DTM Vibration Monitor

DTM
Vibration Monitor
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
Table of Contents
DTM SERIES DISTRIBUTED TRANSMITTER MONITOR INTRODUCTION ...................................................................................2
Fully Digital ......................................................................................................................................................................2
Fully Programmable and Flexible.....................................................................................................................................2
Highly Reliable System ......................................................................................................................................................3
Additional Features ...........................................................................................................................................................3
DTM SELECTION GUIDE.........................................................................................................................................................4
DTM10 PROXIMITY DISTRIBUTED TRANSMITTER-MONITOR .................................................................................................5
Applications include: .........................................................................................................................................................5
DTM10 Fully Configurable via Software ..........................................................................................................................5
DTM10 Features................................................................................................................................................................6
Ordering Information ........................................................................................................................................................9
Optional Accessories .......................................................................................................................................................13
DTM10 System Installation .............................................................................................................................................14
DTM20 SEISMIC VIBRATION DISTRIBUTED TRANSMITTER-MONITOR .................................................................................19
Applications include: .......................................................................................................................................................19
DTM20 Fully Configurable via Software ........................................................................................................................19
DTM20 Features..............................................................................................................................................................19
Ordering Information ......................................................................................................................................................23
Optional Accessories .......................................................................................................................................................24
DTM20 System Installation .............................................................................................................................................25
DTM30 TEMPERATURE MODULE .........................................................................................................................................27
DTM30 Features..............................................................................................................................................................27
Specifications...................................................................................................................................................................27
Ordering Information ......................................................................................................................................................28
Optional Accessories .......................................................................................................................................................28
DTM30 System Installation .............................................................................................................................................29
DTM96 COMMUNICATION MODULE ....................................................................................................................................32
DTM96 Features..............................................................................................................................................................32
Specifications...................................................................................................................................................................32
Ordering Information ......................................................................................................................................................33
Optional Accessories .......................................................................................................................................................33
DTM96 System Installation .............................................................................................................................................34
DTM-CFG CONFIGURATION AND CALIBRATION SOFTWARE ...............................................................................................35
DTM-CFG Features ........................................................................................................................................................35
Specifications...................................................................................................................................................................35
Order Information ...........................................................................................................................................................35
ACCESSORIES I TM900 POWER CONVERTER ........................................................................................................................36
ACCESSORIES II ....................................................................................................................................................................37
DIGITAL NETWORK CONNECTION DIAGRAM ........................................................................................................................38
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
-1-
DTM Series Distributed Transmitter Monitor Introduction
•
Fully Digital
The DTM series digital transmitter monitor is vibration
monitor, vibration transmitter and vibration switch all rolled
into one package. Each DTM module can be operated
independently or networked together to create a machine
protection system. It has all the functionalities of an API 670
multi-channel monitor plus a unique field linearization
feature which enables the use of any manufacturers’ probe
and extension cable combination. DTM modules are fully
programmable, flexible, and highly reliable.
Velocity Transducers
DTM30 is a temperature module which works with:
•
Resistance temperature detector (RTD)
•
Thermocouple
DTM96 is a communication module that can be used to
network up to (32) DTMs together to form a vibration
protection system. The DTM96 can be used to
communicate directly with control systems (PLC or DCS)
via modbus to provide data from the DTMs such as: alarm
status, system status, overall value, and more.
Fully Programmable and Flexible
DTM-CFG is the software used to configure the DTM
The DTM is modular in nature and can easily be expanded
into a larger vibration system with the addition of a:
DTM10 (Proximity Probe Sensor Module)
DTM 20 (Case Vibration Sensors Module)
modules (DTM10 and DTM20) either with a local laptop
DTM 30 (temperature Module)
DTM 96 (Communication Module)
DTM- CFG (Configuration Software)
Configurable Parameters:
computer or a remote computer on the network (requires
Modbus connection).
•
•
DTM10 is a proximity probe sensor module which provides
measurements in radial vibration, axial position(thrust), and
speed / phase reference. The DTM10 works with any
proximity probe system combination (including other
•
•
•
Measurement Type (Case Vibration, Radial
Vibration, Axial Position, and Speed/Phase)
Sensor Type and Sensitivity (Proximity Probe,
Accelerometer and Velocity Transducer)
Full Scale Range (g, ips, mm/s, rms, pk, etc..)
Time Delays
Alarm Set Points
manufacturers) and can be used:
•
With or without Probe Driver
•
In any combination of probe and extension cable.
The DTM10 has a field linearization feature which
enables the DTM10 to interface to any proximity
probe system. This feature greatly reduces the
requirement for spare parts.
•
Works with any shaft material (Steel, Tungsten, Kmonel and more).
DTM20 is a case mounted seismic sensor module which
provides case vibration measurements in acceleration,
velocity, or displacement. The DTM20 works with any case
mounted sensor (including other manufacturers):
•
Observe:
•
•
•
Alarm and Channel OK Status
Trip Multiply
Bypass and Overall Vibration Level
Control:
•
•
Trip Multiply values
Bypass and Reset functions
Note: The DTM can be pre-configured at the factory. DTMCFG software is only required when field configuration is
desired.
Accelerometers
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
-2-
Highly Reliable System
Additional Features
The DTM was designed to be used for critical machines as
well as balance of plant applications. Built into every DTM
is a system redundancy based upon a reliable
microprocessor and proprietary system diagnostics which
all contribute to a robust system design which will maximize
Power-Up Inhibit- This feature decreases false alarms due
system uptime.
to higher vibration levels during machine start-up.
Condition Monitoring- Each DTM module has a buffered
output
for
easy
connection
to
a
condition
monitoring system or other vibration analysis
hardware.
Power Redundancy- The DTM module has redundant power
supply inputs to maximize the reliability of the system.
A single power supply failure will not affect the
operation of the system.
Output Redundancy- The DTM module is equipped with
redundant 4-20mA outputs, redundant relay
outputs, and a Modbus communication port. The
DTM relay outputs can be configured for any logic
configuration required.
Channel Redundancy- the DTM can be configured for
triple redundancy with multiple DTMs networked
together.
System Diagnostics- the DTM performs internal diagnostic
tests to search for errors: sensor status, supply
voltage, system power up, fieldbus status and
more. If there is an error, the system OK status
LED on the DTM will go off, and an error will be
registered for the channel and sent via Modbus.
