General Specifications - Yokogawa Electric Corporation

<<Contents>> <<Index>>
General
Specifications
I/O Adaptors (for N-IO)
GS 33J62F30-01EN
[Release 6]
GENERAL
This General Specifications (GS) describes the hardware specifications of I/O adaptors that enable extended
functions setting for analog digital I/O module (A2MMM843) and the digital I/O module (A2MDV843); such as I/O
signal conversion and isolation can be set by the channels. The adaptors are used by mounting to the base plate
for adaptor (A2BN3D).
STANDARD SPECIFICATIONS
For the installation environmental standards and combination of base plates, I/O modules, I/O adaptors, and I.S.
barriers for mounting of this product, refer to the GS “N-IO System Overview” (GS 33J62A10-01EN).
Type of I/O adaptor
Model
Name
Extended function
A2SAM105
Current input/voltage input adaptor
Current input, voltage input, and isolated channels
A2SAM505
Current output/voltage output adaptor
Current output, voltage output, and isolated channels
A2SAT105
mV/TC/RTD input adaptor
mV input, TC input, RTD input, and isolated channels
A2SAP105
Pulse input signal adaptor (0 to 10 kHz)
Contact ON/OFF, voltage pulse, current pulse, and
isolated channels
A2SDV105
Digital input adaptor
(24 V DC voltage input, dry contact input )
Voltage input, dry contact input, and isolation (*1)
A2SDV505
Digital output adaptor
(24 V DC, current source: 0.5A)
24 V DC/0.5 A output, current source, and isolation (*1)
A2SDV506
Relay output adaptor
(24 V DC, dry contact output: 0.5A)
24 V DC/0.5 A relay contact (dry contact NO/NC), and
isolated channels
A2SMX801
Pass-through I/O signal adaptor
Used to use the basic functions of I/O,
and non-isolated (*2)
A2SMX802
Pass-through I/O signal adaptor
(with field power output)
Used to use the basic functions of I/O,
and non-isolated (*2) (*3)
Note: For mounting I/O adaptors, refer to ”LIMITATIONS AND PRECAUTIONS FOR INSTALLATION” in the GS of “N-IO System
Overview” (GS 33J62A10-01EN).
Note: For signal connection to the base plate for adaptor (A2BN3D) using an I/O adaptor, refer to the TI “CENTUM VP installation
guidance” (TI 33J01J10-01EN).
*1:
*2:
*3:
Isolated from an I/O module, but not isolated among channels.
Non-isolated from an I/O module.
When the A2SMX802 is mounted, channels among A2SDV105, A2SDV505, and A2SMX801 are not isolated.
Yokogawa Electric Corporation
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802
GS 33J62F30-01EN
©Copyright Feb. 2015 (YK)
6th Edition Mar. 20, 2017 (YK)
2
<<Contents>> <<Index>>
Current input/voltage input adaptor
Item
Specifications
Model
A2SAM105
Input signal
Voltage input
Current input
Rated input range (maximum
guaranteed accuracy range)
0 to 10 V DC
4 to 20 mA DC
Input resistance
1 MΩ at power-on
100 kΩ or higher at power-off
320 Ω (20 mA) to 640 Ω (4 mA) at power-on
(*1)
100 kΩ or higher at power-off (*2)
Allowable input
voltage/current
0 to 30 V DC
0 to 40 mA DC
—
15.0 V DC min (20mA)
24.0 V DC max (0mA)
Accuracy
±4 mV (23°C ±2°C)
±8 mV (0°C to 60°C)
±12 mV (-40°C to 70°C)
±12 μA (23°C ±2°C)
±24 μA (0°C to 60°C)
±40 μA (-40°C to 70°C)
Data update period
For A2SAM105 alone : 2 ms (*3)
Maximum Current consumption
24 V DC system power supply: 42 mA
5 V DC internal power supply: 10 mA (*4)
Withstanding voltage
Between input signal and system: 1500 V AC for 1 minute, 42 V DC (*5)
Between I/O adaptors: 500 V AC for 1 minute, 42 V DC
Mounting
Mounted on the base plate for adaptor (A2BN3D)
Transmitter power supply
HART communication
function
Input signal setting
—
Input signals and input signal ranges are set by the software.
