Vykon JACE 2/JACE 6
Powerful and flexible platforms for NiagaraAX
DIN rail mounting with I/O expansion modules
The JACE 2 and JACE 6 are compact,
DIN-rail mounting platforms utilising the
NiagaraAX Framework® for integration,
control and web serving. Ethernet and
serial comms ports are included as
standard. Plug-in option cards enable
additional comms ports and a GPRS
modem option to be added into 2
expansion slots within the unit. Up to 66
points of directly wired input and outputs
can also be added via DIN rail mounted
I/O modules.
Connectivity
Basic unit has 2 Ethernet ports plus one RS 232
and one RS 485 port.
Key features
AX
•
Runs the Niagara
•
DIN rail mounting
•
2 x Ethernet + 1 x RS232 and 1 x RS485
ports
•
Optional plug-in cards for comms & GPRS
modem
Engineering
•
Plug-in IO modules provide up to 66 points
Integrated Graphical Engineering Tool is
embedded in JACE 2 and JACE 6 so engineering
can be carried out from a browser.
•
24Vac or 230V PSU options
•
Supports Open Communication networks
LON, BACnet, KNX-IP, Modbus, M-bus,
SNMP, Z-wave and oBIX
•
Full network management of LONworks
devices
•
Built-in Web Server provides Graphical
User Interface via Browser
•
Different licensed versions match different
types and sizes of application
A GPRS modem card can be fitted internally.
A third party dial-up or GPRS modem can be
connected to a serial port, and a DSL
modem/router can be connected to an Ethernet
port, enabling IP communication for remote
access and management.
Optional Modules
2 slots are available for plug-in communications
modules:
• LON FTT-10a port
• 2 x RS485 ports
• RS232 port
• GPRS modem
Plug-on DIN rail mounted modules:
• 16 point I/O – 8xUI, 4xAO, 4xDO
• 34 point I/O – 16xUI, 8xAO, 10xDO
• 24V PSU module
Framework
DIN rail
mounted
I/O
modules
plug-in to
the JACE
JACE 2/6 Datasheet v1.4 6.2.09.
Vykon JACE 2/6
Datasheet
Specifications
Platform
JACE 2
IBM PowerPC processor 250 MHz
DRAM
128MB
JACE 6
524Mhz
256MB
Serial Flash
128MB
64MB
Battery back-up 5 minutes typical – shut down begins
within 10 secs
Data Base storage and Real-time clock – 3 month
battery back-up
Communications
2 Ethernet Ports - 10/100Mb (RJ45 connectors)
1 RS232 port (9 pin D-connector)
1 RS485 non-isolated port (3 way two part connector)
Optional Communications Cards (plug-in, internally
mounted)
LON adaptor FTT-10A, RS485, RS232, GPRS modem
Din Rail Mounted Input Output Modules
Connection to JACE-2 and JACE 6 is via a single multipin plug
Removable screw terminals for all inputs and outputs (in
blocks of 6)
Universal Inputs (UI) for:
Type 3 (10K) Thermistors, input accuracy +/-1% of
span
Other types may be supported by entering custom
non-linear curve interpolation points for each nonlinear input
•
0-10Vdc acc. +/- 2% of span without user calibration
•
4-20mA acc. +/- 2% of span, without user calibration
Uses externally connected resistor for current input
(provided)
Self-powered or board powered sensors accepted
•
Dry contact V open circuit, 300-uA short-circuit
current
Pulsing dry contact up to 20Hz; 50% duty cycle
Digital Outputs (DO):
•
Form A relay contacts max 30Vac or dc, 0.5A max
current; suitable for on / off control only, floating
control not supported
Analog Outputs (AO)
0-10Vdc 4mA drain max.
Operating System
QNX operating system
IBM J9 Java Virtual Machine
AX
Niagara Framework
Chassis
Construction: plastic enclosure, internal air convection
cooling. Intended for indoor wall or panel mounting only
Modules Available
JACE 2 and JACE 6
162 x 104 (122) x 62mm (with terminals)
Panel fixing lugs add 20mm to the main module width
IO16 module
8UI 4 DO 4 AO
max 4 per JACE or 2 in combination with IO 34
80 x 104(122) x 62mm (with terminals)
IO34 module
16UI 10DO 8AO
max 1 per JACE
includes integral 24vac/dc PSU
162 x 104(122) x 62mm (with terminals)
Power Supply
90 - 240Vac 50-60Hz universal plug-top PSU providing
15Vdc to JACE
Available with European, UK or US plug types
DIN rail mounting PSU module: 24Vac/dc 50-60Hz 25VA
This PSU is integral with the IO 34 module
One PSU required per JACE and IO module combination
Environment
Operating temperature range: 0 to 50°C
Storage Temperature range: 0 to 70°C
Relative humidity: 5 to 95%, non-condensing
Agency Listings
CE, UL 916, C-UL listed to Canadian Standards Assoc (CSA)
C22.2 No. 205-M1983 “Signal Equipment”
FCC part 15 Class A, C-tick (Australia)
How to order
JCX660
JCX650
JCX250
JCX240
JCX230
JCX220
ION16P
ION34P
PMPEUP
PMPUKP
PMD24V
JOCLON
JOC485
JOC232
JOCGPR
GPREXT
Tridium Europe Ltd
1 The Grainstore, Brooks Green Road, Coolham, West Sussex RH13 8GR, UK
Telephone: +44 (0) 1403 740290 www.tridium.com
JACE 6 with 96MB Java Heap Memory
JACE 6 limited to 48MB Heap Memory
JACE 2 with 48MB Java Heap Memory
JACE 2 limited to 16MB Heap Memory
JACE 2 limited to 16MB Heap Memory
450K resource limit
200 points max/network
JACE 2 limited to 16MB Heap Memory
350K resource limit
8 points max/network
34 points max NDIO
Niagara + 1 other network
16 point IO module
34 point IO module with built-in 24Vac/dc
PSU
90-240Vac Plug Top PSU Europe 2 pin
90-240Vac Plug Top PSU UK 3 pin
24Vac DIN rail mounting PSU
Plug-in LON FTT card
Plug-in RS485 card (2 ports)
Plug-in RS232 card
Plug-in GPRS modem card
Extension cable and bracket for modem
JACE 2/6 Datasheet v1.4 6.2.09.
Download PDF