USER MANUAL
BORRI B300R
1000VA-3000VA
Line Interactive
Uninterruptible Power Supply System
BORRI Ltd
Systems House, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 Fax: 01246 431 444
35
IMPORTANT SAFETY
INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the
B300R 1-3kVA series that should be followed during
the installation and maintenance of the UPS and
batteries. Please read all safety and operating
instructions before operating the UPS. Adhere to all
warnings on the unit and those contained within this
manual.
Please also follow all operating and user
instructions provided.
CONTENTS
1. Introduction ················································································ 1
2. Safety Warning ············································································· 3
2.1 Description of Commonly Used Symbols ··········································· 5
3. Installation ·················································································· 6
3.1 Inspection of Unit ······································································ 6
3.2 Unpacking the Cabinet ································································ 6
3.3 UPS Setup ·············································································· 6
3.4 EBM Installation (Optional) ························································· 11
3.5 UPS Initial Startup ··································································· 18
4. Operation ················································································· 19
4.1 Display Panel ········································································· 19
4.2 Operating Mode ······································································ 24
4.3 Configuring Load Segment ························································· 25
4.4 Configuring UPS for EBM Numbers ··············································· 26
4.5 Configuring Green Function ························································ 27
5. Communication Port ···································································· 28
5.1 RS-232 and USB Communication Ports ·········································· 28
5.2 Emergency Power Off (EPO) ······················································· 29
5.3 Network Management Card (Optional) ············································ 30
6. UPS Maintenance ········································································ 31
6.1 UPS and Battery Care······························································· 31
6.2 Storing the UPS and Batteries ····················································· 31
6.3 Time to Replace the Batteries ······················································ 32
6.4 Replacing the UPS Internal Batteries ············································· 33
6.5 Testing New Batteries ······························································· 36
6.6 Recycling the Used Battery: ························································ 36
7. Specification ············································································· 35
7.1 Specification ·········································································· 35
7.2 Rear Panels ·········································································· 38
8. Trouble Shooting ········································································ 41
8.1 Audible Alarm Trouble Shooting ···················································· 41
8.2 General Trouble Shooting··························································· 41
9. Software Installation ···································································· 42
1. Introduction
The B300R is a compact, Line Interactive, pure sinewave UPS. The B300R is
designed to support critical equipment, such as desktop PCs, servers,
workstations, and other networking equipment. The B300R is available with an
output rating of 1 – 3kVA.The B300R protects connected equipment from power
problems including power sags, spikes, brownouts, line noise and blackouts.
TheB300R can either be Rack mounted or configured as a free standing Tower.
The front panel of the UPS includes a LCD display with four control buttons that
allow the user to monitor, configure and control the unit On the LCD, a graphical
bar, two status indications and four alarm indications are included.
See the Image
below:
A control button from the front panel allows the user to turn off the AC fail alarm
and initiate the UPS self-test sequence. The UPS case is made of metal. This UPS
is powered from the AC mains and supplies an AC output via the C13ports on the
rear of the UPS. Communication and control of the UPS is available through serial
or USB ports located on the rear panel. The serial port will support
communications directly to a server.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
1
Features:
 Cold start capabilities.
 Selectable input and output ranges.
 Easy battery replacement design.
 Ability to extend runtime with scalable external battery module (EBM).
 Built-in boost and buck Automatic Voltage Regulator (AVR).
 Built-in Dry contact/RS-232/USB communication ports.
 Microprocessor control guarantees high reliability.
 High frequency design.
 SNMP allows for web-based, remote or monitoring management. (Optional)
 Overload, short-circuit, and overheat protection.
 Rack/Tower 2 in 1 Design.
 19 inch rack mount available for all models.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
2
2.Safety Warning
DANGER:
This UPS contains high voltages. All repairs and servicing should be performed by
authorized service personnel only. There are no user serviceable parts inside the
UPS.
WARNING:
 This UPS contains its own energy source (batteries).The UPS output may carry
live voltage even when the UPS is not connected to an AC supply.
 To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive
contaminants.(Ambient :0-40°C)
 To reduce the risk of fire, please connect to a circuit breaker rated at 20
amperes.
 To comply with international standards and wiring regulations, the total of the
leakage current of the UPS and the connected loads must not exceed 3.5mA.
