Data sheet 707010
Page 1/9
JUMO dTRANS T01 HART® / T01T HART® /
T01 Junior / T01 Ex / T01 HART® Ex
Programmable 2-wire transmitter
for connection to RTD temperature probes and thermocouples
for installation in : terminal head Form B to DIN 43729
for mounting on : rail
Type 707011/... (HART®),
Type 707015/... (Ex),
Type 707016/... (HART® Ex)
Brief description
The 2-wire transmitter detects the temperature by means of an RTD temperature probe or
a thermocouple. For RTD temperature probes, the probe can be connected in a 2-wire
circuit, 3-wire circuit, or 4-wire circuit. The probe type, connection type, and measuring
range can be configured using a setup program. The output signal 4 to 20 mA or reversed
20 to 4 mA is available in a linearized way (temperature linear).
The device is designed for industrial applications and complies with the respective European standards to guarantee electromagnetic compatibility (EMC).
The inexpensive version dTRANS T01 Junior type 707014/... supports a limited selection
of RTD temperature probes and thermocouples. This type does not have a customerspecific linearization.
The versions 707015/... and 707016/... are electrical equipment for use in a potentially
explosive area.
The transmitters JUMO dTRANS T01 (types 707011/..., 707013/... and 707016/...) can
also be programmed using a HART® modem in conjunction with a PC setup program.
Type 707014/... (Junior)
System diagrams
Connection examples (Types 707011/... to 707014/...) with power supply unit
Type 707013/... (HART®)
Features
k Types 707011/..., 707013/... and
Connection examples (Types 707015/... and 707016/...) for Ex application
with Ex supply isolator
Ex area
outside Ex area
Ex 2-wire
transmitter
+
4—20 mA
-
-
= =
~
L1
Only in conjunction
with certified
Ex supply isolator
+
-
+
-
+
-
+
-
4—20 mA / 0—20 mA
-
N
-
+
+
0—10 V
-
2013-01-10/00383981
k Type 707016/... with HART® interface
and as Ex version
Recorder
+
+
1
Indicator
II 1 G Ex ia IIC T6
II 1 G Ex ia IIC T6/T5/T4
II 2 G Ex ia IIC T6/T5/T4
Ex supply
isolator 1
+
=
Controller
707016/... with HART® interface
k Type 707015/... Ex version
-
k Type 707013/... in
rail-mounting housing
k input and output
electrically isolated
k freely configurable ranges
k customized linearization
for RTD temperature probe
and thermocouple
(excepting 707014/… )
k configuration via Windows
setup program
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Data sheet 707010
Page 2/9
Technical data
Input for Thermocouple for the types 707011/..., 707013/..., 707015//..., 707016/...
Designation
Accuracya (typical)
Range limits
43710
c
Fe-CuNi
„L“
DIN
Fe-CuNi
„J“
DIN EN 60584
Cu-CuNi
„U“
DIN
Cu-CuNi
-200 … +900°C
typ. 0,5 K
-210 … +1200°C
typ. 0,5 K above -150°C
43710c
-200 … +600°C
typ. 0,5 K
„T“
DIN EN 60584c
-270 … +400°C
typ. 0,5 K above -200°C
NiCr-Ni
„K“
DIN EN 60584
-270 … +1372°C
typ. 0,5 K above -140°C
NiCr-CuNi
„E“
DIN EN 60584c
-270 … +1000°C
typ. 0,5 K above -150°C
NiCrSi-NiSi
„N“
DIN EN 60584c
-270 … +1300°C
typ. 1 K above -100°C
Pt10Rh-Pt
„S“
DIN EN 60584c
-50 … +1768°C
„R“
c
-50 … +1768°C
DIN EN 60584c
0 … 1820°C
typ. 2 K above 400°C
MoRe5-MoRe41b
0 ...
2000°C
typ. 2 K above 500°C
W3Re-W25Re „D“c
0 ...
2495°C
typ. 1 K above 500°C
W5Re-W26Re „C“c
0 ...