Reliable Microprocessor- critical data and system
configuration is stored in a solid-state memory
chip. The memory chips are designed not to lose
data during an interruption of power. Once power
is restored, the critical data and system
configuration are recovered from the memory
chips.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
-3-
DTM Selection Guide
Model Number
DTM10
DTM20
DTM30
Radial Shaft
Case
Temperature,
Accessory:
Accessory:
Vibration,
Vibration
Dual
Communication
Configuration
Channels
Module
Software
Thrust & Speed
DTM96
DTM-CFG
Available as Pre- Configured or
Field Programmable *1
●
●
●
●
Vibration Measurements
Radial Vibration
●
Axial Position
●
Speed/ Phase Reference
●
●
Case Vibration
●
Temperature
Sensor Interfaces
●
Accelerometer
●
Velocity Transducer
Proximity Probe
●
Works With or Without Probe Driver
●
●
Thermocouple, RTD
Outputs/ Communications
Redundant 4-20mA Output
●
●
S
Relay Output
●
●
●
Redundant Power Supply Input
●
●
S
Modbus Output
●
●
Buffered Output
●
●
(Limited Settings)
●
●
●
Power-Up Inhibit
●
●
●
System OK Checking
●
●
●
2ExnAIIT4X
●
●
Network DTMs via Modbus *2
●
●
Warranty- 2 years
●
●
● (isolation)
Features
Push Button Setup
Hazardous Rating (CSA, ATEX,
GOST R)
II3GExnAIIT4
Class l, Div.2; Grps A, B, C & D, T4
●
●
●
●
● = Complete Offering, S= Single 4-20mA Output or power supply input
Notes:
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
-4-
*1 = Field programming requires DTM-CFG-K Configuration Software kit. Without the software, the DTMs can only be configured
for alarm set points and ZERO adjustment.
*2 =To network up to 32 DTMs via Modbus, requires (1) DTM96 Communication Module
DTM10 Proximity Distributed Transmitter-Monitor
(Shaft Vibration, Thrust Position and Speed)
The DTM10 distributed vibration transmitter-monitor is
DTM10 Fully Configurable via Software
ideal for monitoring machine vibration using proximity
probes and a Modbus interface to a PLC or DCS system.
Vibration Monitor Module
The DTM also contains redundant power supplies and
redundant
4-20mA
transmissions.
Using
Thrust Position Monitor Module
unique
strategy, the DTM can interface with almost any
Speed Monitor Module
proximity probe system without hardware changes.
Phase Reference Monitor module
Applications include:
Turbines
Compressors
Motors
Pumps
Fans
Blowers
Centrifuges
Generators
Turbochargers
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
-5-
LED indication of system OK, Alert , Danger,
DTM10 Features
Interface with almost any manufacture’s
and Bypass
proximity probe system
Local and remote RESET/BYPASS and Trip-
Works with or without probe driver
multiply
Direct Modbus RTU interface
Buffered Output for condition monitoring
Redundant 4-20mA outputs
Aluminum case for RFI/EMI reduction
Redundant power supplies
Digital condition monitoring (optional)
Measure shaft vibration, thrust position, or
speed
Full digital field-configuration
Dual alarms (SPDT)
Specifications
Electrical
Dual 4-20mA, sourced (loop power not required)
Power Supply:
Maximum load resistance:
Alarm Setup:
22-30VDC, 150mA.
Accepts dual power supply inputs
Galvanic isolation:
Accuracy:
380Ω
0 ~ 100% FS.
±0.1%.
Relays:
Among power, circuits and alarms
Frequency Response (-3dB):
Normal frequency:
4 ~ 3.0KHz
Low frequency:
0.5 ~ 100Hz
Proximity probe Interface:
Sensitivity:
Seal:
Epoxy
Capacity:
0.2A/240VAC, 0.4A/110VAC or
2.0A/24VDC, resistive load
Relay type:
SPTD
Isolation:
1000VDC
LED Machine Condition Indicator:
5mm and 8mm probe: 8 mV/um (200 mV/mil)
OK:
System OK indication
11mm probe:
4 mV/um (100 mV/mil)
ALT:
Vibration over ALERT level
25mm probe:
0.787 mV/um (20 mV/mil)
DNG:
Vibration over DANGER level
BYP:
System in BYPASS
TRX:
Digital Transmission Active
Buffered Output:
Original, un-filtered signal
Impedance:
150Ω
RESET/BYPASS:
Maximum cable distance:
300m (1000ft)
Front panel push button
Sensitivity:
same as the sensor
Remote RESET/BYPASS terminals
Local BNC connection and terminal block
Trip Multiply:
for phase reference monitor, buffered outputs TTL
Double Multiply or Triple Multiply set in DTM-CFG
compatible signal
Short Trip/Multi terminal to COM terminal
4-20mA Output:
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
-6-
System alarm level will increase by a factor of 2 or 3
DTM-CFG software. DTM10’s factory default is 10
(DTM10-201 / 301 only)
hours. Every DTM10 could store maximum 1024
Modbus:
trend data.
Alarm Data:
RS485 Modbus RTU
The dynamic alarm data could be stored by the
Not isolated (use DTM96 for isolation)
Local push button programming:
DTM10 when it’s powered on. The DTM10 only
stores one alarm data with highest measured value.
Alert and danger set-point, ZERO calibration
Software programming (DTM-CFG):
User could view waveform and spectrum plot of
Alert and danger set-point, time delay
alarm data by Condition management software or
ZERO and Full-Scale calibration
portable vibration data collector.
Full-scale high and low setup
Alarm latching/ non-latching, energized/ de-energized
Physical
Alarms programmable with alert, danger or system ok
Dimension:
Probe selection, linearization, and system calibration
75mm (2.95″)
Height:
Monitor function change: vibration, position, or speed
see figure below
Modbus communication setup
Trip-multiply setup
Weight:
2.0lb (1.0kg)
Case:
Aluminum cast (copper free)
Real-time bar-graph and alarms
Configure speed monitor to phase reference only monitor
3 layers of password protection
+
TRX
BYP
DNG
OK
ALT
Condition management software or portable vibration
BUF
PROBE
Digital condition monitoring (optional)
data collector of Technivib could collect, store, and
analyze machine running condition based on vibration via
the bus communication of the DTM10.
Rail Mounting
Dynamic waveform data:
Real-time vibration data could be uploaded and the
waveform and spectrum plot could be view by
DIGITAL-TRANSMITTER-MONITOR
TRX
BYP
DNG
BUF
OK
The vibration data could be periodically stored by the
ALT
Trend Data:
PREDICTECH
PROVIBTECH
Condition management software or portable vibration
data collector.
DTM10 when it’s powered on. User could collect
trend data and view trend plots by Condition
management
Electrical specifications continued
software or portable vibration data collector. The
Plate Mounting
trend sampling interval is configured by the related
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
-7-
Environmental
Temperature:
Operation:
-40℃ ~ +85℃
Storage:
-50℃ ~ +100 ℃
Humidity:
90% non-condensing
Certification
CE:
certified with EMC compliance
CSA:
Class I, Div. 2, Grps A, B, C&D, T4
ATEX:
II 3G Ex nA II T4
GOST R:
2Ex nA II T4X
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
-8-
CSA:
ATEX:
Ordering Information
Class I, Div.2, Grps A, B, C&D, T4
II 3G Ex nA II T4
GOST R: 2Ex nA II T4X
DTM10-AX-BX-CX-EXX-MX-SX
Customer configurable proximity distributed
transmitter-monitor
Distributed vibration monitor, fully field configurable, with
Modbus RTU.