Setting of 2-wire or 4-wire
transmitter
Weight
HART7 is supported (*6)
—
Can be set
—
40 mA or lower (2-wire type)
0.10 kg or less
Current limitation
Note: A2MMM843 style 2 or later must be used in combination.
*1: *2: *3: *4: *5: *6: The module’s input resistance viewed from the terminals is as calculated as below:
240 Ω + (voltage drop in the input protection circuit / current value).
When A2SAM105 is powered off or overcurrent is detected, the current input loop becomes open.
The data update cycle is max.10 ms, when the A2SAM105 is used with this I/O module.
The internal power supply is a power supply which draws power from the I/O module.
For the withstanding voltage when connecting to a field power supply, refer to the GS “Base plates (for N-IO)” (GS
33J62F40-01EN).
Up to 5 HART communication field devices (e.g. transmitter) can be connected to A2SAM105 by multi-drop connection.
A2SAM105 can drive up to 24 mA including inrush current of field devices.
For details of HART communication, refer to the GS “I/O modules (for N-IO)” (GS 33J62F20-01EN).
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
3
<<Contents>> <<Index>>
Current output/voltage output adaptor
Item
Specifications
Model
A2SAM505
Output signal
Voltage output
Current output
Rated input range (maximum
guaranteed accuracy range)
0 to 10 V DC
4 to 20 mA DC
Output resistance
1 Ω or lower
Allowable load
resistance
10 kΩ or higher
0 to 750 Ω (20 mA), 0 to 600 Ω (23 mA)
Output range
-0.3 to 10.3 V DC
1 to 23 mA DC
—
Output voltage limit
—
25.5 V DC or lower
Output open detection
—
0.65 mA or lower
Accuracy
±12 mV (23°C ±2°C)
±24 mV (0°C to 60°C)
±36 mV (-40°C to 70°C)
Data update period
For A2SAM505 alone : 2 ms (*1)
Maximum Current consumption
24 V DC system power supply: 38 mA
5 V DC internal power supply: 10 mA (*2)
Withstanding voltage
Between output signal and system: 1500 V AC for 1 minute, 42 V DC (*3)
Between I/O adaptors: 500 V AC for 1 minute, 42 V DC
Mounting
Mounted on the Base Plate for Adaptor (A2BN3D)
HART communication
function
—
±48 μA (23°C ±2°C)
±64 μA (0°C to 60°C)
±80 μA (-40°C to 70°C)
HART7 is supported(*4)
Output signal setting
Output signals and output signal ranges are set by the software.
Weight
0.10 kg or less
Current limitation
15 mA or lower
23 mA or lower
Note: A2MMM843 style 2 or later must be used in combination.
*1: *2: *3: *4: The data update period is max. 10 ms, when the A2SAM505 is used with this I/O module.
The internal power supply is a power supply which draws power from the I/O module.
For the withstanding voltage when connecting to a field power supply, refer to the GS “Base plates (for N-IO)” (GS
33J62F40-01EN).
For details of HART communication, refer to the GS “I/O modules (for N-IO)” (GS 33J62F20-01EN).