2320°C
Pt13Rh-Pt
Pt30Rh-Pt6Rh „B“
DIN EN 60584
Shortest span
typ. 2 K above 20°C
typ. 2 K above 50°C
typ. 1 K above 500°C
Type L, J, U, T, K, E, N:
Type S, R, B:
Type MoRe5-MoRe41, D, C:
Cold junction
Pt100 internal or external cold junction (adjustable from 0 ... 80 °C)
Cold junction accuracy
±1 K
Sampling rate
>1 measurement per second
Sensor current
350 nA
Input filter
1st order digital filter; filter constant adjustable:
- on Type 707015/... within the range 0 ... 125sec
- on Types 707011/..., 707013/... and 707016/... within the range 0 ... 100 sec
Features
a
b
c
50 K
500 K
500 K
also programmable in °F; freely programmable range limits;
input isolated from output
The accuracy refers to the maximum range span.
Only for type 707015/....
For type 707013/... on request only.
Input RTD temperature probe for the types 707011/..., 707013/..., 707015/..., 707016/...
Designation
Range limits
Pt100
DIN EN 60751
-200 … +850°C
-100 … +200 °C
-200 … +850 °C
±0,2 K
±0,4 K
Pt100
JIS
-200 … +649°C
-100 … +200 °C
-200 … +649 °C
±0,2 K
±0,4 K
Pt500
DIN
-200 … +250°C
-100 … +200 °C
-200 … +250 °C
±0,2K
±0,4 K
Pt1000
DIN
-200 … +250°C
-100 … +200 °C
-200 … +250 °C
±0,2 K
±0,4 K
Ni100
-60 … +250°C
-60 … +250 °C
±0,2 K
Ni500
-60 … +150°C
-60 … +150 °C
±0,2 K
Ni1000
-60 … +150°C
-60 … +150 °C
±0,2 K
Connection circuit
Shortest span
Sensor lead resistance
- for 3-, 4-wire connection
- for 2-wire connection
2-,3- or 4-wire circuit
10 K
 11 per conductor
measuring resistance +  22  internal lead resistance
Sensor current
 0,6 mA
Sampling rate
> 1 measurement per second
Input filter
Features
a
Accuracya
Range
The accuracy refers to the maximum range span.
2013-01-10/00383981
1st order digital filter; filter constant adjustable:
- on type 707015/...within a range 0 … 125s
- on types 707011/..., 707013/... and 707016/... within a range 0 … 100s
also programmable in °F; freely programmable range limits;
input isolated from output
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Data sheet 707010
Input thermocouple for the type 707014/...
Designation
Accuracya (typical)
Range limits
Fe-CuNi
„J“
DIN EN 60584
-210 … +1200 °C
typ. 0,5K above -150 °C
NiCr-Ni
„K“
DIN EN 60584
-270 … +1372 °C
typ. 0,5K above -140 °C
NiCrSi-NiSi
„N“
DIN EN 60584
-270 … +1300 °C
typ. 1K above -100 °C
Pt10Rh-Pt
„S“
DIN EN 60584
-50 … +1768 °C
typ. 2K above 20 °C
Pt13Rh-Pt
„R“
DIN EN 60584
-50 … +1768 °C
typ. 2K above 50 °C
Shortest span
Type J, K, N:
Type S, R:
Cold junction
50K
500K
Pt100 internal or external cold junction (adjustable from 0 ... 80 °C)
Cold junction accuracy
±1 K
Sampling rate
>1 measurement per second
Sensor current
350nA
Input filter
1st order digital filter; filter constant adjustable:
- on type 707014/... within the range 0 … 125s
Features
a
also programmable in °F; freely programmable range limits;
input isolated from output
The accuracy refers to the maximum range span.
Input RTD temperature probe for the type 707014/...