AX: Alarms
DTM10-201-AX-CX-GX-IX-MX-SX
Factory configured for vibration (probe driver
required)
AX: Full Scale
A0: Dual alarms with epoxy sealed relays
A1: No Alarm
BX: Mounting
A0*: 0 ~ 200um pk-pk
B0: DIN rail mounting.
B1: Plate mounting.
CX: External Proximity Driver
C0:
Not required (Requires Probe and Extension
Cable) (301, 302, 502 type modules)
C1: Required (Requires Probe, Extension Cable and
Probe Driver) (201, 202, 501 type modules)
EXX: Probe and Cable (Series and Length) -Purchased
0 ~ 1000um pk-pk
A2:
0 ~ 100um pk-pk
A3:
0 ~ 10mil pk-pk
A4:
0 ~ 50mil pk-pk
A5:
0 ~ 5.0mil pk-pk
A6:
0 ~ 200um pk-pk
A7:
0 ~ 1000um pk-pk (0.5 ~ 100Hz)
A8:
0 ~ 100um pk-pk
(0.5 ~ 100Hz)
(0.5 ~ 100Hz)
CX: Alarms
C0*: Dual alarms with epoxy sealed relays
Separately
E00*:
E01:
E02:
E03:
E04:
E05:
E06:
E07:
A1:
TM0180, 5m Cable
TM0180, 9m Cable
8mm Probe, 3300, 5m Cable
8mm Probe, 3300, 9m Cable
8mm Probe, 7200, 5m Cable
8mm Probe, 7200, 9m Cable
TM0105, 5m Cable
TM0105, 9m Cable
E08: TM0110, 5m Cable
E09: TM0110, 9m Cable
E10: 11mm Probe, 3300, 5m Cable
E11: 11mm Probe, 3300, 9m Cable
E12: 11mm Probe, 7200, 5m Cable
E13: 11mm Probe, 7200, 9m Cable
E99: Other probe systems (requiring field calibration)
MX: Digital Communication
M1*:
With Modbus
M2:
With Modbus and digital condition monitoring
C1:
No Alarm
GX: Mounting
G0*: DIN rail mounting.
G1:
Plate mounting.
IX: Frequency Response
I0*:
Normal Frequency (4~3000Hz)
I1:
Low Frequency
(0.5~100Hz)
MX: Digital Communication
M1*: With Modbus
M2:
With Modbus and digital condition monitoring
SX: Approvals.
S0*: CE
S1:
CE
CSA:
Class I, Div.2, Grps A, B, C&D,T4
ATEX:
II 3G Ex nA II T4
GOST R: 2Ex nA II T4X
SX: Approvals
S0*: CE
S1:
CE
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
-9-
DTM10-202- AX-CX-GX-SX
Factory configured for axial position (probe
driver required)
AX: Full Scale
A0*: -1.0 - 0 - 1.0mm (-40 - 0 - 40mil)
(requires TM0180 or other 8mm proximity probe
transducer; TM0105 or other 5mm proximity
probe transducer)
A1: -2.0 - 0 - 2.0mm (-80 - 0 - 80mil)
A2:
A3:
(requires TM0110 or other 11mm proximity
probe transducer)
-5.0 - 0 - 5.0mm (-0.2 - 0 - 0.2inch)
(requires TM0120 or other 25mm, 35mm
proximity probe transducer)
-12.0 - 0 - 12.0mm (-0.5 - 0 - 0.5inch)
(requires TM0150 or other 50mm proximity probe
transducer)
No Alarm
A0:
0 ~ 1,000 rpm
A1*: 0 ~ 3,600 rpm
A2:
0 ~ 6,000 rpm
A3:
0 ~ 10,000 rpm
A4:
0 ~ 30,000 rpm
A5:
0 ~ 50,000 rpm
A6:
phase reference output
A7:
phase reference output for digital condition
monitoring
CX: Alarm
C0*: Dual alarms with epoxy sealed relays
No Alarm
F01*: 1
FXX: Customer specify, number of teeth =XX
GX: Mounting
GX: Mounting
G0*: DIN rail mounting.
Plate mounting.
G0*: DIN rail mounting.
G1:
SX: Approvals
Plate mounting.
SX: Approvals
S0*: CE
S1:
AX: Full Scale
FXX: Teeth per Revolution
C0*: Dual alarms with epoxy sealed relays
G1:
Factory configured for speed (probe driver
required)
C1:
CX: Alarms
C1:
DTM10-501-AX-CX-FXX-GX-SX
S0*: CE
CE
CSA:
Class I, Div.2, Grps A, B, C&D,T4
ATEX:
II 3G Ex nA II T4
GOST R: 2Ex nA II T4X
S1:
CE
CSA:
Class I, Div.2, Grps A, B, C&D,T4
ATEX:
II 3G Ex nA II T4
GOST R: 2Ex nA II T4X
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 10 -
DTM10-301-AX-CX-EXX-GX-IX-MX-SX
Factory configured for vibration (built-in
probe driver)
AX: Full Scale
A0*: 0 ~ 200um pk-pk
A1: 0 ~ 500um pk-pk
A2: 0 ~ 100um pk-pk
A3: 0 ~ 10mil pk-pk
A4: 0 ~ 25mil pk-pk
A5: 0 ~ 5.0mil pk-pk
A6: 0 ~ 200um pk-pk (0.5 ~ 100Hz)
A7: 0 ~ 500um pk-pk (0.5 ~ 100Hz)
A8: 0 ~ 100um pk-pk (0.5 ~ 100Hz)
CX: Alarms
C0*: Dual alarms with epoxy sealed relays
C1: No Alarm
EXX: Probe and Cable
E00*:
TM0180, 5m Cable
E01: TM0180, 9m Cable
E02: 8mm Probe, 3300, 5m Cable
E03: 8mm Probe, 3300, 9m Cable
E04: 8mm Probe, 7200, 5m Cable
E05: 8mm Probe, 7200, 9m Cable
E06: TM0105, 5m Cable
E07: TM0105, 9m Cable
E08: TM0110, 5m Cable
E09: TM0110, 9m Cable
E10: 11mm Probe, 3300, 5m Cable
E11: 11mm Probe, 3300, 9m Cable
E12: 11mm Probe, 7200, 5m Cable
E13: 11mm Probe, 7200, 9m Cable
GX: Mounting
G0*: DIN rail mounting.