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
4
<<Contents>> <<Index>>
mV/thermocouple/RTD input adaptor
Item
Specifications
Model
A2SAT105
Input signal
mV
Thermocouple (*1)
· JIS C 1602, IEC
60584-1 (ITS-90) Type J,
K, E, B, R, S, T, N(*2)
RTD (3-wire type) (*3)
· JIS C 1604, IEC 60751
(ITS-90) Pt100, Pt200,
Pt500 (*4)
· DIN 43760-1987 :
Ni100
· Minco : Ni120
3-wire potentiometer
-50 to 150 mV
400 Ω range : 0 to 400 Ω
2000 Ω range: 0 to
2000 Ω
Total resistance:
· 100 to 2000 Ω
Span resistance:
· 50% or higher of the
total resistance (*5)
Input range
-50 to 150 mV
Allowable input voltage
-0.5 to 4.0 V DC (between terminals A and B)
Input resistance
1 MΩ (at power-on), 10 kΩ (at power-off)
Accuracy rating
±20 uV
Data update period
For A2SAT105 alone : 124 ms (*6)
Signal source resistance
1000 Ω or lower
RJC accuracy
±20 uV
—
Measuring current
—
—
400 Ω range : ±0.08 Ω
2000 Ω range : ±0.40 Ω
150 Ω or lower (wiring resistance per wire)
±1.0 °C (*7) (*8)
—
—
400 Ω range : 1.0 mA
2000 Ω range : 0.2 mA
Burnout detection
Select from UP, DOWN, or OFF
Burnout detection time
60 s or lower
Burnout detection
current
0.1 μA
Withstanding voltage
Between input signal and system: 1500 V AC for 1 minute, 42 V DC (*9)
Between I/O adaptors: 500 V AC for 1 minute, 42 V DC
Mounting
Mounted on the Base Plate for Adaptor (A2BN3D)
Maximum Current
consumption
24 V DC system power supply: 12 mA
5 V DC internal power supply: 10 mA (*10)
Input linearization
None
Available
Available
Influence of signal
source
resistance/wiring
resistance
(burnout is OFF)
For 1 kΩ signal source resistance:
Input conversion ±20 μV or lower
Influence by Drift
due to ambient
temperature change
For 10 °C change: ±20 μV
For 10 °C change:
400 Ω range : ±0.16 Ω
2000 Ω range : ±0.8 Ω
Input signal setting
Input signals and input signal ranges are set by the software setting.
Weight
0.10 kg or less
—
—
None
For wiring resistance 10
Ω of terminals A and C:
Input conversion ±40
mΩ or lower (wiring
of terminals A and C
must have the same
resistance)
Current limitation
±0.2 %
—
For 10 °C change:
±0.4% of span
1.5 mA or lower
Note: A2MMM843 style 2 or later and A2BN3D style 2 or later must be used in combination.
Note: Do not use a multi-core cable in common with a digital-input/output signal. The accuracy of A2SAT105 is interfered by
capacitive coupling.
*1: *2: *3: *4: *5: *6:
For using a thermocouple input, A2SAT105 must be mounted on the A2BN3D-1.
Type B does not perform reference junction compensation.
400 Ω range is applicable for input range of Pt100, Ni100, or Ni120. 2000 Ω range is applicable for input range of Pt200 or
Pt500.
A2SAT105 also supports JIS C 1604: 1989 JPt100.
The permissible input range is defined as 0 to 30 kΩ; however, using the A2SAT105 within the input range is suggested for
maintaining the accuracy rating.
The data update cycle is max. 132 ms, when the A2SAT105 is used with the I/O module.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
5
<<Contents>> <<Index>>
*7: When the measuring temperature is under 0 ºC, multiply the following coefficient (K) with the above value.
K=
*8: (Thermo-electromotive force per degree at 0 °C)
(Thermo-electromotive force per degree at measured temperature)
The reference junction compensation accuracy varies depending on the ambient temperature.
Temperature environment
Reference junction compensation accuracy
-40 to 0 °C
±1.5 °C
0 to 50 °C
±1.0 °C
50 to 70 °C
±1.5 °C
When A2SAM105, A2SAM505, A2SAP105, A2SDV505, A2SDV506, A2SMX802 are mounted on the adjacent channels, or
a heating device is placed directly under the base plate for adaptor without heat shield, the reference junction compensation
accuracy is ±1.5 °C. The reference junction temperature sensor is mounted on the base plate for adaptor (A2BN3D).
*9: For the withstanding voltage when connecting a field power supply, refer to the GS “Base plates (for N-IO)” (GS
33J62F40-01EN).
