Fire Alarm Aspiration Sensing Technology®
FAAST XT
Agency Listings
General
FAAST XT aspirating smoke detectors deliver highly accurate
Very Early Warning Fire Detection over a wide coverage area
and offer extensive communication capabilities.
The FAAST XT aspirating smoke detector combines
advanced particle separation with unique dual source optical
smoke detection technology to provide highly sensitive Very
Early Warning Fire Detection while providing enhanced
immunity to false alarms. This technology enables FAAST XT
to accurately detect incipient fire conditions as early as 60
minutes before a fire actually starts when set for Early
Warning and Very Early Warning Fire Detection in
applications ranging from mission critical to harsh and
extreme environments.
An installed FAAST XT device can protect up to 28,800 sq. ft.
(2,676 sq. m) in standard coverage type applications and can
be monitored in several different ways, including: Serial or
TCP Modbus, Ethernet over a LAN or a direct connection, or
via FAAST XT’s onboard USB. When connected to a LAN,
FAAST XT’s email server can provide email event notification
to appropriate personnel. FAAST XT also communicates
alarm and notifications via form C relays.
PipeIQ® is FAAST XT’s intuitive design, configuration, and
monitoring software. The all-in-one program can be used to
create a pipe network tailored to meet site specific
requirements, configure a FAAST XT device, and monitor an
installed device -- including live trending and reading of
historic reports.
* A complimentary download of PipeIQ is available at
systemsensor.com/faast.
Features
• Provides Very Early Warning Fire Detection, as precise as
0.00046%/ft obscuration
• Five alarm levels and three sensitivity modes provide
application flexibility
• User configurable 3-speed fan, allowing for maximum
coverage area or minimizing on current consumption
• Ultrasonic flow sensing for each pipe inlet and chamber
airflow monitoring for precise system health information
• A single device covers up to 28,800 square feet
FAAST XT
• Dual source optical detection chamber with
enhanced algorithms provide high sensitivity
with greater immunity to nuisance conditions
• Patented particle separator removes large,
non-fire particulate, ensuring chamber
health and extending the life of the fieldreplacable filter
• TCP and Serial modbus for easy integration
with building management systems
• Easy configuration via USB interface, no
external power needed
• Onboard Ethernet interface enables remote
monitoring, configuration, web server and email notifications
• Multilingual LCD user interface allows for
detailed device information and interaction
such as: Active faults, precise airflow
monitoring, reset of airflow baseline,
test/reset/isolate, and more
• Configurable air flow fault thresholds and
verification period
• Convenient wiring compartment
• Status-at-a-glance provides immediate
alarm, fault and airflow status
P/N 351566 Rev B
Copyright © 2015 Honeywell International Inc.
FAAST XT User Interface Display
The User Interface consists of 5 Alarm levels – Alert,
Action 1, Action 2, Fire 1, and Fire 2, 10 Particulate
levels, 10 Bi-color Flow and Fault graph.
Specifications
Electrical
External Supply Voltage
Remote Reset Time
Power Reset
Operating Current
Alarm Current
Relay Contact Ratings
Environmental
18-30 VDC
External monitor must be pulled
low for a minimum of 100 ms
1 sec.
Fan High - 465mA, 11.2W;
Fan Med - 340mA, 8.2W;
Fan Low - 220mA, 5.3W
Fan High - 493mA, 11.85W;
Fan Med - 368mA, 8.85W;
Fan Low - 248mA, 6W
3.0 A @ 30 VDC, 0.5 A @ 125
VAC 8 form C, 3 AMP,
programmable latching or nonlatching
Operating Temperature
Sampled Air Temperature
Humidity Range
Sensitivity Range
IP Rating
Coverage Area
Air Movement
32°F (0°C) to 100°F (38°C)
-4°F (-20°C) to 140°F (60°C)
10 to 95% (non-condensing)
0.00046% Obs/ft to 6.25% Obs/ft
IP30
28,800 sq.ft. (2,676 sq.m)
0-4,000 ft./min. (0-1,219 m/min.)
Dimensions
13.1” W x 13.3” H x 7.5” D
(33.274 x 33.783 x 19.050 cm)
4 1-inch (2.54 cm) cable entry
holes on top and bottom of unit
12 AWG (2.05 mm)max. to
24AWG (0.5 mm) min.
400 ft. (123 m) *other three pipes
disabled
1050 ft. (320 m) *all designs must
be verified within PipeIQ software
Physical
Cable Access
Wire Gauge
Max Single Pipe Length
Total Pipe Length
Outside Pipe Dim
Internal Pipe Dim
Relays
1.050 inches, IPS (25 mm)
0.591 to 0.827 inches (15-21 mm)
8 form C, 3 AMP, programmable
latching or non-latching
Diagnostic Specifications
Event Log
Trend Data Log
Service Log
18,000 events stored
Configurable sampling period 1
minute to 1 day
300 custom user entries
Networking Specifications
Communication Network
Network Services
Ethernet
Modbus
Email
Webserver
Ethernet monitoring, 6 email
address alerts, TCP and Serial
Modbus
DHCP, SMTP, HTTP,
MODBUS/TCP, AutoIP, NetBIOSNS, Serial MODBUS
10/100Mbps, MDI-X
TCP or Serial RS-485
6 recipients, selectable
notifications
Read Configuration, Live View,
Logs
Configuration Specifications
PipeIQ
Modbus
USB or Ethernet
Ethernet or RS-485
9400X
System Sensor Conventional
FAAST Fire Alarm Aspiration
Sensing Technology
Ordering Information
Accessories
Various†
UL - Approved Pipe and Fittings
† Additional accessory information, including part numbers,
can be accessed at systemsensor.com/faast.
System Sensor® is a registered trademarks of Honeywell International Inc
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For more
information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610
Phone: (800) 328-0103, Fax: (203) 484-7118. www.farenhyt.com