G1: Plate mounting.
IX: Frequency Response
I0*: Normal Frequency (4~3000Hz)
I1:
Low Frequency (0.5~100Hz)
MX: Digital Communication
M1*: With Modbus
M2:
With Modbus and digital condition monitoring
CSA:
ATEX:
Class I, Div.2, Grps A,B,C&D,T4
II 3G Ex nA II T4
GOST R: 2Ex nA IIT4X
DTM10-302-AX-CX-EXX-GX-SX
Factory configured for axial position (built-in
probe driver)
AX: Full Scale
A0*: -1.0 - 0 - 1.0mm (-40 - 0 - 40mil)
(Requires TM0180 or other 8mm proximity probe
transducer)
A1: -2.0 - 0 - 2.0mm (-80 - 0 - 80mil)
(Requires TM0110 or other 11mm proximity
probe transducer)
CX: Alarms
C0*: Dual alarms with epoxy sealed relays
C1: No Alarm
EXX: Probe and Cable
E00*:
TM0180, 5m Cable
E01: TM0180, 9m Cable
E02: 8mm Probe, 3300, 5m Cable
E03: 8mm Probe, 3300, 9m Cable
E04: 8mm Probe, 7200, 5m Cable
E05: 8mm Probe, 7200, 9m Cable
E06: TM0105, 5m Cable
E07: TM0105, 9m Cable
E08: TM0110, 5m Cable
E09: TM0110, 9m Cable
E10: 11mm Probe, 3300, 5m Cable
E11: 11mm Probe, 3300, 9m Cable
E12: 11mm Probe, 7200, 5m Cable
E13: 11mm Probe, 7200, 9m Cable
GX: Mounting
G0*: DIN rail mounting.
G1: Plate mounting.
SX: Approvals
S0*: CE
S1:
CE
CSA:
Class I, Div.2, Grps A, B, C&D, T4
ATEX:
II 3G Ex nA II T4
GOST R: 2Ex nA II T4X
SX: Approvals
S0*: CE
S1:
CE
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 11 -
GOST R: 2Ex nA IIT 4X
DTM10-502-AX-CX-EXX-FXX-GX-SX
Factory configured for speed (built-in probe
driver)
* Denote factory default.
AX: Full Scale
A0: 0 ~ 1,000 rpm
A1*: 0 ~ 3,600 rpm
A2: 0 ~ 6,000 rpm
A3: 0 ~ 10,000 rpm
A4: 0 ~ 30,000 rpm
A5: 0 ~ 50,000 rpm
A6: phase reference output
A7:
phase reference output for digital condition
monitoring
CX: Alarms
C0*: Dual alarms with epoxy sealed relays
C1: No Alarm
EXX: Probe and Cable
E00*:
TM0180, 5m Cable
E01: TM0180, 9m Cable
E02: 8mm Probe, 3300, 5m Cable
E03: 8mm Probe, 3300, 9m Cable
E04: 8mm Probe, 7200, 5m Cable
E05: 8mm Probe, 7200, 9m Cable
E06: TM0105, 5m Cable
E07: TM0105, 9m Cable
E08: TM0110, 5m Cable
E09: TM0110, 9m Cable
E10: 11mm Probe, 3300, 5m Cable
E11: 11mm Probe, 3300, 9m Cable
E12: 11mm Probe, 7200, 5m Cable
E13: 11mm Probe, 7200, 9m Cable
FXX: Teeth per Revolution
F01*: 1
FXX: Customer specify, number of teeth =XX
GX: Mounting.
G0*: DIN rail mounting.
G1: Plate mounting.
SX: Approvals
S0*: CE
S1:
CE
CSA:
ATEX:
Class I, Div.2, Grps A, B, C&D, T4
II 3G Ex nA II T4
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 12 -
RS485-USB converter with cable
Optional Accessories
TM900
DTM-CAL
Power converter with isolation. Converts 95-250 VAC into
The DTM field calibration kit is capable of calibrating any
24VDC and is capable of powering up to five DTM modules.
5mm, 8mm, or 11mm probe system. The kit includes:
DTM-CFG configuration and calibration software CD
RS485-USB converter with cable
TM0540 proximity probe field calibration kit
DTM-CFG-K
The DTM configuration and calibration software kit includes:
DTM-CFG configuration and calibration software CD
Proximity Sensor Systems
TM0180:
TM0105:
TM0110:
TM0181:
TM0182:
TM0120:
8mm probe
5mm probe
11mm probe
Extension cable
Probe driver
25mm probe system
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 13 -
DTM10 System Installation
4-20mA+(1)
COM
SIG
TM0200 or
PLC,DCS
BUF
Buffer
Out
PWR
BUF
COM
DTM10-201/202/501 Field-Wiring Diagram
TM0182 Driver
+
SIG
COM
COM
POW-24V
4-20mA+(2)
COM
COM
TRIP/M
RST/BYP
PROVIBTECH
Trip /Multiply
or phase
reference
input/output
COM
TM0200 or
PLC,DCS
Remote
Reset
OK
ALT
TM0181
Cable
BUF
DNG
BYP
NO2
NO1
ARM2
ARM1
NC2
NC1
COM
24V+(2)
24V+(2)
GND
24V+(1)
To
Alert
GND
To
Danger
BUS(+)
RS-485+
RS-485- PLC/DCS or
DTM-CFG
24V+(1)
TM0180
Proximity Probe
BUS(-)
TRX
Power
Power
Supply 1 Supply 2
Note:
Power supply 2 and 4-20mA(2) are optional outputs used for redundancy.
Alert and Danger relays are shown connected as normally open. Connect ARM and NC for normally closed.
Connecting COM and RST/BYP with an external continuous or momentary closed switch will initiate a remote reset.
Temporarily closing the switch will result in a system reset, continuous close will result in a system bypass.
If the DTM10-201 has the digital condition monitoring function, the Trip/Multi and COM pins are used for phase
reference input. Moreover, the DTM10-201 won’t provide Multiply Alarm function anymore, so you should set Multiply
Alarm property to “None” by DTM-CFG software.
If Full Scale of DTM10-501 is phase reference output (A6), Buffer output terminal will provide phase reference signal.
If Full Scale of DTM10-501 is phase reference output for digital condition monitoring (A7), Trip/Multi terminal provides
the phase reference signal for the DTM10-201, DTM10-301 or DM200. A DTM10-501 can provide the phase reference
signal for up to 6 DTMs or DM200s.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 14 -
DTM10-201/202/501 Field-Wiring Diagram (Probe is TM0120)
Note:
Power supply 2 and 4-20mA(2) are optional outputs used for redundancy.
Alert and Danger relays are shown connected as normally open. Connect ARM and NC for normally closed.