 The electrical supply that feeds the UPS shall be installed near the UPS and
shall be easily accessible.
 Disconnection of an earth line should be made at the point that is furthest away
from the UPS, in order to maintain the dedicated earth line.
 The UPS and Extra Battery Modules (EBMs)should be connected closely
together to ensure that the interconnecting wires cannot be touched.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
3
CAUTION:
 Batteries can present a risk of electrical shock or burns from high short-circuit
current. Observe proper precautions. Servicing should only be performed by
qualified service personnel who have knowledge of batteries and the required
precautions. Keep untrained personnel away from the batteries.
 The safe disposal of batteries is required. Refer to your local environmental
regulations e.g. WEEE Regs. for disposal requirements.
 Never dispose of batteries in a fire. Batteries may explode when exposed to
flames.
The following block diagram shows the basic internal circuit configuration of the UPS:
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
4
2.1 Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual and therefore,
all users should familiarise themselves with their definitions.
Table1. Description of Commonly Used Symbols
Symbol
Description
Warning: Attention Required
Caution: high voltage
Alternating current source (AC)
Direct current source(DC)
Protective ground
Recycle
Keep UPS in a clear area
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
5
3. Installation
3.1 Inspection of Unit
Inspect the UPS upon receiving it. If the UPS appears to have been damaged
or if the internal packaging has been damaged during shipment, please keep
the box and packaging materials in their original form for the carrier and contact
the supplier immediately.
3.2 Unpacking the UPS
To unpack the system:
1. Open the outer box and remove the accessories packaged with the UPS.
2. Carefully lift the UPS out of the outer box and set it on a flat, stable surface.
3. Discard or recycle the packaging in a responsible manner, or store it for
future use.
3.3 UPS Setup
Both models of the B300R are designed for tower or rack purpose. Please
follow the instructions on the next few pages that relate to the configuration
that’s best for your system.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
6
 Tower setup
The B300R can be placed either horizontally or vertically. An optional stand is
included with this UPS in order to allow for tower configuration.
The stand can
be used in order to position the UPS in an upright position. In order to achieve
this, the UPS stand should be attached to the bottom of the tower.Please use
the following instructions in order to install the UPS within the UPS stand:
1. Carefully place the UPS within the stands.
2. Slide the UPS stands to each end of the tower.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
7
2. Pull out the LCD panel and rotate it in a clockwise direction to 90 degrees
and then push it back into the front panel.(The LCD is on a short wire please
take care when executing this step)
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
8
 Rack-mount setup
The UPS can also be installed within a 19 inch rack. The UPS takes up 2U rack
space for each additional EBM installed an additional 2U rack space is required.
Use the following procedure to install the UPS within a rack.
1. Align the mounting ears with the screw holes on the side of the UPS, and
tighten the screws.
2. Assemble the rack rails with the rack-mounting.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
9
3. Slide the UPS into the rack rails and lock it into the
rack enclosure.
4. Tighten the screws. The UPS is now ready for cabling, unless you are
installing EBMs.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
10
3.4 EBM Installation (Optional)
 Connecting the EBM in Tower form:
1. Position the UPS and EBM within the extended UPS stands then slide the
stands to either end of the tower.
2. Tighten the screw on the UPS cover for stabilisation.
3. Connect an Earth line from the UPS (port A) to the EBM (port B)
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
11
4. Take off the front panel.
To do this remove the 2 top screws from the front
of the UPS and carefully take out the LCD screen and remove the screw
that’s behind it.
Finally push inward the small gate on the side of the front
panel in order to remove it.
This then enables you to connect battery
terminal (A) from the UPS to the EBM terminal (B) shown below.
After
doing this reassemble the front panel.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
12
 Connecting the EBM in a rack form
1. Using the same method as assembling the UPS in rack form, assemblethe
EBM into the rack-mounting above or below the UPS.
2. Connect an earth line from the UPS (port A) to the EBM (port B)
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
13
3. Take off the LCD box, and unscrew the internal screws.
Unscrew
4.
Take off the front panel.
To do this remove the 2 top screws from the
front of the UPS and carefully take out the LCD screen and remove the
screw.
Finally push inward the small gate on the side of the front panel
in order to remove it.
