i-Vu® Building Automation System MPC Open XP IO

i-Vu® Building Automation System
Part Numbers: OPN-MPCXPIO48
The i-Vu® Building Automation System provides everything
you need to access, manage, and control your building,
including the powerful i-Vu user interface, plug-and-play
BACnet controllers, and state-of-the-art Carrier equipment.
The MPC Open XP IO expanders add additional I/O point
capacity to the MPC Open XP controller. Flexible and
versatile, the MPC Open XP controller supports multiple
I/O configurations for accomplishing both common and
custom HVAC control strategies. The MPC Open XP
controller connects to up to 20 field points directly (8
outputs and 12 inputs), while also supporting up to 3 MPC
XP IO expanders. Each MPC XP IO48 expander adds
support for up to 12 additional field points (4 outputs, 8
inputs), while each MPC XP IO816 expander adds support
for up to 24 additional field points (8 outputs, 16 inputs).
When combined, the MPC Open XP controller and it’s
associated MPC XP IO expanders can support up to 92
total points.
Application Features
Comprehensive library of factory-engineered control
programs available for complete air-side and waterside system control
Graphically programmable using the Snap
programming tool
Supports Carrier communicating room sensors, which
allow for local setpoint adjustment and local overrides
Hardware Features
Expands the MPC Open XP Controller to support up
to 92 I/O points
Removable screw terminals for I/O connections
First MPC XPIO expander can be mounted directly on
MPC XP controller to save panel space
System Benefits
Fully plug-and-play with the Carrier i-Vu Building
Automation System
Supports demand limiting and optimal start for
maximum energy savings
Compatible with i-Vu Tenant Billing for tracking
tenants’ after-hours energy usage
Sample Applications
Cooling Towers
i-Vu® Building Automation System
Part Numbers: OPN-MPCXPIO48
Communication Ports Xnet Remote Expansion port: For connecting to an MPC Open XP controller via the Xnet network
-MPC XPIO48: 8 inputs
-MPC XPIO816: 16 inputs
Inputs configurable for 0-5 VDC, 0-10 VDC, 0-20 mA, thermistor (5k, 10k Type II), 1k RTD (Platinum,
Nickel, or Balco), and Dry Contact.
Inputs are 14 bit A/D and support up to 40 pulses per second (12.5 msec min. pulse).
-MPC XPIO48: 4 outputs
-MPC XPIO816: 8 outputs
Outputs jumper configurable for 0-10 VDC, 0-20 mA (12 bit A/D), or 24 VDC (50 mA relay drive).
Outputs have HOA (hand/off/auto) switches, including potentiometer for manual adjustment of
analog outputs.
Protection Incoming power: 2 replaceable 3 Amp Pico® fuses
The power, network, and I/O are also protected against voltage transient and surge events.
Status Indicators LED status of communications, running, errors, and outputs
Listed by
UL-916 (PAZX), cUL-916 (PAZX7),
FCC Part 15-Subpart B-Class A, CE
Environmental Operating Range Operating: 0 to 140ºF (-18 to 60ºC) 10 to 90% RH, non-condensing
Storage: -24 to 140ºF (-30 to 60ºC) 10 to 90% RH, non-condensing
Power Requirements
24VAC ± 10%, 50-60Hz
45 VA power consumption
26VDC (25V min, 30V max), 21W
Single Class 2 source only, 100 VA or less
A: 9” (22.9 cm)
B: 4-13/16” (12.2 cm)
C: 8-5/8” (21.9 cm)
D: 1” (2.5 cm)
E: 2-13/16” (7.1 cm)
F: 1/4” (.5 cm)
Depth: 1-7/16” (3.7 cm)
Weight: 13.3 oz. (.377 kg)
For more information, contact
your local Carrier Controls Expert.
Controls Expert Locator:
© Carrier Corporation 2014 Cat. No. 11-808-484-01 Rev. 06/17
Manufacturer reserves the right to discontinue, or change at
any time, specifications or designs, without notice and without
incurring obligations. Trademarks are properties of their
respective companies and are hereby acknowledged.
Download PDF
Similar pages