Connecting COM and RST/BYP with an external continuous or momentary closed switch will initiate a remote reset.
Temporarily closing the switch will result in a system reset, continuous close will result in a system bypass.
If the DTM10-201 has the digital condition monitoring function, the Trip/Multi and COM pins are used for phase
reference input. Moreover, the DTM10-201 won’t provide Multiply Alarm function anymore, so you should set Multiply
Alarm property to “None” by DTM-CFG software.
If Full Scale of DTM10-501 is phase reference output (A6), Buffer output terminal will provide phase reference signal.
If Full Scale of DTM10-501 is phase reference output for digital condition monitoring (A7), Trip/Multi terminal provides
the phase reference signal for the DTM10-201, DTM10-301 or DM200. A DTM10-501 can provide the phase reference
signal for up to 6 DTMs or DM200s.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 15 -
DTM10-201/202/501 Hazardous Area Field-Wiring Diagram
Note:
Power supply 2 and 4-20mA(2) are optional outputs used for redundancy.
Alert and Danger relays are shown connected as normally open. Connect ARM and NC for normally closed.
Connecting COM and RST/BYP with an external continuous or momentary closed switch will initiate a remote reset.
Temporarily closing the switch will result in a system reset, continuous close will result in a system bypass.
If the DTM10-201 has the digital condition monitoring function, the Trip/Multi and COM pins are used for phase
reference input. Moreover, the DTM10-201 won’t provide Multiply Alarm function anymore, so you should set Multiply
Alarm property to “None” by DTM-CFG software.
If Full Scale of DTM10-501 is phase reference output (A6), Buffer output terminal will provide phase reference signal.
If Full Scale of DTM10-501 is phase reference output for digital condition monitoring (A7), Trip/Multi terminal provides
the phase reference signal for the DTM10-201, DTM10-301 or DM200. A DTM10-501 can provide the phase reference
signal for up to 6 DTMs or DM200s.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 16 -
DTM10-201/202/501 Hazardous Area Field-Wiring Diagram (Probe is TM0120)
Note:
Power supply 2 and 4-20mA(2) are optional outputs used for redundancy.
Alert and Danger relays are shown connected as normally open. Connect ARM and NC for normally closed.
Connecting COM and RST/BYP with an external continuous or momentary closed switch will initiate a remote reset.
Temporarily closing the switch will result in a system reset, continuous close will result in a system bypass.
If the DTM10-201 has the digital condition monitoring function, the Trip/Multi and COM pins are used for phase
reference input. Moreover, the DTM10-201 won’t provide Multiply Alarm function anymore, so you should set Multiply
Alarm property to “None” by DTM-CFG software.
If Full Scale of DTM10-501 is phase reference output (A6), Buffer output terminal will provide phase reference signal.
If Full Scale of DTM10-501 is phase reference output for digital condition monitoring (A7), Trip/Multi terminal provides
the phase reference signal for the DTM10-201, DTM10-301 or DM200. A DTM10-501 can provide the phase reference
signal for up to 6 DTMs or DM200s.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 17 -
DTM10-301/302/502 Field-Wiring Diagram
Note:
Power supply 2 and 4-20mA(2) are optional outputs used for redundancy.
Alert and Danger relays are shown connected as normally open. Connect ARM and NC for normally closed.
Connecting COM and RST/BYP with an external continuous or momentary closed switch will initiate a remote reset.
Temporarily closing the switch will result in a system reset, continuous close will result in a system bypass.
If the DTM10-201 has the digital condition monitoring function, the Trip/Multi and COM pins are used for phase
reference input. Moreover, the DTM10-201 won’t provide Multiply Alarm function anymore, so you should set Multiply
Alarm property to “None” by DTM-CFG software.
If Full Scale of DTM10-501 is phase reference output (A6), Buffer output terminal will provide phase reference signal.
If Full Scale of DTM10-501 is phase reference output for digital condition monitoring (A7), Trip/Multi terminal provides
the phase reference signal for the DTM10-201, DTM10-301 or DM200. A DTM10-501 can provide the phase reference
signal for up to 6 DTMs or DM200s.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 18 -
DTM20 Seismic Vibration Distributed Transmitter-Monitor
(Acceleration, Velocity and Displacement)
The
DTM20
distributed
vibration
transmitter-monitor
provides a simple and cost-effective solution for monitoring
“balance-of-plant” equipment. The DTM20 monitor can
interface with almost any seismic vibration sensor and can
be fully field-configurable. In addition to this it also improves
system reliability with redundant power supplies and
redundant 4-20mA transmissions.
Applications include:
Motors
Pumps
DTM20 Features
Fans
Blowers
Engines
Compressors
Centrifuges
Generators
Turbines
Turbochargers
DTM20 Fully Configurable via Software
Acceleration Monitor
Velocity Monitor
Displacement Monitor
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 19 -
Measures acceleration, velocity or
Local and remote RESET / BYPASS and trip-
displacement
multiply
Direct Modbus RTU interface
Buffered Output for condition monitoring
Redundant 4-20mA outputs (pk or RMS)
Aluminum case for RFI/EMI
Redundant power supplies
Epoxy potted for better environmental
Fully digital field-configuration
protection
Dual relay output with Alert and Danger
Signal filtering
(SPDT)
Digital condition monitoring (optional)
LED indication of system OK, alert, and
danger
Specifications
Electrical
100mV/in/sec
Power Supply:
4mV/um
Specified sensitivity of any vibration sensor
22-30VDC, 150mA.
Accepts dual power supply inputs
Current Source
Nominal
Galvanic isolation:
Among power, circuits and alarms
Frequency Response (-3dB):
Seismic Velocity Sensor Interface:
Sensitivity:
User specified for any vibration sensor
Nominal Frequency:
Acceleration:
4 ~ 3KHz
Velocity:
4 ~ 3KHz
Displacement:
4 ~ 3KHz
Software programmable
Buffered Output:
Original vibration, un-filtered
Impedance:
Low Frequency:
300m (1000ft)
0.5 ~ 100Hz (TM079VD)
Sensitivity:
same as the sensor
0.5 ~ 100Hz(TM079VD)
Local BNC connection and remote terminal connection
0.5 ~ 100Hz
Velocity:
Displacement:
4-20mA Output:
High Frequency:
Acceleration:
10 – 20KHz (peak)
Filtering:
Dual 4-20mA, sourced (loop power not required)
Maximum load resistance
8 pole 160dB/ Dec .Low-pass
Alarm Setup:
1 pole 20dB/ Dec. High-pass
Accuracy:
Factory setting
0 ~ 100% FS
±0.1%.
Relays:
Customer specifiable
Sensitivity:
150Ω
Maximum cable distance:
Acceleration:
ICP Sensor Interface:
4mA@24VDC
Seal:
Epoxy.