Designation
Range limits
Pt100
DIN EN 60751
-200 … +850 °C
-100 … +200 °C
-200 … +850 °C
±0,2 K
±0,4 K
Pt100
JIS
-200 … +649 °C
-100 … +200 °C
-200 … +649 °C
±0,2 K
±0,4 K
Pt1000
DIN
-200 … +250 °C
-100 … +200 °C
-200 … +250 °C
±0,2 K
±0,4 K
Connection circuit
2-,3- or 4-wire circuit
Shortest span
Sensor lead resistance
- for 3-, 4-wire connection
- for 2-wire connection
10K
 11  per conductor
measuring resistance +  22  internal lead resistance
Sensor current
 0,6 mA
Sampling rate
> 1 measurement per second
Input filter
Features
a
Accuracya
Range
1st order digital filter; filter constant adjustable:
- on type 707014/... within the range 0 … 125 s
also programmable in °F; freely programmable range limits;
input isolated from output
The accuracy refers to the maximum range span.
Measurement circuit monitoring
Underrange
Overrange
Probe short circuit /
probe and lead break
linear drop to 3.8 mA (as per NAMUR recommendation 43)
linear rise to 20.5 mA (as per NAMUR recommendation 43)
RTD temperature probe:  3.5 mA or  21.0 mA (configurable)
thermocouple:  3.5 mA or  21.0 mA (configurable)a
Current limiting on probe short circuit
or probe break
a
Probe short-circuit recognition is not possible for thermocouple.
2013-01-10/00383981
 23 mA
Page 3/9
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Data sheet 707010
Page 4/9
Output
Types 707014/..., 707015/...
Output signal
Electrical isolation
Test voltage
Types 707011/..., 707013/..., 707016/...
proportional DC current 4 ... 20 mA, 20 ... 4 mA
between input and output
U = 2.0 kV/50 Hz
between input and output
Type 707014/...: Upeak = 1.0 kV/50 Hz
Type 707015/...: Upeak = 3.75 kV/50 Hz
Transfer characteristic
linear with temperature
Type 707015/...: customized linearization
customized linearization
reversion of output signal
Burden (Rb)
Rb = (Ub - 8 V) / 0.022 A
24V DC at approx. 22 °C /  ± 0.05 %a
Calibration conditions / accuracy
1st order digital filter
0 — 125 sec configurable
0 — 100 sec configurable
 2 sec (with filter constant 0 sec)
Step response 0 — 100 %
5 sec
Switch-on delay (correct measurement
after connecting the supply voltage
only after ...)
a
Rb = (Ub - 10V) / 0.022A
 ± 0.02 % / 100 a
Burden error
4 sec
All specified values refer to 20 mA full scale.
Custom linearization
Types 707011/..., 707013/..., 707016/...
- Number of calibration points
- Polynomial
maximum: 40 with linear interpolation
4th order polynomial
Type 707015/...
- Number of calibration points
maximum: 40 with linear interpolation
Type 707014/...
No custom linearization available
Supply
Supply voltage (Ub)
with reverse polarity protection
Type 707014/...: DC 8 ... 35V
Type 707015/...: DC 8 ... 30V
 ± 0,01% per V deviation from 24 Va
Supply voltage error
a
Type 707011/...: DC 11,5 ... 35V
Type 707013/...: DC 11,5 ... 35V
Type 707016/...: DC 11,5 ... 30V
All specified values refer to 20 mA full scale.
Environmental influences
Operating temperature range
-40 to +85 °C
Storage temperature range
-40 to +100 °C
Temperature error
RTD temperature probe:  ± 0.005 % per °C deviation from 22 °Ca
thermocouple± 0.005 % per °C deviation from 22 °Ca plus accuracy of cold junction
Long-term stability
 0.1 °C per yearb or  0.05 % per yearb,c
rel. humidity 95 %, with condensation
Climatic conditions
Vibration strength
according to GL characteristic 2
EN 61326-1
Class B
to industrial requirements
Electromagnetic compatibility (EMC)
- interference emission
- immunity to interference
IP protection
- in terminal head
- open mounting
- on rail
a
b
c
All specified values refer to 20 mA full scale
under calibration conditions
% refer to the selected span. The larger value applies.