This then enables you to connect the battery
terminal (A) from the UPS to the EBM terminal (B) shown below.
After
doing this reassemble the front panel.
5. After installing the UPS into the rack, the load can then be connected to the
UPS. Please make sure the load equipment is turned off before connecting all
loads into the output C13 ports.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
14
 Connecting Multiple EBMs
The B300R UPS includes an external battery port that allows users to connect
multiple EBM’s in order to provide additional backup time. In order to do this
please follow the instructions provided on the next few pages of this manual.
Connecting multiple EBMs in Tower form
1. Connect an Earth line between the UPS and the first EBM, and then connect
a second Earth Line between the first EBM and the second EBM.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
15
2. Take off the front panel.
To do this remove the 2 top
screws from the front of the UPS and carefully take out the LCD screen and
remove the screw.
Finally push inward the small gate on the side of the front
panel in order to remove it. This then enables you to connect the battery
terminal (A) from the UPS to the EBM terminal (B) shown below.
Then
connect the battery terminal (D) from the first EBM to the battery terminal (E) of
the second EBM. Then users need to reassemble the front panel.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
16
Connecting Multiple EBMs in rack form
1. Connect an Earth line between the UPS and the first EBM, and then connect
an Earth Line between the first EBM and the second EBM.
2. Take off the front panel. To do this remove the 2 top screws from the front
of the UPS and carefully take out the LCD screen and remove the screw.
Finally push inward the small gate (C) on the side of the front panel in order to
remove it.
This then enables you to connect the battery terminal (A) from the
UPS to the EBM terminal (B) shown below.
Then connect the battery terminal
(D) from the first EBM to the battery terminal (E) of the second EBM. After doing
this reassemble the front panel.
Note: Three or more EBMs can be connected to the UPS in the same way as shown
above.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
17
3.5 UPS Initial Start up
To start up the UPS:
1. Verify that the internal batteries are connected. If optional EBMs are installed,
verify that the EBMs are connected to the UPS.
2. Connect the UPS to the equipment you need to protect.
3. Connect the UPS to the mains. The UPS LCD will illuminate and the UPS
status display will show “STbY”.
4. Press and hold the power button
for longer than 3 seconds to turn on
the UPS. Once this is done the UPS status display will change to “NORM”.
6. Check the UPS display for active alarms or notices. Resolve any active
alarms before continuing. See “Troubleshooting” on page 35 for an overview
of possible problems and how to resolve them.
8. If optional EBMs are installed, see “Configuring UPS for EBM numbers” on
page 22 to set the number of installed EBMs.
9. To change any other factory-set defaults, see “Operation” (from the next page)
for step-by-step instructions on how to change these settings.
Note: At initial start up, the UPS sets the system frequency according to the
input line frequency from the mains supply.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
18
4. Operation
4.1 Display Panel
The UPS has a four-button graphical LCD with dual colour backlight. The
standard back-light is used to light up the display with black text and a blue
background. When the UPS has a critical alarm, the backlight changes the
background to red. See the diagram below for an illustration of the LCD panel:
 Control Buttons functions:
There are four buttons on the LCD control panel.
ON/OFF
UPS Test /Alarm Silence
Select
Enter
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
19
The following table describes the functions of the LCD control buttons.
Table2. Description of control button
Control
Button
Switch
ON/OFF
UPS Test
Alarm Silence
Select
Enter
Function
--To turn the UPS on/off.
Press and hold the Power button for longer than 3
seconds.
--To remove the UPS from fault mode.
Disconnect the mains input to the UPS and then
press and hold the Power button
for longer than
2 seconds to shut down the UPS.
--To perform basic function test.
Press and hold the
button for 3 seconds.
--To perform Battery life test.
Press and hold the button for 10 seconds.
-- To disable alarm buzzer.
Press the
button for one second.
Press the Select button
to scroll through the
settings one by one.
-- Enter settings mode
Press and hold the button more than 3 seconds.
-- Enter settings item
Press and hold the Enter button more than one
second, the UPS allows users to configure the
settings, and the settings string will flash.
--Confirm settings
Press and hold the Enter button
for one second.
-- Exit Settings mode
Press and hold the Enter button
for 3 seconds or
button
for 0.5 second.