*10: The internal power supply is a power supply which draws power from the I/O module.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
6
<<Contents>> <<Index>>
 Pulse input signal adaptor (for 0 to 10 kHz)
Item
Specifications
Model
A2SAP105
Input signal
2-wire type: Contact ON/OFF, voltage pulse, current pulse
(possible to supply transmitter power supply)
3-wire type: Power-supply-type voltage pulse
Input frequency
0 to 10 kHz (*1)
Minimum input pulse width
40 μs or higher
Input signal level
Contact input
Relay contact, transistor contact
Open/close detection level Open: 100 kΩ or higher
Close: 200 Ω or lower
Contact capacity: 15 V DC/15 mA or higher (when supplying 12 V DC)
30 V DC/30 mA or higher (when supplying 24 V DC)
Voltage/current pulse input (Current input is converted to voltage)
VH (high level): 3 to 24 V DC
VL (low level):
-1 to 8 V DC
VH - VL (Swing width):
3V or higher
Signal source resistance 1 kΩ or lower
Shunt resistance
Can be Selected from ON (4 kΩ) or OFF (*2)
Filter
Filter for eliminating chattering can be set (*3)
Pull-up resistance
68 kΩ (12 V DC or 24 V DC)
Transmitter power supply
Can be selected from 24 V DC or 12 V DC
12 V DC ± 1.2 V DC/35 mA or lower
24 V DC ± 2.4 V DC/24 mA or lower
(Output current limitation: 40 mA DC or lower) (*4)
Maximum current consumption
24 V DC system power supply: 50 mA
5 V DC internal power supply: 10 mA (*5)
Withstanding voltage
Between input signal and system: 1500 V AC for 1 minute, 42 V DC (*6)
Between I/O adaptors: 500 V AC for 1 minute, 42 V DC
Mounting procedure
Mounted on the base plate for adaptor (A2BN3D)
Weight
0.10 kg or less
Data update period
For A2SAP105 alone: 2 ms (*7)
Current limitation
40 mA or lower
*1: Connection for the following frequencies in the case of receiving dry contact signal.
0 to 5 kHz : Connect the input signal between A and B terminals.
0 to 10 kHz :Connect the input signal between A and B terminals then connect an external shunt resistor between C and
D terminals.
0 to 800 Hz:Connect the input signal between B and C terminals.
*2: Recommended resistance values of external shunt resistors are as follows:
Resistance
1W
510 Ω ±5%
1W
When 1 kΩ shunt resistor is required, use 2 pieces of 510 Ω, 1 W resistors to connect in series.
A terminal block for the external resistor has to be mounted. The table below shows recommended terminal blocks.
Handle an external shunt resistor with care as it may become high in temperature. Use a cover to prevent from touching
the resistor directly to avoid being burned.
For details on mounting, refer to the TI “CENTUM VP installation guidance” (TI 33J01J10-01EN).
Manufacturer
Phoenix Contact
*3:
*4:
*5:
*6:
*7:
Rated power
220 Ω ±5%
Model
PT 2, 5-TG-3210185, D-PT 2, 5-MT-3211003, P-CO-3036796
(Up to 1 W resistor can be mounted)
Use A2SAP105-S1 (with explosion protection) only in an application where an external resistor is not required because
the A2SAP105-S1 cannot take an external resistor due to the regulation of the standards for hazardous location
equipment.
Chattering can be eliminated when the pulse input signal is a dry contact (e. g. mechanical relay) up to 10 Hz.
When A2SAP105 is powered off or overcurrent is detected, the current input loop becomes open.
The internal power supply is a power supply which draws power from the I/O module.
For the withstanding voltage when connecting to a field power supply, refer to the GS “Base Plates (for N-IO)” (GS
33J62F40-01EN).
The sum of the data update cycle of I/O modules becomes max.10 ms of delay.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
7
<<Contents>> <<Index>>
Digital input adaptor (24 V DC voltage input, dry contact input)
Item
Specifications
Model
A2SDV105
Input format
Voltage input and dry contact input
Rated input voltage
24 V DC (voltage input)
Input current (at rated input voltage)
6 mA ±1.2 mA
Input ON voltage
18 to 26.4 V DC (voltage input)
Input OFF voltage
5.0 V DC or lower (voltage input)
Field voltage rating
24 V DC ±2.4 V DC (contact input), current capacity: 10 mA or higher (*1)
Input ON resistance
1 kΩ or lower (contact input)
Input OFF resistance
50 kΩ or higher (contact input)
Maximum allowable input voltage
30.0 V DC
Withstanding voltage
Between input signal and system: 1500 V AC for 1 minute, 42 V DC (*2)
Between I/O adaptors: 500 V AC for 1 minute, 42 V DC (*3) (*4)
Maximum current consumption
24 V DC system power supply: Unused
5 V DC internal power supply: 14 mA (*5)
Input response time
For A2DV105 alone: 150 μs
In combination with the I/O module: Up to 22 ms
Mounting procedure
Mounted on the base plate for adaptor (A2BN3D)
Weight
0.10 kg or less
Current limitation
20 mA or lower (contact input)
*1:
*2:
*3:
*4:
*5:
Current capacity in normal operation per A2SDV105. The current capacity is 20 mA when the circuit is grounded.