2013-01-10/00383981
IP54
IP00
–
Types 707011/... and 707016/...: IP66
Types 707011/... and 707016/...: IP00
Type 707013/...: IP20
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Data sheet 707010
Page 5/9
Housing
Types 707011/..., 707014/...,
707015/..., 707016/...
Material
Screw terminal
Mounting
polycarbonate (encapsulated)
polycarbonate
 1.75 mm²; max. tightening torque 0.6 Nm
 2.5 mm²; max. tightening torque 0.6 Nm
in terminal head Form B DIN 43729;
in surface-mounting case (on request);
in switchgear cabinet
(mounting bracket is required)
on DIN rail 35mm x 7.5mm (EN 60715);
on DIN rail 15mm (EN 60715);
on G rail (EN 60715)
Operating position
Weight
Type 707013/...
unrestricted
approx. 40g
approx. 90g
Version 707015/... (Ex) - Extract from the EC Type-Examination Certificate ZELM 99 ATEX 0018X
Marking
II 1 G Ex ia IIC T6
Temp. range in “II 2 G” and “II 3 G”
T6 = -40 to +55°C / T5 = -40 to +70°C / T4 = -40 to +75°C
Temp. range in “II 1 G”
T6 = -40 to +40°C / T5 = -40 to +50°C / T4 = -40 to +60°C
Supply circuit
Max. values at the terminals
1(+) and 2(-)
Internal inductance
and capacitance
Sensor circuit
Max. values at the terminals
3, 4, 5 and 6
Max. permissible external inductance
and capacitance
Ex ia IIC
Ex ia IIB
Ui = 30V DC
Ii = 100 mA
Pi = 750 mW
Li = negligible
Ci = negligible
Uo = 9.6V DC
Io = 4.5 mA
Po = 11 mW
linear output characteristic
Lo = 4.5 mH / Co = 709 nF
Lo = 8.5 mH / Co = 1300 nF
Version 707016/... (Ex) - Extract from the EC Type-Examination Certificate PTB 01 ATEX 2124
Marking
II 1 G Ex ia IIC T6/T5/T4
II 2 G Ex ia IIC T6/T5/T4
Temp. range in “II 2 G” and “II 3 G”
T6 = -40 to +55 °C / T5 = -40 to +70 °C / T4 = -40 to +85 °C
Temp. range in “II 1 G”
T6 = -20 to +40 °C / T5 = -20 to +50 °C / T4 = -20 to +60 °C
Supply circuit
Max. value at the terminals
1(+) and 2(-)
Internal inductance
and capacitance
Sensor circuit
Max. values at the terminals
3, 4, 5 and 6
Ui = 30 VDC
Ii = 100 mA
Pi = 750 mW
Li = negligible
Ci = negligible
Uo = 5 V DC
Io = 5.4 mA
Po = 6.6 mW
linear characteristic
Internal inductance
and capacitance
Li = negligible
Ci = negligible
Connected circuit without lumped
external inductance
or capacitance
Lo = 1000 mH
Co = 100 µF
Connected circuit with lumped
external inductance
or capacitance
Ex ia IIC
Ex ia IIB, Ex ia IIA
2013-01-10/00383981
Lo = 100 mH / Co = 2 µF
Lo = 100 mH / Co = 9.9 µF
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Approvals/marks of conformity
Mark of
Testing
conformity
laboratory
II 1 G Ex ia IIC T6 ZELM Ex
II 1 G Ex ia IIC
T6/T5/T4
II 2 G Ex ia IIC
T6/T5/T4
PTB
Certificates/
certification numbers
ZELM 99 ATEX 0018 X
PTB 01 ATEX 2124
Data sheet 707010
Test basis
valid for
EN 60079-0:2009
EN 60079-11:2007
EN 60079-26:2007
EN 1127-1:2007
EN 60079-0:2006
EN 60079-11:2007
EN 60079-26:2004
Type 707015/...