Capacity:
0.2A/240VAC,
0.4A/110VAC
100mV/g
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 20 -
500Ω
2.0A/24VDC, resistive load
Relay type:
SPTD
Isolation:
1000VDC
LED Machine Condition Indicator:
OK:
System OK indication
ALT:
Vibration over Alert level
DNG:
Vibration over Danger level
BYP:
System in BYPASS
TRX:
Digital transmission active
RESET/BYPASS:
Front panel push-button
Remote RESET/BYPASS terminals
Trip-Multiply
Double Multiply or Triple Multiply set in DTM-CFG
Short Trip/Multi terminal to COM terminal
System alarm level will increase by a factor of 2 or 3
Modbus:
RS485 Modbus RTU
Real-time vibration data could be uploaded and the
waveform and spectrum plot could be view by
Condition management software or portable vibration
data collector.
Trend Data:
The vibration data could be periodically stored by the
DTM20 when it’s powered on. User could collect trend
data and view trend plots by Condition management
software or portable vibration data collector. The trend
sampling interval is configured by the related DTMCFG software. DTM20’s factory default is 10 hours.
Every DTM20 could store maximum 1024 trend data.
Alarm Data:
The dynamic alarm data could be stored by the
DTM20 when it’s powered on. The DTM20 only stores
one alarm data with highest measured value. User
could view waveform and spectrum plot of alarm data
by Condition management software or portable
vibration data collector.
Physical
Non-isolated (use DTM96 for isolation)
Dimension:
Software programming (DTM-CFG):
Height:
Alert and danger set-point, time delay
see figure below
ZERO and Full-Scale calibration
Full-scale high and low setup
75mm (2.95″)
Weight:
Case:
2.0lb (1.0kg)
Aluminum cast (copper free)
Alarm latching/ non-latching, energized/ de-energized
Alarms programmable with alert, danger or system ok
Sensor selection and system calibration
Measurand / Integration changes: A, V, D
Modbus communication setup
Trip-multiply setup
Electrical specifications continued
Environmental
Temperature:
Operation:
-40℃ ~ +85℃.
Storage:
-50℃ ~ +100℃.
Humidity:
90% non-condensing.
Real-time bar-graph and alarms
3 layers of password protection
Digital condition monitoring (optional)
Condition management software or portable vibration
data collector of Technivib could collect, store, and
analyze machine health condition based on vibration via
the bus communication of the DTM20.
Dynamic waveform data:
Certification
CE certified with EMI compliance
CSA:
ATEX:
GOST R:
Class I, Div. 2, Grps A,B,C&D,T4
II 3G Ex nA II T4
2Ex nA II T4X
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 21 -
TRX
BYP
DNG
OK
ALT
BUF
+
DIGITAL-TRANSMITTER-MONITOR
BYP
TRX
BUF
ALT
DNG
OK
PREDICTECH
PROVIBTECH
Rail Mounting
Plate Mounting
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 22 -
Ordering Information
DTM20-AX-BX-IX-MX-SX
Customer configurable seismic distributed
transmitter-monitor
Distributed vibration monitor, fully field configurable, with
Modbus RTU.
AX: Alarm and sensors
A0: With Epoxy sealed relays, ICP sensors
A1: No Alarm, ICP sensors
A2: Dual epoxy sealed relay alarms, seismic velocity
A3: No Alarm, seismic velocity
BX: Mounting
B0: DIN rail mounting.
B1: Plate mounting.
IX: Frequency response
I0*: Normal/ High frequency
I1:
Low frequency
MX: Digital Communication
M1*: With Modbus
M2:
A11: 0 - 25mm/s pk
A12: 0 - 5.0g pk
A13: 0 - 10g pk
A14: 0 – 8mil pk-pk
A15: 0 – 20mil pk-pk
A16: 0 – 4mil pk-pk
A17: 0 – 10mil pk-pk
A18: 0 – 5mil pk-pk
A19: 0 – 2.0 ips pk
A20: 0 – 4.0 ips pk
A21: 0 – 0.8 ips pk
A22: 0 – 1.0 ips pk
A26: 0 - 50mm/s rms
A27: 0 - 100mm/s rms
A28: 0 - 20mm/s rms
A31: 0 - 25 mm/s rms
A32: 0 - 2.0 ips rms
A33: 0 - 4.0 ips rms
A34: 0 - 0.8 ips rms
A35: 0 - 1.0 ips rms
CX: Alarms
C0*: Dual alarms with epoxy sealed relays
C1:
GX: Mounting
G0*: DIN rail mounting.
With Modbus and digital condition monitoring
SX: Approvals
G1:
Plate mounting.
HX: Sensor (not include)
S0*: CE
S1: CE
CSA:
Class I, Div. 2,Grps A,B,C&D,T4
ATEX:
II 3G ExnA II T4
GOST R: 2Ex nA II T4X
H0*: TM0782A or any ICP accelerometer with 100mV/g
(A00~A05 not available)
H1: TM0793V or any ICP velocity sensor with
4mV/mm/s (A12, 13 not applicable)
H2: TM079VD (A12, 13 not available)
HXXX: Seismic velocity sensor, Sensitivity = XXX
DTM20-101-AXX-CX-GX-HX-IX-MX-SX
Factory configured seismic monitor
AXX: Full Scale
A00:
A01:
A02:
A03:
A05:
A06*:
A07:
A08:
No Alarm
0 - 200um pk-pk
0 - 500um pk-pk
0 - 100um pk-pk
0 - 250um pk-pk
0 - 125um pk-pk
0 - 50mm/s pk
0 - 100mm/s pk
0 - 20mm/s pk
mV/in/sec (A12, 13 not available)
IX: Frequency Response
I0*:
I1:
I2:
Normal Frequency (4 ~ 3KHz, H2 not available)
Low Frequency (0.5~100Hz)
High frequency (10 – 20KHz, A12, A13 only with
accelerometer)
MX: Digital Communication
M1*: With Modbus
M2:
With Modbus and digital condition monitoring
SX: Approvals
S0*: CE
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 23 -
S1:
CE
CSA:
Class I, Div. 2,Grps A,B,C&D,T4
ATEX:
II 3G ExnA II T4
GOST R: 2ExnAIIT4X
TM900
Power converter with isolation. Converts 95-250 VAC into
24VDC and is capable of powering up to five DTM modules.
* Denotes factory default.
Optional Accessories
Seismic Sensor Systems
DTM-CFG-K
The DTM configuration and calibration software kit includes:
DTM-CFG configuration and calibration software CD
TM0782A-K-M:
Accelerometer kit
TM0783A-K-M:
Accelerometer with cable
TM0793V-K-M:
Velocity sensor kit
TM079VD-V/H-K: Low frequency sensor
RS485-USB converter with cable
.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 24 -
DTM20 System Installation
DTM20 Field-Wiring Diagram
Note:
Power supply 2 and 4-20mA(2) are optional connections used for redundancy.