For the withstanding voltage when connecting a field power supply, refer to the GS “Base Plates (for N-IO)” (GS
33J62F40-01EN).
Channels among A2SDV105, A2SDV505, and A2SMX802 are not isolated.
The following shows the permissible potential difference in common mode.
Between dry contact inputs: Not isolated
Between voltage inputs: 30 V for 1 minute
Between voltage input and dry contact input: 30 V for 1 minute
The internal power supply is a power supply which draws power from the I/O module.
 Digital output adaptor (24 V DC, current source: 0.5 A)
Item
Specifications
Model
A2SDV505
Output format
Current source
Field power supply rating
24 V DC ±2.4 V DC, current capacity: 0.55 A or higher (*1)
Voltage drop
1 V or lower (*2)
Leak current maximum value when
output off
1 mA or lower
Maximum load current
500 mA (including rush current) (*3)
Load resistance range
48 Ω or higher
Maximum current consumption
24 V DC system power supply: Unused
5 V DC internal power supply: 18 mA (*4)
Withstanding voltage
Between output signal and system: 1500 V AC for 1 minute, 42 V DC (*5)
Between I/O adaptors: 500 V AC for 1 minute, 42 V DC (*6)
Mounting procedure
Mounted on the base plate for adaptor (A2BN3D)
Output response time
For A2SDV505 alone: 5 ms
In combination with the I/O module: Up to 17 ms
Weight
0.10 kg or less
Current limitation
0.8 A or lower
*1:
*2:
*3:
*4:
*5:
*6:
Current capacity in normal operation per A2SDV505. The current capacity is 0.8 A when the circuit is shorted.
Voltage drop includes that from the field power supply input terminal to the field connection terminal via the module.
When driving an inductive load, a spark killer diode must be connected.
The internal power supply is a power supply which draws power from the I/O module.
For the withstanding voltage when connecting a field power supply, refer to the GS “Base Plates (for N-IO)” (GS
33J62F40-01EN).
Channels among A2SDV105, A2SDV505, and A2SMX802 are not isolated.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
8
<<Contents>> <<Index>>
 Relay output adaptor (24 V DC, dry contact output: 0.5A)
Item
Specifications
Model
A2SDV506
Rated applied voltage
24 V DC
Maximum load
Resistance load: 24 V DC/0.5 A, 30 V DC/0.5 A
Inductive load: 24 V DC/0.5 A, 30 V DC/0.4 A (*1)
Maximum voltage
Resistance load: 30 V DC, inductive load: 30 V DC
Maximum current
Resistance load: 0.5 A DC (including rush current),
Inductive load: 0.5 A DC (including rush current)
Output format
NC/NO
Withstanding voltage
Between output signal and system: 1500 V AC for 1 minute, 42 V DC (*2)
Between I/O adaptors: 500 V AC for 1 minute, 42 V DC
Relay switching life
Resistance load: 100,000 open/close cycles (at maximum load)
Inductive load: 100,000 open/close cycles (at maximum load)
Mounting procedure
Mounted on the base plate for adaptor (A2BN3D)
Weight
0.10 kg or less
Relay operating time
For A2SDV506 alone: 8 ms or lower (bouncing is not included)
In combination with the I/O module: Up to 20 ms
Relay recovery time
For A2SDV506 alone: 20 ms or lower (bouncing is not included)
In combination with the I/O module: Up to 32 ms
Maximum current consumption
24 V DC system power supply: Unused
5 V DC internal power supply: 8 mA (*3)
Note: Replacement is not recommended while current flows through the terminals, because the connectors of the base plate and
the module may be damaged or deteriorate. Turn off the field signal externally before replacing this module.
Note: The operating temperature range is -40 to 70°C. When mounted on the same base plate with A2SAP105, A2SAM105 or
A2SAM505 the operating temperature range is -40 to 60°C.
