emerg-power systems - Emergi-Lite

Option Details
INTEGRATED OUTPUT CIRCUIT BREAKERS:
-OCB
12
20
Trip Alarm
Number of Circuit Breakers
OCB - No
Breaker Trip
Alarm
Combination of 1 pole, 2 pole
and 3 pole breakers available.
Breaker
Rating
(Amps)
OCA - With
Breaker Trip
Alarm
* For max. number of
circuit breakers available
please consult factory
* Various
ratings
available
Number
of poles
Breaker Voltage
Operation Mode
Blank - 1 pole
Blank- matches
system output voltage
Blank:
Normally-On
-2P - 2 poles
-120VAC
-3P - 3 poles
-208VAC
-NOFF:
Normally-Off
-240VAC
-277VAC
-480VAC
Distribution circuit breakers are for output load protection. Protection for the normally on and/or for the normally off loads.
All circuit breakers are rated for 10,000 AIC.
If ordered, an audible and visual alarm activates when an output distribution circuit breaker is open or has tripped.
(-20YR) 20 YEAR SEALED LEAD CALCIUM BATTERIES
Maintenance free battery requires no addition of water over the life of the
battery. The battery cells are housed in protective, modular steel trays. Life
expectancy is designed for 20-years at 77ºF (25ºC).
(-NOFF) NORMALLY OFF OUTPUT
This output circuit is dedicated for the “emergency only” equipment. Emergency
only equipment operates during power outages and when the system is on
battery back up. This option leaves the normally off load circuits off during
normal utility power conditions. A 1-pole circuit breaker is provided. For 3
phase systems, 3 pole normally off circuits are available as well.
(-12HR) 12 HOUR FAST RECHARGE
Battery charger upgrade option which decreases the time required to return a
fully discharged battery to the fully charged state. The normal 24 hour recharge
cycle is reduced to a 12 hour period.
(-MOD) EXTERNAL MODEM
External modem device is designed to boost the signal level of the RS-232
diagnostic interface to remote monitoring locations located more than 100 feet
away from the system.
(-MBYP) INTERNAL MAINTENANCE BYPASS SWITCH
Internally mounted device permits maintenance personnel to easily bypass the
protected equipment directly to the AC utility power. The manual make before
break switch isolates the system to perform routine maintenance or servicing
without interruption of utility power to the connected load.
(-FAX) INTERNAL FAX MODEM
The internal fax modem enables the system to send a fax automatically to
several pre-programmed numbers when one of the following conditions occurs:
utility failure, output failure or any alarm. The Fax Modem option requires a user
supplied dedicated phone line.
(-EMBP) EXTERNAL MAINTENANCE BYPASS SWITCH
The external maintenance bypass switch is mounted in a 20”H x 16”W x 9”D
NEMA 1 separate enclosure, used to completely isolate the inverter system
from the connected load and AC utility input. This option allows the system to
be safely powered down for maintenance or service. The option may not be
used on systems with more than one single pole output circuit breaker which
must be sized for the total system output current.
(-BPR) BYPASS RELAYS
Internal bypass relays will allow overriding circuits that can be switched on/off,
so in case of a power failure the emergency circuits will be supplied from the
inverter system whatever the position of the switching device. Please consult
factory for more details.
(-RMP) REMOTE METER PANEL
The panel allows monitoring of parameters and control from remote locations
up to 150 feet away from the inverter system. Also, the remote panel provides a
complete touch pad interface allowing the user to monitor, control and program
the inverter system.
(-DIAL) AUTO DIALER
The Auto Dialer modem option automatically dials up to four userprogrammable phone numbers in the event of any system alarm condition. The
option is designed to deliver a predetermined digital or audible message when
activated. The Auto Dialer option requires a user supplied dedicated digital or
analog phone line.
(-RSAP) REMOTE SUMMARY ALARM PANEL
Wall mountable box provides visual and audible alarms with silent switch. The
panel consists of LED indicators and built-in audible alarm and may be located
up to 1,000 feet away from the inverter system.
(-SEIS) SEISMIC MOUNTING KIT
The seismic mounting kit option is designed to prevent system movement
during seismic events. Heavy-duty brackets are provided to secure system
cabinetry to floor surfaces. Meets Zone 4 requirements.
(-DCS) SUMMARY ALARM DRY CONTACTS
Form C dry contacts for remote monitoring purposes. Rated at 5 amps max.
(250VAC/30VDC), the contacts will change state when any of the following
alarms: are tripped High/Low Battery Charger Voltage, High/Low AC Input
Voltage, Near Low Battery Voltage, Low Battery Voltage, Load Reduction Fault,
High Ambient Temperature, Inverter Fault, Output Fault, Output Overload or
Optional circuit breaker.
(-ZONEM) ZONE MONITORING
Allows voltage monitoring of different circuits than the standard AC utility input.
When the voltage of one of these circuits drops, the inverter system will go into
battery back-up operation mode. Number and voltage of the monitored circuits
to be specified.
(-RS232) DIAGNOSTIC INTERFACE
A microprocessor-based data acquisition system designed to monitor all the
system parameters remotely. Monitors alarm log, event log and automatic test
log. User can command the system to perform a battery test and review all
system parameters. Access is through a DB9 connector and transmits at 9600
baud.
(-INVON) INVERTER ON DRY CONTACTS
Form C dry contacts that will change state when the system transfers to
battery operation
(-VTD) VARIABLE TIME DELAY (FOR NORMALLY OFF CIRCUITS)
After a return of AC utility power, delays retransfer of the inverter for up to 15
min. and continues to supply emergency power to the normally off circuits.
(-BATM) BATTERY CYCLE WARRANTY MONITOR
Device providing battery monitoring at string level or cell level. Please consult
factory for more details.