEST FUNCTIONS
Operation Including
Relay Coil Continuity and
Propagation Test on LED 3:
DEVICE ENCLOSURE
Type:
Dimensions:
Mounting:
Tinted Lid:
POWER REQUIREMENTS
Power Input:
Power Consumption:
OPERATING ENVIRONMENT
Operating Temperature:
Relative Humidity:
REGULATORY COMPLIANCE
Surge Withstand Capability:
Federal Communications
Commission (FCC)
From one up to 8 Upper and associated Lower Extended Addresses.
Controls load (Interrupts/Restores relay contact).
Cisco Mesh Networks
Other Communication Paths available:
FCC
Recalls the last command received.
Recalls the position of the CapBank switch
Number of times the Trip and/or Close have been operated
Provides the VAR details
LED 1 in steady state on denotes trip operation. Blinking state denotes
delay period prior to trip.
LED 2 in steady state on denotes close operation. Blinking state denotes
delay period prior to close.
LED 3 in blinking state denotes unit is under test.
LED 4 in steady state on denotes unit is in local state out of service,
manual operation only.
LED 3 indication in response to Test Command and Propagation signal
from a handheld transmitter or Load Management System Transmitter.
High-impact Molded Lexan® with neoprene enclosure gasket for raintight
operation. Meets NEMA 250 – Enclosures for Electrical Equipment
(1000 Volts Maximum). Provision for utility meter seal.
8 5/16” X 9 3/4” X 5 1/2” – 2.75 lbs.
Standard 4 or 6 jaw meter socket.
For LED observation.
120 or 240 VAC ±20%; 60 Hz. Specified at time of order.
5 Watts maximum at 120 or 240VAC with full load.
Specified at time of order.
0 -100% (non-condensing).
Meets and exceeds ANSI C37.90a requirements.
FCC Part 15
Radiated Emission ANSI C63.4
All devices are 100% Factory Tested and Inspected in accordance with Factory Acceptance Testing Procedures
mutually determined with each utility.
® Lexan is a registered trademark of General Electric Company
Specifications subject to change
1215 Brookville Way, Indianapolis, Indiana 46239
P: 317-375-3600 ♦ F: 317-375-3610 ♦ www.corporatesystems.com
CELLULAR TWO-WAY CAPACITOR BANK
CONTROLLER/MONITOR
MODEL KFP00-RCR1109
Overview
Hardware Features
The CSE multifunction all season Capacitor Bank
Controllers (CapBank) are two-way terminals for
remote control and monitoring of power factor
correction for line capacitors and other similar control
capabilities. CSE CapBank controls are based upon
one or more of the following functions:
Ability to Integrate with:
 Dispatch at energy control center
 Retail energy desk (Energy Supply and Marketing)
 Supervisory control (SCADA)
 Customer Information System (CIS, CICS, or
other)
Communication Options:
 Cellular Dual-band CDMA 800 / 1900 MHz
 Built in UDP/TCP/IP stack
 Other Communication Paths available
Capacitor Bank Control Features:
 Cost effective remote controllable & programmable
 Historical event counters
 Over four million individual addresses with remote
programmability
 Data recall parameters
 Visual indicators
 Remote test functions
 Standard 4-jaw or 6-jaw meter socket Mount:
NEMA 250 enclosure with seal & latch
 Field Safety - local out of service
 Power Factor
 Load Current
 Voltage
 Temperature
 VAR Management  Time of day and day of
week
The functions listed above can be factory programmed
as defined by the Utility; however, these functions can
be overridden by the Control Platform. The Control
Platform is flexible and can be an interface with an
existing software application, such as SCADA/EMS,
or a part of the CSE Demand Response Control
Platform. The Control Platform is configurable to
operate by SCADA control or as an independent
Control Platform with SCADA override. CSE
applications are windows based, menu driven and can
be used on any PC.
The two-way communications is achieved via cellular
network. This two-way communication is managed
utilizing a high speed processor and flash memory.
With two-way communication, users can monitor realtime line conditions, retrieve load data and program the
CapBank. Data from the CapBank can be retrieved
during off-peak hours conserving airtime and
communication costs or in near real-time.
1215 Brookville Way, Indianapolis, Indiana 46239
P: 317-375-3600 ♦ F: 317-375-3610 ♦ www.corporatesystems.com
CELLULAR TWO-WAY CAPACITOR BANK
CONTROLLER/MONITOR
MODEL KFP00-RCR1109
ADDRESS CODES
Individual Address:
Common Individual Address:
Group:
4,194,304 (222) Possibilities.
Addresses all units.
16,384 (214) Possible groups
Group Address:
127 (27-1) Possible groups with subgroups
Subgroup Address:
128 (27) Possible subgroups each
Address Assignment (Remote):
Address Function:
COMMUNICATION OPTIONS
Type:
Regulatory Compliance:
DATA RECALL PARAMATERS
Last Message Received
CapBank Switch Position
Trip/Close Operation Counter
VAR Recordings
VISUAL INDICATORS
LED 1 Trip:
LED 2 Close:
LED 3 Test:
LED 4 Local Control Status:
TEST FUNCTIONS
Operation Including
Relay Coil Continuity and
Propagation Test on LED 3:
DEVICE ENCLOSURE
Type:
Dimensions:
Mounting:
Tinted Lid:
POWER REQUIREMENTS
Power Input:
Power Consumption:
OPERATING ENVIRONMENT
Operating Temperature:
Relative Humidity:
REGULATORY COMPLIANCE
Surge Withstand Capability:
Federal Communications
Commission (FCC)
From one up to 8 Upper and associated Lower Extended Addresses.
Controls load (Interrupts/Restores relay contact).
Cellular Dual-band CDMA 800 / 1900 MHz
Built in UDP/TCP/IP stack
Other Communication Paths available:
FCC
Cellular Operation – Verizon Network Certified
Recalls the last command received.
Recalls the position of the CapBank switch
Number of times the Trip and/or Close have been operated
Provides the VAR details
LED 1 in steady state on denotes trip operation. Blinking state denotes
delay period prior to trip.
LED 2 in steady state on denotes close operation. Blinking state denotes
delay period prior to close.
LED 3 in blinking state denotes unit is under test.
LED 4 in steady state on denotes unit is in local state out of service,
manual operation only.
LED 3 indication in response to Test Command and Propagation signal
from a handheld transmitter or Load Management System Transmitter.
High-impact Molded Lexan® with neoprene enclosure gasket for raintight
operation. Meets NEMA 250 – Enclosures for Electrical Equipment
(1000 Volts Maximum). Provision for utility meter seal.
8 5/16” X 9 3/4” X 5 1/2” – 2.75 lbs.
Standard 4 or 6 jaw meter socket.
For LED observation.
120 or 240 VAC ±20%; 60 Hz. Specified at time of order.
5 Watts maximum at 120 or 240VAC with full load.
Specified at time of order.
0 -100% (non-condensing).
Meets and exceeds ANSI C37.90a requirements.
FCC Part 15
Radiated Emission ANSI C63.4
All devices are 100% Factory Tested and Inspected in accordance with Factory Acceptance Testing Procedures
mutually determined with each utility.
® Lexan is a registered trademark of General Electric Company
Specifications subject to change