Note: Ensure the battery is fully charged during line mode before conducting any
functionality tests.
Note: The list of events shown below are not able to disable the alarm buzzer:
Low Battery, Fan Failed, Fan Fault Time Out, and Overheat.
Note: The user can disable the alarm buzzer when it’s sounding, but an alarm
will still sound when a new alarm event is encountered.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
20
 LCD display functions:
The following table describes the functions of the LCD display.
Table3. Description of LCD display function
No.
Description
Function
Input frequencyand
voltage
Indicates the value of input frequency and
voltage.
This Light switches on when the UPS is
charging from the mains.
Input plug indicator
Output
frequencyandvoltag
e
Output plug
indicator
UPS status/user
setting display
Warning indication
light
Settings light
Indicates the value of output frequencyand
voltage.
The UPS has two groups of outlets. The
output plug indicator will light up if there is an
output connected.
Indicates the UPS’ current mode of
operation (see Table 4).Or Indicates the
settings currently being altered by the user
(see Table 5).
This light will turn on when the UPS alarm is
active or if there’s an error that is causing the
UPS to malfunction.
This light will turn on when the UPS is within
settings mode.
Battery capacity
level indicator
This light Indicates the amount of battery
capacity remaining. Each battery capacity
level bar indicates 20% of the total battery
capacity.
Load capacity level
indicator
Indicates the percentage of the UPS load
capacity which is being used by the
protected equipment. Each LCD level bar
indicates 20% of the total UPS output
capacity.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
21
 UPS Status Display String Description:
The following table shows the description of the LCD display string messages:
Table4. UPS Status Display String
LCD Display String
Description
STbY
IPVL
IPVH
IPFL
IPFH
NORM
AVR
bATT
TEST
OPVH
OPVL
OPST
OVLD
bATH
bATL
OVTP
FNLK
bTWK
The UPS is currently in standby mode.
The Input voltage is too low. (below minimum
operating conditions)
The Input voltage is too high. (above maximum
operating conditions)
The Input frequency is too low. (below minimum
operating conditions)
The Input frequency is too high. (above maximum
operating conditions)
The UPS is operating under normal conditions.
Equipment is being powered from mains supply,
not from the UPS batteries.
The UPS is operating in AVR mode.
The UPS is providing power to equipment from
the UPS batteries. This will occur if there’s a
problem with the mains supply. UPS will follow
shutdown procedures established using the
Winpower Software.
The UPS is currently set to perform tests on the
batteries.
Displayed during battery operation if the input is
too high. (above maximum operating conditions)
Displayed during battery operation if the input is
too low. (below minimum operating conditions)
Output short.
The UPS output is overloaded
The Battery voltage is too high
The Battery voltage is too low
The Internal temperature of UPS is too high.
The UPS Fan is locked/not operating.
The Batteries are weak and are in need of
charging or replacing.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
22
 User Setting String Description:
The following table shows the options that can be changed by the user:
Table5. User Setting String
OPV
Output voltage mode
selection
AVR
Input type selection
EbM
TEST
AR
GF
bZ
LS1
LS2
External battery module
(EBM) settings
Auto self-test function
Automatic restart
Green function
Buzzer control
Load segment 1
Load segment 2
[220]= 220V
[230]= 230V
[240]= 240V
[000]= Normal range mode
[001]= Wide range mode
[002]= Generator mode
0~9 is the number of external battery
module(s)
[000]=Disable[001]=Enable
[000]=Disable[001]=Enable
[000]=Disable[001]=Enable
[000]=Disable[001]=Enable
[000]=Turn off[001]=Turn on
[000]=Turn off[001]=Turn on
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
23
4.2 Operating Mode
 Normal range mode: The UPS accepts an AC input voltage within the range of
+/-20%.
 Generator mode: The low frequency transfer point of the UPS can go as low as
40Hz and as high as 70Hz before being transferred to battery mode.
 Wide range mode: The UPS accepts an AC input voltages within the range of
-30% ~ +20%.
 Battery mode:
When the UPS is operating during a power outage, the alarm beeps once every
four seconds and the LCD display string shows “bATT” to indicate the UPS is
working from the batteries.
If the batteries volume becomes low whilst in Battery mode, the alarm beeps once
every second and the LCD display string shows “bATL”.