Alert and Danger relays are shown connected as normally open. Connect ARM and NC for normally closed.
Connecting COM and RST/BYP with an external continuous or momentary closed switch will initiate a remote reset.
Temporarily closing the switch will result in a system reset, continuous close will result in a system bypass.
If DTM20 has the digital condition monitoring function, the Trip/Multi and COM pins are used for phase reference input.
Thus, the DTM20 won’t provide the Trip Multiply and the Trip Multiply property should be set to “None” in the DTM-CFG
software.
When using the signal condition monitoring function the DTM20 works with DTM10-501/502 to provide a phase
reference output. In this case connect Trip/Multi of DTM20 with Trip/Multi of DTM10-501/502 and connect COM of
DTM20 with COM of DTM10-501/502.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 25 -
DTM20 Hazardous Area Field-Wiring Diagram
Note:
Power supply 2 and 4-20mA(2) are optional connections used for redundancy.
Alert and Danger relays are shown connected as normally open. Connect ARM and NC for normally closed.
Connecting COM and RST/BYP with an external continuous or momentary closed switch will initiate a remote reset.
Temporarily closing the switch will result in a system reset, continuous close will result in a system bypass.
If DTM20 has the digital condition monitoring function, the Trip/Multi and COM pins are used for phase reference input.
Thus, the DTM20 won’t provide the Trip Multiply and the Trip Multiply property should be set to “None” in the DTM-CFG
software.
When using the signal condition monitoring function the DTM20 works with DTM10-501/502 to provide a phase
reference output. In this case connect Trip/Multi of DTM20 with Trip/Multi of DTM10-501/502 and connect COM of
DTM20 with COM of DTM10-501/502.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 26 -
DTM30 Temperature Module
The DTM30 temperature module is a single channel
Specifications
temperature signal conditioner and pro
cessing unit. DTM30 accepts resistance temperature
detector (RTD) and thermocouple signal input and
Electrical
Power Supply:
24V DC ±10% @200 mA
has a choice of output options including an isolated (0 or 4
to 20) mA re-transmission signal, change over trip relay,
twin normally open relays or various combinations. DTM30
has a high degree of functionality and configurability. For
systems that require more local input, DTM30 with an inbuilt keypad and digital display are available where
functions can be accessed via the front panel keys.
DTM30 Features
Input/output/power isolation
Inputs:
DTM30 units can accept the following input types.
RTD:
Pt100, Ni120
Thermocouple:
K, J, T, R, S, E, F, N, B
RTD:
Sensor range:
-200 to 850°C
Linearization:
Pt100 (BS EN 60751/JISC
1604)/Ni120/Custom
Basic accuracy:
0.1°C ± 0.05% of read ing
Powerful standard functions which the user
Thermal drift (zero):
±0.004Ω/°C
can easily configure via front panel keys
Thermal drift (span):
100ppm/°C
Digital display measurement value
Excitation current:
1mA
Isolated (0 or 4 to 20) mA output
Lead resistance effect:
0.002 °C/ Ω
Max lead resistance:
50Ω/leg
Dual relay output
35mm DIN rail mounting
Thermocouple:
Sensor range:
Type
Range(°C)
K
-200 to 1370
J
-200 to 1200
T
-210 to 400
R
-10 to 1760
S
-10 to 1760
E
-200 to 1000
F
-100 to 600
N
-180 to 1300
B
-10 to 1650
Custom
user defined
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 27 -
Basic accuracy:
EMC emissions:
BS EN50081-1
± 0.04% FS or ± 0.04% reading or ±0.5°C,
EMC immunity:
BS EN50082-2
whichever is greater(For type R & S, stated
Display Range:
-1999 to 9999
accuracy only applies between 800 &1760°C)(For
type B, stated accuracy only applies between 400
Physical
Cold junction error:
±0.5°C
Cold junction tracking:
0.05°C/°C
Cold junction range:
-20 to 70°C
Thermal drift (zero):
± 4µV/°C
Thermal drift (span):
± 200ppm /°C
Temperature Module
Custom
PROVIBTECH
O/P1 RE-TRAN O/P2 N/C RELAY
BS4937 / IEC 584-3 /
DTM30
& 1650°C)
Linearization:
Outputs:
Relays
Alarm Action:
Off, High, Low, Deviation, Test
PROVIBTECH
Max switching voltage: 48V RMS (AC)/ 48V (DC)
Max current:
1A @48V(AC)/ 1A @ 30V(DC)
Max power:
60VA(AC)/ 30W(DC)
Hysteresis:
Programmable 0 to 100%
Delay Time:
Programmable (Alarm must
SUPPLY:
PN:
SN:
24V±10% 6VA MAX
DTM30-A0
SN89000001
www.provibtech.com
be continuously present for
this period in order to be
recognized)
Start-up Delay:
Programmable
Operate time:
<5ms
Electrical life @ full load: 100,000 operations
Mechanical life:
10,000,000 operations
Environmental
Temperature:
Operation:
Storage:
Humidity:
-30℃ ~ +60℃.
-50℃ ~ +85℃.
10 to 90% RH
Current Retransmission:
Output Range:
0-10, 0-20, 4-20 mA source or sink
Maximum current output: <23mA
Accuracy:
0.07%
Max power supply:
30V (In sink mode)
Ordering Information
DTM30-AX
A0:Basic module
Optional Accessories
General:
EMC Approval:
EN61326: 1997
Immunity:
Annex A Industrial
Response Time:
300mSec typical
Power converter with isolation. It converts 95-250 VAC into
Isolation:
500V AC I/P~O/P~PSU
24VDC and is capable of powering up to five DTM modules.
TM900
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 28 -
DTM30 System Installation
DTM30 Field-Wiring Diagram for RTD
Note:
DTM30 is provided with a unique ‘BUS JUMPER’ system for quick wiring of communications and power connections. To
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 29 -
use the Bus Jumper, disconnect all power supply/communications connectors and place them so that they connect
between the two units. Wiring to one connector then connects to all units.
DTM30 Field-Wiring Diagram for Thermocouple
Note:
DTM30 is provided with a unique ‘BUS JUMPER’ system for quick wiring of communications and power connections. To
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 30 -
use the Bus Jumper, disconnect all power supply/communications connectors and place them so that they connect
between the two units. Wiring to one connector then connects to all units.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 31 -
DTM96 Communication Module
The DTM96 functions as an RS232 to RS485 convertor
and / or enables (32) DTM modules to be networked
together via Modbus. Combined with the DTM-CFG
configuration software, the DTM96 truly provides a
distributed vibration system. The Modbus interface
enables users to remotely monitor, configure, and
calibrate the DTMs.
