spec
LP
9O4-543-1223, 8OO-997-2443, Fax: 9O4-543-133O, www.paigeelectric.com
P7359-SP
2.0
FEATURES:
• Excellent flexibility.
2.1
• Highly ozone, sun, weather,
water and flame resistant.
• Rated and flexible at –40ºC.
• Excellent impact and abrasion resistant.
• Oil and heat resistant.
• Indent printed for easy identification.
CONSTRUCTION:
Conductors:
3.1
Annealed flexible stranded tin coated
copper in accordance with ASTM B-172
4.0
and ICEA S-75-381.
Pa
ig
3.0
APPLICATIONS:
These Cable are used for Heavy Duty
1.1
Submersible Motors where shielding is
required and Per NEC code for motors
over 2400Volts. The cables are (Cul)
Listed Submersible Pump Cable and
MSHA Approved. Designed for use as
heavy duty deep well fresh or salt water
(suitable for continuous submersion to
984') submersible pump.
eE
1.0
lec
tric
SUBMERSIBLE PUMP CABLE
HYDROFLEX EPR/NEOPRENE
SHIELDED 8000V 90°C
WET/DRY C(UL) MSHA
STANDARDS: ICEA S-75-381/NEMA WC-58
ICEA S-68-516/NEMA WC-8
ASTM B172, ASTM B 33
3.2
Conductor shielding:
Semi-conducting layer over the conductor.
3.3
Insulation:
Ethylene-propylene rubber (EPR).
3.4
Insulation shield:
Non conducting bedding tape +composite
tinned copper/fiber braid.
Covering minimum 60%.
3.5
Circuit identification:
The nylon in the shielding braid is col-
®
ored black, white, red in accordance
with ICEA S-75-381.
3.6
Grounding conductors:
Annealed tin coated copper as per
Tab. 3-24 of ICEA S-75-381.
3.7
Ground check:
Annealed tin coated copper as per
Tab. 3-21 of ICEA S-75-381. Color of
insulation: yellow
3.8
Assembly:
Three power, ground check and two
non-insulated grounding conductors
cabled together. Single faced rubber
filled binder tape applied overall.
Integral filled jacket for higher torsion
resistance.
3.9
Jacket:
A reinforced NEOPRENE, CPE, TPU
optional jacket available.
Type extra heavy duty in accordance
with Par. 3.21 of ICEA S-75-381.
3.10
Color of jacket:
Black, other colors available upon
request
APPROVALS
MSHA:
4.1
3.1.1 P-7K-254029-1 (Neoprene)
3.1.2 P-7K-268101 (CPE)
3.1.3 P-07-KA030001 (TPU)
4.2
We’re Big in Big pump cable.
Standard length cable packing:
1000 ft reels. Other forms of packaging available upon request.
page 1
09/04/14
5.0
POWER
CONDUCTOR
SIZE
POWER
CONDUCTOR
STRANDING
GROUND
CHECK
COND.
SIZE
GROUNDING
CONDUCTOR
AWG or MCM
NO. OF WIRES
AWG
AWG
NOMINAL
INSULATION
THICKNESS
NOMINAL
JACKET
THICKNESS
APPROX.
O.D.
APPROX.
WEIGHT
NO. OF WIRES
INCHES
INCHES
INCHES
MM
Ibs/1000 ft
ft kgs/km
4 AWG
259
7x37
8
8
133
7x19
0.150
0.205
1.94
49.3
2132
3173
2 AWG
259
7x37
8
6
133
7x19
0.150
0.220
2.12
53.8
2780
4137
1 AWG
259
7x37
8
5
133
7x19
0.150
0.220
2.21
56.0
3300
4911
1/0 AWG
266
19x14
8
4
259
7x37
0.150
0.220
2.32
58.9
3530
5112
2/0 AWG
342
19x18
8
3
259
7x37
0.150
0.235
2.46
62.5
4160
6191
3/0 AWG
418
19x22
8
2
259
7x37
0.150
0.250
2.62
66.6
5000
7440
259
4/0 AWG
532
19x28
8
1
7x37
0.150
0.250
2.75
69.9
5590
8319
250 MCM
627
19x33
8
1/0
266 19x14
0.150
0.250
2.89
73.4
6680
9941
350 MCM
888
37x24
8
2/0
342 19x18
0.150
0.280
3.20
81.3
8410
12515
500 MCM
1221 37x33
8
4/0
532 19x28
0.150
0.295
3.39
86.1
9909
14746
5.1
POWER
GROUNDING
CONDUCTOR SIZE
POWER
CONDUCTOR
RESISTANCE
AT 20°C
GROUNDING
CONDUCTOR
RESISTANCE
AT 20°C
GROUND
CHECK
RESISTANCE
AT 20°C
INDUCTANCE
PER UNIT
LENGTH
OPERATING
CAPACITANCE
PR UNIT
LENGTH
PERMISSIBLE
SHORT-CIRCUIT
CURRENT2 (1S)
AMPACITY1
40°C
AMBIENT
TEMP.
MAXIMUM
PERMISSIBLE
TENSILE
FORCE
AWG or MCM
Ω /1000Ft
Ω /1000Ft
Ω /1000Ft
mH/1000Ft
μF/1000Ft
kA
A
N
4 AWG – 8 AWG
0.274
0.697
0.679
0.129
0.08
3.03
122
950
2 AWG – 6 AWG
0.172
0.436
0.679
0.122
0.09
4.80
159
1500
1 AWG – 5 AWG
0.137
0.349
0.679
0.117
0.09
6.06
184
1900
1/0 AWG – 4 AWG
0.109
0.274
0.679
0.113
0.10
7.65
211
2400
2/0 AWG – 3 AWG
0.0868
0.227
0.679
0.107
0.11
9.64
243
3000
3/0 AWG – 2 AWG
0.0688
0.172
0.679
0.106
0.11
12.15
279
3800
4/0 AWG – 1 AWG
0.0546
0.137
0.679
0.101
0.13
15.30
321
4800
250 MCM – 1/0 AWG
0.0466
0.109
0.436
0.094
0.16
18.16
355
5800
350 MCM – 2/0 AWG
0.0333
0.0868
0.436
0.090
0.18
25.31
435
7900
500 MCM – 4/0 AWG
0.0233
0.0546
0.436
0.086
0.21
36.18
536
11400
5.2
STANDARD PRINT LEGEND:
Paige Electric Hydroflex Submersible Pump Cable
8000Volts Shielded 90°C (Cul) E# MSHA P7359D
We’re Big in Big pump cable.
(1) Ampacity- Free air measured; Based on
continuous duty at 90˚C conductor temperature
(2) Short-circuit current (1s) – Based on
conductor temperature from 90˚C up to 250˚C
page 1