 Standby mode:
When the UPS is turned off but remains plugged into the mains supply, the UPS is
in Standby mode. The LCD display string shows “STbY” to indicate that power is
not available to your equipment. The battery recharges when necessary.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
24
4.3 Configuring Load Segment
The Load Segment is a set of C13 ports that can be controlled through the LCD
display. Each UPS has two configurable load segments. See “Rear Panels” on
pages 38- 40 for images which show all connections on the back of the UPS
including the load segment (AC Outputs).
Note: This setting can be altered whilst the UPS is switched on.
To configure the load segment through the display:
1. Enter settings mode: Press and hold the Enter button
for longer than 3
seconds. This will cause the UPS to go into settings mode.
2. Select settings item:Press the Select button
to cycle through the setting
items shown in Table 5.
3. Enter settings item:When the LCD displays“LS1” or “LS2”, press the enter
button
for longer than one second to enter LS1 or LS2 settingsthis will
cause the settings string to flash.
4. Select setting value:Press the Select button
to select the settings value.
Select the value [001] to turn on that load segment or select [000] to turn off that
load segment.
5. Confirm settings:Press and hold the Enter button
for one second, and the
UPS will then return to settings mode.
6. Exit Settings mode:Press and hold the Enter button
power button
for 3 seconds or the
for 0.5 second to exit settings mode
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
25
4.4 Configuring UPS for EBM Numbers
To ensure the LCD displays the correct battery capacity, configure the UPS for the
correct number of EBMs:
1. Enter settings mode: Press and hold the Enter button
seconds.
for longer than 3
This will cause the UPS to go into settings mode.
2. Select settings items: Press the Select button
to cycle through the settings
until you reach the settings item “EbM”.
3. Enter settings item: Press the Enter button
for longer than one second to
enter the setting item.
4. Select setting value: Press the Select button
to select the number of EBMs
according to your UPS configuration. (up to a maximum of 9)
5. Confirm settings:Press and hold the Enter button
for one second, and the
UPS will then return to settings mode.
6. Exit Settings mode:Press and hold the Enter button
Power button
for 3 seconds or the
for 0.5 second to exit settings mode.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
26
4.5 Configuring Green Function
The Green Function enables the UPS to detect the level of load being supported if
an insignificant level of load is detected the UPS will shut down automatically, but
only if it’s currently operating from the batteries.
The green function is disabled by default but the user can configure the Green
Function through the display:
1. Enter settings mode: Press the Enter button
for longer than 3 seconds to
enter settings mode.
2. Select settings items: Press the Select button
to cycle through the settings
to select the setting item “GF”.
3. Enter settings item: Press the Enter button
for longer than one second to
enter the settings item.
4. Select setting value: Press the Select button
to select “001” to activate the
Green Function.
5. Confirm settings: Press and hold the Enter button
for one second, and
the UPS will then return to settings mode.
6. Exit Settings mode: Press and hold the Enter button
button
for 3 seconds or
for 0.5 second to exit settings mode.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
27
5. Communication Port
5.1 RS-232 and USB Communication Ports
To establish communication between the UPS and a computer, connect your
computer to one of the UPS communication ports using an appropriate
communication cable (USB or RS232 lead).
When the communication cable is installed, power management software (Winpower,
see page 47) can exchange data between the computer and the UPS. The software
polls the UPS for detailed information on the status of the power environment. The
software can be configured so that in the event of a power cut it initiates the saving of
all data and the safe shutdown of the protected equipment.
The pin configuration for the RS-232 communication port is identified below, and the
pin functions are described in Table 6.
Table6. DB9 Female (RS232 +dry contact)
PIN #
1
2
3
4
5
6
7
8
Description
BATLOW
RXD
TXD
DTR
Common
DTR
RING
LNFAIL1
I/O
Output
input
Output
Input
-Input
Output
Output
Function Explanation
Battery low
RXD
TXD
N/A
Common (tied to chassis)
N/A
Ring
Line fail
RS232 Communication Port
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
28
5.2 Emergency Power Off(EPO)
The EPO function of the UPS is used to shut down the equipment remotely. This
feature can be used for shutting down the load during an Emergency.