*1:
*2:
*3:
When driving an inductive load, a spark killer diode must be connected.
For the withstanding voltage when connecting a field power supply, refer to the GS “Base plates (for N-IO)” (GS
33J62F40-01EN).
The internal power supply is a power supply which draws power from the I/O module.
 Pass-through I/O signal adaptor
Item
Model
I/O signal
Specifications
A2SMX801-S0
A2SMX801-S1
Signals from a field device are output to I/O module as is.
Signals from I/O module are output to the field device as is.
Protection
—
With protection(*1)
Input/output resistance
—
7 Ω max
Maximum Current consumption
No current is consumed
Mounting procedure
Mounted on the base plate for adaptor (A2BN3D)
Weight
0.10 kg or less
*1:
By using the adaptor in combination with the base plate with a protection function, the influence of the excess voltage status
caused by wrong wiring or such can be minimized to the adaptor itself and prevent other channels from failing. For more
details, refer to “N-IO system overview” (GS 33J62A10-01EN).
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
9
<<Contents>> <<Index>>
 Pass-through I/O signal adaptor (with field power output)
Item
Specifications
Model
A2SMX802 (*1)
I/O signal
Signals from a field device are output to I/O module as is.
Signals from I/O module are output to the field device as is.(*2)
Protection
With protection (*3)
Input / output resistance
7 Ω max
Field power supply rating
24 V DC ±2.4 V DC, current capacity: 0.55 A or higher (*4)
Voltage drop
1 V or lower (*5) (*6)
Maximum load current
500 mA (Maximum inrush current 1 A) (*7)
Maximum Current consumption
No current is consumed
Mounting procedure
Mounted on the base plate for adaptor (A2BN3D)
Weight
0.10 kg or less
Current limitation
*1:
*2:
*3:
*4:
*5:
*6:
*7:
1.6A or lower
When the A2SMX802 is mounted, channels among A2SDV105, A2SDV505, and A2SMX801 are not isolated.
When driving an inductive load, a spark killer diode must be connected.
By using the adaptor in combination with the base plate with a protection function, the influence of the excess voltage status
caused by wrong wiring or such can be minimized to the adaptor itself and prevent other channels from failing. For more
details, refer to “N-IO system overview” (GS 33J62A10-01EN).
Current capacity in normal operation per A2SMX802. The current capacity is 1.6 A when the circuit between C and B
terminal or between C and D terminal is shorted.
Voltage drop includes that from the field power supply input terminal to the field connection terminal via the module.
When the A2SDV505 digital output adaptor is mounted on the same base plate, the field power supply output may include
maximum 0.6 V of ripple.
When using the digital output function in the style of current sink output, refer to the specification of I/O module (GS
33J62F20-01EN) for I/O signal specifications current.
 Filed digital output voltage when field power supply is in use
The table below shows the output terminal voltage of the base plate (A2BN3D) of which digital output function is
operated by using field power supply.
Table Digital output terminal voltage when field power is in use
A2SDV505-
Model name
A2SMX801-0 (*1)
A2SMX801-1 (*1)
A2SMX802- (*1)
Min. [V]
(*2)
Max. [V]
Min. [V]
(*3)
Max. [V]
Min. [V]
(*3)
Max. [V]
Min. [V]
(*3)
Max. [V]
Field power supply
terminal input voltage
(24V-10 % )
20.6
21.6
19.6
21.6
18.9
21.6
17.9
21.6
Field power supply
terminal input voltage
(24V±0 % )
23.0
24.0
22.0
24.0
21.3
24.0
20.3
24.0
Field power supply
terminal input voltage
(24V+10 % )
25.4
26.4
24.4
26.4
23.7
26.4
22.7
26.4
*1:
*2:
*3:
In case the I/O module outputs signals in the form of the current sink output of the digital output function.
Maximum load current 500 mA
Maximum load current 100 mA
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
10
<<Contents>> <<Index>>
EXTERNAL DIMENSIONS
Unit:mm
130
40
12.8
F01.ai
Nominal tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal
tolerance is ± 1.5 mm.
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.