Page 6/9
Type 707016/...
Setup program
The setup program is available for configuring the transmitter from a PC. With Types 707014/... and 707015/... , the connection is via the
PC interface with a an USB/TTL converter and the setup interface of the transmitter, in the case of Types 707011/..., 707013/... and
707016/..., via a HART® modem. The connection for the setup circuit must only be used outside the hazardous area. It is not permissible
to configure the transmitter inside the Ex area.
The protective cover must be closed after programming type 707015/... .
Configurable parameters
Sensor type
TAG number (10 characters)
on Types 707011/..., 707013/... and 707016/..., 8 characters only,
but with additional 16-character description
Connection circuit (2-/3-/4-wire)
External and internal cold junction
Customized linearization (not for type 707014/...)
Range limits
Output signal rising/falling (reversion)
Digital filter
Response to probe break/short circuit
Recalibration/fine calibration
(not for Types 707011/..., 707013/... and 707016/...)
Lead resistance with 2-wire circuit
If no power supply (supply isolator) is available, the 2-wire transmitter Type 707014/... or 707015/... has to be configured using a 9V block
battery as a power source.
Fine calibration (not on Types 707011/..., 707013/... and 707016/...)
Fine calibration means correction of the output signal. The signal can be adjusted within ± 5 % of the 20 mA full-scale value. Fine calibration is performed through the setup program. Values for 4 mA (zero), 20 mA (full scale) and offset can be calibrated separately, via the
setup program.
Hardware and software requirements
The following hardware and software requirements must be met when installing and operating the setup program:
IBM-PC or compatible PC from 486DX-2-100
16 MB main memory
15MB free space on hard disk
CD-ROM drive
1 free serial interface or
1 USB interface (e. g. for HART® modem)
Windows 95, 98, ME, NT4.0, 2000 or XP
(full USB support is ensured only in Windows XP)
2013-01-10/00383981
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Data sheet 707010
Setup interface (Types 707014/... and 707015/...)
Protective cover
for the 4-pole
setup plug
Setup plug
Type 707014/...
Type 707015/...
HART® interface (Type 707011/... and 707013/...)
Connection via HART® modem
Supply
10—35V DC
Transmitter
dTRANS T01
+
-
=
Burden1
up to 15 transmitters
(multidrop)
HARTÒ
modem
PC or
notebook
1
USB
Burden ⭐ (Ub - 10V) / 0.022A
Burden with HARTÒ min. 250⍀, max. 1100⍀
HART® interface (Type 707016/...)
Connection via HART®modem for Ex application
Ex area
outside Ex area
Ex 2-wire
transmitter
HART ®
Ex supply isolator,
HART® capable (Type 707530)
1
=
+
4—20 mA
2
-
= =
=
+
®
HART
modem
PC or
notebook
2013-01-10/00383981
USB
Burden
with HART ®
min. 250Ω
Page 7/9
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Data sheet 707010
Page 8/9
Ø44
Ø5
Ø
7
+1
0
21
+0.5
0
Connection diagram
Connection for
Supply voltage
for Type 707011/...
11,5 ... 35V DC
Supply voltage
for Type 707014/...
8 ... 35V DC
Supply voltage
for Type 707015/...
8 ... 30V DC (Ex)a
Supply voltage
for Type 707016/...
11,5 ... 30V DC (Ex)a
Current output
4 — 20 mA
Terminals
+1
-2
U b – 11 ,5 V
R B = ------------------------22mA
U b – 8V
R B = -----------------22mA
Ub – 8 V
R B = -----------------22mA
U b – 11 ,5 V
R B = ------------------------22mA
RB = burden resistance
Ub = supply voltage
Ex version only in conjunction with certified Ex transmitter supply unit
Analog inputs
33
Ø5
Ø44
7
Ø
Thermocouple
+4
-6
RTD temperature probe
in 2-wire circuit
3
6
+1
0
Setup
Type 707011/..., Type 707015/...,
Type 707016/...