Warning:
This circuit must be separated from hazardous voltage circuits by reinforced
insulation.
Caution:
The EPO must not be connected to any mains supply source. Cabling for the
EPO circuit should be isolated from sources of interference i.e. mains supply.
The EPO Switch must have a minimum rating of 24Vdc and 20mA and be a
dedicated latching-type switch not tied into any other circuit. The EPO signal
must remain active for at least 20ms for proper operation.
Wire Function
EPO
EPO Connections
Terminal Wire Size Rating
2
4-0.32mm (12-22AWG)
Suggested Wire Size
2
0.82mm (18AWG)
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
29
Note: Leave the EPO connector installed in the EPO
port on the UPS even if the EPO function is not need.
EPO Connector
5.3 Network Management Card (Optional)
The Network Management Card allows the UPS to communicate in a variety of
networking environments and with different types of devices. The B300RUPS has one
available communication slot for Webpower or other optional cards to achieve remote
management of the UPS through internet/ intranet. Please contact your supplier or
BORRI LTD if you require an SNMP card.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
30
6. UPS Maintenance
6.1 UPS and Battery Care
For the best preventative maintenance, keep the area around the UPS clean and
dust-free. If the atmosphere is very dusty, clean the outside of the system with a
vacuum cleaner. For long battery life, keep the UPS at an ambient temperature of
20-25°C (77°F)
6.2 Storing the UPS and Batteries
When the UPS is being stored for a long period of time, recharge the battery every 6
months by connecting the UPS to the mains supply. The batteries charge to 90%
capacity in approximately 4 hours. However, it is recommended that the batteries
charge for 48 hours after long-term storage.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
31
6.3 Time to Replace the Batteries
When the LCD backlight turns to red, the screen displays “bTWK” and there is a
continuous sounding, the battery may need to be replaced. Please check the battery
connection or contact your supplier or BORRI LTD. to order new battery.
WARNING:
 Turn off the UPS and disconnect it from the mains supply.
 Servicing should only be performed by qualified service personnel with knowledge
of batteries, UPS systems and understand the required precautions. Keep
unauthorized personnel away from batteries.
 Batteries can present a risk of electrical shock or burn from high short circuit
currents. The following precautions should be observed when working on batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Do not lay tools or metal parts on top of batteries.
4. Wear rubber gloves and boots.
5. Disconnect the charging source prior to connecting or disconnecting the
battery terminal.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
32
 When replacing batteries,replace with the same type and number of batteries or
battery packs. Contact your Supplier or BORRI LTD. to order new batteries.
 Do not dispose of batteries in a fire. Batteries may explode when exposed to
flames.
 The safe disposal of batteries is required. Refer to your local environmental
policies e.g. WEEE Regs. for disposal requirements.
 Do not open or damage the battery. Released toxic electrolyte is harmful to skin
and eyes.
Note: If you are not qualified to replace the batteries, do not attempt to open the
battery cabinet. Please call your supplier or BORRI LTD.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
33
6.4 Replacing the UPS Internal Batteries
Follow the steps and Charts shown below in order to replace the batteries:
1. Take off the LCD panel, and remove the screws.
2. Slide and Pull the front panel as indicated below and then take it off.
3. Disconnect the cable from the UPS and battery pack.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
34
4. Remove the right inner battery bracket.
5. Pull the battery pack out onto a flat surface.
6. Install the new battery pack into the UPS.
7. Screw the battery bracket back into the UPS and reconnect the battery cable A and
B.
8. Re-install the front panel on the UPS.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
35
6.5 Testing New Batteries
For a battery test, please check:
 The batteries must be fully charged.
 The UPS must be in Normal mode with no active alarms.
 Don’t connect/disconnect equipment to/from the UPS
To test batteries:
1. Connect the UPS to mains power for at least 48 hours to charge the batteries.
2. Press and hold the
button for10 secondsto start the battery test.The status
display string will show “TEST”
6.6Recycling the Used Battery:
Warning:
 Never dispose of batteries in a fire. It may explode.
 Do not open or damage the batteries. Released electrolyte is harmful to the
skins and eyes. It may be toxic. A battery can present a risk of electrical shock and
high short circuit current.