DTM96 Features
Direct Modbus RTU interface
Optically isolated RS485, RS422, and RS232
communications
Physical
Dimension:
Height:
Communicate with the DTM using your
computers RS232 connection
75mm (2.95″)
see figure below.
1.0lb (0.5kg).
Aluminum cast (copper free)
Weight:
Case:
TX
Specifications
POWER
PROVIBTECH
DTM
RX
Provides galvanic isolation between PC and
Electrical
DTM96
Modbus TCP
RJ45 Ethernet connection
Galvanically Isolated
Rail Mounting
TX
Modbus RTU
RS485 and RS232
Galvanically Isolated
RX
Modbus:
POWER
22-30VDC, 150mA
Galvanic isolation
PROVIBTECH
PREDICTECH
Power Supply:
Plate Mounting
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 32 -
Ordering Information
Environmental
DTM96-AX-BX-SX
Temperature:
Operation:
Storage:
-40℃ ~ +85℃ .
-50℃ ~ +100℃ .
Humidity:
90% non-condensing.
DTM interface module with RS485 and RS232.
Certification
CE certified with EMI compliance
CSA:
Class I, Div. 2, Grps A, B, C&D, T4
ATEX:
II 3G Ex nA II T4
GOST R: 2Ex nA II T4X
Hazardous area
AX: Output
A0*: Modbus RS485, RS232, RS422
BX: Mounting
B0*: DIN rail mounting
B1: Plate mounting
SX: Approvals
S0*: CE
S1: CE certified with EMI compliance
CSA: Class I, Div. 2, Grps A, B, C&D, T4
ATEX: II 3G Ex nA II T4
GOST R: 2Ex nA II T4X
Marking:
* Denotes factory default.
ATEX Standards :
EN 60079-0
EN 60079-15
Special condition in hazardous area:
― The ambient temperature range is: -40℃≤Ta≤70℃
― DTMs must be placed inside an enclosure that is in
accordance with EN 60079-15:2005.
― Provisions must be made externally to prevent the
rated voltage from being exceeded by transient
disturbances of more than 40 %.
Optional Accessories
TM900
Power converter with isolation. It converts 95-250 VAC
into 24VDC and is capable of powering up to five DTM
modules.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 33 -
DTM96 System Installation
Installation – field-wiring diagram
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 34 -
DTM-CFG Configuration and Calibration Software
DTM-CFG is the configuration and calibration software
used to configure all DTM modules. DTM-CFG works with
Windows XP or Windows 2000 operating system.
DTM-CFG can be connected to the DTM modules with the
interface of a RS485-USB cable kit.
DTM-CFG combined with the DTM96 allows the user to
remotely interface with 32 DTMs networked together in the
field.
DTM-CFG Features
DTM Configuration
Order Information
DTM Calibration
DTM-CFG-K
DTM configuration and calibration software kit includes:
Specifications
DTM-CFG configuration and calibration software CD
RS485-USB converter with cable
User manual
Module Configuration:
Module type selection
Modbus ID address, Range
Communication baud rate
Auto manual search of communication port
English or metric selection
Password and security
DTM-CFG
DTM configuration and calibration software includes:
DTM-CFG configuration and calibration software CD
User manual
DTM-CAL
Operation Configuration:
Sensor and sensitivity selection
Measurement unit selection
Full-scale
Dual-alarm set-points, time delay, latching
Relay energized/de-energized. Relay programmed to
Alert or OK
OK set-points
Maintenance Calibration:
ZERO calibration, SPAN calibration
Probe linearization calibration
Real-time overall and status display
Record of overall and status
Configuration parameter save as file
The DTM field calibration kit with probe calibration
capability with any 5mm, 8mm and 11mm probe system.
The kit includes:
DTM-CFG configuration and calibration software CD
RS485-USB converter with cable
TM0540 proximity probe field calibration kit
User manual
Optional Accessories
RS485-USB: RS485 to USB converter with cable
RS232-USB: RS232 to USB converter with cable
DTM96: Isolated communication module
TM0540:
Proximity
probe
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 35 -
field
calibration
kit
Accessories I TM900 Power Converter
Reliable Power Converter
The TM900 power converter is designed specifically for the
DTM series transmitter-monitor. Each TM900 can supply
power for up to five DTM series transmitter-monitors. The
24Vdc output of the power converter is isolated from its
input and is short circuit protected.
Specifications
Electrical
AC Power Input:
90~250VAC
Power Output:
Current:
Isolation:
Voltage: 24VDC±5%.
< 750mA.
1000VAC.
Fuse:
2.0A, 250VAC.
TM900 Plate Mounting
Physical
Dimension:
Height:
Weight:
75mm (2.95″)
see figure below
1.0kg (2.0 lb)
Environmental
Temperature:
Operation:
-40℃ ~ +85℃.
Storage:
Humidity:
-50℃ ~ +100℃.
90% non-condensing.
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 36 -
Certifications
CE certified with EMC compliance
Ordering Information
TM900–GX
GX: Mounting.
G0*: 35mm DIN rail mounting.
G1: Plate mounting.
TM900 DIN Rail Mounting
Accessories II
DTM-CFG
Configuration and calibration software
DTM RS485-USB
Converter from RS485 to USB for
configuration with laptop computer
DTM RS485-RS232
PCM370
PCM370 condition monitoring software is
ideal for plant wide condition monitoring.
and trending of overall vibration levels
PT2060/98-PC
Touch panel PC with IP65 rating. Ideal to
work with PCM370 and DTM-CFG
Converter from RS485 to RS232 for
configuration with desktop computer
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 37 -
Digital Network Connection Diagram
Condition
Monitoring
Condition
Monitoring
PCM370
PCM370
Condition
Monitoring
OR
PCM370
Monitor
Display
/Config
OR
DTM-CFG
PLC/DCS
Modbus Network
4-20mA to
PLC/DCS
DTM10
DTM20 DTM30
4-20mA to
PLC/DCS
DTM96
DTM SUB-SYSTEM 1
DTM10
DTM20 DTM30
4-20mA to
PLC/DCS
DTM96
DTM SUB-SYSTEM 2
DTM10
DTM20 DTM30
DTM96
DTM SUB-SYSTEM 3
Note:
Relay outputs and 4-20mA outputs can be hard wired directly to the PLC/DCS.
Digital communication via modbus is available to communicate with the Plant Information Network.
Relay alarms and controls such as Reset, Trip-multiply etc. need to be hardwired to the control system
(PLC/DCS)
technivib - Z.I de Pringy - 531 route des vernes – 74 370 PRINGY – France
Tél : 0033 4 50 01 23 20.– Fax : 0033 4 50 01 57 81 – e.mail : info@technivib.com
Website : www.technivib.com
- 38 -