MODELS AND SUFFIX CODES
Current input/voltage input adaptor
Description
Model
Suffix
Codes
A2SAM105
Current input/voltage input adaptor
-H
With digital communication (HART protocol)
0
With no explosion protection
0
Basic type
1
With ISA standard G3 option
2
With temperature (-40 to 70 °C) option
3
With ISA standard G3 option and temperature (-40 to 70 °C) option
0
Always 0
Current output/voltage output adaptor
Description
Model
Suffix
Codes
A2SAM105
Current output/voltage output adaptor
-H
With digital communication (HART protocol)
0
With no explosion protection
0
Basic type
1
With ISA standard G3 option
2
With temperature (-40 to 70 °C) option
3
With ISA standard G3 option and temperature (-40 to 70 °C) option
0
Always 0
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
11
<<Contents>> <<Index>>
mV/TC/RTD input adaptor
Description
Model
Suffix
Codes
A2SAT105
mV/TC/RTD input adaptor
-S
Standard type
0
With no explosion protection
0
Basic type
1
With ISA standard G3 option
2
With temperature (-40 to 70 °C) option
3
With ISA standard G3 option and temperature (-40 to 70 °C) option
0
Always 0
Pulse input signal adaptor
Description
Model
Suffix
Codes
A2SAP105
Pulse input signal adaptor (0 to 10 kHz)
-S
Standard type
0
With no explosion protection
1
With explosion protection
0
Basic type
1
With ISA standard G3 option
2
With temperature (-40 to 70 °C) option
3
With ISA standard G3 option and temperature (-40 to 70 °C) option
0
Always 0
Digital input adaptor
Description
Model
Suffix
Codes
A2SDV105
Digital input adaptor (24 V DC voltage input, dry contact input)
-S
Standard type
0
With no explosion protection
1
With explosion protection
0
Basic type
1
With ISA standard G3 option
2
With temperature (-40 to 70 °C) option
3
With ISA standard G3 option and temperature (-40 to 70 °C) option
0
Always 0
Digital output adaptor
Description
Model
Suffix
Codes
A2SDV505
Digital output adaptor (24 V DC, current source: 0.5 A)
-S
Standard type
0
With no explosion protection
1
With explosion protection
0
Basic type
1
With ISA standard G3 option
2
With temperature (-40 to 70 °C) option
3
With ISA standard G3 option and temperature (-40 to 70 °C) option
0
Always 0
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
GS 33J62F30-01EN Mar. 20, 2017-00
12
<<Contents>> <<Index>>
Relay output adaptor
Description
Model
Suffix
Codes
A2SDV506
Relay output adaptor (24 V DC, dry contact output: 0.5 A)
-S
Standard type
0
With no explosion protection
1
With explosion protection
0
Basic type
1
With ISA standard G3 option
2
With temperature (-40 to 70 °C) option
3
With ISA standard G3 option and temperature (-40 to 70 °C) option
0
Always 0
Pass-through I/O signal adaptor
Description
Model
Suffix
Codes
A2SMX801
Pass-through I/O signal adaptor
-S
Standard type
0
With no explosion protection
1
With explosion protection
0
Basic type
1
With ISA standard G3 option
2
With temperature (-40 to 70 °C) option
3
With ISA standard G3 option and temperature (-40 to 70 °C) option
0
With no protection
1
With protection
Description
Model
Suffix
Codes
A2SMX802
Pass-through I/O signal adaptor (With field power output)
-S
Standard type
0
With no explosion protection
0
Basic type
1
With ISA standard G3 option
2
With temperature (-40 to 70 °C) option
3
With ISA standard G3 option and temperature (-40 to 70 °C) option
0
Always 0
APPLICABLE STANDARDS
Refer to the GS “Integrated production control system CENTUM VP system overview” (GS 33J01A10-01EN).
ORDERING INFORMATION
Specify models and suffix codes when ordering.
For selecting the right products for explosion protection, please refer to TI 33Q01J30-01E without fail.
TRADEMARKS
•CENTUM is a registered trademark of Yokogawa Electric Corporation.
•Other company and product names appearing in this document are trademarks or registered trademarks of their
respective holders.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation
Subject to change without notice.
GS 33J62F30-01EN Mar. 20, 2017-00