To properly recycle the used battery, please do not discard the UPS, battery
pack and batteries into the trash bin. Please follow your local environmental
regulations e.g. WEEE Regs; you may contact your local recycling waste
management centre for further information to properly dispose of the used UPS,
battery pack, and batteries.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
36
7. Specification
7.1 Specification
Table7. Electrical Specification
Model
Capacity
Input
Output
Watt
Input voltage range
Frequency range
Voltage
Voltage Regulation
(Batt. Mode)
Frequency
Waveform
B300R-010-E
1000VA/900W
0-300VAC
50/60Hz ±5Hz for
Normal Mode
40-80Hz for Generator
Mode
220/230/240VAC
B300R-010-B
B300R-015-B
1000VA 900W
1500VA 1350W
161-276VAC
±5%
±5%
50Hz or 60Hz
Pure sinewave
50Hz or 60Hz
Pure Sinewave
110% ±10%,
Line Mode
150% ±10%,
110 % ±10%,Fault
Battery Mode
after 30 Seconds
120 % ±10 %,
Fault after 100ms
Battery Type
Internal
battery
Backup Time
(at full load) (mins)
Recharge Time
External
battery
module
(EBM)
Interface
220/230/240VAC
110% -0%, +8%: shutdown after 3
Fault after 3 Minutes. minutes.
Fault after 200ms
Overload
rating
50/60Hz ±5Hz for Normal Mode
40-70Hz for Generator Mode
150% -0%, +10%: shutdown after about
200ms
110% ± 6%; shutdown after 30 seconds.
120 % ± 6 %; Shutdown after about
100ms
2*12V/9AH
3*12V/7AH
3
4.5
3*12V/9AH
3
8 hours to 90% after 3 hours to 90% after
discharged
discharged
4 hours to 90%
after discharged
Battery Type
N/A
12V/7AH
RS-232
YES
YES
Dry-Contact
YES
YES
USB
YES
YES
SNMP
N/A
Optional
EPO
N/A
Optional
BORRI Ltd
Systems House, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 Fax: 01246 431 444
35
Model
Capacity
Watt
B300R-020-B
B300R-030-B
2000VA
1800W
3000VA
2700W
Input voltage range
161-276VAC
Input
50/60Hz ±5Hz for Normal Mode
40-70Hz for Generator Mode
Frequency range
Voltage
Output
220/230/240VAC
Voltage Regulation
(Batt. Mode)
±5%
Frequency
50Hz or 60Hz
Waveform
Pure Sinewave
110% -0%, +8%: shutdown after 3 minutes.
Line Mode
150% -0%, +10%: shutdown after about 200ms
Overloadrating
110% ± 6%; shutdown after 30 seconds.
Battery Mode
120 % ± 6 %; Shutdown after about 100ms
Battery Type
Internal battery
Recharge Time
External battery
module(EBM)
Interface
6*12V/7AH
Backup Time
(at full load) (mins)
6*12V/9AH
4.5
3
3 hours to 90% after
discharged
4 hours to 90% after
discharged
Battery Type
12V/7AH
RS-232
YES
Dry-Contact
YES
USB
YES
SNMP
Optional
EPO
Optional
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
36
Table8.Indicators and Audiblealarm
AC Mode
NORM---normal mode
Show “bATT” and sounding every 4 seconds
Backup Mode
Load/Battery Level
LCD showing
Indicator
UPS Fault
LCD will show ared screen and “ **** ”
Overload
LCD will show a red screen and “ OVLD ”
Low Battery
LCD will show a red screen and “ bTLW ”
Backup Mode
Audible alarm
Sounding every 4seconds
Low Battery
Sounding every second
UPS Fault
Continuously Sounding
Overload
Sounding every second
Battery Replacement
Sounding every second
Table9. Operating Environment
Temperature
20 to25°C
Humidity
20%-80% relative humidity (non-condensing)
Altitude
<1500m
Storage Temperature
-15to 45 C
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
37
Table10. Dimensions and weights
B300R-010- B300R-010- B300R-015B300R-020-B B300R-030-B
E
B
B
Model
UPS
Case
EBM
Case
Net weight (kg)
Dimension
(mm) (WxHxD)
Dimension
(mm) (WxHxD)
Net weight (kg)
13.0
17.8
17.8
438X86.5x436
27.8
27.8
438X86.5x608
N/A
438X86.5x436
438X86.5x608
N/A
20.5
33.3
7.2 Rear Panels
The UPS rear panel description table and pictures are shown below:
No.
