EPC Panel Mount

EPC Panel Mount
APPLICATION
UL924 Emergency Power Control
Switched Loads up to 20A
In the past, emergency lights were kept on 24 hours
a day to meet life safety codes. Now, you can use a
UL 924 listed Emergency Power Control, Model EPC
Panel Mount, to convert regular light fixtures into
approved emergency lights. The EPC Panel Mount
saves energy and money while ensuring compliance
with both life safety and energy codes.
Project:
Model No.:
Comments:
During normal operation, the same room switch,
occupancy sensor, relay panel, or lighting control
switches regular and emergency fixtures on and off
simultaneously.
During a utility power interruption, the EPC Panel
Mount automatically bypasses the regular lighting
controls, turning the emergency lights ON, regardless of switch position.
The EPC Panel Mount is panel mounted in a junction
box or enclosure and is usually located in the electrical room.
FEATURES
MOUNTING
Unique, Patented Automatic Diagnostic
Regular Line Hot
Emergency Hot
Switch Leg
Emergency Switch Leg
Emergency Load
*
**
Regular Load
Regular Line Neutral
Emergency Neutral
* Optional Occupancy
Sensor Contact
LED COMPATIBILE
C
UL
®
US
UL924 LISTED
5
YEAR
WARRANTY
When the room switch is turned off, the EPC
Panel Mount will run a 2.5 self-test routine, verifying that the emergency power source was
available and that the EPC Panel Mount, ballast,
and lamp(s) are all functioning correctly. This
feature eliminates the need for time-consuming
and costly manual monthly testing and is
approved for this purpose. This also allows the
unit to be installed in remote or inaccessible locations, because the unit does not rely on access to
its manual test switch.
Fire Alarm, Remote Test & 0-10V Dimming
Option
Utility & Emergency Power Indicator LED’s
Panel mounting with easy to wire terminal
blocks
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216
Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707
www.lvscontrols.com
SINGLE LINE DRAWING
REGULAR
ROOM
LIGHTS
Regular
Utility Power
REGULAR
PANEL
EPC
Panel Mount
$
DESIGNATED
EMERGENCY
LIGHTS
Regular
Utility Power
Emergency
Power Source
(Neutral
Not Shown)
EMERGENCY
PANEL OR
INVERTER
UL 1008
Transfer Switch
Or Equivalent
EPC
Panel Mount
EPC
Panel Mount
TO ADDITIONAL
EPC CONTROLS
WIRING DIAGRAM
20A
EMERGENCY
PANEL OR
INVERTER
#1 BLACK/ORANGE
#6 BLUE
EMERGENCY HOT
#5 YELLOW
EMERGENCY
POWER
TEST
Emergency Light
#4 WHITE/BLUE
*
#2 RED
SWITCH
UTILITY
POWER
#3 WHITE
20A
REGULAR HOT
REGULAR
PANEL
Regular Light (optional)
EMERGENCY NEUTRAL
REGULAR NEUTRAL
* Relay Panel, Power Pack, Sensor, or other (optional)
Note: Emergency Light is also called N/E Light or
Normal/Emergency Light by many specifiers
SPECIFICATIONS
EPC Panel Mount
SENSING INPUT
120V / 277V
LOAD RATING
120V - 277V (20A)
BALLAST LOAD RATING 20A (120-277V)
INCANDESCENT LOAD
1800W (120V) / 1500W (277V)
WARRANTY
5 Year Replacement Warranty
ORDERING INFORMATION
EPC Panel Mount
For 0-10V dimming, see EPC-1-D
For alternate mounting, see EPC-PM & EPC-A-1
20160422_E001_Spec
MECHANICAL
ELECTRICAL
MODEL NO.
MOUNTING
Screw mount in metal enclosure
RATING
UL94V-0 Flame Rating
SHIPPING WEIGHT / COLOR
7 oz. / Black
TEMPERATURE
32ºF - 140ºF (0ºC - 60ºC)
BODY SIZE
3-1/2” x 3” x 3”
ADDITIONAL RESOURCES
Installation Instructions
Theory of Operation & FAQ
Alternative Wiring Diagrams
Terms & Conditions/Warranty Information
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216