RTD temperature probe
in 3-wire circuit
RTD temperature probe
in 4-wire circuit
33
Type 707014/...
3
5
6
3
4
5
6
RL  11 
RL = lead resistance
per conductor
RL  11 
RL = lead resistance
per conductor
RL  11 
RL = lead resistance
per conductor
Ex version: please note connection data of the Ex input circuit!
a
On types 707015/... and 707016/... only up to 30V. The connection must only be made to an intrinsically safe circuit.
Connection for
Supply voltage
for Type 707013/...
11,5 — 35 V DC
Terminals
+81
U b – 11 ,5 V
R B = ------------------------22mA
81 82
+
–
11
12
+
–
11
13
-82
Current output
4 — 20 mA
RB = burden resistance
Ub = supply voltage
Analog inputs
Thermocouple
(special feature: see
order details)
+11
-12
RTD temperature probe
in 2-wire circuit
11
13
RL  11 
RL = lead resistance
per conductor
RTD temperature probe
in 3-wire circuit
11
12
13
RL  11 
RL = lead resistance
per conductor
RTD temperature probe
in 4-wire circuit
11
12
13
14
RL  11 
RL = lead resistance
per conductor
J
Depth behind
panel
98 max.
Caution: the order details on P. 9 must be observed
2013-01-10/00383981
11
12 13
J
11 14
J
12 13
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Data sheet 707010
Page 9/9
Order details: JUMO dTRANS T01 / T01T
Programmable 2-wire transmitter
(1) Basic type
dTRANS T01 B HART®
programmable 2-wire transmitter with HART® interface
707011
dTRANS T01 T HART
programmable 2-wire transmitter with HART interface
installed in rail mounting housinga
(Caution: observe the footnotes)
707013
707014
dTRANS T01 Junior
707015
dTRANS T01 B Ex
programmable 2-wire transmitter with Ex protection
II 1 G Ex ia IIC T6
dTRANS T01 B Ex HART®
programmable 2-wire transmitter with HART® interface
and Ex protection
707016
II 1 G Ex ia IIC T6/T5/T4
II 2 G Ex ia IIC T6/T5/T4
(2)
x x x x x
x x x x x
x x x x x
x x x x x
x x x x x
x x x x x
x x x x x
x
Order code
Order example
a
b
Input (programmable)
factory-set (Pt100 DIN 4w / 0 ... 100 °C)
configuration to customer specificationb
(3) Output (proportional DC current)
888
factory-set (4 — 20 mA)
999
configuration to customer specification (20 ... 4 mA)
(4) Probe break/ short circuit
888
factory-set (positive protection)
999
configuration to customer specification (negative protection)
(5) Extra codes
000
none
243
transmitter in surface-mounting case
(1)
(2)
(3)
(4)
(5)
/
/
707010
/ 888 - 888 - 888 / 243
888
999
When ordering, please specify the type of sensor required (thermocouple or RTD temperature probe). For thermocouple inputs, the sensor
input cannot be changed retrospectively, because of the internal compensating cable. For RTD temperature probe inputs, all types of RTD
temperature probes listed on P. 2 can be connected, but no thermocouples. Thermocouple inputs are available on request.
Probe type and range have to be specified in plain text for configuration to customer specification.
Standard accessories
- 1 Operating Instructions
- Fixing items: 2 screws, 2 compression springs (not for Type 707013/...)
Accessories
- PC setup program, multilingual
- PC interface with USB/TTL converter, adapter (socket) and adapter (pins) for Types 707014/... and 707015/...
- Bracket for mounting on DIN rail, part no. 00352463
- HART® modem USB (for Types 707011/..., 707013/... and 707016/...), part no. 00443447
- Power supply units 1- and 4-way (Data Sheet 707500)
- Ex-i power supply/input isolating amplifier (Data Sheet 707530), part no. 00577948
2013-01-10/00383981