1
2
3
4
5
6
Function( B300R-010-E)
AC Output
Modem/Network Surge Protection
AC Input
RS232 / Dry-Contact Communication Port
USB Port
Earth Line Port
B300R-010-E Standard model rear panel
No.
1
2
3
4
5
6
7
8
Function( B300R-010-B/ B300R-015-B)
AC Output
Modem/Network Surge Protection
SNMP Port
AC Input
RS232 / Dry-Contact Communication Port
USB Port
EPO
Earth Line Connection
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
38
2
3
4
IN
OUT
INTERFACE OPTION
INPUT 220-240V~
LS2 OUT PUT
25KV~ 10A
LS1 OUT PUT
25KV~ 10A
NETWORK/TELEPHONE PROTECTION
1
RS232
USB
EPO
1
5
6
7
8
B300R-010-B/ B300R-015-B Standard model rear panel
No.
1
2
3
4
5
6
7
8
9
Function( B300R-020-B/ B300R-030-B)Standard model)
AC Output
Modem/Network Surge Protection
SNMP Port
Fan
AC Input
RS232 / Dry-Contact Communication Port
USB Port
EPO
Earth Line connection
1
5
4
3
2
1
OUT
NETWORK/ TELEPHONE PROTECTI ON
IN
RS232
6
USB
7
EPO
8
I NPUT 220- 240V~
LS2 OUT PUT
25KV~ 10A
LS1 OUT PUT
25KV~ 10A
I NTERFACE OPTI ON
9
B300R-020-B Standard model rear panel
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
39
B300R-030-B model rear panel
The EBM rear panel description table and picture are shown below:
No.
1
Function( B3RBB36V6-12-7/ B3RBB72V12-12-9)
( B3RBB36V/ B3RBB72V)
Earth Line connection
1
1
B3RBB36V6-12-7/B3RBB72V12-12-9
B3RBB36V/B3RBB72V
Rear panel
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
40
8. Trouble Shooting
8.1 Audible Alarm Trouble Shooting
Indication
Sounding every 4
seconds
Sounding every
Second and “bATL”
on screen
Sounding every
second and “OVLD”
on screen
Continuously
sounding and red
display
Cause
Solution
The UPS is on battery
mode.
Check the input voltage.
The battery voltage is
low.
Save your work and turn off your
equipment.
Output overload.
Check load level indicator and
remove some load.
The UPS fails.
Please contact your supplier.
8.2 General Trouble Shooting
Problem
Cause
The UPS can't be
turned on when power
switch is pressed
Solution
Internal fuse may be
broken.
UPS is on and there is
no power to the load
Output Jumpers are
not connected
correctly.
No power on output
receptacle.
Please contact your supplier.
Check output Jumpers.
Battery aging.
Check if the LS1 and LS2 are set
up from "001 to 000".
Re-charge the battery for at least
24 hours.
Replace the Battery.
Continuously
sounding and
displaybackground is
red
The UPS fails.
Please contact your supplier.
Buttons not working
correctly
The setting mode is
not configured
correctly.
Button is Broken.
Backup time is short
Battery is empty.
Please see right configuring
method.
Please contact your supplier.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
41
9. Software Installation
Winpower is UPS monitoring software which provides a user-friendly interface
to monitor and control your UPS.
This unique software provides safe auto
shutdown for multiple computer systems during a power failure. With this
software the user can monitor and control any UPS on the same LAN
regardless of distance from the UPSs.
Installation procedure:
1. Go to the website: http://www.borri.co.uk/softwaredownload
2. Choose the operating system you use and follow the instructions described
on the website to download the software.
3. When downloading the required files from the internet, enter the serial No.:
S11C1-01220-0100-478DF2A to initiate installation of the software. When the
computer restarts, the Winpower software will appear as a green plug icon
located in the system tray, near the clock.
BORRI Ltd
Systems House, EckingtonBusinessPark, Rotherside Road, Eckington, Sheffield, S21 4HL
Tel: 01246 431 431 Fax: 01246 431 444
42